No part of this document is to be reproduced or utilized in any form or by any
means without the written consent of KEYENCE Corporation.
The contents of this document are subject to revision without notice.
If you have any problems or questions regarding this document, please contact
one of the KEYENCE offices listed on the last page of this document.
KEYENCE is not responsible for any results of the application of the product.
If the document contains incomplete printing, it can be exchanged for a complete
one.
• MS-DOS is a registered trademark of Microsoft U. S. A.
• MS-Windows is a trademark of Microsoft U. S. A.
• Other company names and product names are registered trademarks or trademarks of the respective companies.
Wire colors and signal types ............................................................................................................................2
Power supply wiring .........................................................................................................................................2
Preset Function (Compare with:) ...................................................................................20
What is the preset function? ........................................................................................................................... 20
Wildcard symbols (“!” and “?”) ........................................................................................................................20
Additional Information ....................................................................................................21
Max. Code Length (Designated Digit )
Output Function ...............................................................................................................23
Chapter 3: Setup Software
Controlling the BL-180 ....................................................................................................26
Outline of Operation ....................................................................................................................................... 28
Main setting screen ........................................................................................................................................ 32
Communication setting .................................................................................................................................. 38
Communication strings setup ......................................................................................................................... 38
Other setting .................................................................................................................................................. 39
Version Display .............................................................................................................................................. 40
List of Error Messages ................................................................................................... 41
How to Use Terminal Software ...................................................................................... 42
Chapter 4: Serial Communication (RS-232C/RS-422A)
Serial Communication .................................................................................................... 46
Communication Setup .................................................................................................................................... 46
Details on Data Communication .................................................................................... 47
Communication Protocols(Hardware handshaking) ....................................................................................... 47
Capacity of Transmission Buffer .................................................................................................................... 48
Read Data Format ......................................................................................................................................... 48
System Configuration ..................................................................................................... 79
Using the RS-232C and RS-422A ................................................................................................................. 79
Using the RS-485 multidrop link .................................................................................................................... 79
Other Options ................................................................................................................................................. 79
Connecting the AC power supply ................................................................................................................... 81
Connecting the BL-U1 to a BL series ............................................................................................................. 81
Page 5
v
Setting the BL-U1 DIP switches ..................................................................................................................... 82
Function and wiring on the I/O terminal block ................................................................................................ 83
RS-232C port pin assignment ........................................................................................................................ 84
RS-232C port wiring .......................................................................................................................................85
RS-422A port wiring ....................................................................................................................................... 85
Wiring the RS-485 (multidrop link) .................................................................................................................86
Precautions before use ..................................................................................................................................87
Installing the BL-U1 ........................................................................................................................................88
Outline of Multidrop Link ................................................................................................89
Multidrop Link .................................................................................................................................................89
System Configuration .....................................................................................................................................89
Setup and Connection Procedures ................................................................................90
Communication ................................................................................................................91
Outline of Communication types ....................................................................................................................91
Communication Format ..................................................................................................................................91
Details on Data Communication ..................................................................................................................... 93
Details of Command Communication ............................................................................................................. 95
Precautions for Programming ........................................................................................97
Thank you for choosing the BL-180 series CCD bar-code reader . This User’s Manual describes details on operations and functions of the BL-180. Read this manual
carefully to maximize the BL-180 performance.
There are two packages: A BL-180 package and a software package.
Each package contains the following components. Be sure to check the items
Setup software floppy disk (3.5-inch)1
User’s Manual (this document)1
Note
The setup software and user’s manual are not included in the BL-180 package.
You can order the software package, free of charge, separately.
Safety Precautions
Be sure to observe the following precautions when using this unit:
• Do not use the BL-180 as a controller for equipment which could potentially
harm a person.
• Be sure to match the polarities (+ and -) of the power supply when soldering
the connections. Reversing the polarities will damage the unit.
• Do not disassemble the BL-180. Doing so may make repair impossible.
• This is a precision instrument. Dropping the unit could damaged it. Exercise
caution when moving or installing.
• For shipping, a protective seal covers the optical pickup. Remove this before
use.
• Be sure that there is no water, oil or dust on the optical pickup. Such obstructions can cause read errors. Clean the pickup by gently wiping with a soft lens
cloth soaked with water.
Conventions
This document uses the following conventions to help you easily recognize important and useful information.
CAUTION
Note
vi
Important information which must be read to avoid damaging the unit.
Provides information for effective use of the unit. Read as required.
Any reference to the BL-180 in this manual refers to information on all products in
the BL-180 series. When refering to specific product information, the product
name exclusively will be used.
Page 7
System Configuration
Note
BL-180/185
5VDC
Power-supply unit*
Trigger input
Timing sensor
RS-232C null modem cable
OP-22149 (1.5 m) + OP-25057
(25- to 9-pin adapter)
RS-232C
OK/NG
output
PLC etc.
BL-18H1E
Setup software
3.5-inch version
WINDOWS 3.1
The 5 VDC power supply unit must be purchased separately.
The optional BL-U1 or BL-U2 power supply is also available.
