This Pre-Installation document provides the information and data needed to
plan and qualify the customer site prior to equipment delivery and installation.
This document considers only the Generator and its associated components.
Product information, environmental and electrical requirements are specified.
For system-related requirements, such as room layout, and system
interconnections, refer to documentation provided with other subsystems.
1.1RESPONSIBILITY OF PURCHASER
HF Series Generators
Pre-Installation
Note .
Site planning and preparation are the responsibilities of the purchaser. The
following points should be considered fundamental to the customers
Pre-Installation activities; addition work may be needed depending on specific
site circumstances:
•Install required material prior the delivery of the system components.
•Complete room floor, ceiling and wall finish.
•Install c onduit, duct, and raceway.
•Install proper size junction boxes with covers at locations specified in the
installation plan.
•Install mains power of proper voltage output and adequate kVA rating.
•Install all safety devices according to this document and Local Codes.
•Provide current room dimensions, including hall way and entry door
sizes.
Complete and proper Pre-Installation will avoid delays and
confusion.
PI-1005R3
1
Page 8
HF Series Generators
Pre-Installation
This page intentionally left blank.
2
PI-1005R3
Page 9
SECTION 2PRE-INSTALLATION DATA
This section provides product information and illustrations showing physical
dimensions, weight, mounting holes and normal access areas for cabling and
service. (Refer to Illustration 2-1.)
PHYSICAL CHARACTERISTICS
HF Series Generators
Pre-Installation
COMPONENT
LINE POWERED GENERATORS
Vertical Generator Cabinet
with LF-RAC (LSS) or DRAC (HSS)
Compact Generator Cabinet
(for only 1 Tube (LSS))
Compact Generator Cabinet
(for 1 or 2 Tubes (LSS or HSS))
CAPACITOR ASSISTED GENERATORS
Compact Generator Cabinet
with Capacitors Module
DIMENSIONS
WEIGHT
LengthWidthHeight
506 mm468 mm1101 mm148 kg
445 mm360 mm568 mm72 kg
592 mm360 mm690 mm95 kg
500 mm360 mm790 mm108 kg
BATTERY POWERED GENERATORS
Compact--ESM Generator Cabinet
with Batteries Module
Compact--ESM Generator Cabinet
with Batteries Module (17 A/h batteries)
PI-1005R3
813 mm436 mm948 mm235 kg
813 mm436 mm1223 mm372 kg
3
Page 10
HF Series Generators
TouchScreenConsol
e
Pre-Installation
PHYSICAL CHARACTERISTICS
COMPONENT
STANDARD CONTROL CONSOLES
RAD Control Consoles
R&F Control Consoles
RAD Console Graphic Display
Touch Screen Console
(TPC 10” or 12”)
Optional Pedestal for
RAD Console Graphic Display or Touch Screen Console
Note.-- Dimensions for no-standard Consoles are not indicated in this document.
w/o Pedestal433 mm298 mm123 mm8kg
with Pedestal433 mm298 mm1023 mm22 kg
w/o Pedestal554 mm360 mm124 mm12 kg
with Pedestal554 mm360 mm1010 mm35 kg
with Handswitch support545 mm290 mm50 mm6kg
w/o Handswitch support430 mm290 mm50 mm6kg
with Handswitch support468 mm290 mm11 4 m m8kg
w/o Handswitch support360 mm290 mm11 4 m m8kg
DIMENSIONS
WEIGHT
LengthWidthHeight
298 mm236 mm930 mm10 kg
TOUCH SCREEN CONSOLE AND PC UNIT
Touch Screen Console400 mm200 mm400 mm5kg
PC Unit480 mm200 mm400 mm15 kg
PC Interface Box130 mm140 mm46 mm0.6 kg
Note.-- Specifications of Touch Screen Consoles and PC Units subject to c hange without notice.
4
PI-1005R3
Page 11
METHOD OF MOUNTING
COMPONENTNORMAL METHOD OF MOUNTING
HF Series Generators
Pre-Installation
Generator Cabinet
Control ConsolesDesk freestanding, wall mounted or anchor to an optional pedestal.
Note: Anchoring hardware should be field supplied. For seismic areas all components must be anchored,
Local Standards should be applied.
Floor freestanding, wall mounted or anchor to floor with
four M10 (3/8”) bolts.
MINIMUM RECOMMENDED FREE AREA FOR SERVICE ACCESS
COMPONENT
Generator Cabinet
Control Consoles
Note: Ventilation conditions requires to keep a minimum free distance of 15 cm (6”) from both lateral sides of the Generator
Cabinet and also the same distance from the rear side when the Generator is provided with High Speed Starter (fans for the
starter module).
Left SideRight SideFrontRearTopBottom
50 cm
(20”)
10 cm
(4”)
50 cm
(20”)
10 cm
(4”)
SURFACE
100 cm
(40”)
Completely
free
--
(see note)
10 cm
(4”)
Completely
free
Completely
free
--
--
PI-1005R3
5
Page 12
HF Series Generators
Pre-Installation
Illustration 2-1
Generators
Cable Access
568
COMPACT
GENERATOR
(For only 1 Tube)
445
251
28
435
200
676757 5757 5783
4415033 4015080206
8
67.5
427.5
Generator
Wall Support
702
Floor Support
422
110224
Wall and Floor Supports are options
19
40
315
6
PI-1005R3
Page 13
Illustration 2-1 (cont.)
Generators
HF Series Generators
Pre-Installation
Cable Access
690
COMPACT
GENERATOR
(For 1 or 2 Tubes)
592
6857 575757
8
28
250
336
580
6857 575757
4415033 4020040280
40
67.5
427.5
Generator
827
Wall Support
Floor Support
422
PI-1005R3
105234
Wall and Floor Supports are options
19
40
462
7
Page 14
HF Series Generators
Pre-Installation
Illustration 2-1 (cont.)
Generators
CAPACITORS
GENERATOR
Cable Access
790
Cable Access
VERTICAL
GENERATOR
1101
Cable Access
Cable Access
1223
948
COMPACT-ESM
GENERATOR
8
COMPACT-ESM
GENERATOR
(with Batteries 17 A/h)
PI-1005R3
Page 15
Illustration 2-1 (cont.)
Consoles
124
HF Series Generators
Pre-Installation
R&F CONSOLE
1010
Cable Access
PEDESTAL (optional)
Mounting Holes ø8
123
1023
Cable Access
RAD CONSOLE
PEDESTAL (optional)
Mounting Holes ø8
PI-1005R3
400
TOUCH SCREEN CONSOLE
FOR PC
400
PC UNIT
Cable Access
45
PC INTERFACE BOX
9
Page 16
HF Series Generators
Pre-Installation
Illustration 2-1 (cont.)
Consoles
TABLE SUPPORT
RAD CONSOLES -- GRAPHIC DISPLAY
WALL SUPPORT
TOUCH SCREEN CONSOLES (TPC)
10
PEDESTAL
THESE CONSOLES CAN BE MOUNTED ON A TABLE SUPPORT, WALL SUPPORT OR PEDESTAL
PI-1005R3
Page 17
SECTION 3ROOM REQUIREMENTS
3.1ENVIRONMENTAL REQUIREMENTS
HF Series Generators
Pre-Installation
LINE POWERED GENERATORS /
CAPACITOR ASSISTED GENERATORS
Storage / Transport
Environmental Conditions
Operating
Environmental Conditions
Heat Output
Temperature range of --40oCto70oC
Relative Humidity range of 10% to 100%
Atmospheric Pressure range of 500 hPa to 1060 hPa
(Battery Powered Generators: for a longer life cycle of batteries it is recommended a t emperature around 22
In normal environmental circumstances the maximum heat output of the equipment can reach:
-- for Line Powered Generators 0.16 kW (544 btu/hr)
-- for Capacitor Assisted Generators 0.20 kW (682 btu/hr)
-- for Battery Powered Generators 0.26 kW (890 btu/hr).
Components must not be allowed to overheat.
Overheating of components can cause system malfunction.
3.2ELECTRICAL REQUIREMENTS
This Generator contains advanced circuitry which will maintain the selected
X-ray techniques during adverse line conditions. However, there is a limit to the
Generators ability to correct for inadequate line power.
To ensure proper operation:
BATTERY POWERED GENERATORS
Temperature range of --20oCto40oC
Relative Humidity range of 10% to 100%
Atmospheric Pressure range of 500 hPa to 1060 hPa
Temperature range of 10oCto40oC
Relative Humidity (no condensing) range of 30% to 75%
Atmospheric Pressure range of 700 hPa to 1060 hPa
o
C)
PI-1005R3
•Do not under size the Distribution Transformer (Line Powered
Generators). It is recommended that the secondary of Distribution
Transformer has a “Star” configuration.
•Size feeder and ground wires per this document.
•Ensure and maintain input mains voltage to specification. Ensure that
the ground resistance is lower than 10
Ω.
The power requirements given here (wire sizes, etc.) are the recommended
specification. With the exception of high current carrying conductors and
grounds, low voltage connections are made with preterminated wires.
The installation should c omply with all the electrical
requirementsindicatedinthisdocument.These
requirements should be upgraded if Local Standards were
more stringent.
11
Page 18
HF Series Generators
Pre-Installation
3.3LINE POWERED GENERATORS -- POWER LINE REQUIREMENTS
Maximum kVp125 kVp150 kVp125 kVp150 kVp125 kVp150 kVp
Power LineAABBC/DC/D
GENERATOR MODELSHF-630SHF-635SHF-835
Maximum Power kW64 kW (or 65 kW under special order)80 kW
Maximum mA640 mA (or 650 mA under special order)800 mA (or 1000 mA under special order)
Maximum kVp125 kVp150 kVp150 kVp
Power LineC/DC/DD (or E for 1000 mA)
POWER LINE
ABCDE
230 / 240 VAC,
Single-Phase, 50 / 60 Hz
NOTES: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
-- For 80 kW Generators operating with lines at 400 / 415 / 440 VAC an auxiliary boost transformer is required to adequate
the line voltage to 480 VAC (or 530 VAC).
12
230 / 240 VAC,
Three-Phase, 50 / 60 Hz
Line voltage automatic compensation: ±10%.
Maximum line regulation for maximum kVA demand: 5%.
