This documentation applies to the SM2 and SM4 Vector frequency inverter, and contains important
technical data and describes installation, operation, and commissioning.
These instructions are only valid for SM2 and SM4 Vector frequency inverters with software rev 20
(see drive nameplate).
Please read the instructions before commissioning.
CABD
Type:
174621.00
Id-No: 00000000
Made in USA
Inverter
SM2 Vector
A
Certications
Type
B
Scope of deliveryImportant
• 1 SM2 or SM4 Vector inverter
with EPM installed
(see Section 4.4)
• 1 Operating Instructions
INPUT:
Input Ratings
C
D
Output Ratings
After receipt of the delivery, check immediately whether the
items delivered match the accompanying papers. LEESON does
not accept any liability for deciencies claimed subsequently.
Claim
• visible transport damage immediately to the forwarder.
• visible deciencies / incompleteness immediately to your
LEESON representative.
3~ (3/PE)
400/480 V
2.9/2.5 A
50-60 HZ
OUTPUT:
3~ (3/PE)
0 - 400/460 V
2.4/2.1 A
0.75 KW/1HP
0 - 500 HZ
For detailed information
refer to instruction
Manual: SV06
V0115
2
Safety information
All safety information given in these Operating Instructions have the same layout:
Signal Word! (characterizes the severity of the danger)
Note (describes the danger and informs on how to proceed)
Icon
Warning of
hazardous
electrical voltage
Warning of a
general danger
Warning of damage
to equipment
Information
Signal Words
DANGER!
WARNING!
STOP!
Note
Warns of imminent / impending danger.
Consequences if disregarded:
will result in Death or severe injuries.
Warns of potential, very hazardous situations.
Consequences if disregarded:
could result in Death or serious injuries.
Warns of potential damage to material and equipment.
Consequences if disregarded:
Damage to the controller/drive or its
environment.
Designates a general, useful note.
If you observe it, handling the controller/drive
system is made easier.
Note for UL approved system with integrated controllers: UL warnings are notes which
apply to UL systems. The documentation contains special information about UL.
• Suitable for use on a circuit capable of delivering not more than 200,000 rms
symmetrical amperes, at the maximum voltage rating marked on the drive.
• Use minimum 75 °C copper wire only.
Warnings!
• Shall be installed in a pollution degree 2 macro-environment.
Operation
Systems including controllers must be equipped with additional monitoring and protection devices
according to the corresponding standards (e.g., technical equipment, regulations for prevention of
accidents, etc.). The controller may be adapted to your application as described in this documentation.
DANGER!
• After the controller has been disconnected from the supply voltage, live components
and power connection must not be touched immediately, since capacitors could be
charged. Please observe the corresponding notes on the controller.
• Please close all protective covers and doors prior to and during operation.
• Do not cycle input power to the controller more than once every two minutes.
3
Safety information
1 Safety information
General
DANGER!
Some parts of LEESON controllers can be electrically live and some surfaces
can be hot.
Non-authorized removal of the required cover, inappropriate use, and incorrect installation or
operation creates the risk of serious injury to personnel or damage to equipment.
All operations concerning transport, installation, and commissioning as well as maintenance must be
carried out by qualied, skilled personnel who are familiar with the installation, assembly, commissioning,
and operation of variable frequency drives and the application for which it is being used.
Installation
Ensure proper handling and avoid excessive mechanical stress. Do not bend any components and
do not change any insulation distances during transport, handling, installation or maintenance.
Do not touch any electronic components or contacts. This drive contains electrostatically sensitive
components, which can easily be damaged by inappropriate handling. Static control precautions
must be adhered to during installation, testing, service and repair of this drive and associated
options. Component damage may result if proper procedures are not followed.
This drive has been tested by Underwriters Laboratory (UL) and is an approved component in
compliance with UL508 Safety Standard.
This drive must be installed and congured in accordance with both national and international
standards. Local codes and regulations take precedence over recommendations provided in this
and other LEESON documentation.
The SM2 and SM4 Vector drive is considered a component for integration into a machine or process.
It is neither a machine nor a device ready for use in accordance with European directives (reference
machinery directive and electromagnetic compatibility directive). It is the responsibility of the end
user to ensure that the machine meets the applicable standards.
Electrical connection
WARNING!When working on live drive controllers, applicable national safety regulations must
be observed.
The electrical installation must be carried out according to the appropriate regulations (e.g.
cable cross-sections, fuses, protective earth [PE] connection). While this document makes
recommendations in regard to these items, national and local codes must be adhered to.
The documentation contains information about installation in compliance with EMC (shielding,
grounding, lters and cables). These notes must also be observed for CE-marked controllers.
The manufacturer of the system or machine is responsible for compliance with the required limit
values demanded by EMC legislation.
Application
WARNING!
The drive must not be used as a safety device for machines where there is a
risk of personal injury or material damage. Emergency Stops, over-speed
protection, acceleration and deceleration limits, etc. must be made by other
devices to ensure operation under all conditions.
The drive features many protection devices which are aimed at protecting the drive and the driven
equipment by generating a fault and shutting the drive and motor down by removing power. Mains
power variances can also result in shutdown of the drive. When the fault condition disappears or is
cleared, the drive can be congured to automatically restart. It is the responsibility of the user and/
or OEM and/or integrator to ensure that the drive is congured for safe operation.
4
Technical data
2 Technical data
2.1 Standards and application conditions
Conformity
Approvals
Input voltage phase imbalance
Supported Power Systems
Humidity
Temperature range
Installation height
Vibration resistance
WARNING!
Earth leakage current
Max Permissable Cable Length
Enclosure
Protection measures against
Compliance with EN 61000-3-2
Requirements
Compliance with EN 61000-3-12
Requirements (2)
Operation in public supply networks (Limitation of harmonic currents i.a.w. EN 61000-3-2, Electromagnetic
Compatibiliy (EMC) Limits). Limits for harmonic current emissions (equipment input current up to 16A/phase).
(1) The stated cable lengths are permissiable at default carrier frequencies (refer to parameter P166).
(2) The additional measures described only ensure that the controller meets the requirements of the EN 61000-3-2.
The machine/system manufacturer is responsible for the machine’s compliance with the regulations.
(2)
CE Low Voltage Directive (73/23/EEC)
UL 508C Underwriters Laboratories - Power Conversion Equipment
< 2%
– For central grounded systems, operation is
TT
TN
< 95% non-condensing
Transport-25 … +70°C
Storage-20 … +70°C
Operation
0 … 4000m a.m.s.l.
(with 5%/1000 m current derating above 1000m a.m.s.l.)
acceleration resistant up to 1.0g
> 3.5 mA to PE
<=4.0 Hp (3.0 kW) 30 meters shielded, 60 meters un-shielded
NEMA 1 and NEMA 4X model enclosures are plenun rated in accordance
with UL 508C and are suitable for installation in a compartment handling
conditioned air.
short circuit, earth fault, phase loss, over voltage, under voltage, motor
stalling, over temperature, motor overload
< 0.5 kWwith mains choke
0.5 ... 1 kWwith active lter
> 1 kWwithout additional measures
16 ... 75 amp
permitted without restrictions.
– For corner grounded 400/500V systems, operation
is possible but reinforced insulation to control
circuits is compromised.
-10 … +55°C
above +40°C)
Additional measures required for compliance with
EN 61000-3-12
(with 2.5%/°C current derating
5
Technical data
2.2 Ratings
120VAC Doubler / 240VAC Models
Type
1746030.33 / 0.25
174604174652
174605174653
174651174654
Power
[Hp/kW]
0.5 / 0.379.24.62.42003232
1 / 0.7516.68.34.22005241
1.5 / 1.120.010.06.02007474
Voltage
120 V Single-phase (1/N/PE)
(90 … 132 V)
240 V Single-phase (2/PE)
(170 … 264 V)
MainsOutput Current
(1)
OR
I
(120V) Iin (240V)I
in
6.83.41.720024
CLim
n
240VAC Models
Type
1746060.33 / 0.25
174607-174655 0.5 / 0.37
174608-1746561 / 0.758.85.04.22004142
174609-1746571.5 / 1.112.06.96.02006463
174610-1746582 / 1.513.38.17.02007573
174611-1746593 / 2.217.110.89.620010397
1746121.5 / 1.1
1746132 / 1.5-8.17.02007569
1746143 / 2.2-10.89.620010393
174615-1746605 / 4.0-18.616.5200154139
174616-1746617.5 / 5.5-2623200225167
174617-17466210 / 7.5-3329200274242
17461815 / 11-4842180485468
17461920 / 15-5954180614591
(1) Frequency Range: 48 Hz … 62 Hz
(2) Current Limit (CLim) is a percentage of the output current, In. CLim
(2) Current Limit (CLim) is a percentage of the output current, In. CLim
For 480VAC models, the CLim
The CLim
Power
[Hp/kW]
600 V Three-phase (3/PE)
value in the 480V column of the table is used when P107 is set to 1.
value in the 400V column is used when P107 is set to 0.
max
max
MainsOutput Current
(1)
Voltage
(425 … 660 V)
I
in
2.01.7200
is the maximum setting for P171.
max
I
CLim
n
SM2
(2)
Watts
max
Loss
SM2
Watts
(2)
max
Loss
3731
SM4
Watts
Loss
SM4
Watts
Loss
STOP!
Drive Derating
The SM2 and SM4 Vector Series drive is designed to operate at the Nominal Output Current (In)shown
in the Ratings tables for most standard applications and industrial environments. The drive output
current or operating temperature may need to be limited as described below:
• For installations above 1000m a.m.s.l., derate I
• Operation above 40°C, derate In by 2.5% per °C, do not exceed 55°C.