IBM PC/AT
or compatible
Parts and Functions
BL-180
OK/NG
STABILITY
BL-180
OK output: Lights in green.
NG output: Lights in red.
STABILITY LED
Indicates reading stability
(see P. 31).
Cable (2 m)
Light source/optical
pickup
Light source LED
Lights during reading
vii
Page 8
viii
Page 9
Chapter 1
Connection and Installation
Page 10
5VDC
BL-180
+5V
Red
GND
Black
+
1.1 BL-180 Connections
1.1BL-180 Connections
1.1.1
1.1.2
Wire colors and signal types
The following wires extend from the BL-180. Solder the required wires to a connector to connect the BL-180 to a computer/controller.
Wire Color
Shield
PurpleRSBrownRD (RXD) Receive dataInput
PinkRS (RTS) Request to send (always on)Output
BlueCS (CTS) Request to receiveInput
BlackGND (SG)
YellowTIMTrigger inputInput
WhiteOKOK outputOutput
GrayNGNG outputOutput
Red+ 5V+ 5V power supply inputInput
SymbolDescriptionSignal Direction
ShieldConnect to ground (SG)——
232C
Power supply wiring
SD (TXD) Send dataOutput
Ground (common ground for
respective signals)
——
1.1.3
CAUTION
Wiring I/O
• Be sure to match the polarities of the power supply when soldering the connections. Reversing the polarities will damage the unit.
• Make sure that the power supply provides a stable 5 VDC ± 5%. If the power
supply does not function in the above range, it can damage the unit.
• Do not use a power cable longer that 2 meters. A long power cable can cause
a voltage drop, preventing the BL-180 from starting properly.
• If the power supply is UL rated, it must provide Class 2 output.
Trigger (TIM) input
The trigger input is used to signal the BL-180 to start reading (Start laser emission).
The trigger input is a non-voltage input (TTL input is also available).
BL-180
10KΩ
Internal circuit
5VDC
4.7
KΩ
TIM
GND
Yellow
Black
With or
without relay
2
Page 11
3
1.1 BL-180 Connections
OK/NG output
This output signals whether the readout data is the same as the preset data.
When no preset data has been registered, the signal indicates bar code read status. It is an NPN open-collector output.
BL-180
1.1.4
RS-232C Connections
Note
This BL-180 setup software applies to port 1 and port 2 only.
Communication cannot be performed with another port.
When using a D-sub 9-pin connector:
OK/NG
1kΩ
Internal circuit
BL-180
ShieldConnector case
Shield
Purple
SD
Blown
RD
Blue
CS
Pink
RS
Black
GND
Red
+5V
+
5VDC
Write/Gray
Black
GND
*Rated load: 24 VDC
(100 mA) max.
PC
–
2
3
7
8
5
4
6
D-sub 9-pin (male)
# 4-40 screw
Load
+
RD
SD
RS
CS
SG
DR
ER
Note
Use a metallic connector housing for the D-sub 9-pin connector. Connect the
shielded cable with the connector housing.
When using a D-sub 25-pin connector:
BL-180
ShieldFG
Shield
Blown
RD
SD
Purple
Blue
CS
Pink
RS
Black
GND
Red
+5V
+
5VDC
PC
1
2
SD
3
RD
4
RS
5
CS
7
SG
6
DR
20
ER
D-sub 25-pin (male)
M 2..6 screw
Be sure the BL-180’s shielded cable is properly connected. Refer to “1.1.3 Connecting shielded cables” in the User’s Manual.
Page 12
1.1 BL-180 Connections
Hints on correct use
Trigger (TIM) input
Set the trigger input to be long enough to allow the laser beam to cover the entire
bar code.
If the trigger input needs to be on for only a short period of time, select one-shot
mode.
Influence from mirror surface
If a mirror surface (metallic surface) is near the bar code and the laser beam reflects off the mirror, the BL-180 may cause a read error. Protect the unit from the
influence of a mirror surface by covering the surface or changing the bar code label position.
Bar code pitch
Do not place several bar codes in the field of the laser beam, unless you are in
multi-label read mode (Multi 3).
OK/NG
STABILITY
BL-180
If you use multi-label read mode (multi 3), the BL-180 can simultaneously read 2
to 4 bar codes in the field of the laser beam.
Influence from photoelectric sensor
When using a photoelectric sensor to control trigger, block the sensor beam so it
does not enter the BL-180 optical pickup.
The beam from the photoelectric sensor can interfere with the BL-180, deteriorating reading performance. If this case, reposition the photoelectric sensor.
Object
Bar code
OK/NG
STABILITY
BL-180
Light
source
Optical
pickup
4
Page 13
5
1.1 BL-180 Connections
Bar code height
The bar code height must be at least 3 mm. However, adjust any bar code of 3
mm or more height so that it is arranged from one end to the other on the lightreceiving axis.
3 mm or more
Lightreceiving
axis
Page 14
M3 screws
M3 screws
M3 screws
1.2 Installing the BL-180 Series
1.2Installing the BL-180 Series
Installation method
Use the mounting holes on the side panel to install the unit. To prevent dust from
entering the unit, seals have been placed over the screw holes. Remove the seals
before mounting.
