Kodak PI-1005 Service manual [gb]

Page 1
Technical Publication
PI-1005R3
Pre-Installation
HF Series Generators
Page 2
Page 3
REVISION DATE REASON FOR CHANGE
0 JUL 15, 2002 First edition
1 SEP 20, 2003 kW corrections for SHF-5xx model
2 FEB 17, 2004 New equipments
HF Series Generators
Pre-Installation
3
This Document is the English original version, edited and supplied by the manufacturer.
The Revision state of this Document is indicated in the code number shown at the bottom of this page.
SEP 15, 2005 Revision of environmental and electrical requirements
ADVISORY SYMBOLS
The following advisory symbols will be used throughout this manual. Their application and meaning are described below.
DANGERS ADVISE OF CONDITIONS OR SITUATIONS THAT IF NOT HEEDED OR AVOIDED WILL CAUSE SERIOUS PERSONAL INJURY OR DEATH.
ADVISE OF CONDITIONS OR SITUATIONS THAT IF NOT HEEDED OR AVOIDED COULD CAUSE SERIOUS PERSONAL INJURY, OR CATASTROPHIC DAMAGE OF EQUIPMENT OR DATA.
PI-1005R3
Advise of conditions or situations that if not heeded or avoided could cause personal injury or d amage to equipment or data.
Note . Alert readers to pertinent facts and conditions. Notes represent
information that is important to know but which do not necessarily relate to possible injury or damage to equipment.
Page 4
Page 5
HF Series Generators
Pre-Installation
TABLE OF CONTENTS
Section Page
1 INTRODUCTION 1.........................................................
1.1 Responsibility of Purchaser 1..........................................
2 PRE-INSTALLATION DATA 3...............................................
3 ROOM REQUIREMENTS 11.................................................
3.1 Environmental Requirements 11.........................................
3.2 Electrical Requirements 11.............................................
3.3 Line Powered Generators -- Power Line Requirements 12...................
3.4 Line Powered Generators -- Recommended Wire Size 15...................
3.5 Capacitor Assisted Generator s -- Power Line Requirements 17..............
3.6 Capacitor Assisted Generators -- Recommended Wire Size 17...............
3.7 Battery Powered generators -- Power Line Requirements 18.................
3.8 Battery Powered Ggenerators -- Recommended Wire Size 18...............
3.9 Interconnection and Grounding Requirements 19..........................
3.10 Safety Devices 22.....................................................
i
PI-1005R3
Page 6
HF Series Generators
Pre-Installation
PI-1005R3
ii
Page 7
SECTION 1 INTRODUCTION
This Pre-Installation document provides the information and data needed to plan and qualify the customer site prior to equipment delivery and installation.
This document considers only the Generator and its associated components. Product information, environmental and electrical requirements are specified.
For system-related requirements, such as room layout, and system interconnections, refer to documentation provided with other subsystems.
1.1 RESPONSIBILITY OF PURCHASER
HF Series Generators
Pre-Installation
Note .
Site planning and preparation are the responsibilities of the purchaser. The following points should be considered fundamental to the customers Pre-Installation activities; addition work may be needed depending on specific site circumstances:
Install required material prior the delivery of the system components.
Complete room floor, ceiling and wall finish.
Install c onduit, duct, and raceway.
Install proper size junction boxes with covers at locations specified in the
installation plan.
Install mains power of proper voltage output and adequate kVA rating.
Install all safety devices according to this document and Local Codes.
Provide current room dimensions, including hall way and entry door
sizes.
Complete and proper Pre-Installation will avoid delays and confusion.
PI-1005R3
1
Page 8
HF Series Generators
Pre-Installation
This page intentionally left blank.
2
PI-1005R3
Page 9
SECTION 2 PRE-INSTALLATION DATA
This section provides product information and illustrations showing physical dimensions, weight, mounting holes and normal access areas for cabling and service. (Refer to Illustration 2-1.)
PHYSICAL CHARACTERISTICS
HF Series Generators
Pre-Installation
COMPONENT
LINE POWERED GENERATORS
Vertical Generator Cabinet
with LF-RAC (LSS) or DRAC (HSS)
Compact Generator Cabinet
(for only 1 Tube (LSS))
Compact Generator Cabinet
(for 1 or 2 Tubes (LSS or HSS))
CAPACITOR ASSISTED GENERATORS
Compact Generator Cabinet
with Capacitors Module
DIMENSIONS
WEIGHT
Length Width Height
506 mm 468 mm 1101 mm 148 kg
445 mm 360 mm 568 mm 72 kg
592 mm 360 mm 690 mm 95 kg
500 mm 360 mm 790 mm 108 kg
BATTERY POWERED GENERATORS
Compact--ESM Generator Cabinet
with Batteries Module
Compact--ESM Generator Cabinet
with Batteries Module (17 A/h batteries)
PI-1005R3
813 mm 436 mm 948 mm 235 kg
813 mm 436 mm 1223 mm 372 kg
3
Page 10
HF Series Generators
TouchScreenConsol
e
Pre-Installation
PHYSICAL CHARACTERISTICS
COMPONENT
STANDARD CONTROL CONSOLES
RAD Control Consoles
R&F Control Consoles
RAD Console Graphic Display
Touch Screen Console
(TPC 10” or 12”)
Optional Pedestal for
RAD Console Graphic Display or Touch Screen Console
Note.-- Dimensions for no-standard Consoles are not indicated in this document.
w/o Pedestal 433 mm 298 mm 123 mm 8kg
with Pedestal 433 mm 298 mm 1023 mm 22 kg
w/o Pedestal 554 mm 360 mm 124 mm 12 kg
with Pedestal 554 mm 360 mm 1010 mm 35 kg
with Handswitch support 545 mm 290 mm 50 mm 6kg
w/o Handswitch support 430 mm 290 mm 50 mm 6kg
with Handswitch support 468 mm 290 mm 11 4 m m 8kg
w/o Handswitch support 360 mm 290 mm 11 4 m m 8kg
DIMENSIONS
WEIGHT
Length Width Height
298 mm 236 mm 930 mm 10 kg
TOUCH SCREEN CONSOLE AND PC UNIT
Touch Screen Console 400 mm 200 mm 400 mm 5kg
PC Unit 480 mm 200 mm 400 mm 15 kg
PC Interface Box 130 mm 140 mm 46 mm 0.6 kg
Note.-- Specifications of Touch Screen Consoles and PC Units subject to c hange without notice.
4
PI-1005R3
Page 11
METHOD OF MOUNTING
COMPONENT NORMAL METHOD OF MOUNTING
HF Series Generators
Pre-Installation
Generator Cabinet
Control Consoles Desk freestanding, wall mounted or anchor to an optional pedestal.
Note: Anchoring hardware should be field supplied. For seismic areas all components must be anchored,
Local Standards should be applied.
Floor freestanding, wall mounted or anchor to floor with four M10 (3/8”) bolts.
MINIMUM RECOMMENDED FREE AREA FOR SERVICE ACCESS
COMPONENT
Generator Cabinet
Control Consoles
Note: Ventilation conditions requires to keep a minimum free distance of 15 cm (6”) from both lateral sides of the Generator Cabinet and also the same distance from the rear side when the Generator is provided with High Speed Starter (fans for the starter module).
Left Side Right Side Front Rear Top Bottom
50 cm
(20”)
10 cm
(4”)
50 cm
(20”)
10 cm
(4”)
SURFACE
100 cm
(40”)
Completely
free
--
(see note)
10 cm
(4”)
Completely
free
Completely
free
--
--
PI-1005R3
5
Page 12
HF Series Generators
Pre-Installation
Illustration 2-1 Generators
Cable Access
568
COMPACT
GENERATOR
(For only 1 Tube)
445
251
28
435
200
6767 57 57 57 5783
44150 33 40 150 80206
8
67.5
427.5
Generator
Wall Support
702
Floor Support
422
110224
Wall and Floor Supports are options
19
40
315
6
PI-1005R3
Page 13
Illustration 2-1 (cont.) Generators
HF Series Generators
Pre-Installation
Cable Access
690
COMPACT
GENERATOR
(For 1 or 2 Tubes)
592
68 57 57 57 57
8
28
250
336
580
6857 57 57 57
44150 33 40 200 40280
40
67.5
427.5
Generator
827
Wall Support
Floor Support
422
PI-1005R3
105234
Wall and Floor Supports are options
19
40
462
7
Page 14
HF Series Generators
Pre-Installation
Illustration 2-1 (cont.) Generators
CAPACITORS
GENERATOR
Cable Access
790
Cable Access
VERTICAL
GENERATOR
1101
Cable Access
Cable Access
1223
948
COMPACT-ESM
GENERATOR
8
COMPACT-ESM
GENERATOR
(with Batteries 17 A/h)
PI-1005R3
Page 15
Illustration 2-1 (cont.) Consoles
124
HF Series Generators
Pre-Installation
R&F CONSOLE
1010
Cable Access
PEDESTAL (optional)
Mounting Holes ø8
123
1023
Cable Access
RAD CONSOLE
PEDESTAL (optional)
Mounting Holes ø8
PI-1005R3
400
TOUCH SCREEN CONSOLE
FOR PC
400
PC UNIT
Cable Access
45
PC INTERFACE BOX
9
Page 16
HF Series Generators
Pre-Installation
Illustration 2-1 (cont.) Consoles
TABLE SUPPORT
RAD CONSOLES -- GRAPHIC DISPLAY
WALL SUPPORT
TOUCH SCREEN CONSOLES (TPC)
10
PEDESTAL
THESE CONSOLES CAN BE MOUNTED ON A TABLE SUPPORT, WALL SUPPORT OR PEDESTAL
PI-1005R3
Page 17
SECTION 3 ROOM REQUIREMENTS
3.1 ENVIRONMENTAL REQUIREMENTS
HF Series Generators
Pre-Installation
LINE POWERED GENERATORS /
CAPACITOR ASSISTED GENERATORS
Storage / Transport Environmental Conditions
Operating Environmental Conditions
Heat Output
Temperature range of --40oCto70oC
Relative Humidity range of 10% to 100%
Atmospheric Pressure range of 500 hPa to 1060 hPa
(Battery Powered Generators: for a longer life cycle of batteries it is recommended a t emperature around 22
In normal environmental circumstances the maximum heat output of the equipment can reach:
-- for Line Powered Generators 0.16 kW (544 btu/hr)
-- for Capacitor Assisted Generators 0.20 kW (682 btu/hr)
-- for Battery Powered Generators 0.26 kW (890 btu/hr).
Components must not be allowed to overheat. Overheating of components can cause system malfunction.
3.2 ELECTRICAL REQUIREMENTS
This Generator contains advanced circuitry which will maintain the selected X-ray techniques during adverse line conditions. However, there is a limit to the Generators ability to correct for inadequate line power.
To ensure proper operation:
BATTERY POWERED GENERATORS
Temperature range of --20oCto40oC
Relative Humidity range of 10% to 100%
Atmospheric Pressure range of 500 hPa to 1060 hPa
Temperature range of 10oCto40oC
Relative Humidity (no condensing) range of 30% to 75%
Atmospheric Pressure range of 700 hPa to 1060 hPa
o
C)
PI-1005R3
Do not under size the Distribution Transformer (Line Powered Generators). It is recommended that the secondary of Distribution
Transformer has a “Star” configuration.
Size feeder and ground wires per this document.
Ensure and maintain input mains voltage to specification. Ensure that
the ground resistance is lower than 10
Ω.
The power requirements given here (wire sizes, etc.) are the recommended specification. With the exception of high current carrying conductors and grounds, low voltage connections are made with preterminated wires.
The installation should c omply with all the electrical requirements indicated in this document. These requirements should be upgraded if Local Standards were more stringent.
11
Page 18
HF Series Generators
Pre-Installation
3.3 LINE POWERED GENERATORS -- POWER LINE REQUIREMENTS
Operation:
GENERATOR MODEL SHF-310 SHF-315 SHF-320 SHF-325 SHF-330 SHF-335
Max. Power kW 32 kW
Maximum mA 400 mA
Maximum kVp 125 kVp 150 kVp 125 kVp 150 kVp 125 kVp 150 kVp
Power Line A A B B C/D C/D
GENERATOR MODEL SHF-410 SHF-415 SHF-420 SHF-425 SHF-430 SHF-435
Max. Power kW 40 kW
Maximum mA 500 mA
Maximum kVp 125 kVp 150 kVp 125 kVp 150 kVp 125 kVp 150 kVp
Power Line A A B B C/D C/D
GENERATOR MODEL SHF-510 SHF-515 SHF-520 SHF-525 SHF-530 SHF-535
Maximum Power kW 50 kW
Maximum mA 640 mA (or 630 mA under special order)
Maximum kVp 125 kVp 150 kVp 125 kVp 150 kVp 125 kVp 150 kVp
Power Line A A B B C/D C/D
GENERATOR MODEL SHF-630 SHF-635 SHF-835
Maximum Power kW 64 kW (or 65 kW under special order) 80 kW
Maximum mA 640 mA (or 650 mA under special order) 800 mA (or 1000 mA under special order)
Maximum kVp 125 kVp 150 kVp 150 kVp
Power Line C/D C/D D (or E for 1000 mA)
POWER LINE
A B C D E
230 / 240 VAC,
Single-Phase, 50 / 60 Hz
NOTES: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
-- For 80 kW Generators operating with lines at 400 / 415 / 440 VAC an auxiliary boost transformer is required to adequate the line voltage to 480 VAC (or 530 VAC).
12
230 / 240 VAC,
Three-Phase, 50 / 60 Hz
Line voltage automatic compensation: ±10%.
Maximum line regulation for maximum kVA demand: 5%.
400 / 415 / 440 VAC,
Three-Phase, 50 / 60 Hz
480 VAC,
Three-Phase, 50 / 60 Hz
530 VAC,
Three-Phase, 50 / 60 Hz
PI-1005R3
Page 19
HF Series Generators
Pre-Installation
RMS line current during a X-ray exposure, minimum line power required, Generator stand-by consumption (W), the differential sensitivity (mA) and the thermomagnetic breaker should be:
LINEVOLTAGE
208 VAC * 192 A 240 A 300 A
230 VAC 174 A 217 A 272 A
240 VAC 167 A 208 A 260 A
Minimum kVA required Maximum kW x 1.25
Stand-by Consumption 500 W
Differential Sensitivity
(Earth Leakage / Ground Fault)
Differential, Thermomagnetic
(Fuses) and Contactor
NOTE: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
LINEVOLTAGE
208 VAC * 111 A 138 A 173 A -- --
32 kW 40 kW 50 kW
(RMS = momentary line current based on 100 ms X-ray exposures)
32 kW 40 kW 50 kW 64 kW (or 65 kW) 80 kW *
SINGLE-PHASE GENERATORS
30 mA
50% of the RMS line current
THREE-PHASES GENERATORS
230 VAC 100 A 125 A 156 A
240 VAC 96 A 120 A 150 A -- --
400 VAC 58 A 72 A 90 A 115 A 144 A
415 VAC 55 A 69 A 87 A 111 A 139 A
440 VAC 52 A 65 A 82 A 105 A 135 A
480 VAC 48 A 60 A 75 A 96 A 120 A
Minimum kVA required Maximum kW x 1.25
Stand-by Consumption 500 W
Differential Sensitivity
(Earth Leakage / Ground Fault)
Differential, Thermomagnetic
(Fuses) and Contactor
NOTES: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
-- For 80 kW Generators operating with lines at 400 / 415 / 440 VAC an auxiliary boost transformer is required to adequate the line voltage to 480 VAC (or 530 VAC).
(RMS = momentary line current based on 100 ms X-ray exposures)
50% of the RMS line current
30 mA
PI-1005R3
13
Page 20
HF Series Generators
Pre-Installation
LINEVOLTAGE
208 VAC * 0.045 0.035 0.028
230 VAC 0.055 0.045 0.036
240 VAC 0.060 0.045 0.036
Maximum Power Line Impedance. The Impedance of the Power Line in the installation must be lower than the maximum value indicated below:
SINGLE-PHASE GENERATORS POWER
32 kW 40 kW 50 kW
NOTES: -- The above values comply with the Standard IEC-60601.2.7.
NOTES: -- The above values comply with the Standard IEC-60601.2.7.
-- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
THREE-PHASE GENERATORS POWER
LINEVOLTAGE
32 kW 40 kW 50 kW 64 kW (or 65 kW) 80 kW *
208 VAC * 0.070 0.055 0.044 N.A. N.A.
230 VAC 0.087 0.070 0.056 N.A. N.A.
240 VAC 0.094 0.075 0.060 N.A. N.A.
400 VAC 0.270 0.220 0.170 0.135 0.110
415 VAC 0.300 0.240 0.180 0.150 0.120
440 VAC 0.340 0.270 0.200 0.170 0.135
480 VAC 0.400 0.320 0.240 0.200 0.160
-- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
-- For 80 kW Generators operating with lines at 400 / 415 / 440 VAC an auxiliary boost transformer is required to adequate the line voltage to 480 VAC (or 530 VAC).
14
PI-1005R3
Page 21
HF Series Generators
LIN
E
,
φ
,
φ
,
φ
,
φ
3.4 LINE POWERED GENERATORS -- RECOMMENDED WIRE SIZE
Correct sizing of the feeder wires is critical to proper Generator operation. Wire size is dependent on the Generator power, the line voltage and the distance from the Distribution Transformer to the Generator Cabinet. The maximum voltage drop during an exposure must not exceed 5% of the nominal mains value.
It is recommended that the Distribution Transformer (Hospital) used as power source have at least a power of the 25% more than the maximum power of the X-ray Generator.
