VARI-PRIME
TM
Document 7031Installation Kit
®
VARI-PRIME
TM
Installation Kit for
N
EOTHERM
Modulating Boilers with EMEA Display
Model NTH. Sizes 285–850 MBTU/h
FOR YOUR SAFETY: This procedure must be performed by a professional service technician, qualied in
hot water boiler installation. Improper connections could create an electrical hazard, which could cause
serious injury, property damage, or death.
VARI-PRIMETM: A variable pump control that, when used with a variable speed pump, maintains a user-chosen temperature rise
between the inlet and outlet of the boiler.
GENERAL PCB OPERATION:
1. The desired Delta T can be set to any of the following values by moving or adding jumpers to the (JP2) terminal on the control:
See Figure 2.
15 deg F/8 deg C 20 deg F/10 deg C 25 deg F/13 deg C 30 deg F/ 16 deg C
By adding a second jumper, one on “15 deg F” and one on “20 deg F”, it is possible to achieve 35 deg F /19 deg C.
By adding a second jumper, one on “15 deg F” and one on “25 deg F”, it is possible to achieve 40 deg F/22 deg C.
2. As shipped, the VARI-PRIME has a jumper on the (JP4) terminal, to operate a 0-10 VDC output. If a 4-20 mA output is needed,
move the jumper to the (JP5) terminal.
3. VARI-PRIME can operate in °F or °C. A jumper on the (JP1) terminal has set the default to °F. Remove that jumper for °C.
4 If Main Gas valve is “OFF” AND a call for heat is “TRUE” then the PCB overrides the PID control and runs the pump
output at 100% (10 VDC, or 20 mA).
5. Once the Main Gas valve is energized the PCB will maintain pump output at 100% for 60 seconds to allow the system to stabilize.
Once the 60 second timer has expired, the PCB will then run the pump output speed based on the jumper setpoint.
6. When“T-T”issatised,thePCBwillrunpumpat100%outputforthedurationofthepumpoverruntime.
7. The VARI-PRIMEPCBhasalowendcaptopreventnuisancelowowtrips.Thecapisfactoryprogrammedto2VDC.
8. Factory settings are: Degrees - Fahrenheit Output Signal - 0 -10VDC
INSTALLATION INSTRUCTIONS
P.I.D. CONTROL ADJUSTMENT:
With Variable Speed Pumping, the boiler control P.I.D. needs to be adjusted.
• These settings are found in your NeoTherm controls under:
AdvancedSetup>CHCong>CHCong
It is recommended to start with:
P = 20 I =15 D = Factory set-point
Depending on pump sizing and application requirements; these P.I.D. settings may
needtobeusedtone-tuneboilerperformance.
• Once you have adjusted the P.I.D. contols, then disconnect power source from boiler.
• Remove front panels from boiler.
• Mount the VARI-PRIME control box in desired location. The side of the boiler is an
acceptable mounting location.
Important: Ensure there is nothing on the back side of the jacket before mounting.
• Run the wires from the VARI-PRIME control box, through the chosen ‘knock-out’ hole
and into the boiler. See Figure 1. Power wires must be run through conduit from the
VARI-PRIME box to the boiler. The Black and White wires are for the 120V pump contact.
Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583
Headquarters: 20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com Litho in U.S.A. © Laars Heating Systems 1405 Document 7031
Figure 1
H2368400
pg 1 of 4
POWER CONNECTIONS:
FIRMWARE SETTINGS
P = 20
I = 10
D = 0
ANTI RESET WINDUP = 600
CONTROL ERROR = 70
10K
R14 C12 R13 C11
2
4
V
INLET
SENSOR
1
2
3
4
1
2
3
4
1
2
3
2
3
4
4
1
1
2
3
2
4
6
8
1
3
5
7
1
3
5
7
+
2
4
V
6
8
SENSOR
2
4
10K OUTLET
JP5
TB1
7&8 = F
1&2 = SPARE JUMPER
TB2
TB5
TB4
TB6
PCB
DIGITIZED
P/N E2345200
LED1
JP1
7&8 = (Delta T) 30 DEG F / 16 DEG C
TB3
JP4
JP2
1&2 = (Delta T) 15 DEG F / 8 DEG C
3&4 = (Delta T) 20 DEG F / 10 DEG C
5&6 = (Delta T) 25 DEG F / 13 DEG C
JP3
N/C
COM
4-20MA(-)
4-20MA(+)
0-10VDC(+)
0-10VDC(-)
N/O
• Connect the Blue wire anywhere on the
24V+ boiler Terminal Block (TB3).
• Connect the Yellow wire anywhere on the
24V Neutral boiler Terminal Block (TB4).
• Connect the White wire to the
boiler pump connections on
boiler Terminal Block (TB5)
across from the other white wire.
• Connect the Black wire to the
other boiler pump connection on
boiler Terminal Block (TB5).
• Locate the Blue Gas Valve power wire coming from the Sola control.
Trace the wire through where it passes into the back panel, and locate
therstwire.Disconnectthemale/femalespadeconnection.Insertthe
VARI-PRIME connections as shown.
FIELD CONNECTIONS:
• Remove VARI-PRIME Cover.
• Remove the VARI-PRIME control box from the packaging and
familiarize yourself with each connection point.
See Figure 2
Terminal
Blocks
Figure 2
Headquarters: 20 Industrial Way, Rochester, NH 03867 • 603.335.6300 • Fax 603.335.3355
1869 Sismet Road, Mississauga, Ontario, Canada L4W 1W8 • 905.238.0100 • Fax 905.366.0130
www.Laars.com Litho in U.S.A. © Laars Heating Systems 1405 Document 7031
Jumpers
Customer Service and Product Support: 800.900.9276 • Fax 800.559.1583
H2368400
pg 2 of 4