• Carrier Frequency (P166):
- If P166=2 (8 kHz), derate I
- If P166=3 (10 kHz), derate In to 84% of drive rating or do not exceed 27°C ambient
For combinations of the above, please consult LEESON applications support for proper derating.
to 92% of drive rating or do not exceed 33°C ambient
n
by 5% per 1000m, do not exceed 4000m a.m.s.l.
n
7
Installation
3 Installation
3.1 Dimensions and mounting
3.1.1 NEMA 1 (IP31)
Mounting
Screws
4 X #10
18 lb-in
4 X M5
( )
20 Nm
b
b1
s2
s1s1
CH1
CH2
CH3
CH4
CH5
a1
a
Type
174603 - 174608,
174620 - 174621,
174631
174609 - 174614,
174622 - 174624,
174632 - 174633
174651
174615, 174625,
174634
174616 - 174617,
174626 - 174627,
174635 - 174636
174618 - 174619,
174628 - 174630,
174637 - 174639
174991, 174993
Conduit Hole DimensionsType
P1
P
N
a
in (mm)
in (mm)b in (mm)
3.90
3.10
(99)
(79)
3.90
3.10
(99)
(79)
3.90
3.10
(99)
(79)
5.12
4.25
(130)
(108)
6.92
5.75
(176)
(146)
Q
Q
S
s2
s1
in (mm)
4.35
0.6
(110)
(15)
5.45
0.6
(138)
(15)
5.80
0.6
(147)
(15)
6.25
0.6
(159)
(15)
8.09
0.6
(205)
(15)
P1
in (mm)Q in (mm)S in (mm)
mm (in)
in (mm)
7.50
(190)
7.50
(190)
7.50
(190)
9.83
(250)
12.50
11.88
(318)
N
in (mm)P in (mm)
c
b1
7.00
(178)
7.00
(178)
7.00
(178)
9.30
(236)
(302)
b2
in (mm)c in (mm)
0.25
(6)
0.25
(6)
0.25
(6)
0.25
(6)
0.31
(8)
b2
a1
CH11.84 (47) 1.93 (49).70 (18) 1.00 (25).88 (22)
CH21.84 (47) 3.03 (77).70 (18) 1.00 (25).88 (22)
CH31.84 (47) 3.38 (86).70 (18) 1.00 (25).88 (22)
CH42.46 (62) 3.55 (90).13 (3)1.38 (35)
CH53.32 (84) 4.62 (117) .73 (19)1.40 (36)
s2
in (mm)m lb (kg)
2.0
2.0
(50)
(0.9)
2.0
2.8
(50)
(1.3)
2.0
3.2
(50)
(1.5)
2.0
6.0
(50)
(2.0)
2.0
13.55
(50)
(6.15)
1.13 (29)
.88 (22)
1.31 (33)
.88 (22)
V0102
WARNING!
Drives must not be installed where subjected to adverse environmental conditions
8
such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive
vibration or excessive temperatures. Contact LEESON for more information.
3.1.1 NEMA 1 (IP31) Models > 30HP (22kW)
a
CH6
Type
174992
174994
in (mm)
8.72
(221)
a1
in (mm)b in (mm)
7.50
14.19
(190)
(360)
in (mm)
13.30
(338)
Installation
b1
b2
in (mm)c in (mm)
0.45
(11.4)
10.07
(256)
s1
in (mm)
0.6
(15)
s2
in (mm)m lb (kg)
2.0
24.0
(50)
(10.9)
V0102
CH7
CH8
174710
174712
174711
174713
Conduit Hole DimensionsType
8.72
(221)
8.72
(221)
WARNING!
Drives must not be installed where subjected to adverse environmental conditions
such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive
vibration or excessive temperatures. Contact LEESON for more information.
Drives must not be installed where subjected to adverse environmental conditions
such as: combustible, oily, or hazardous vapors or dust; excessive moisture; excessive
vibration or excessive temperatures. Contact LEESON for more information.
Installation
3.2 Electrical installation
Installation After a Long Period of Storage
STOP!
Severe damage to the drive can result if it is operated after a long period of storage
or inactivity without reforming the DC bus capacitors.
If input power has not been applied to the drive for a period of time exceeding
three years (due to storage, etc.), the electrolytic DC bus capacitors within the
drive can change internally, resulting in excessive leakage current. This can result in
premature failure of the capacitors if the drive is operated after such a long period
of inactivity or storage.
In order to reform the capacitors and prepare the drive for operation after a long
period of inactivity, apply input power to the drive for 8 hours prior to actually
operating the motor.
3.2.1 Power Connections
DANGER!
Hazard of electrical shock! Circuit potentials are up to 600 VAC above earth ground.
Capacitors retain charge after power is removed. Disconnect power and wait at
least three minutes before servicing the drive.
STOP!
• Verify mains voltage before connecting to drive.
• Do not connect mains power to the output terminals (U,V,W)! Severe damage to
the drive will result.
• Do not cycle mains power more than once every two minutes. Damage to the
drive will result.
Mains and Motor Terminations
TypeTorqueStrip Length
174991, 17499224 lb-in (2.7 Nm)7/16 in (10mm)
174710, 17471127 lb-in (3.05 Nm) 0.75 in (19mm)
3.2.1.1 Mains connection to 120VAC Single-Phase Supply
174603
174604
174605
174651
174652
174653
174654
PE L1 L2 N
PE L1 N
11
Installation
3.2.1.2 Mains connection to 240VAC Single-Phase Supply
174603
174604
174605
174651
174652
174653
174654
174607
174608
174609
174610
174611
(2/PE AC)
174606
(2/PE AC)
PE L1 L2 N
PE L1 L2
PE L1 L2 L3
PE L1 L2
PE L1 L2
174603
174604
174605
174651
174652
174653
174654
174607
174608
174609
174610
174611
(1/N/PE AC)
174606
(1/N/PE AC)
PE L1 L2 N
PE L1 N
PE L1 L2 L3
PE L1 N
PE L1 L2
PE L1 L2
3.2.1.3 Mains connection to Three-Phase Supply
All
three-phase
models
(3/PE AC)
PE L1 L2 L3
PE L1 L2 L3
3.2.1.4 Motor Connection
U/T1 V/T2 W/T3 PE
PES
PES
PES
PES
M
PES
3~
PE
PES = Protective Earth Shielding
PE
Mains and Motor Terminations
12 lb-in (1.3 Nm)
0.25 in (6mm)
SM4 Cover Screws Torque 6-7 lb-in
WARNING!
Leakage current may exceed 3.5 mA AC.
Minimum size of the protective earth conductor
shall comply with local safety regulations for
high leakage current equipment.
12
PE L1 N
Installation
3.2.1.5 Installation Recommendations for EMC Compliance
For compliance with EN 61800-3 or other EMC standards, motor cables, line cables and control or communications
cables must be shielded with each shield/screen clamped to the drive chassis. This clamp is typically located at the
conduit mounting plate.
Motor cable should be low capacitance (core/core <75pF/m, core/shield <150pF/m). Filtered drives can meet the
class A limits of EN 55011 and EN 61800-3 Category 2 with this type of motor cable up to 10 meters. NOTE: Refer
to Appendix A for recommended cable lengths. Any external line filter should have its chassis connected to the
drive chassis by mounting hardware or with the shortest possible wire or braid.
Enclosure / Backplate
External
Control
Circuits
Control and signal cabling
should be separated from
power cables by
a minimum of 300mm
360° shield termination to
backplate using saddle clamp
From
Motor
3.2.1.6 NEMA 4X (IP65) Input Terminal Block
For NEMA 4X (IP65) models with integrated EMC filter and/or integrated line disconnect, the input terminal block
is located on the right-hand side of the SM4 inverter in the NEMA 4 X (IP65) enclosure. The single and three phase
models are illustrated herein. Refer to paragraph 3.2.3 Control Terminals for pin out information.
From
AC Supply
Screened motor cable:
core/core <75pF/M
core/shield <150pF/M
Single Phase (2/PE) Three Phase (3/PE)
With Filter and/or integrated line disconnect With Filter and/or integrated line disconnect
WARNING
Power remains present for up to 3 minutes on power input terminals (L1, L2 and L3)
and output terminals (U, V and W) even when the disconnect switch is in the OFF
position. Remove input power ahead of the drive and wait 3 minutes before removing
the terminal cover.
13
Installation
3.2.1.7 Dynamic Brake Connections
For NEMA 1 and NEMA 4X Drives rated up to 25 HP the Dynamic Brake connections are made as illustrated herein.
Refer to the SM2 and SM4 Dynamic Brake instructions for complete information.
NEMA 1 (IP31) up to 30 HP
NEMA 4 (IP65) up to 10 HP
The 40...40HP (30...45kW) models include a dynamic brake transitor as standard and only require the connection
of an external resistor kit for dynamic braking operation. The dynamic brake resistor connections for 40...60HP
(30...45kW) drives are standard built-in connections as illustrated in the diagram below. In the 40HP (30kW) model
drives, the dynamic brake connector is on the right-hand side of the drive and the terminals from top to bottom are
B-, BRAKE and B+. In the 50/60HP (37.5/45kW) model drives, the dynamic brake connector is on the left-hand side
of the drive and the terminals from top to bottom are B+, BRAKE and B-.
14
Installation
3.2.2 Fuses/cable cross-sections
Note
Observe local regulations.
Local codes may supersede these recommendations
174639M50 AC50 A50 A68
174993M63 AC63 A60 A108
174994M80 AC80 A70 A166
174712M100 A C100 A 90 A164
(1) Installations with high fault current due to large supply mains may require a type D circuit breaker.
(2) UL Class CC or T fast-acting current-limiting type fuses, 200,000 AIC, preferred. Bussman KTK-R, JJN or JJS or equivalent.
(3) Thermomagnetic type breakers preferred.
174713M125 AC125 A110 A252
M10 AC10 A10 A1.514
M16 AC16 A12 A1.514
M10 AC10 A10 A1.514
Fuse
Miniature
circuit
breaker
Fuse
Breaker
(1)
(N. America)
(2)
or
Input Power Wiring
(3)
[mm²][AWG]
(L1, L2, L3, PE)
15
Installation
ALsw
Observe the following when using Ground Fault Circuit Interrupters (GFCIs):
• Installation of GFCI only between supplying mains and controller.