400 / 415 / 440 VAC,
Three-Phase, 50 / 60 Hz
480 VAC,
Three-Phase, 50 / 60 Hz
530 VAC,
Three-Phase, 50 / 60 Hz
PI-1005R3
Page 19
HF Series Generators
Pre-Installation
•RMS line current during a X-ray exposure, minimum line power required,
Generator stand-by consumption (W), the differential sensitivity (mA)
and the thermomagnetic breaker should be:
LINEVOLTAGE
208 VAC *192 A240 A300 A
230 VAC174 A217 A272 A
240 VAC167 A208 A260 A
Minimum kVA requiredMaximum kW x 1.25
Stand-by Consumption500 W
Differential Sensitivity
(Earth Leakage / Ground Fault)
Differential, Thermomagnetic
(Fuses) and Contactor
NOTE: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
LINEVOLTAGE
208 VAC *111 A138 A173 A----
32 kW40 kW50 kW
(RMS = momentary line current based on 100 ms X-ray exposures)
32 kW40 kW50 kW64 kW (or 65 kW)80 kW *
SINGLE-PHASE GENERATORS
30 mA
50% of the RMS line current
THREE-PHASES GENERATORS
230 VAC100 A125 A156 A
240 VAC96 A120 A150 A----
400 VAC58 A72 A90 A115 A144 A
415 VAC55 A69 A87 A111 A139 A
440 VAC52 A65 A82 A105 A135 A
480 VAC48 A60 A75 A96 A120 A
Minimum kVA requiredMaximum kW x 1.25
Stand-by Consumption500 W
Differential Sensitivity
(Earth Leakage / Ground Fault)
Differential, Thermomagnetic
(Fuses) and Contactor
NOTES: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
-- For 80 kW Generators operating with lines at 400 / 415 / 440 VAC an auxiliary boost transformer is required to adequate
the line voltage to 480 VAC (or 530 VAC).
(RMS = momentary line current based on 100 ms X-ray exposures)
50% of the RMS line current
30 mA
PI-1005R3
13
Page 20
HF Series Generators
Pre-Installation
LINEVOLTAGE
208 VAC *0.045 Ω0.035 Ω0.028 Ω
230 VAC0.055 Ω0.045 Ω0.036 Ω
240 VAC0.060 Ω0.045 Ω0.036 Ω
•Maximum Power Line Impedance. The Impedance of the Power Line in
the installation must be lower than the maximum value indicated below:
SINGLE-PHASE GENERATORS POWER
32 kW40 kW50 kW
NOTES: -- The above values comply with the Standard IEC-60601.2.7.
NOTES: -- The above values comply with the Standard IEC-60601.2.7.
-- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
THREE-PHASE GENERATORS POWER
LINEVOLTAGE
32 kW40 kW50 kW64 kW (or 65 kW)80 kW *
208 VAC *0.070 Ω0.055 Ω0.044 ΩN.A.N.A.
230 VAC0.087 Ω0.070 Ω0.056 ΩN.A.N.A.
240 VAC0.094 Ω0.075 Ω0.060 ΩN.A.N.A.
400 VAC0.270 Ω0.220 Ω0.170 Ω0.135 Ω0.110 Ω
415 VAC0.300 Ω0.240 Ω0.180 Ω0.150 Ω0.120 Ω
440 VAC0.340 Ω0.270 Ω0.200 Ω0.170 Ω0.135 Ω
480 VAC0.400 Ω0.320 Ω0.240 Ω0.200 Ω0.160 Ω
-- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
-- For 80 kW Generators operating with lines at 400 / 415 / 440 VAC an auxiliary boost transformer is required to adequate
the line voltage to 480 VAC (or 530 VAC).
Correct sizing of the feeder wires is critical to proper Generator operation. Wire
size is dependent on the Generator power, the line voltage and the distance
from the Distribution Transformer to the Generator Cabinet. The maximum
voltage drop during an exposure must not exceed 5% of the nominal mains
value.
It is recommended that the Distribution Transformer (Hospital) used as power
source have at least a power of the 25% more than the maximum power of the
X-ray Generator.
Recommended wire sizing is indicated in Table 3-1. These lengths are
measured from the Distribution Transformer to the Room Electrical Cabinet
(room disconnect). From the Room Electrical Cabinet to the Generator
Cabinet 16 mm
exceed 6 m (20 ft). The maximum wire size that can be connected to the
Generator Cabinet (Input Line Fuse H older) is 35 mm
2
(AWG 6) may be used as long as that length does not
Pre-Installation
2
(AWG 2).
Table 3-1
Minimum Wire Size from Distribution Transformer to Room Electrical Cabinet
NOTES: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
-- For 80 kW Generators operating with lines at 400 / 415 / 440 VAC an auxiliary boost transformer is required to adequate
the line voltage to 480 VAC (or 530 VAC).
16
PI-1005R3
Page 23
HF Series Generators
Pre-Installation
3.5CAPACITOR ASSISTED GENERATORS -- POWER LINE REQUIREMENTS
•Operation:
GSingle-Phase at 100 / 110 / 120 / 208 / 230 / 240 VAC.
GLine voltage automatic compensation: ±10%.
G50 Hz / 60 Hz.
•Thermomagnetic Interruptor / Circuit Breaker rating should be:
G8 / 10 / 12.5 / 16 / 20 A (1P+N).
•Differential Sensitivity: 30 mA
•Minimum k W required: 2.0 kW
•Line Impedance should comply with Standard IEC-60601.2.7.
The minimum recommended wire size for the line voltage is:
LI NE V OLTA GEWIRE SIZE
110 VA C4mm
208 / 230 / 240 VAC2.5 mm
2
2
AWG 12
AWG 14
18
PI-1005R3
Page 25
3.9INTERCONNECTION AND GROUNDING REQUIREMENTS
q
ppl
i
electricalrequirement
s.Customersupplie
d
q
v
i
ith
X-ray
Tube.4
Every installation must be provided with a main line disconnect device
(thermomagnetic breaker) and the remote disconnect devices required at all
Consoles that are not located next to the line safety switch. (For more
information about interconnection and grounding refer to “Installation”
document).
Illustration 3-1
Interconnection B lock Diagram for LINE POWERED GENERATORS
HF Series Generators
Pre-Installation
DISTRIBUTION
TRANSFORMER
(Hospital, etc.)
SERIAL CONSOLE or TOUCH SCREEN CONSOLE (TPC)
TOUCH SCREENPCPC INTERFACE BOX
Note .
1
ROOM ELECTRICAL CABINET WITH
CONTROL CONSOLE
X-RAY TUBE
LINE SAFETY SWITCH
(Provided by customer)
HV Cables
For Serial Generators (RS232 / RS422): Console CPUs are located
80 kW GENERATORS WITH LINES AT 400 / 415 / 440 VAC
3
or
Serial Comm.
or
Serial Comm.
4
or
4
AUX. BOOST TRANSFORMER
WHEN POWER LINES IS 210 VAC OR BELOW OR FOR
(Provided by customer)
2
POWER MODULE
HV TRANSFORMER
LF-RAC (LS)
LV-DRAC (HS)
GENERATOR
or
inside the Generator Cabinet and Interconnections are factory made.
Only one cable (serial communication) from J5 of the Generator Cabinet
should be connected to the Serial Console, Touch Screen Console or
PC Interface Box.
CABLE RUNFUNCTIONREMARKS
Single or Three Phase Power.
1
2
3Control Signals and GroundCable quantity depends on the options installed (AEC, etc.)
NOTES: -- For wire size refer to Section 3.4. Consult to Local Standards for feeder and ground wire size requirements.
Illustration 3-2
Interconnection B lock Diagram for CAPACITOR ASSISTED GENERATORS
ROOM ELECTRICAL CABINET
with LINE SAFETY SWITCH
(Customer supplied)
CONTROL CONSOLE
SERIAL CONSOLE or TOUCH SCREEN CONSOLE (TPC)
TOUCH SCREENPCPC INTERFACE BOX
X-RAY TUBE
Note .
For Serial Generators (RS232 / RS422): Console CPUs are located
inside the Generator Cabinet and Interconnections are factory made.
Only one cable (serial communication) from J5 of the Generator Cabinet
should be connected to the Serial Console, Touch Screen Console or
PC Interface Box.
11
(Customer supplied)
2
or
Serial Comm.
or
Serial Comm.
HV Cables
3
POWER MODULE
HV TRANSFORMER
LF-RAC (LS)
GENERATOR
CABINET
CABLE RUNFUNCTIONREMARKS
Single-Phase Line.
1
2Control Signals and GroundCable quantity depends on the options installed (AEC, etc.)
3
NOTES: -- For wire size refer to Section 3.6. Consult to Local Standards for feeder and ground wire size requirements.
100 / 110 / 120 / 208 / 230 / 240 VAC.
Ground.
Stator Supply.
Ground.
-- The system power ground point is located in the Generator Cabinet.
Interconnection B lock Diagram for BATTERY POWERED GENERATORS
HF Series Generators
Pre-Installation
ROOM ELECTRICAL CABINET
with LINE SAFETY SWITCH
(Customer supplied)
CONTROL CONSOLE
SERIAL CONSOLE or TOUCH SCREEN CONSOLE (TPC)
TOUCH SCREENPCPC INTERFACE BOX
HV Cables
X-RAY TUBE
Note .
For Serial Generators (RS232 / RS422): Console CPUs are located
inside the Generator Cabinet and Interconnections are factory made.
Only one cable (serial communication) from J5 of the Generator Cabinet
should be connected to the Serial Console, Touch Screen Console or
PC Interface Box.
11
(Customer supplied)
2
or
Serial Comm.
or
Serial Comm.
3
or
3
POWER MODULE
HV TRANSFORMER
LF-RAC (LS)
LV-DRAC (HS)
GENERATOR
CABINET
or
CABLE RUNFUNCTIONREMARKS
Single-Phase Line.
1
2Control Signals and GroundCable quantity depends on the options installed (AEC, etc.)
NOTES: -- For wire size refer to Section 3.8. Consult to Local Standards for feeder and ground wire size requirements.
110 / 208 / 230 / 240 VAC.
Ground.
Stator Supply.
Ground.
Generator provided with LV-DRAC requires a shielded stator
cable. (Refer to “Installation” document).
-- The system power ground point is located in the Generator Cabinet.
The Unit is connected by a Line Plug.
Power Line
Line plugs and cable are Customer supplied.
Pro
Field supplied.
rom a Room Electrical Cabinet with SafetySwitch.
ded w
PI-1005R3
.
21
Page 28
HF Series Generators
Pre-Installation
3.10SAFETY DEVICES
Devices such as Safety Switch / Emergency Switch, Warning Light, and Door
Interlock Switch should be supplied and installed by the customer. (Refer toIllustration 3-4.)
SAFETY SWITCH / EMERGENCY SWITCH
The main Safety Switch should be installed in the Room Electrical Cabinet
(Room Disconnect) (close to the Generator Cabinet), and provided with light
indicators for “Power On / Off”. It should be used for main disconnection, and
located in an accessible place where it can be seen and controlled during
operation and service.