Using the supplied mounting brackets
Install the BL-180 Series as shown in the figures below.
BL-180 pattern 1BL-180 pattern 2
(BL-185)
• Select screws of the proper length by checking the thickness of the plate used
for mounting. (The screws provided are for use with the mounting bracket.)
• For the mounting hole diameter, see page 65.
Installation with no mounting bracket
(BL-180)(BL-185)
• Prepare M3 male screws separately.
• Although the mounting holes are on both sides of the unit, only one side should
be mounted.
• For the mounting hole diameter, see page 65.
CAUTION
6
Do not insert screws into the BL-180 by 5 mm or deeper. Doing so may damage
the unit parts.
Select screws of the proper length by checking the thickness of the plate used for
mounting.
Page 15
Mounting angle and mounting distance
BL-180
BL-180
1.2 Installing the BL-180 Series
12.5
15.3
10°
Note
33
BL-185
Set the angle and reading distance by referring to the read range characteristics
and angle characteristics described on page 63 and 64.
The allowable reading distance and angle may vary depending on the narrow bar
width of the bar code, the bar code size, and the readability of the bar code. Set
these parameters after performing a test read of the required bar code using the
unit.
Do not set the unit at an angle at which the light-receiving axis is perpendicular to
the surface of the bar code. The beam will be fully reflected into the reader, making correct reading impossible (see page 64).
Set the angle so that the light-receiving axis will be centered on the bar codes.
Bar codes of insufficient height may deviate from the desired position in relation
to the light-receiving axis. Be sure to position the unit carefully. (The bar codes
must have a height of at least 3 mm.)
The reading check test mode (see page 17) allows you to set the optimal reading
position.
Light-receiving axis
7
Page 16
1.2 Installing the BL-180 Series
8
Page 17
Chapter 2
Functions for Reading Operation
Page 18
Trigger input
Bar code
LED beams
Communication time
OK/NG outputOK/NGNG
<Succeed to read><Fail to read>
*2
*1
*3
*4
*5
Data bits + (1: If parity is used) + Start/stop bit
Baud rate
(code length of data to be sent + Header/
number of characters in delimeter)
X
2.1 Read Operation
2.1Read Operation
2.1.1
Scanning method
Level signal trigger
There are two methods for triggering the BL-180 to read bar codes; the “Level signal” method and the “One-shot signal” method. The example given for these two
methods uses the “single label read mode” (see page 12), which reads one bar
code while trigger input turns on once, and uses the “after read” as the data-send
mode (see page 11).
When the trigger input turns on, LED emission begins and the the unit begins
reading. The LED turns off after reaching the specified decode count. Then, the
unit sends the readout data.
1. Set trigger input so that it stays on long enough for the LED beam to cover
the entire bar code.
2. After the trigger input exceeds the preset input time, the LED begins to emit.
3. The communication time can be obtained from the following expression:
4. The length of time that the OK/NG output is on can be changed to between
10 ms and 2.55 s.
5. The OK/NG output turns on 5 ms after the data has been read (or trigger
input turns off in case of reading failure).
10
Page 19
One-shot signal trigger
2.1 Read Operation
The unit detects the rising edge of the trigger input and starts reading bar codes
for the preset input time. The LED beam turns off after reaching the specified decode count and the unit sends the readout data.
The remaining actions are the same as those for level signal trigger.
<Succeed to read><Fail to read>
Trigger input
*1
2.1.2
Bar code
LED beams
Communication time
OK/NG output
1. After the trigger input exceeds the preset input times, the LED begins to emit.
Note
• The BL-180 can read up to 4 types of bar codes without changing the bar code
type setting (see page 32).
• For general operation, see "Level signal trigger"
• Choose “One-shot signal trigger” when the trigger input signal is very short or
you want to set the input time.
Data-send mode
In the single label read mode only, you can select from the two data send modes
(OK/NG output on trigger) described below: In the multi-label read mode, you can
only select the “send after reading” mode.
Send after read
The unit outputs the communication and OK/NG signals after a sucessful read
(trigger output turns on as many times as the preset decode count). This is the
same operation as in the time chart described in “1.1 Scanning method”. Normally, this is the method you should use.
Preset input time
OK/NGNG
Preset input time
Send at trigger input
The unit outputs the communication and OK/NG signal when the trigger input
turns off (or the preset input time has passed if one-shot signal trigger is selected).
OK/NG
<Fail to read>
NG
<Succeed to read>
Trigger input
Bar code
LED beams
Communication time
OK/NG output
11
Page 20
Repeat reading time
OK
NG
<Succeed to read><Fail to read>
Trigger input
Bar code
LED beams
Communication time
OK/NG output
OKOKOK
2.2 Read modes
2.2Read modes
The BL-180 provides 4 types of read modes.
2.2.1
2.2.2
Single label read mode
This mode allows the unit to read one bar code during one trigger input signal.
The operation and timing chart are described on page 10.
Multi-label read mode 1 (Multi 1)
This mode allows the unit to read several bar codes printed on one label as shown
below during one trigger input signal. The unit outputs the readout data sequentially.