Recommended wire sizing is indicated in Table 3-1. These lengths are measured from the Distribution Transformer to the Room Electrical Cabinet (room disconnect). From the Room Electrical Cabinet to the Generator
Cabinet 16 mm exceed 6 m (20 ft). The maximum wire size that can be connected to the Generator Cabinet (Input Line Fuse H older) is 35 mm
2
(AWG 6) may be used as long as that length does not
Pre-Installation
2
(AWG 2).
Table 3-1 Minimum Wire Size from Distribution Transformer to Room Electrical Cabinet
GENERATOR
32 kW, 1 φ
32 kW, 3 φ
40 kW, 1 φ
40 kW, 3 φ
LINE
VO LTAG E
208 VAC *
230 VAC 50 mm2AWG 1/0 95 mm2AWG 3/0 120 mm2AWG 4/0 -- --
240 VAC 50 mm2AWG 1/0 95 mm2AWG 3/0 120 mm2AWG 4/0 -- --
208 VAC *
230 VAC 35 mm
240 VAC 25 mm
400 VAC 16 mm
415 VAC 16 mm
440 VAC 16 mm
480 VAC 16 mm
208 VAC *
230 VAC 70 mm2AWG 2/0 120 mm2AWG 4/0 120 mm2AWG 4/0 -- --
240 VAC 70 mm2AWG 2/0 105 mm2AWG 4/0 120 mm2AWG 4/0 -- --
208 VAC *
230 VAC 35 mm
240 VAC 35 mm
400 VAC 25 mm
415 VAC 25 mm
440 VAC 16 mm
480 VAC 16 mm
15 m 30 m 45 m 60 m
50 mm2AWG 1/0 95 mm2AWG 3/0 120 mm2AWG 4/0 -- --
2
35 mm
70 mm2AWG 2/0 120 mm2AWG 4/0 120 mm2AWG 4/0 -- --
35 mm
AWG 2 70 mm2AWG 2/0 95 mm2AWG 3/0 120 mm2AWG 4/0
2
AWG 2 70 mm2AWG 2/0 95 mm2AWG 3/0 120 mm2AWG 4/0
2
AWG 4 50 mm2AWG 1/0 83 mm2AWG 3/0 105 mm2AWG 4/0
2
AWG 6 35 mm
2
AWG 6 35 mm
2
AWG 6 35 mm
2
AWG 6 25 mm
2
AWG 2 70 mm2AWG 2/0 105 mm2AWG 4/0 120 mm2AWG 4/0
2
AWG 2 70 mm2AWG 2/0 105 mm2AWG 4/0 120 mm2AWG 4/0
2
AWG 2 70 mm2AWG 2/0 95 mm2AWG 3/0 120 mm2AWG 4/0
2
AWG 4 50 mm2AWG 1/0 70 mm2AWG 2/0 83 mm2AWG 3/0
2
AWG 4 35 mm
2
AWG 6 35 mm
2
AWG 6 35 mm
2
2
2
2
2
2
2
NOTE: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
WIRE SIZE AT:
AWG 2 50 mm2AWG 1/0 70 mm2AWG 2/0
AWG 2 50 mm2AWG 1/0 70 mm2AWG 2/0
AWG 2 50 mm2AWG 1/0 50 mm2AWG 1/0
AWG 4 35 mm
AWG 2 70 mm2AWG 2/0 70 mm2AWG 2/0
AWG 2 50 mm2AWG 1/0 70 mm2AWG 2/0
AWG 2 50 mm2AWG 1/0 70 mm2AWG 2/0
2
AWG 2 50 mm2AWG 1/0
PI-1005R3
15
Page 22
HF Series Generators
LIN
E
,
φ
,
φ
φ
64k
W,3
φ
Pre-Installation
Table 3-1 (cont.) Minimum Wire Size from Distribution Transformer to Room Electrical Cabinet
GENERATOR
50 kW, 1 φ
50 kW, 3 φ
64 kW,3
(or 65 kW, 3φ)
*80kW, 3φ
LINE
VO LTAG E
208 VAC *
230 VAC 83 mm2AWG 3/0 120 mm2AWG 4/0 -- -- -- --
240 VAC 83 mm2AWG 3/0 120 mm2AWG 4/0 -- -- -- --
208 VAC *
230 VAC 50 mm2AWG 1/0 83 mm2AWG 3/0 120 mm2AWG 4/0 -- --
240 VAC 50 mm2AWG 1/0 83 mm2AWG 3/0 120 mm2AWG 4/0 -- --
400 VAC 25 mm
415 VAC 25 mm
440 VAC 25 mm
480 VAC 25 mm
400 VAC 35 mm
415 VAC 35 mm
440 VAC 35 mm
480 VAC 25 mm
400 VAC 50 mm2AWG 1/0 83 mm2AWG 3/0 105 mm2AWG 4/0 120 mm2AWG 4/0
415 VAC 35 mm
440 VAC 35 mm
480 VAC 35 mm
15 m 30 m 45 m 60 m
83 mm2AWG 3/0 120 mm2AWG 4/0 -- -- -- --
50 mm2AWG 1/0 95 mm2AWG 3/0 120 mm2AWG 4/0 -- --
2
AWG 4 50 mm2AWG 1/0 70 mm2AWG 2/0 95 mm2AWG 3/0
2
AWG 4 50 mm2AWG 1/0 70 mm2AWG 2/0 95 mm2AWG 3/0
2
AWG 4 50 mm2AWG 1/0 70 mm2AWG 2/0 83 mm2AWG 3/0
2
AWG 4 50 mm2AWG 1/0 70 mm2AWG 2/0 83 mm2AWG 3/0
2
AWG 2 70 mm2AWG 2/0 95 mm2AWG 3/0 120 mm2AWG 4/0
2
AWG 2 70 mm2AWG 2/0 83 mm2AWG 3/0 120 mm2AWG 4/0
2
AWG 2 70 mm2AWG 2/0 83 mm2AWG 3/0 105 mm2AWG 4/0
2
AWG 4 50 mm2AWG 1/0 83 mm2AWG 3/0 105 mm2AWG 4/0
2
AWG 2 70 mm2AWG 2/0 105 mm2AWG 4/0 120 mm2AWG 4/0
2
AWG 2 70 mm2AWG 2/0 105 mm2AWG 4/0 120 mm2AWG 4/0
2
AWG 2 70 mm2AWG 2/0 95 mm2AWG 3/0 120 mm2AWG 4/0
WIRE SECTION AT:
NOTES: -- For lines at 210 VAC or below an auxiliary boost transformer is required to adequate the line voltage to the Generator input.
-- For 80 kW Generators operating with lines at 400 / 415 / 440 VAC an auxiliary boost transformer is required to adequate the line voltage to 480 VAC (or 530 VAC).
16
PI-1005R3
Page 23
HF Series Generators
Pre-Installation
3.5 CAPACITOR ASSISTED GENERATORS -- POWER LINE REQUIREMENTS
Operation:
G Single-Phase at 100 / 110 / 120 / 208 / 230 / 240 VAC. G Line voltage automatic compensation: ±10%. G 50 Hz / 60 Hz.
Thermomagnetic Interruptor / Circuit Breaker rating should be:
G 8 / 10 / 12.5 / 16 / 20 A (1P+N).
Differential Sensitivity: 30 mA
Minimum k W required: 2.0 kW
Line Impedance should comply with Standard IEC-60601.2.7.
3.6 CAPACITOR ASSISTED GENERATORS -- RECOMMENDED WIRE SIZE
The minimum recommended wire size for the line voltage is:
LI NE V OLTA GE WIRE SIZE
100 / 110 VAC 4mm
208 / 230 / 240 VAC 2.5 mm
2
2
AWG 12
AWG 14
PI-1005R3
17
Page 24
HF Series Generators
Pre-Installation
3.7 BATTERY POWERED GENERATORS -- POWER LINE REQUIREMENTS
Operation:
G Single-Phase at 110 / 208 / 230 / 240 VAC. G Line voltage automatic compensation: ±15%. G 50 Hz / 60 Hz.
Thermomagnetic Interruptor / Circuit Breaker rating should be:
G 10 A (1P+N curve type D).
Differential Sensitivity: 30 mA
Minimum k W required:
G without Stand-Alone option: 2.2 kW G with Stand-Alone option: 0.5 kW
Line Impedance should comply with Standard IEC-60601.2.7.
3.8 BATTERY POWERED GENERATORS -- RECOMMENDED WIRE SIZE
The minimum recommended wire size for the line voltage is:
LI NE V OLTA GE WIRE SIZE
110 VA C 4mm
208 / 230 / 240 VAC 2.5 mm
2
2
AWG 12
AWG 14
18
PI-1005R3
Page 25
3.9 INTERCONNECTION AND GROUNDING REQUIREMENTS
q
ppl
i
electricalrequirement
s.Customersupplie
d
q
v
i
ith
X-ray
Tube.4
Every installation must be provided with a main line disconnect device (thermomagnetic breaker) and the remote disconnect devices required at all Consoles that are not located next to the line safety switch. (For more
information about interconnection and grounding refer to “Installation” document).
Illustration 3-1 Interconnection B lock Diagram for LINE POWERED GENERATORS
HF Series Generators
Pre-Installation
DISTRIBUTION
TRANSFORMER
(Hospital, etc.)
SERIAL CONSOLE or TOUCH SCREEN CONSOLE (TPC)
TOUCH SCREEN PC PC INTERFACE BOX
Note .
1
ROOM ELECTRICAL CABINET WITH
CONTROL CONSOLE
X-RAY TUBE
LINE SAFETY SWITCH
(Provided by customer)
HV Cables
For Serial Generators (RS232 / RS422): Console CPUs are located
80 kW GENERATORS WITH LINES AT 400 / 415 / 440 VAC
3
or
Serial Comm.
or
Serial Comm.
4
or
4
AUX. BOOST TRANSFORMER
WHEN POWER LINES IS 210 VAC OR BELOW OR FOR
(Provided by customer)
2
POWER MODULE
HV TRANSFORMER
LF-RAC (LS)
LV-DRAC (HS)
GENERATOR
or
inside the Generator Cabinet and Interconnections are factory made. Only one cable (serial communication) from J5 of the Generator Cabinet should be connected to the Serial Console, Touch Screen Console or PC Interface Box.
CABLE RUN FUNCTION REMARKS
Single or Three Phase Power.
1
2
3 Control Signals and Ground Cable quantity depends on the options installed (AEC, etc.)
NOTES: -- For wire size refer to Section 3.4. Consult to Local Standards for feeder and ground wire size requirements.
(1φ : 230 / 240 VAC) (3φ : 230 / 240 VAC or 400 / 415 / 440 / 480 VAC)
Ground.
Single or Three Phase Power. (1φ : 230 / 240 VAC) (3φ : 230 / 240 VAC or 400 / 415 / 440 / 480 VAC)
Ground.
Stator Supply.
Ground.
Generator provided with LV-DRAC requires a shielded stator cable. (Refer to “Installation” document).
-- The system power ground point is located in the Generator Cabinet.
Connect to Room Electrical Cabinet according to the indicated electrical re
Connect to Generator according to the indicated electrical requirements. Install an Auxiliar Boost Transformer when it is required. Customer supplied.
Pro
Field supplied.
uirements. Customersu
ded w
ed.
CABINET
.
PI-1005R3
19
Page 26
HF Series Generators
f
1
PowerLinefromaRoomElectricalCabinetwithSafetySwitch
v
i
ith
X-ray
Tub
Pre-Installation
Illustration 3-2 Interconnection B lock Diagram for CAPACITOR ASSISTED GENERATORS
ROOM ELECTRICAL CABINET
with LINE SAFETY SWITCH
(Customer supplied)
CONTROL CONSOLE
SERIAL CONSOLE or TOUCH SCREEN CONSOLE (TPC)
TOUCH SCREEN PC PC INTERFACE BOX
X-RAY TUBE
Note .
For Serial Generators (RS232 / RS422): Console CPUs are located inside the Generator Cabinet and Interconnections are factory made. Only one cable (serial communication) from J5 of the Generator Cabinet should be connected to the Serial Console, Touch Screen Console or PC Interface Box.
1 1
(Customer supplied)
2
or
Serial Comm.
or
Serial Comm.
HV Cables
3
POWER MODULE
HV TRANSFORMER
LF-RAC (LS)
GENERATOR
CABINET
CABLE RUN FUNCTION REMARKS
Single-Phase Line.
1
2 Control Signals and Ground Cable quantity depends on the options installed (AEC, etc.)
3
NOTES: -- For wire size refer to Section 3.6. Consult to Local Standards for feeder and ground wire size requirements.
100 / 110 / 120 / 208 / 230 / 240 VAC.
Ground.
Stator Supply.
Ground.
-- The system power ground point is located in the Generator Cabinet.
The Unit is connected by a Line Plug. Power Line
Line plugs and cable are Customer supplied.
Pro
rom a Room Electrical Cabinet with SafetySwitch.
ded w
e.
20
.
PI-1005R3
Page 27
Illustration 3-3
f
1
PowerLinefromaRoomElectricalCabinetwithSafetySwitch
v
i
ith
X-ray
Tube.3
Interconnection B lock Diagram for BATTERY POWERED GENERATORS
HF Series Generators
Pre-Installation
ROOM ELECTRICAL CABINET
with LINE SAFETY SWITCH
(Customer supplied)
CONTROL CONSOLE
SERIAL CONSOLE or TOUCH SCREEN CONSOLE (TPC)
TOUCH SCREEN PC PC INTERFACE BOX
HV Cables
X-RAY TUBE
Note .
For Serial Generators (RS232 / RS422): Console CPUs are located inside the Generator Cabinet and Interconnections are factory made. Only one cable (serial communication) from J5 of the Generator Cabinet should be connected to the Serial Console, Touch Screen Console or PC Interface Box.
1 1
(Customer supplied)
2
or
Serial Comm.
or
Serial Comm.
3
or
3
POWER MODULE
HV TRANSFORMER
LF-RAC (LS)
LV-DRAC (HS)
GENERATOR
CABINET
or
CABLE RUN FUNCTION REMARKS
Single-Phase Line.
1
2 Control Signals and Ground Cable quantity depends on the options installed (AEC, etc.)
NOTES: -- For wire size refer to Section 3.8. Consult to Local Standards for feeder and ground wire size requirements.
110 / 208 / 230 / 240 VAC.
Ground.
Stator Supply.
Ground.
Generator provided with LV-DRAC requires a shielded stator cable. (Refer to “Installation” document).
-- The system power ground point is located in the Generator Cabinet.
The Unit is connected by a Line Plug. Power Line
Line plugs and cable are Customer supplied.
Pro
Field supplied.
rom a Room Electrical Cabinet with SafetySwitch.
ded w
PI-1005R3
.
21
Page 28
HF Series Generators
Pre-Installation
3.10 SAFETY DEVICES
Devices such as Safety Switch / Emergency Switch, Warning Light, and Door Interlock Switch should be supplied and installed by the customer. (Refer to Illustration 3-4.)
SAFETY SWITCH / EMERGENCY SWITCH
The main Safety Switch should be installed in the Room Electrical Cabinet (Room Disconnect) (close to the Generator Cabinet), and provided with light indicators for “Power On / Off”. It should be used for main disconnection, and located in an accessible place where it can be seen and controlled during operation and service.
Other Emergency Switches should be installed in accessible locations in the room (near to the main entrance door or to the Control C onsole) for use in an emergency. They should be connected to the Room Electrical Cabinet (Room Disconnect) so that they cut power to the Generator when they are activated.
The r ating of these switches should be: 10 A, 500 VAC, NC.
DOOR INTERLOCK SWITCH
The Door Interlock Switch indicates to the operator when Doorways to the X-ray room are open. It inhibits or not the X-ray generation, according to the Local Standards and customer preferences.
This switch should be installed in the entrance door(s) and its connecting cable should be routed to the Generator Cabinet.
WARNING LIGHT
The Warning Lights are signal lamps installed outside of the X-ray room (near of the main entrance) that indicate:
1. The system is under voltage (red lamp “ON”).
2. X-ray exposure in process (yellow lamp “ON”) (for connection refer to Installation document.)
The Warning Lights connection cables should be routed to the Generator Cabinet.
22
Note .
In any case, the installation must be in compliance with the Local Regulation.
PI-1005R3
Page 29
Illustration 3-4 Room Electrical Cabinet and Mains Connection
EC
Electrical Cabinet
HF Series Generators
Pre-Installation
DCB
TCB
CR
L
L
SS
ON OFF
GEN
EM
EM
LEGEND
EC: Electrical Cabinet (Room Disconnect) for powering X-ray equipment. (Customer supplied)
DCB: Differential Circuit Breaker.
TCB: Thermomagnetic (or Fuses) Circuit Breaker.
CR: Contactor controlled by the Safety Switch (SS).
SS: Safety Switch used for Generator main disconnection, with ON/OFF positions.
L: ON / OFF Indicator Lamps located on the Electrical Cabinet.
EM: Emergency S witch near to Control Console and/or to the Room main entrance.
GEN: Generator Cabinet.
WL1: X-ray Emission Indicator Lamp (yellow lamp) connected to the Generator Cabinet,
located outside of the X-ray Room (above the exam room entrance).
WL2: Warning Light (red lamp) located outside of the X-ray Room (above the exam room entrance).
DIS: Door Interlock Switch located on the main entrance(s).
System
Ground Bar
WL1
WL2
DIS
PI-1005R3
23
Page 30
HF Series Generators
Pre-Installation
This page intentionally left blank.
