KROHNE 70 User Manual

DIN A4: 7.02182.37.00
©
KROHNE 11/2000 US size: 7.02182.77.00
GR/LP
Status: 05-1998
Installation and operating instructions (Reference Manual)
Non-contact level gauging using electromagnetic waves
Variable area flowmeters
Vortex flowmeters
Flow controllers
Electromagnetic flowmeters
Ultrasonic flowmeters
Mass flowmeters
Level measuring instruments
Communications engineering
Engineering systems & solutions
Contents:
General advice on safety ................................3
Product liability and warranty .........................3
Items included with supply ..............................3
Software history ..............................................4
1. Range of application ................................6
2. Mode of operation and system structure.6
2.1 Operating principle ...................................6
2.2 Signal processing (digital) .........................7
2.3 Modularity (signal converter, flange,
antenna)....................................................7
3. Input...........................................................8
3.1 Measured variable (distance, level,
volume, reflection) ....................................8
3.2 Measuring range [0.5-35/40 m
(1.64-115/131 ft)] .....................................8
3.3 Block distance...........................................8
3.4 Out-of-range performance.........................8
4. Output........................................................9
4.1 Variants.....................................................9
4.2 Ex-e current output HART
4.3 Ex-i current output HART
(type of protection: Ex de [ia]) ................10
4.4 HART
®
communication............................11
®
....................10
®
4.5 Current output (non-communicable) .......11
4.6 Digital interface RS 485 .........................11
4.7 Breakdown signal .................................... 13
4.8 Digital input.............................................13
8. User interface ..........................................35
8.1 Local display .........................................35
8.2 Function of the keys ...............................36
8.3 Operator control concept........................37
8.4 Table fo settable functions
(Version 3.00, 3.03, 4.02, 4.03) .............39
8.5 Configuration examples..........................42
8.6 Description of functions..........................44
8.7 Functional checks...................................55
8.8 Pointers and error messages during
measurements.......................................56
8.9 Messages on start-up.............................58
8.10 Faults and symptoms during start-up
and measurement .................................58
8.11 Calculation of the measured value .......61
8.12 User program PC-CAT
for Windows .........................................62
9. Power supply ..........................................63
9.1 Options, technical data...........................63
9.2 Fuses ....................................................63
9.3 Changeover of operating voltage and
replacement of fuses .............................63
9.4 Advice on safety.....................................64
10. Certificates and approvals....................66
10.1 Hazardous-duty approvals.....................66
10.2 Other approvals and certificates ...........66
10.3 Explosion proof acc. to ATEX ...............67
10.4 Radio approval .....................................68
10.5 CE manufacturer’s declaration...............69
5. Measuring accuracy................................14
5.1 Reference conditions...............................14
5.2 Error of measurement ............................14
5.3 Repeatability ...........................................15
5.4 Measured value resolution/hysteresis .....15
5.5 Transient recovery time ..........................16
5.6 Turn-on drift / turn-on characteristics ......16
5.7 Long-term drift .......................................16
5.8 Effect of ambient temperature ................16
6. Operating conditions .............................17
6.1 Installation conditions .............................17
6.2 Ambient conditions..................................25
6.3 Product conditions................................... 26
6.4 Maintenance ......... .................................27
7. Design......................................................28
7.1 Models ..... .............................................28
7.2 Dimensions and weights .........................29
7.3 Replacement of the signal converter .......30
7.4 Field assembly ........................................ 30
Selection of antenna type and size..............31
7.5
7.6 Materials of construction .........................32
7.7 Process connection .................................32
7.8 Electrical connection ...............................33
7.9 Terminating resistor for the
RS 485 interface .....................................34
11. Order information .................................70
12. External standards, codes and
directives .............................................. 71
13. Quality assurance .................................71
Annex
Annex A: Technical Data ............................72
Annex B: Type code / nameplates...............74
Annex C: Spare parts .................................77
Annex D: Signed declaration to accompany
a device returned to KROHNE ....80
Annex E: Table on documentation of
device configuration....................81
Annex F: Index............................................82
BM 70 A/P Montage- und Betriebsanleitung Seite: 2 11/00
General advice on safety:
To carry: the device will weigh between approx. 16 kg (35.5 lb) and 30 kg (66.1 lb) or more! To
carry, use both hands to lift the device carefully by the converter housing. If necessary, use lifting gear.
When handling the BM 70 A/P, avoid hard blows, jolts, impacts, etc.
Product liability and warranty:
The BM 70 A/P level gauge is designed solely for measuring the distance, level, volume and reflection of liquids, pastes, slurries, solids and particulate materials.
The BM 70 A/P level gauge does not form part of an overfill protection system as defined in WHG. Special codes and regulations apply to its use in hazardous areas. Responsibility as to suitability and intended use of these level gauges rests solely with the user. Improper installation and operation of our level gauges may lead to loss of warranty. In addition, the "General conditions of sale", forming the basis of the purchasing contract, are appli-
cable. If you need to return the level gauge to the manufacturer or supplier, please refer to the information
given in Annex D.
Items included with supply:
The scope of supply encompasses, in the version as ordered:
Signal converter bolted to waveguide window and antenna
Optionally: antenna extension, sunshade (with fastening material in each case)
Shielding material with strap retainer (not for the US market)
Report on factory settings for the signal converter
Bar magnet for operator control / parameter assignment (only in version with local display)
Wrench for the covers
Installation material (stud bolts, flange gasket and cabling) not supplied, to be provided by customer!