• The GFCI can be activated by:
- capacitive leakage currents between the cable screens during operation (especially with long,
screened motor cables)
- connecting several controllers to the mains at the same time
- RFI lters
3.2.3 Control terminals
Control Terminal Strip for 0.33-10HP (0.25-7.5 kW):
COM
1 2 4
+10 V
AIN
AIN
4.5 lb-in
(0.5 Nm)
0.25 in (6 mm)
AWG 26…16
(<1mm²)
COM
512
2k … 10k
625411
13A
13B
13C
14 30
DIGOUT
16
AOUT
17
+12 VDC - 0 %
+30 VDC + 0 %
Terminal Data for control connections
1
Digital Input: Start/Stopinput resistance = 4.3kΩ
2
Analog Common
5
Analog Input: 0...10 VDCinput resistance: >50 kΩ
6
Internal DC supply for speed pot+10 VDC, max. 10 mA
25
Analog Input: 4...20 mAinput resistance: 250Ω
4
Digital Reference/Common+15 VDC / 0 VDC, depending on assertion level
11
Internal DC supply for external devices+12 VDC, max. 50 mA
13A
Digital Input: Congurable with P121
13B
Digital Input: Congurable with P122
13C
Digital Input: Congurable with P123
13D*
Digital Input: Congurable with P124
14
Digital Output: Congurable with P142DC 24 V / 50 mA; NPN
30
Analog Output: Congurable with P150…P155 0…10 VDC, max. 20 mA
16
Relay output: Congurable with P140
17
2*
TXA*
TXB*
Analog Common
RS485 TXA
RS485 TXB
input resistance = 4.3kΩ
AC 250 V / 3 A
DC 24 V / 2 A … 240 V / 0.22 A, non-inductive
* = Terminal is part of the terminal strip for the 15-25 HP models only
ALsw
13A 13B 13C
+15V
PNPNPN
…
0 … 10 V
0 … 5 V
1 2 4
52
ALsw
COM
252
4 … 20 mA
13A 13B 13C
V0109
16
Commissioning
625411
13A
13B
13C
TXA
512
14 30
2
AOUT
DIGOUT
2k … 10k
+10 V
+12 V
AIN
AIN
COM
COM
ALsw
17
16
TXB
13D
13D
13D
252
4 … 20 mA
52
0 … 10 V
1 2 4
13A 13B 13C
+12 VDC - 0 %
. . .
+30 VDC + 0 %
ALsw
+15V
1 2 4
13A 13B 13C
ALsw
COM
4.5 lb-in
(0.5 Nm)
0.25 in (6 mm)
AWG 26…16
(<1mm²)
Control Terminal Strip for 15HP (11 kW) and Greater Drives:
The digital inputs can be congured for active-high or active-low by setting the Assertion Level
Switch (ALsw) and P120. If wiring to the drive inputs with dry contacts or with PNP solid state
switches, set the switch and P120 to “High” (+). If using NPN devices for inputs, set both to
“Low” (-). Active-high (+) is the default setting.
HIGH = +12 … +30 V
LOW = 0 … +3 V
Note
An F.AL fault will occur if the Assertion Level switch (ALsw) position does not match
the parameter P120 setting and P100 or any of the digital inputs (P121...P123) is set
to a value other than 0.
4 Commissioning
4.1 Local Keypad & Display
FWDAUTO
REV
RUN
STOP
V0105
15HP (1kW) and greater Models
17
Commissioning
AUTO
Display START BUTTON
In Local Mode (P100 = 0, 4, 6), this button will start the drive.
RUN
STOP BUTTON
Stops the drive, regardless of which mode the drive is in.
STOP
WARNING!
When JOG is active, the STOP button will not stop the
drive!
ROTATION
In Local Mode (P100 = 0, 4, 6), this selects the motor rotation direction:
- The LED for the present rotation direction (FWD or REV) will be on
- Press R/F; the LED for the opposite rotation direction will blink
- Press M within 4 seconds to confirm the change
- The blinking direction LED will turn on, and the other LED will turn off
When rotation direction is changed while the drive is running, the commanded direction LED will blink
until the drive is controlling the motor in the selected direction.
MODE
Used to enter/exit the Parameter Menu when programming the drive and to enter a changed parameter
value.
UP AND DOWN BUTTONS
Used for programming and can also be used as a reference for speed, PID setpoint, or torque setpoint.
When the s and t buttons are the active reference, the middle LED on the left side of the display will
be on.
Display INDICATING LEDs (on 4-character display)
FWD
FWD LED: Indicate the present rotation direction is forward. Refer to ROTATION description above.
REV LED: Indicate the present rotation direction is reverse. Refer to ROTATION description above.
REV
AUTO LED: Indicates that the drive has been put into Auto mode from one of the TB13 inputs (P121…
P124 set to 1…7). Also indicates that PID mode is active (if enabled).
RUN LED: Indicates that the drive is running.
RUN
18
s t LED: Indicates that the s t are the active reference.
Commissioning
NOTE
If the keypad is selected as the auto reference (P121…P124 is 6) and the
corresponding TB-13 input is closed, the AUTO LED and s t LEDs will both be on.
FUNCTIONS THAT FOLLOW ARE APPLICABLE TO SM2 DRIVES 15HP (11kW) AND GREATER
CTRL
CTRL
The CTRL pushbutton selects the start and speed reference control sources for the drive.
Press [
] mode button to accept the new control mode selection.
CTRL LEDs
MAN
REMOTE
LOCAL
REMOTE
LOCAL
REMOTE
LOCAL
REMOTE
LOCAL
MAN
MAN
AUTO
MAN
AUTO
AUTO
AUTO
[LOCAL] [MAN]
[LOCAL] [AUTO]
[REMOTE] [MAN]
[REMOTE] [AUTO]
If P100 = 6 the CTRL button is used to toggle
start control between the terminal strip
[REMOTE] and the keypad [LOCAL]
If P113 = 1 the CTRL button is used to toggle
reference control between the TB-13x setup
[AUTO] and P101 [MANUAL]
If P100 = 6 and P113 = 1, it is possible to
change the start and reference control sources
at the same time
START CONTROLREFERENCE CONTROL
KeypadP101 Settings
KeypadTerminal 13x Settings
Terminal StripP101 Settings
Terminal StripTerminal 13x Settings
- REM/LOC LED indicating the present start control source
is ON
- Press [CTRL]; the LED for other start control source will
blink
- Press [M] within 4 sec to confirm the change
- Blinking LED will turn ON (the other LED will turn OFF)
- AUT/MAN LED indicating present reference control is ON
- Press [CTRL]; the other reference control will blink
- Press [M] within 4 sec to confirm change
- Blinking LED will turn ON (the other LED will turn OFF)
19
Commissioning
Display START CONTROL
The REMOTE/LOCAL LEDs indicate the current start control source. If the start control source is a
remote keypad or the network, then both LEDs will be OFF.
REFERENCE CONTROL
The AUTO/MANUAL LEDs indicate the current reference control source.
IF P113 = 0 or 2, the AUTO/MANUAL LEDs will match the AUTO LED on the 4-character display. IF
P113 = 0 and no AUTO reference has been setup on the terminal strip, the MANUAL LED will turn ON
and the AUTO LED will turn OFF.
IF P113 = 1, the AUTO/MANUAL LEDS show the commanded reference control source as selected by
the [CTRL] button. If the [CTRL] button is used to set the reference control source to AUTO but no
AUTO reference has been setup on the terminal strip, reference control will follow P101 but the AUTO
LED will remain ON.
UNITS LEDs
HZ: current display value is in HzIn Speed mode, if P178 = 0 then HZ LED will be ON.
%: current display value is in %
RPM: current display value is in RPM
AMPS: current display value is in Amps
/UNITS current display value is a per unit (i.e./
sec, /min, /hr, etc.)
If P178 > 0, the Units LEDs follow the setting of P177
when the drive is in run (non-programming) mode.
In Torque mode, the HZ LED will be ON when the drive
is in run (non-programming) mode.
In Pid mode, the Units LEDs follow the setting of P203
when the drive is in run (non-programming) mode.
If P179 > 0, the Units LEDs will show the unit of the
diagnostic parameter that is being displayed.
4.2 Drive Displays and Modes of Operation
Speed Mode Display
In the standard mode of operation, the drive frequency output is set directly by the selected
reference (keypad, analog reference, etc.). In this mode, the drive display will show the drive’s
output frequency.
PID Mode Display
When the PID mode is enabled and active, the normal run display shows the actual PID setpoint.
When PID mode is not active, the display returns to showing the drive’s output frequency.
Torque Mode Display
When the drive is operating in Vector Torque mode, the normal run display shows the drive’s
output frequency.
Alternate (Run-Screen) Display
When P179 (Run Screen Display) is set to a value other than 0, one of the diagnostic parameters
(P501...P599) is displayed. Example: if P179 is set to 1, then diagnostic parameter P501 (Software
version) is displayed. If P179 = 2, then P502 (Drive ID) is displayed.
20
Commissioning
4.3 Parameter setting
Status/fault messages Change Parameters
StoP
60.0
CL
Err
F.AF
F.UF
4.4 Electronic programming module (EPM)
The EPM contains the drive’s operational memory. Parameter settings are stored in
the EPM and setting changes are made to the “User settings” in the EPM.
An optional EPM Programmer (model EEPM1RA) is available that allows:
Tmd007
• An EPM to be copied directly to another EPM.
• An EPM to be copied to the memory of the EPM Programmer.
• Stored les can be modied in the EPM Programmer.
• Stored les can be copied to another EPM.
As the EPM Programmer is battery operated, parameter settings can be copied
to an EPM and inserted into a drive without power being applied to the drive. This
means that the drive will be fully operational with the new settings on the next
application of power.
Additionally, when the drive’s parameter settings are burned into an EPM with
the EPM Programmer, the settings are saved in two distinct locations: the “User
settings” and the “OEM default settings”. While the User settings can be modied
in the drive, the OEM settings cannot. Thus, the drive can be reset not only to the
“factory” drive default settings (shown in this manual), but can be set to the Original
Machine settings as programmed by the OEM.
