Lenze SMD 0-37kW-22kW User Manual

SMD
Frequency Inverter: Full I/O with CANopen 0.37 kw... 22kW
Operating Instructions
(13466183)
Copyright © 2013 - 2005 Lenze AC Tech Corporation
All rights reserved. No part of this manual may be reproduced or transmitted in any form without written permission from Lenze AC Tech Corporation. The information and technical data in this manual are subject to change without notice. Lenze AC Tech Corporation makes no warranty of any kind with respect to this
material, including, but not limited to, the implied warranties of it’s merchantability and tness for a given
purpose. Lenze AC Tech Corporation assumes no responsibility for any errors that may appear in this manual.
All information given in this documentation has been carefully selected and tested for compliance with the hardware and software described. Nevertheless, discrepancies cannot be ruled out. We do not accept any responsibility nor liability for damages that may occur. Any necessary corrections will be implemented in subsequent editions.
This document printed in the United States
Contents
1 Safety Information ..............................................................................5
1.1 Pictographs used in these Instructions.......................................6
2 Technical Data ....................................................................................8
2.1 Standards and Application Conditions........................................8
2.2 Ratings .......................................................................................9
3 Installation ........................................................................................10
3.1 Mechanical Installation .............................................................10
3.1.1 Dimensions and Mounting ................................................10
3.2 Electrical Installation................................................................. 11
3.2.1 Installation according to EMC Requirements ................... 11
3.2.2 Fuses/Cable Cross-Sections ............................................ 11
3.2.3 Connection Diagram ........................................................12
3.2.4 Control Terminals .............................................................13
4 Commissioning .................................................................................14
4.1 Parameter Setting ....................................................................14
4.2 Electronic Programming Module (EPM) ...................................14
4.3 Parameter Menu.......................................................................15
4.4 CANopen Mapping Details .......................................................26
4.4.1 RPDO Mapping (h66 / h76) ..............................................26
4.4.2 TPDO Mapping (h86 / h96) ..............................................29
4.5 Quick CAN Set-up ....................................................................33
5 Troubleshooting and Fault Elimination .............................................34
Lenze 13466183 EDBSC03 v7 3
About These Instructions
A
B
C
D
E
F
This documentation applies to the smd frequency inverter, and contains important technical data and describes installation, operation, and commissioning.
Please read the instructions before commissioning.
Type: ESMD223C4TXA Id-No: 13xxxxxx
LISTED
IND. CONT. EQ.
5D81
C
Input Ratings
D
Output Ratings
After receipt of the delivery, check immediately whether the items delivered match the accompanying papers. Lenze does not accept any liability for
deciencies claimed subsequently.
Claim
visible transport damage immediately to the forwarder.
• visible deciencies/incompleteness immediately to your Lenze
Made in USA
Inverter
smd
CANopen: Full I/O
A
Certications
B
Type
Scope of delivery Important
1 smd inverter (ESMD...)
with EPM installed (see Section 4.2)
1 Operating Instructions
Input: 3/PE
400/480 V 52/45 A 50-60 Hz
N10104
Z519
representative.
Output: 3/PE
0-400 / 460 V 46/40 A 22 kW 0 - 240 Hz
1341308801234567
For detailed information
refer to instruction
SN: 13xxxxxx012345678 ESMD223C4TXA000XX XX XX
E
Hardware Version
F
Software Version
Manual SC03
+
C0001
4 Lenze 13466183 EDBSC03 v7
Safety information
1 Safety Information
General
Some parts of Lenze controllers (frequency inverters, servo inverters, DC controllers) can be live, moving and rotating. Some surfaces can be hot. Non-authorized removal of the required cover, inappropriate use, and incorrect installation or operation creates the risk of severe injury to personnel or damage to equipment. All operations concerning transport, installation, and commissioning as well as maintenance must be
carried out by qualied, skilled personnel (IEC 364 and CENELEC HD 384 or DIN VDE 0100 and IEC
report 664 or DIN VDE0110 and national regulations for the prevention of accidents must be observed).
According to this basic safety information, qualied skilled personnel are persons who are familiar with the installation, assembly, commissioning, and operation of the product and who have the qualications
necessary for their occupation.
Application as directed
Drive controllers are components which are designed for installation in electrical systems or machinery. They are not to be used as appliances. They are intended exclusively for professional and commercial purposes according to EN 61000-3-2. The documentation includes information on compliance with the EN 61000-3-2. When installing the drive controllers in machines, commissioning (i.e. the starting of operation as directed) is prohibited until it is proven that the machine complies with the regulations of the EC Directive 2006/42/EC (Machinery Directive); EN 60204 must be observed. Commissioning (i.e. starting of operation as directed) is only allowed when there is compliance with the EMC Directive (2004/108/EC). The drive controllers meet the requirements of the Low Voltage Directive 2006/95/EC. The harmonised standards of the series EN 50178/DIN VDE 0160 apply to the controllers. Note: The availability of controllers is restricted according to EN 61800-3.These products can cause radio interference in residential areas. In this case, special measures can be necessary.