Other Emergency Switches should be installed in accessible locations in the
room (near to the main entrance door or to the Control C onsole) for use in an
emergency. They should be connected to the Room Electrical Cabinet (Room
Disconnect) so that they cut power to the Generator when they are activated.
The r ating of these switches should be: 10 A, 500 VAC, NC.
DOOR INTERLOCK SWITCH
The Door Interlock Switch indicates to the operator when Doorways to the X-ray
room are open. It inhibits or not the X-ray generation, according to the Local
Standards and customer preferences.
This switch should be installed in the entrance door(s) and its connecting cable
should be routed to the Generator Cabinet.
WARNING LIGHT
The Warning Lights are signal lamps installed outside of the X-ray room (near
of the main entrance) that indicate:
1.The system is under voltage (red lamp “ON”).
2.X-ray exposure in process (yellow lamp “ON”) (for connection refer toInstallation document.)
The Warning Lights connection cables should be routed to the Generator
Cabinet.
22
Note .
In any case, the installation must be in compliance with the Local
Regulation.
PI-1005R3
Page 29
Illustration 3-4
Room Electrical Cabinet and Mains Connection
EC
Electrical Cabinet
HF Series Generators
Pre-Installation
DCB
TCB
CR
L
L
SS
ON OFF
GEN
EM
EM
LEGEND
EC:Electrical Cabinet (Room Disconnect) for powering X-ray equipment. (Customer supplied)
DCB: Differential Circuit Breaker.
TCB: Thermomagnetic (or Fuses) Circuit Breaker.
CR:Contactor controlled by the Safety Switch (SS).
SS:Safety Switch used for Generator main disconnection, with ON/OFF positions.
L:ON / OFF Indicator Lamps located on the Electrical Cabinet.
EM:Emergency S witch near to Control Console and/or to the Room main entrance.
GEN: Generator Cabinet.
WL1: X-ray Emission Indicator Lamp (yellow lamp) connected to the Generator Cabinet,
located outside of the X-ray Room (above the exam room entrance).
WL2: Warning Light (red lamp) located outside of the X-ray Room (above the exam room entrance).
DIS:Door Interlock Switch located on the main entrance(s).
System
Ground Bar
WL1
WL2
DIS
PI-1005R3
23
Page 30
HF Series Generators
Pre-Installation
This page intentionally left blank.
24
PI-1005R3
Page 31
Technical Publication
IN-1052R0
Installation
HF Series Generators
(ONLY FOR GENERATORS WITH U-ARM POSITIONERS)
Page 32
HF Series Generators
Installation
REVISION HISTORY
REVISIONDATEREASON FOR CHANGE
0FEB 26, 2008First edition
This Document is the english original version, edited and supplied by the manufacturer.
The R evision state of this Document is indicated in the code number shown at the bottom of this page.
ADVISORY SYMBOLS
The following advisory symbols will be used throughout this manual. Their
application and meaning are described below.
DANGERS ADVISE OF CONDITIONS OR SITUATIONS THAT
IF NOT HEEDED OR AVOIDED WILL CAUSE SERIOUS
PERSONAL INJURY OR DEATH.
ADVISE OF CONDITIONS OR SITUATIONS THAT IF NOT
HEEDED OR AVOIDED COULD CAUSE SERIOUS PERSONAL
INJURY, OR CATASTROPHIC DAMAGE OF EQUIPMENT OR
DATA.
Advise of conditions or situations that if not heeded or
avoided could cause personal injury or d amage to equipment
or data.
Note .Alert readers to pertinent facts and conditions. Notes represent
information that is important to know but which do not necessarily
relate to possible injury or damage to equipment.
The Installation process depends on the Generator and System configuration.
Installation must be performed in the order indicated along this document.
Perform only the sections required to install this Generator.
1.1TOOLS AND TEST EQUIPMENT
The following hand tools and products are required for the Installation:
•Standard s ervice engineers tool kit.
•Electric drill motor and assorted bits.
HF Series Generators
Installation
•Silicone Insulating Grease (proofing compound).
•Alcohol cleaning agent.
The following test equipment is required for Configuration and Calibration:
•Digital Multimeter.
•Non-invasive kVp Meter.
•Digital mAs Meter.
•Calculator.
•Only for AEC purposes:
GSensitometer (only for Film).
GDensitometer (only for Film).
GCopper Plates for the Collimator Filter Holder (recommended):
2 units of 1 mm thickness,
1 unit of 0.5 mm thickness,
2 units of 0.2 mm thickness,
1 unit of 0.1 mm thickness.
IN-1052R0
GAcrylic Plastic Plates can be used Instead of Copper Plates:
6 units of 5 cm. thickness,
5 units of 1cm. thickness.
GDosimeter (optionally).
•Only for Tomo purposes:
GTomophantom tool.
1
Page 36
HF Series Generators
Installation
1.2PRE-INSTALLATION CHECK
Prior to beginning installation, it is recommended to inspect the site and verify
that the X-ray room complies with Pre-installation requirements, such as:
•Incoming Line.
•Main Switch and Safety Devices.
•Conduits.
•Space Requirements.
(Refer to the “Pre-Installation” document.)
2
IN-1052R0
Page 37
1.3GENERAL CAUTIONS
HF Series Generators
Installation
MAKE SURE THAT THE MAIN STORAGE CAPACITORS OF
THE HIGH VOLTAGE INVERTER DO NOT CONTAIN ANY
RESIDUAL CHARGE. WAIT UNTIL THE LIGHT EMITTING
DIODES ON THE CHARGE-DISCHARGE MONITOR BOARDS
ARE OFF, APPROXIMATELY 3 MINUTES AFTER THE UNIT IS
TURNED OFF.
ALWAYS
HAVE THE “IPM DRIVER BOARD” CONNECTED IN
THE GENERATOR PREVIOUS TO MAINS POWER IS
ACTIVATED IN IT. IF THE “IPM DRIVER BOARD” IS NOT
CONNECTED, PERMANENT DAMAGE WILL OCCUR TO
IGBTS.
TO AVOID ELECTRIC SHOCK, DO NOT TOUCH ANY
HEATSINKOFTHECIRCUITBOARDSEVENTHE
GENERATORISTURNEDOFF.PREVIOUSTO
DISASSEMBLE ANY BOARD, REMOVE ALL CONNECTORS
PLUGGED TO IT.
LINE POWERED GENERATOR
:
THIS GENERATOR IS PERMANENTLY CONNECTED TO THE
POWER LINE, AND POWERED ON UNLESS THE SAFETY
SWITCH INSTALLED IN THE ROOM ELECTRICAL CABINET
IS OFF. WHEN THE GENERATOR IS POWERED, THE NEON
LAMP (GREEN) LOCATED ON THE TRANSFORMER 6T2
(GENERATOR CABINET) IS ON.
IN-1052R0
INTERNAL PARTS OF THE GENERATOR (ALL FUSES, LINE
CONTACTOR (6K5), INPUT TRANSFORMER (6T2), ON/OFF
RELAY (3K3) AND LF-RAC MODULE) ARE PERMANENTLY
POWERED ON THROUGH POWER LINE ALTHOUGH THE
CONTROL CONSOLE IS OFF. BE SURE THAT THE SAFETY
SWITCH IS OFF BEFORE HANDLING ANY INTERNAL PART
OF THE EQUIPMENT.
3
Page 38
HF Series Generators
Installation
This page intentionally left blank.
4
IN-1052R0
Page 39
HF Series Generators
Installation
SECTION 2UNPACKING, POWER LINE CONNECTION
AND CABINET INSTALLATION
The Generator is shipped in one box to facilitate transport and installation.
Upon receipt of the X-ray unit and associated equipment, inspect all shipping
containers for signs of damage. If damage is found, immediately notify the
carrier or their respective agent.
It is recommended to install the U-Arm Positioner before than
the Generator. (Refer to t he Positioner Service Manual).
1.Open the shipping box. Take out the Control Console (if provided),
Interconnection Cables, Cabinet Cover and other furnished parts. Do not
discard any packing material such as envelopes, boxes or bags until all
parts are accounted for as listed on the packing list.
Illustration 2-1
Compact Generators
2.Remove the packing material from the pallet.
3.Remove the Generator Cabinet from the shipping pallet, placing it near
its chosen room position. This operation requires at least two people.
4.When the equipment is unpacked, verify that all items on the customer
order are present, and the hardware and internal wiring is secure.
5.Check the part numbers / serial numbers of each component with its
identification labels, and inspect all pieces for visible damage. If any
damaged parts are found, repair or order replacements to prevent
unnecessary delay in installation.
IN-1052R0
5
Page 40
HF Series Generators
Installation
6.Previous to install the Generator Cabinet on the upper side of the
Positioner Control Box, it is recommended to perform the Power Line
connection.
KEEP IN MIND THE GENERAL CAUTIONS FOR LINE
POWERED GENERATORS INDICATED IN SECTION 1.3.
DO NOT POWER ON THE GENERATOR UNTIL SPECIFICALLY
INSTRUCTED IN THIS SERVICE MANUAL.
7.The power supply line should conform with the Generator model defined
in the “Pre-Installation” document. Wire sizes indicated in this document
are relative to the power supply line and wire length. Verify that the power
line voltage and phase of the Generator coincides with the one for Room
Electrical Cabinet.
Note .
As indicated in the Pre-Installation document, 16 mm
may be used from the Room Electrical Cabinet to the Generator
Cabinet provided that the length does not exceed 6 m (20 ft).
8.Route the Power Line C ables and the Ground wires to the Input Line
Fuses and Ground Studs in the Cabinet Frame (Ground Studs are above
the input fuses or close to the right side of the HV Transformer). These
cables can be secured to the Fastening Bar of the Cabinet and routed
internally along the rear side of the Cabinet (always apply Local Codes
for cable r outing). (Refer to Illustration 2-2.)
Illustration 2-2
Cable Routing in the Line Powered Generator
Fastening Bar
Input Transformer 6T2
2
(AWG 6)
Power Line Cables
6
Ground Terminals
Input Line Fuses
IN-1052R0
Page 41
HF Series Generators
Installation
9.For Single Phase Generators, connect the Power wires L1 and N (L2)
to the Fuse Holders of F3 and F4 (right side of the Cabinet), and the
Ground wire to the Ground stud in the Cabinet Frame (above these fuses
or close to the right side of the HV Transformer).
SINGLE PHASE GENERATORS ARE FACTORY DELIVERED
TO OPERATE ON PHASE AND NEUTRAL. IN CASE OF
CONNECTING THE EQUIPMENT TO A TWO-PHASE LINE,
REPLACE THE NEUTRAL CARTRIDGE WITH THE FUSE
SUPPLIED WITH THE GENERATOR.