24
PI-1005R3
Page 31
Technical Publication
IN-1052R0
Installation
HF Series Generators
(ONLY FOR GENERATORS WITH U-ARM POSITIONERS)
Page 32
HF Series Generators
Installation
REVISION DATE REASON FOR CHANGE
0 FEB 26, 2008 First edition
This Document is the english original version, edited and supplied by the manufacturer.
The R evision state of this Document is indicated in the code number shown at the bottom of this page.
ADVISORY SYMBOLS
The following advisory symbols will be used throughout this manual. Their application and meaning are described below.
DANGERS ADVISE OF CONDITIONS OR SITUATIONS THAT IF NOT HEEDED OR AVOIDED WILL CAUSE SERIOUS PERSONAL INJURY OR DEATH.
ADVISE OF CONDITIONS OR SITUATIONS THAT IF NOT HEEDED OR AVOIDED COULD CAUSE SERIOUS PERSONAL INJURY, OR CATASTROPHIC DAMAGE OF EQUIPMENT OR DATA.
Advise of conditions or situations that if not heeded or avoided could cause personal injury or d amage to equipment or data.
Note . Alert readers to pertinent facts and conditions. Notes represent
information that is important to know but which do not necessarily relate to possible injury or damage to equipment.
IN-1052R0
Page 33
HF Series Generators
Installation
TABLE OF CONTENTS
Section Page
1 INTRODUCTION 1.........................................................
1.1 Tools and Test Equipment 1............................................
1.2 Pre-Installation Check 2...............................................
1.3 General Cautions 3...................................................
2 UNPACKING, POWER LINE CONNECTION AND CABINET INSTALLATION 5...
2.1 Control Console Installation (optional) 14.................................
3 CABLE CONNECTIONS 15..................................................
3.1 Cable Routing Inside Generator Cabinet 15...............................
3.1.1 G eneral Cable Routing 15.......................................
3.2 High Voltage Cables Connection 17......................................
3.2.1 X-ray Tubes with Metallic Insert Envelope 17.......................
3.2.2 High Voltage Cables 18..........................................
3.3 X-ray Tube Connection 19..............................................
3.3.1 Stator Cable 19.................................................
3.3.2 Tube Selection Signals 22.......................................
3.4 Interconnection Cables 22..............................................
3.4.1 Serial Interconnection RS232 / RS422 24..........................
3.4.2 Collimator Error Signal (optional) 30...............................
3.4.3 Door Interlock Signal 30.........................................
3.4.4 Warning Light Signal 31.........................................
3.4.5 Collimator Lamp and System Locks 31............................
3.4.6 Buckys (optional) 32............................................
3.4.7 Tomo Device (optional) 32.......................................
3.4.8 Ion Chambers (optional) 33......................................
IN-1052R0
i
Page 34
HF Series Generators
Installation
Section Page
4 FINAL INSTALLATION AND CHECKS 37.....................................
4.1 HV Transformer 37....................................................
4.2 Cable Fastening and Covers 37.........................................
5 SYSTEM INTERCONNECTIONS 39...........................................
5.1 System Interconnection Signals 39.......................................
5.2 System Interconnection Maps 41........................................
ii
IN-1052R0
Page 35
SECTION 1 INTRODUCTION
The Installation process depends on the Generator and System configuration. Installation must be performed in the order indicated along this document. Perform only the sections required to install this Generator.
1.1 TOOLS AND TEST EQUIPMENT
The following hand tools and products are required for the Installation:
Standard s ervice engineers tool kit.
Electric drill motor and assorted bits.
HF Series Generators
Installation
Silicone Insulating Grease (proofing compound).
Alcohol cleaning agent.
The following test equipment is required for Configuration and Calibration:
Digital Multimeter.
Non-invasive kVp Meter.
Digital mAs Meter.
Calculator.
Only for AEC purposes:
G Sensitometer (only for Film).
G Densitometer (only for Film).
G Copper Plates for the Collimator Filter Holder (recommended):
2 units of 1 mm thickness, 1 unit of 0.5 mm thickness, 2 units of 0.2 mm thickness, 1 unit of 0.1 mm thickness.
IN-1052R0
G Acrylic Plastic Plates can be used Instead of Copper Plates:
6 units of 5 cm. thickness, 5 units of 1cm. thickness.
G Dosimeter (optionally).
Only for Tomo purposes:
G Tomophantom tool.
1
Page 36
HF Series Generators
Installation
1.2 PRE-INSTALLATION CHECK
Prior to beginning installation, it is recommended to inspect the site and verify that the X-ray room complies with Pre-installation requirements, such as:
Incoming Line.
Main Switch and Safety Devices.
Conduits.
Space Requirements.
(Refer to the “Pre-Installation” document.)
2
IN-1052R0
Page 37
1.3 GENERAL CAUTIONS
HF Series Generators
Installation
MAKE SURE THAT THE MAIN STORAGE CAPACITORS OF THE HIGH VOLTAGE INVERTER DO NOT CONTAIN ANY RESIDUAL CHARGE. WAIT UNTIL THE LIGHT EMITTING DIODES ON THE CHARGE-DISCHARGE MONITOR BOARDS ARE OFF, APPROXIMATELY 3 MINUTES AFTER THE UNIT IS TURNED OFF.
ALWAYS
HAVE THE “IPM DRIVER BOARD” CONNECTED IN THE GENERATOR PREVIOUS TO MAINS POWER IS ACTIVATED IN IT. IF THE “IPM DRIVER BOARD” IS NOT CONNECTED, PERMANENT DAMAGE WILL OCCUR TO IGBTS.
TO AVOID ELECTRIC SHOCK, DO NOT TOUCH ANY HEATSINK OF THE CIRCUIT BOARDS EVEN THE GENERATOR IS TURNED OFF. PREVIOUS TO DISASSEMBLE ANY BOARD, REMOVE ALL CONNECTORS PLUGGED TO IT.
LINE POWERED GENERATOR
: THIS GENERATOR IS PERMANENTLY CONNECTED TO THE POWER LINE, AND POWERED ON UNLESS THE SAFETY SWITCH INSTALLED IN THE ROOM ELECTRICAL CABINET IS OFF. WHEN THE GENERATOR IS POWERED, THE NEON LAMP (GREEN) LOCATED ON THE TRANSFORMER 6T2 (GENERATOR CABINET) IS ON.
IN-1052R0
INTERNAL PARTS OF THE GENERATOR (ALL FUSES, LINE CONTACTOR (6K5), INPUT TRANSFORMER (6T2), ON/OFF RELAY (3K3) AND LF-RAC MODULE) ARE PERMANENTLY POWERED ON THROUGH POWER LINE ALTHOUGH THE CONTROL CONSOLE IS OFF. BE SURE THAT THE SAFETY SWITCH IS OFF BEFORE HANDLING ANY INTERNAL PART OF THE EQUIPMENT.
3
Page 38
HF Series Generators
Installation
This page intentionally left blank.
4
IN-1052R0
Page 39
HF Series Generators
Installation
SECTION 2 UNPACKING, POWER LINE CONNECTION
AND CABINET INSTALLATION
The Generator is shipped in one box to facilitate transport and installation.
Upon receipt of the X-ray unit and associated equipment, inspect all shipping containers for signs of damage. If damage is found, immediately notify the carrier or their respective agent.
It is recommended to install the U-Arm Positioner before than the Generator. (Refer to t he Positioner Service Manual).
1. Open the shipping box. Take out the Control Console (if provided), Interconnection Cables, Cabinet Cover and other furnished parts. Do not discard any packing material such as envelopes, boxes or bags until all parts are accounted for as listed on the packing list.
Illustration 2-1 Compact Generators
2. Remove the packing material from the pallet.
3. Remove the Generator Cabinet from the shipping pallet, placing it near its chosen room position. This operation requires at least two people.
4. When the equipment is unpacked, verify that all items on the customer order are present, and the hardware and internal wiring is secure.
5. Check the part numbers / serial numbers of each component with its identification labels, and inspect all pieces for visible damage. If any damaged parts are found, repair or order replacements to prevent unnecessary delay in installation.
IN-1052R0
5
Page 40
HF Series Generators
Installation
6. Previous to install the Generator Cabinet on the upper side of the Positioner Control Box, it is recommended to perform the Power Line connection.
KEEP IN MIND THE GENERAL CAUTIONS FOR LINE POWERED GENERATORS INDICATED IN SECTION 1.3.
DO NOT POWER ON THE GENERATOR UNTIL SPECIFICALLY INSTRUCTED IN THIS SERVICE MANUAL.
7. The power supply line should conform with the Generator model defined in the “Pre-Installation” document. Wire sizes indicated in this document are relative to the power supply line and wire length. Verify that the power line voltage and phase of the Generator coincides with the one for Room Electrical Cabinet.
Note .
As indicated in the Pre-Installation document, 16 mm may be used from the Room Electrical Cabinet to the Generator Cabinet provided that the length does not exceed 6 m (20 ft).
8. Route the Power Line C ables and the Ground wires to the Input Line Fuses and Ground Studs in the Cabinet Frame (Ground Studs are above the input fuses or close to the right side of the HV Transformer). These cables can be secured to the Fastening Bar of the Cabinet and routed internally along the rear side of the Cabinet (always apply Local Codes for cable r outing). (Refer to Illustration 2-2.)
Illustration 2-2 Cable Routing in the Line Powered Generator
Fastening Bar
Input Transformer 6T2
2
(AWG 6)
Power Line Cables
6
Ground Terminals
Input Line Fuses
IN-1052R0
Page 41
HF Series Generators
Installation
9. For Single Phase Generators, connect the Power wires L1 and N (L2) to the Fuse Holders of F3 and F4 (right side of the Cabinet), and the Ground wire to the Ground stud in the Cabinet Frame (above these fuses or close to the right side of the HV Transformer).
SINGLE PHASE GENERATORS ARE FACTORY DELIVERED TO OPERATE ON PHASE AND NEUTRAL. IN CASE OF CONNECTING THE EQUIPMENT TO A TWO-PHASE LINE, REPLACE THE NEUTRAL CARTRIDGE WITH THE FUSE SUPPLIED WITH THE GENERATOR.
10. For Three Phase Generators, connect the Power wires L1, L2 and L3 to the Fuse Holders of F3, F4 and F5 (right side of the Cabinet), and the Ground wire to the Ground Studs in the Cabinet Frame (located above these fuses or close to the right side of the HV Transformer).
Illustration 2-3 Power Line connections
Three Phase Generators do not need Neutral (N) wire connection from the Line. If the unit is provided with the optional Fuse Module, connect the Neutral (N) wire from the Line to the Neutral Stud below F3 Fuse Holder.
Input Transf. 6T2
GND Studs
GND Stud
L1 Input Line
L2 Input Line
L3 Input Line
IN-1052R0
Neutral Stud
(optional)
7
Page 42
HF Series Generators
Installation
SEP-UP TRANSFORMER
Input: 380 VAC / 400 VAC / 415 VAC, Three-Phase.
Output: 480 VAC / 530 VAC, Three-Phase.
Max Power Output: 80 kW, 10% duty cicle
Rising Temperature: 40
(approx. 5 seconds / minute)
o
C
For 80 kW Generators, the power supply line must be 480 VAC (or 530 VAC). If the Generator is supplied with an external step-up autotransformer, it will include the cables to connect the autotransformer to the Generator Cabinet. Power line should be connected to the autotransformer terminals according to the line.
480 V
(or 530 V)
415 V 400 V 380 V
380 V 400 V 415 V
480 V
380 V 400 V 415 V
(or 530 V)
480 V
(or 530 V)
Illustration 2-4 Line Contactor 6K5
11. The whole System (Tables, Spot Film Devices, etc.) can be switched ON/OFF when the Generator is switched ON/OFF. For this, power the System through the output terminals of the Line Contactor 6K5 (upper contactor close to the Input Transformer). These terminals are located underneath the Line Contactor 6K5.
Line Contactor 6K5
Input Transformer 6T2
Output Terminals
8
IN-1052R0
Page 43
12. Three-Phase Generators can be provided with an optional Fuse Module
T
mounted on Module-12, for switching ON/OFF the whole system when the Generator is turned ON/OFF.
For this, connect the Neutral (N) wire from the Line to the Neutral Stud below F3 Fuse Holder. Power the System through the Output Terminals 12TS4 (U, V, W, N, GND) close to Fuses F14, F15, F16.
Illustration 2-5 Power Line connections in the optional Fuse Module
GND Studs
HF Series Generators
Installation
Input Transf. 6T2
erminals 12TS4
Note .
GND Stud
L1 Input Line
L2 Input Line
L3 Input Line
Neutral Stud
13. According to the nominal voltage of the line, verify or connect the wire “
:” to the indicated terminal (TB) of Transformer 6T2. This wire is
factory connected to 230 VAC (for 1-Phase), 400 VAC (for 3-Phase) or 480 VAC / 530 VAC (for 80 kW 3-Phase Generators). (Refer to
Schematic 543020XX).
For 220 VAC power line, connect the wire “ terminals. For 380 VAC power line, connect the wire “
:
” to the 230 VAC
:
”tothe
400 VAC terminals.
6T2 Terminal Strip
6T2
IN-1052R0
9
Page 44
HF Series Generators
Installation
14. After connecting the Power Line Cables, secure them to the Fastening Bar using cable ties if they are routed over the Fastening Bar, or using a suitable clamp if they are routed through the Round Cable Outlet on the Rear Cover of the Cabinet (always apply Local Codes).
15. The Generator Cabinet is installed on the upper side of the Positioner Control Box as follows.
COMPACT GENERATOR
CONTROL BOX
Lateral Cable Entrance
BACK COVER
Upper Cable Entrance
(HV Cables, Stator Cable)
690
(27.16”)
600
(23.62”)
52
37
21
213
212850
8.38”
65
2.55”
R9.5
462
(18.18”)
Anchoring Holes
65
2.55”
10
These s teps are also described in the Positioner Service Manual.
a. Place the Control Box on its final position of the room, keep in
mind:
G the length of the Column Harness (approx. 1.5 m) that goes
from the Column of the Positioner to the Control Box,
G the length of the High Voltage Cables (X-Ray Tube -- HV
Transformer in the Generator Cabinet),
G the Swivel Arm movements.
(Refer to Room Layout illustrations in the Positioner
Service Manual)
IN-1052R0
Page 45
HF Series Generators
Installation
b. Level the Control Box using the Adjustable Leveling Legs. Keep
the Base at the maximum distance from the floor.
Seismic areas and other conditions require to secure firmly the Control Box to the floor through the mounting holes at its base. In this case, place the four spacers (provided) under the base and secure them to the floor. Keep the four Leveling Legs at the same height than the spacers.
Cable Access
Spacer for using in Seismic Areas
Adjustable Leveling Legs
c. Assemble the supplied Back Cover for the Generator Cabinet to
the upper side of the Control Box using two M6x20 screws (supplied).
Back Cover
Fixing Screws
Control Box
d. Remove the four Adjustable Leveling Legs from the base of the
Generator Cabinet.
IN-1052R0
11
Page 46
HF Series Generators
Installation
Hook
e. Hang the Generator Cabinet on the Back Cover and secure it to
the Control Box using four M6x20 screws (supplied). At least two people are required for this operation. Fix the two screws that join the r ear side of the Cabinet to the Back Cover.
Generator Cabinet
Back Cover
Fixing Screws
Control Box
P2--Shield P1
J1
Ground Wire / GND Stud
P3
f. In some cases, due to transport safety requirements, the HV
Transformer is shipped out of the Generator Cabinet. Install the HV Transformer inside the Cabinet (upper area) and secure it with the respective anchors or plates, then connect the following cables from the Power Module to the corresponding terminals on the HV Transformer:
G P2-Shield (2 thin wires), P1 and P3. Connect these cables to
the stud-brass terminals using two wrenches to tighten the nuts (one to hold the base nut in place and the other to tighten the nut over the cable) and avoiding twisting the studs. Ensure that the connection is secure and properly tightened.
G Ground wire to Ground stud.
G Connector J1.
THE HV TRANSFORMER HAS TO BE SECURED WITH ITS ANCHORS OR PLATES INSIDE THE CABINET. OTHERWISE P1, P2 AND P3 STUDS MAY BE IN CONTACT WITH THE CABINET FRAME AND PRODUCE A SHORT-CIRCUIT.
12
IN-1052R0
Page 47
g. Leave a working area around the Generator Cabinet until its final
installation.
Cable Access to the Generator Cabinet
(HV Cables, Stator / Thermostat, AEC, ...)
HF Series Generators
Installation
Emergency Switch-Off Button
ON / OFF Button
16. Verify that the power supply line is “OFF” in the Room Electrical Cabinet. Verify that the power line to the Generator is cut when the Emergency Switch(es) is(are) activated.
17. Cut the cables to the appropriate length and remove insulation from both ends of the power and ground wires. Connect them to the respective terminals in the Room Electrical Cabinet.
IN-1052R0
18. Install the Control Console as indicated in Section 2.1.
13
Page 48
HF Series Generators
Installation
2.1 CONTROL CONSOLE INSTALLATION (OPTIONAL)
1. Control Console can be freestanding, wall supported or mounted on an optional Pedestal. Console is provided with several mounting holes on the bottom for anchoring to the Pedestal or another support.
Console CPU Boards and AEC Control Board can be located inside the Console (standard) or inside the Generator Cabinet (for Serial communication).
2. When a Pedestal is used, secure the Pedestal to the floor through the anchoring holes on its base and place the base cover. Attach the C onsole to the Pedestal using the mounting holes on the bottom of the Console.