Installation
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and do not change any insulation distances during transport or handling. Do not touch any electronic components and contacts. Controllers contain electrostatically sensitive components, which can easily be damaged by inappropriate handling. Do not damage or destroy any electrical components since this might endanger your health!
Electrical Connection
When working on live drive controllers, applicable national regulations for the prevention of accidents (e.g. VBG 4) must be observed. The electrical installation must be carried out according to the appropriate regulations (e.g. cable cross­sections, fuses, PE connection). Additional information can be obtained from the documentation. The documentation contains information about installation in compliance with EMC (shielding,
grounding, lters and cables). These notes must also be observed for CE-marked controllers.
The manufacturer of the system or machine is responsible for compliance with the required limit values demanded by EMC legislation.
Lenze 13466183 EDBSC03 v7 5
Safety information
Operation
Systems including controllers must be equipped with additional monitoring and protection devices according to the corresponding standards (e.g. technical equipment, regulations for prevention of accidents, etc.). You are allowed to adapt the controller to your application as described in the documentation.
DANGER!
After the controller has been disconnected from the supply voltage, live components and power connection must not be touched immediately, since capacitors could be charged. Please observe the corresponding notes on the controller.
Do not continuously cycle input power to the controller more than once every three minutes.
Please close all protective covers and doors during operation.
1.1 Pictographs used in these Instructions
Pictograph Signal Word Meaning Consequences if ignored
DANGER!
WARNING!
Warning of Hazardous Electrical
Impending or possible danger for
Voltage.
persons
Reference to an imminent danger that may result in death or serious
personal injury if the corresponding
measures are not taken.
Death or injury
STOP!
NOTE
Possible damage to equipment Damage to drive system or its
Useful tip: If observed, it will make
using the drive easier
surroundings
6 Lenze 13466183 EDBSC03 v7
Safety Information
Note for UL approved system with integrated controllers
UL warnings are notes which apply to UL systems. The documentation contains special information about UL.
• Integral solid state protection does not provide branch circuit protection. Branch
circuit protection must be provided in accordance with the National Electrical Code and any additional local codes. The use of fuses or circuit breakers is the
Warnings!
only approved means for branch circuit protection.
• When protected by CC and T Class Fuses, suitable for use on a circuit capable of
delivering not more than 200,000 rms symmetrical amperes, at the maximum voltage rating marked on the drive.
• Additionally suitable when protected by a circuit breaker having an interrupting
rating not less than 200,000 rms symmetrical amperes, at the maximum voltage rating marked on the drive. (Excludes ESMD113_4T_, ESMD112_2Y_, ESMD113_2T_, ESMD152_2Y_, ESMD153_2T_, ESMD222_2Y_, ESMD223_4T_, ESMD402_2T_, ESMD552_2T_, ESMD752_2T_, ESMD153_4T_, and ESMD183_4T_).
• Use minimum 75°C copper wire only, except for control circuits.
• For control circuits, use wiring suitable for NEC Class 1 circuits only.
• Torque Requirements are listed in section 3.2.3, Connection diagram.
• Shall be installed in a pollution degree 2 macro-environment.
DANGER!
Risk of Electric Shock! Capacitors retain charge for approximately 180 seconds after power is removed. Disconnect incoming power and wait at least 3 minutes before touching the drive.
DANGER!
Risque de choc électrique! Les condensateurs restent sous charge pendant environ 180 secondes après une coupure de courant. Couper l’alimentation et patienter pendant au moins 3 minutes avant de toucher l’entraînement.
WARNING!
The opening of branch-circuit protective device may be an indication that a fault
has been interrupted. To reduce the risk of re or electric shock, current carrying
parts and other components of the controller should be examined and replaced if damaged.
AVERTISSEMENT!
Le déclenchement du dispositif de protection du circuit de dérivation peut être dû à une coupure qui résulte d’un courant de défaut. Pour limiter le risque d’incendie ou de choc électrique, examiner les pièces porteuses de courant et les autres éléments du contrôleur et les remplacer s’ils sont endommagés
Lenze 13466183 EDBSC03 v7 7
Technical data
2 Technical Data
2.1 Standards and Application Conditions
Conformity
Approvals
Max. permissible motor cable
(1)
length
Input voltage phase imbalance
Humidity
Output frequency
Environmental conditions
Temperature range
Installation height
Vibration resistance
Earth leakage current
Enclosure (EN 60529)
Protection measures against
Operation in public supply networks (Limitation of harmonic currents according to EN 61000-3-2)
(1) For compliance with EMC regulations, the permissible cable lengths may change.