While the EPM can be removed for copying or to use in another drive, it must be
installed for the drive to operate (a missing EPM will trigger an
M
PASS
0225
M
P194 = 0000
60 s
p100
p104
p541
M
15 s
F.F1 fault).
20.0
12.0
M
V0106
21
Commissioning
4.5 Parameter menu
4.5.1 Basic Setup Parameters
CodePossible Settings
No.NameDefault Selection
P100
Start Control
Source
00 Local KeypadUse RUN button on front of drive to
1 Terminal StripUse start/stop circuit wired into the
2 Remote Keypad OnlyUse RUN button on optional Remote
3 Network Only• Start command must come from
4 Terminal Strip or Local
Keypad
5 Terminal Strip or Remote
Keypad
IMPORTANT
start
terminal strip. See Section 3.2.3
Keypad to start
network (Modbus, CANopen, etc)
• Requires optional communication
module (refer to the network
module documentation).
• Must also set one of the TB-13
inputs to 9 (Network Enable); see
P121...P123
Allows start control to be switched
between terminal strip and local
keypad using one of the TB-13
inputs. See note below.
Allows start control to be switched
between terminal strip and optional
remote keypad using one of the TB-
13 inputs. See note below.
22
6 CTRL Button SelectAllows start control to be switched
WARNING!
P100 = 0 disables TB-1 as a STOP input! STOP circuitry may be
disabled if parameters are reset back to defaults (see P199)
Note
• P100 = 4, 5: To switch between control sources, one of the TB-13
inputs (P121...P123) must be set to 08 (Control Select);
TB-13x OPEN (or not congured): Terminal strip control
TB-13x CLOSED: Local (P100 = 4) or Remote (P100 = 5) keypad
• P100 = 0, 1, 4: Network can take control if P121...P123 = 9 and the
corresponding TB-13x input is CLOSED.
• The STOP button on the front of the drive is always active except in
JOG mode.
•
An F.AL fault will occur if the Assertion Level switch (ALsw)
between terminal strip and local
keypad using the CTRL button.
NOTE: P100 Selection 6 is applicable
to 15 HP (11kW) and higher models
only.
position does not match the P120 setting and P100 is set to a
value other than 0.
Commissioning
CodePossible Settings
No.NameDefault Selection
Standard
P101
Reference
Source
Minimum
P102
Frequency
Maximum
P103
Frequency
WARNING!
Consult motor/machine manufacturer before operating above rated frequency. Overspeeding the
motor/machine may cause damage to equipment and injury to personnel!
Acceleration
P104
Time 1
Deceleration
P105
Time 1
Example: if P103 = 120 Hz, P104 = 20.0 s and P167 (base frequency) = 60 Hz;
rate of frequency change from 0 Hz to 120 Hz = 40.0 s
00 Keypad (Local or Remote)Selects the default speed or torque
1 0-10 VDC
2 4-20 mA
3 Preset #1
4 Preset #2
5 Preset #3
6 Network
7 Preset Sequence Segment #1 Selections 7, 8 & 9 are not valid for
8 Preset Sequence Segment #2
9 Preset Sequence Segment #3
0.0 0.0 {Hz} P103• P102, P103 are active for all speed
60.0 7.5 {Hz} 500
Note
• P103 cannot be set below Minimum Frequency (P102)
• To set P103 above 120 Hz:
- Scroll up to 120 Hz; display shows
- Release s button and wait one second
- Press s button again to continue increasing P103
20.0 0.0 {s} 3600• P104 = time of frequency change
20.0 0.0 {s} 3600
reference when no Auto Reference is
selected using the TB-13 inputs
PID setpoint or torque reference.
references
• When using an analog speed
reference, also see P160, P161
from 0 Hz to P167 (base frequency)
• P105 = time of frequency change
from P167 to 0 Hz
• For S-ramp accel/decel, adjust
IMPORTANT
HiFr (ashing).
S-Ramp
P106
Integration Time
(1)
Line Voltage
P107
Selection
(1) Any changes to this parameter will not take effect until the drive is stopped
0.0 0.0 {s} 50.0• P106 = 0.0: Linear accel/decel
• P106 > 0.0: Adjusts S-ramp curve
1*0 Low (120, 200, 400, 480VAC) * The default setting is 1 for all
1 High (120, 240, 480, 600VAC)
ramp
for smoother ramp
drives except when using “reset
50” (Parameter P199, selection 4)
with 480V models. In this case, the
default setting is 0.
23
Commissioning
CodePossible Settings
No.NameDefault Selection
Motor Overload100 30 {%} 100
P108
Note
Do not set above the rated motor current as listed on the motor
dataplate. The motor thermal overload function of the SM2 is UL
approved as a motor protection device. If line power is cycled, the
motor thermal state is reset to cold state. Cycling power after an
overload fault could result in signicantly reducing the motor life.
Motor Overload
P109
Type
00 Speed Compensation
1 No Speed Compensation
Start Method00 Normal
P110
1 Start on Power-upDrive will automatically start when
2 Start with DC BrakeWhen start command is applied, drive
3 Auto RestartDrive will automatically restart after
4 Auto Restart with DC Brake Combines settings 2 and 3
5 Flying Start/Restart #1• Drive will automatically restart after
6 Flying Start/Restart #2
IMPORTANT
motor current rating
P108 =
SM2 output rating
Example: motor = 3 amps; SM2 = 4
amps; P108 = 75%
1
Ir
100%
0
60%
30 f
x 100
V0108
power is applied.
will apply DC braking according to
P174, P175 prior to starting the motor
faults, or when power is applied.
faults, or when power is applied.
• After 3 failed attempts, drive will
Auto Restart with DC brake.
• P110 = 5: Performs speed search,
starting at Max Frequency (P103)
• P110 = 6: Performs speed search,
starting at the last output frequency
prior to faulting or power loss
• If P111 = 0, a ying START is
performed when a start command
is applied.
24
Commissioning
CodePossible Settings
No.NameDefault Selection
Note
• P110 = 0, 2: Start command must be applied at least 2 seconds
after power-up;
soon.
• P110 = 1, 3…6: For automatic start/restart, the start source must be
the terminal strip and the start command must be present.
• P110 = 2, 4…6: If P175=999.9, dc braking will be applied for 15s.
• P110 = 3…6: Drive will attempt 5 restarts; if all restart attempts fail,
drive displays
• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip
into
F.rF fault.
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel!
Automatic starting/restarting should only be used on equipment that is inaccessible to personnel.
Stop Method00 CoastDrive’s output will shut off
P111
1 Coast with DC BrakeThe drive’s output will shut off and
2 RampThe drive will ramp the motor to a
3 Ramp with DC BrakeThe drive will ramp the motor to 0 Hz
Rotation00 Forward OnlyIf PID mode is enabled, reverse
P112
1 Forward and Reverse
F.UF fault will occur if start command is applied too
LC (fault lockout) and requires manual reset.
immediately upon a stop command,
allowing the motor to coast to a stop
then the DC Brake will activate (see
P174, P175)
stop according to P105 or P126.
and then the DC Brake will activate
(see P174, P175)
direction is disabled (except for Jog).
IMPORTANT
25
Commissioning
4.5.2 I/O Setup Parameters
CodePossible Settings
No.NameDefault Selection
Auto/Manual
P113
Control
MOP Speed
P115
Initialization at
Power-Up
Assertion Level2
P120
0
0 Terminal Strip Control
1 Auto/Manual (CTRL button
select)
2 Manual Control OnlyReference is dictated by P101
NOTE
P113 is applicable to 15 HP (11kW) and higher models only.
00 Set to last MOP speed at
power up
1 Set to 0.0Hz at power up
2 Set to Preset #3 at power up
1 Low
2 High
IMPORTANT
The reference is dictated by the
settings and state of the TB-13x
terminals. If no AUTO reference has
been setup on the terminal strip then
reference control is dictated by P101.
Allows the reference to be switched
between auto and manual using
the CTRL pushbutton on the drive
keypad. If the CTRL pushbutton
has selected AUTO reference but
no AUTO reference has been setup
on the terminal strip, then reference
control is dictated by P101.
regardless of any AUTO source
that may be selected by the TB-13x
terminals.
P120 and the Assertion Level
switch must both match the desired
assertion level unless P100, P121…
P123 are all set to 0. Otherwise an
F.AL fault will occur.
26
Commissioning
CodePossible Settings
No.NameDefault Selection
TB-13A Input
P121
Function
TB-13B Input
P122
Function
P123
TB-13C Input
Function
p124
TB-13D* Input
Function
NOTE: P124 is
applicable to SMV
15HP (11kW) and
greater models
only
WARNING!
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be
deactivated or a fault condition induced.
00 NoneDisables input
1 AUTO Reference: 0-10 VDC For frequency mode, see P160...P161,
2 AUTO Reference: 4-20 mA
3 AUTO Reference: PresetFor frequency mode see P131...P137,
4 AUTO Reference: MOP Up• Normally open: Close input to
5 AUTO Reference: MOP Down
6 AUTO Reference: Keypad
7 AUTO Reference: Network
8 Control SelectUse when P100 = 4, 5 to switch
9 Network EnableRequired to start the drive through
19 Auxiliary Ramp to StopNormally closed: Opening input will
20 Clear FaultClose to reset fault
21 External Fault
22 Inverse External Fault
23 AUTO Ref: Sequence
Segment #1
24 Start Sequence
25 Step SequenceTransition from non-asserted to
26 Suspend Sequence
F.EF
For PID mode, see P204…P205,
For vector torque mode, see P330
For PID mode, see P231…P233,
For torque mode see, P331…P333
increase or decrease speed, PID
setpoint or torque setpoint.
• MOP Up is not active while in STOP
between terminal strip control and
local or remote keypad control.
the network.