3. When the Console is wall supported, secure the support to the wall and attach the Consoleto the support using the mounting holes on the bottom of the Console.
4. Leave a sufficient working area around the equipment until its final assembly.
14
IN-1052R0
Page 49
SECTION 3 CABLE CONNECTIONS
This section provides the information necessary to connect the Generator Cables with the system and options.
HF Series Generators
Installation
Note .
Note .
For more information about electrical requirements and cable connections, refer to the “Pre-Installation” document and Section 5 “System Interconnections” at the end of this document.
Identification of some terminal connections (TB, TS), boards, etc... along with this document (text and schematics) may have a prefix number which indicates the module number in the equipment. (a.e. TS2 as 4TS2, 10TS2 or 11TS2).
Some safety devices such as the Safety Switch / Emergency Switch, Warning Light, and Door Interlock Switch are supplied and installed by the customer. Verify that safety devices have been properly installed and routed during the Pre-Installation procedure.
3.1 CABLE ROUTING INSIDE GENERATOR CABINET
3.1.1 GENERAL CABLE ROUTING
1. Before connecting the Interconnection cables within the Generator Cabinet, cables must be first connected to each Device (Positioner, Tables, Buckys, etc.) and routed through the raceways. Remove the ferrite blocks of the cables (factory clamped) when it is required to carry out a correct routing, then re-install the ferrite blocks where they originally were around cables.
IN-1052R0
Cables Entrance (upper side of Wall Support
2. Inside the Generator Cabinet, all Interconnection cables must be routed over the Fastening Bar (upper rear bar) of the Cabinet Frame minding the upper Cable Outlet at the rear side of the Cabinet Cover. (Refer to
Illustration 3-1).
15
Page 50
HF Series Generators
Installation
Illustration 3-1 Cable Routing in Compact Generator
Stator & Interconnections Cables Entrance
Fastening Bar
Stator & Interconnections
Cables Outlet (rear side)
Cable Ties
Cable Ties
Fastening Bar
Input Transformer
Ground Terminals
Input Line Fuses
Power Line Cable Entrance
Stator & Interconnections Cable Entrance
Power Line Cables
HV Cables
Stator & Interconnections Cables
Input Transformer
16
Power Line Cable Entrance
Input Line Fuses
IN-1052R0
Page 51
HF Series Generators
Installation
3. For Generators with the Low or High Speed Starter located on a shelf (Module 10 or 11), Stator and Interconnections Cables have to be routed internally through the Cabinet close to the HV Transformer.
In order to avoid signal interferences, it is strongly recommended to fold and fasten close to the Generator Cabinet the portion of cables not routed (see picture below). Never wrap in circles.
4. Connect all cables as indicated in Section 3 “Cable Connections”.
5. Secure all cables to the Fastening Bar using cable ties after all cable / wire connections are complete.
3.2 HIGH VOLTAGE CABLES CONNECTION
FOR GENERATORS WITH A HV TRANSFORMER WITH DOUBLE X-RAY TUBE RECEPTACLES (ANODE / CATHODE TO CONNECT TWO TUBES): CONNECTIONS OF THE FILAMENT LEADS “FIL-1 RTN” (J4-15) AND “FIL-2 RTN” (J4-16) ON THE INTERFACE CONTROL BOARD HAVE BEEN INVERTED. THESE CONNECTIONS ARE FACTORY SET. (REFER TO SCHEMATIC 543020XX).
YES NO
3.2.1 X-RAY TUBES WITH METALLIC INSERT ENVELOPE
In case of X-ray Tubes with a Metallic Insert Envelope, it is required to connect the wire from the Metallic Insert Envelope to the Black Banana Plug connection on the HV Transformerto obtain a correct mA measures. Forthese X-ray Tubes the part number of the HV Transformer has to be coded in revision A or higher (a.e. A6094--16A). (Refer to Section 5.2 -- Map 54302035).
IN-1052R0
17
Page 52
HF Series Generators
Installation
3.2.2 HIGH VOLTAGE CABLES
Connect the HV Cables in the HV Transformer (Generator).
These cables must enter into the Generator through the c able outlet on the upper side of the Cabinet and then attached to the fastening bar (upper rear bar) of the Cabinet frame minding the upper cable outlet at the rear side of the Cabinet cover.
1. The mounting accessories of each termination plug are factory
The Terminal Pins of the High Voltage cables are extremely delicate and easily damaged. Therefore they must be handled carefully. Make sure that they are straight and that the splits in the pins are open (parallel to sides).
assembled. For extended information refer to the HV Cable manufacturer’s instructions located inside the HV Cable package.
Contact Pins
Termination Plug
Do not install the Silicone washer supplied with the HV Cables.
2. Unscrew the grub screw of the ring nut. (Refer to the illustration below.)
Nipple
Ring Nut
Grub Screw
Contact
3. Prepare the high voltage terminals that will be installed in the HV Transformer. Put approximately 1 cm (0.5”) of HV Oil in the HV Transformer receptacles (included in the HV cables package). If HV Oil is not available, fill the receptacles using silicone paste provided with the X-ray Tube.
18
4. Carefully insert the anode and cathode termination plug into the respective receptacle socket (watch the nipple on the plug to ensure correct positioning of the contact pins).
5. Hand tighten the ring nut. It must be secure. Tighten the grub screw.
IN-1052R0
Page 53
3.3 X-RAY TUBE CONNECTION
3.3.1 STATOR CABLE
X-ray Tubes are equipped with the Stator cable installed.
A LV-DRAC (Low Voltage - Digital Rotatory Anode Controller) is required for High Speed X-ray Tubes. Connections between LV-DRAC and Power Module are factory made.
Route the Stator cable together with the HV cables to the Generator Cabinet. Connect the Stator cable terminals to the indicated Terminal Block TS2:
HF Series Generators
Installation
Note .
Note .
STATOR WIRES
TERMINAL TS2
TUBE-1 TUBE-2
MAIN TS2-1 TS2-9
AUX (Shift) TS2-2 TS2-10
COMMON TS2-3 TS2-11
Terminal Block TS2 may be marked as 10TS2 or 11TS2 depending on the Generator model.
For Philips or Siemens X-ray Tubes refer to Interconnection Maps I/F-021 or I/F-024.
IN GENERATORS EQUIPPED WITH LV-DRAC: THE LV-DRAC OUTPUT CAN BE AS HIGH AS 1000 Vrms. FOR SAFETY REASONS (TO AVOID ELECTRIC SHOCKS), THE STATOR CABLE MUST BE SHIELDED AND BOTH ENDS OF THE SHIELD MUST BE CONNECTED TO GROUND.
DUE TO ELECTROMAGNETIC INTERFERENCE (EMC) PROBLEMS, THE IGBT’s HEATSINK IS NOT GROUNDED. IT IS CONNECTED TO THE NEGATIVE TERMINAL OF THE INPUT R ECTIFIER. TO AVOID ELECTRIC SHOCK, BE SURE THAT THE INPUT LINE IS DISCONNECTED AND THE CAPACITOR BANK IS PROPERLY DISCHARGED BEFORE MANIPULATING THE LV-DRAC.
IN-1052R0
MAKE SURE THAT STATOR WIRES ARE PROPERLY CONNECTED. BEFORE MAKING ANY EXPOSURE, CHECK THAT THE ANODE ROTATES CORRECTLY.
19
Page 54
HF Series Generators
TUB
E
TUB
E
Installation
FANS
Wires from fans should be routed with the Stator Cables, and connected to the indicated terminal of the Generator Cabinet. Depending on the model of X-ray Tube, the fans are powered at 115 VAC or 220 VAC. Make the following connections to select the fan voltage.
For Compact Generators with the Low Speed Starter LF-RAC located on a shelf at the bottom of the Generator (module-10), connect wires from fans to:
TUBE
CONNECTION
AS TUBE-1
AS TUBE-2
TUBE
CONNECTION
AS TUBE-1
AS TUBE-2
GENERATOR WITH LOW SPEED STARTER
WIRES FROM FANS 115 VAC 220 VAC
10TS2-6 and 10TS2-7
on the Generator Cabinet
10TS2-14 and 10TS2-15
on the Generator Cabinet
TB4-T1 with TB1-22 or TB1-23
on the LF-RAC Board
TB4-T2 with TB1-22 or TB1-23
on the LF-RAC Board
TB4-T1 with TB1-25 or TB1-26
on the LF-RAC Board
TB4-T2 with TB1-25 or TB1-26
on the LF-RAC Board
For Compact Generators with the High Speed Starter LV-DRAC located on a shelf at the bottom of the Generator (module-11), connect wires from fans to:
GENERATOR WITH HIGH SPEED STARTER
WIRES TO FANS 115 VAC 220 VAC
11T S2 -6 a nd 11TS2-7
on the LV-DRAC Module
11TS2-14 and 11TS2-15 on the LV-DRAC Module
wire marked “T1” with 11TS2-17
on the LV-DRAC Module
wire marked “T2” with 11TS2-17
on the LV-DRAC Module
wire marked “T1” with 11TS2-18
on the LV-DRAC Module
wire marked “T2” with 11TS2-18
on the LV-DRAC Module
20
IN-1052R0
Page 55
HF Series Generators
CONNECTIONO
F
Installation
THERMOSTAT OR PRESSURE SWITCH SIGNAL
o
If the X-ray Tube is provided with a Safety Thermostat (approx. 65
C) or Pressure Switch (must be NC Contact), the two wires should be routed to the Terminal Block TS2 in the Generator Cabinet and connected to the following Terminals.
Note .
In case that the X-ray Tube is provided with a Safety Thermostat (approx. 65
o
C) and a Pressure Switch (both must be NC Contacts), connect them in series before routing, connecting both wire-ends to their respective Terminals in TS2.
THERMOSTAT WIRES TUBE-1 TUBE-2
THERMOSTAT SIGNAL TS2-4 TS2-12
THERMOSTAT COMMON TS2-5 TS2-13
Terminal Block TS2 may be marked as 10TS2 or 11TS2 depending on the Generator model.
If an X-ray Tube is not provided with Thermostat signal, jump both connections in the Terminal Block TS2 (refer to above table).
GND AND/OR SHIELD
The connection of the GND and/or Shield wire of the Stator cables depend on the Generator model.
GENERATOR MODEL
Number of X-ray Tubes Starter type and Location
1 or 2 Tubes
1 or 2 Tubes
LF-RAC (Low Speed)
Lower Cabinet Shelf (Module 10)
LV-DRAC (High Speed)
Lower Cabinet Shelf (Module 11)
CONNECTION OF
GND and/or SHIELD WIRE
10TS2--8 or 10TS2--16
11TS2--8 (for Tube-1)
11TS2--16 (for Tube-2)
IN-1052R0
21
Page 56
HF Series Generators
Installation
3.3.2 TUBE SELECTION SIGNALS
Note .
This section only applies to Generators with two X-ray Tubes.
The Tube Selection signals are available through two contacts free of voltage locatedonthestarter.
TUBE-1 SELECTION TUBE-2 SELECTION SELECTION COMMON
on the LF-RAC Board J1-10 J1-11 J1-12
on the LV-DRAC Module 11KT1-84 11 KT 1-72
11KT1-83 and 11KT1-71
3.4 INTERCONNECTION CABLES
(connect both)
This section identifies the cables and runs needed for Generator and System Interconnection. Route and connect the interconnection cables from each component installed in the system to the Generator Cabinet as indicated in Illustration 3-2 and Section 5.2 -- Interconnection Maps “543010XX”.
Interconnection cables should not be routed into the same conduit or cable raceway as the Power or High Voltage cables.
22
IN-1052R0
Page 57
Illustration 3-2 Interconnection C ables
ATP C ONS OLE C PU
J1
POWER CABLE
(factory supplied)
HF Series Generators
Installation
GENERATOR CABINET
J2
J3
J14
J7 or J8
J2
J5
J13
COMMUNICATION CABLE
SERIAL COMMUNICATION (factory supplied)
INTERFACE CABLE
AEC INTERFACE CABLE
TOMO INTERFACE CABLE (factory supplied)
GND CABLES
(factory supplied)
(factory supplied)
(factory supplied)
(factory supplied)
J3
J5
TS1
TS1
TS2
TS3
COMPATIBILITIES
ADAPTATIONS
L1/L2/L3/N/GND
SERIAL COMMUNICATION
ROOM DOOR CABLE
(customer supplied)
ROOM LIGHT CABLE
(customer supplied)
CABLES FROM BUCKY 1 & 2 (ONLY FOR SYSTEMS WITH 1 OR 2 BUCKY)
(field supplied)
STATOR, FAN & THERMOSTAT FROM TUBES
(field supplied)
ION CHAMBERS, TOMO DEVICES BUCKY 3 & 4, IMAGE SYSTEMS
(customer supplied)
POWERLINE&GNDFOR LINE POWERED GENERATORS
(customer supplied)
IN-1052R0
Note .
For Serial Generators (RS232 / RS422): Console CPUs are located inside the Generator Cabinet and Interconnections are factory made. Only one cable (serial communication) from J5 of the Generator Cabinet should be connected to the Control Box, or PC Interface Box, or Serial Console.
23
Page 58
HF Series Generators
Installation
3.4.1 SERIAL INTERCONNECTION RS232 / RS422
GENERATOR TOUCH SCREEN (TPC) USING A POSITIONER WITHOUT TOUCH SCREEN
For Generator using a TPC, perform the following connections:
(Refer to Illustration 3-3)
1. Connect the AC Supply Cable (A7059--xx) from “AC Supply” connector of the TPC to the respective terminals in TS1 of the Generator Cabinet.
2. Connect the Serial Interconnection Cable (A7067--xx) from “COM1
(Generator)” of the TPC to J5 of the Generator Cabinet.
Note .
3. Connect the Handswitch Cable to the Handswitch connector of the TPC.
4. The TPC includes extra connectors for the Mouse and the Keyboard. Connect them as indicated in the illustration below. In some cases, these communication ports are used to interface the TPC with other devices.
For futher information, refer to Section 5.2 -- Maps 54301052 and A6188--03 at the end of this Document.
24
IN-1052R0
Page 59
HF Series Generators
Illustration 3-3 Connection of the Generator Touch Screen (TPC) using a Positioner without Touch Screen
Installation
GENERATOR TPC
HANDSWITCH
TS1
J5
AC SUPPLY CABLE (A7059--xx)
SERIAL CABLE (A7067--xx)
AC SUPPLY
COM 1 (GENERATOR)
COM 2
TOUCH SCREEN
(INTERNAL)
M (MOUSE) OPTIONAL MOUSE
KB (KEYBOARD)
HANDSWITCH
COM 3
COM 4
OPTIONAL KEYBOARD
Label of Operating System Licence
Serial Interconnection Cable (COM1)
Other Connections (keyboard, etc.)
IN-1052R0
AC Supply Cable
Handswitch
25
Page 60
HF Series Generators
Installation
GENERATOR TOUCH SCREEN (TPC) USING A POSITIONER WITH TOUCH SCREEN
For Generator using a TPC, perform the following connections:
(Refer to Illustration 3-4)
1. Connect the AC Supply Cable (A7059--xx) from “AC Supply” connector of the TPC to the respective terminals in TS1 of the Generator Cabinet.
2. Connect the Serial Interconnection Cable (A3352--xx) from “COM1 (Generator)”oftheTPCtoJ2“Console” of the System Interface Panel in the Control Box.
3. Connect the Serial Interconnection Cable (A7067--xx) from J1 “Generator” of the System Interface Panel in the Control Box to J5 of the Generator Cabinet.
Note .
4. Connect the Handswitch Cable to the Handswitch connector of the TPC.
5. The TPC includes extra connectors for the Mouse and the Keyboard. Connect them as indicated in the illustration below. In some cases, these communication ports are used to interface the TPC with other devices.
For further information, refer to Section 5.2 -- Maps 54301052 and A6188--03 at the end of this Document, and refer to the respective Positioner Service Manual.
26
IN-1052R0
Page 61
HF Series Generators
Illustration 3-4 Connection of the Generator Touch Screen (TPC) using a Positioner with Touch Screen
Installation
GENERATOR TPC
HANDSWITCH
TS1
J5
AC SUPPLY CABLE (A7059--xx)
AC SUPPLY
COM 1 (GENERATOR)
COM 2
TOUCH SCREEN
(INTERNAL)
POSITIONER CONTROL BOX
SERIAL CABLE (A7067--xx)
J1 (GENERATOR)
J2 (CONSOLE)
J6 (REMOTE ON) ON
REMOTE ON CABLE (A9611--xx)
SERIAL CABLE (A3352--xx)
M (MOUSE) OPTIONAL MOUSE
KB (KEYBOARD)
HANDSWITCH
COM 3
COM 4
OPTIONAL KEYBOARD
Label of Operating System Licence
Serial Interconnection Cable (COM1)
Other Connections (keyboard, etc.)
IN-1052R0
AC Supply Cable
Handswitch
27
Page 62
HF Series Generators
Installation
VIRTUAL CONSOLE (PC) USING A POSITIONER WITHOUT TOUCH SCREEN
Systems using a Virtual Console running on a PC usually must have a PC Interface Box installed between the PC and Generator.
(Refer to Illustration 3-5)
Perform the following connections:
1. Remove the Back Cover of the PC Interface Box.
2. Connect the Serial Interconnection Cable (A3352--01) from J1 of the PC Interface Box to J5 of the Generator Cabinet.
3. Connect the Handswitch Cable to J2 of the PC Interface Box.
4. Connect the Interface Box--Computer Cable (A3363 --01) to J3 of the PC Interface Box and the other end (2 connectors) to COM1 (Communication) and J1 (Auto ON/OFF) of the Computer connectors.