Multi-label read mode 1 operation
In the multi-label read mode 1, the unit reads several bar codes continuously, and
outputs them sequentially as it reads while LED beam remains on and trigger input turns on after bar codes have been read (or during the preset input time if oneshot signal trigger is selected).
To prevent the unit from reading the same bar code twice, the time for one bar
code to pass across the LED beam’s field and read, plus the repeat reading time
must be set (100 ms to 25.5 s). During the repeat reading time, the unit cannot
read the same bar code repeatedly, but can read different bar codes.
A reading error is issued only when the unit cannot read any bar code while the
trigger input is on.
For OK/NG output, “OK” turns on every time the unit reads a bar code and “NG”
turns on if the unit fails to read a bar code. (Comparison to the preset data is not
performed.)
12
Page 21
2.2 Read modes
2.2.3
Multi-label read mode 2 (Multi 2)
As with multi 1 mode, this mode allows the unit to read several bar codes continuously while the trigger input is on. (The number of bar codes that can be read
depends on the buffer capacity. See page 48.) The difference between the two
modes is that multi 2 modesends all the readout data at one time after the trigger
input turns off.
Multi-label read mode 2 operation
<Succeed to read><Fail to read>
Trigger input
Bar code
LED beams
Communication time
OK/NG output
Multi 2 mode allows the unit to read several bar codes while the trigger input is on
(or during the preset input time if one-shot signal trigger is selected) and sends all
the readout data at one time after the trigger input turns off (or after the preset
input time is expired if one-shot signal trigger is selected).
To prevent the unit from reading the same bar code twice, the time for one bar
code to pass across the LED light’s field and read, plus the repeat reading time
must be set. During the repeat reading time, the unit cannot read the same bar
code repeatedly, but can read different bar codes.
For OK/NG output, after trigger input turns off, “OK” turns on if the unit reads at
least one bar code and “NG” turns on if the unit fails to read a bar code. (Comparison to the preset data is not performed.)
12345
Repeat reading
time
12345
OK
NG
Reading data format
2.2.4
Multi-label read mode 3 (Multi 3)
Header
Each data packet is separated by a comma (, : 2CH) (intermediate delimiter).
The unit sends as many data packets the number of bar codes read.
See page 46 for “header string” and “delimeter”.
As described in multi-label read modes 1 and 2, this mode also allows the unit to
read several bar codes (up to 4 codes) while the trigger input is on.
The unit sends the readout data at one time according to a specified sequence
after the trigger input turns off. When up to 4 codes are in the LED beam’s field,
the unit can simultaneously reads all of them.
1st
data
2nd
,
data
3rd
,
data
4th
,
data
,Delimeter
13
Page 22
OK
Trigger input
Bar Code
LED beams
Communication time
OK/NG output
Code 1 Code 2 Code 3 Code 4
Code 1
Code 2
Code 3
Code 4
NG
2.2 Read modes
Operation of multi-label read mode 3
This mode allows the unit to continuously read each one of 4 bar code types
“Code 1”, “Code 2”, “Code 3”, and “Code 4” as specified in the “code setup” of the
setup software (see page 32). If 3 types are specified in the “code setup”, the unit
reads 3 bar codes (each of 3 types). If 2 types are specified, the unit reads 2 bar
codes.
The following time chart is given.
The above example chart is with all four codes specified in the “code setup” of the
setup software.
• The bar code reading sequence is not fixed.
• The unit communicates the readout data in the order of Code 1 to Code 4.
After the trigger input turns off, the unit sends all the data at one time.
• For OK/NG output, “OK” turns on if the unit reads all the specified Codes 1 to 4
and “NG” turns on if the unit fails to read at least one bar code. (Comparison to
the preset data is not performed.)
Reading data format
Example Suppose that the following codes are specified:
Header
Data read
from Code
1
Data read
from Code
,
Data read
from Code
2
,
3
Data read
from Code
,
4
,Delimeter
• Each data packet is separated by a comma (, : 2CH) (intermediate delimiter).
• If an read error occurs on any one of Codes 1 to 4, or the corresponding bar
code does not exist, “ERROR” (see page 49 for the reading error codes),
instead of the read data is sent.
• See page 48 for “header string” and “delimeter”.
The unit cannot read the bar code having the same content twice while trigger input turns on once.
ABCD123,XYZ3333,1234567,KEYENCE,Delimeter
Page 24
OK/NG
NG
<Specified orientation>
<Non-specified orientation>
Trigger input
Bar code
LED beams
Communication time
OK/NG output
2.3 Label orientation mode
2.3Label orientation mode
As shown below, this mode allows the unit to read bar codes only in the specified
orientation when bar code labels are moving both in the forward and reverse orientations.
Forward orientation Reverse orientation
4 9000000
4 9000000
OK/NG
STABILITY
BL-180
Normally, the unit can read bar codes regardless of the orientation.
An reading error is issued when the unit reads a bar code label running in the orientation which is not specified.
The above chart applies to the single label read mode. You can also use this
mode together with the desired multi-label read mode. However, in any case, the
unit reads bar codes running in the specified orientation only.
