About these Operating Instructions
Conventions used in this Manual
1Preface and general information
1.1About these Operating Instructions
These Operating Instructions will assist you in connecting and commissioning the ECSxA...
axis modules.
They contain safety instructions which must be observed!
All persons working on and with the ECSxA... axis modules must have the Operating
Instructions available and must observe the information and notes relevant for their work.
The Operating Instructions must always be in a complete and perfectly readable state.
1.1.1Conventions used in this Manual
This Manual uses the following conventions to distinguish between different types of
information:
Information typePrint
(in the descriptive text)
System block nameboldThe SB DIGITAL_IO...
System block variable identifieritalicsThe input DIGIN_bIn1_b...
Example
Further information ...
about the conventions used for the Lenze variable identifiers, system blocks,
function blocks, and functions can be found in the appendix of the DDS online
documentation "Introduction to IEC 61131−3 programming".
The compliance with these conventions ensures uniform and universal
labelling and makes reading PLC programs easier.
14
EDBCSXA064 EN 3.2
1.1.2Terminology used
TermIn the following text used for
Power supply module
ECSxE...
Capacitor module
ECSxK...
Axis module
Controller
Standard device
ECSxS...
ECSxP...
ECSxM...
ECSxA ...
Drive systemECS drive system consisting of:
24 V supply
Low−voltage supply
AIFAutomation InterFace
System bus (CAN)Lenze standard bus system based on CANopen for
MotionBus (CAN)The "MotionBus (CAN)" term expresses the functionality of the CAN interface X4 in
DDSDrive PLC Developer Studio
GDCGlobal Drive Control
GDOGlobal Drive Oscilloscope
CxxxxCode Cxxxx (e.g. C0351)
Cxxxx/ySubcode y of code Cxxxx (e. g. C0470/3 = subcode 3 of code C0470)
Xk/yTerminal y on terminal strip Xk (e.g. X6/B+ = terminal B+ on terminal strip X6)
Preface and general information
About these Operating Instructions
Terminology used
ECSxE... power supply module
ECSxK... capacitor module
Axis module of the ECS series
l ECSxS... − "Speed and Torque"
l ECSxP... − "Posi and Shaft"
l ECSxM... − "Motion"
l ECSxA... − "Application"
l ECSxE... power supply module
l Axis module ECSxS... / ECSxP... / ECSxM... / ECSxA...
l ECSxK series capacitor module (optional)
l further Lenze drive components (accessories)
Voltage supply
l of the control card, voltage range 20 ... 30 V DC (±0 V)
l of the "safe torque off" function (formerly "safe standstill"), voltage range
18 ... 30 V DC (±0 V)
l of the motor holding brake, voltage range 23 ... 30 V DC (±0 V)
l communication with a higher−level host system (PLC) or further controllers.
l parameter setting and diagnostics.
case of ECSxS/P/M... axis modules, where communication takes place using a
higher−level host system (PLC) or further controllers exclusively via the X4 interface.
Interface X14 (CAN−AUX) is exclusively used for parameter setting and diagnostics.
(Lenze software for PLC programming acc. to IEC 61131)
(Lenze software for parameter setting and diagnostics)
(additional diagnostic tool of the GDC)
Parameters which serve to parameterise or monitor the controller.
1
EDBCSXA064 EN 3.2
15
1
Preface and general information
About these Operating Instructions
Code descriptions
1.1.3Code descriptions
Lenze codes are described in the form of tables with the following structure:
ColumnAbbreviationMeaning
No.
NameLCD display of the keypad XT EMZ9371BC
Lenze/{Appl.}
Selection1{%}99 minimum value{unit} maximum value
IMPORTANTShort code description
Cxxxx
1Subcode 1 of Cxxxx
2Subcode 2 of Cxxxx
CxxxxChanged input value of the code or subcode is accepted after pressing
[Cxxxx]Changed input value of the code or subcode is accepted after pressing
xLenze setting:
{xxx...}Different application initialisation value
àThe "Important" column contains further information
Code no. Cxxxx
.
when the controller is inhibited.
l Value at the time of delivery or after loading the Lenze setting using
C0002.
l Value at the time of delivery
l After loading the Lenze setting using C0002, the application
initialisation value is overwritten with the Lenze setting.
l The application initialisation values can be restored by loading the
application software with "Global Drive Loader" (GDL).
Example
CodePossible settingsIMPORTANT
No.DesignationLenze/
{Appl.}
C0003 Par save0
C1192Selection of resistance
1 Char.: OHM1000
2 Char.: OHM2225PTC characteristic:
Selection
Non−volatile saving of parameter
set
0No response
1Save parameter set
characteristic for PTC
0{1 W}30000 PTC characteristic:
{0}
resistance R1 at T1
resistance R2 at T2
16
EDBCSXA064 EN 3.2
Preface and general information
About these Operating Instructions
Structure of the system block descriptions
1.1.4Structure of the system block descriptions
All system block descriptions contained in this Manual have the same structure:
1
Headline with SB identifier
SB function and node number
Brief description of the SB and its most important
features
Graph including all corresponding system variables
l Input variables
l Output variables
Table giving information about input and output
variables:
l Identifier
l Data type
l Signal type
l Address
l Display code
l Display format
l Information
l Detailed functional description of the SB
l Code description
EDBCSXA064 EN 3.2
17
1
1.2Features of the ECSxA axis module
Preface and general information
Features of the ECSxA
ƒ Safety function "safe torque off" (formerly "safe standstill")
ƒ PLC programming according to IEC 61131−3 with the Lenze software "Drive PLC
Developer Studio" (DDS)
ƒ Functions that can be used in your projects are available as system blocks(SB).
– Chapter "1.5 Introduction of system blocks" ( 21)
– Chapter "13 System blocks" ( 255)
Information and auxiliary devices related to the Lenze products can be found
in the download area at
http://www.Lenze.com
EDBCSXA064 EN 3.2
19
1
Preface and general information
Legal regulations
1.4Legal regulations
Identification
Application as
directed
Liabilityl The information, data and notes in these Instructions met the state of the art at the time of printing. Claims
Warrantyl Terms of warranty: See terms of sales and delivery of Lenze Drive Systems GmbH.
NameplateCE designationManufacturer
Lenze controllers are
unambiguously designated by the
contents of the nameplate.
ECSxA... axis modules
l must only be operated under the conditions prescribed in these Instructions.
l are components
– for open and closed loop control of variable speed drives with PM synchronous motors and asynchronous
motors.
– for installation into a machine
– for assembly with other components to form a machine.
l are electrical equipment for the installation in control cabinets or similar closed operating areas.
l comply with the protective requirements of the EC Low−Voltage Directive.
l are not machines for the purpose of the EC Machinery Directive.
l are not to be used as domestic appliances, but for industrial purposes only.
Drive systems with ECSxA... axis modules
l comply with the EC Directive "Electromagnetic compatibility" if they are installed according to the guidelines
of CE−typical drive systems.
l can be used
– at public and non−public mains.
– in industrial premises.
l The user is responsible for the compliance of his application with the EC directives.
Any other use shall be deemed inappropriate!
on modifications referring to axis modules and components which have already been supplied cannot be
derived from the information, illustrations and descriptions given in these Instructions.
l The specifications, processes, and circuitry described in these Instructions are for guidance only and must be
adapted to your own specific application. Lenze does not take responsibility for the suitability of the process
and circuit proposals.
l Lenze does not accept any liability for damages and failures caused by:
– Disregarding the Operating Instructions
– Unauthorised modifications to the axis module
– Operating errors
– Improper working on and with the axis module
l Warranty claims must be made to Lenze immediately after detecting the deficiency or fault.
l The warranty is void in all cases where liability claims cannot be made.
Lenze pursues the principle to describe functions of the controller by means of function
blocks (FB). This principle is also described in the standard IEC 61131−3.
ƒ Functions that you can use in your project as software functionalities, are contained
in the function libraries as function blocks or functions.
ƒ Moreover, quasi hardware functions are available as system blocks(SB).
1.5.1System blocks ˘ principle
ƒ System blocks partly respond to real hardware.
ƒ The system blocks are assigned/identified via node numbers. ( 22)
ƒ The inputs/outputs of the system blocks are assigned via:
General safety and application notes for Lenze controllers
2Safety instructions
2.1General safety and application notes for Lenze controllers
(in accordance with Low−Voltage Directive 2006/95/EC)
For your personal safety
Disregarding the following safety measures can lead to severe injury to persons and
damage to material assets:
ƒ Only use the product as directed.
ƒ Never commission the product in the event of visible damage.
ƒ Never commission the product before assembly has been completed.
ƒ Do not carry out any technical changes on the product.
ƒ Only use the accessories approved for the product.
ƒ Only use original spare parts from Lenze.
ƒ Observe all regulations for the prevention of accidents, directives and laws
applicable on site.
ƒ Transport, installation, commissioning and maintenance work must only be carried
out by qualified personnel.
– Observe IEC 364 and CENELEC HD 384 or DIN VDE 0100 and IEC report 664 or
DIN VDE 0110 and all national regulations for the prevention of accidents.
– According to this basic safety information, qualified, skilled personnel are persons
who are familiar with the assembly, installation, commissioning, and operation of
the product and who have the qualifications necessary for their occupation.
ƒ Observe all specifications in this documentation.
– This is the condition for safe and trouble−free operation and the achievement of
the specified product features.
– The procedural notes and circuit details described in this documentation are only
proposals. It is up to the user to check whether they can be transferred to the
particular applications. Lenze Automation GmbH does not accept any liability for
the suitability of the procedures and circuit proposals described.
ƒ Depending on their degree of protection, some parts of the Lenze controllers
(frequency inverters, servo inverters, DC speed controllers) and their accessory
components can be live, moving and rotating during operation. Surfaces can be hot.
– Non−authorised removal of the required cover, inappropriate use, incorrect
installation or operation, creates the risk of severe injury to persons or damage to
material assets.
– For more information, please see the documentation.
28
ƒ High amounts of energy are produced in the controller. Therefore it is required to
wear personal protective equipment (body protection, headgear, eye protection, ear
protection, hand guard).
EDBCSXA064 EN 3.2
Safety instructions
General safety and application notes for Lenze controllers
Application as directed
Controllers are components which are designed for installation in electrical systems or
machines. They are not to be used as domestic appliances, but only for industrial purposes
according to EN 61000−3−2.
When controllers are installed into machines, commissioning (i.e. starting of the operation
as directed) is prohibited until it is proven that the machine complies with the regulations
of the EC Directive 2006/42/EC (Machinery Directive); EN 60204 must be observed.
Commissioning (i.e. starting of the operation as directed) is only allowed when there is
compliance with the EMC Directive (2004/108/EC).
The controllers meet the requirements of the Low−Voltage Directive 2006/95/EC. The
harmonised standard EN 61800−5−1 applies to the controllers.
The technical data and supply conditions can be obtained from the nameplate and the
documentation. They must be strictly observed.
Warning: Controllers are products which can be installed in drive systems of category C2
according to EN 61800−3. These products can cause radio interferences in residential areas.
In this case, special measures can be necessary.
2
Transport, storage
Please observe the notes on transport, storage, and appropriate handling.
Observe the climatic conditions according to the technical data.
Installation
The controllers must be installed and cooled according to the instructions given in the
corresponding documentation.
The ambient air must not exceed degree of pollution 2 according to EN 61800−5−1.
Ensure proper handling and avoid excessive mechanical stress. Do not bend any
components and do not change any insulation distances during transport or handling. Do
not touch any electronic components and contacts.
Controllers contain electrostatic sensitive devices which can easily be damaged by
inappropriate handling. Do not damage or destroy any electrical components since this
might endanger your health!