10.For Three Phase Generators, connect the Power wires L1, L2 and L3
to the Fuse Holders of F3, F4 and F5 (right side of the Cabinet), and the
Ground wire to the Ground Studs in the Cabinet Frame (located above
these fuses or close to the right side of the HV Transformer).
Illustration 2-3
Power Line connections
Three Phase Generators do not need Neutral (N) wire connection from
the Line. If the unit is provided with the optional Fuse Module, connect
the Neutral (N) wire from the Line to the Neutral Stud below F3 Fuse
Holder.
Input Transf. 6T2
GND Studs
GND Stud
L1 Input Line
L2 Input Line
L3 Input Line
IN-1052R0
Neutral Stud
(optional)
7
Page 42
HF Series Generators
Installation
SEP-UP TRANSFORMER
Input: 380 VAC / 400 VAC / 415 VAC, Three-Phase.
Output: 480 VAC / 530 VAC, Three-Phase.
Max Power Output: 80 kW, 10% duty cicle
Rising Temperature: 40
(approx. 5 seconds / minute)
o
C
For 80 kW Generators, the power supply line must be 480 VAC (or
530 VAC). If theGenerator is supplied with an external step-up
autotransformer, it will include the cables to connect the autotransformer
to the Generator Cabinet. Power line should be connected to the
autotransformer terminals according to the line.
480 V
(or 530 V)
415 V
400 V
380 V
380 V
400 V
415 V
480 V
380 V
400 V
415 V
(or 530 V)
480 V
(or 530 V)
Illustration 2-4
Line Contactor 6K5
11.The whole System (Tables, Spot Film Devices, etc.) can be switched
ON/OFF when the Generator is switched ON/OFF. For this, power the
System through the output terminals of the Line Contactor 6K5 (upper
contactor close to the Input Transformer). These terminals are located
underneath the Line Contactor 6K5.
Line Contactor 6K5
Input Transformer 6T2
Output Terminals
8
IN-1052R0
Page 43
12.Three-Phase Generators can be provided with an optional Fuse Module
T
mounted on Module-12, for switching ON/OFF the whole system when
the Generator is turned ON/OFF.
For this, connect the Neutral (N) wire from the Line to the Neutral Stud
below F3 Fuse Holder. Power the System through the Output Terminals
12TS4 (U, V, W, N, GND) close to Fuses F14, F15, F16.
Illustration 2-5
Power Line connections in the optional Fuse Module
GND Studs
HF Series Generators
Installation
Input Transf. 6T2
erminals 12TS4
Note .
GND Stud
L1 Input Line
L2 Input Line
L3 Input Line
Neutral Stud
13.According to the nominal voltage of the line, verify or connect the
wire “
:” to the indicated terminal (TB) of Transformer 6T2. This wire is
factory connected to 230 VAC (for 1-Phase), 400 VAC (for 3-Phase) or
480 VAC / 530 VAC (for 80 kW 3-Phase Generators). (Refer to
Schematic 543020XX).
For 220 VAC power line, connect the wire “
terminals. For 380 VAC power line, connect the wire “
:
” to the 230 VAC
:
”tothe
400 VAC terminals.
6T2 Terminal Strip
6T2
IN-1052R0
9
Page 44
HF Series Generators
Installation
14.After connecting the Power Line Cables, secure them to the Fastening
Bar using cable ties if they are routed over the Fastening Bar, or using
a suitable clamp if they are routed through the Round Cable Outlet on the
Rear Cover of the Cabinet (always apply Local Codes).
15.The Generator Cabinet is installed on the upper side of the Positioner
Control Box as follows.
COMPACT
GENERATOR
CONTROL BOX
Lateral Cable Entrance
BACK COVER
Upper Cable Entrance
(HV Cables, Stator Cable)
690
(27.16”)
600
(23.62”)
52
37
21
213
212850
8.38”
65
2.55”
R9.5
462
(18.18”)
Anchoring Holes
65
2.55”
10
These s teps are also described in the Positioner Service Manual.
a.Place the Control Box on its final position of the room, keep in
mind:
Gthe length of the Column Harness (approx. 1.5 m) that goes
from the Column of the Positioner to the Control Box,
Gthe length of the High Voltage Cables (X-Ray Tube -- HV
Transformer in the Generator Cabinet),
Gthe Swivel Arm movements.
(Refer to Room Layout illustrations in the Positioner
Service Manual)
IN-1052R0
Page 45
HF Series Generators
Installation
b.Level the Control Box using the Adjustable Leveling Legs. Keep
the Base at the maximum distance from the floor.
Seismic areas and other conditions require to secure firmly the
Control Box to the floor through the mounting holes at its base. In
this case, place the four spacers (provided) under the base and
secure them to the floor. Keep the four Leveling Legs at the same
height than the spacers.
Cable Access
Spacer for using in Seismic Areas
Adjustable Leveling Legs
c.Assemble the supplied Back Cover for the Generator Cabinet to
the upper side of the Control Box using two M6x20 screws
(supplied).
Back Cover
Fixing Screws
Control Box
d.Remove the four Adjustable Leveling Legs from the base of the
Generator Cabinet.
IN-1052R0
11
Page 46
HF Series Generators
Installation
Hook
e.Hang the Generator Cabinet on the Back Cover and secure it to
the Control Box using four M6x20 screws (supplied). At least two
people are required for this operation. Fix the two screws that join
the r ear side of the Cabinet to the Back Cover.
Generator Cabinet
Back Cover
Fixing Screws
Control Box
P2--ShieldP1
J1
Ground Wire / GND Stud
P3
f.In some cases, due to transport safety requirements, the HV
Transformer is shipped out of the Generator Cabinet. Install the
HV Transformer inside the Cabinet (upper area) and secure it with
the respective anchors or plates, then connect the following cables
from the Power Module to the corresponding terminals on the HV
Transformer:
GP2-Shield (2 thin wires), P1 and P3. Connect these cables to
the stud-brass terminals using two wrenches to tighten the
nuts (one to hold the base nut in place and the other to tighten
the nut over the cable) and avoiding twisting the studs. Ensure
that the connection is secure and properly tightened.
GGround wire to Ground stud.
GConnector J1.
THE HV TRANSFORMER HAS TO BE SECURED WITH ITS
ANCHORS OR PLATES INSIDE THE CABINET. OTHERWISE
P1, P2 AND P3 STUDS MAY BE IN CONTACT WITH THE
CABINET FRAME AND PRODUCE A SHORT-CIRCUIT.
12
IN-1052R0
Page 47
g.Leave a working area around the Generator Cabinet until its final
installation.
Cable Access to the Generator Cabinet
(HV Cables, Stator / Thermostat, AEC, ...)
HF Series Generators
Installation
Emergency Switch-Off Button
ON / OFF Button
16.Verify that the power supply line is “OFF” in the Room Electrical Cabinet.
Verify that the power line to the Generator is cut when the Emergency
Switch(es) is(are) activated.
17.Cut the cables to the appropriate length and remove insulation from both
ends of the power and ground wires. Connect them to the respective
terminals in the Room Electrical Cabinet.
IN-1052R0
18.Install the Control Console as indicated in Section 2.1.
13
Page 48
HF Series Generators
Installation
2.1CONTROL CONSOLE INSTALLATION (OPTIONAL)
1.Control Console can be freestanding, wall supported or mounted on an
optional Pedestal. Console is provided with several mounting holes on
the bottom for anchoring to the Pedestal or another support.
Console CPU Boards and AEC Control Board can be located inside the
Console (standard) or inside the Generator Cabinet (for Serial
communication).
2.When a Pedestal is used, secure the Pedestal to the floor through the
anchoring holes on its base and place the base cover. Attach the C onsole
to the Pedestal using the mounting holes on the bottom of the Console.
3.When the Console is wall supported, secure the support to the wall and
attach the Consoleto the support using the mounting holes on the bottom
of the Console.
4.Leave a sufficient working area around the equipment until its final
assembly.
14
IN-1052R0
Page 49
SECTION 3CABLE CONNECTIONS
This section provides the information necessary to connect the Generator
Cables with the system and options.
HF Series Generators
Installation
Note .
Note .
For more information about electrical requirements and cable
connections, refer to the “Pre-Installation” document and
Section 5 “System Interconnections” at the end of this document.
Identification of some terminal connections (TB, TS), boards, etc...
along with this document (text and schematics) may have a prefix
number which indicates the module number in the equipment.
(a.e. TS2 as 4TS2, 10TS2 or 11TS2).
Some safety devices such as the Safety Switch / Emergency Switch, Warning
Light, and Door Interlock Switch are supplied and installed by the customer.
Verify that safety devices have been properly installed and routed during the
Pre-Installation procedure.
3.1CABLE ROUTING INSIDE GENERATOR CABINET
3.1.1GENERAL CABLE ROUTING
1.Before connecting the Interconnection cables within the Generator
Cabinet, cables must be first connected to each Device (Positioner,
Tables, Buckys, etc.) and routed through the raceways. Remove the
ferrite blocks of the cables (factory clamped) when it is required to carry
out a correct routing, then re-install the ferrite blocks where they originally
were around cables.
IN-1052R0
Cables Entrance (upper side of Wall Support
2.Inside the Generator Cabinet, all Interconnection cables must be routed
over the Fastening Bar (upper rear bar) of the Cabinet Frame minding the
upper Cable Outlet at the rear side of the Cabinet Cover. (Refer to
Illustration 3-1).
15
Page 50
HF Series Generators
Installation
Illustration 3-1
Cable Routing in Compact Generator
Stator & Interconnections
Cables Entrance
Fastening Bar
Stator & Interconnections
Cables Outlet (rear side)
Cable Ties
Cable Ties
Fastening Bar
Input Transformer
Ground Terminals
Input Line Fuses
Power Line
Cable Entrance
Stator & Interconnections
Cable Entrance
Power Line Cables
HV Cables
Stator & Interconnections Cables
Input Transformer
16
Power Line Cable Entrance
Input Line Fuses
IN-1052R0
Page 51
HF Series Generators
Installation
3.For Generators with the Low or High Speed Starter located on a shelf
(Module 10 or 11), Stator and Interconnections Cables have to be routed
internally through the Cabinet close to the HV Transformer.
In order to avoid signal interferences, it is strongly
recommended to fold and fasten close to the Generator
Cabinet the portion of cables not routed (see picture below).
Never wrap in circles.
4.Connect all cables as indicated in Section 3 “Cable Connections”.
5.Secure all cables to the Fastening Bar using cable ties after all
cable / wire connections are complete.