See note for typical circuit
See note for typical circuit
WARNING! Active even if P112 = 0
ramp drive to STOP according to P127,
even if P111 is set to Coast (0 or 1).
Normally closed circuit; open to trip
Normally open circuit; close to trip
F.EF
Works in Speed Mode only
asserted state
IMPORTANT
27
Commissioning
CodePossible Settings
No.NameDefault Selection
WARNING!
If the input dened to “Start Sequence” is opened during a sequence, the drive will exit
sequencer mode and will run at the specied standard or alternate speed source (dependent on
drive conguration).
Note
• When input is activated, settings 1...7 override P101
• When TB-13A...TB-13C are congured for Auto References other than MOP, TB-13C overrides
TB-13B, and TB-13B overrides TB-13A. Any other Auto Reference will have priority over MOP.
• Settings 10...14 are only valid in Terminal Strip mode (P100 = 1, 4, 5)
• If Start/Run/Jog Forward and Start/Run/Jog Reverse are both activated, drive will STOP
• If Jog input is activated while the drive is running, the drive will enter Jog mode; when Jog
input is deactivated, drive will STOP
•
An F.AL fault will occur if the Assertion Level switch (ALsw) position does not match the
IMPORTANT
P120 setting and any of the digital inputs (P121...P123) are set to a value other than 0.
• An F.IL fault will occur under the following conditions:
- TB-13A...TB-13C settings are duplicated (each setting, except 0 and 3, can only be used
once)
- One input is set to “MOP Up” and another is not set to “MOP Down”, or vice-versa.
- One input is set to 10 and another input is set to 11…14.
- One input is set to 11 or 12 and another input is set for 13 or 14.
• Typical control circuits are shown below:
- If any input is set to 10, 12 or 14, P112 must be set to 1 for Reverse action to function.
Acceleration
P125
Time 2
Deceleration
P126
Time 2
Deceleration
P127
Time for
Auxiliary Ramp
to Stop
Automatic
P129
Accel/Decel rate
switch threshold
Run / Stop
with Direction
P121 = 10
13 A
14
FWD
STOP
REV
RUN
20.0 0.0 {s} 3600• Selected using TB-13A...TB-13C
20.0 0.0 {s} 3600
20.0 0.0 {s} 3600• Selected using TB-13A...TB-13C
0.0 0.0 {Hz} 1000If Actual Frequency < P129 Use
Start Forward /
Start Reverse
P121 = 11, P122 = 12
13 A13B
14
FWD
REVSTOP
Run Forward /
P121 = 13, P122 = 14
14
(P121...P123 = 17)
• For S-ramp accel/decel, adjust
P106
(P121...P123 = 19).
• For S-ramp accel/decel, adjust
P106
• Once executed, this ramp time has
priority over P105 and P126.
Accel/decel time #2 (P126/P127)
If Actual Frequency ≥ P129 Use
Accel/decel time #1 (P104/P105)
Run Reverse
13 A13B
RUN
FWD
RUN
REV
28
Commissioning
CodePossible Settings
No.NameDefault Selection
Preset Speed #10.0 0.0 {Hz} 500
P131
Preset Speed #20.0 0.0 {Hz} 500
P132
Preset Speed #30.0 0.0 {Hz} 500
P133
Preset Speed #40.0 0.0 {Hz} 500
P134
Preset Speed #50.0 0.0 {Hz} 500
P135
Preset Speed #60.0 0.0 {Hz} 500
P136
Preset Speed #70.0 0.0 {Hz} 500
P137
Preset Speed #80.0 0.0 {Hz} 500
P138
P140
Relay Output
TB-16, 17
00 NoneDisables the output
1 RunEnergizes when the drive is running
2 ReverseEnergizes when reverse rotation is
3 Fault
4 Inverse FaultEnergizes when the drive trips
5 Fault LockoutP110 = 3...6: De-energizes if all
6 At SpeedEnergizes when output frequency =
7 Above Preset Speed #6Energizes when output freq. > P136
IMPORTANT
PRESET
SPEED
4 (alternate) ------X
8 (alternate) --X--X
8 (alternate) ----XX
• Speed setting is used by P158
• 13D available on 15HP (11kW) &
higher drives.
active
De-energizes when the drive trips, or
power is removed
restart attempts fail
commanded frequency
13A 13B 13C 13D
1X-----2--X---3----X-4XX----
5X--X--
6--XX--
7XXX--
8 Current LimitEnergizes when motor current = P171
9 Follower Loss (4-20 mA)Energizes when 4-20 mA signal falls
10 Loss of LoadEnergizes when motor load drops
below 2 mA
below P145; see also P146
29
Commissioning
CodePossible Settings
No.NameDefault Selection
Relay Output
P140
TB-16, 17
(cont)
TB-14 Output00...23 (same as P140)
P142
011 Local Keypad Control Active
12 Terminal Strip Control Active
13 Remote Keypad Control Active
14 Network Control Active
15 Standard Reference ActiveEnergizes when P101 reference is
16 Auto Reference ActiveEnergizes when Auto Reference is
17 Sleep Mode ActiveSee P240...P242
18 PID Feedback < Min. Alarm Energizes when PID feedback signal
19 Inverse PID Feedback < Min.
Alarm
20 PID Feedback > Max Alarm Energizes when PID feedback
21 Inverse PID Feedback > Max
Alarm
22 PID Feedback within
Min/Max Alarm range
23 PID Feedback outside
Min/Max Alarm range
24 Reserved
25 Network ActivatedRequires optional communication
26 Loss of 0-10V Input
27 Sequencer ControlledState set in individual sequencer
28 Sequencer Active
29 Sequencer Suspended
30 Sequence DoneEnd Sequence
31 Actual Speed = 0.0Hz
24 Dynamic BrakingFor use with Dynamic Braking option
25...31 (same as P140)
IMPORTANT
Energizes when the selected source
is active for start control
active
activated using TB-13 input; see
P121...P123
< P214
De-energizes when PID feedback
signal < P214
signal > P215
De-energizes when PID feedback
signal > P215
Energizes when PID feedback signal
is within the Min/Max Alarm range;
see P214, P215
Energizes when PID feedback signal
is outside the Min/Max Alarm range;
see P214, P215
module (refer to the network module
documentation).
segments
30
Commissioning
CodePossible Settings
No.NameDefault Selection
Digital Output
P144
Inversion
Loss of Load
P145
Threshold
Loss of Load
P146
Delay
Analog Offset0.0 0 {%} 100Scaled value. Example: P149 = 10%,
P149
TB-30 Output00 None2-10 VDC signal can be converted
P150
TB-30 Scaling:
P152
Frequency
TB-30 Scaling:
P153
Load
00 {%} 200P140, P142 = 10: Output will energize
0.0 0.0 {s} 240.0
60.0 3.0 {Hz} 2000If P150 = 1 or 2, sets the frequency at
200 10 {%} 500If P150 = 3 or 4, sets the Load (as
P144
NOTE
Inverting P140 or P142 when the parameter is set to NONE (0) will
result in the output being energized continuously.
NOTE
For SM Vector drives rated at 0.33 to 10 HP (0.25 to 7.5 kW), P144 is
only available with software versions 3.0 and higher (refer to P501).
1 0-10 VDC Output Frequency
2 2-10 VDC Output Frequency
3 0-10 VDC Load
4 2-10 VDC Load
5 0-10 VDC Torque
6 2-10 VDC Torque
7 0-10 VDC Power (kW)
8 2-10 VDC Power (kW)
9 Network ControlledRequires optional communication
10 Sequencer ControlledValue set in individual sequencer
Invert
P142
0NONO
1NOYES
2YESNO
3YESYES
Used to invert the selections for
Invert
P140 (Relay Output) and P142 (TB-14
P140
Output).
EXAMPLE: When P140 = 6 (AT
SPEED), the relay is energized when
output frequency = commanded
frequency. IF P144 = 1 or 3, then
P140 is inverted (INVERSE AT SPEED)
and the relay is energized when the
output frequency does not equal the
command frequency.
if motor load falls below P145 value
longer than P146 time
• Digital outputs can also indicate a
loss of 4-20 mA signal; see P140,
P142
2.0 0.0 {mA} 10.0
Set voltage for bus compensation in
V/Hz mode
10 4 kHz• As carrier frequency is increased,
1 6 kHz
2 8 kHz
3 10 kHz
motor noise is decreased
• Observe derating in Section 2.2
• Automatic shift to 4 kHz at 120%
load
ref
0V
10V
(20mA)
V0111
33
Commissioning
CodePossible Settings
No.NameDefault Selection
(1)
Base Frequency 60.0 10.0 {Hz} 1500
P167
Fixed Boost0.0 {%} 30.0
P168
Note
• P167 = rated motor frequency for standard applications
• P168 default setting depends on drive rating
Accel Boost0.0 0.0 {%} 20.0Accel Boost is only active during
P169
Slip
P170
Compensation
(1)
Current Limit200 30 {%} CLim
P171
Current Limit
P172
Reduction
Decel Override
P173
Time
DC Brake
P174
Voltage
0.0 0.0 {%} 10.0Increase P170 until the motor speed
00 Current Limit Reduction
Active - Normal response
1 Current Limit Reduction Active
- Fast response
2 Current Limit Reduction
Disabled - Normal response
3 Current Limit Reduction
Disabled - Fast response
2.0 0.0 {s} 60.0Maximum time before drive trips into
0.0 0.0 {%} 30.0Setting is a percent of the nominal
acceleration
no longer changes between no load
and full load conditions.
• When the limit is reached, the
max
drive displays
acceleration time increases or the
output frequency decreases.
• Digital outputs can also indicate
when the limit is reached; see
P140, P142.
• Refer to section 2.2 for CLim
In eld weakening, the Current Limit
is inversely proportional to the speed.
HF fault.
DC bus voltage.