EDBCSXA064 EN 3.2
29
2
Safety instructions
General safety and application notes for Lenze controllers
Electrical connection
When working on live controllers, observe the applicable national regulations for the
prevention of accidents (e.g. VBG 4).
The electrical installation must be carried out according to the appropriate regulations
(e.g. cable cross−sections, fuses, PE connection). Additional information can be obtained
from the documentation.
This documentation contains information on installation in compliance with EMC
(shielding, earthing, filter, and cables). These notes must also be observed for CE−marked
controllers. The manufacturer of the system is responsible for compliance with the limit
values demanded by EMC legislation. The controllers must be installed in housings (e.g.
control cabinets) to meet the limit values for radio interferences valid at the site of
installation. The housings must enable an EMC−compliant installation. Observe in
particular that e.g. the control cabinet doors have a circumferential metal connection to
the housing. Reduce housing openings and cutouts to a minimum.
Lenze controllers may cause a DC current in the PE conductor. If a residual current device
(RCD) is used for protection against direct or indirect contact for a controller with
three−phase supply, only a residual current device (RCD) of type B is permissible on the
supply side of the controller. If the controller has a single−phase supply, a residual current
device (RCD) of type A is also permissible. Apart from using a residual current device (RCD),
other protective measures can be taken as well, e.g. electrical isolation by double or
reinforced insulation or isolation from the supply system by means of a transformer.
Operation
If necessary, systems including controllers must be equipped with additional monitoring
and protection devices according to the valid safety regulations (e.g. law on technical
equipment, regulations for the prevention of accidents). The controllers can be adapted to
your application. Please observe the corresponding information given in the
documentation.
After the controller has been disconnected from the supply voltage, all live components
and power terminals must not be touched immediately because capacitors can still be
charged. Please observe the corresponding stickers on the controller.
All protection covers and doors must be shut during operation.
Notes for UL−approved systems with integrated controllers: UL warnings are notes that
only apply to UL systems. The documentation contains special UL notes.
30
EDBCSXA064 EN 3.2
Safety instructions
General safety and application notes for Lenze controllers
Safety functions
Certain controller versions support safety functions (e.g. "Safe torque off", formerly "Safe
standstill") according to the requirements of the EC Directive 2006/42/EC (Machinery
Directive). The notes on the integrated safety system provided in this documentation must
be observed.
Maintenance and servicing
The controllers do not require any maintenance if the prescribed operating conditions are
observed.
Disposal
Recycle metal and plastic materials. Ensure professional disposal of assembled PCBs.
The product−specific safety and application notes given in these instructions must be
observed!
2
EDBCSXA064 EN 3.2
31
2
Safety instructions
Thermal motor monitoring
2.2Thermal motor monitoring
Note!
2
ƒ I
x t monitoring is based on a mathematical model which calculates a
thermal motor load from the detected motor currents.
ƒ The calculated motor load is saved when the mains is switched.
ƒ The function is UL−certified, i.e. no additional protective measures are
required for the motor in UL−approved systems.
ƒ However, I
the motor load could not be detected as for instance changed cooling
conditions (e.g. interrupted or too warm cooling air flow).
2
x t load of the motor is displayed in C0066.
Die I
The thermal loading capacity of the motor is expressed by the thermal motor time
constant (t, C0128). Find the value in the rated motor data or contact the manufacturer of
the motor.
2
The I
x t monitoring has been designed such that it will be activated after 179 s in the
event of a motor with a thermal motor time constant of 5 minutes (Lenze setting C0128),
a motor current of 1.5 x I
Two adjustable trigger thresholds provide for different responses.
2
x t monitoring is no full motor protection as other influences on
N
and a trigger threshold of 100 %.
ƒ Adjustable response OC8 (TRIP, warning, off).
– The trigger threshold is set in C0127.
– The response is set in C0606.
– The response OC8, for instance, can be used for an advance warning.
ƒ Fixed response OC6−TRIP.
– The trigger threshold is set in C0120.
Behaviour of the I2 x t monitoringCondition
The I2 x t monitoring is deactivated.
C0066 is set = 0 % and
MCTRL−LOAD−I2XT is set = 0.00 %.
I2 x t monitoring is stopped.
The current value in C0066 and at the
MCTRL−LOAD−I2XT output is frozen.
I2 x t monitoring is deactivated.
The motor load is displayed in C0066.
When C0120 = 0 % and C0127 = 0 %, set controller
inhibit.
When C0120 = 0 % and C0127 = 0 %, set controller
enable.
Set C0606 = 3 (off) and C0127 > 0 %.
Note!
An error message OC6 or OC8 can only be reset if the I2 x t load falls below the
set trigger threshold by 5 %.
32
EDBCSXA064 EN 3.2
Forced ventilated or naturally ventilated motors
2.2.1Forced ventilated or naturally ventilated motors
Parameter setting
2
The following codes can be set for I
CodeMeaningValue rangeLenze setting
C0066Display of the I2 x t load of the motor0 ... 250 %−
C0120Threshold: Triggering of error "OC6"0 ... 120 %0 %
C0127Threshold: Triggering of error "OC8"0 ... 120 %0 %
C0128Thermal motor time constant0.1 ... 50.0 min5.0 min
C0606Response to error "OC8"TRIP, warning, offWarning
x t monitoring:
Calculate release time and I2 x t load
Formula for release timeInformation
t +*(t) ln
ȡ
ȧ
ȧ
Ȣ
1 *
I
ȣ
z ) 1
I
Mot
ǒ
Ǔ
I
N
2
100
ȧ
ȧ
Ȥ
Mot
I
r
tThermal motor time constant (C0128)
zThreshold value in C0120 (OC6) or C0127 (OC8)
Actual motor current (C0054)
Rated motor current (C0088)
Safety instructions
Thermal motor monitoring
2
Formulae for I2 x t loadInformation
L(t)Chronological sequence of the I2 x t load of the motor
2
I
Mot
ǒ
L(t) +
If the controller is inhibited, the I2 x t load is reduced:
Ǔ
100% ǒ1 * e
I
N
L(t) + L
Start
Ǹ
e
*t
t
t
*
t
I
Ǔ
Mot
IrRated motor current (C0088)
tThermal motor time constant (C0128)
L
Start
(Display: C0066)
Actual motor current (C0054)
I2 x t load before controller inhibit
If an error is triggered, the value corresponds to the
threshold value set in C0120 (OC6) or
C0127 (OC8).
Read release time in the diagram
Diagram for detecting the release times for a motor with a thermal motor time constant
of 5 minutes (Lenze setting C0128):
L [%]
120
100
50
0
Fig. 2−1I2 × t−monitoring: Release times for different motor currents and trigger thresholds
I= 3 × I
MotN
0100200300400500600700800900
I
Mot
I
r
LI
TTime
I= 2 × I
MotN
Actual motor current (C0054)
Rated motor current (C0088)
2
x t load of the motor (display: C0066)
I= 1.5 × I
MotN
I= 1 × I
MotN
t [s]
1000
9300STD105
EDBCSXA064 EN 3.2
33
2
Safety instructions
Thermal motor monitoring
Self−ventilated motors
2.2.2Self−ventilated motors
Due to the construction, self−ventilated standard motors are exposed to an increased heat
generation in the lower speed range compared to forced ventilated motors.
Warnings!
For complying with the UL 508C standard, you have to set the
speed−dependent evaluation of the permissible torque via code C0129/x.
Parameter setting
The following codes can be set for I
CodeMeaningValue rangeLenze setting
C0066Display of the I2 x t load of the motor0 ... 250 %−
C0120Threshold: Triggering of error "OC6"0 ... 120 %0 %
C0127Threshold: Triggering of error "OC8"0 ... 120 %0 %
C0128Thermal motor time constant0.1 ... 50.0 min5.0 min
C0606Response to error "OC8"TRIP, warning, offWarning
C0129/1S1 torque characteristic I1/I
C0129/2S1 torque characteristics n2/n
2
x t monitoring:
rated
rated
10 ... 200 %100 %
10 ... 200 %40 %
Effect of code C0129/x
I / I
N
1.1
1.0
3
0.9
0.8
0.7
0.6
Fig. 2−2Working point in the range of characteristic lowering
0
0
00.1
C0129/1
0.132
C0129/2
1
2
0.20.30.4
n / n
N
9300STD350
The lowered speed / torque characteristic (Fig. 2−2) reduces the permissible thermal load
of self−ventilated standard motors. The characteristic is a line the definition of which
requires two points:
ƒ Point : Definition with C0129/1
This value also enables an increase of the maximally permissible load.
ƒ Point : Definition with C0129/2
With increasing speeds, the maximally permissible load remains unchanged
(I
Mot
= I
rated
).
In Fig. 2−2, the motor speed and the corresponding permissible motor torque () can be
read for each working point (on the characteristic () ... ). can also be calculated
using the values in C0129/1and C0129/2 (evaluation coefficient "y", 35)
34
EDBCSXA064 EN 3.2
Thermal motor monitoring
Calculate release time and I2 x t load
Calculate the release time and the I
2
x t load of the motor considering the values in
C0129/1 and C0129/2(evaluation coefficient "y").
Formulae for release timeInformation
TRelease time of the I2 x t monitoring
ȡ
I
Mot
ǒ
yI
Ǹ
e
z ) 1
Ǔ
N
n
) C0129ń1
n
N
*
T +*(t) ln
ȧ
ȧ
1 *
Ȣ
100% * C0129ń1
y +
Formulae for I2 x t loadInformation
If the controller is inhibited, the I2 x t load is reduced:
L(t) +
C0129ń2
I
Mot
ǒ
y I
L(t) + L
2
Ǔ
100% ǒ1 * e
N
Start
2
100
t
t
ȣ
tThermal motor time constant (C0128)
InFunction: Natural logarithm
ȧ
ȧ
I
Mot
Ȥ
I
r
zThreshold value in C0120 (OC6) or C0127 (OC8)
yEvaluation coefficient
n
rated
L(t)Chronological sequence of the I2 x t load of the motor
yEvaluation coefficient
*t
Ǔ
t
I
Mot
IrRated motor current (C0088)
tThermal motor time constant (C0128)
L
Start
Actual motor current (C0054)
Rated motor current (C0088)
Rated speed (C0087)
(Display: C0066)
Actual motor current (C0054)
I2 x t load before controller inhibit
If an error is triggered, the value corresponds to the
threshold value set in C0120 (OC6) or
Safety instructions
Self−ventilated motors
C0127 (OC8).
2
EDBCSXA064 EN 3.2
35
2
2.3Residual hazards
Safety instructions
Residual hazards
Protection of persons
ƒ Before working on the axis module, check that no voltage is applied to the power
terminals, because
– the power terminals +UG, −UG, U, V and W remain live for at least 3 minutes after
mains switch−off.
– the power terminals +UG, −UG, U, V and W remain live when the motor is stopped.
ƒ The heatsink has an operating temperature of > 70 °C:
– Direct skin contact with the heatsink results in burns.
ƒ The discharge current to PE is > 3.5 mA AC or. > 10 mA DC.
– EN 61800−5−1 requires a fixed installation.
– The PE connection must comply with EN 61800−5−1.
– Comply with the further requirements of EN 61800−5−1 for high discharge
currents!
Device protection
ƒ All pluggable connection terminals must only be connected or disconnected when
no voltage is applied!
ƒ The power terminals +UG, −UG, U, V, W and PE are not protected against polarity
reversal.
– When wiring, observe the polarity of the power terminals!
ƒ Power must not be converted until all devices of the power system are ready for
operation. Otherwise, the input current limitation may be destroyed.