Note .
J1 connector is only available in Computers provided with Auto ON/OFF Board inside (factory installed).
5. Re-install the Back Cover of the PC Interface Box.
6. Check to set proper Line Voltage on PC. Plug the Power Line cable for the Computer to a 110 VAC or 230 VAC socket.
Note .
For further information, refer to Section 5.2 -- Maps 54301052, A6188--03 and I/F-036 at the end of this Document.
Illustration 3-5 Connection of the Virtual Console (PC) using a Positioner without Touch Screen
28
GENERATOR
CABINET
J5
SERIAL CABLE (A3352--01)
HANDSWITCH
PC INTERFACE
BOX
J1
J2
J3
PC BOX / PC CABLE
(A3363--01)
POWER LINE CABLE
TO 110 / 230 VAC SOCKET
PC (COMPUTER)
J1
COM1
IN-1052R0
Page 63
HF Series Generators
Installation
VIRTUAL CONSOLE (PC) USING A POSITIONER WITH TOUCH SCREEN
Systems using a Virtual Console running on a PC usually must have a PC Interface Box installed between the PC and Generator.
(Refer to Illustration 3-5)
Perform the following connections:
1. Remove the Back Cover of the PC Interface Box.
2. Connect the Serial Interconnection Cable (A3352--01) from J1 of the PC Interface Box to J2 “Console” of the System Interface Panel in the Control Box.
3. Connect the Serial Interconnection Cable (A7067--xx) from J1 “Generator” of the System Interface Panel in the Control Box to J5 of the Generator Cabinet.
4. Connect the Handswitch Cable to J2 of the PC Interface Box.
5. Connect the Interface Box--Computer Cable (A3363 --01) to J3 of the PC Interface Box and the other end (2 connectors) to COM1 (Communication) and J1 (Auto ON/OFF) of the Computer connectors.
Note .
J1 connector is only available in Computers provided with Auto ON/OFF Board inside (factory installed).
6. Re-install the Back Cover of the PC Interface Box.
7. Check to set proper Line Voltage on PC. Plug the Power Line cable for the Computer to a 110 VAC or 230 VAC socket.
Note .
For further information, refer to Section 5.2 -- Maps 54301052, A6188--03 and I/F-036, and refer to the respective Positioner Service Manual.
Illustration 3-6 Connection of the Virtual Console (PC) using a Positioner with Touch Screen
CABINET
J5
SERIAL CABLE (A7067--xx)
CONTROL
BOX
J2
J1
SERIAL CABLE (A3352--01)
HANDSWITCH
PC INTERFACE
BOX
J1
J2
J3
PC BOX / PC CABLE
(A3363--01)
PC (COMPUTER)GENERATOR
J1
COM1
IN-1052R0
POWER LINE CABLE
TO 110/230 VAC SOCKET
29
Page 64
HF Series Generators
Installation
GENERATOR SERIAL CONSOLE
For systems using a Serial Console, only a Serial Interconnection Cable (A7066--xx) from J5 of the Generator Cabinet must be connected to the J1 of the Serial Console. (Refer to Section 5.2 -- Maps 54301052, A6188-- 03).
3.4.2 COLLIMATOR ERROR SIGNAL (OPTIONAL)
This option must be requested on the customer order. For systems using an Automatic Collimator, the X-ray exposure can be inhibited due to a Collimator Error. This signal can be used only for one Automatic Collimator in the system, special interconnection should be required w hen two Collimators are present.
Connect two wires from the Collimator to Terminal Block 4TS3-20 (Collimator Error signal) and 3TS1-18 (or another GND in this Terminal Block). Collimator Error signal goes (through the Interface Cable) from 4TS3-20 in the Generator Cabinet to terminal J2-6 in Connector J2 of the ATP Console CPU Board. If the system is not provided with Automatic Collimator connect 4TS3--20 to GND (3TS1--18).
3.4.3 DOOR INTERLOCK SIGNAL
Connect two wires from the Room Door Interlock Switch(es) to Terminal Block 3TS1-22 (Door signal) and 3TS1-23 (Door Rtn - gnd). If the X-ray Room is not provided with a Door signal, place a jumper between both connections in Terminal Block 3TS1.
At this point, proceed to perform t he complete Configuration and the Calibration procedures except for AEC. Once Configuration and Calibration tasks have been performed, proceed with the rest of the Installation and Calibration tasks.
30
IN-1052R0
Page 65
3.4.4 WARNING LIGHT SIGNAL
Room Warning Lamp(s) can be externally powered, or internally by the Terminal Block 3TS1. Room Lamp(s) must be connected through the Terminal Block 3TS1-47 and 3TS1-48 (internal relay on Interface Control Board) to enable the Generator switches On/Off the Room Warning Lamps. (Refer to Section 5.2 -- I/F-008).
3.4.5 COLLIMATOR LAMP AND SYSTEM LOCKS
The Generator can supply power to the Manual Collimator Lamp and System Locks (Table, Vertical Bucky, etc.)
HF Series Generators
Installation
Note .
Connect wires from the Collimator Lamp to Terminal Block TB7-3 (24 VAC) and TB7-4 ( 0 VAC) of the Lock Board.
Connect wires from the Locks to Terminal Block TB7-5 (+24 VDC) and TB7-6 (0 VDC) of the Lock Board.
Lock Board
When required, voltages (VAC and VDC) on TB7 can be changed by connecting their respective wires to the other available terminals on the Input Transformer 6T2. (Refer to Schematics 543020XX).
IN-1052R0
31
Page 66
HF Series Generators
Installation
3.4.6 BUCKYS (OPTIONAL)
Connect the Bucky as indicated in the Section 5.2 (Interconnections Maps for Buckys), and test them before connecting the Ion Chambers.
The following table represents the standard Bucky cable connections:
SYSTEM CABLE FROM BUCKY IS CONNECTED TO
Systems with 1 or 2 Bucky
Systems with 3 or 4 Bucky
The Bucky of a RAD only Table with Tomo Device
Note .
Optional “Tomo / Bucky Adaptation Board” is required to install more than two Buckys in the System. (Refer to the “Tomo / Bucky Adaptation Board” and the Manual for the Bucky).
If the “ Bucky Start” signal enters the Bucky through a relay or another inductive device (a.e. a motor), it is mandatory to add the supplied R2--C2 close to each Bucky, so they have to be connected on the terminal output of the Bucky assembly. The R-Cs are attached to the Generator harness in a bag.
If “Bucky Start” signal enters the Bucky through an optocoupler, do not add the suppliedR2--C2fortheBucky.
Note .
The operations described above will prevent noises and uncontrolled Bucky movements that can cause exposure cutting or console blocking.
Terminal Block 3TS1 of the Generator Cabinet
(Refer to Section 5.2 -- Bucky)
Terminal Block TB2 of the optional “Tomo / Bucky Adaptation Board”,
located in the Generator Cabinet
(Refer to Tomo / Bucky Adaptation Board” and Section 5.2 -- Buckys).
Terminal Block TB1 of the optional “Tomo / Bucky Adaptation Board”,
located in the Generator Cabinet
(Refer to Tomo / Bucky Adaptation Board” and Section 5.2 -- Buckys).
3.4.7 TOMO DEVICE (OPTIONAL)
RAD Only T
The Tomo cable (A3083-01) from connector J13 of the “ATP Console CPU Board” has to be connected to the Terminal Blocks TB1 and TB2 of the optional
Tomo / Bucky Adaptation Board”, located in the Generator Cabinet.
The cables from the Tomo Device are also connected to the Terminal Blocks TB1 and TB2 of the optional “Tomo / Bucky Adaptation Board”. Refer to theTomo / Bucky Adaptation Board” for more detailed information and interface. (Refer also to the Manuals of the Tomo Device).
Note .
RAD only Table requires the optional “Tomo / Bucky Adaptation Board”.
32
able
IN-1052R0
Page 67
3.4.8 ION CHAMBERS (OPTIONAL)
The “AEC Control Board” (A3012-XX) must be installed on the ATP Console CPU Board before installing the Ion Chamber(s). The “AEC Adaptation Board” (A3263-03) is also required. (Refer to the “Ion Chamber” Service Manuals).
Perform the following tasks in the order described:
HF Series Generators
Installation
Note .
The Generator is only compatible with Ion Chambers that output a positive ramp.
1. If an Ion Chamber requires High Voltage(200to 500 VDC), the Generator must include an Interface Control Board (version A3009-09/12) that supplies this voltage.
The Interface Control Board must have Jumpers from W3 to W8 in “A” position. This High Voltage is supplied through Terminal Block 3TS1-39 “PT SPLY” of the Generator Cabinet and sent with a wire to TB1-9 of theAEC Adaptation Board”.
ION CHAMBERS WITH HIGH VOLTAGE
GE BVM-CGR
AMP-Phenolic Connector DB 15 Connector
300 VDC 230 VDC 500 VDC 400 VDC
Notes: -- If the System included both GE and BVM-CGR Ion Chambers, Terminal TB1-9 must supply 270 VDC.
-- Philips Amplimat Ion Chambers can not be installed with GE or BVM-CGR Ion Chambers.
PHILIPS AMPLIMAT
IN-1052R0
DO NOT CONNECT ANY ION CHAMBER TO THE GENERATOR CABINET UNTIL HIGH VOLTAGE IS EITHER VERIFIED OR ADJUSTED TO THE VALUES REQUIRED. OTHER VOLTAGE COULD DAMAGE THE ION CHAMBERS.
Turn the Generator ON and verify voltage in TB1-9 according to the Ion Chambers to be installed. If necessary, adjust the High Voltage at Potentiometer R20 of the Interface Control Board. Turn the Generator OFF after adjustment.
33
Page 68
HF Series Generators
Installation
2. Connect each Ion Chamber cable to J1 (IC1), J2 (IC2), J3 (IC3) or J5 (IC4) of the “AEC Adaptation Board”. The code for the Ion Chamber cable supplied by the Generator manufacturer is A3253--01.
Note .
Note .
Same Ion Chamber types have to be installed in consecutive order starting at J1 (IC1). In the case of using four Ion Chambers, IC3 and IC4 must have the same film/cassette combination.
The Vacutec, AID or similar Ion Chamber type is directly connected to the “AEC Adaptation Board”. For Comet Ion Chambers, cable connection has to be made previously through the Comet Preamplifier PA-021 and then directly to the “AEC Adaptation Board”.
For other cases, a cable adapter is required. The Generator manufacturer has the following cable adapters available: GE (A3082--01), CGR-BVM (A3081--01), Philips Amplimat (A3080--01/02 with DB-15 or A6727-01/02 with Phenolic connector) and MEDYS (A6715--01).
34
IN-1052R0
Page 69
Illustration 3-7
*
Four Ion Chamber Connection
HF Series Generators
Installation
GENERATOR
POWER INTERFACE Cable
TS1
ATP CONSOLE BOARD
J5
AEC INTERFACE Cable
ATP CONSOLE CPU BOARD
AEC ADAPTATION BOARD
TB1
J4
POWER INTERFACE CABLE
AEC INTERFACE CABLE
(A3263--03)
AEC ADAPTATION PCB
TB1TS1 (Generator Cabinet)
ADAPTATION CABLE*
ADAPTATION CABLE*
TB1--9
ADAPTATION CABLE*
ADAPTATION CABLE*
J4J5
J1
J2
J3
J5
* Connections free of voltage IC Adaptation Cables
ION CHAMBER Cable
J1
ION CHAMBER Cable
J2
ION CHAMBER Cable
J3
ION CHAMBER Cable
J5
IC 1 PREAMPLIFIER
IC 2 PREAMPLIFIER
IC 3 PREAMPLIFIER
IC 4 PREAMPLIFIER
Connections with IC Adaptation Cables
ION CHAMBER 1
(field supplied)
ION CHAMBER 2
(field supplied)
ION CHAMBER 3
(field supplied)
ION CHAMBER 4
(field supplied)
3. Configure Jumpers from JP1 to JP8 and from JP13 to JP16 according to the group of Ion Chamber type:
ION CHAMBER TYPE
JP3, JP4, JP7, JP8 JP1, JP2, JP5, JP6 JP13, JP14, JP15, JP16
IC1 = IC2 = IC3 = IC4 B B B
IC1 = IC2 = IC3 B B A
IC1 = IC2 B A A
IC1 IC2 IC3 IC4 A A A
IN-1052R0
JUMPERS POSITION
35
Page 70
HF Series Generators
Installation
4. Each type of Ion Chamber requires a specified reference voltage for “Area Selections” and “AEC Reset” signals:
G Vacutec, AID and Comet Ion Chambers require GND (TB1-10).
G MEDYS, CGR-BVM, GE and Philips Amplimat Ion Chambers
require +24 VDC (TB1-4).
The reference voltage is provided from: TB1-7 “Relay 1” for IC1; TB1-6 “Relay 2” for IC2; TB1-5 “Relay 3” for IC3; and TB1-8 “Relay 4” for IC4.
For each group of Ion Chambers of the same type, connect a wire between each of the above mentioned terminals to TB1-10 (GND), TB1-4 (+24 VDC) or TB1-3 (+12 VDC) depending on the voltage required (examples: for four MEDYS Ion Chambers add only a wire-jumper
between TB1-7 and TB1-4; or for one MEDYS Ion Chamber as IC-1 and one COMET Ion Chamber as IC-2add a wire-jumper between TB1-7 and TB1-4, and another wire between TB1-6 and TB1-10).
DO NOT TURN ON THE GENERATOR UNTIL THE INPUT SIGNALS OF ALL THE ION CHAMBERS ARE CONNECTED TO THE REQUIRED VOLTAGE. OTHER VOLTAGE MIGHT DAMAGE THE ION CHAMBERS.
5. Ion Chambers output must be 0 VDC when there is no-radiation (No-Offset adjustment). If an Ion Chamber output has an offset, it must be adjusted to 0 VDC with the respective Potentiometer.
Configure Jumpers from JP9 to JP12 and turn ON the Generator only to adjust the following Potentiometers (if needed) according to the Ion Chamber output:
ION CHAMBER OUTPUT
NO-OFFSET ADJUSTMENT A A A A
OFFSET ADJUSTMENT B B B B
TEST POINT AND POTENTIOMETER
(ONLY IF JUMPER IS IN “B” POSITION)
JP9 (IC1) JP10 (IC2) JP11 (IC3) JP12 (IC4)
TP1 -- R11 TP2 -- R8 TP4 -- R2 TP12 -- R5
JUMPERS POSITION
36
IN-1052R0
Page 71
HF Series Generators
SECTION 4 FINAL INSTALLATION AND CHECKS
4.1 HV TRANSFORMER
This point does not apply to the hermetic HV Transformers (black aluminium HV Transformers).
Installation
Ventilation Screw
The HV Transformer contains “Shell Diala AX” oil. Check that there is no oil leakage. If leakage is found, remove the oil fill plug from the top of the HV Transformer and verify that the oil level is within 20 mm (3/4”) from the top of the H V Transformer. Add “Shell Diala AX” oil if necessary.
Unscrew the Ventilation Screw from the top of the HV Transformer.
4.2 CABLE FASTENING AND COVERS
Note .
Before re-installing cabinet covers, perform the rest of the required Calibration procedures (a.e. AEC).
Check that all electrical connections are firm and secure. Cables should be correctly routed. (Refer to Section 3.1)
In order to avoid signal interferences, it is strongly recommended to fold and fasten close to the Generator Cabinet the portion of cables not routed (see picture below). Never wrap in circles.
IN-1052R0
YES NO
Re-install the Cabinet covers and connect its internal ground wires. Power line, High Voltage and Interconnections cables must go through the cover cable outlet.
37
Page 72
HF Series Generators
Installation
This page intentionally left blank.
38
IN-1052R0
Page 73
SECTION 5 SYSTEM INTERCONNECTIONS
5.1 SYSTEM INTERCONNECTION SIGNALS
All input signals are active low. This means the inputs must be pulled to ground (chassis ground of the Generator) thru relay contacts, by a transistor or other switching device. The current requirement of the switch is less than 10 mA.
Do not apply 115 / 220 VAC logic signals to any of the logic inputs. If 115 / 220 VAC logic signals are used in the X-ray table, these signals must be converted to a contact closure by a relay.
HF Series Generators
Installation
The outputs signals from the Generator to the subsystem devices are usually active low (switched to chassis ground of the Generator). The outputs are open collector transistor drivers with a maximum current of 0.5 Amperes.
Table 5-1 System Interconnection Signals
SIGNAL NAME SIGNAL DESCRIPTION
AUX BUCKY SPLY External voltage supply required for the Bucky motion, when this voltage is not +24 VDC.
--BUCKY 1 DR CMD A low signal to the Interface Control Board as a command to output a Bucky-1 (normally the Table Bucky) drive signal.
--BUCKY 1 MOTION This low going signal from Bucky-1 indicates Bucky-1 motion, and therefore the exposure is enabled.
BUCKY 1 DR This signal is originated from the Bucky supply of the Power Module when an exposure order. It starts the Bucky.
--BUCKY 2 DR CMD Alow signal to the InterfaceControlBoard as a commandtooutput a Bucky-2 (normally theVertical Bucky Stand)drivesignal.
--BUCKY 2 MOTION This low going signal from Bucky-2 indicates Bucky-2 in motion, and therefore the exposure is enabled.
BUCKY 2 DR This signal is originated from the Bucky supply of the Power Module when an exposure order. It starts the Bucky.
--BUCKY EXP This low going (0 volts) signal starts the Bucky exposure. The signal originates on the Interface Board
BUCKY SPLY Voltage supply required for the Bucky drive command.