Documentation supplied:
Condensed instructions: installation, connection, start-up and safety advice in condensed form,
but sufficient for most applications. Please read through these instructions first!
Instruction card: overview of the configuration menu and meaning of the markers in cheque card
format.
Installation and operating instructions (this manual): detailed user manual and reference book,
including description of special versions and functions. This documentation is structured on lines similar to those given in the DIN V 19259 Standard.
Approval documents, unless reproduced in the installation and operating instructions.
Installation and operating instructions BM 70 A/P Page: 3 11/00
Software history
Signal Converter Firmware
For BM 70 A:
Introduction Mth./Yr 06/97 3.00PREnn 06/97 Test versions 01/98 3.00 11/97-11/00 First serial version. Errors when empty spectrum recorded
05/98 3.01 11/97-11/00 Elimination of errors in V. 3.00; improved application of empty
07/99 3.02 05/98-11/00 Implementation of the ModBus protocol; adaptation to
11/99 3.03 05/98-11/00 Correction of a bug in the mode "Hold on Error" (output
Firmware Version
Device Instructions
Remarks
with WAVE-STICK; automatic reset when signal is extremely weak.
spectrum at tank bottom.
PROFIBUS interface; improved application of empty spectrum at tank bottom; improvement of PC-CAT protocol switching in multidrop operation; definition of 3.6 mA as lower error current for the IS current output; improved tank bottom tracing; improved spectrum evaluation at tank heights > 15 m.
current went to 1 mA or 3.6 mA; only V. 3.02); Adaption of the HART protocol for operation with the program AMS, and some smaller error corrections; Improved "tank bottom recognition" (measured value now always goes to the programmed tank bottom position); If no measured value is found after start-up, the instrument goes directly into "tank bottom recognition" and the local display to level = 0, if Fct.
3.2.5 Error Messages = NO is set.
For BM 70 P:
Introduction Mth./Yr 05/98 4.00PREnn
07/99 4.02 05/98-11/00 First serial version. 11/99 4.03 05/98-11/00 Correction of a bug in the mode "Hold on Error" (output
Firmware Version
4.01PREnn
4.02PREnn
Device Instructions 05/98 Test versions
Remarks
current went to 1 mA or 3.6 mA; only V. 4.02); Adaption of the HART protocol for operation with the program AMS, and some smaller error corrections; Improved "tank bottom recognition" (measured value now always goes to the programmed tank bottom position); If no measured value is found after start-up, the instrument goes directly into "tank bottom recognition" and the local display to level = 0, if Fct.
3.2.5 Error Messages = NO is set.
Installation and operating instructions BM 70 A/P Page: 4 11/00
Compatibility between PC-CAT Software and BM 70x Level-Radar Instruments
I N S T R U M E N T S
Software
(1)
Operating System
BM 70 BM 70 Nautic
BM 70 A BM 70 P
BM 700 BM 702
PC-CAT (DOS) 1.00 PC-CAT (DOS) 2.00
(4)
PC-CAT (DOS) 2.10/2.11 PC-CAT (DOS) 2.30
(4)
DOS 3.00 DOS 3.00 DOS 3.00
DOS 5.00
(7)
(2)
YES
(3)
YES
YES NO NO NO YES Up to firmw.
3.02/4.02
PC-CAT (DOS) 3.00
DOS 5.00
(7)
YES Up to firmw.
3.02/4.02
PC-CAT (DOS) 3.01
DOS 5.00
PC-CAT Windows 4.00/4.01 Windows
(7)
YES YES YES YES
NO YES YES YES
95,98,2000,NT
PC-CAT Windows Lite 4.01 Windows
NO YES YES YES
95,98,2000,NT
(1)
table is not including PRE versions of PC-CAT
(2)
limited to configuration parameters up to firmware 2.02/2.10
(3)
limited to configuration parameters up to firmware 2.20
(4)
Attention!! Does not run on fast PCs !!
(5)
with reduced display and configuration capability
(6)
not with firmware 7.00/PRE0x
(7)
or DOS-Window in Windows 3.1x, 9x (not Windows NT, 2000)
NO NO NO NO NO NO
(5)
Up to
firmw.
5.02 Up to
(5)
NO
NO
firmw. 5.02
(6)
Installation and operating instructions BM 70 A/P Page: 5 11/00
1 Range of application
The BM 70 A/P Level-Radar level gauging system is designed to measure the distance, level, volume and reflection of liquids, pastes, slurries, solids and particulate materials. It can be operated on storage and process tanks and also on stilling wells.
BM 70 P is specially designed for applications on storage tanks with highest precision requirements. BM 70 A/P Ex hazardous-duty versions are suitable for use in Ex-Zone 0, 1 and 2. In Germany (and, depending on the respective radio approval, in some other countries as well) its use
is restricted to closed tanks or containers made of metal or concrete. Because of the low output involved, however, the microwaves are not harmful to human beings.
2 Mode of operation and system structure
2.1 Operating principle (FMCW-Radar)
A radar signal is given via an antenna, reflected on the measuring surface and received after a delay time t.
FMCW: Frequency Modulated Continuous Wave
The FMCW-radar uses a high frequency signal (~10 GHz) which transmit frequency increasing linearly 1 GHz during the measurement (frequency sweep) (1). The signal is emitted, reflected on the measuring surface and received time-delayed (2). For further signal processing the difference f is calculated from the actual transmit frequency and the receive frequency (3). The difference is directly proportional to the distance i.e. a large frequency difference correspond to a large distance and vice versa.