Frequent mains switching (e.g. inching mode via mains contactor) can overload and
destroy the input current limitation of the axis module, if
ƒ the axis module is supplied via the ECSxE supply module and the input current
limitation is activated depending on the DC−bus voltage (C0175 = 1 or 2).
ƒ the axis module is not supplied via a supply module delivered by Lenze.
ƒ the low−voltage supply (24 V) is switched off.
For this reason allow a break of at least three minutes between two starting operations!
Use the safety function ˜Safe torque off˜ (STO) for frequent disconnections for safety
reasons.
36
EDBCSXA064 EN 3.2
Safety instructions
Residual hazards
Motor protection
ƒ Only use motors with a minimum insulation resistance of û = 1.5 kV,
min. du/dt = 5 kV/ms.
– Lenze motors meet these requirements.
ƒ When using motors with an unknown insulation resistance, please contact your
motor supplier.
ƒ Some settings of the axis module lead to an overheating of the connected motor,
e.g. longer operation of self−ventilated motors with low speeds.
ƒ Use PTC thermistors or thermostats with PTC characteristic for motor temperature
monitoring.
2
EDBCSXA064 EN 3.2
37
2
Safety instructions
Safety instructions for the installation according to UL
2.4Safety instructions for the installation according to UL
Warnings!
General markings:
ƒ Use 60/75 °C or 75 °C copper wire only.
ƒ Maximum ambient temperature 55 °C, with reduced output current.
Markings provided for the supply units:
ƒ Suitable for use on a circuit capable of delivering not more than 5000 rms
symmetrical amperes, 480 V max, when protected by K5 or H Fuses
(400/480 V devices).
combination motor controller type E) may be used in lieu of above fuses
when it is shown that the let−through energy (i
) of the inverse−time current−limiting circuit breaker will be less
p
current (I
than that of the non−semiconductor type K5 fuses with which the drive has
been tested.
ƒ Alternate − An inverse−time circuit breaker may be used, sized upon the
input rating of the drive, multiplied by 300 %.
Markings provided for the inverter units:
ƒ The inverter units shall be used with supply units which are provided with
overvoltage devices or systems in accordance with UL840 2nd ed., Table 5.1.
ƒ The devices are provided with integral overload and integral thermal
protection for the motor.
ƒ The devices are not provided with overspeed protection.
2
t) and peak let−through
Terminal tightening torque of lb−in (Nm)
Terminallb−inNm
X 21, X 22, X 23, X 2410.6 ... 13.31.2 ... 1.5
X4, X6, X141.95 ... 2.20.22 ... 0.25
X 254.4 ... 7.10.5 ... 0.8
Wiring diagram AWG
TerminalAWG
X 21, X 22, X 23, X 2412 ... 8
X4, X6, X1428 ... 16
X 2524 ... 12
38
EDBCSXA064 EN 3.2
2.5Notes used
The following pictographs and signal words are used in this documentation to indicate
dangers and important information:
Safety instructions
Structure of safety instructions:
Danger!
(characterises the type and severity of danger)
Note
(describes the danger and gives information about how to prevent dangerous
situations)
Pictograph and signal wordMeaning
Danger!
Danger!
Stop!
Safety instructions
Notes used
Danger of personal injury through dangerous electrical voltage.
Reference to an imminent danger that may result in death or
serious personal injury if the corresponding measures are not
taken.
Danger of personal injury through a general source of danger.
Reference to an imminent danger that may result in death or
serious personal injury if the corresponding measures are not
taken.
Danger of property damage.
Reference to a possible danger that may result in property
damage if the corresponding measures are not taken.
2
Application notes
Pictograph and signal wordMeaning
Note!
Tip!
Special safety instructions and application notes for UL and UR
Pictograph and signal wordMeaning
Warnings!
Warnings!
Important note to ensure troublefree operation
Useful tip for simple handling
Reference to another documentation
Safety or application note for the operation of a UL−approved
device in UL−approved systems.
Possibly the drive system is not operated in compliance with UL
if the corresponding measures are not taken.
Safety or application note for the operation of a UR−approved
device in UL−approved systems.
Possibly the drive system is not operated in compliance with UL
if the corresponding measures are not taken.
EDBCSXA064 EN 3.2
39
3
Technical data
General data and operating conditions
3Technical data
3.1General data and operating conditions
Standards and operating conditions
ConformityCELow−Voltage Directive (2006/95/EG)
Approvals
Max. permissible
Motor cable length
Packaging (EN ISO 4180)Shipping package
Installationl Installation into IP20 control cabinet
Mounting positionvertically suspended
Free space
shielded50 mFor rated mains voltage and switching frequency of 8 kHz
above³ 65 mm
below³ 65 mm
to the sidescan be mounted directly side by side without any clearance
UL 508C
CSA 22.2 No. 14
l For the "safe torque off" function (formerly "safe standstill"): mounting in IP54
control cabinet
With ECSZS000X0B shield mounting kit: > 195 mm
Power Conversion Equipment
Underwriter Laboratories (File No. E132659)
for USA and Canada
Environmental conditions
Climate3k3 in accordance with IEC/EN 60721−3−3
Condensation, splash water and ice formation
not permissible.
Site altitude0 ... 4000 m amsl
PollutionEN 61800−5−1, UL840: Degree of pollution 2
Vibration resistanceAcceleration resistant up to 0.7 g (Germanischer Lloyd, general conditions)
StorageIEC/EN 60721−3−11K3 (−25 ... + 55 °C)
TransportIEC/EN 60721−3−22K3 (−25 ... +70 °C)
OperationIEC/EN 60721−3−33K3 (0 ... + 55 °C)
l Atmospheric pressure: 86 ... 106 kPa
l Above +40 °C: reduce the rated output
current by 2 %/°C.
l Reduce rated output current by
5 %/1000 m above 1000 m amsl.
l Over 2000 m amsl: Use is only permitted in
environments with overvoltage category II
40
EDBCSXA064 EN 3.2
Technical data
General data and operating conditions
General electrical data
EMCCompliance with the requirements acc. to EN 61800−3
Noise emissionCompliance with the limit class C2 acc. to EN 61800−3
(achieved by using collective filters typical for the application)
Noise immunity
Insulation resistanceEN61800−5−1, UL840: Overvoltage category III
Discharge current to PE
(Acc. to EN 61800−5−1)
EnclosureIP20 for
Protective measures againstl Short circuit in power terminals
Protective insulation of control circuitsProtective separation from the mains
1)
Noise immunity in the above−mentioned severities must be guaranteed by the control cabinet! The user
must check the compliance with the severities!
Requirements acc. to EN 61800−3
RequirementStandardSeverity
1)
ESD
Conducted high frequencyEN 61000−4−610 V; 0.15 ... 80 MHz
RF interference (housing)EN 61000−4−33, i. e. 10 V/m;
BurstEN 61000−4−43/4, i. e. 2 kV/5 kHz
Surge (surge voltage on mains
cable)
> 3.5 mA AC
l Standard installation (built−in unit)
l Cold−plate technique
l Mounting with thermal separation (push−through technique), IP54 on heatsink side
– Motor terminal has a limited protection against short circuit (after short circuit
detection, the error message must be reset.)
l Short circuit in auxiliary circuits
– Digital outputs: Short−circuit−proof
– Bus and encoder systems: Limited protection against short circuit (if necessary,
monitoring functions can be switched off, in this case, error messages must be
reset:)
l Earth fault (earth−fault protected during operation, limited earth−fault protection
on mains power−up)
l Overvoltage
l Motor stalling
l Motor overtemperature (input for KTY, I
Double/reinforced insulation acc. to EN 61800−5−1
EN 61000−4−23, i. e.
EN 61000−4−53, i. e. 1.2/50 ms
2
x t monitoring)
3
l 8 kV for air discharge
l 6 kV for contact discharge
80 ... 1000 MHz
l 1 kV phase/phase
l 2 kV phase/PE
EDBCSXA064 EN 3.2
41
3
Technical data
Rated data
3.2Rated data
Rated dataType
ECSx004ECSx008ECSx016
Output power 400 V mainsS
Data for operation with upstream power supply module
on mains voltage
DC−bus voltageV
DC−bus currentI
Rated output current at 4 kHz
(causes a heatsink temperature of 70°C at an ambient
temperature of 20°C)
Rated output current at 8 kHz(at an ambient
temperature of 20°C it causes a heatsink temperature
of 70°C)
Max. output current
(acceleration current)
Continuous current at standstill
(holding current at 90°C, 4 kHz)
Short−time standstill current
(holding current at 90 °C, 4 kHz)
Short−time standstill current
(holding current at 70 °C, 4 kHz)
Short−time standstill current
(holding current at 70 °C, 8 kHz)
Power loss (operation with rated
current at 4 kHz / 8 kHz)
Max. output frequencyf
Massm [kg]approx. 2.4
1)
2)
2)
2)
Total
Inside the device13.317.320.7
Heatsink14.029.064.0
1)
If the heatsink temperature reaches 70°C, the switching frequency automatically changes to 4 kHz.
2)
The indicated temperature is the measured heatsink temperature (C0061).
Application software:
[kVA]1.32.65.3
rated
V
[V]400480400480400480
mains
[V]15 ... 770
DC−bus
[A]2.52.04.93.99.87.8
DC−bus
Ir [A]2.01.64.03.28.06.4
Ir [A]1.41.12.72.25.34.2
I
[A]4.08.016.0
max
I
0,eff 4 kHz
I
0,eff 4 kHz
I
0,eff 4 kHz
I
0,eff 8 kHz
S = Speed & TorqueP = Posi & Shaft
M = MotionA = Application
[A]2.01.64.03.28.06.4
[A]2.34.69.1
[A]3.06.012.0
[A]1.53.06.0
27.346.384.7
P
[W]
loss
[Hz]600
out
Axis module
42
EDBCSXA064 EN 3.2
Technical data
Rated data
3
Rated dataType
ECSx032ECSx048ECSx064
Output power 400 V mainsS
Data for operation with upstream power supply module
on mains voltage
DC−bus voltageV
DC−bus currentI
Rated output current at 4 kHz
(causes a heatsink temperature of 70°C at an ambient
temperature of 20°C)
Rated output current at 8 kHz(at an ambient
temperature of 20°C it causes a heatsink temperature
of 70°C)
Max. output current
(acceleration current)
Continuous current at standstill
(holding current at 90°C, 4 kHz)
Short−time standstill current
(holding current at 90 °C, 4 kHz)
Short−time standstill current
(holding current at 70 °C, 4 kHz)
Short−time standstill current
(holding current at 70 °C, 8 kHz)
Power loss (operation with rated
current at 4 kHz / 8 kHz)
Max. output frequencyf
Massm [kg]approx. 2.4approx. 3.3
1)
2)
2)
2)
2)
Total
Inside the device27.534.541.0
Heatsink117.0132.0158.0
1)
If the heatsink temperature reaches 70°C, the switching frequency automatically changes to 4 kHz.
2)
The indicated temperature is the measured heatsink temperature (C0061).