C--HT CLK Serial data clock to the HT Control Board. This clock synchronizes the C--HT DATA signal.
C--HT DATA Serial data to the HT Control Board. This data is synchronous with the C--HT CLK signal.
--COLLIMATOR
This active lowsignalindicates that NO EXPOSURE HOLD condition existsatthe Collimator. This input is readonlywhen the Radiographic Tube is selected.
--DOOR This low signal is the interlock for the Door of the X-ray room.
IN-1052R0
39
Page 74
HF Series Generators
Installation
Table 5-1 (cont.) System Interconnection Signals
SIGNAL NAME SIGNAL DESCRIPTION
--FLD1 DR A low signal to select the right field in the Ion Chamber.
--FLD2 DR A low signal to select the left field in the Ion Chamber.
--FLD3 DR A low signal to select the center field in the Ion Chamber.
HT--C CLK Serial data clock from the HT Control Board. This clock synchronizes the HT--C DATA signal.
HT--C DAT Serial data from the HT Control Board. This data is synchronous with the HT--C CLK signal.
-- H T I N L
This signal is low when the switch in the high voltage transformer is in the RAD position. This is a safety interlock which prevents an exposure if the high voltage switch (in the HV Transformer) is in the wrong position.
HV PT CRL
IC GND GNDfortheICSPLY.
IC1 INPUT This input is the output of the Bucky 1 Ion Chamber (normally the Table Ion Chamber).
IC2 INPUT This input is the output of the Bucky 2 Ion Chamber (normally the Vertical Bucky Stand Ion Chamber).
IC3 INPUT This input is the output of the Spot Film Ion Chamber.
IC SPLY Power supply for the Ion Chamber. This output should be within the range of 500 to 800 volts.
--LINE CONT A low signal energizes the main line contactor K5 in the Power Module.
--PREP
--READY
--ROOM LIGHT
-- S T R T D R A low signal to indicate the start of an exposure to the Ion Chamber.
--THERMOSTAT-1 This signal from X-ray Tube indicates the overheat of the Tube-1.
--THERMOSTAT-2 This signal from X-ray Tube indicates the overheat of the Tube-2.
This analogicsignal(originates in the optionalAECControl Board) controls theoutputof the HVPowerSupply on the Interface Control Board. +5 volts programs the output to be 0 volts, and 0 volts programs the output to approximately --1200 volts.
Commands totheHT Control Board toboost X-ray Tube Filamenttothe value of mA selectedand to start the X-rayTube Rotor is RAD Tube is selected.
This lowgoingsignal indicates thesystemis ready to makean exposure (Prep cyclecomplete). This signalisused to interface to certain peripheral devices such as Film Changers, etc.
This low going signal indicates the X-ray preparation or exposure. This signal is used to interface to the Room X-ray warning light.
40
IN-1052R0
Page 75
5.2 SYSTEM INTERCONNECTION MAPS
Refer to the following maps for details of the wire connections.
SYSTEM INTERCONNECTION
Compact / Compact-ESM Generators.
System Interconnection 54301045.............................
Serial Communication to Generator.
System Interconnection 54301052.............................
RS-232/422/485 Serial Communication A6188--03...............
PC / Serial Interface Box I/F-036............................
Metallic Case X-ray Tube Connection 54302035.................
HF Series Generators
Installation
Earthing Diagram I/F-103..................................
STATOR INTERFACE
Philips Tubes -- Stator Interface I/F-021......................
Siemens Tubes -- Stator Interface I/F-024....................
ROOM LAMPS
Room Warning Light Interface I/F-008.......................
BUCKYS
Table Bucky Interface
(Liebel / Midwest / Ultravit / Dong-A) I/F-001..................
Vertical Bucky Interface
(Liebel / Midwest / Ultravit / Dong-A) I/F-002..................
AEC -- ION CHAMBERS
IN-1052R0
AEC -- VACUTEC / AID / COMET Compatibility
for more than one Ion Chamber I/M-015......................
AEC Adaptation A3263--03...................................
41
Page 76
HF Series Generators
Installation
This page intentionally left blank.
42
IN-1052R0
Page 77
FLUORO CPU BOARD
CONNECTOR J4
SIGNAL C--FL DAT GND
--CAM FL EXP C--FL CLK FL--C DAT GND FL-- CCLK CAM SYNC +12V ISO N.U.
ATP CONSOLE BOARD
FLUORO
CONNECTOR J4
SIGNAL C--FL DAT
--CAM FL EXP FL--C DAT FL-- CCLK +12V ISO GND C--FL CLK GND CAM SYNC
TOMO
CONNECTOR J13
SIGNAL TIME1 TIME2 TIME3 TIME4
--PS (DSI) SEL
--CINE (DSA) SEL
--HCF SEL SPARE IN
--TOMO PREP
--TOMO EXP TOMO ON EXT REF GND EXP STOP
-- FS
POWER
CONNECTOR J1
SIGNAL GND UNR +12V UNR +12VDC
-- PW R O FF
-- PW R O N GND UNR GND +12V UNR
--12VDC
HAND-- SWITCH (orVET PEDAL SWITCH)
CONNECTOR J15
SIGNAL COM PREP EXP
CONNECTOR J1 / J10
SIGNAL
--4 IN SEL
--9 IN SEL +12 VDC
I/O
PIN
I
1
I/O
2
O
3
I
4
O
5
I/O
6 7
O
8
O
9
I
10
I/O
PIN
1
O I
2
I
3
I
4 5
I
6
I/O
7
I
8
I/O
9
O
V SYNC
-- FT S W C MD FL START
--CAM FL EXP N.U.
--ABS
--6 IN SEL BEEP GND
-- ME M E N
-- ME M G AT E N.U.
A.E.C.
CONNECTOR J5
SIGNAL IC1 INPUT IC3 INPUT
--FLD1 DR
--FLD3 DR GND IC2 INPUT IC4 INPUT
--FLD2 DR
-- ST R T D R
I/O
PIN
O
1
O
2
O
3
I
4
I
5
O
6 7
O
8 9
O
10
O O
11
O
12
O
13
O
14 15
FLUORO CABLE
ADAPTATIONS
BOARDS
AEC CABLE
I/O
PIN
1
I I
2
O
3
O
4 5
O
6
I
7
I
8
O
9
O
TOMO CABLE
INTERFACE
I/O
PIN
I
1
I
2
I
3
I
4
I
5
I
6 7
I
8
I
9
O
10
O O
11
I
12
I/O
13
I
14 15
O
I/O
PIN
1
I I
2
I
3
O
4
O
5 6
I
7
I
8
I
9
I
I/O
PIN
O
1
I
2
I
3 4N.U.
CONNECTOR J2
SIGNAL
-- GE N O K
--SFD SEL
--THERMOSTAT 1
--SF PREP GND (THERM. COM)
--COLLIMATOR TABLE ERR(COMP)
--ROOM LIGHT
--READY EXP OK ABC OUT/--LEFT
--DIRECT SEL PT INPUT EXT SYNC (FL DSI) SPARE IN2
--SFC ( -- PTSEL)
--FL EXP GND (DOOR RTN)
--DOOR
--THERMOSTAT 2
-- AU T O O F F SPARE IN1 ALOE
-- AL O E
--ACT EXP
COMMUNICATION
CONNECTOR J3
SIGNAL
--EXP C--HT DAT HT--C DAT
--PREP C--HT CLK HT--C CLK HV PT CRL
-- KV D W N LINE SYNC
--LINE CONT
--BUCKY 2 DR CMD
--BUCKY EXP
-- HT I N L
--BUCKY 1 DR CMD
-- KV U P
GND STUD
I/O
PIN
1
O
2
O
3
I I
4
I/O
5
I
6
I
7
O
8
O
9
O
10
O
11
O
12
I
13
I
14
I
15
I
16
I
17
I/O
18
I
19
I
20 21
O
22
I
O
23
O
24
O
25
I/O
PIN
O
1
O
2
I
3
O
4
O
5
I
6
O
7
O
8
I
9
O
10
O
11
I
12
I
13
O
14
O
15
HAND--SWITCH
(or VET PEDAL SWITCH)
INTERFACE CABLE
POWER CABLE
COMMUNICATION CABLE
GND CABLE
F
Adaptation Boards
E
CN 04/032
New interfaceD
New interfaceC
CN 00/211B
New interfaceA
F. GARCIA 01/09/06
F. GARCIA 26/04/04
F. GARCIA 08/01/02
F. GARCIA 02/02/01
F. GARCIA 04/01/01
F. GARCIA 05/05/00
NOTE : Signal for Thermostats go to 4TS3
andthentoTS2orgodirectlytoTS2 depending on Generator model
GND STUD
DRAWING
REVISED
REV DESCRIPTION ISSUED BY DATE
TERMINAL BLOCK 3TS1
SIGNAL
PIN
I/O
O
1
SUPPLY (BUCKY 1)
2
O
BUCKY SPLY 1
O
3
0 VAC (BUCKY 1) BUCKY 1 DR
O
4 5
I
--BUCKY 1 MOT
6
BUCKY 1 MOT RTN
I
7
GND
O O
8
SUPPLY (BUCKY 2)
O
BUCKY SPLY 2
9
O
0 VAC (BUCKY 2)
10
BUCKY 2 DR
O
11
--BUCKY 2 MOT
I
12
I
13
BUCKY 2 MOT RTN GND
O
14
O+12V
15 16
O
-- 12 V
O
17
+24V UNR
18 O
GND
22
--DOOR
I
23
DOOR RTN
O
--ROOM LIGHT
O
24
26
O
220 VAC SW
O
27
115 VAC SW
--SF PREP
36
O
--FL EXP
37
O
39
O
PT SPLY IC GND
42
O O
47
ROOM LIGHT SUP
O
48
ROOM LIGHT SW
51
I
PT INPUT
-- AL O E
O5352 O
--READY
54 O 220 VAC SPLY
TERMINAL BLOCK 4TS3
SIGNAL
I/O
PIN
--THERMOSTAT 1
I
1 2
--THERMOSTAT 2
I
3
I
THERM. COMM
II5
TABLE ERROR
7
--SFC ( -- PTSEL)
8
O
ALOE
O
10
-- GE N O K
11
--SFD SEL
O
--DIRECT SEL
12
O
15
O
EXP OK
16
--ACT EXPO
O
-- AU T O O F F
17 18
I
ABC OUT / --LEFT
19
I
EXT SYNC(FL DSI)
20
I
-- CO L LI M AT OR
A
Foot Switch Cmd.I
GND
B
Prep/Rdy Acq Rad
C
O
D
I
Boost Fluoro
I
E
Digital Exposure
CONNECTOR 6J3
I/O
PIN
O
1
O
2
I
3
O
4
O
5
I
6
O
7
O
8
I
9 10 11 12 13 14 15
--LINE CONT
O
--BUCKY 2 DR CMD
O
--BUCKY EXP
I I
--BUCKY 1 DR CMD
O O
NAME DATE
F. GARCIA 04/04/99
A. DIAZ 28/01/00
SEDECAL
SIGNAL
--EXP C--HT DAT HT--C DAT
--PREP C--HT CLK HT--C CLK
HV PT CRL
-- KV D W N
LINE SYNC
-- HT I N L
-- KV U P GNDO16
COMPACT GENERATOR CABINET
FOR GENERATORS LINE POWERED
L1
L2/N
L3
GND
L3 only for Three Phase
FOR GENERATORS BATTERIES POWERED
1TB1--LINE
L
1
N
2
GND
3
NOTE.-- For Generator with DRAC :
The ROTOR TUBE connections are made to TS2 on the DRAC
TERMINAL BLOCK
SHEET / OF
4TS2 / 10TS2 / 11TS2
--THERMOSTAT 1
THERMOST. COMM.
--THERMOSTAT 2
THERMOST. COMM.
NOTE : TS2-- 6 is GND when TS2 only has 6 terminals.
NOTE -- For Serial Cabinet :
-- the Interface cable connections are factory made to 3TS1, TS2 and 4TS3 terminal blocks.
-- 6J2 is not supplied, Power cable is directly connected in factory to J1 of the ATPConsole.
-- 6J3 is not supplied, Power cable is directly connected in factory to J3 of the ATPConsole.
DWG:
I/O
PIN
SIGNAL
MAIN T1
O
1
O O
I I
FAN 1
O
0VAC
O
GND
O O O O
I I
FAN 2
O
O
0VAC
O
GND
CONNECTOR 6J2
I/O
1
O
2
O
3
O
4
I
5
I
6
O O
7
O
8
O
9
LOCKS BOARD
SIGNAL
24 VAC LAMP
0VACLAMP
0 VDC LOCKS
0 VDC LOCKS
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
+12V UNR
-- PW R O FF
+12V UNR
I/O
O O O O O O
AUX T1
COM T1
MAIN T2
AUX T2
COM T2
PIN
TERMINAL BLOCK TB7
+24 VDC LOCKS
+24 VDC LOCKS
-- PW R O N
54301045
1/2
COMPACT / COMPACT-ESM GENERATORS
SYSTEM INTERCONNECTION
SIGNAL
GND
+12VDC
GND GND
-- 12 V DC
PIN
3 4 5
6 7
8
TO LINE VOLTAGE
}
BREAKER
TO EARTH GROUND
TO SOCKET
}
(Line Voltage)
TO RO TOR TUBE
}
COLLIMATOR LAMP
LOCKS (Table & Tube Stand)
AREVBCDEF
Page 78
NOTE.-- The Adaptation Boards are optional
GENERATOR CABINET
to J5 of ATP Console Board
3TS1
16
15
17
18
+24V UNR
--12V
+12V
GND
ADAPTATION BOARD
J4
TB1
2
3
4
10
NOTE Depending on the Ion Chamber, make jumpers configuration and interface as specific schematic IM-xxx
ADAPTATION BOARD
TB1
12
13
AEC
(A3263--03)
TOMO / BUCKY
(A3261--03/05)
GENERATOR CABINET
ADAPTATION BOARD
to J5 of ATP Console Board
J1
J2
to Ion Chamber #1
to Ion Chamber #2
RF ADAPTATION BOARD
J3
J5
to Ion Chamber #3
to Ion Chamber #4
3TS1
39
(A3514--04)
HIGH VOLTAGE SUPPLY (if r equired)
TB1
3
4
5
2
--12V
+12V
+24V UNR
GND
J4
TB1
9
2
3
4
10
NOTE Depending on the Ion Chamber, make jumpers configuration and interface as specific schematic IM-xxx
ADAPTATION BOARD
TB1
12
13
AEC
(A3263--03)
TOMO / BUCKY
(A3261--03/05)
J1
J2
J3
J5
to Ion Chamber #1
to Ion Chamber #2
to Ion Chamber #3
to Ion Chamber #4
NOTE Depending on the Tomo Device, make jumpers configuration and interface as specific schematic IM-xxx
Interconnection of Adaptation Boards
for a Generator without RF Adaptation Board
F
Adaptation Boards
E
New interfaceD
New interfaceC
New interfaceA
CN 04/032
CN 00/211B
F. GARCIA 01/09/06
F. GARCIA 26/04/04 F. GARCIA 08/01/02
F. GARCIA 02/02/01
F. GARCIA 04/01/01
F. GARCIA 05/05/00
REV DESCRIPTION ISSUED BY DATE
NOTE Depending on the Tomo Device, make jumpers configuration and interface as specific schematic IM-xxx
Interconnection of Adaptation Boards
for a Generator with RF Adaptation Board
DRAWING
REVISED
NAME DATE
F. GARCIA 04/04/99
A. DIAZ 28/01/00
SHEET / OF
2/2
DWG:
SEDECAL
54301045
AREVBCDEF
COMPACT GENERATORS
SYSTEM INTERCONNECTION
Page 79
SERIAL OPERATOR CONSOLE
Board
J1
+24 VDC UNR
1
PWR GND
3
CHASSIS GND
5 7
9 11 13 15
2
4
6
8 10 12 14 16
NOTES: RXD ON GENERATOR IS CONNECTED TOTXD ON SERIAL OPERATOR CONSOLE TXD ON GENERATOR IS CONNECTED TORXD ON SERIAL OPERATOR CONSOLE
SPARE
RXD
PREP/EXP COMM
EXP ORDER
POWER ON
+24 VDC UNR
PWR GND
CHASSIS GND
SPARE
TXD PREP ORDER POWER COMM
POWER OFF
J1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
TPC or PC INTERFACE BOX
CONNECTOR J1
SIGNAL
CTS ( RXD-- )
RXD ( RXD+ )
TXD ( TXD+ )
RTS ( TXD-- )
SPARE PIN 5
LOGIC GND CHASSIS GND CHASSIS GND
PREP/EXP COMM
EXP ORDER
PREP ORDER
POWER COMM
POWER OFF
POWER ON
SPARE PIN 20 SPARE PIN 21
+24 VDC UNR
NOTES:
RXD AND TXD ARE INTERNALLY REVERSED INTPC OR PC INTERFACE BOX REFER TO SCHEMATICS I/F--036 FOR OTHER PC INTERFACE BOX CONNECTIONS
+24 VDC UNR
ACT EXP
+12 VDC
-- AL O E PWR GND PWR GND
DOOR
DOOR RTN
I/O PIN
I
I O O
O O O O
O O O
I
I I/O
I
I
O O
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
SERIAL INTERCONNECTION CABLE FOR SERIAL CONSOLE (A7066--xx or A3149--01)
SERIAL INTERCONNECTION CABLE FOR TPC (A7067 --xx or A3 352-- 01) SERIAL INTERCONNECTION CABLE FOR INTERFACE BOX (A3352-- 01)
GENERATOR CABINET
NOTE: FOR GENERAL INTERCONNECTIONS REFER TO SCHEMATIC
54301045 (COMPACT / COMPACT-ESM GENERATORS)
CONNECTOR J5
SIGNAL
I/O
PIN
1
CTS ( RXD-- )
I
2
RXD ( RXD+ )
I
3
TXD ( TXD+ )
O O
4
RTS ( TXD-- ) SPARE PIN 5
5
O
6
ACT EXP
O
7
LOGIC GND
O
8
CHASSIS GND
O
9
CHASSIS GND 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
+12 VDC
-- AL O E
PWR GND
O
PWR GND
O
PREP/EXP COMM
O
EXP ORDER
I
PREP ORDER
I
POWER COMM
I/O
I
POWER OFF
I
POWER ON
SPARE PIN 20
SPARE PIN 21
DOOR
DOOR RTN
+24 VDC UNR
O O
+24 VDC UNR
NOTE: REFER TO SCHEMATICA6188 --02 FOR RS-- 232/422/485SERIAL COMMUNICATION
NC 03 / 050C
New schematicB
ConnectionsA
F. GARCIA 08/03/03
F. GARCIA 08/01/02
F. GARCIA 02/02/01
REV DESCRIPTION ISSUED BY DATE
DRAWING
REVISED
NAME DATE
F. GARCIA 07/07/99
A. DIAZ 24/01/00
SEDECAL
SHEET / OF
1/1
DWG:
54301052
AREVBC
SERIAL COMMUNICATION TO GENERATOR
SYSTEM INTERCONNECTION
Page 80
GND
+12V UNR
+12V
OFF
ON
GND
GND
+12V UNR
--12V
--EXP
C--HT DAT
HT--C DAT
--PREP
C--HT CLK
HT--C CLK
HV PT CRL
-- K V D W N
LINE SYNC
--LINE CONT
--BUCKY 2 DR CMD
--BUCKY EXP
-- H T I N L
--BUCKY 1 DR CMD
-- K V U P
ATP CONSOLE BD. ( Multilayer )
J14
RXD+
TXD+
+5V
GND
TXD--
RXD--
RXD
TXD
DTR
GND
1
2
3
6
RS--xxx
J8
1
2
3
4
5
6
7
8
9
RS--232
J7
1
2
3
4
5
6
7
8
9
4
5
+24V UNR
Note.-- Signals between ( ) when RS--232 Serial Communication
J2
1
2
3
4
5
6
7
8
9
J3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
POWER CABLE
COMMUNICATION
CABLE
J1
1
GND
2
+12V UNR
3
+12V
4
OFF
5
ON
6
GND
7
GND
8
+12V UNR
9
-- 1 2 V
J3
1
--EXP
2
C--HT DAT
3
HT--C DAT
4
--PREP
5
C--HT CLK
6
HT--C CLK
7
HV PT CRL
8
-- K V D W N
9
LINE SYNC
10
--LINE CONT
11
--BUCKY 2 DR CMD
12
--BUCKY EXP
13
-- H T I N L
14
--BUCKY 1 DR CMD
15
-- K V U P
PREP/EXP COMM
PREP ORDER
EXP ORDER
POWER OFF
POWER ON
POWER COMM
ACT EXP
ACT EXP
GND
J5 HARNESS
TS1
15
52
18
17
22
23
51
/////
J5
14
PREP/EXP COMM
16
PREP ORDER
15
EXP ORDER
18
POWER OFF
19
POWER ON
17
POWER COMM
10
+12 VDC
11
-- A L O E
12
PWR GND
13
PWR GND
24
+24 VDC UNR
25
+24 VDC UNR
22
DOOR
23
DOOR RTN
21
PT INPUT
6
ACT EXP
2
RXD+ ( RXD )
3
TXD+ ( TXD )
20
7
LOGIC GND
5
4
TXD--
1
RXD--
8
CHASSIS GND
9
CHASSIS GND
See Note
A 09/09/04F. GARCIACN 04/148
REV DESCRIPTION ISSUED BY DATE
DRAWING
REVISED
NAME DATE
F. GARCIA 04/04/04
A. DIAZ 04/04/04
SEDECAL
SHEET / OF
1/1
DWG:
A6188--03
AREV
RS--232/422/485 SERIAL COMMUNICATION
Page 81
PC INTERFACE BOX
(A6509--01)
J1
14
16
15
25
+24V UNR
13
PWR GND
LAMP
HAND--SWITCH
J2
1
2
3
HANDSWITCH CABLE
(A3223--05)
PREP/EXP COMM
PREP ORDER
EXP ORDER
COMPUTER
CONNECTION TO GENERATOR
INTERFACE BOX CABLE
(A3352--01)
19
18
17
5
N.U.