(2) The additional measures described only ensure that the controllers meet the requirements of the EN 61000-3-2. The machine/system manufacturer is responsible for the compliance with the regulations of the machine!
CE Low Voltage Directive (2006/95/EC)
UL 508C Underwriters Laboratories - Power Conversion Equipment
shielded: 50 m (low-capacitance)
unshielded: 100 m
< 2%
< 95% non-condensing
0...240 Hz
Class 3K3 to EN 50178
Transport -25 … +70 °C
Storage -20 … +70 °C
Operation 0 … +55 °C (with 2.5 %/°C current derating above +40 °C)
0 … 4000 m a.m.s.l. (with 5 %/1000 m current derating above 1000 m a.m.s.l.)
acceleration resistant up to 0.7 g
> 3.5 mA to PE
IP 20
short circuit, earth fault, overvoltage, motor stalling, motor overload
Total power
connected to
the mains
< 0.5 kW With mains choke
0.5 … 1 kW With active lter (in preparation)
> 1 kW Without additional measures
Compliance with the requirements
(2)
8 Lenze 13466183 EDBSC03 v7
2.2 Ratings
Type
ESMD371C2YXA
ESMD751C2YXA
ESMD112C2YXA
ESMD152C2YXA
ESMD222C2YXA
ESMD302C2TXA
ESMD402C2TXA
ESMD552C2TXA
ESMD752C2TXA
ESMD113C2TXA
ESMD153C2TXA
ESMD371C4TXA
ESMD751C4TXA
ESMD112C4TXA
ESMD152C4TXA
ESMD222C4TXA
ESMD302C4TXA
ESMD402C4TXA
ESMD552C4TXA
ESMD752C4TXA
ESMD113C4TXA
ESMD153C4TXA
ESMD183C4TXA
ESMD223C4TXA
Power
[kW]
0.37
0.75 8.4 4.8 4.0 3.7 6.0 5.6
1.1 12.0 6.9 6.0 5.5 9.0 8.3
1.5 12.9 7.9 6.8 6.3 10.2 9.5
2.2 17.1 10.8 9.6 8.8 14.4 13.2
3.0
4.0 17.1 15.2 14.0 23 21
5.5 25 22 20 33 30
7.5 32 28 26 42 39
11 48 42 39 63 58
15 59 54 50 81 75
0.37
0.75 3.0 2.5 2.5 2.1 2.3 1.9 3.8 3.2 3.5 2.9
1.1 4.3 3.6 3.6 3.0 3.3 2.8 5.4 4.5 5.0 4.2
1.5 4.8 4.0 4.1 3.4 3.8 3.1 6.2 5.1 5.7 4.7
2.2 6.4 5.4 5.8 4.8 5.3 4.4 8.7 7.2 8.0 6.6
3.0 8.3 7.0 7.6 6.3 7.0 5.8 11.4 9.5 10.5 8.7
4.0 10.6 8.8 9.4 7.8 8.6 7.2 14.1 11.7 12.9 10.8
5.5 14.2 12.4 12.6 11.0 11.6 10.1 18.9 16.5 17.4 15.2
7.5 18.1 15.8 16.1 14.0 14.8 12.9 24 21 22 19.4
11 27 24 24 21 22 19.3 36 32 34 29
15 35 31 31 27 29 25 47 41 43 37
18.5 44 38 39 34 36 31 59 51 54 47
22 52 45 46 40 42 37 69 60 64 55
Mains Output Current
Voltage, frequency
1/N/PE 230 V OR
3/PE 230 V
(180 V -0%…264 V +0%)
50/60 Hz
(48 Hz -0%…62 Hz +0%)
3/PE 230 V
(180 V -0%…264 V +0%)
50/60 Hz
(48 Hz -0%…62 Hz +0%)
3/PE 400/480 V
(320 V -0%…528 V +0%)
50/60 Hz
(48 Hz -0%…62 Hz +0%)
Technical data
(3)
Current
(3)
[A]
[A]
I
N
(1)
[A]
(2)
1~ 3~ 3~ 3~ 3~ 3~
4.7 2.7 2.2 2.0 3.3 3.0
13.5 12.0 11.0 18.0 16.5
400V 480V 400V 480V 400V 480V 400V 480V 400V 480V
1.6 1.4 1.3 1.1 1.2 1.0 2.0 1.7 1.8 1.5
[A]
I
max
(1)
for 60 s
[A]
(2)
(1) For rated mains voltage and carrier frequencies 4, 6, and 8 kHz (2) For rated mains voltage and carrier frequency 10 kHz (3) Maximum current is a function of setting C90 (input voltage selection)
Lenze 13466183 EDBSC03 v7 9
Installation
3 Installation
3.1 Mechanical Installation