Application software:
[kVA]8.311.213.2
rated
U
[V]400480400480400480
mains
[V]15 ... 770
DC−bus
[A]15.612.520.916.824.519.6
DC−bus
Ir [A]12.710.217.013.620.016.0
Ir [A]8.56.811.39.013.310.6
I
[A]32.048.064.0
max
I
0,eff 4 kHz
I
0,eff 4 kHz
I
0,eff 4 kHz
I
0,eff 8 kHz
S = Speed & TorqueP = Posi & Shaft
M = MotionA = Application
[A]16.012.823.018.427.021.6
[A]18.127.236.3
[A]24.036.048.0
[A]12.118.124.2
144.5166.5199.0
P
[W]
loss
[Hz]600
out
Axis module
EDBCSXA064 EN 3.2
43
3
Technical data
Current characteristics
Increased continuous current depending on the control factor
3.3Current characteristics
3.3.1Increased continuous current depending on the control factor
In the lower speed range ˘ the motor does not need the full motor voltage ˘ particularly
the more powerful ECS axis modules can be permanently operated with increased output
current (cp. continuous current I
I [A]
I [A]
0
30.0
27.0
25.0
23.0
20.0
16.0
15.0
10.0
8.0
5.0
4.0
2.0
0.0
0 %50 %
Fig. 3−1Continuous device current, depending on the output voltage for U
I
r
U
Mot_n
U
Mot_max
Rated output current of the axis module
Actual controller output voltage
0.9 x current mains voltage
42).
0,eff
ECSxS/P/M/A064
ECSxS/P/M/A048
ECSxS/P/M/A032
ECSxS/P/M/A016
ECSxS/P/M/A008
ECSxS/P/M/A004
I [A]
N
20.0
17.0
12.7
U/U
Mot
£ 400 V at 4 kHz
mains
8.0
4.0
2.0
100 %
max
ECSXA002
The permissible continuous current depends on the control factor of the power output
stages, approximately on the ratio of the motor voltage output in the operating point
(U
the components involved at rated load and a control margin, U
) to the maximum possible output voltage (U
Mot_n
Mot_max
). Due to voltage drops across
Mot_max
can be estimated
with 90 % of the mains voltage.
Tip!
The operating threshold of the device utilisation monitoring (I x t) function is
automatically adapted to the continuous device current which changes
depending on the output voltage (see fig.).
44
EDBCSXA064 EN 3.2
Technical data
Current characteristics
Increased continuous current depending on the control factor
The following table shows the connections between mains voltage, DC−bus voltage and
motor voltage:
3
Mains voltage
]
[U
mains
3 x 230 V AC310 V DC3 x 205 V AC
3 x 380 V AC510 V DC3 x 340 V AC
3 x 400 V AC540 V DC3 x 360 V AC
3 x 415 V AC560 V DC3 x 370 V AC
3 x 460 V AC620 V DC3 x 415 V AC
3 x 480 V AC650 V DC3 x 435 V AC
3 x 528 V AC712 V DC3 x 475 V AC
DC−bus voltage
= U
[U
DC
mains
x 1.35]
Output voltage (motor voltage)
nominally achievable for 100 %
modulation
[U
mot
= 0.66 x UDC]
For steady−state operation in generator mode with increased DC−bus voltage or supply
from a closed−loop DC−voltage source, interpolate accordingly between the values given in
the table.
The increased rated currents are valid for the entire voltage range specified at switching
frequencies of 4 kHz and 8 kHz.
Note!
If in this connection a heatsink temperature of > 70 °C is reached, the drive
switches to a switching frequency of 4 kHz, independently of the selected
switching frequency.
EDBCSXA064 EN 3.2
45
3
Technical data
Current characteristics
Increased continuous current depending on the control factor
Example:
The ECS axis module suitable for operation in conjunction with a Lenze motor of type
MCS 14L32 is to be determined.
ƒ Rated motor data
– Rated motor torque (M
– Rated motor speed (n
– Motor voltage at 3250 rpm (U
– Rated motor current (I
– Max. motor current (I
ƒ Application data:
– Max. torque (M
) = 35 Nm
max
– Max. operating speed (n
– An effective process power (P
– The drive rating results in an effective motor current (I
) = 17.2 Nm
mot
) = 3225 rpm
mot
) = 15 A
mot
mot_max
) = 2500 rpm
max
mot_n3250
) = 275 V
) = 92 A
) of 4.5 kW arises on the basis of the Mn diagram.
eff
Mot_eff
) of 14.8 A.
A first estimation based on the rated current of the ECS axis module would probably lead
to selecting the ECSxA048 module with a rated current of 17.0 A.
However, if we take into account the increased continuous current for smaller control
factors, the more cost−effective ECSxA032 axis module with a rated current of 12.7 A can
be used here.
ƒ When the MCS 14L32 is operated with 2500 rpm, the real motor voltage is
(U
Mot_n2500
U
ƒ This leads to the following max. control factor (α
):
Mot_n2500
a
max
+ U
+
Mot_n3250
U
Mot_n2500
U
max
n
max
@
n
Mot
Þ
Þ
275V @
max
2500rpm
3250rpm
+ 212V
) of the axis module:
212V
360V
+ 0.59 + 59%
Using the current characteristic of Fig. 3−1 ( 44), a continuous current of 15.5 A can
be determined for the ECSxA032 axis module when the control factor (α
ƒ Result:
max
) is 59 %.
Under the conditions mentioned above the MCS 14L32 Lenze motor can be operated
continuously on the ECSxA032 axis module.
46
EDBCSXA064 EN 3.2
3.3.2Device protection by current derating
The maximum output current is limited. With output frequencies < 5 Hz the limitation
depends on the heatsink temperature.
Technical data
Current characteristics
Device protection by current derating
3
1.00
Iout
Imax
0.75
0.57
0.38
0.00
Fig. 3−2Current derating characteristics
≤ 70 °C
90 °C
0510
Operation with switching frequency = 8 kHz (C0018 = 1).
l If the current exceeds the characteristic , the switching frequency is automatically
changed to 4 kHz (e.g. for higher torque in acceleration processes).
Operation with switching frequency = 4 kHz (C0018 = 0).
l The current limitation follows the characteristic .
l With output frequencies < 5 Hz and heatsink temperatures between 70 and 90 °C the
current limit is steplessly adjusted in the range .
1.00
0.67
fout [Hz]
ECSXA024
Type
Switching frequency 8 kHz Switching frequency 4 kHz
ƒ Axis modules of the ECS series provide IP20 enclosure and can therefore only be
used for installation in control cabinets.
ƒ If the cooling air contains air pollutants (dust, fluff, grease, aggressive gases):
– Take suitable preventive measures , e.g. separate air duct, installation of filters,
regular cleaning.
ƒ Possible mounting positions:
– Vertical at the mounting plate
– DC bus connections (X23) at the top
– Motor connection (X24) at the bottom
ƒ Maintain the specified clearances (above and below) to other installations!
– If the ECSZS000X0B shield mounting kit is used, an additional clearance is
required.
– Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
– Several modules of the ECS series can be installed in the control cabinet next to
each other without any clearance.
ƒ The mounting plate of the control cabinet
– must be electrically conductive.
– must not be varnished.
ƒ In case of continuous vibrations or shocks use shock absorbers.
48
EDBCSXA064 EN 3.2
Mechanical installation
Mounting with fixing rails (standard installation)
4.2Mounting with fixing rails (standard installation)
4.2.1Dimensions
Note!
Mounting with ECSZS000X0B shield mounting kit:
ƒ Mounting clearance below the module > 195 mm
4
Dimensions
0
g
³ 65 mm
³ 65 mm
Fig. 4−1Dimensions for "panel−mounted" design
Axis moduleDimensions [mm]
TypeSizeabdd1ehg
ECSE004
ECSE008
ECSE016
ECSE032
ECSE048
ECSE064
1)
Max. 212 mm, depending on the plugged−on communication module
Mounting with thermal separation (push−through technique)
Mounting steps
4.3.2Mounting steps
How to mount the axis module:
1. Prepare the fixing holes for the wire clamps on the mounting area.
For this purpose, apply a drilling jig.
2. Prepare the mounting cutout.
The edges of the mounting cutout and the fixing holes for the wire clamps have to be
slightly arched inwardly (to the axis module).
3. Apply liquid thread sealant to the threads of the screws for the wire clamps.
4. Fix the wire clamps together with the functional earth conductor supplied (Fig. 4−4).
The functional earth conductor is part of the scope of supply of the ECSDx... axis module
5. Push the axis module into the mounting cutout.
6. Engage axis module in the wire clamp at the top and the bottom.
7. Connect the functional earth conductor to the axis module (Fig. 4−4).
Note!
Fixing the functional earth conductor to the ECSDx... axis module is required
for a better electromagnetic compatibility (EMC).
ECSXA081
Fig. 4−4Functional earth conductor at the ECSDx... axis module
Functional earth conductor
54
EDBCSXA064 EN 3.2
4.4Mounting in cold−plate design
The axis modules ECSC... are intended for mounting in cold−plate design (e.g. on collective
coolers).
Requirements for collective coolers
The following requirements must be met to ensure a safe operation of the axis modules:
ƒ Good thermal contact with the cooler
– The contact surface between collective cooler and axis module must be at least as
large as the cooling plate of the axis module.
– Smooth contact surface, max. deviation 0.05 mm.
– Connect the collective cooler with all specified screwed connections to the axis
module.
Mechanical installation
Mounting in cold−plate design
4
ƒ Maintain the thermal resistance R
according to the table.
th
– The values apply for operating the axis modules under rated conditions.
Axis modulePower to be dissipatedHeat sink − environment
1. Prepare the fixing holes on the mounting plate.
– Use a drilling jig for this purpose.
ÀÁÂ
ECSXA030
2. Clean and degrease the contact area of collective cooler and heatsink of the
axis module (e.g. with methylated spirit).
3. Screw the support onto the collective cooler.
4. Insert the axis module from above into the support and fasten the two stud
bolts with 3.5 ... 4.5 Nm .
Note!
Penetration depth of the screws into the collective cooler: approx. 15 mm!
Tip!
The heat transfer resistance is reduced if − following step 2. −
ƒ a thin layer of heat conducting paste is applied to the contact surface or
ƒ heat conducting foil is used.
EDBCSXA064 EN 3.2
57
5
Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
5Electrical installation
5.1Installation according to EMC (installation of a CE−typical drive system)
General information
ƒ The electromagnetic compatibility of a machine depends on the type of installation
and care taken.Especially consider the following:
– Assembly
– Filtering
– Shielding
– Earthing
ƒ For diverging installations, the evaluation of the conformity to the EMC Directive
requires a check of the machine or system regarding the EMC limit values. This for
instance applies to:
– Use of unshielded cables
– Use of collective interference filters instead of the assigned RFI filters
– Operating without RFI filters
ƒ The compliance of the machine application with the EMC Directive is in the
responsibility of the user.
– If you observe the following measures, you can assume that the machine will
operate without any EMC problems caused by the drive system, and that
compliance with the EMC Directive and the EMC law is achieved.
– If devices which do not comply with the CE requirement concerning noise
immunity EN 61000−6−2 are operated close to the ECS modules, these devices may
be electromagnetically affected by the ECS modules.
58
EDBCSXA064 EN 3.2
Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
Assembly
ƒ Connect the ECS modules, RFI filters, and mains choke to the earthed mounting
plate with a surface as large as possible:
– Mounting plates with conductive surfaces (zinc−coated or stainless steel) allow for
permanent contact.
– Painted plates are not suitable for an EMC−compliant installation.
ƒ If you use the ECSxK... capacitor module:
– Install the capacitor module between the power supply module and the axis
module(s).
– If the total cable length in the DC−bus connection is > 5 m, install the capacitor
module as close as possible to the axis module with the greatest power.
ƒ If you use several mounting plates:
– Connect as much surface of the mounting plates as possible (e.g. with copper
bands).
ƒ Ensure the separation of the motor cable and the signal or mains cables.
5
ƒ Avoid a common terminal/power strip for the mains input and motor output.
ƒ Lay the cables as close as possible to the reference potential. Freely suspended
cables act like aerials.
Filters
Only use RFI filters and mains chokes which are assigned to the power supply modules:
ƒ RFI filters reduce impermissible high−frequency interferences to a permissible value.