You can specify the orientation individually for Codes 1 to 4, such as specifying
“forward orientation” for Code 1, and “reverse orientation” for Code 2.
16
Page 25
2.4Test Mode
2.4 Test Mode
Test mode can be used for the bar code reading test. Because trigger input is not
required, this mode allows you to perform a reading test easily. You can select
one of the following 3 methods to enter the test mode.
Send the command
Enter test mode by sending the serial command for the test mode (TEST1,
TEST2). Commands should be entered in all uppercase characters.
Turning on trigger input
You can use the BL-180 to switch to test mode by turning on the trigger input (see
page 35). If you select this method to enter the test mode, trigger input is disabled
to ensure normal operation.
Turning on power supply
You can set the BL-180 to enter test mode by turning on the power supply (see
page 37).
Note
When you try to enter the test mode by turning on trigger input, you cannot use
the serial command to enter the test mode.
The following 2 types of test modes are available:
Reading rate check mode
The unit scans a bar code100 times and analyzes how many times it can decode
the scanned data (reading rate). This mode is useful in the following cases:
• When adjusting the mounting distance and angle
• When verifying the reading stability of the bar code to be used
• The analyzed result will be output anytime (every 100 scans) using the follow-
ing format:
• Although an OK/NG signal is not output, the OK/NG LED lights (see page 19).
Tact check mode
In this test mode, the unit counts how many scans can be decoded (the decode
count) while reading one bar code.
This mode is useful when testing which line speed can be expected when actually
implementing the BL-180 system on the line.
• The analyzed data is output using the following format 0.2 seconds after the
bar code has passed the LED beam’s field.
Readout data
Delimiter
:m%
m = 0 to 100 (zero-suppressed)
Readout data
• The unit continues to read a bar code while the code is in the LED beam’s field
and does not output the result. If the LED beam does not detect a bar code for
0.2 seconds, the unit stops scanning and outputs the result.
• If the unit reads the same bar code twice within the 0.2 seconds, the unit cannot separate the bar codes and will add to the read count. However, the unit
can continuously reads different bar codes within the 0.2 seconds by recognizing the delimiter.
Delimiter
:m
m = 1 to 999 (zero-suppressed)
17
Page 26
2.4 Test Mode
18
• The read count can be up to 9999.
• Although an OK/NG signal is not output, the OK/NG LED lights (see page 19).
Note
When the unit is running in test mode, the LED beam remains on, which can
shorten the LED’s service life.
Select the test mode only when you need to perform a test read.
Avoid long emission times.
When using the “additional information” (see page 21 to 22) in the test mode, the
selected data is added in the same manner as in the normal operation mode.
However, only when selecting the reading rate check mode, the decode count
and scan count are not added to the analyzed results.
Page 27
2.5STABILITY LEDs
STABILITY LEDs allows you to easily check reading stability.
STABILITY LEDs light only when the test mode gets started or the decode count
adding function (see P. 34) is used.
Indication of reading stability
When reading rate check mode is selected
STABILITY LEDs light according to the reading rate shown in the table below. Although, in the test mode, the unit does not output an OK/NG singnal, the OK/NG
LED lights as below. (Comparison to the preset data is not performed.)
2.5 STABILITY LEDs
Reading rate
80 to 100%
50 to 79%OrangeGreen
20 to 49%RedGreen
1 to 19%——Green
0%——Red
STABILITY LEDOK/NG LED
GreenGreen
When tact check mode is selected
STABILITY LEDs light according to the scan count (decode count), which indicates the number of successful reads, as shown in the table below.
Although, in the test mode, the unit does not output an OK/NG signal, OK/NG LED
lights as below. (Comparison to the preset data is not performed.)
Decode count
50 or more
10 to 49 Orange
5 to 9Red
1 to 4——
0——Red
STABILITY LEDOK/NG LED
GreenGreen (decode counts are
equal to or greater than
the preset match count)
Red (decode counts are
less than the preset
match count)
When using the decode count adding function
STABILITY LEDs light as shown in the table below according to the decode
count.
OK/NG output (OK/NG LED) turns ON/OFF based on the result of comparison to
the preset data.
CAUTION
Decode count
50 or more
10 to 49Orange
5 to 9Red
4 or less——
STABILITY LED
Green
When you do not use the decode count adding function or use the multi-label read
mode 3, STABILITY LEDs do not light.
19
Page 28
2.6 Preset Function (Compare with:)
2.6Preset Function (Compare with:)
?:
!:
2.6.1
2.6.2
What is the preset function?
The BL-180 can store one bar codeas preset data. It compares the preset data to
the bar code data actually read and outputs an OK/NG signal to whether there is
a match.
Using the BL-180 preset function, you can prevent the wrong products from entering the line without using a PC.
If no preset data is registered, the unit outputs OK when it successfully reads a
bar code and NG when it fails to read a bar code.
• See page 10 to 16 for output timing.
• Use the setup software and serial command to register the preset data (see
page 39 and page 59).
Note
• The bar code actually read can be compared to the preset data only in the single label read mode.
• See page 70 if you want to use CODE128.
Wildcard symbols (“!” and “?”)