The frequency difference is transformed via a Fourier transformation (FFT) into a frequency spectrum and then the distance is calculated from the spectrum. The level results from the difference between tank height and distance.
Linearity of frequency sweeps
The measuring accuracy of a FMCW radar is determined from the linearity of the frequency sweeps and their reproducibility. The linearity correction is deduced via reference measurement of the oscillator.
The non-linearity is corrected up to 98% (BM 700/BM 70 A). An immediate frequency regulation is necessary with the BM 70 P device because of the higher
demand on the measuring accuracy. With the PLL technology (Phase Locked Loop) the signal frequency is directly recorded as a digital
data and the converter oscillator locks automatically on the right frequency.
3) differential frequency formed
f
∆∆f
1) radar frequency linearly changed
non-linear sweep linear sweep
f
Stop
∆∆f
antenna
2) delay time due to wave propagation
t
f
Start
Installation and operating instructions BM 70 A/P Page: 6 11/00
As the transmit frequency is changed during a short time interval by FMCW radar the transmitted frequency has to follow the nominal frequency within micro seconds. This ensues via modern, fast electronic and processors.
Microprocessor
control
PLL structure
Reference oscillator
Microwave oscillator
Loop filter
Antenna
Phase detector
2.2 Signal processing (digital)
The radar signals are digitally processed by a microprocessor. The processing system is based on intelligent procedures that allow for plausibilities and history.
The following diagram describes the path of internal signal processing:
measurement
signal
gain
switch
V
gain
control
filter
analog to
digital
conversion
Fourier
transform
spectrum
empty tank spectrum
plausi-
bility
After automatic gain control, the measuring signal is filtered, digitized and converted into a frequency spectrum by means of the Fourier transform. Plausibility of the value obtained is assessed with the aid of the so-called empty-tank spectrum, which contains information about constant interference reflectors. Interpolation of the spectrum helps to improve resolution of the measured value.
spectrum
interpolation
corrected spectrum
distance
2.3 Modularity (signal converter, flange, antenna)
The measuring system consists of the flange system and the signal converter. The flange system contains the microwave window separating product from pressure, and the
antenna system. The compact signal converter contains the microwave generator and the entire signal processing
system, including provision of a standardized output signal (4 - 20 mA or digital interface). The signal converter can be separated from the flange system under process conditions, without loss
of pressure or escape of product.
OO
Converter
OO
Flange with micro­wave window
Antenna system
Installation and operating instructions BM 70 A/P Page: 7 11/00
3 Input
3.1 Measured variable (distance, level, volume, reflection)
The primary measured variable is the distance between a reference point (as standard: tank mounting flange) and a reflecting surface (e.g. surface of the liquid). The filling level is determined by allowing arithmetically for the entered tank height. Volume measurements are possible by entering a conversion table (max. 50 points). The strength of the reflected signal can be measured for qualitative assessment of the tank product or its surface.
3.2 Measuring range [0.5-35/40 m (1.64-115/131 ft)]
Minimum tank height 0.5 m (1.64 ft) Maximum measuring BM 70 A 40 m (131 ft) / optionally 100 m (328 ft)
BM 70 A mit Wave-Stick 20 m (65.62 ft) BM 70 P 35 m (115 ft)
The useful range will depend on the antenna size, the reflection properties of the tank product, the installation position, and the presence of interference reflectors (see Sections 6.1 and 7.5).
3.3 Block distance
The block distance is the minimum measured distance between the mounting flange (reference point) and surface of the tank product. Recommended minimum values: see following sketches.
Horn antenna without stilling well:
Antenna size* = Type3: 22cm/8.7"; Type4: 34cm/13";
* Hastelloy: +3cm / 1,2 "
Recommended antenna distance:
Storage tanks: 10cm/4"; Process tanks: 20cm/8"
Product surface
The length of any antenna extension used must be added on!
Stilling well / Wave-Guide Wave-Stick
Antenna size * = Type1: 11cm/4";
Type2: 15cm/5.5"; Type3: 22cm/8.7" Wave-Stick SW: 6cm/2.4"
(Wave-Guide: no antenna)
Recommended antenna distance = 30 cm / 12"
Product
* Hastelloy: 3 cm (0.4")
Minimum block distance = Standard: 184 mm Normal: Rod length - 200 mm (7.87")
3.4 Out-of-range performance
max.
200 mm
8"
Product
Block
distance
Maximum
level
Standard:
384 mm/15.1"
When the level measuring range is exceeded (including flooding) the measured value will stick at the (adjustable) block distance (see Sect. 8.6.14).
If the measured value drops below the level range, it will stay put at the set lower range limit (distance = tank height).
Installation and operating instructions BM 70 A/P Page: 8 11/00
4 Output
4.1 Variants
Variants Remarks Described
in Section
Ex-e current output HART®Ex-e; active; HART® protocol;
together with switching output and digital input
Ex-i current output HART®intrinsically safe; passive; HART® protocol
(optionally with intrinsically safe switching output) Current output Ex-e; active; non-communicable 4.5 RS 485 + current output BM70 protocol or ModBus-RTU or HART
®
PROFIBUS-PA intrinsically safe; see Supplementary Instructions ­Foundation Fieldbus (FF) intrinsically safe; see Supplementary Instructions -
All versions with HART® or BM70 protocols can be operated with the PC-CAT PC program (see Section 8.12).