ƒ Mains chokes reduce low−frequency interferences which in particular depend on the
motor cables and their lengths.
EDBCSXA064 EN 3.2
59
5
Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
Shielding
ƒ Connect the motor cable shield to the axis module
– with the ECSZS000X0B shield mounting kit.
– extensively to the mounting plate below the axis module.
– Recommendation: For the shield connection, use earthing clamps on bare metal
mounting surfaces.
ƒ If contactors, motor protection switches or terminals are located in the motor cable:
– Connect the shields of the connected cables to each other and connect them to the
mounting plate, too, with a surface as large as possible.
ƒ Connect the shield in the motor terminal box or on the motor housing extensively to
PE:
– Metal glands at the motor terminal box ensure an extensive connection of the
shield and the motor housing.
ƒ Shield UG cables and control cables from a length of 0.3 m:
– Connect both shields of the digital control cables.
– Connect one shield end of the analog control cables.
– Always connect the shields to the shield connection at the axis module over the
shortest possible distance.
ƒ Use of the ECS modules in residential areas:
– Additionally dampen the shield in orde r to lim it the interfering radiation: ³1 0 d B . This can be achieved
by using standard, closed, metallic, and earthed control cabinets or boxes.
Earthing
ƒ Earth all metallically conductive components (e.g. ECS modules, RFI filters, motor
filters, mains chokes) using suitable cables connected to a central earthing point (PE
rail).
ƒ Maintain the minimum cross−sections prescribed in the safety regulations:
– For EMC not the cable cross−section is important, but the surface of the cable and
the contact with a cross−section as large as possible, i.e. large surface.
60
EDBCSXA064 EN 3.2
5.2Power terminals
Electrical installation
Power terminals
5
Fig. 5−1Plug connectors for power terminals
Danger!
Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when the device is touched in the event of a fault.
Protective measures:
ƒ Implement the actions required in the EN 61800−5−1. Especially:
– Fixed installation
– PE connection must conform to standards (PE conductor diameter
³ 10 mm
2
or PE conductor must be connected twice)
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ Observe the maximally permissible mains voltage.
ƒ Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.
ECSXA080
EDBCSXA064 EN 3.2
61
5
Electrical installation
Power terminals
ƒ All power connections are plug connections and coded. The ECSZA000X0B plug
connector set must be ordered separately.
ƒ Installation of the cables to EN 60204−1.
ƒ The cables used must comply with the approvals required at the site of use (e.g. VDE,
UL, etc.).
Note!
ECSDA... axis modules:
For a better electromagnetic compatibility (EMC), connect the functional earth
conductor to the ECSDA... axis module ( 54).
This is not required for the ECSEA... (standard installation) and ECSCA... (cold
plate) axis modules!
Assignment of the plug connectors
Plug
connector/terminal
X23DC−bus voltage connection
X23/+UG
X23/+UG
X23/−UG
X23/−UG
X23/PE
X23/PE
X24Motor connection
X24/UMotor phase U
X24/V
X24/WMotor phase W
X24/PEEarth connection
cables twisted and as short as possible. Ensure short−circuit−proof
G
cables.
G
Cable length
(module/
module)
Up to 20 m
> 20 m
Wire end ferruleCable cross−section Tightening torqueStripping length
Without wire end
ferrule
With insulated wire end
ferrule
Without wire end
ferrule
With insulated wire end
ferrule
Use pin−end connectors
for wiring!
2
6 mm
(AWG 10)
10 mm
(AWG 8)
5 mm for screw
1.2 ... 1.5 Nm
(10.6 ... 13.3 lb−in)
2
connection
10 mm for spring
connection
64
EDBCSXA064 EN 3.2
Electrical installation
Power terminals
Connection to the DC bus (+U
Fuses
ƒ Mains fuses are not included in the Lenze delivery program. Use standard fuses.
ƒ When using ECSxE power supply modules which are fused on the supply side the
DC−bus supply need not be fused.
ƒ When ECS axis modules are supplied by devices of the 82xx and 93xx series with a
continuous DC current > 40 A, install the following fuses between the supplying
device and the ECS devices:
FuseSupport
Value [A]Lenze typeLenze type
50EFSGR0500ANINEFH20007
ƒ Observe the national and regional regulations (VDE, UL, EVU, ...).
, −UG)
G
Warnings!
ƒ Use UL−approved cables, fuses and fuse holders only.
ƒ UL fuse:
– Voltage 500 ... 600 V
– Tripping characteristic "H", "K5" or "CC"
5
Replacing defective fuses
Danger!
Hazardous electrical voltage
Components can carry hazardous voltages up to 3 minutes after power−off.
Possible consequences:
ƒ Death or severe injuries when touching the device.
Protective measures:
ƒ Replace fuses in the deenergised state only.
– Set controller inhibit (CINH) for all axis modules in DC−bus operation and
disconnect all power supply modules from the mains.
EDBCSXA064 EN 3.2
65
5
Electrical installation
Power terminals
Connection plan for mimimum wiring with internal brake resistor
5.2.2Connection plan for mimimum wiring with internal brake resistor
Documentation of the ECSxE power supply module
Observe the enclosed notes.
Stop!
Always operate the ECS power supply modules with a brake resistor
(internal/external).
The ECS power supply modules in the standard built−in unit and push−through design
(ECSEE / ECSDE) are provided with a device−internal brake resistor.
In order to use the internal brake resistor (Rb), carry out the following wiring:
ƒ Bridge between the terminals X22/+UG and X22/BR0 (CR)
Current flow from +UG via the internal brake resistor (Rb) and the brake transistor to
−UG.
ƒ Bridge between the terminals X6/T1 and X6/T2 (CR)
Deactivate the temperature monitoring of the non−existing external brake resistor.
66
EDBCSXA064 EN 3.2
Electrical installation
5
Power terminals
Connection plan for mimimum wiring with internal brake resistor
K1
L1
L2
L3
N
F4
Off
On
K1
K1
F1...F3
Z1
"
"
ECSEE...
ECSDE...
L1 L2
X6
T1
L3
PE
BR0
+UG
X21
...
T2
BR1
Rb
+UG
-UG
X22
PE
+UG
+UG
ECSxS/P/M/A...
X25
BD2
BD1
-UG
X23
-UG
UV
X24
PE
W
"
"
M
3~
J
+
Fig. 5−2Interconnected power system with internal brake resistor
HF−shield termination by large surface connection to functional earth (see mounting
K1Mains contactor
F1 ... F4 Fuse
Z1Mains choke / mains filter, optional
RbInternal brake resistor
JKTY thermal sensor of the motor
System cable for feedback
instructions for shield mounting ECSZS000X0B)
Twisted cables
PE
+UG
+UG
-UG
X23
-UG
PE
PE
ECSxS/P/M/A...
X7
PE
BD1
X25
BD2
UV
X24
W
0
"
"
2
"
"
6
R
M
3~
J
X7
PE
0
"
"
6
R
2
+
ECSXA011
EDBCSXA064 EN 3.2
67
5
Electrical installation
Power terminals
Connection plan for mimimum wiring with external brake resistor
5.2.3Connection plan for mimimum wiring with external brake resistor
Documentation of the ECSxE power supply module
Observe the enclosed notes.
Stop!
ƒ Always operate the ECS power supply modules with a brake resistor.
ƒ A parallel wiring of internal and external brake resistor is not permissible!
ƒ Implement the thermal contact of the brake resistor into the system
monitoring so that the mains supply of the power supply module will be
switched off in case the brake resistor will be overheated.
ƒ Read the documentation for the external brake resistor. Observe the safety
instructions contained therein.
If the power supply module needs a high amount of braking power when it comes as
standard built−in unit or in push−through technique design (ECSEE / ECSDE), an external
and more powerful brake resistor can be connected instead of the internal brake resistor.
A power supply module in cold plate technique design (ECSCE) is not provided with an
internal brake resistor so that this version always requires an external brake resistor
(Rbext).
ƒ Connect the brake resistor to X22/BR1 and X22/+UG.
ƒ Connect the thermal contact (NC contact) of the external brake resistor to X6/T1
and X6/T2.
68
EDBCSXA064 EN 3.2
Electrical installation
5
Power terminals
Connection plan for mimimum wiring with external brake resistor
K1
L1
L2
L3
N
F4
F1...F3
Z1
Rb
ext
J
"
Off
On
K1
K1
"
J
(Rb
L1 L2
X21
ECSxE...
X6
...
T1
T2
)
ext
L3
PE
BR0
+UG
BR1
+UG
-UG
X22
PE
+UG
+UG
-UG
X23
-UG
PE
ECSxS/P/M/A...
BD2
UV
X24
PE
W
BD1
X25
"
"
M
3~
J
+
Fig. 5−3Interconnected power system with external brake resistor
HF−shield termination by large surface connection to functional earth (see mounting
K1Mains contactor
F1 ... F4 Fuse
Z1Mains choke / mains filter, optional
Rb
JKTY thermal sensor of the motor
System cable for feedback
instructions for shield mounting ECSZS000X0B)
Twisted cables
External brake resistor
ext
PE
+UG
+UG
-UG
X23
-UG
PE
PE
ECSxS/P/M/A...
2
"
"
X7
BD1
X25
BD2
UV
X24
W
0
"
"
6
R
M
3~
J
X7
PE
0
"
"
6
R
2
+
ECSXA012
EDBCSXA064 EN 3.2
69
5
Electrical installation
Power terminals
Motor connection
5.2.4Motor connection
Fig. 5−4Motor and motor holding brake connection
Motor cables
ƒ Use low−capacitance motor cables. Capacitance per unit length:
ƒ The cross−section of the motor cables are selected according to the motor standstill
current (I
) for asynchronous motors.
(I
N
ƒ Length of the unshielded ends: 40 ... 100 mm (depending on the cable cross−section)
ƒ Lenze system cables meet these requirements.
ƒ Use the ECSZS000X0B shield mounting kit for EMC−compliant wiring.
) when using synchronous motors or according to the rated motor current
0
Mounting instructions for ECSZS000X0B shield mounting
Here you can find more information on wiring according to EMC.
70
EDBCSXA064 EN 3.2
5.2.5Motor holding brake connection
The motor holding brake
ƒ is connected to X25/BD1 and X25/BD2.
ƒ is supplied with low voltage via the terminals X6/B+ and X6/B−:
+23 ... +30 V DC, max.1.5 A
Stop!
ƒ Protect X6/B+ with an F 1.6 A fuse.
ƒ If no suitable voltage (incorrect amount, incorrect polarity) is connected to
the brake, it is applied and can overheat or be destroyed by the continuously
running motor.
5.2.5.1Spark suppressor
The axis module comes with an integrated spark suppressor for protecting the contacts of
the integrated brake relay when the motor holding brake (inductive load) is switched.
Electrical installation
Power terminals
Motor holding brake connection
5
5.2.5.2Monitoring the brake connection
The connection of the motor holding brake can be monitored for voltage failure and cable
breakage if monitoring is activated under C0602.
The monitoring system of the brake connection trips under the following conditions:
Case 1, motor holding brake released (brake relay contact is closed):
ƒ Current via holding brake (I
ƒ Voltage at X6/B+ and X6/B− (V
Case 2, motor holding brake closed (brake relay contact is open):
ƒ Voltage at X6/B+ and X6/B− (V
B
) < 140 mA +/−10 % or
) < +4 V +/−10 %
B
) < +4 V +/−10 %
B
EDBCSXA064 EN 3.2
71
5
Electrical installation
Power terminals
Motor holding brake connection
5.2.5.3Requirements on the brake cables
ƒ Use a Lenze system cable with integrated brake cable.
– The shielding of the brake cable must be separated.