2
3
7
9
21
10
11
22
23
POWER ON
POWER OFF
POWER COMM
TxD
RxD
GND
PT INPUT
+12 VDC
-- A L O E
DOOR
DOOR RTN
////
for external connection
GND STUD
AUTO ON/OFF
J1/J2
4
1
6
COM 1
RS232
3
2
5
(A3179--01/02)
J2
1
+12V
2
GND
INTERFACE BOX--COMPUTER CABLE
J3
4
1
6
3
2
5
(A3363--01)
C F. GARCIA 10/09/04CN 04/148 B F. GARCIA 09/05/03CN 03/050 A F. GARCIA 07/07/00CN 00/148
REV DESCRIPTION ISSUED BY DATE
DRAWING
REVISED
NAME DATE
F. GARCIA 30/03/00
A. DIAZ 30/03/00
SEDECAL
SHEET / OF
1/1
I/F--036
AREVBC
PC/SERIAL INTERFACE
Page 82
5
D D
4
3
2
1
Anode supply
Black
X-ray Tube
mA
C C
mA -
Red
Shunt
Shunt
mA +
B B
Cathode supply
A A
REV DESCRIPTION ISSUED BY DATE
5
4
DRAWING
REVISED
NAME DATE SHEET / OF
11/02/03F. Díaz
11/02/03A. Díaz
1/1
SEDECAL
3
54302035
METALLIC CASE X-RAY TUBE CONN.
2
1
REV
Page 83
ROOM ELECTRICAL CABINET
GND cable
( yellow/green, AWG #10 )
GENERATOR CABINET
(6)
(7)
(1)
(5)
(2)
(4)
(3)
(1)
Central Ground
(2)
GND Stud
(3)
Cabinet Cover GND
(4)
Back Panel GND
(5)
Front Panel GND
(6)
Filter LF1 Cover GND
(7)
Adaptations Panel GND
(8)
Console GND (Bottom Panel)
(9)
Console Support GND
(10)
Pedestal Tube GND
(11)
Pedestal Cover GND
(12)
GND STUD
OPERATOR CONSOLE
See Note
(9)
(8)
PEDESTAL
(10)
(11)
GND cable
( yellow/green, AWG #10 )
(Option)
(12)
REV DESCRIPTION ISSUED BY DATE
DRAWING
REVISED
NAME
F. GARCIA
A. DIAZ 30/06/04
DATE
30/06/04
SEDECAL
GND
HV TANK
SHEET / OF
1/1
Note.-- (9) applicable only for metallical Box Console
I/F--103
REV
EARTHING DIAGRAM
Page 84
STATOR ROTALIX 350/351 CONNECTIONS
100
1
23
54
6
7
9
AUXILIARY
COMMON
200
2
43
56
8
10
7
MAIN
STATOR SUPER ROTALIX 350 CONNECTIONS
100
1
43
56
8
7
9
AUXILIARY
200
2
43
56
8
10
7
MAIN
COMMON
REV DESCRIPTION ISSUED BY DATE
DRAWING
REVISED
NAME DATE
F. GARCIA 09/09/98
A. DIAZ 09/09/98
SEDECAL
SHEET / OF
1/1
Interconnection
Interconexión
PHILIPS TUBES--STATOR INTERFACE
I/F--021
REV
Page 85
STATOR 100 CONNECTIONS ( BIANGULIX and OPTILILIX TUBES )
Estator 100
BIANGULIX and OPTILIX ( SIEMENS )
Output connector
Ia
0
Make jumper
COMMON
I
AUXILIARY
Make jumper
Ib
II
MAIN
NOTE
CONNECT THE STATOR CABLE AS SHOWN. CHECK THE CABLE SUPPLIED WITH THE TUBE.
REV DESCRIPTION ISSUED BY DATE
DRAWING
REVISED
NAME DATE
F. GARCIA 09/09/98
A. DIAZ 09/09/98
SEDECAL
SHEET / OF
1/1
Interconnection
Interconexión
I/F--024
SIEMENS TUBES--STATOR INTERFACE
REV
Page 86
Interconnection 1.-- For Generator Interface with control relay and externally powered
POWER
TS1
X--RAY ROOM
MODULE
ROOM LIGHT SUP
ROOM LIGHT SW
47
48
ROOM
WARNING
LIGHT
115 / 220 VAC
}
Interconnection 2.-- For Generator Interface with control relay and internally powered
POWER MODULE
115 or 220 VAC SW
add jumper
ROOM LIGHT SUP
ROOM LIGHT SW
TS1
47
48
X--RAY ROOM
*
ROOM
WARNING
LIGHT
(in TS1-3 or TS1-10)
0VAC
*
Select the power supply on TS1 according to the lamp voltage.
*
Add jumper to TS1-26 for 220 VAC or to TS1-27 for 115 VAC.
Interconnection 3,-- Additional option to meet some Local Electrical Codes
POWER
MODULE
ROOM LIGHT SUP
Contact 7A 1/6HP
125, 250 V AC
3A 30 V DC
ROOM LIGHT SW
TS1
47
48
I/F update F. GARCIA 20/06/04E I/F update F. GARCIA 02/02/02D
I/F changing F. GARCIA 05/05/99C
TS1 changing F. GARCIA 24/05/96B
EMC F. GARCIA 29/03/96A
REV DESCRIPTION ISSUED BY DATE
DRAWING
REVISED
NAME DATE
F. GARCIA 04/19/95
A. DIAZ 04/19/95
SEDECAL
SHEET / OF
1/1
I/F--008
AREVBCDE
ROOM WARNING LIGHT INTERFACE
INTERFAZ LAMPARA RAYOS--X SALA
Page 87
GENERATOR POWER MODULETABLE
BUCKY LIEBEL (Semi--Automatic) BUCKY MIDWEST BUCKY INNOMED (IBC 430)
Semi--Automatic
Bucky
B1
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
B2
B3
(SEE NOTE 3)
R2
C2
B8
B4
BUCKY 1 MOTION
BUCKY 1 MOTION RTN
BUCKY 1 DR
0VAC
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--5
TS1--6
TS1--4
TS1--3
TS1--2
TS1--1
J4--11
J4--8
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K5
K5
+24 VDC
J4--9
K3
K5
BUCKY EXP
BUCKY 1 DR CMD
NOTE 1: Be sure that B2 terminal is
not connected to B3 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and C2=470 nF, 250 VAC as shown. Don’t add that R2--C2 for Liebel--Flarsheim 8000 Series Bucky, and remove resistor R36 and R37 in the INTERFACE CONTROL board.
NOTA 1: Asegurarse que el terminal
B2 no está conectado al B3.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%, y C2=470 nF, 250 VAC según se muestra. Para Bucky Liebel--Flarsheim Series 8000, no añadir esa R2--C2, y quitar las resistencias R36 y R37 en la tarjeta INTERFACE CONTROL.
Interf. board revised
8
Innomed added
7
REV DESCRIPTION ISSUED BY DATE
14/03/08F. GARCIA
09/09/02F. GARCIA
DRAWING
REVISED
NAME DATE
F. GARCIA 15/03/95
A. DIAZ 15/03/95
SEDECAL
SHEET / OF
1/4
Interconnection Cable
Cable de Inerconexión
TABLE BUCKY INTERFACE
INTERFAZ BUCKY MESA
I/F--001
7REV8
Page 88
GENERATOR POWER MODULETABLE
BUCKY LIEBEL (Automatic) BUCKY INNOMED (IBC 430)
Automatic
Bucky
B1
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
B2
B3
B8
B4
ADD
JUMPER
(SEE NOTE 3)
R2
C2
BUCKY 1 MOTION
BUCKY 1 MOTION RTN
BUCKY 1 DR
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--5
TS1--6
TS1--4
TS1--3
TS1--2
TS1--1
J4--11
J4--8
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K5
K5
+24 VDC
J4--9
K3
K5
BUCKY EXP
BUCKY 1 DR CMD
NOTE 1: Be sure that B2 terminal is
not connected to B3 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and C2=470 nF, 250 VAC as shown. Don’t add that R2--C2 for Liebel--Flarsheim 8000 Series Bucky, and remove resistor R36 and R37 in the INTERFACE CONTROL board.
NOTA 1: Asegurarse que el terminal
B2 no está conectado al B3.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%, y C2=470 nF, 250 VAC según se muestra. Para Bucky Liebel--Flarsheim Series 8000, no añadir esa R2--C2, y quitar las resistencias R36 y R37 en la tarjeta INTERFACE CONTROL.
Innomed added7
REV DESCRIPTION ISSUED BY DATE
F. GARCIA
F. GARCIA
14/03/08Interf. board revised8
09/09/02
DRAWING
REVISED
NAME DATE
F. GARCIA 15/03/95
A. DIAZ 15/03/95
SEDECAL
SHEET / OF
2/4
Interconnection Cable
Cable de Inerconexión
TABLE BUCKY INTERFACE
INTERFAZ BUCKY MESA
I/F--001
7REV8
Page 89
GENERATOR POWER MODULETABLE
BUCKY
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
BUCKY ULTRAVIT
1
2
4
(SEE NOTE 3)
R2
7
5
8
C2
ADD
JUMPER
BUCKY 1 MOTION
BUCKY 1 MOTION RTN
BUCKY 1 DR
0VAC
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--5
TS1--6
TS1--4
TS1--3
TS1--2
TS1--1
J4--11
J4--8
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K5
K5
+24 VDC
J4--9
K3
K5
BUCKY EXP
BUCKY 1 DR CMD
NOTE 1: Be sure that 2 terminal is
not connected to 4 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and C2=470 nF, 250 VAC as shown.
NOTA 1: Asegurarse que el terminal 2
no está conectado al 4.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%; y C2=470 nF, 250 VAC según se muestra.
8
Interf. board revised
Innomed added7
REV DESCRIPTION ISSUED BY DATE
F. GARCIA
F. GARCIA
14/03/08
09/09/02
DRAWING
REVISED
NAME DATE
F. GARCIA 15/03/95
A. DIAZ 15/03/95
SEDECAL
SHEET / OF
3/4
Interconnection Cable
Cable de Inerconexión
TABLE BUCKY INTERFACE
INTERFAZ BUCKY MESA
I/F--001
7REV8
Page 90
GENERATOR POWER MODULETABLE
BUCKY
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
BUCKY DONG-- A
5
6
4
(SEE NOTE 3)
R2
C2
2
3
ADD
JUMPER
1
7
BUCKY 1 MOTION
BUCKY 1 MOTION RTN
BUCKY 1 DR
0VAC
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--5
TS1--6
TS1--4
TS1--3
TS1--2
TS1--1
J4--11
J4--8
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K5
K5
+24 VDC
J4--9
K3
K5
BUCKY EXP
BUCKY 1 DR CMD
NOTE 1: Be sure that 6 terminal is
not connected to 4 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and C2=470 nF, 250 VAC as shown.
NOTA 1: Asegurarse que el terminal 6
no está conectado al 4.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%; y C2=470 nF, 250 VAC según se muestra.
F. GARCIA
Innomed added7
REV DESCRIPTION ISSUED BY DATE
F. GARCIA
14/03/08Interf. board revised8
09/09/02
DRAWING
REVISED
NAME DATE
F. GARCIA 15/03/95
A. DIAZ 15/03/95
SEDECAL
SHEET / OF
4/4
Interconnection Cable
Cable de Inerconexión
TABLE BUCKY INTERFACE
INTERFAZ BUCKY MESA
I/F--001
7REV8
Page 91
GENERATOR POWER MODULEVERTICAL BUCKY
BUCKY LIEBEL (Semi--Automatic) BUCKY MIDWEST BUCKY INNOMED (IBC 430)
Semi--Automatic
Bucky
B1
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
B3
B8
B2
(SEE NOTE 3)
R2
C2
B4
BUCKY 2 MOTION
BUCKY 2 MOTION RTN
BUCKY 2 DR
0VAC
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--12
TS1--13
TS1--11
TS1--10
TS1--9
TS1--8
J4--10
J4--7
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K4
K4
+24 VDC
J4--9
K3
K4
BUCKY EXP
BUCKY 2 DR CMD
NOTE 1: Be sure that B2 terminal is
not connected to B3 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and C2=470 nF, 250 VAC as shown. Don’t add that R2--C2 for Liebel--Flarsheim 8000 Series Bucky, and remove resistor R36 and R37 in the INTERFACE CONTROL board.
NOTA 1: Asegurarse que el terminal
B2 no está conectado al B3.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%, y C2=470 nF, 250 VAC según se muestra. Para Bucky Liebel--Flarsheim Series 8000, no añadir esa R2--C2, y quitar las resistencias R36 y R37 en la tarjeta INTERFACE CONTROL.