Overview of digital Communication possibilities:
BM 70 A
RS 485
communication interfaces
Modbus PROFIBUS-PA
...........
Other
4.2 + 4.4
4.3 + 4.4
4.6 + 4.5
RS 485
4 ... 20mA + HART ®
Converter
HART
FIELD COMMUNICATIONS PROTOCOL
F1 F2 F3 F4
HART Communicator
I
>>>>>>
O
A B C D E F G H I
7 8 9
J K L M N O P Q R
4 5 6
S T U V W X Y Z /
1 2 3
# % & < > : +
*
0 . _
HART-
HHC
PC-CAT
or
HART specific software
and operating devices
4mA (Ex i) + HART®
HART
FIELD COMMUNICATIONS PROTOCOL
F1 F2 F3 F4
HART Communicator
I
>>>>>>
O
A B C D E F G H I
7 8 9
J K L M N O P Q R
4 5 6
S T U V W X Y Z /
1 2 3
# % & < > : +
*
0 . _
HART-
HHC
HART-Master
Point-to-point Multidrop
Tank Inventory System
Installation and operating instructions BM 70 A/P Page: 9 11/00
4.2 Ex-e current output HART
®
Function Level, distance, volume (conversion table) or reflection,
and error identification;
galvanically isolated from digital input and switching output Current 4-20 mA; without or with error message (2 mA and 22 mA) Accuracy/linearity 0.05
% (rel. 20 mA; at T = 20°C, 100 load impedance and nominal operating voltage)
Temperature drift < 100 ppm/K (typically 30 ppm/K) Load impedance < 500 Effect of load impedance < 0.02 % (rel. 20 mA for RB = 0...500 Ω) Effect of power < 0.02 % (rel. 20 mA for UB within limits of tolerance) Hazardous-duty version: Ex e
Note: together with switching output and digital input
Digital input (terminals 81/82):
Can be used to suspend the entire measurement procedure, i.e. measurements are "frozen" (standard setting), or to hot start the device (reprogra mming by KROHNE Service).
Applicable voltage: 5...28 V DC Input resistance: > 1 k
Switching output (terminals 41/42):
Can be progra mmed as a limit switch, alarm contact or error message. The contact is open in the de-energized condition.
Operating data: max. 100 mA / 30 V DC or 30 V AC. Internal resistance: < 20
4.3 Ex-i current output HART® (type of protection: Ex de [ia])
Function Level, distance, volume (conversion table) or reflection;
and error identification;
passive output (current sink) Current 4-20 mA; without or with error message (3.6 mA / 22 mA);
4 mA constant, adjustable for HART Temperature drift < 100 ppm/K (typically 30 ppm/K) Accuracy/linearity 0.05 % (rel. 20 mA; at T = 20°C, 10 V supply voltage and nominal operating voltage) Supply voltage U 8-30 V (between terminals 31 and 32) Load impedance < (U
- 8V) / 22 mA (US = external supply voltage)
S
Effect of supply voltage < 0.02 % (rel. 20 mA for U = 8...30 V) Effect of power < 0.02 % (rel. 20 mA for UB within limits of tolerance)
Note: Digital input not available.
-Multidrop
Optional switching output (terminals 41/42):
can be progra mmed as limit switch, alarm contact or error message. The contact is open in the de-energized condition.
Operating data: 6...30 V; I
< 110 mA; U
Low
Low
< 2V; I
< 900 µA (U=30V) and I
High
High
Ex-i safety limits
Signal circuit in type of protection: Intrinsic Safety EEx ia IIC/IIB or EEx ib IIC/IIB for connection to a certified intrinsically safe circuit with the following peak values: Uo = 30 V; Ik = 250 mA
Effective inner capacitance 0; effective inner inductance ≈ 0
Installation and operating instructions BM 70 A/P Page: 10 11/00
= 200 µA (U=8V)
4.4 HART® communication
The HART Communications protocol can, in accordance with the Rosemount Standard, be used with a BM 70 A/P. Electrical connection: see Section 7.8. There are two ways of using the HART
®
Communication:
a) As a point-to-point connection between the BM 70 A/P and the HART
A BM 70 A/P can be used either with an Ex-e current output HART
®
master equipment.
®
or with an Ex-i current output
HART®.
HART Master
b) As a multipoint connection (multidrop) with up to 15 devices (BM 70, BM 70 A/P or other
HART
®
equipment), in parallel on a 2-wire bus:
4...20 mA
A BM70 A/P is normally used with Ex-i current output, but an Ex-e current output can also be used (constant 4 mA in both cases.)
HART Master
4mA 4mA 4mA 4mA
other
HART device
other
HART device
4.5 Current output (non-communicable)
Function Level, distance, volume (conversion table) or reflection,
Current 4-20 mA; without or with error message (2 mA and 22 mA) Accuracy/linearity 0.3 Temperature drift < 200 ppm/K (typically 70 ppm/K) Load impedance < 250 Effect of load impedance < 0.1 % (rel. 20 mA for RB = 0...250 Ω) Effect of power < 0.1 % (rel. 20 mA for UB within limits of tolerance) Hazardous-duty version: Ex e
and error identification
% (rel. 20 mA; at T = 20°C, 100 load impedance and nominal operating voltage)
When operated as a switching output (digital output): Function limit switch, alarm contact or error message Low status current < 2 mA
High status current = 22 mA (when load < 250 Ω) No-load voltage < 18 V
4.6 Digital interface RS 485
RS 485 is a bus that allows two-way Communication (half-duplex operation) with the BM 70 A/P Level-Radar. When the computer system sends out a request, the BM 70 A/P transmits: level, distance; volume (conversion table), reflection, setting parameters and status. A PC can configure any BM 70 A/P via the bus (RS 485/RS232 converter required) by means of the PC-CAT program, provided no master is active. The maximum cable length - excluding amplifier - is 2000 m.