ƒ Length: max. 50 m
ƒ If a separately installed brake cable is required, lay it in a shielded manner.
Note!
Due to the monitoring circuit of the brake connection, an additional constant
voltage drop of 1.5 V is produced. The voltage drop can be compensated by a
higher voltage at the cable entry.
The voltage required at X6/B+ and X6/B− for the Lenze system cables is calculated as
follows:
V
ƪ
UK[V] + UB[V] ) 0.08
ƫ
@ LL[m] @ IB[A] ) 1.5[V]
m @ A
V
Voltage required at 6X/B+ and X6/B− [V]
comp
V
Rated operating voltage of the brake [V]
B
L
Length of the brake cable [m]
L
Brake current [A]
I
B
1.5 A
B+
X6
F 1.6 A
+23 ... +30 V DC
max. 1.5 A
B-
_
+
X25
"
"
BD2
BD1
_
+
M
3~
+
Fig. 5−5Connection of the motor holding brake to X25
HF−shield termination by large−surface connection to functional earth (see Mounting
Instructions for ECSZS000X0B shield mounting kit)
ECSXA017
72
EDBCSXA064 EN 3.2
Electrical installation
Power terminals
Connection of an ECSxK... capacitor module (optional)
5
5.2.6Connection of an ECSxK... capacitor module (optional)
The ECS capacitor modules support the DC−bus voltage for the drive system. These
capacitor module types are available:
Contactor relay
System cable ˘ feedback
Terminal X6/SI1 of the connected axis modules (controller enable/inhibit)
-UG
-UG
+UG
PE
+UG
+UG
-UG
X23
-UG
PE
PE
ECSxK...
X26
+UG
X23
ECSxS/P/M/A...
X25
BD2
BD1
"
"
2
UV
M
3~
+
X24
PE
PE
X7
PE
W
1
"
"
6
J
R
2
ECSXX004
EDBCSXA064 EN 3.2
73
5
5.3Control terminals
Electrical installation
Control terminals
Fig. 5−7Plug connectors for control terminals (X6)
ECSXA070
For the supply of the control electronics an external 24 V DC voltage at terminals X6/+24
and X6/GND is required.
Stop!
ƒ The control cables must always be shielded to prevent interference
injections.
ƒ The voltage difference between X6/AG, X6/GND and PE of the axis module
may maximally amount to 50 V.
ƒ The voltage difference can be limited by:
– overvoltage−limiting components or
– direct connection of X6/AG and X6/GND to PE.
ƒ The wiring has to ensure that for X6/DO1 = 0 (LOW level) the connected axis
modules do not draw energy from the DC bus. Otherwise, the power supply
module may be damaged.
74
EDBCSXA064 EN 3.2
Electrical installation
Control terminals
Shield connection of control cables and signal cables
The plate on the front of the device serves as the mounting place (two threaded holes M4)
for the shield connection of the signal cables. The screws used may extend into the inside
of the device by up to 10 mm. For optimum contact of the shield connection, use the wire
clamps from the ECSZS000X0B shield mounting kit.
+UG
L1 L2
X21
L3
PE
BR0
BR1
X22
+UG
-UG
PE
+UG
+UG
X23
-UG-UG
PEPE
5
"
"
0
T1
T2
ECSxE...
X6
DI1
DI2
DO1
D24
+24V
GND
1
+24 VDC
GND
ECSxS/P/M/A...
DI1
DI2
DO1
AI+
DI3
DI4
"
"
24 VDC
X6
AI-
AG
+24V
GND
SI1
SO
S24
"
"
-
=
+
+
=
-
4
Fig. 5−8Interconnection: Control signals with internal brake resistor
HF−shield termination by large surface connection to functional earth (see mounting
/ Contactor relay
Voltage supply of motor holding brake 23 ... 30 V DC, max. 1.5 A
Safe torque off (formerly: "Safe standstill")
Controller enable/inhibit
instructions for shield mounting ECSZS000X0B)
B-
B+
SI2
"
F 1,6 A
U
2
3
ECSXA013
EDBCSXA064 EN 3.2
75
5
Electrical installation
Control terminals
Switch−on sequence for the auxiliary relay
Stop!
Overload of the charging connection in the power supply module
The controller enable for the axes may only take place when the charging
process of the DC bus is completed and the power supply module is ready for
operation.
Possible consequences:
ƒ Destruction of the power supply module
Protective measures:
ƒ Use of switching the central controller enable for the axes via the inputs and
outputs DI2 and DO1 of the power supply module (see the following
descriptions).
The switch−on sequence of the auxiliary relay (see Fig. 5−8) is as follows:
1. The digital input X6/DI1 (power supply enable) of the power supply module is
switched to HIGH by the higher−level control or by the operator.
– The DC bus is charged.
2. The ready for operation output of the axis module (DO1) now switches the X6/DI2
digital input (central controller enable) of the power supply module via the relay .
– In the default Lenze setting of the ECS axis modules, DO1 is set to "ready". "Ready"
is only present if a specified DC−bus voltage has been reached.
3. The central controller enable for the axis module takes place via the X6/DO1 output
of the power supply module. The central controller enable DO1 only switches if the
charging process of the DC bus is completed AND the X6/DI2 input is set.
76
EDBCSXA064 EN 3.2
Electrical installation
Control terminals
Assignment of the plug connectors
Plug connector X6
TerminalFunctionElectrical data
X6/+24Low−voltage supply of the control electronics
X6/GNDReference potential of low−voltage supply
X6/DO1Digital output 124 V DC, 0.7 A (max. 1.4 A)
X6/DI1Digital input 1
X6/DI2Digital input 2
X6/DI3Digital input 3
X6/DI4Digital input 4
X6/AI+Analog input +
X6/AI−Analog input −
X6/AGReference potential of analog input (internal
X6/B+Brake supply +
X6/B−Brake supply −
X6/S24
X6/SO
X6/SI1
X6/SI2
ground)
Connection of "safe torque off" (formerly "safe
standstill")
20 ... 30 V DC, 0. A (max. 1 A)
for starting current of 24 V:
max. 2 A for 50 ms
short−circuit−proof
LOW:
−3 ... +5 V;
−3 ... +1.5 mA
HIGH:
+15 ... +30 V;
+2 ... +15 mA
Input current at 24 V DC:
8 mA per input
Adjustable with jumper strip X3:
−10 ... +10 V, max. 2 mA
−20 ... +20 mA
Resolution: 11 bits + sign
23 ... 30 V DC
max. 1.5 A
Set brake voltage so that the permissible
voltage at the brake is not under−run or
exceeded ˘ otherwise malfunction or
destruction!
80
5
Cable cross−sections and screw−tightening torques
Cable typeWire end ferruleCable cross−sectionTightening torqueStripping length
Flexible
Without wire end
ferrule
With insulated wire
end ferrule
0.08 ... 1.5 mm
(AWG 28 ... 16)
0.25 ... 0.5 mm
(AWG 22 ... 20)
2
0.22 ... 0.25 Nm
2
(1.95 ... 2.2 lb−in)
5 mm for screw
connection
9 mm for spring
connection
We recommend to use control cables with a cable cross−section of 0.25 mm2.
EDBCSXA064 EN 3.2
77
5
Electrical installation
Control terminals
Digital inputs and outputs
5.3.1Digital inputs and outputs
Stop!
If an inductive load is connected to X6/DO1, a spark suppressor with a limiting
function to max. 50 V ± 0 % must be provided.
GNDext
47k
1k
3k3
3k3
3k3
3k3
1.5 A
X6
DI1
DI2
DI3
DI4
GND
DO1
+24
"
"
_
=
24 VDC
+
Fig. 5−9Digital inputs and outputs at X6
HF−shield termination by large−surface connection to functional earth (see Mounting
ƒ The digital inputs X6/DI1 ... DI4 are freely assignable.
ƒ The polarity of the digital inputs X6/DI1 ... DI4 is set under C0114/x.
ƒ The polarity of the digital output (X6/DO1) is set under C0118/1.
Instructions for ECSZS000X0B shield mounting kit)
ECSXA014
78
EDBCSXA064 EN 3.2
Electrical installation
Control terminals
Analog input
5
5.3.2Analog input
82k5
X3
5
3.3 nF
=
AI-
X6
"
"
Fig. 5−10Analog input at X6
HF−shield termination by large−surface connection to functional earth (see Mounting
Analog input configuration
ƒ Use C0034 to set whether the input is to be used for a master voltage (±10 V) or a
master current (+4 ... 20 mA or ±20 mA).
6
82k5
250R
GND
3.3 nF
=
AI+
AG
Instructions for ECSZS000X0B shield mounting kit)
ECSXA015
ƒ Set jumper bar X3 according to the setting in C0034:
Stop!
Do not plug the jumper on the pins 3−4! The axis module cannot be initialised
like this.
Jumper bar X3SettingMeasuring range
5
3
1
5
3
1
6
4
Jumper on 1−2: Parking position
5−6 open
2
6
4
5−6 closed
2
C0034 = 0 (master voltage)
l Level: −10 ... +10 V
l Resolution: 5 mV (11 bits + sign)
l Scaling: ±10 V º ±16384 º ±100 %
C0034 = 1 (master current)
l Level: +4 ... +20 mA
l Resolution: 20 mA (10 bits without sign)
l Scaling:
+4 mA º 0 º 0 %
+20 mA º 16384 º 100 %
C0034 = 2 (master current)
l Level: −20 ... +20 mA
l Resolution: 20 mA (10 bits + sign)
l Scaling: ±20 mA º ±16384 º ±100 %
EDBCSXA064 EN 3.2
79
5
Electrical installation
Control terminals
Safe torque off
5.3.3Safe torque off
The axis modules support the "safe torque off" safety function (formerly "safe standstill"),
"protection against unexpected start−up", in accordance with the requirements of
EN ISO 13849−1, Performance Level Pld. For this purpose, the axis modules are equipped
with two independent safety paths. The Performance Level Pld is obtained if the output
signal is additionally checked with regard to correctness at X6/SO.
5.3.3.1Implementation
In the axis module, the "safe torque off" connection is implemented with optocouplers.
The optocouplers isolate the following areas electrically from each other:
Fig. 5−11Implementation of the "safe torque off" function
Area 1:Inputs and outputs
Area 2:Circuit for the internal control
Area 3:Power output stage
>1
&
&
&
&
&
&
Stop!
Use insulated wire end ferrules when wiring the "safe torque off" circuits to
X6.
X2
U
V
W
ECSXA100
80
EDBCSXA064 EN 3.2
5.3.3.2Functional description
The "safe torque off" state can be initiated any time via the input terminals X6/SI1
(controller enable/inhibit) and X6/SI2 (pulse enable/inhibit). For this purpose a LOW level
has to be applied at both terminals:
ƒ X6/SI1 = LOW (controller inhibited):
The inverter is inhibited via the microcontroller system.
ƒ X6/SI2 = LOW (pulses inhibited):
The supply voltage for the optocouplers of the power section driver is switched off,
i. e. the inverter can no longer be enabled and controlled via the microcontroller
system.
The input signal at X6/SI2 to the hardware is additionally directed to the
microcontroller system and is evaluated for the state control there. For the external
further processing a HIGH level is output for the state "safe torque off active" at the
digital output X6/SO.
The control of the inverter thus is prevented by two different methods that are
independent of each other. Therefore an unexpected start−up by the motor is avoided.
Electrical installation
Control terminals
Safe torque off
5
EDBCSXA064 EN 3.2
81
5
5.3.3.3Important notes
Electrical installation
Control terminals
Safe torque off
Danger!
When using the "safe torque off" function, additional measures are required
for "emergency stops"!