Using “!” and “?” in the preset data allows for flexible settings.
Does not define numeric values (characters) of certain digit(s) of the bar code.
Ignores numeric values and symbols within the dot box and recognizes the bar codes
as the same group.
Setting examples
Note
4912 3456
4912 5256
4912 AB5 6
When using “?” data as “4912??56”, 2
digits positioned in “??” can contain
any numeric values (or characters),
expanding the allowable range. Identifies all the bar codes to be OK as
long as the beginning or ending
strings match.
If you do not register preset data, “!” is automatically registered. Therefore, when
the unit sucessfully reads a bar code, “OK” is output; when the unit fails to read,
“NG” is output.
You cannot use the “*” character as a wild card symbol with the BL series.
When using “!” as “4912!”, any bar
code which begins with “4912” will be
OK. When using “!” as “!4912”, any
bar code which ends with “4912” will
be OK.
4912 3456
4912 C
4912
20
Page 29
2.7Additional Information
When sending the bar code data, you can add the following data to the readout
data.
Additional information types
Decode match count add function
Adds the number of successful scans during one bar code reading (decode
count) to the end of the readout data (up to 9999 count). However, this decode
count is never less than the preset decoding match count.
• This function can be used to check reading stability and code label quality.
When using this function, output turns on at a different time from normal operation.
• In single label read mode, output turns on after one bar code has been read
(after trigger input turns off). Even if you set the data-send to “after read”, the
data is forced sent after trigger input turns off.
• In multi-label read mode 1, a bar code passes across the LED beam’s field,
after repeat read time, and is finally output.
• In multi-label read mode 2 or 3, operation is the same as when you do not use
the decode match count adding function.
2.7 Additional Information
Delimiter
Readout data
The value is zero-suppressed.
:d
d = [Decoding match count] to
9999: Decode count
Note
Code type add function
When you use the decode count adding function, STABILITY LEDs light to show
reading stability (see P. 31).
Scan count add function (valid only when using the read count add function)
Adds the number of scans, including when no bar code exists, to the end of the
decode count (up to 9999).
Delimiters
Readout data
The value is zero-suppressed.
Adds the bar code type before the readout data .
Delimiter
t
:
t = 0:Code39
1:ITF
2:Industrial 2 of 5
3:Codabar
4:EAN/UPC (A•E)
5:CODE 128
6:COOP 2 of 5
7:Read error
:d/s
m = 1 to 999 (zero-suppressed)
Readout data
21
Page 30
2.7 Additional Information
4 9000000
4 9000000
Forward orientation Reverse orientation
OK/NG
STABILITY
BL-180
r =F:Forward
R:Reverse
If an read error occurs, this information is not added.
Delimiter
r
:
Readout data
label orientation add function
Adds the orientation of bar code travel before the readout data.
Order of additional information
If you select to include all the additional information functions, they appear in the
following order:
22
Note
Code type
:
label
orientation
:Readout data:
Decode match
count
:Scan count
You can change the delimiter as desired (one character), except the delimiter of
the scan count.
Page 31
2.8 Max. Code Length (Designated Digit ) Output Function
2.8Max. Code Length (Designated Digit )
Output Function
This function allows you to output the designated digit(s) as desired from the
readout bar code data. For example, from bar code data “49123456”, you can extract “1234” for output.
Setting digits to be output
Set the digits to be output as shown below. Individually set the digits for codes 1
to 4.
1. Set the direction to designate.
Set from which direction you want to start counting.
ForwardReverse
4 9 1 2 3 4 5 6
2. Set from which digit you want to begin designation (destination start digit).
5th digit by counting forward
4 9 1 2 3 4 5 6
3. Set how many digits you want to designate for output starting from the designation start digit in (2) (designation effective digits).
3 digits starting from 5th digit by counting forward
4 9 1 2 3 4 5 6
Example Designating and outputting “34” from bar codes “158423421” and “58423421”
5 8 4 2 3 4 2 1
Note
1 5 8 4 2 3 4 2 1
Designate 2 digits starting from 3rd digit by counting reversely.
• Regardless of the designated direction, the data is output forward in the com-
munication application.
• When the bar code group includes those having different digits, take special
care on the designated direction when setting the digits to be output.
• When comparing to the preset data, all the digits of the bar code are used.
23
Page 32
2.8 Max. Code Length (Designated Digit ) Output Function
24
Page 33
Chapter 3
Setup Software
Page 34
3.1 Controlling the BL-180
3.1Controlling the BL-180
The BL-180 can be controlled by computer using an RS-232C serial communication with Windows™ Terminal software or using BL-180 Setup Software. This
chapter describes how to set the BL-180 using the BL-180 setup software. For
more information on using the serial communication, see “Chapter 4” on page 45.
3.1.1
Setup Software Requirements
Starting the setup
software
The BL-180 Setup Software for Windows operates in the following environments:
Personal Computer
IBM PC/AT or compatible model (100% compatible)
CPU: 80386 or higher
Memory: 4 MB or more
Floppy drive: One or more 3.5 inch drives
RS-232C: One serial port (COM 1 or COM 2)
DOS: Windows 3.1
* The BL-180 Setup Software applies to COM 1 only.