3.2HIGH VOLTAGE CABLES CONNECTION
FOR GENERATORS WITH A HV TRANSFORMER WITH
DOUBLE X-RAY TUBE RECEPTACLES (ANODE / CATHODE
TO CONNECT TWO TUBES): CONNECTIONS OF THE
FILAMENT LEADS “FIL-1 RTN” (J4-15) AND “FIL-2 RTN”
(J4-16) ON THE INTERFACE CONTROL BOARD HAVE BEEN
INVERTED. THESE CONNECTIONS ARE FACTORY SET.
(REFER TO SCHEMATIC 543020XX).
YESNO
3.2.1X-RAY TUBES WITH METALLIC INSERT ENVELOPE
In case of X-ray Tubes with a Metallic Insert Envelope, it is required to connect
the wire from the Metallic Insert Envelope to the Black Banana Plug connection
on the HV Transformerto obtain a correct mA measures. Forthese X-ray Tubes
the part number of the HV Transformer has to be coded in revision A or higher
(a.e. A6094--16A). (Refer to Section 5.2 -- Map 54302035).
IN-1052R0
17
Page 52
HF Series Generators
Installation
3.2.2HIGH VOLTAGE CABLES
Connect the HV Cables in the HV Transformer (Generator).
These cables must enter into the Generator through the c able outlet on the
upper side of the Cabinet and then attached to the fastening bar (upper rear bar)
of the Cabinet frame minding the upper cable outlet at the rear side of the
Cabinet cover.
1.The mounting accessories of each termination plug are factory
The Terminal Pins of the High Voltage cables are extremely
delicate and easily damaged. Therefore they must be handled
carefully. Make sure that they are straight and that the splits
in the pins are open (parallel to sides).
assembled. For extended information refer to the HV Cable
manufacturer’s instructions located inside the HV Cable package.
Contact Pins
Termination Plug
Do not install the Silicone washer supplied with the HV
Cables.
2.Unscrew the grub screw of the ring nut. (Refer to the illustration below.)
Nipple
Ring Nut
Grub Screw
Contact
3.Prepare the high voltage terminals that will be installed in the HV
Transformer. Put approximately 1 cm (0.5”) of HV Oil in the HV
Transformer receptacles (included in the HV cables package). If HV Oil
is not available, fill the receptacles using silicone paste provided with the
X-ray Tube.
18
4.Carefully insert the anode and cathode termination plug into the
respective receptacle socket (watch the nipple on the plug to ensure
correct positioning of the contact pins).
5.Hand tighten the ring nut. It must be secure. Tighten the grub screw.
IN-1052R0
Page 53
3.3X-RAY TUBE CONNECTION
3.3.1STATOR CABLE
X-ray Tubes are equipped with the Stator cable installed.
A LV-DRAC (Low Voltage - Digital Rotatory Anode Controller) is required for
High Speed X-ray Tubes. Connections between LV-DRAC and Power Module
are factory made.
Route the Stator cable together with the HV cables to the Generator Cabinet.
Connect the Stator cable terminals to the indicated Terminal Block TS2:
HF Series Generators
Installation
Note .
Note .
STATOR WIRES
TERMINAL TS2
TUBE-1TUBE-2
MAINTS2-1TS2-9
AUX (Shift)TS2-2TS2-10
COMMONTS2-3TS2-11
Terminal Block TS2 may be marked as 10TS2 or 11TS2
depending on the Generator model.
For Philips or Siemens X-ray Tubes refer to Interconnection Maps
I/F-021 or I/F-024.
IN GENERATORS EQUIPPED WITH LV-DRAC: THE LV-DRAC
OUTPUT CAN BE AS HIGH AS 1000 Vrms. FOR SAFETY
REASONS (TO AVOID ELECTRIC SHOCKS), THE STATOR
CABLE MUST BE SHIELDED AND BOTH ENDS OF THE
SHIELD MUST BE CONNECTED TO GROUND.
DUE TO ELECTROMAGNETIC INTERFERENCE (EMC)
PROBLEMS, THE IGBT’s HEATSINK IS NOT GROUNDED. IT
IS CONNECTED TO THE NEGATIVE TERMINAL OF THE
INPUT R ECTIFIER. TO AVOID ELECTRIC SHOCK, BE SURE
THAT THE INPUT LINE IS DISCONNECTED AND THE
CAPACITOR BANK IS PROPERLY DISCHARGED BEFORE
MANIPULATING THE LV-DRAC.
IN-1052R0
MAKE SURE THAT STATOR WIRES ARE PROPERLY
CONNECTED. BEFORE MAKING ANY EXPOSURE, CHECK
THAT THE ANODE ROTATES CORRECTLY.
19
Page 54
HF Series Generators
TUB
E
TUB
E
Installation
FANS
Wires from fans should be routed with the Stator Cables, and connected to the
indicated terminal of the Generator Cabinet. Depending on the model of X-ray
Tube, the fans are powered at 115 VAC or 220 VAC. Make the following
connections to select the fan voltage.
For Compact Generators with the Low Speed Starter LF-RAC located on a shelf
at the bottom of the Generator (module-10), connect wires from fans to:
TUBE
CONNECTION
AS TUBE-1
AS TUBE-2
TUBE
CONNECTION
AS TUBE-1
AS TUBE-2
GENERATOR WITH LOW SPEED STARTER
WIRES FROM FANS115 VAC220 VAC
10TS2-6 and 10TS2-7
on the Generator Cabinet
10TS2-14 and 10TS2-15
on the Generator Cabinet
TB4-T1 with TB1-22 or TB1-23
on the LF-RAC Board
TB4-T2 with TB1-22 or TB1-23
on the LF-RAC Board
TB4-T1 with TB1-25 or TB1-26
on the LF-RAC Board
TB4-T2 with TB1-25 or TB1-26
on the LF-RAC Board
For Compact Generators with the High Speed Starter LV-DRAC located on a
shelf at the bottom of the Generator (module-11), connect wires from fans to:
GENERATOR WITH HIGH SPEED STARTER
WIRES TO FANS115 VAC220 VAC
11T S2 -6 a nd 11TS2-7
on the LV-DRAC Module
11TS2-14 and 11TS2-15
on the LV-DRAC Module
wire marked “T1” with 11TS2-17
on the LV-DRAC Module
wire marked “T2” with 11TS2-17
on the LV-DRAC Module
wire marked “T1” with 11TS2-18
on the LV-DRAC Module
wire marked “T2” with 11TS2-18
on the LV-DRAC Module
20
IN-1052R0
Page 55
HF Series Generators
CONNECTIONO
F
Installation
THERMOSTAT OR PRESSURE SWITCH SIGNAL
o
If the X-ray Tube is provided with a Safety Thermostat (approx. 65
C) or
Pressure Switch (must be NC Contact), the two wires should be routed to the
Terminal Block TS2 in the Generator Cabinet and connected to the following
Terminals.
Note .
In case that the X-ray Tube is provided with a Safety Thermostat (approx. 65
o
C)
and a Pressure Switch (both must be NC Contacts), connect them in series
before routing, connecting both wire-ends to their respective Terminals in TS2.
THERMOSTAT WIRESTUBE-1TUBE-2
THERMOSTAT SIGNALTS2-4TS2-12
THERMOSTAT COMMONTS2-5TS2-13
Terminal Block TS2 may be marked as 10TS2 or 11TS2
depending on the Generator model.
If an X-ray Tube is not provided with Thermostat signal, jump both connections
in the Terminal Block TS2 (refer to above table).
GND AND/OR SHIELD
The connection of the GND and/or Shield wire of the Stator cables depend on
the Generator model.
GENERATOR MODEL
Number of X-ray TubesStarter type and Location
1 or 2 Tubes
1 or 2 Tubes
LF-RAC (Low Speed)
Lower Cabinet Shelf (Module 10)
LV-DRAC (High Speed)
Lower Cabinet Shelf (Module 11)
CONNECTION OF
GND and/or SHIELD WIRE
10TS2--8 or 10TS2--16
11TS2--8 (for Tube-1)
11TS2--16 (for Tube-2)
IN-1052R0
21
Page 56
HF Series Generators
Installation
3.3.2TUBE SELECTION SIGNALS
Note .
This section only applies to Generators with two X-ray Tubes.
The Tube Selection signals are available through two contacts free of voltage
locatedonthestarter.
TUBE-1 SELECTIONTUBE-2 SELECTIONSELECTION COMMON
on the LF-RAC BoardJ1-10J1-11J1-12
on the LV-DRAC Module11KT1-8411 KT 1-72
11KT1-83 and 11KT1-71
3.4INTERCONNECTION CABLES
(connect both)
This section identifies the cables and runs needed for Generator and System
Interconnection. Route and connect the interconnection cables from each
component installed in the system to the Generator Cabinet as indicated in
Illustration 3-2 and Section 5.2 -- Interconnection Maps “543010XX”.
Interconnection cables should not be routed into the same
conduit or cable raceway as the Power or High Voltage
cables.
22
IN-1052R0
Page 57
Illustration 3-2
Interconnection C ables
ATP C ONS OLE C PU
J1
POWER CABLE
(factory supplied)
HF Series Generators
Installation
GENERATOR CABINET
J2
J3
J14
J7 or J8
J2
J5
J13
COMMUNICATION CABLE
SERIAL COMMUNICATION (factory supplied)
INTERFACE CABLE
AEC INTERFACE CABLE
TOMO INTERFACE CABLE (factory supplied)
GND CABLES
(factory supplied)
(factory supplied)
(factory supplied)
(factory supplied)
J3
J5
TS1
TS1
TS2
TS3
COMPATIBILITIES
ADAPTATIONS
L1/L2/L3/N/GND
SERIAL COMMUNICATION
ROOM DOOR CABLE
(customer supplied)
ROOM LIGHT CABLE
(customer supplied)
CABLES FROM BUCKY 1 & 2
(ONLY FOR SYSTEMS WITH 1 OR 2 BUCKY)
(field supplied)
STATOR, FAN & THERMOSTAT FROM TUBES
(field supplied)
ION CHAMBERS, TOMO DEVICES
BUCKY 3 & 4, IMAGE SYSTEMS
(customer supplied)
POWERLINE&GNDFOR
LINE POWERED GENERATORS
(customer supplied)
IN-1052R0
Note .
For Serial Generators (RS232 / RS422): Console CPUs are
located inside the Generator Cabinet and Interconnections are
factory made. Only one cable (serial communication) from J5 of
the Generator Cabinet should be connected to the Control Box, or
PC Interface Box, or Serial Console.
23
Page 58
HF Series Generators
Installation
3.4.1SERIAL INTERCONNECTION RS232 / RS422
GENERATOR TOUCH SCREEN (TPC) USING A POSITIONER WITHOUT
TOUCH SCREEN
For Generator using a TPC, perform the following connections:
(Refer to Illustration 3-3)
1.Connect the AC Supply Cable (A7059--xx) from “AC Supply” connector
of the TPC to the respective terminals in TS1 of the Generator Cabinet.