There is neither an electrical isolation between motor and axis module nor a
"service" or "repair switch".
Possible consequences:
ƒ Death or severe injuries
ƒ Destruction or damage of the machine/drive
Protective measures:
An "emergency stop" requires the electrical isolation of the motor cable, e.g.
by means of a central mains contactor with emergency stop wiring.
Installation/commissioning
ƒ The "safe torque off" function must only be installed and commissioned by qualified
personnel.
ƒ All control components (switches, relays, PLC, ...) and the control cabinet must meet
the requirements of EN ISO 13849. These include for instance:
– Switches, relays in enclosure IP54.
– Control cabinet in enclosure IP54.
– All other requirements can be found in EN ISO 13849.
ƒ Wiring with insulated wire end ferrules is essential.
ƒ All safety−relevant cables (e.g. control cable for the safety relay, feedback contact)
outside the control cabinet must be protected, e.g. in the cable duct. It must be
ensured that short circuits between the individual cables cannot occur. For further
measures, see EN ISO 13849.
ƒ If force effects from outside (e.g. sagging of hanging loads) are to be expected when
the "safe torque off" function is active, additional measures have to be taken (e.g.
mechanical brakes).
During operation
ƒ After installation, the operator must check the "safe torque off" function.
ƒ The function check must be repeated at regular intervals, but no later than after one
year.
82
EDBCSXA064 EN 3.2
5.3.3.4Technical data
Terminal assignment
Plug connector X6
Terminal FunctionLevelElectrical data
X6/S24Low−voltage supply18 ... 30 V DC
X6/SO"Safe torque off" feedback
output
X6/SI1Input 1 (controller
enable/inhibit)
X6/SI2Input 2 (pulse enable/inhibit)
Electrical installation
Control terminals
Safe torque off
LOWDuring operation
HIGH"Safe torque off" active
LOWController inhibited
HIGHController enabled
LOWPulses for power section are
inhibited
HIGHPulses for power section are
enabled
5
0.7 A
24 V DC
0.7 A (max. 1.4 A)
Short−circuit−proof
LOW level:
−3 ... +5 V
−3 ... +1.5 mA
HIGH level:
+15 ... +30 V
+2 ... +15 mA
Input current at 24 V DC:
8 mA per input
Cable cross−sections and screw−tightening torques
Cable typeWire end ferruleCable cross−sectionStarting torqueStripping length
5 mm for screw
connections
9 mm for spring
connections
Flexible
With insulated wire
end ferrule
Without wire end
ferrule
0.25 ... 1.5 mm
(AWG 22 ... 16)
Not permitted when the "Safe torque off" function is used
2
0.22 ... 0.25 Nm
(1.95 ... 2.2 lb−in)
EDBCSXA064 EN 3.2
83
5
Electrical installation
Control terminals
Safe torque off
5.3.3.5Function check
ƒ After installation the operator must check the "safe torque off" function.
ƒ The function check must be repeated at regular intervals, after one year at the
latest.
Stop!
If the function check leads to impermissible states at the terminals,
commissioning cannot take place!
Test specifications
ƒ Check the circuitry with regard to correct function.
ƒ Check directly at the terminals whether the "safe torque off" function operates
faultlessly in the axis module:
States of the "safe torque off" function on the axis module
Level at input terminal
X6/SI1X6/SI2X6/SOX6/SO
LOWLOWHIGHLOW
LOWHIGHLOW
HIGHLOWLOW
HIGHHIGHLOW
Resulting level at
output terminal
Impermissible level at
output terminal
HIGH
84
EDBCSXA064 EN 3.2
Electrical installation
Control terminals
Safe torque off
5.3.3.6Example: Wiring with electronic safety switching device "Pilz PNOZ e1vp" for
Performance Level Pl
ƒ The motor is shut down in accordance with stop category 1 of EN 60204 when the
safety function is requested.
ƒ The delay time of the safety switching device and the quick stop deceleration time
have to be coordinated with the brake closing time.
ƒ The diode−capacitor combination prevents the test pulses of the safety switching
device from disturbing the smooth running of the motor, as otherwise a short−time
inhibit of the controller cannot be ruled out. The diode−capacitor combination can be
procured from the company Pilz (Pilz order number: 774195) as a complete terminal
block.
EDBCSXA064 EN 3.2
85
5
Electrical installation
Control terminals
Safe torque off
Description of the function
ƒ The "PNOZ" safety switching device has a two−channel effect on the controller. In
the case of an emergency stop request the two channels (terminals 14 and 24)
become deenergised. The safety switching device monitors the diagnostic output of
the controller.
ƒ The safety switching device is provided with test pulses at the output side, so that
short circuits within the wiring are detected.
ƒ Diagnostics is effected via the wiring of diagnostic output SO to input Y7 of the
safety switching device. Y7 is the input of the feedback loop which has to be on
HIGH level (+24 V) before the outputs 14 and 24 are activated. There is only HIGH
level if both disconnecting paths have switched off.
ƒ At least once a year a manual test has to be carried out to verify the independence
and cutout ability of the two disconnecting paths.
Manual test of the disconnecting paths
ƒ The disconnecting paths have to be checked individually in succession.
ƒ When any test key (T1, T2) is pressed the motor has to become torqueless
immediately. Additionally the brake has to be applied, since the supply of the brake
is switched off via contact X6/B+.
ƒ When the safety switching device is switched off, or if both pushbuttons are pressed
at the same time, the STO state has to be signalled via the indicator light H1. In all
other states this message has to be inactive.
If a deviation from the response described above is determined, the controller must be
switched off immediately. Eliminate the fault before restarting the controller.
For obtaining a Performance Level PL
requirements for PL
62061 are to be used in all upstream applications!
in accordance with EN ISO 13849−1 or SIL 2 in accordance with EN
d
(SIL 2), only components which also comply with the
d
Interconnection examples can be found in the download area (Application
Knowledge Base) at:
www.Lenze.com
86
EDBCSXA064 EN 3.2
Electrical installation
Control terminals
Safe torque off
5.3.3.7Example: Wiring with electromechanical safety switching device "Siemens 3TK2827"
for Performance Level Pl
Not-Halt/ Emergency stop
d
5
Y21
Y10
24V DC
A1
13
23
47
A2
Fig. 5−13Example: Wiring with "Siemens 3TK2827" safety switching device
Y11
Siemens 3TK2827
T1 Test key 1
T2 Test key 2
Y22
Y12
14
24
48
5857
Y33
Y34
T1T2
Start
H1
ECSxS/P/M/A
X6
QSP
DI1
SI1
SI2
S24
S0
GND
B+
B-
X25
BD2
BD1
ECSXA035
ƒ The motor is shut down in accordance with stop category 1 of EN 60204 when the
safety function is requested.
ƒ The delay time of the safety switching device and the quick stop deceleration time
have to be coordinated with the brake closing time.
Description of the function
ƒ The "Siemens 3TK2827" safety switching device has a two−channel effect on the
controller. In the case of an emergency stop request the two channels (terminals 48
and 58) become deenergised. The safety switching device monitors the diagnostic
output of the controller.
ƒ If the "safe torque off" safety function is activated, output X6/SO is at HIGH level.
This state is shown to the operator by means of the indicator light H1. Afterwards
switch−on is possible again using the Start pushbutton.
ƒ At least once a year a manual test has to be carried out to verify the independence
and cutout ability of the two disconnecting paths.
EDBCSXA064 EN 3.2
87
5
Electrical installation
Control terminals
Safe torque off
Manual test of the disconnecting paths
ƒ The disconnecting paths have to be checked individually in succession.
ƒ When any test key (T1, T2) is pressed the motor has to become torqueless
immediately. Additionally the brake has to be applied, since the supply of the brake
is switched off via contact X6/B+.
ƒ When the safety switching device is switched off, or if both pushbuttons are pressed
at the same time, the STO state has to be signalled via the indicator light H1. In all
other states this message has to be inactive.
If a deviation from the response described above is determined, the controller must be
switched off immediately. Eliminate the fault before restarting the controller.
For obtaining a Performance Level PL
requirements for PL
62061 are to be used in all upstream applications!
in accordance with EN ISO 13849−1 or SIL 2 in accordance with EN
d
(SIL 2), only components which also comply with the
d
Interconnection examples can be found in the download area (Application
Knowledge Base) at:
www.Lenze.com
88
EDBCSXA064 EN 3.2
5.4Automation interface (AIF)
The keypad XT or a communication module can be attached to or removed from the
automation interface (X1). This is also possible during operation.
ƒ The keypad XT serves to enter and visualise parameters and codes.
ƒ The communication modules serve to network the modules of the ECS servo system
with the host system (PLC or PC).
The following combinations are possible:
Electrical installation
Automation interface (AIF)
5
Operating/communication moduleType/order number
Keypad XTEMZ9371BCüü
Diagnosis terminal (keypad XT with hand−held)E82ZBBXCüü
LECOM−A (RS232)EMF2102IB−V004üü
LECOM−B (RS485)EMF2102IB−V002üü
LECOM−A/B (RS232/485)EMF2102IB−V001üü
LECOM−LI (optical fibre)EMF2102IB−V003üü
LONEMF2141IB˘ü
INTERBUSEMF2113IB˘ü
PROFIBUS−DPEMF2133IB˘ü
CANopenEMF2178IB˘ü
DeviceNetEMF2179IB˘ü
EtherCATEMF2192IBüü
Can be used together with
ECSxEECSxS/P/M/A
Further information ....
on wiring and application of communication modules can be found in the
corresponding Mounting Instructions and Communication Manuals.
EDBCSXA064 EN 3.2
89
5
Electrical installation
Wiring of system bus (CAN)
5.5Wiring of system bus (CAN)
Note!
System bus (CAN)
The ECSxA...axis module can communicate with a higher−level host system
(PLC) or further controllers via both CAN interfaces (X4 or X14).
MotionBus (CAN)
The "MotionBus (CAN)" term expresses the functionality of the CAN interface
X4 in case of ECSxS/P/M... axis modules, where communication takes place
using a higher−level host system (PLC) or further controllers exclusively via the
X4 interface. Interface X14 (CAN−AUX) is exclusively used for parameter setting
and diagnostics.
Basic wiring of the CAN bus networks
The two following schematic diagrams show drive systems with different master value
concepts:
ƒ In Fig. 5−14 a higher−level control assumes the function of the master, e.g. ETC.
ƒ In Fig. 5−15 the function of the master is enabled by a controller intended as master.
In both representations, the master value transmission is effected via the
MotionBus(CAN), interface X4.
The system bus (CAN), interface X14, serves to diagnose and/or parameterise the drives.
M
X4X14X14X14X4X4
PC
HMI
MB
SB
SSS
ECS_COB006
Fig. 5−14MotionBus (CAN) with master control
PC
X4X14X14X14X4X4
HMI
MB
SB
90
M
Fig. 5−15MotionBus (CAN) with controller as master
MBMotionBus (CAN), interface X4
SBSystem bus (CAN), interface X14
MMaster
SSlave
PCPC with the Lenze parameter setting and operating software (GDC, GDL, GDO)
HMIHMI / operating unit
SS
ECS_COB007
EDBCSXA064 EN 3.2
Fig. 5−16Bus connections on the controller
Assignment of the plug connectors
Electrical installation
Wiring of system bus (CAN)
5
ECS_COB003
X4 (CAN)X14 (CAN−AUX)Description
CHCAHCAN−HIGH
CLCALCAN−LOW
CGCAGReference potential
Specification of the transmission cable
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable typePaired with shielding
Impedance120 W (95 ... 140 W)
Fig. 5−17Example: System bus (CAN) wiring via interface X4
ECSECS axis module
MMaster control, e.g. ETC
Note!