Installation and operating instructions BM 70 A/P Page: 11 11/00
Transmission rate: 1200 to 38400 bauds
)
120 ohms
120 ohms
Address: 0 to 255 Protocols: KROHNE Protocol, HART
®
, Modbus RTU (from firmware
V.3.02/4.02)
Additional information: see "BM 70 A/P Communication RS 485" instructions
Additional current output: The current output is conductively coupled to the RS 485 interface.
Technical data: see Section 4.5
Note: Switching contact and digital input are not available. However, the
current output can be configured as a switching output.
Various bus configurations
A) Connection of a BM 70 A/P as a single RS 485 user:
Computer system
RS485 connection must be terminated with 120 ohms (if necessary insert resistor between A and B
Bus line (2 shielded wires)
with termination
resistance
120 ohms
B) Connection of several BM 70 A/P in the RS 485 bus system via stubs to the bus cable:
Computer system
RS485 connection must be terminated with 120 ohms (if necessary insert resistor between A and B)
Bus line (2 shielded wires)
without termination resistance
without termination resistance
...........
without termination resistance
with termination
resistance
C) Connection of several BM 70 A/P in the RS 485 bus system, with bus cable looped through to
further field instruments:
Computer system
Bus line (2 shielded wires)
RS485 connection must be terminated with 120 ohms (if necessary insert resistor between A and B)
without termination resistance
without termination resistance
...........
without termination resistance
with termination
resistance
Notes:
If other devices are operated together with the BM 70 A/P Level-Radar on one bus, all devices
must use the same Communications protocol (e.g. ModBus devices of different makes or BM 70 A/P and TTM 70 with KROHNE Protocol).
When "HART
®
" is set as the protocol type, use only the protocol in keeping with the "HART
®
Specification". The "Hardware Implementation RS 485" does not conform to the HART® Standard (see Sections 4.2 and 4.3).
Installation and operating instructions BM 70 A/P Page: 12 11/00
Since signal reflections at the line ends can interfere with Communication, both the line beginning
(at the computer system) and the line end (at the last device) should be terminated with the typical surge impedance of the cable (120 ). To do this inside the BM 70 A/P: see Section 7.9.
4.7 Breakdown signal
Breakdown information can be called up via the following interfaces:
Local display: flashing display, plain text information
Current output: error signal 2 mA (Exi = 3.6 mA) or 22 mA
Switching output: contact opens or closes
Digital interfaces: interrogation of error flags
4.8 Digital input
The digital input (for electrical data: see Section 4.2) can be used for temporarily "freezing" measure­ments or for carrying out a hot start. It is only available in the "Ex-e current output HART
The "freeze" function can be used to blank out larger, temporary interferences, e.g. very slow agitator, slide gate, ball valve in the stilling well. The last measured values in each case are present at outputs I and S, and in the display. The digital input is also taken into account when the empty-tank spectrum is being recorded (totalizer does not continue). marker 6 in the display indicates that the digital input is active in the "freeze" function.
NOTE: The function of the digital input is set as standard to "freeze". To switch the function to "hot start" or to deactivate it completely, the setting will need to be changed in the Service menu of the BM 70 A/P
®
" version.
Installation and operating instructions BM 70 A/P Page: 13 11/00
5 Measuring accuracy
5.1 Reference conditions
Temperature = +20°C / +68°F
Pressure = 1013 mbar abs. / 14.5 psia
Air humidity = 65%
Highly reflecting product (e.g. water) with calm surface
Tank diameter > 5 m / 16.4 ft
Mounted at least 1/7 x tank height away from tank edge (BM 70 P: 1/5 x tank height)
No interference reflections inside the radiation lobe (± 6...9°; see Section 6.1.1)
5.2 Error of measurement
Since the measuring process primarily determines distance, measuring accuracy can only be specified as a function of the distance. For that reason, all figures given in this Section 5 refer to the measured distance.
BM 70 A: With antenna type 3 (139 mm / 5.47") or type 4 (200 mm / 7.87") or stilling well or Wave­Guide
Accuracy
inch cm
12
4.8
10
4
8
3.2
6
2.4
4
1.6
2
0.8
± 1 cm (0.4")
0 5 10 15 20 25 30 35 40 m
1
block
16 33 49 66 82 98 1153
-0.8
-1.6
-2.4
-3.2
-4.8
0
0
-2
-4
-6
-8
-4
-10
-12
distance
± 0.3 %
Distance to flange
131ft
BM 70 A Wave-Stick:
Accuracy
inch cm
12
4.8 10
4
8
3.2 6
2.4 4
1.6 2
0.8
± 1.5 cm (0.6")
0 5 10 15 20 25 30 35 40 m
1
0.18
0.6
Installation and operating instructions BM 70 A/P Page: 14 11/00
-0.8
-1.6
-2.4
-3.2
-4
-4.8
0
0
-2
-4
-6
-8
-10
-12
± 0.3 %
16 33 49 66 82 98 1153
Distance to flange
131ft
BM 70 A Precision (with special calibration and certificate): Only with antenna type 4 (200 mm / 7.87") or stilling well 80 - 200 mm dia. (3 - 8")
Accuracy
inch cm
12
4.8
10
4
8
3.2
6
2.4
4
1.6
0.8
2
0
0
-0.8
-2
-1.6
-4
-2.4
-6
-3.2
-8
-4
-10
-4.8
-12 0 5 10 15 20 25 30 35 40 m
block
distance
± 5 mm (0.2")
1
16 33 49 66 82 98 1153
± 0.1 %
Distance to flange
= calibration range = not verified by calibration
BM 70 P
Only with antenna type 4 (200 mm / 7.87") or stilling well 100 - 200 mm dia. (4 - 8")
Accuracy
inch mm
12
0.48
10
0.4
0.32
0.24
0.16
0.08
0
-0.08
-0.16
-0.24
-0.32
-0.4
-0.48
±
8
20
...