Innomed added7
REV DESCRIPTION ISSUED BY DATE
F. GARCIA
F. GARCIA
14/03/08Interf board revised8
09/09/02
DRAWING
REVISED
NAME DATE
F. GARCIA 15/03/95
A. DIAZ 15/03/95
SEDECAL
SHEET / OF
1/4
Interconnection Cable
Cable de Inerconexión
VERTICAL BUCKY INTERFACE
INTERFAZ BUCKY VERTICAL
I/F--002
7REV8
Page 92
GENERATOR POWER MODULEVERTICAL BUCKY
BUCKY LIEBEL (Automatic) BUCKY INNOMED (IBC 430)
Automatic
Bucky
B1
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
B2
B3
B8
B4
ADD
JUMPER
(SEE NOTE 3)
R2
C2
BUCKY 2 MOTION
BUCKY 2 MOTION RTN
BUCKY 2 DR
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--12
TS1--13
TS1--11
TS1--10
TS1--9
TS1--8
J4--10
J4--7
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K4
K4
+24 VDC
J4--9
K3
K4
BUCKY EXP
BUCKY 2 DR CMD
NOTE 1: Be sure that B2 terminal is
not connected to B3 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and C2=470 nF, 250 VAC as shown. Don’t add that R2--C2 for Liebel--Flarsheim 8000 Series Bucky, and remove resistor R36 and R37 in the INTERFACE CONTROL board.
NOTA 1: Asegurarse que el terminal
B2 no está conectado al B3.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%, y C2=470 nF, 250 VAC según se muestra. Para Bucky Liebel--Flarsheim Series 8000, no añadir esa R2--C2, y quitar las resistencias R36 y R37 en la tarjeta INTERFACE CONTROL.
F. GARCIA
F. GARCIA
REV DESCRIPTION ISSUED BY DATE
14/03/08Interf board revised8 09/09/02Innomed added7
DRAWING
REVISED
NAME DATE
F. GARCIA 15/03/95
A. DIAZ 15/03/95
SEDECAL
SHEET / OF
2/4
Interconnection Cable
Cable de Inerconexión
VERTICAL BUCKY INTERFACE
INTERFAZ BUCKY VERTICAL
I/F--002
7REV8
Page 93
GENERATOR POWER MODULEVERTICAL BUCKY
BUCKY
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
BUCKY ULTRAVIT
1
2
4
(SEE NOTE 3)
R2
7
5
8
C2
ADD
JUMPER
BUCKY 2 MOTION
BUCKY 2 MOTION RTN
BUCKY 2 DR
0VAC
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--12
TS1--13
TS1--11
TS1--10
TS1--9
TS1--8
J4--10
J4--7
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K4
K4
+24 VDC
J4--9
K3
K4
BUCKY EXP
BUCKY 2 DR CMD
NOTE 1: Be sure that 2 terminal is
not connected to 4 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and C2=470 nF, 250 VAC as shown.
NOTA 1: Asegurarse que el terminal 2
no está conectado al 4.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%; y C2=470 nF, 250 VAC según se muestra.
F. GARCIA
F. GARCIA
REV DESCRIPTION ISSUED BY DATE
14/03/08Interf board revised8 09/09/02Innomed added7
DRAWING
REVISED
NAME DATE
F. GARCIA 15/03/95
A. DIAZ 15/03/95
SEDECAL
SHEET / OF
3/4
Interconnection Cable
Cable de Inerconexión
VERTICAL BUCKY INTERFACE
INTERFAZ BUCKY VERTICAL
I/F--002
7REV8
Page 94
GENERATOR POWER MODULEVERTICAL BUCKY
BUCKY
EXP INT
(SEE NOTE 1)
BUCKY START
(SEE NOTE 2)
BUCKY DONG-- A
5
6
4
(SEE NOTE 3)
R2
2
3
1
7
C2
ADD
JUMPER
BUCKY 2 MOTION
BUCKY 2 MOTION RTN
BUCKY 2 DR
0VAC
115/220 VAC
GND
INTERFACE PANEL
Interface Control Board
+24 VDC
TS1--12
TS1--13
TS1--11
TS1--10
TS1--9
TS1--8
J4--10
J4--7
0VAC
ADD JUMPER
BUCKY SPLY
ADD JUMPER TO
TS1--27for115VAC
{
TS1--26 for 220 VAC
K4
K4
+24 VDC
J4--9
K3
K4
BUCKY EXP
BUCKY 2 DR CMD
NOTE 1: Be sure that 6 terminal is
not connected to 4 terminal.
NOTE 2: Select correct voltage in the
bucky according to AC input
NOTE 3:
In the case of noise due to Bucky, add R2=22 ohm, 1/2w, 5%; and C2=470 nF, 250 VAC as shown.
NOTA 1: Asegurarse que el terminal 6
no está conectado al 4.
NOTA 2: Seleccionar la tensión del
bucky según la entrada AC
NOTA 3:
En caso de ruidos debido al Bucky, añadir R2=22 ohm, 1/2w, 5%; y C2=470 nF, 250 VAC según se muestra.
F. GARCIA
F. GARCIA
REV DESCRIPTION ISSUED BY DATE
14/03/08Interf board revised8
09/09/02Innomed added7
DRAWING
REVISED
NAME DATE
F. GARCIA 15/03/95
A. DIAZ 15/03/95
SEDECAL
SHEET / OF
4/4
Interconnection Cable
Cable de Inerconexión
VERTICAL BUCKY INTERFACE
INTERFAZ BUCKY VERTICAL
I/F--002
7REV8
Page 95
GENERATOR POWER MODULE
CONSOLE
TS1
42 16 15 17
18
J5
5 7
1
6 2 8 3 4 9
POWER INTERFACE Cable
IC GND
–12 VDC
+12 VDC
+24 VDC
GND
jumper
AEC INTERFACE Cable
GND IC4 INPUT IC1 INPUT IC2 INPUT IC3 INPUT
–FLD 2 DR –FLD 1 DR –FLD 3 DR –STRT DR
Shield
TB1
9 1 2 3 4 8
5 6 7
10
J4
5 7 1 6 2 8 3 4 9
C5
0.1 uF
RP1
TP6
10K
IC4
56
R4 1K
7
C8
0.1 uF
JP12
BA
C6 100uF 35V
TP3
ST
R13
10K
CR2
1N4148
CR3
1N4148
CR4
1N4148
CR1
1N4148
LF347
U1
+
6 1
13
6 1
13
6 1
13
6 1
13
K10
K11
K12
K9
6
5
7 8
RP2 10K
65
RP2
10K
78
RP1
10K
8
8
8
8
+12 VDC
IC4 OUT
JUMPERS JP9, JP10, JP11, JP12 POS. A – NO OFFSET ADJUSTMENT
POS. B – OFFSET ADJUSTMENT
R6 3K01
R5 1K
FLD2–IC1
FLD1–IC1
FLD3–IC1
STRT–IC1
TP1
IC1
AEC ADAPTATION BD. ( A3263–03 )
+12 VDC
RP3 10K
9
65
U1
RP3
LF347
10K
10
+
7
78
RP4
10K
8
IC1 OUT
K6
JP8
A
6 1
B
13
K7
JP4
A
6 1
B
13
K8
JP7
A
6 1
B
13
K5
JP3
A
6 1
B
13
Ion Chamber Jumpers
Type
R10 1K
C10
0.1 uF
BA
RP4 10K
56
8
JP9
IC1=IC2=IC3=IC4
IC1=IC2=IC3
IC1=IC2
//
/
IC1=IC2=IC3=IC4
R12 3K01
R11 1K
8
8
8
8
RP4
TP2
IC2
10K
12
R9
1K
14
C9
0.1 uF
JP10
BA
FLD2–IC2
FLD1–IC2
FLD3–IC2
STRT–IC2
JP3,JP4,JP7,JP8
+12 VDC
RP3
10K
13
21
U1
RP3
LF347
10K
12
+
3
34
RP4
10K
4
JP6
A B
JP2
A B
JP5
A B
JP1
A B
Jumpers
JP1,JP2,JP5,JP6
IC2 OUT
6 1
13
6 1
13
6 1
13
6 1
13
BB B B
B A
AA
R7 3K01
R8 1K
K2
8
K3
8
K4
8
K1
8
JP13, JP14, JP15, JP16
+12 VDC
– U1 LF347
+
–12 VDC
IC3
FLD2–IC3
FLD1–IC3
FLD3–IC3
STRT–IC3
Jumpers
4
11
TP4
R3
1K
C7
0.1 uF
BA
B A A A
10K
12
1
JP11
RP1
C1
0.1 uF
C2
0.1 uF
LF347
J1
IC1 OUT
+12 VDC
–12 VDC
FLD2–IC1 FLD1–IC1 FLD3–IC1
STRT–IC1
IC2 OUT FLD2–IC2 FLD1–IC2 FLD3–IC2 STRT–IC2
IC3 OUT FLD2–IC3 FLD1–IC3 FLD3–IC3 STRT–IC3
IC4 OUT
TP5 GND
J2
J3
J5
C3 100uF 35V
C4
100uF
35V
+12 VDC
R1
RP2
3K01
10K
2
R2
21
+
3 3
4
JP14
JP16
JP15
JP13
RP2
10K
34
RP1 10K
A B
A B
A B
A B
1K
IC3 OUT
K15
6 1
13
K14
6 1
13
K13
6 1
13
K16
6 1
13
8
8
8
8
U1
1 7 8 9 5 3 2 6 4
1 7
8 9 5 3 2 6 4
1 7 8 9 5 3 2 6 4
1 7 8 9 5
3 2 6 4
ION CHAMBER Cable
–12 VDC +12 VDC
GND
IC1 OUTPUT
CENTER AREA
LEFT AREA
RIGHT AREA
RESET
Screen
ION CHAMBER Cable
–12 VDC +12 VDC
GND
IC1 OUTPUT
CENTER AREA
LEFT AREA
RIGHT AREA
RESET
Screen
ION CHAMBER Cable
–12 VDC +12 VDC
GND
IC1 OUTPUT
CENTER AREA
LEFT AREA
RIGHT AREA
RESET
Screen
ION CHAMBER Cable
–12 VDC +12 VDC
GND
IC1 OUTPUT
CENTER AREA
LEFT AREA RIGHT AREA
RESET
Screen
ION CHAMBER #1
1 7 8 9 5 3 2 6 4
ION CHAMBER #2
1 7 8 9 5 3 2 6 4
ION CHAMBER #3
1 7 8 9 5 3 2 6 4
ION CHAMBER #4
1 7 8 9 5 3 2 6 4
Preamplifier
Preamplifier
Preamplifier
Preamplifier
Note.– Compatible interface with preamplifier for Ion Chamber types : – Expos–AID – Vacutec 70145/70151 – Comet Ion Chambers with PA–021 Preamplifier
A Version 03 F. GARCIA 10/10/99
REV DESCRIPTION ISSUED BY DATE
DRAWING
REVISED
NAME DATE
F. GARCIA 07/08/96
A. DIAZ 10/10/96
SEDECAL
SHEET / OF
1 / 1
DWG:
IM–015
A REV
AEC – AID / VACUTEC / COMET COMPATIBILITY
Page 96
--
FIELDSEL3
FEDC B A
TB1
COMM
-- 1 2 V D C
+12 VDC
+24 VDC
4
RELAY 4
RELAY 3
RELAY 2
RELAY 1
GND
GND
IC4 INPUT
IC1 INPUT
IC2 INPUT
IC3 INPUT
-- F L D 2 D R
3
-- F L D 1 D R
-- F L D 3 D R
-- S T RT D R
C5
0.1 uF
2
10K
1
Ion Chamber Jumpers
Typ e
IC1=IC2=IC3=IC4
IC1=IC2=IC3
IC1=IC2
/
//
IC1=IC2=IC3=IC4
1
2
3
4
8
5
6
J4
7
--
+
6
65
5
7
78
RP1 10K
8
RP2
10K
RP2 10K
+12 VDC
R6 3K01
R5
1K
IC4 OUT
RP1
9
10
5
7
1
TP6
IC4
R4 1K
7
C8
0.1 uF
JP12
BA
10K
56
U1
LF347
TP1
R10 1K
8
C10
0.1 uF
JP9
BA
RP4 10K
6
5
U1
LF347
IC1
--
+
9
65
10
78
7
RP4
8
10K
RP3 10K
RP3
10K
+12 VDC
R12
3K01
R11
1K
IC1 OUT
6
2
8
3
4
9
JP8
JP4
JP7
JP3
K6
A
6
B
A
B
A
B
A
B
1
13
8
K7
6
1
13
8
K8
6
1
13
8
K5
6
1
13
8
R13
TP3
C6 100uF 35V
ST
CR2
1N4148
CR3
1N4148
CR4
1N4148
CR1
1N4148
K10
1
6
8
13
K11
6
13
K12
6
13
K9
6
13
FLD2--IC1 FLD2--IC2
1
8
FLD1--IC1
1
8
FLD3--IC1
1
8
STRT-- IC1
JUMPERS JP9, JP10, JP11, JP12
POS. A -- NO OFFSET ADJUSTMENT POS. B -- OFFSET ADJUSTMENT
JP3,JP4,JP7,JP8
Jumpers
JP1,JP2,JP5,JP6
BB
B
B
B
A
AA
FE
Jumpers
JP13, JP14, JP15, JP16
B
A
A
A
REV DESCRIPTION ISSUED BY DATE
D
FLD1--IC2
FLD3--IC2
STRT-- IC2
-- 1 2 V D C
IC1 OUT
FLD2--IC1
FLD1--IC1
FLD3--IC1
STRT-- IC1
GND
IC2 OUT
FLD2--IC2
FLD1--IC2
FLD3--IC2
STRT-- IC2
IC3 OUT
FLD2--IC3
FLD1--IC3
FLD3--IC3
STRT-- IC3
IC4 OUT
TP5
+12 VDC
4
-­U1
LF347
+
11
TP2
R9
1K
14
C9
0.1 uF
JP10
BA
RP4 10K
2
1
U1
LF347
JP6
IC2
JP2
JP5
JP1
--
+
A
B
A
B
A
B
A
B
13
12
3
4
RP3 10K
21
RP3 10K
34
RP4
10K
K2
6
13
K3
6
13
K4
6
13
K1
6
13
+12 VDC
R7 3K01
R8
1K
IC2 OUT
1
8
1
8
1
8
1
8
-- 1 2 V D C
TP4
IC3
BA
FLD2--IC3
FLD1--IC3
FLD3--IC3
STRT-- IC3
R3 1K
C7
0.1 uF
JP11
12
1
RP1 10K
C2
0.1 uF
U1
LF347
--
+
2
3
3
4
C1
0.1 uF
JP14
JP16
JP15
JP13
21
34
RP1 10K
RP2 10K
RP2
10K
A
B
A
B
A
B
A
B
C4 100uF 35V
+12 VDC
R1 3K01
R2 1K
IC3 OUT
K15
6
13
K14
6
13
K13
6
13
K16
6
13
C3 100uF 35V
8
1
8
+12 VDC
1
8
1
8
1
Note.-- Version 03 as CN 99/45
DRAWING
REVISED
NAME DATE
F. GARCIA 07/07/99
A. DIAZ 07/07/99
SEDECAL
SHEET / OF
1/1
DWG:
A3263--03
AEC ADAPTATION
ADAPTACION AEC
J1
1
COMM
7
-- 1 2 V D C
8
+12 VDC
9
GND
5
IC1 OUTPUT
3
CENTER AREA
2
LEFT AREA
6
RIGHT AREA
4
--RESET
J2
1
COMM
7
-- 1 2 V D C
8
+12 VDC
9
GND
5
IC2 OUTPUT
3
CENTER AREA
2
LEFT AREA
6
RIGHT AREA
4
--RESET
J3
1
COMM
7
-- 1 2 V D C
8
+12 VDC
9
GND
5
IC3 OUTPUT
3
CENTER AREA
2
LEFT AREA
6
RIGHT AREA
4
--RESET
J5
1
COMM
7
-- 1 2 V D C
8
+12 VDC
9
GND
5
IC4 OUTPUT
3
CENTER AREA
2
LEFT AREA
6
RIGHT AREA
4
--RESET
4
3
2
1
REV
Page 97
Technical Publication
DB-1004R4
Data Book
HF Series Generators
Page 98
REVISION DATE REASON FOR CHANGE
0 APR 1, 2001 First edition
1 FEB 10, 2003 Documentation update
2 JAN 25, 2005 Documentation update
3 NOV 2, 2004 Documentation update
HF Series Generators
Data Book
4
This Document is the English original version, edited and supplied by the manufacturer.
The R evision state of this Document is indicated in the code number shown at the bottom of this page.
OCT 26, 2006 Extended Memory Locations
ADVISORY SYMBOLS
The following advisory symbols will be used throughout this manual. Their application and meaning are described below.
DANGERS ADVISE OF CONDITIONS OR SITUATIONS THAT IF NOT HEEDED OR AVOIDED WILL CAUSE SERIOUS PERSONAL INJURY OR DEATH.
ADVISE OF CONDITIONS OR SITUATIONS THAT IF NOT HEEDED OR AVOIDED COULD CAUSE SERIOUS PERSONAL INJURY, OR CATASTROPHIC DAMAGE OF EQUIPMENT OR DATA.
DB-1004R4
Advise of conditions or situations that if not heeded or avoided could cause personal injury or d amage to equipment or data.
Note . Alert readers to pertinent facts and conditions. Notes represent
information that is important to know but which do not necessarily relate to possible injury or damage to equipment.
Page 99
HF Series Generators
Data Book
TABLE OF CONTENTS
Section Page
1 INTRODUCTION 1.........................................................
1.1 Installation Data 1....................................................
1.2 Maintenance History 2................................................
2 DATA TABLES 3..........................................................
DB-1004R4
i
Page 100
HF Series Generators
Data Book
ii
DB-1004R4
Loading...