Connect one bus terminating resistor (120 W) each to the first and last node of
the system bus (CAN).
92
EDBCSXA064 EN 3.2
Electrical installation
Wiring of system bus (CAN)
Bus cable length
Note!
The permissible cable lengths must be observed.
1. Check the compliance with the total cable length in Tab. 5−1.
The baud rate determines the total cable length.
CAN baud rate [kbit/s] Max. bus length [m]
501500
125630
250290
500120
100025
Tab. 5−1Total cable length
5
2. Check the compliance with the segment cable length in Tab. 5−2.
The segment cable length is determined by the cable cross−section used and the number
of nodes. Without a repeater, the segment cable length corresponds to the total cable
length.
Number of nodes
2240 m430 m650 m940 m
5230 m420 m640 m920 m
10230 m410 m620 m900 m
20210 m390 m580 m850 m
32200 m360 m550 m800 m
63170 m310 m470 m690 m
Tab. 5−2Segment cable length
Cable cross−section
0.25 mm
2
0.5 mm
2
0.75 mm
2
1.0 mm
2
3. Compare the two values detected.
If the value detected from Tab. 5−2 is smaller than the total cable length to be provided
from Tab. 5−1 , repeaters must be used. Repeaters divide the total cable length into
segments.
EDBCSXA064 EN 3.2
93
5
Electrical installation
Wiring of system bus (CAN)
Example: Selection help
Specifications
2
l Cable cross−section:0.5 mm
l Number of nodes:63
l Repeater:Lenze−repeater, type 2176 (cable reduction: 30 m)
(according to cable specifications 91)
For the max. number of nodes (63), the following cable lengths / number of repeaters from
the specifications must be observed:
Baud rate [kbit/s]501202505001000
Max. cable length [m]150063029012025
Segment cable length [m]31031029012025
Number of repeaters52−−−
Check repeater application
Given:
l Baud rate:125 kbps
l Cable cross−section:0.5 mm
l Number of nodes:28
l Cable length:450 m
2
ProcedureCable lengthSee
1. Total cable length at 125 kbps:630 mTab. 5−1
2. Segment cable length for 28 bus nodes and a cable cross−section of
3. Comparison: The value under point 2 is smaller than the required cable length of 450 m.
Conclusion
l It is not possible to use a cable length of 450 m without using a repeater.
l After 360 m (point 2) a repeater must be installed.
Result
l The Lenze repeater type 2176 is used (cable reduction: 30 m)
l Calculation of the maximum cable length:
à Maximum possible cable length with repeater: 690 m.
à Now it is possible to use the required cable length.
2
0.5 mm
First segment: 360 m
Second segment: 360 m (according to Tab. 5−1) minus 30 m (cable reduction when a repeater is used)
:
360 mTab. 5−2
Note!
Repeaters are recommended as a
ƒ Service interface
Advantage: Trouble−free connecting during bus operation is possible.
ƒ Calibration interface
Advantage: Calibration/programming unit remains electrically isolated.
94
EDBCSXA064 EN 3.2
5.6Wiring of the feedback system
You can connect various feedback systems to the axis module:
ƒ Resolver on X7 ( 96)
ƒ Encoder on X8 ( 97)
– Incremental encoder with 5V−TTL level, RS−422
– SinCos encoder with zero track without Hiperface, signal level 1 Vss
– SinCos absolute value encoder (single−turn/multi−turn) with serial communication
(Hiperface® interface), supply voltage 5 ... 8 V
Note!
If a "safe isolation" acc. to EN 61140 between the encoder cable and motor
cable (e.g. by using separating webs or separated trailing cables) is not ensured
on the entire cable length cable due to an installation on the system side, the
encoder cable must be provided with an insulation resistance of 300 V. Lenze
encoder cables meet this requirement.
ƒ We recommend to use Lenze encoder cables for wiring.
ƒ In case of self−prepared cables
– only use cables with shielded cores twisted in pairs.
– Observe the notes on wiring/preparation on the following pages.
Electrical installation
Wiring of the feedback system
5
EDBCSXA064 EN 3.2
95
5
Electrical installation
Wiring of the feedback system
Resolver connection
5.6.1Resolver connection
Note!
ƒ Use the prefabricated Lenze system cables for the connection of a resolver.
ƒ Cable length: max. 50 m
ƒ Depending on the cable length and resolver used parameterise the code
C0416 (resolver excitation amplitude).
Check the resolver control with code C0414 (recommended values: 0.5 ...
1.2; ideal value: 1.0).
ƒ Before using a resolver from another manufacturer, please consult Lenze.
Connect a resolver via the 9−pole Sub−D socket X7.
Features
ƒ Resolver: U = 10 V, f = 4 kHz
ƒ Resolver and resolver supply cable are monitored for open circuit (fault
message "Sd2").
KTY
Fig. 5−18Resolver connection
+REF
-REF
+COS
-COS
+SIN
-SIN
R1 (+KTY)
R2 (-KTY)
X7
Æ
mm2AWG
1
2
3
4
5
6
7
8
9
0.5
0.14
20
26
X7
1
5
6
9
ECSXA022
96
Assignment of socket connector X7: Sub−D 9−pole
Pin1
23456789
Signal+Ref−RefGND+COS−COS+SIN−SINR1
(+KTY)R2(−KTY)
0.5 mm
(AWG 20)
2
˘
0.14 mm
(AWG 26)
2
EDBCSXA064 EN 3.2
Electrical installation
Wiring of the feedback system
Encoder connection
5
5.6.2Encoder connection
Danger!
Valid when using an operating software up to and including V7.0:
When absolute value encoders are used, uncontrolled movements of the drive
are possible!
If an absolute value encoder is disconnected from the axis module during
operation, the fault OH3−TRIP occurs. If the absolute value encoder now is
connected to X8 again and a TRIP−RESET is carried out, the drive may start up in
an uncontrolled manner with a high speed and a high torque. A SD8−TRIP will
not occur, as would be expected.
Possible consequences:
ƒ Death or severe injuries
ƒ Destruction or damage of the machine/drive
Protective measures:
ƒ If a fault (trip) occurs during commissioning when an absolute value
encoder is used, check the history buffer C0168. If an Sd8−TRIP is at the
second or third place, a reinitialisation is absolutely necessary
purpose, switch off and on again the 24−V supply of the control electronics.
. For this
Via the 9−pole Sub−D−plug X8, you can connect the following encoders:
ƒ Incremental encoder (TTL encoder)
– with two 5 V complementary signals (RS−422) that are electrically shifted by 90°.
– with zero track that can be connected optionally.
ƒ Sin/cos encoder (singleturn or multiturn rotary transducer)
– with supply voltage (5 ... 8 V).
– with serial communication.
The initialisation time of the axis module is extended to approx. 2 s.
The controller supplies the encoder with voltage.
Use C0421 to set the supply voltage V
drop [DV] on the encoder cable:
DU ^ 2 @ L
DVVoltage drop on the encoder cable [V]
L
L
R/mOhmic resistance per meter of cable length [W/m]
I
G
[m] @ Rńm[Wńm] @ IG[A]
L
Cable length [m]
Encoder current [A]
(5 ... 8 V) to compensate, if required, the voltage
CC
Stop!
Observe the permissible supply voltage of the encoder used. If the values in
C0421 are set too high, the encoder can be destroyed!
EDBCSXA064 EN 3.2
97
5
Electrical installation
Wiring of the feedback system
Encoder connection
Incremental encoder (TTL encoder)
Features
Input/output frequency:0 ... 200 kHz
Current consumption:6 mA per channel
Current on output VCC (X8/pin 4):Max. 200 mA
KTY
<50m
R1 (+KTY)
R2 (-KTY)
GND
B
B
A
A
V
CC
Z
Z
5
X8
1
2
3
4
5
6
7
8
9
9
6
1
A
A
B
B
Z
Z
Fig. 5−19Connection of incremental encoder with TTL level (RS−422)
Signals in case of clockwise rotation
Cores twisted in pairs
Assignment of plug connector X8: Sub−D 9−pole
Pin123456789
SignalBAAV
0.14 mm
2
(AWG 26)
CC
(R1/+KTY)
2
1 mm
(AWG 18)
GND
ZZR2
(−KTY)
0.14 mm
2
(AWG 26)
ECSXA026
B
98
EDBCSXA064 EN 3.2
Electrical installation
Wiring of the feedback system
Encoder connection
SinCos encoders and SinCos absolute value encoders with Hiperface
Features
Input/output frequency:0 ... 200 kHz
Internal resistance (Ri):221 W
Offset voltage for signals SIN, COS, Z:2.5 V
ƒ The differential voltage between signal track and reference track must not exceed
1 V ± 10 %.
ƒ The connection is open−circuit monitored (fault message "Sd8")
ƒ For encoders with tracks sine, sine and cosine, cosine:
– Assign RefSIN with sine
– Assign RefCOS with cosine
ƒ For SinCos absolute value encoders with Hiperface, the serial interface (RS 485) is
available instead of the zero track (Z track).
.
.
5
KTY
<50m
RefCOS
R1 (+KTY)
R2 (-KTY)
RefSIN
SIN
COS
GND
V
CC
Z
Z
5
X8
1
2
3
4
5
6
7
8
9
9
6
1
SIN
2.5 V
COS
2.5 V
0.5V
0 V
0 V
0.5 V
RefSIN
RefCOS
Fig. 5−20Connection of SinCos encoder
Signals in case of clockwise rotation
Cores twisted in pairs
Assignment of plug connector X8: Sub−D 9−pole
Pin123456789
SignalSINRefCOS
(cos
0.14 mm
(AWG 26)
)
2
COSV
CC
1 mm
(AWG 18)
GND
(R2/−KTY)
2
Z or
−RS458
Z or
+RS485
0.14 mm
(AWG 26)
R1
(+KTY)
2
RefSIN
ECSXA023
(sin
)
EDBCSXA064 EN 3.2
99
5
Electrical installation
Wiring of the feedback system
Digital frequency input/output (encoder simulation)
5.6.3Digital frequency input/output (encoder simulation)
The digital frequency coupling of ECSxS/P/A axis modules basically is effected as a
master−slave connection via the interface X8. This interface can either be used as a digital
frequency input or as a digital frequency output (e. g. for encoder simulation)
(configuration via C0491).
Features
X8 as digital frequency inputX8 as digital frequency output
l Input frequency: 0 ... 200 kHz
l Current consumption: max. 6 mA per channel
l Two−track with inverse 5 V signals and zero track
l Possible input signals:
– incremental encoder with two 5 V complementary
signals (TTL encoders) offset by 90°
l The function of the inputs signals can be set via
l Output frequency: 0 ... 200 kHz
l Permissible current loading: max. 20 mA per
channel
l Two−track with inverse 5 V signals (RS422)
l The function of the output signals can be set via
C0540.
C0427.
Wiring
ƒ 1 slave on the master:
Wire master and slave to each other directly via interface X8.
<50m
X8
(ECS-Master)
B
1
2
3
4
5
6
7
8
9
B
A
A
GND
Z
Z
1
2
3
4
5
6
7
8
9
X8
(ECS-Slave)
Fig. 5−21Connection of the master frequency input/output X8 (master « slave)
Signals for clockwise rotation
Cores twisted in pairs
Assignment of plug connector X8: Sub−D 9−pole
Pin123456789
Input signalBAA˘GNDZZ˘B
Output signalBAA˘GNDZZ˘B
0.14 mm
2
(AWG 26)
5
9
6
1
A
A
B
B
Z
Z
2
1 mm
(AWG 18)
0.14 mm
(AWG 26)
2
ECSXA029
100
EDBCSXA064 EN 3.2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.