6
30
4
mm
2
0
-2
-4
-6
-8
-10
-12
± 1 mm (0.04")
0 5 10 15 20 25 30 35 40 m
Block-
distance
1
16 33 49 66 82 98 1153
Distance to flange
± 0.01 %
131ft
131ft
5.3 Repeatability
Repeatability is equal to half the value for the error of measurement.
5.4 Measured value resolution/hysteresis
Measured value resolution is: 1 mm / 0.04" for BM 70 A, and 0.1 mm / 0.004" for BM 70 P Hysteresis is at least 20 times less than the error of measurement.
Installation and operating instructions BM 70 A/P Page: 15 11/00
5.5 Transient recovery time
The transient recovery time is determined by the setting parameter "time constant" (1 ... 100 s). The transient recovery time relative to 1% deviation from the steady-state value is approx. 4.6 times
the time constant. However, in the case of unusually rapid changes in level, the transient recovery time may deviate
from this figure.
5.6 Turn-on drift / turn-on characteristics
A rough measured value is initially displayed about 1 minute after the BM 70 A has been switched on. The first self-calibration is completed after about 2 minutes. Full measuring accuracy is attained after 30 minutes operating time.
The measured value from the BM 70 P is accurate directly after the startup phase (approx. 1.5 minutes).
Typical turn-on drift (example):
Measured value
BM 70 A
BM 70 P
Time/min012 30
5.7 Long-term drift
The long-term drift is within the specified error of measurement.
5.8 Effect of ambient temperature
Temperature coefficient, signal output:
Ex-e current output HART Ex-i current output HART Current output: < 200 ppm/°C (typically: 70 ppm/°C) Digital interfaces: no temperature effect
The temperature has no effect on the measured value as the device carries out a regular self-calibra­tion.
The effect of temperature of the atmosphere above the liguid product results theoretically in ­1ppm/°C for air.
In respect of proof of temperature effect with the aid of reference measurements in liquid tanks, it needs to be borne in mind that liquids generally have a high coefficient of cubic expansion (organic liquids: typically 0.15 %/°C)!
®
: < 100 ppm/°C (typically: 30 ppm/°C)
®
: < 100 ppm/°C (typically: 30 ppm/°C)
Installation and operating instructions BM 70 A/P Page: 16 11/00
6 Operating conditions
Hazardous-duty systems
The BM 70 A/P is certified in conformity with European Standard (ATEX) for use in Zone 0, 1 and
2 hazardous locations.
The BM 70 A/P also has FM Approval (Factory Mutual) for CLASS I, DIV 1, GROUPS B,C,D;
CLASS II/III, DIV 1, GROUPS E,F,G.
Attention is drawn to the information given on the nameplate and the specifications in the
approval certificates.
When carrying out installation, dismantling work or making electrical connections in the
hazardous area, be sure to observe the pertinent wiring and installation regulations, e.g. as specified in VDE 0165.
Within the scope of routine checks required to be carried out on systems operated in hazardous
areas (maintaining the system in good working order), the "flameproof enclosure" (large cover on signal converter) should also be visually inspected for signs of external damage and corrosion.
Before opening the "flameproof enclosure" (e.g. to inspect the inside or for repair purposes)
make absolutely certain in the hazardous location:
- that the BM 70 A/P Level-Radar is disconnected from voltage, and then allow the prescribed waiting time of 22 minutes to elapse first,
- and that there is no explosion hazard (gas-free certificate!).
Safety
Operator control via the keys: on electrical safety grounds, operator control of the keys (below
the display, with the housing open) may only be carried out by specialist personnel for service and repair work, on no account, however, when there is risk of explosion!
Surface temperature: the housing of the signal converter can, in extreme ambient conditions,
assume temperatures of more than 70°C (158°F)!
6.1 Installation conditions
Refer to Section 7.5 for selection of the optimum antenna type
6.1.1 Transmission angle
The transmission angle is defined as the angle α to the vertical, in which the power density of the radar waves assumes half the value of the maximum power density (half-power beamwidth):
Antenna Type Diameter
mm (inches)
Type 4 200 (7.87) 10 cm (3.94”) Type 3 140 (5.51) 14 cm (5.51”) Type 2 * 100 (3.94) 12° * 22 cm (8.67”) Type 1 * 80 (3.15) 16° * 30 cm (11.8”) Wave-Stick 25 (0.98) 16 cm (6.3”) Wave-Guide / stilling well
αα
s
* Should only be used in stilling wells; the transmission angle given applies to line-of-sight propagation, i.e. without stilling well.