2.Connect the Serial Interconnection Cable (A7067--xx) from “COM1
(Generator)” of the TPC to J5 of the Generator Cabinet.
Note .
3.Connect the Handswitch Cable to the Handswitch connector of the TPC.
4.The TPC includes extra connectors for the Mouse and the Keyboard.
Connect them as indicated in the illustration below. In some cases, these
communication ports are used to interface the TPC with other devices.
For futher information, refer to Section 5.2 -- Maps 54301052 and
A6188--03 at the end of this Document.
24
IN-1052R0
Page 59
HF Series Generators
Illustration 3-3
Connection of the Generator Touch Screen (TPC) using a Positioner without Touch Screen
Installation
GENERATORTPC
HANDSWITCH
TS1
J5
AC SUPPLY CABLE (A7059--xx)
SERIAL CABLE (A7067--xx)
AC SUPPLY
COM 1 (GENERATOR)
COM 2
TOUCH SCREEN
(INTERNAL)
M (MOUSE)OPTIONAL MOUSE
KB (KEYBOARD)
HANDSWITCH
COM 3
COM 4
OPTIONAL KEYBOARD
Label of Operating System Licence
Serial Interconnection Cable (COM1)
Other Connections (keyboard, etc.)
IN-1052R0
AC Supply Cable
Handswitch
25
Page 60
HF Series Generators
Installation
GENERATOR TOUCH SCREEN (TPC) USING A POSITIONER WITH
TOUCH SCREEN
For Generator using a TPC, perform the following connections:
(Refer to Illustration 3-4)
1.Connect the AC Supply Cable (A7059--xx) from “AC Supply” connector
of the TPC to the respective terminals in TS1 of the Generator Cabinet.
2.Connect the Serial Interconnection Cable (A3352--xx) from “COM1(Generator)”oftheTPCtoJ2“Console” of the System Interface Panel
in the Control Box.
3.Connect the Serial Interconnection Cable (A7067--xx) from J1
“Generator” of the System Interface Panel in the Control Box to J5 of the
Generator Cabinet.
Note .
4.Connect the Handswitch Cable to the Handswitch connector of the TPC.
5.The TPC includes extra connectors for the Mouse and the Keyboard.
Connect them as indicated in the illustration below. In some cases, these
communication ports are used to interface the TPC with other devices.
For further information, refer to Section 5.2 -- Maps 54301052 and
A6188--03 at the end of this Document, and refer to the respective
Positioner Service Manual.
26
IN-1052R0
Page 61
HF Series Generators
Illustration 3-4
Connection of the Generator Touch Screen (TPC) using a Positioner with Touch Screen
Installation
GENERATORTPC
HANDSWITCH
TS1
J5
AC SUPPLY CABLE (A7059--xx)
AC SUPPLY
COM 1 (GENERATOR)
COM 2
TOUCH SCREEN
(INTERNAL)
POSITIONER CONTROL BOX
SERIAL CABLE (A7067--xx)
J1 (GENERATOR)
J2 (CONSOLE)
J6 (REMOTE ON)ON
REMOTE ON CABLE (A9611--xx)
SERIAL CABLE (A3352--xx)
M (MOUSE)OPTIONAL MOUSE
KB (KEYBOARD)
HANDSWITCH
COM 3
COM 4
OPTIONAL KEYBOARD
Label of Operating System Licence
Serial Interconnection Cable (COM1)
Other Connections (keyboard, etc.)
IN-1052R0
AC Supply Cable
Handswitch
27
Page 62
HF Series Generators
Installation
VIRTUAL CONSOLE (PC) USING A POSITIONER WITHOUT TOUCH
SCREEN
Systems using a Virtual Console running on a PC usually must have a PC
Interface Box installed between the PC and Generator.
(Refer to Illustration 3-5)
Perform the following connections:
1.Remove the Back Cover of the PC Interface Box.
2.Connect the Serial Interconnection Cable (A3352--01) from J1 of the PC
Interface Box to J5 of the Generator Cabinet.
3.Connect the Handswitch Cable to J2 of the PC Interface Box.
4.Connect the Interface Box--Computer Cable (A3363 --01) to J3 of the PC
Interface Box and the other end (2 connectors) to COM1
(Communication) and J1 (Auto ON/OFF) of the Computer connectors.
Note .
J1 connector is only available in Computers provided with Auto
ON/OFF Board inside (factory installed).
5.Re-install the Back Cover of the PC Interface Box.
6.Check to set proper Line Voltage on PC. Plug the Power Line cable for
the Computer to a 110 VAC or 230 VAC socket.
Note .
For further information, refer to Section 5.2 -- Maps 54301052,
A6188--03 and I/F-036 at the end of this Document.
Illustration 3-5
Connection of the Virtual Console (PC) using a Positioner without Touch Screen
28
GENERATOR
CABINET
J5
SERIAL CABLE (A3352--01)
HANDSWITCH
PC INTERFACE
BOX
J1
J2
J3
PC BOX / PC CABLE
(A3363--01)
POWER LINE CABLE
TO 110 / 230 VAC SOCKET
PC (COMPUTER)
J1
COM1
IN-1052R0
Page 63
HF Series Generators
Installation
VIRTUAL CONSOLE (PC) USING A POSITIONER WITH TOUCH SCREEN
Systems using a Virtual Console running on a PC usually must have a PC
Interface Box installed between the PC and Generator.
(Refer to Illustration 3-5)
Perform the following connections:
1.Remove the Back Cover of the PC Interface Box.
2.Connect the Serial Interconnection Cable (A3352--01) from J1 of the PC
Interface Box to J2 “Console” of the System Interface Panel in the Control
Box.
3.Connect the Serial Interconnection Cable (A7067--xx) from J1
“Generator” of the System Interface Panel in the Control Box to J5 of the
Generator Cabinet.
4.Connect the Handswitch Cable to J2 of the PC Interface Box.
5.Connect the Interface Box--Computer Cable (A3363 --01) to J3 of the PC
Interface Box and the other end (2 connectors) to COM1
(Communication) and J1 (Auto ON/OFF) of the Computer connectors.
Note .
J1 connector is only available in Computers provided with Auto
ON/OFF Board inside (factory installed).
6.Re-install the Back Cover of the PC Interface Box.
7.Check to set proper Line Voltage on PC. Plug the Power Line cable for
the Computer to a 110 VAC or 230 VAC socket.
Note .
For further information, refer to Section 5.2 -- Maps 54301052,
A6188--03 and I/F-036, and refer to the respective Positioner
Service Manual.
Illustration 3-6
Connection of the Virtual Console (PC) using a Positioner with Touch Screen
CABINET
J5
SERIAL CABLE (A7067--xx)
CONTROL
BOX
J2
J1
SERIAL CABLE (A3352--01)
HANDSWITCH
PC INTERFACE
BOX
J1
J2
J3
PC BOX / PC CABLE
(A3363--01)
PC (COMPUTER)GENERATOR
J1
COM1
IN-1052R0
POWER LINE CABLE
TO 110/230 VAC SOCKET
29
Page 64
HF Series Generators
Installation
GENERATOR SERIAL CONSOLE
For systems using a Serial Console, only a Serial Interconnection Cable
(A7066--xx) from J5 of the Generator Cabinet must be connected to the J1 of
the Serial Console. (Refer to Section 5.2 -- Maps 54301052, A6188-- 03).
3.4.2COLLIMATOR ERROR SIGNAL (OPTIONAL)
This option must be requested on the customer order. For systems using an
Automatic Collimator, the X-ray exposure can be inhibited due to a Collimator
Error. This signal can be used only for one Automatic Collimator in the system,
special interconnection should be required w hen two Collimators are present.
Connect two wires from the Collimator to Terminal Block 4TS3-20 (Collimator
Error signal) and 3TS1-18 (or another GND in this Terminal Block). Collimator
Error signal goes (through the Interface Cable) from 4TS3-20 in the Generator
Cabinet to terminal J2-6 in Connector J2 of the ATP Console CPU Board. If the
system is not provided with Automatic Collimator connect 4TS3--20 to GND
(3TS1--18).
3.4.3DOOR INTERLOCK SIGNAL
Connect two wires from the Room Door Interlock Switch(es) to Terminal Block
3TS1-22 (Door signal) and 3TS1-23 (Door Rtn - gnd). If the X-ray Room is not
provided with a Door signal, place a jumper between both connections in
Terminal Block 3TS1.
At this point, proceed to perform t he complete Configuration
and the Calibration procedures except for AEC. Once
Configuration and Calibration tasks have been performed,
proceed with the rest of the Installation and Calibration tasks.
30
IN-1052R0
Page 65
3.4.4WARNING LIGHT SIGNAL
Room Warning Lamp(s) can be externally powered, or internally by the Terminal
Block 3TS1. Room Lamp(s) must be connected through the Terminal Block
3TS1-47 and 3TS1-48 (internal relay on Interface Control Board) to enable the
Generator switches On/Off the Room Warning Lamps. (Refer to Section 5.2 --I/F-008).
3.4.5COLLIMATOR LAMP AND SYSTEM LOCKS
The Generator can supply power to the Manual Collimator Lamp and System
Locks (Table, Vertical Bucky, etc.)
HF Series Generators
Installation
Note .
Connect wires from the Collimator Lamp to Terminal Block TB7-3 (24 VAC) and
TB7-4 ( 0 VAC) of the Lock Board.
Connect wires from the Locks to Terminal Block TB7-5 (+24 VDC) and TB7-6
(0 VDC) of the Lock Board.
Lock Board
When required, voltages (VAC and VDC) on TB7 can be changed
by connecting their respective wires to the other available
terminals on the Input Transformer 6T2. (Refer to Schematics
543020XX).
IN-1052R0
31
Page 66
HF Series Generators
Installation
3.4.6BUCKYS (OPTIONAL)
Connect the Bucky as indicated in the Section 5.2 (Interconnections Maps for
Buckys), and test them before connecting the Ion Chambers.
The following table represents the standard Bucky cable connections:
SYSTEMCABLE FROM BUCKY IS CONNECTED TO
Systems with 1 or 2 Bucky
Systems with 3 or 4 Bucky
The Bucky of a RAD only Table with Tomo Device
Note .
Optional “Tomo / Bucky Adaptation Board” is required to install
more than two Buckys in the System. (Refer to the “Tomo / Bucky
Adaptation Board” and the Manual for the Bucky).
If the “ Bucky Start” signal enters the Bucky through a relay or another inductive
device (a.e. a motor), it is mandatory to add the supplied R2--C2 close to each
Bucky, so they have to be connected on the terminal output of the Bucky
assembly. The R-Cs are attached to the Generator harness in a bag.