1. Prepare the following items before starting.
• BL-180
• Power supply unit for BL-180 (5 VDC) or the BL-U1
• RS-232C cable described on p. 2 to 4 in this manual
• Setup software
• Personal computer
• Mouse
2. Connect the PC with the BL-180 or BL-U1 using the RS-232C cable.
3. Set the DIP switches on the BL-U1 to RS-232C when you use the BL-U1.
4. Install the setup software.
Turn the PC’s power switch ON to start Windows.
5. Insert the setup software into the floppy disk drive.
6. Select File - Run on the menu bar of the program manager.
26
7. When the following screen appears, type the name of the floppy disk drive
and the name of the installed file “SETUP” in the “Command Line”. After typing the above, click on the OK button.
Example When the floppy drive is drive A, type as follows:
A:\SETUP
Then, the target directory for installation is displayed.
“C:\BL180”
is displayed.
Page 35
27
OK
3.1 Controlling the BL-180
8. To accept the directory name, click on the OK button.
9. To change the directory name, click on the column displying the directory
name, type a desired directory name using the keyboard, and click on the
buttonAfter the installation is completed, the “KEYENCE Barcode
Reader” window is created in the program manager. In this window, icon
“BL18WIN” is created.
10. To start the setup software, double-click on the “BL18WIN” icon.
Note
11. After the setup software gets started, the following screen appears:
When using a monochrome display on a laptop PC, the display appears in reverse video. To make the display clearer, set the laptop’s display to reverse video
and then restart the setup software.
Page 36
3.2 Operating Procedure
3.2Operating Procedure
3.2.1
Outline of Operation
To operate the setup software, place the mouse pointer on the item to be
changed, and click the left button of the mouse.
Use the Down Arrow button to select an item from a list. Place the mouse pointer
on a desired item, and click on the item.
Click on the Option button to select one of several items.
In the above settings, Read mode is set to “Single” and Data-send is set for “At
trigger input.”
The Check Box is used to enable special functions. An “X” in the Check Box indicates that a function has been enabled.
In the above settings, “Inspect check-digit[Modulus43]” is enabled.
To enter characters or a value in a field, insert the mouse pointer over the field.
The pointer will change to a cursor. Click inside the field and type in the desired
value.
If the specified value exceeds the setting range, an error message will appear
To shift to a different screen, click the mouse cursor one of the buttons in the window. For example to return to the previous screen, click on the button.
28
Page 37
3.3 Setup Software Operating Procedure
3.3Setup Software Operating Procedure
After the setup software is started, the following screen (main setting screen) is
displayed.
The function of each display is as follows.
Title (Name of the current setting screen)
Menu bar (*)
Parameter
Current file name
The initial file name is “Untitled. CFG”.
Setting screen selector buttons
The setup software provides the following setting screens according to the parameters.
Main setting [Main]
• Type of the bar code to be read
• Read mode and its setup
• Decoding match count
• Additional information
Setting details for the specified code type [Code setup]
• Setting No. of bar code length, inspection of check-digit, etc.
Trigger input setup [Setup Trigger input]
• Setting the operation mode and the trigger input
• Selecting the test mode starting method
• Setting characters for the trigger ON/OFF command
Communication parameters [Setup comm]
• Setting the baud rate, data bits, stop bit and parity
• Setting the protocol
• Setting the Communication strings (header string, delimiter, read error code,
etc.)
Utility [Utility]
• Setting the beeper
• Duration of OK/NG output
• Registration of preset data
For the operating procedure, see “Setup Software Operating Procedure” on
page 29.
For the error messages displayed during operation, see page 41.
29
Page 38
3.3 Setup Software Operating Procedure
Menu Bar
3.3.1
File Operation
The following operations can be performed using the menu bar.
File Menu (Alt+F)
Specifies a file name/Saves a file.
Exits the setup software.
Send Settings (Alt+S)
Sends settings to the BL-180.
Info (Alt+I)
Indicates the version number of this software.
The following is the procedure for specifying a file name, saving a file or exiting
the setup software.
Click on File in the menu bar.
The following menu appears.
New
New
Cancels the current setting file and calls the initial setting.
Open
Calls the previously stored file.
Save As
Saves a file with a specified file name.
Save
Saves a file.
Exit
Exits the setup software.
1. Click on New.
The following message appears.
30
2. To cancel the current settings and call the initial setting, click on the OK button. If you wish not to execute this operation, click on Cancel
.
Page 39
3.3 Setup Software Operating Procedure
Open
1. Click on Open .
2. The following screen is displayed for selection of the file to be read.
Select a desired file from those listed in the file selection column, and click on
the OK button.
If you wish to cancel this operation, click on the Cancel button.
To change the directory or drive, select a desired directory or drive in the di-
rectory/drive selection column.
3. When you click on the OK button on the above screen, the following message appears.
Save As
To cancel the current setting and call a new file, click on the OK button. If you
wish not to execute this operation, click on the Cancel button.