IMPORTANT
V0112
CL, and either the
max
(1) The drive can only be restarted if the error message has been reset
34
Commissioning
CodePossible Settings
No.NameDefault Selection
DC Brake Time0.0 0.0 {s} 999.9
P175
Note
CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING
DC Brake voltage (P174) is applied for the time specied by P175 with
the following exceptions:
• If P111=1, 3 and P175=999.9 the brake voltage will be applied
continuously until a run or fault condition occurs.
• If P110=2, 4…6 and P175=999.9, brake voltage will be applied for 15s
• If P121…P123=18 and the corresponding TB-13 input is CLOSED,
brake voltage will be applied until the TB-13 input is OPENED or a
fault condition occurs.
Keypad Setpoint
P176
Single Press
Increment
(2)
Speed Units00 HzSelect the UNITS LED that will be
P177
Display
P178
Frequency
Multiplier
Run Screen
P179
Display
Oscillation
P180
Damping Control
0.1 0.1 100.0Used for run screen setpoint editing
1 RPM
2 %
3 /UNITS
4 NONE
0.00 0.00 650.00 • Allows frequency display to be
Example: If P178 = 29.17 and actual frequency = 60 Hz,
00 {Parameter Number} 599 • 0 = Normal Run Screen, this display
00 800 = Damping disabled
Drive displays 1750 (rpm)
only. If P176>0.1 then scrolling of
keypad setpoint is disabled.
illuminated when the drive is running
in speed control mode. For this
parameter to be used, P178 must be
set to a value other than 0. IF P178 is
set to 0, the Hz LED will be illuminated
regardless of the value set in P177.
scaled
• P178 = 0.00: Scaling disabled
• P178 > 0.00: Display = Actual
Frequency X P178
depends on mode of operation.
See Section 4.2.
• Other selections choose a
diagnostic parameter to display
(P501…P599).
• Parameters P560 - P564 are
selectable if the sequencer is
enabled (P700 is not 0). P560 - P564
are not visible until P700 is enabled.
Compensation for resonances within
drive
IMPORTANT
(2) Parameter applicable to models 15HP (11kW) and higher.
35
Commissioning
CodePossible Settings
No.NameDefault Selection
Skip frequency 10.0 0.0 {Hz} 500• Drive will not run in the dened skip
P181
Skip frequency 20.0 0.0 {Hz} 500
P182
Skip frequency
P184
bandwidth
Voltage
P185
Midpoint V/Hz
characteristic
(2)
Frequency
P187
Midpoint V/Hz
characteristic
Motor Braking0 Disabled
P190
Motor Brake
P191
Level
Motor Braking
P192
Deceleration
Reduction Level
Password225 0000 9999• Must enter password to access
P194
0.0 0.0 {Hz} 10.0
Note
Bandwidth (Hz) = fs (Hz) + P184 (Hz) fs = P181 or P182
Example: P181 = 18 Hz and P184 = 4 Hz; skip range is from 18 to 22 Hz
00.0 {V} P165Valid only when P300 = 0 or 2.
0.0 0.0 {Hz} P167Valid only when P300 = 0 or 2.
1 Braking with BUS threshold
2 Braking always on with
deceleration
3 Braking with bus regulator
4 Special (Consult factory
before using)
00 {%} 75
(ux
braking
disabled)
0.0 0 P167
(base freq)
Raising the value of P191
reduces the drive deceleration
rate during ux braking.
range; used to skip over frequencies
that cause mechanical vibration
• P181 and P182 dene the start of
the skip ranges
• P184 > 0 denes the bandwidth of
both ranges.
Use with P187 to dene midpoint on
V/Hz curve.
Use with P185 to dene midpoint on
V/Hz curve.
Active when P190 > 0 and drive is in
deceleration mode. Use to reduce
deceleration time on high inertia loads.
NOTE: Over usage of P190 can cause
frequent ‘overload’ trips “F.PF”
Not active for P300 = 5 (Torque mode)
Active when P190 > 0 and P192 > 0.0,
Drive is in deceleration mode. Use
to reduce deceleration time on high
inertia loads.
NOTE: Usage of P192 can cause
the drive to decelerate faster than
settings in P105/P127.
Not active for P300 = 5 (Torque mode)
parameters
• P194 = 0000: Disables password
IMPORTANT
(2) Parameter applicable to models 15HP (11kW) and higher.
36
Commissioning
CodePossible Settings
No.NameDefault Selection
P197
P199
Clear Fault
History
Program
Selection
00 No Action
1 Clear Fault History
0 Operate from User settings
1 Operate from OEM settings See Notes 1, 2 and 3
2 Reset to OEM default
settings
3 Reset to 60 Hz default
settings
4 Reset to 50 Hz default
settings
5 TranslateSee Note 5
WARNING!
Modication of P199 can affect drive functionality! STOP and EXTERNAL
FAULT circuitry may be disabled! Check P100 and P121...P123
Note 1
If the EPM does not contain valid OEM settings, a ashing GF will be
displayed when P199 is set to 1 or 2.
Note 2
When P199 is set to 1, the drive operates from the OEM settings stored
in the EPM Module and no other parameters can be changed (
be displayed if attempted).
Note 3
Auto Calibration is not possible when operating from OEM Settings.
Note 4
Reset 60 and Reset 50 will set the Assertion Level (P120) to “2” (High).
P120 may need to be reset for the digital input devices being used.
An F.AL fault may occur if P120 and the Assertion switch are not set
identically.
Note 5
If an EPM that contains data from a previous compatible software
version is installed:
• The drive will operate according to the previous data, but parameters
cannot be changed (
• To update the EPM to the current software version, set P199 = 5. The
parameters can now be changed but the EPM is incompatible with
previous software revisions.
IMPORTANT
See Note 1
• See Note 4
• Parameters are reset to the
defaults listed in this manual.
• For P199=4, the following
exceptions apply:
- P103, P152, P161, P167 = 50.0 Hz
- P304 = 50 Hz;
- P305 = 1450 RPM
- P107 = 0 (480 V drives only)
cE will be displayed if attempted)
GE will
37
Commissioning
4.5.4 PID Parameters
CodePossible Settings
No.NameDefault Selection
PID Mode00 Disabled• Normal-acting: As feedback
P200
1 Normal-acting
2 Reverse-acting
3 Normal-acting, Bi-directional
4 Reverse-acting, Bi-directional
Note
To activate PID mode, one of the TB-13 inputs (P121...P123) must
be used to select the Auto Reference that matches the desired PID
setpoint reference. If the selected PID setpoint reference uses the same
analog signal as the PID feedback (P201), an
Example: The desired PID setpoint reference is the keypad (s and t).
Set TB-13x = 6 (Auto Reference: Keypad):
• TB-13x = closed: PID mode is active
• TB-13x = open: PID mode is disabled and the drive speed will be
controlled by the reference selected in P101.
PID Feedback
P201
Source
PID Decimal
P202
Point
(2)
PID Units00 %Select the UNITS LED that will be
P203
Feedback at
P204
Minimum Signal
Feedback at
P205
Maximum Signal
00 4-20 mA (TB-25)Must be set to match the PID
1 0-10 VDC (TB-5)
10 PID Display = XXXXApplies to P204, P205, P214, P215,
1 PID Display = XXX.X
2 PID Display = XX.XX
3 PID Display = X.XXX
4 PID Display = .XXXX
1 /UNITS
2 AMPS
3 NONE
0.0 -99.9 3100.0 Set to match the range of the
100.0 -99.9 3100.0
increases, motor speed decreases
• Reverse-acting: As feedback
increases, motor speed increases
• PID mode is disabled in Vector
Torque mode (P300 = 5)
• Selections 3, 4: If P112=1, PID
controller output sets the speed,
(range -max freq to +max freq)
feedback signal
P231...P233, P242, P522, P523
illuminated when the drive is running
in PID control mode
feedback signal being used
Example: Feedback signal is 0 - 300
PSI; P204 = 0.0, P205 = 300.0
IMPORTANT
F.IL fault will occur.
(2) Parameter applicable to models 15HP (11kW) and higher.
38
Commissioning
CodePossible Settings
No.NameDefault Selection
Proportional
P207
Gain
Integral Gain0.0 0.0 {s} 20.0
P208
Derivative Gain0.0 0.0 {s} 20.0
P209
PID Setpoint
P210
Ramp
Minimum Alarm0.0 P204 P205Use with P140, P142 = 18...23
P214
Maximum Alarm0.0 P204 P205
P215
Preset PID
P231
Setpoint #1
Preset PID
P232
Setpoint #2
Preset PID
P233
Setpoint #3
(2)
Preset PID
P234
Setpoint #4
Sleep Threshold0.0 0.0 {Hz} 500.0• If drive speed < P240 for longer
P240
Sleep Delay30.0 0.0 {s} 300.0
P241
Sleep Bandwidth 0.0 0.0 B
P242
Feedback Sleep
P243
Entry Threshold
5.0 0.0 {%} 100.0Used to tune the PID loop:
Note
• Derivative Gain is very sensitive to noise on the feedback signal and
must be used with care
• Derivative Gain is not normally required in pump and fan applications
20.0 0.0 {s} 100.0• time of setpoint change from P204
0.0 P204 P205TB-13A activated; P121 = 3 and
0.0 P204 P205TB-13B activated; P122 = 3 and
0.0 P204 P205TB-13C activated; P123 = 3 and
0.0 P204 P205TB-13D activated; P124 = 3 and
Where: B
0.0 P204 P205Active only when P244 = 1 or 2
= |(P205 - P204)|
max
• Increase P207 until system
becomes unstable, then decrease
P207 by 10-15%
• Next, increase P208 until feedback
matches setpoint
• If required, increase P209 to
compensate for sudden changes in
feedback
to P205 or vice versa.
• Used to smooth the transition
from one PID setpoint to another,
such as when using the Preset PID
Setpoints
(P231...P233)
P200 = 1 or 2
P200 = 1 or 2
P200 = 1 or 2
P200 = 1 or 2
than P241, output frequency = 0.0
Hz; drive display =
• P240 = 0.0: Sleep mode is
max
disabled.