If “Bucky Start” signal enters the Bucky through an optocoupler, do not add the
suppliedR2--C2fortheBucky.
Note .
The operations described above will prevent noises and
uncontrolled Bucky movements that can cause exposure cutting
or console blocking.
Terminal Block 3TS1 of the Generator Cabinet
(Refer to Section 5.2 -- Bucky)
Terminal Block TB2 of the optional “Tomo / Bucky Adaptation Board”,
located in the Generator Cabinet
(Refer to “Tomo / Bucky Adaptation Board” and Section 5.2 -- Buckys).
Terminal Block TB1 of the optional “Tomo / Bucky Adaptation Board”,
located in the Generator Cabinet
(Refer to “Tomo / Bucky Adaptation Board” and Section 5.2 -- Buckys).
3.4.7TOMO DEVICE (OPTIONAL)
RAD Only T
The Tomo cable (A3083-01) from connector J13 of the “ATP Console CPU
Board” has to be connected to the Terminal Blocks TB1 and TB2 of the optional
“Tomo / Bucky Adaptation Board”, located in the Generator Cabinet.
The cables from the Tomo Device are also connected to the Terminal Blocks
TB1 and TB2 of the optional “Tomo / Bucky Adaptation Board”. Refer to the
“Tomo / Bucky Adaptation Board” for more detailed information and interface.
(Refer also to the Manuals of the Tomo Device).
Note .
RAD only Table requires the optional “Tomo / Bucky Adaptation
Board”.
32
able
IN-1052R0
Page 67
3.4.8ION CHAMBERS (OPTIONAL)
The “AEC Control Board” (A3012-XX) must be installed on the ATP Console
CPU Board before installing the Ion Chamber(s). The “AEC Adaptation Board”
(A3263-03) is also required. (Refer to the “Ion Chamber” Service Manuals).
Perform the following tasks in the order described:
HF Series Generators
Installation
Note .
The Generator is only compatible with Ion Chambers that output
a positive ramp.
1.If an Ion Chamber requires High Voltage(200to 500 VDC), the Generator
must include an Interface Control Board (version A3009-09/12) that
supplies this voltage.
The Interface Control Board must have Jumpers from W3 to W8 in “A”
position. This High Voltage is supplied through Terminal Block 3TS1-39
“PT SPLY” of the Generator Cabinet and sent with a wire to TB1-9 of the
“AEC Adaptation Board”.
ION CHAMBERS WITH HIGH VOLTAGE
GEBVM-CGR
AMP-Phenolic ConnectorDB 15 Connector
300 VDC230 VDC500 VDC400 VDC
Notes: -- If the System included both GE and BVM-CGR Ion Chambers, Terminal TB1-9 must supply 270 VDC.
-- Philips Amplimat Ion Chambers can not be installed with GE or BVM-CGR Ion Chambers.
PHILIPS AMPLIMAT
IN-1052R0
DO NOTCONNECT ANYION CHAMBERTO THE
GENERATOR CABINET UNTIL HIGH VOLTAGE IS EITHER
VERIFIED OR ADJUSTED TO THE VALUES REQUIRED.
OTHER VOLTAGE COULD DAMAGE THE ION CHAMBERS.
Turn the Generator ON and verify voltage in TB1-9 according to the Ion
Chambers to be installed. If necessary, adjust the High Voltage at
Potentiometer R20 of the Interface Control Board. Turn the Generator
OFF after adjustment.
33
Page 68
HF Series Generators
Installation
2.Connect each Ion Chamber cable to J1 (IC1), J2 (IC2), J3 (IC3) or J5
(IC4) of the “AEC Adaptation Board”. The code for the Ion Chamber cable
supplied by the Generator manufacturer is A3253--01.
Note .
Note .
Same Ion Chamber types have to be installed in consecutive order
starting at J1 (IC1). In the case of using four Ion Chambers, IC3
and IC4 must have the same film/cassette combination.
The Vacutec, AID or similar Ion Chamber type is directly
connected to the “AEC Adaptation Board”.For Comet Ion
Chambers, cable connection has to be made previously through
the Comet Preamplifier PA-021 and then directly to the “AEC
Adaptation Board”.
For other cases, a cable adapter is required. The Generator
manufacturer has the following cable adapters available: GE
(A3082--01),CGR-BVM(A3081--01),PhilipsAmplimat
(A3080--01/02 with DB-15 or A6727-01/02 with Phenolic
connector) and MEDYS (A6715--01).
34
IN-1052R0
Page 69
Illustration 3-7
*
Four Ion Chamber Connection
HF Series Generators
Installation
GENERATOR
POWER INTERFACE Cable
TS1
ATP CONSOLE BOARD
J5
AEC INTERFACE Cable
ATP CONSOLE CPU BOARD
AEC ADAPTATION BOARD
TB1
J4
POWER INTERFACE CABLE
AEC INTERFACE CABLE
(A3263--03)
AEC ADAPTATION PCB
TB1TS1 (Generator Cabinet)
ADAPTATION CABLE*
ADAPTATION CABLE*
TB1--9
ADAPTATION CABLE*
ADAPTATION CABLE*
J4J5
J1
J2
J3
J5
* Connections free of voltage IC Adaptation
Cables
ION CHAMBER Cable
J1
ION CHAMBER Cable
J2
ION CHAMBER Cable
J3
ION CHAMBER Cable
J5
IC 1 PREAMPLIFIER
IC 2 PREAMPLIFIER
IC 3 PREAMPLIFIER
IC 4 PREAMPLIFIER
Connections with IC Adaptation Cables
ION CHAMBER 1
(field supplied)
ION CHAMBER 2
(field supplied)
ION CHAMBER 3
(field supplied)
ION CHAMBER 4
(field supplied)
3.Configure Jumpers from JP1 to JP8 and from JP13 to JP16 according to
the group of Ion Chamber type:
4.Each type of Ion Chamber requires a specified reference voltage for
“Area Selections” and “AEC Reset” signals:
GVacutec, AID and Comet Ion Chambers require GND (TB1-10).
GMEDYS, CGR-BVM, GE and Philips Amplimat Ion Chambers
require +24 VDC (TB1-4).
The reference voltage is provided from: TB1-7 “Relay 1” for IC1; TB1-6
“Relay 2” for IC2; TB1-5 “Relay 3” for IC3; and TB1-8 “Relay 4” for IC4.
For each group of Ion Chambers of the same type, connect a wire
between each of the above mentioned terminals to TB1-10 (GND), TB1-4
(+24 VDC) or TB1-3 (+12 VDC) depending on the voltage required
(examples: for four MEDYS Ion Chambers add only a wire-jumper
between TB1-7 and TB1-4; or for one MEDYS Ion Chamber as IC-1 and
one COMET Ion Chamber as IC-2add a wire-jumper between TB1-7 and
TB1-4, and another wire between TB1-6 and TB1-10).
DO NOT TURN ON THE GENERATOR UNTIL THE INPUT
SIGNALS OF ALL THE ION CHAMBERS ARE CONNECTED TO
THE REQUIRED VOLTAGE. OTHER VOLTAGE MIGHT
DAMAGE THE ION CHAMBERS.
5.Ion Chambers output must be 0 VDC when there is no-radiation
(No-Offset adjustment). If an Ion Chamber output has an offset, it must
be adjusted to 0 VDC with the respective Potentiometer.
Configure Jumpers from JP9 to JP12 and turn ON the Generator only to
adjust the following Potentiometers (if needed) according to the Ion
Chamber output:
ION CHAMBER OUTPUT
NO-OFFSET ADJUSTMENTAAAA
OFFSET ADJUSTMENTBBBB
TEST POINT AND POTENTIOMETER
(ONLY IF JUMPER IS IN “B” POSITION)
JP9 (IC1)JP10 (IC2)JP11 (IC3)JP12 (IC4)
TP1 -- R11TP2 -- R8TP4 -- R2TP12 -- R5
JUMPERS POSITION
36
IN-1052R0
Page 71
HF Series Generators
SECTION 4FINAL INSTALLATION AND CHECKS
4.1HV TRANSFORMER
This point does not apply to the hermetic HV Transformers
(black aluminium HV Transformers).
Installation
Ventilation Screw
The HV Transformer contains “Shell Diala AX” oil. Check that there is no oil
leakage. If leakage is found, remove the oil fill plug from the top of the HV
Transformer and verify that the oil level is within 20 mm (3/4”) from the top of
the H V Transformer. Add “Shell Diala AX” oil if necessary.
Unscrew the Ventilation Screw from the top of the HV Transformer.
4.2CABLE FASTENING AND COVERS
Note .
Before re-installing cabinet covers, perform the rest of the required
Calibration procedures (a.e. AEC).
Check that all electrical connections are firm and secure. Cables should be
correctly routed. (Refer to Section 3.1)
In order to avoid signal interferences, it is strongly
recommended to fold and fasten close to the Generator
Cabinet the portion of cables not routed (see picture below).
Never wrap in circles.
IN-1052R0
YESNO
Re-install the Cabinet covers and connect its internal ground wires. Power line,
High Voltage and Interconnections cables must go through the cover cable
outlet.
37
Page 72
HF Series Generators
Installation
This page intentionally left blank.
38
IN-1052R0
Page 73
SECTION 5SYSTEM INTERCONNECTIONS
5.1SYSTEM INTERCONNECTION SIGNALS
All input signals are active low. This means the inputs must be pulled to ground
(chassis ground of the Generator) thru relay contacts, by a transistor or other
switching device. The current requirement of the switch is less than 10 mA.
Do not apply 115 / 220 VAC logic signals to any of the logic
inputs. If 115 / 220 VAC logic signals are used in the X-ray
table, these signals must be converted to a contact closure
by a relay.
HF Series Generators
Installation
The outputs signals from the Generator to the subsystem devices are usually
active low (switched to chassis ground of the Generator). The outputs are open
collector transistor drivers with a maximum current of 0.5 Amperes.
Table 5-1
System Interconnection Signals
SIGNAL NAMESIGNAL DESCRIPTION
AUX BUCKY SPLYExternal voltage supply required for the Bucky motion, when this voltage is not +24 VDC.
--BUCKY 1 DR CMDA low signal to the Interface Control Board as a command to output a Bucky-1 (normally the Table Bucky) drive signal.
--BUCKY 1 MOTIONThis low going signal from Bucky-1 indicates Bucky-1 motion, and therefore the exposure is enabled.
BUCKY 1 DRThis signal is originated from the Bucky supply of the Power Module when an exposure order. It starts the Bucky.
--BUCKY 2 DR CMDAlow signal to the InterfaceControlBoard as a commandtooutput a Bucky-2 (normally theVertical Bucky Stand)drivesignal.