25-200
(0.98-7.87)
Trans­mission angle α
Propagation only inside the
Lobe expansion s per metre distance
stilling well
Installation and operating instructions BM 70 A/P Page: 17 11/00
6.1.2 Recommendations for positioning on the tank
A) Horn antenna or Wave-Stick without stilling well
Recommended
distance from the tank wall:
Antenna Type 3 or Wave-Stick
>1/7×H, but max. 1/3×D
D
H
min. measurable level
Antenna Type 4
>1/10×H, but max. 1/3×D
BM 70 P : > 1/5 x H
D
H
Lower measuring range limited Several BM 70 A/P can be operated when tank has tapered bottom. in one tank.
Do not position in Do not mount dead centre Do not position tank centreline!onmanhole cover! above internals! (multiple reflections!) (multiple reflections!) (interference reflections!)
If these recommendations cannot be followed because of the tank geometry, please consult KROHNE.
Installation and operating instructions BM 70 A/P Page: 18 11/00
B) Stilling well or Wave-Guide
A stilling well or Wave-Guide may be mounted in any position on the tank. (For design layout: see also Section 6.1.4; for block distance: see Section 3.3).
Stilling well application In a side vessel BM 70 A Wave-Guide
A stilling well or Wave-Guide is positively recommended for horizontal cylindrical tanks (to avoid multiple reflections):
6.1.3 Mounting on tank fitting
A) Horn antenna
Should be mounted on the tank fitting as close to the horizontal as possible (deviation < ± 2°). Exception: if product surface is not horizontal, (e.g. particulate materials) the flange can be aligned
roughly parallel to it.
The antenna should project out of the fitting:
Antenna Diameter D Length l* Type 4 200 mm (8”) 335 mm (13.2”) Type 3 140 mm (5.5”) 223 mm (8.8”) * Hastelloy: + 30 mm (1.2”)
(subject to change without notice)
Tank nozzle
L
D
Installation and operating instructions BM 70 A/P Page: 19 11/00
An antenna extension should be added if the antenna does not project out of the fitting:
Antenna
Tank nozzle
extension
Antenna extensions are available from 100 to 2000 mm (3.94" to 78.74") in steps of 100 mm (3.94"). Several extensions can be joined up:
Exception: When the tank fitting is sy mmetrical, the antenna may end in the fitting so as to enlarge the measuring range (minimum dead zone to tank cover, see Sect. 3.3 "block distance" and Sect. 5.2 "error of measurement"):
Tank nozzle
Narrow tank fitting
If the inside diameter of the fitting is smaller than the diameter of the antenna, and the fitting is accessible from inside the tank for mounting purposes, the antenna with extension can be mounted from the inside (not for versions made of titanium or tantalum). The antenna extension should be about 100 mm (3.94") longer than the height of the fitting.
Antenna
Tank nozzle
extension
Installation and operating instructions BM 70 A/P Page: 20 11/00
B) Wave-Stick
Note the requirements pertaining to diameter and length of the tank fitting:
Version Length L max.
Tank nozzle
min. 50 mm/2"
max. X
Standard 384 mm
L
Option 500...1000 mm
(19.7” - 39.4”)
6.1.4 Mounting on stilling wells
Antenna Type Outside
height of
fitting X
150 mm
(15.12”)
(15.12”)
L - 234 mm
(L - 9.2”)
diameter
1 80 mm (3.15”)
1s 76 mm (2.99”)
2, 2s 100 mm (3.94”)
3 140 mm (5.51”)
3s 152 mm (5.98”)
4, 4s 200 mm (7.87”)
If necessary, turn antenna to size!
Antenna size must match inside diameter
A standard Wave-Stick will not function in a stilling well! For stilling wells 40-55 mm a type Wave-Stick SW can be used.
60mm
Further requirements concerning stilling wells:
The well must be electrically conductive.
Minimum inside diameter of well: 40 mm (1.57"). (BM 70 P: 80 mm,
better > 100 mm).
If possible, use only smooth walled, straight stilling wells. If nevertheless an assembled stilling well
is necessary, abrupt changes in diameter along the pipe should be less than 1 mm (0.04"). Surface roughness of the inside of the pipe should not be more than + 0.1 mm (0.004").
For the BM 70 P the antenna types 1s, 2s, 3s or 4s have to be used to achieve a high measuring
accuracy.
Installation and operating instructions BM 70 A/P Page: 21 11/00
It is possible to measure through a full-bore open ball valve if the valve and the pipe adapters above and below the valve are relatively smooth-walled.
It is not possible to measure levels below the end of the stilling well.
To ensure equalization of pressure, drill one or two small holes in the stilling well above the
maximum filling level.
If necessary, several holes can be drilled along the
whole length of the pipe. All holes must be deburred. The holes should be as small as possible and spaced wide apart (Recommen­dation: see drawing on the right).
It is advisable to fit a reference point at the end of
Ø max.
10 mm
/ 0.4"
the stilling well in the form of a rod or screw of approx. 6 mm (0.24") diameter. See drawing below.
Ø 6 mm
6 mm Ø
Ø 0.24"
min.
50 mm
/ 1.97"
6.1.5 Wave-Guide
The "Wave-Guide" is a pipe with an outside diameter of 30 mm (1.18") and an inside diameter of 25 mm (0.98"), that is bolted direct to the BM 70 A flange system (in the same way as an antenna extension). It functions like a stilling well and can be used for clean products. The Wave-Guide is not practical in conjunction with the BM 70 P as it will not provide high measuring accuracy.
maximum length: Ex: max. 3 m (9.84 ft) (except tantalum: max. 1 m (3.28 ft)).