• P200 = 0…2: Drive will start again
when speed command is above
P240
• P242 > 0.0: Drive will restart when
the PID feedback differs from the
setpoint by more than the value
of P242 or when the PID loop
requires a speed above P240.
IMPORTANT
(2) Parameter applicable to models 15HP (11kW) and higher.
SLP
39
Commissioning
CodePossible Settings
No.NameDefault Selection
Sleep Entry
P244
Mode
Sleep Entry Stop
P245
Type
Feedback
P246
Recovery
from Sleep
Threshold
Sleep Recovery
P247
Mode
Auto Rinse in
P250
Sleep
Mode
Time Delay
P251
between
Auto Rinses
Auto Rinse
P252
Speed
Auto Rinse Time0.0 0.0 {sec} 6553.5Does not include time to decel back
P253
00 Enter SLEEP if Drive Speed
<P240
1 Enter SLEEP if Feedback
>P243
2 Enter SLEEP if Feedback
<P243
00 Coast to Stop
1 Ramp to Stop
2 Stop with P111 settings
0.0 P204 P205Active only when P247 = 1 or 2
00 Recovery if Speed Setpoint
> P240 or if PID feedback
differs from setpoint by more
than P242
1 Recovery only if Feedback
< P246
2 Recovery only if Feedback
> P246
00 DisabledActivated in sleep mode only.
1 EnabledSleep Recovery cancels Auto Rinse
30.0 0.0 {min} 6553.5 Time delay reset by re/entering sleep
• Format: n.xxx where: n = 1..8,
1 is the newest fault; xxx = fault message
(w/o the F.)
• Refer to section 5.3
hours, seconds.
The “hhhh” screen is displayed after hours
exceed 999.
For example: 3 external faults occur over a
period of time with no other errors occurring.
Then P552 will indicate 3, P550 will indicate
the error EF and P551 will indicate the time of
the rst fault occurrence.
Unit depends on P708 (0.1sec, sec or minutes)
IMPORTANT
46
Commissioning
Code
No.Name
Sequencer: Time
P562
Remaining in
Active Segment
Sequencer:
P563
Number of
cycles since
start
Sequencer:
P564
Number of
cycles remaining
Display Range
(READ ONLY)
0.0 {P708} 6553.5
0 {P708} 65535
0 65535
0 65535
Note: Parameters P560-P564 are visible only when P700 > 0 (i.e. the
sequencer is enabled)
4.5.7.1 Terminal and Protection Status Display
Parameter P530 allows monitoring of the control terminal
points and common drive conditions:
An illuminated LED segment indicates:
• the protective circuit is active (LED 1)
• the Logic Assertion Switch is set to High (+)
• input terminal is asserted (LED 2)
• output terminal is energized (LED 4)
• the Charge Relay is not a terminal, this segment will
be illuminated when the Charge Relay is energized
(LED 4)
IMPORTANT
Unit depends on P708 (0.1sec, sec or minutes)
4.5.7.2 Keypad Status Display
Parameter P531 allows monitoring of the keypad
pushbuttons:
An illuminated LED segment indicates when the button
is depressed.
LED 1 and LED 2 are used to indicate pushbutton
presses on a remote keypad that is attached to the
drive. LED 3 and LED 4 indicate button presses on the
local drive keypad.
If P795 = 0 then toggling the start sequence input will also restart the
sequencer cycle but in the interim where TB13X is open the drive will
ramp to the standard or specied alternate speed source depending on
the drive conguration.
WARNING
If the input dened to “Start Sequence” is opened during a sequence, the
drive will exit sequencer mode and will run at the specied standard or
alternate speed source (dependent on drive conguration).
IMPORTANT
bit = 1: ON (Energized)
The corresponding digital output/
relay must be set to accept value the
from the sequencer: P140, P142=27
be set to accept this value: P150
= 10
SEQUENCE will start the cycle
from ‘end segment Stop’ or ‘end
segment DC Brake’.
57
Commissioning
4.5.9.1 Sequencer Parameters
Sequencer Flow Diagram
Digital Input priority:
TB-13A -Lowest
TB-13B
TB-13C
Drive Stop/Start Control
Start from
Local Keypad
Start from
Terminal Strip
TB-13D - Highest
(2)
P100
0
1
2
Start from
Remote Keypad
(1)
Start from Network
(SMV communications
module)
(1)
Refer to relevant communications module user guide for starting from a
(1) Refer to relevant communications module user guide for
communications network, RS485 etc..
starting from a communications network, RS485 etc.
(2)
Refer to P100 description in the SMV Operating instructions for further
(2) Refer to P100 description in the Operating instructions for
further combinations of start sources.
(3) TB-13D available on models rated 15HP (11kW) or greater.
> Selections shown as default values
3
If none of the digital inputs (TB-13A,B,C or D) are asserted
but a start signal is given from the Start/Stop source (P100)
then the drive will run at the output frequency value governed by
the frequency reference source (P101).
P700
Notes
Notes
(3)
Sequencer
mode
disabled
0
1
2
3
WARNING
P12124 P122
3
2
“Start Segment” number selection
TB-13B
TB-13A
TB-13C
P123
24
24
P124
TB-13D
24
Segment
Start
Segment
P702
Start
Segment
P703
Start
Segment
P704
Start
P701
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
58
WARNING
If the input dened to “Start Sequence” is opened during a sequence, the
drive will exit sequencer mode and will run at the specied standard or
alternate speed source (dependent on drive conguration).
4.5.9.2 Sequencer Parameters
Commissioning
Action after Stop/Start (P100) transition/digital input (if setup for
sequencer mode) transition or restart after trip.
P706
Action
Restart at beginning of sequence (pointed by TB13x)
0
Restart at beginning of current segment
1
2
Start at beginning of prior segment
3
Start at beginning of next segment
1
2
3
P
P712
P710
1
1
7
P
P720
7
1
6
P715
21
P7
P722
P717
SUSPEND SEQUENCE
Asserting input will suspend
sequencer in the currently active
segment, and when un-asserted
sequencer will continue to complete
the time remaining in the segment
TB-13x
P121/2/3/4
26
Suspend Sequencer
5
P7
P732
P730
3
6
P
7
3
1
6
P737
P735
7
P
P742
8
P740
P
1
7
4
4
7
P747
6
P745
10
9
P
P750
7
5
1
6
5
P7
P752
P757
4
P7
2
6
P725
P727
Number of repeat Cycles P707
Ramp with DC Brake (See P174/P175)
Coast with DC Brake (See P174/P175)
Quick Stop (based on P128)
Keep running (based on P790)
(4)
The end segment is entered once the highest number segment with a non-zero value in the
“time in current segment” (P712/P711 etc..) parameter has completed and the number of
repeat cycles P707 has completed.
> A value of “0” in the segment time (P712 etc.) will result in the segment being skipped.
> Segment time and Accel/Decel (P712/P711 etc.) scaling is seconds as default.
> The sequencer will start from the segment pointed to by the digital input with the highest priority.
> Selections shown as default values.
Notes
11
P760
1
6
7
P755
P
P762
Coast to Stop
Stop (based on P111)
12
P
7
6
6
P765
P767
1
14
P770
2
3
5
4
3
2
1
0
P
7
7
P777
Segment
3
2
0
2
0
15
6
P775
P
P782
No
(4)
End
13
1
77
P
P772
3
P780
1
8
7
Number of
completed
Yes
P791
P795
16
P
7
8
6
P785
P787
cycles set
in P707
?
P790
P792
59
Commissioning
4.5.9.3 Sequencer Status
Internal 0-10V reference
P150 = 10
Segment 1 active
Segment 2 active
Segment 3 active
Segment 4 active
Segment 5 active
Segment 6 active
Segment 7 active
Segment 8 active
Segment 9 active
Segment 10 active
Segment 11 active
Segment 12 active
Segment 13 active
Segment 14 active
Segment 15 active
Segment 16 active
End Segment active
End
Segment Delay
P792
Output Voltage
P714
Output Voltage
P719
Output Voltage
P724
Output Voltage
P729
Output Voltage
P734
Output Voltage
P739
Output Voltage
P744
Output Voltage
P749
Output Voltage
P754
Output Voltage
P759
Output Voltage
P764
Output Voltage
P769
Output Voltage
P774
Output Voltage
P779
Output Voltage
P784
Output Voltage
P789
Output Voltage
P794
TB30
60
NOTE
On the “End Segment”, the output voltage is not present until after the end
segment delay P792 has expired. On the other segments the output voltage is
present on entry to the segment. The same is true for the digital outputs.
data from a previous software
version has been installed
Current Limit (P171) reachedMotor overload• Increase P171
CL
Decel OverrideThe drive has stopped
dEC
ErrorInvalid data was entered, or an
Err
Fast Current LimitOverloadVerify drive/motor are proper
FCL
Flying Restart Attempt after Fault P110 = 5,6
fst
OEM Settings Operation
GE
warning
OEM Defaults data warningAn attempt was made to use
GF
Fault LockoutThe drive attempted 5 restarts
LC
• activation of digital input
(P121...P123 = 18)
• automatically (P110 = 2, 4...6)
• automatically (P111 = 1, 3)
the EPM does not match the
drive model.
See P300, P399
An attempt was made to
change parameter settings
decelerating to avoid tripping
into
HF fault, due to excessive
motor regen (2 sec max).
invalid command was attempted
An attempt was made to
change parameter settings
while the drive is operating in
OEM Settings mode (P199 = 1)
(or reset to) the OEM default
settings (P199 = 1 or 2) using an
EPM without valid OEM data.
after a fault but all attempts
were unsuccessful (P110 = 3...6)
Deactivate DC-injection brake
• deactivate digital input
• automatically after P175 time
has expired
• Verify motor data
(P302…P306) and perform
Auto Calibration.
• Set drive mode (P300) to 0 or
1
• Reset the drive (P199 to 3 or
4) and reprogram.