--BUCKY 2 MOTIONThis low going signal from Bucky-2 indicates Bucky-2 in motion, and therefore the exposure is enabled.
BUCKY 2 DRThis signal is originated from the Bucky supply of the Power Module when an exposure order. It starts the Bucky.
--BUCKY EXPThis low going (0 volts) signal starts the Bucky exposure. The signal originates on the Interface Board
BUCKY SPLYVoltage supply required for the Bucky drive command.
C--HT CLKSerial data clock to the HT Control Board. This clock synchronizes the C--HT DATA signal.
C--HT DATASerial data to the HT Control Board. This data is synchronous with the C--HT CLK signal.
--COLLIMATOR
This active lowsignalindicates that NO EXPOSURE HOLD condition existsatthe Collimator. This input is readonlywhen the
Radiographic Tube is selected.
--DOORThis low signal is the interlock for the Door of the X-ray room.
IN-1052R0
39
Page 74
HF Series Generators
Installation
Table 5-1 (cont.)
System Interconnection Signals
SIGNAL NAMESIGNAL DESCRIPTION
--FLD1 DRA low signal to select the right field in the Ion Chamber.
--FLD2 DRA low signal to select the left field in the Ion Chamber.
--FLD3 DRA low signal to select the center field in the Ion Chamber.
HT--C CLKSerial data clock from the HT Control Board. This clock synchronizes the HT--C DATA signal.
HT--C DATSerial data from the HT Control Board. This data is synchronous with the HT--C CLK signal.
-- H T I N L
This signal is low when the switch in the high voltage transformer is in the RAD position. This is a safety interlock which
prevents an exposure if the high voltage switch (in the HV Transformer) is in the wrong position.
HV PT CRL
IC GNDGNDfortheICSPLY.
IC1 INPUTThis input is the output of the Bucky 1 Ion Chamber (normally the Table Ion Chamber).
IC2 INPUTThis input is the output of the Bucky 2 Ion Chamber (normally the Vertical Bucky Stand Ion Chamber).
IC3 INPUTThis input is the output of the Spot Film Ion Chamber.
IC SPLYPower supply for the Ion Chamber. This output should be within the range of 500 to 800 volts.
--LINE CONTA low signal energizes the main line contactor K5 in the Power Module.
--PREP
--READY
--ROOM LIGHT
-- S T R T D RA low signal to indicate the start of an exposure to the Ion Chamber.
--THERMOSTAT-1This signal from X-ray Tube indicates the overheat of the Tube-1.
--THERMOSTAT-2This signal from X-ray Tube indicates the overheat of the Tube-2.
This analogicsignal(originates in the optionalAECControl Board) controls theoutputof the HVPowerSupply on the Interface
Control Board. +5 volts programs the output to be 0 volts, and 0 volts programs the output to approximately --1200 volts.
Commands totheHT Control Board toboost X-ray Tube Filamenttothe value of mA selectedand to start the X-rayTube Rotor
is RAD Tube is selected.
This lowgoingsignal indicates thesystemis ready to makean exposure (Prep cyclecomplete). This signalisused to interface
to certain peripheral devices such as Film Changers, etc.
This low going signal indicates the X-ray preparation or exposure. This signal is used to interface to the Room X-ray warning
light.
40
IN-1052R0
Page 75
5.2SYSTEM INTERCONNECTION MAPS
Refer to the following maps for details of the wire connections.
SYSTEM INTERCONNECTION
•Compact / Compact-ESM Generators.
System Interconnection54301045.............................
•Serial Communication to Generator.
System Interconnection54301052.............................
•RS-232/422/485 Serial CommunicationA6188--03...............
•PC / Serial Interface BoxI/F-036............................
•Metallic Case X-ray Tube Connection54302035.................
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and
C2=470 nF, 250 VAC as shown.
Don’t add that R2--C2 for Liebel--Flarsheim 8000 Series Bucky, and
remove resistor R36 and R37 in the INTERFACE CONTROL board.
NOTA 1: Asegurarse que el terminal
B2 no está conectado al B3.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%, y
C2=470 nF, 250 VAC según se muestra.
Para Bucky Liebel--Flarsheim Series 8000, no añadir esa R2--C2, y quitar
las resistencias R36 y R37 en la tarjeta INTERFACE CONTROL.
Interf. board revised
8
Innomed added
7
REV DESCRIPTIONISSUED BYDATE
14/03/08F. GARCIA
09/09/02F. GARCIA
DRAWING
REVISED
NAMEDATE
F. GARCIA15/03/95
A. DIAZ15/03/95
SEDECAL
SHEET / OF
1/4
Interconnection Cable
Cable de Inerconexión
TABLE BUCKY INTERFACE
INTERFAZ BUCKY MESA
I/F--001
7REV8
Page 88
GENERATOR POWER MODULETABLE
BUCKY LIEBEL (Automatic)
BUCKY INNOMED (IBC 430)
Automatic
Bucky
B1
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
B2
B3
B8
B4
ADD
JUMPER
(SEE
NOTE 3)
R2
C2
BUCKY 1 MOTION
BUCKY 1 MOTION RTN
BUCKY 1 DR
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--5
TS1--6
TS1--4
TS1--3
TS1--2
TS1--1
J4--11
J4--8
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K5
K5
+24 VDC
J4--9
K3
K5
BUCKY EXP
BUCKY 1
DR CMD
NOTE 1: Be sure that B2 terminal is
not connected to B3 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and
C2=470 nF, 250 VAC as shown.
Don’t add that R2--C2 for Liebel--Flarsheim 8000 Series Bucky, and
remove resistor R36 and R37 in the INTERFACE CONTROL board.
NOTA 1: Asegurarse que el terminal
B2 no está conectado al B3.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%, y
C2=470 nF, 250 VAC según se muestra.
Para Bucky Liebel--Flarsheim Series 8000, no añadir esa R2--C2, y quitar
las resistencias R36 y R37 en la tarjeta INTERFACE CONTROL.
Innomed added7
REV DESCRIPTIONISSUED BYDATE
F. GARCIA
F. GARCIA
14/03/08Interf. board revised8
09/09/02
DRAWING
REVISED
NAMEDATE
F. GARCIA15/03/95
A. DIAZ15/03/95
SEDECAL
SHEET / OF
2/4
Interconnection Cable
Cable de Inerconexión
TABLE BUCKY INTERFACE
INTERFAZ BUCKY MESA
I/F--001
7REV8
Page 89
GENERATOR POWER MODULETABLE
BUCKY
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
BUCKY ULTRAVIT
1
2
4
(SEE
NOTE 3)
R2
7
5
8
C2
ADD
JUMPER
BUCKY 1 MOTION
BUCKY 1 MOTION RTN
BUCKY 1 DR
0VAC
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--5
TS1--6
TS1--4
TS1--3
TS1--2
TS1--1
J4--11
J4--8
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K5
K5
+24 VDC
J4--9
K3
K5
BUCKY EXP
BUCKY 1
DR CMD
NOTE 1: Be sure that 2 terminal is
not connected to 4 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%;
and C2=470 nF, 250 VAC as shown.
NOTA 1: Asegurarse que el terminal 2
no está conectado al 4.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%;
y C2=470 nF, 250 VAC según se muestra.
8
Interf. board revised
Innomed added7
REV DESCRIPTIONISSUED BYDATE
F. GARCIA
F. GARCIA
14/03/08
09/09/02
DRAWING
REVISED
NAMEDATE
F. GARCIA15/03/95
A. DIAZ15/03/95
SEDECAL
SHEET / OF
3/4
Interconnection Cable
Cable de Inerconexión
TABLE BUCKY INTERFACE
INTERFAZ BUCKY MESA
I/F--001
7REV8
Page 90
GENERATOR POWER MODULETABLE
BUCKY
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
BUCKY DONG-- A
5
6
4
(SEE
NOTE 3)
R2
C2
2
3
ADD
JUMPER
1
7
BUCKY 1 MOTION
BUCKY 1 MOTION RTN
BUCKY 1 DR
0VAC
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--5
TS1--6
TS1--4
TS1--3
TS1--2
TS1--1
J4--11
J4--8
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K5
K5
+24 VDC
J4--9
K3
K5
BUCKY EXP
BUCKY 1
DR CMD
NOTE 1: Be sure that 6 terminal is
not connected to 4 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%;
and C2=470 nF, 250 VAC as shown.
NOTA 1: Asegurarse que el terminal 6
no está conectado al 4.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%;
y C2=470 nF, 250 VAC según se muestra.
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and
C2=470 nF, 250 VAC as shown.
Don’t add that R2--C2 for Liebel--Flarsheim 8000 Series Bucky, and
remove resistor R36 and R37 in the INTERFACE CONTROL board.
NOTA 1: Asegurarse que el terminal
B2 no está conectado al B3.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%, y
C2=470 nF, 250 VAC según se muestra.
Para Bucky Liebel--Flarsheim Series 8000, no añadir esa R2--C2, y quitar
las resistencias R36 y R37 en la tarjeta INTERFACE CONTROL.
Innomed added7
REV DESCRIPTIONISSUED BYDATE
F. GARCIA
F. GARCIA
14/03/08Interf board revised8
09/09/02
DRAWING
REVISED
NAMEDATE
F. GARCIA15/03/95
A. DIAZ15/03/95
SEDECAL
SHEET / OF
1/4
Interconnection Cable
Cable de Inerconexión
VERTICAL BUCKY INTERFACE
INTERFAZ BUCKY VERTICAL
I/F--002
7REV8
Page 92
GENERATOR POWER MODULEVERTICAL BUCKY
BUCKY LIEBEL (Automatic)
BUCKY INNOMED (IBC 430)
Automatic
Bucky
B1
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
B2
B3
B8
B4
ADD
JUMPER
(SEE
NOTE 3)
R2
C2
BUCKY 2 MOTION
BUCKY 2 MOTION RTN
BUCKY 2 DR
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--12
TS1--13
TS1--11
TS1--10
TS1--9
TS1--8
J4--10
J4--7
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K4
K4
+24 VDC
J4--9
K3
K4
BUCKY EXP
BUCKY 2
DR CMD
NOTE 1: Be sure that B2 terminal is
not connected to B3 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and
C2=470 nF, 250 VAC as shown.
Don’t add that R2--C2 for Liebel--Flarsheim 8000 Series Bucky, and
remove resistor R36 and R37 in the INTERFACE CONTROL board.
NOTA 1: Asegurarse que el terminal
B2 no está conectado al B3.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%, y
C2=470 nF, 250 VAC según se muestra.
Para Bucky Liebel--Flarsheim Series 8000, no añadir esa R2--C2, y quitar
las resistencias R36 y R37 en la tarjeta INTERFACE CONTROL.