3.1.1 Dimensions and Mounting
A
B
C
D
4 x M4
1.2 Nm 10 lb-in
4 x M6
2.8 Nm 24 lb-in
b2
b
b1
s2s2
s1 s1
a1
a
Type
ESMD371C2YXA, ESMD371C4TXA 93 84 146 128 17 100 15 50 0.6
ESMD751C2YXA, ESMD751C4TXA 93 84 146 128 17 120 15 50 0.9
ESMD112C4TXA 93 84 146 128 17 146 15 50 1.0
ESMD112C2YXA 114 105 146 128 17 133 15 50 1.4
ESMD152C4TXA 11 4 105 146 128 17 122 15 50 1.4
ESMD222C4TXA 11 4 105 146 128 17 139 15 50 1.4
ESMD152C2YXA, ESMD222C2YXA ESMD302C2TXA ESMD302C4TXA
ESMD402C2TXA ESMD402C4TXA, ESMD552C4TXA
ESMD552C2TXA, ESMD752C2TXA ESMD752C4TXA, ESMD113C4TXA
ESMD113C2TXA, ESMD153C2TXA ESMD153C4TXA... ESMD223C4TXA
a
[mm]
114 105 146 128 17 171 15 50 2.0
114 105 146 100 17 171 15 50 2.0
146 137 197 140 17 182 30 100 3.2
195 183 248 183 23 203 30 100 6.4
c
a1
[mm]b [mm]b1 [mm]b2 [mm]c [mm]
smd402
s1
[mm]s2 [mm]m [kg]
WARNING!
Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive vibration or excessive temperatures. Contact Lenze for more information.
10 Lenze 13466183 EDBSC03 v7
Installation
3.2 Electrical Installation
3.2.1 Installation according to EMC Requirements
EMC
Compliance with EN 61800-3/A11
Noise emission Compliance with limit value class A according to EN 55011 if installed in a control cabinet with the appropriate footprint lter and the motor cable length does not exceed 10m
Screen clamps
A
Control cable
B
Low-capacitance motor cable
C
(core/core < 75 pF/m, core/screen < 150 pF/m)
Electrically conductive mounting plate
D
Filter
E
3.2.2 Fuses/Cable Cross-Sections
Type
Fuse Miniature
[A] [A]
ESMD371C2YXA 10 C10 10 2.5 14 ESMD751C2YXA 16 C16 15 2.5 14
1/N/PE
ESMD112C2YXA 20 C20 20 4 12 ESMD152C2YXA 25 C25 25 6 12 ESMD222C2YXA 32 C32 30 4 10
ESMD371C2YXA ... ESMD751C2YXA ESMD371C4TXA ... ESMD222C4TXA
ESMD112C2YXA, ESMD152C2YXA ESMD302C4TXA
ESMD222C2YXA 16 C16 15 2.5 12 ESMD402C4TXA 16 C16 15 2.5 14
ESMD302C2TXA ESMD552C4TXA
3/PE
ESMD402C2TXA ESMD752C4TXA
ESMD552C2TXA, ESMD113C4TXA 40 C40 35 6 8
ESMD752C2TXA, ESMD153C4TXA 50 C50 45 10 8
ESMD183C4TXA 63 C63 60 16 6
ESMD113C2TXA, ESMD223C4TXA 80 C80 70 16 6
ESMD153C2TXA 100 C100 90 16 4
(1) Observe the applicable local regulations. (2) Pulse-current or universal-current sensitive earth leakage circuit breaker. (3) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, required. Bussman KTK-R, JJN, JJS or equivalent. (4) Connection without end ferrules or with attached pin end connectors. (5) Installations with high fault current due to large supply mains may require a type D circuit breaker. (6) Thermomagnetic type breakers preferred.
10 C10 10 2.5 14
16 C16 12 2.5 14
20 C20 20 4 12
25 C25 25 6 10
Recommendations
circuit
(5)
breaker
(3)
Fuse
or
Breaker
(N. America)
[A]
B
(1)
Input Power Wiring
(6)
(L1, L2/N, L3, PE)
[mm²] [AWG]
A
C
E
D
Tmd005
E.l.c.b.
> 30 mA
(2)
Lenze 13466183 EDBSC03 v7 11
Loading...
+ 25 hidden pages