Non-Ex: up to 3 m (9.84 ft) without additional support
Pipes longer than 3 m (9.84 ft) need to be fixed at two points.
6.1.6 Curved antenna extensions
Rectangular and S-shaped extensions are available for particularly difficult operating conditions. Such extensions can be used in cases where the antenna is exposed to especially high temperatures and where there are problems of space, (e.g. to avoid internals; positioning the antenna away from the centre of sy mmetry; lateral mounting of the signal converter).
Standard sizes (others on request):
271 (10.67")
271 (10.67")
R 110 (4.33")
323 (12.72")
300 (11.81")
Dimensions in mm (inches)
Installation and operating instructions BM 70 A/P Page: 22 11/00
6.1.7 Special options for the flange
y p
g
y
p
p
Antenna heating/cooling device (> DN150/6") Purging device (>
DN100)
Double-walled antenna for cooling or heating, With connection for purging the inside surface e.g. to avoid condensation (recommended for of the antenna to prevent heavy deposits of liquid sulphur). product or to heat or cool the antenna. max. differential pressure at antenna: Standard DN150 = 6 bar (87 psig) (information on other pressure levels provided on request)
If a liquid is used for purging, this may interfere with the functioning of the BM 70 A/P during the process. Continuous purging with gas is not a problem as it does
Hazardous-duty systems:
1. In Zone 0, the temperature of the
heating system and antenna may not exceed 80 % of the ignition temperature of the stored material.
2. Continuous monitoring shall
ensure, and operational inspections shall verify, that the 80% level of
not interfere with measurements. The purge connection is closed off by the manufacturers
with a ¼" screw. When this screw is removed to connect up a purging system, the operator is responsible for ensuring conformity with "Ex" requirements in connection with the purging circuit (e.g. fitting a flame trap).
the ignition temperature stated in Point 1 above is not exceeded.
6.1.8 Ultimate installation on the tank
After carefull
tank fittin
ositioning the BM 70 A/P on the
flange (not forgetting the gasket),
align the BM 70 A/P and the gasket.
Insert stud bolts and tighten nuts slightly (b
hand). (These items not included with supply).
Press shielding strip C* in the gap between
tank flange and the BM 70 A/P flange and secure with stra
retainer S* (both items
included with supply).
Strap retainer S* must fit closely and overla
both flanges.
* only required for European radio approvals
Tighten down stud bolts and nuts firmly. The
torque is dependent on the strength properties of the stud bolts and the pressure rating of the tank.
Installation and operating instructions BM 70 A/P Page: 23 11/00
C* = shielding strip B = BM 70 A/P flange S* = strap retainer F = tank flange
6.1.9 Sunshade
315 (12.40")
A sunshade SD is recommended to protect the signal converter from the effects of direct sunshine from above. This will increase the overall installa­tion height by approx. 20 mm.
The sunshade is easily fitted/dismantled with the aid of 4 screws S (included). An Allen key (size 4 mm) is required.
Dimensions in mm (inches)
353 (13.89")
Installation and operating instructions BM 70 A/P Page: 24 11/00
6.2 Ambient conditions
6.2.1 Hazardous locations
BM 70 A/P Ex is suitable for use in hazardous locations of the following zones: 0, 1, 2 Temperature classes: T6...T2; danger groups: IIA...IIC
For further information: see Section 10.
6.2.2 Ambient temperature of signal converter
BM 70 A/P with horn antenna or Wave-Guide: -20 ... +55°C (-4 ... +131°F)
A "BM 70 sunshade" should be fitted if the converter is located in the open with the likelihood of strong insolation (see Section 6.1.9).
6.2.3 Flange temperature
Horn antenna, Wave-Guide (T Horn antenna, Wave-Guide (T High-temperature version with distance piece and
amb* 50°C): -30 ... +130°C (-22 ... +266°F) amb* 55°C): -30 ... +120°C (-22 ... +248°F)
FFKM gasket (Kalrez 4079 or Parofluor V3819-75): -30 ... +250°C ** (-22 ... +482°F) Kalrez 2035 gasket: -30 ... +210°C (-22 ... +410°F) Viton gasket: -30 ... +200°C (-22 ... +392°F) FEP-sheathed gasket: -30 ... +200°C (-22 ... +392°F)
Wave-Stick, permanently: -20 ... +100°C (-4 ... +218°F) Wave-Stick, pressure-dependent (see 6.3.5), with no mechanical
loading radial to the rod: bis +150°C (302°F)
Wave-Stick, steam cleaning (CIP, SIP) for 30 minutes: max. +160°C (320°F)
* Tamb is the ambient temperature of the signal converter ** Safety limit: +280°C (536°F)
6.2.4 Ambient temperature limits Signal converter:
Measuring function OK, but LCD "freezes up": min. - 40°C (-40°F) Functional upper limit, for max. 2 hours: max. +70°C (+158°F)
Flange system:
see Section 6.2.3
6.2.5 Storage temperature
-20 ... +60°C (-4 ... +140°F)
6.2.6 Environment class
Locations exposed direct to open-air climate, D1 Severity in conformity with EN 60654-1
6.2.7 Protection category
Signal converter: IP 66 / IP 67 (equivalent to NEMA 6)
Installation and operating instructions BM 70 A/P Page: 25 11/00
Loading...
+ 58 hidden pages