Parameter settings can only be
changed after the EPM data is
converted to the current version
(P199 = 5)
• Verify drive/motor are proper
size for application
If drive trips into
• Increase P105, P126
• Install Dynamic Braking
option
size for application
In OEM Settings mode, making
changes to parameters is not
permitted
Install an EPM containing valid
OEM Defaults data
• Drive requires manual reset
• Check Fault History (P500)
and correct fault condition
HF fault:
61
Troubleshooting and Diagnostics
Status / WarningCauseRemedy
PID Deceleration StatusPID setpoint has nished
PdeC
PID Mode ActiveDrive has been put into PID
PID
Sleep Mode is activeSee P240...P242
SLP
Start PendingThe drive has tripped into a
SP
PID Mode disabled.Drive has been taken out of PID
spd
Output frequency = 0 Hz
stoP
(outputs U, V, W inhibited)
its ramp but the drive is still
decelerating to a stop.
Mode. See P200.
fault and will automatically
restart (P110 = 3...6)
Mode. See P200.
Stop has been commanded
from the keypad, terminal strip,
or network
To disable Auto-Restart, set
P110 = 0...2
Apply Start command (Start
Control source depends on
P100)
62
Troubleshooting and Diagnostics
5.2 Drive Conguration Messages
When the Mode button is pressed and held, the drive’s display will provide a 4-digit code that
indicates how the drive is congured. If the drive is in a Stop state when this is done, the display
will also indicate which control source commanded the drive to Stop
(the two displays will alternate every second).
L.stp = Stop command came from Local Keypad
t.stp = Stop command came from Terminal Strip
r.stp = Stop command came from Remote Keypad
n.stp = Stop command came from Network
y = Mode:
S = Speed mode
P = PID mode
t = Vector Torque mode
Stop Source Display
zz = Reference:
CP = Keypad s t
EU = 0-10 VDC (TB-5)
E1 = 4-20 mA (TB-25)
JG = Jog
nt = Network
OP = MOP
P1...P7 = Preset 1...7
01...16 = Sequencer
Segment
63
Troubleshooting and Diagnostics
5.3 Fault Messages
The messages below show how they will appear on the display when the drive trips. When
looking at the Fault History (P500), the F. will not appear in the fault message.
FaultCause
High Temperature faultDrive is too hot inside• Reduce drive load
f.AF
Assertion Level fault• Assertion Level switch is
f.AL
changed during operation
• P120 is changed during
operation
•
P100 or P121...P123 are set
to a value other than 0 and
• Improve cooling
• Make sure the Assertion Level
switch and P120 are both set
for the type of input devices
being used, prior to setting
P100 or P121...P123.
See 3.2.3 and P120.
P120 does not match the
Assertion Level Switch.
Personality faultDrive Hardware • Cycle Power
f.bf
Control faultAn EPM has been installed that is
f.CF
Incompatible EPM fault An EPM has been installed
f.cF
Dynamic Braking faultDynamic braking resistors are
f.dbF
External fault• P121…P123 = 21 and that
f.EF
EPM faultEPM missing or defectivePower down and replace EPM
f.F1
Internal faultsContact factory technical support
f.F2
…
f.F12
Control Conguration
f.Fnr
Fault
Loss of 4-20 mA signal
f.FoL
fault
OEM Defaults data fault Drive is powered up with
f.GF
either blank or corrupted
that contains data from an
incompatible parameter version
overheating
digital input has been opened.
• P121…P123 = 22 and that
digital input has been closed.
The drive is setup for REMOTE
KEYPAD control (P100=2 or 5) but
is not setup to communicate with
a remote keypad
The drive is setup for NETWORK
ONLY control (P100=3) but is not
setup for network communications
4-20 mA signal (at TB-25) is below
2 mA (P163 = 1)
P199 =1 and OEM settings in the
EPM are not valid.
• Power down and install EPM
with valid data
• Reset the drive back to defaults
(P199 = 3, 4) and then re-
program
• If problem persists, contact
factory technical support
• Increase active decel time
(P105, P126, P127).
• Check mains voltage and P107
• Correct the external fault
condition
• Make sure digital input is set
properly for NC or NO circuit
Set P400 = 1, or P600 = 1
Set P400 or P600 to a valid
network communications protocol
selection
Check signal/signal wire
Install an EPM containing valid
OEM Defaults data or change
P199 to 0.
(1) The drive can only be restarted if the error message has been resent.
Low DC Bus Voltage fault Mains voltage too lowCheck mains voltage
f.LF
No Motor ID faultAn attempt was made to start the
f.n1d
Module communication
f.ntF
fault
Network FaultsRefer to the module documentation.
f.nF1
…
f.nF9
Output fault:
f.OF
Transistor fault
Mains voltage is too highCheck mains voltage and P107
Decel time is too short, or too
much regen from motor
More than one digital input set for
the same function
Only one digital input congured
for MOP function (Up, Down)
PID mode is entered with setpoint
reference and feedback source
set to the same analog signal
One of the digital inputs (P121…
P123) is set to 10 and another is
set to 11…14.
One of the digital inputs (P121…
P123) is set to 11 or 12 and
another is set to 13 or 14.
PID enabled in Vector Torque mode
(P200 = 1 or 2 and P300 = 5)
drive in Vector or Enhanced V/
Hz mode prior to performing the
Motor Auto-calibration
Communication failure between
drive and Network Module.
for Causes and Remedies.
Output short circuitCheck motor/motor cable
Acceleration time too shortIncrease P104, P125
Severe motor overload, due to:
• Mechanical problem
• Drive/motor too small for
application
Boost values too highDecrease P168, P169
Excessive capacitive charging
current of the motor cable
Failed output transistorContact factory technical support
Increase active decel time
(P105, P126, P127) or install
Dynamic Braking option
Each setting can only be used
once (except settings 0 and 3)
One input must be set to MOP Up,
another must be set to MOP Down
Change PID setpoint reference
(P121…P123) or feedback source
(P201).
Recongure digital inputs
PID cannot be used in Vector
Torque mode
See P300…P399 for Drive Mode
setup and calibration.
Check module connections
• Check machine / system
• Verify drive/motor are proper
• Use shorter motor cables with
• Use low capacitance motor
• Install reactor between motor
Remedy
size for application
lower charging current
cables
and drive.
(1) The drive can only be restarted if the error message has been resent.
(1)
65
Troubleshooting and Diagnostics
FaultCause
Output fault: Ground
f.OF1
fault
Motor Overload faultExcessive motor load for too long • Verify proper setting of P108
f.PF
Flying Restart faultController was unable to
f.rF
Single-Phase faultA mains phase has been lostCheck mains voltage
f.SF
Start faultStart command was present when
f.UF
Grounded motor phaseCheck motor and motor cable
Excessive capacitive charging
current of the motor cable
synchronize with the motor during
restart attempt; (P110 = 5 or 6)
power was applied (P110 = 0 or 2).
Use shorter motor cables with
lower charging current
• Verify drive and motor are
proper size for application
Check motor / load
• Must wait at least 2 seconds
after power-up to apply Start
command
• Consider alternate starting
method (see P110).
(1) The drive can only be restarted if the error message has been reset.
Remedy
(1)
66
66
Appendix
Appendix A
A.1 Permissable Cable Lengths
The table herein lists the permissable cable lengths for use with an SM Flux Vector inverter with an
internal EMC lter.
NOTE
This table is intended as a reference guideline only; application results may
vary. The values in this table are based on testing with commonly available
low-capacitance shielded cable and commonly available AC induction motors.
Testing is conducted at worst case speeds and loads.
Maximum Permissible Cable Lengths (Meters) for SM Flux Vector Models
MainsModel4 kHz Carrier
ESV251GG2SFG 3812351033530N/A
ESV371GG2SFG 3812351033530N/A
ESV751GG2SFG 3812351033530N/A
(2/PE)
ESV112GG2SFG 3812351033530N/A
240 V, 1-phase
ESV152GG2SFG 3812351033530N/A
ESV222GG2SFG 3812351033530N/A
ESV371GG4TFG 30425220N/A10N/A
ESV751GG4TFG 30425220N/A10N/A
ESV112GG4TFG 30425220N/A10N/A
ESV152GG4TFG 30425220N/A10N/A
ESV222GG4TFG 30425220N/A10N/A
(3/PE)
ESV302GG4TFG 30425220N/A10N/A
400/480 V,3-phase
ESV402GG4TFG 545483422N/AN/A
ESV552GG4TFG 545483422N/AN/A
ESV752GG4TFG 545483422N/AN/A
NOTE: The “GG” and “G” symbols are place holders in the Model part number that contain different
information depending on the specic conguration of the model.
with Internal EMC Filters
(P166 = 0)
Class AClass BClass AClass BClass AClass BClass AClass
6 kHz Carrier
(P166 = 1)
8 kHz Carrier
(P166 = 2)
10 kHz Carrier
(P166 = 3)
B
Important Information
Resale of Goods
In the event of the resale of any of the goods, in whatever form, Resellers/Buyers will include the
following language in a conspicuous place and in a conspicuous manner in a written agreement
covering such sale:
The manufacturer makes no warranty or representations, express or implied, by operation
of law or otherwise, as to the merchantability or tness for a particular purpose of the goods
sold hereunder. Buyer acknowledges that it alone has determined that the goods purchased
hereunder will suitably meet the requirements of their intended use. In no event will the
manufacturer be liable for consequential, incidental or other damages. Even if the repair or
replacement remedy shall be deemed to have failed of its essential purpose under Section
2-719 of the Uniform Commercial Code, the manufacturer shall have no liability to Buyer for
consequential damages.
Resellers/Buyers agree to also include this entire document including the warnings and cautions
above in a conspicuous place and in a conspicuous manner in writing to instruct users on the safe
usage of the product.
This information should be read together with all other printed information supplied by LEESON
Electric.
For more information contact: LEESON Electric, 1051 Cheyenne Avenue, Grafton, Wisconsin 53024
Phone: 262-377-8810 Fax: 262-377-9025.
LEESON Electric
Grafton, Wisconsin 53024 U.S.A.
PH: 262-377-8810
FAX: 262-377-9025