1. Click on Save As .
2. The “Save As” screen appears.
3. Click in the file name entry field and type a file name using the keyboard.
Type a file name of up to 8 characters. Be sure to add extension “CFG” to the
file name.
31
Page 40
3.3 Setup Software Operating Procedure
Example When the file name is “TEST”:
1. Click on the file name entry column.
2. Enter “TEST. CFG” as the file name .
3. Click on the OK button.
If you wish cancel this operation, click on the Cancel button.
To change the directory or drive, select a desired directory or drive in the
directory/drive selection column.
4. If the specified file name has already been stored, the following message will
appear.
To save the setting by overwriting the existing file, click on the OK button. If
you wish not to save the setting, click on the Cancel button.
32
Save
Exit
3.3.2
A file name must be entered before the file can be saved
1. Click on Save . The file will be saved.
1. Click on Exit .
The following message appears.
2. To exit the setup softw are, clic k on the OK button. If y ou wish cancel, clic k on
Cancel .
Save the current settings before exiting the setup software.
Main setting screen
1. Place the mouse cursor at the item to be changed and click it, or move to the
target item by pressing [TAB] . Then, change the setting using [Space] .
2. To codes 1 to 4, specify the types of bar codes to be read.
If you specify 4 different types of bar codes, the BL-180 can read them without changing the settings.
3. To set the code length or the inspect for check-digit, click Setup or press
[ENTER] to move to the setup screen for each code (see page 33 to 36).
Page 41
33
3.3 Setup Software Operating Procedure
4. When selecting Single for Read mode, the following appears on the screen:
When selecting Multi 1 or Multi 2, the following appears on the screen:
Set the time within the range from 1 to 255 (100 ms to 25.5 s).
When selecting Multi 3, none of the above information appears.
5. In the Additional information field, you can select one or more items. However, the scan count is given only when the decode count is selected.
3.3.3
Note
Read mode --> Page 12
Data-send --> Page 11
Repeating-reading time --> Page 12
Decoding match count --> Page 10
Additional information --> Page 21
CODE39 setup
When setting CODE39 to any one of codes 1 to 4 and trying to set details, this
setting screen appears.
1. Place the mouse cursor at the item to be changed and click it, or move to the
target item by pressing [TAB] . Then, change the setting using [Space] .
2. Setting Max code length and Min code length allows the BL-180 to read bar
codes having the specified range of digits. If you want to read bar codes with
the specific code length, set the same value to both Max code length and
Min code length.
The allowable setting range is 3 to 32 digits including the start/stop character.
3. When you select Send start/stop character, * is added to the data when
being sent.
Page 42
3.3 Setup Software Operating Procedure
4. When you select Inspect check-digit, the following information appears:
The above setting sends the data together with the check-digit.
Modulus 43 is used to calculate the check-digit.
5. When you select Max code length output, the following information appears:
Set Effective and Starting from 1 to 32.
6. When you select Specify label orientation, the following information appears:
7. Click the Return button or press [ENTER] to return to the main setting
screen.
1. Setup is the same as the CODE39 setup. However, ITF does not have Start/
stop character.
2. Set code length using a even value within the range from 2 to 32.
3. Modulus 10/Weight3 is used to calculate the check-digit.
3.3.5
Note
When reading the standard distribution code (bar code on the corrugated fiberboard box), set the code length to 14 or 16 and select the Inspect check-digit.
Setup for Industrial 2 of 5 and COOP 2 of 5
1. Setup is the same as the CODE39 setup. However, a start/stop character
and Inspect check-digit are not provided.
2. Set code length within the range from 1 to 32.
Page 43
3.3 Setup Software Operating Procedure
3.3.6
Codabar setup
1. Set code length from 3 to 32 including the start/stop character.
2. When you select Send start/stop character, A, B, C, and D are added to the
data to be sent.
In this case, the following information appears:
You can select lowercase or uppercase for the start/stop character.
3. When you select Inspect check-digit, the following information appears:
Specify the check-digit calculation method and whether or not the check-digit
is sent.
4. Set the other parameters in the same manner as for CODE39.
35
Page 44
3.3 Setup Software Operating Procedure
3.3.7
UPC/EAN setup
1. Select Read EAN 8 code, Read UPC-A[EAN13] code or Read UPC-E to
enable to read.
If you select Read UPC-A[EAN13] code, the following information appears,
asking you to select which digits you want to output on UPC-A.
If you select Read UPC-E, the following information appears, asking if you
want to send data with the leading zero-suppressed.
3.3.8
2. You can use the same setting procedure as f or CODE39 f or Max code length
output and Specify label orientation. However, the setting range of Effective
and Starting in Max code length output is limited to the code length of the
readout UPC/E code.
• Although the check-digit parameter is not provided on the screen, the system
internally calculates it using modulus 10/Weight3. (The calculated data is
sent.)
CODE128 setup
1. The setting range of code length depends on the start character type CODEA to C (see page 70).
• CODE-A and B --- 1 to 32
• CODE-C --- 2 to 64
The code length does not include the start/stop character or check-digit. Also,
FNC1 to 4 (function codes), SHIFT, and CODE-A to C are excluded from the
code length.
36
Page 45
2. Check that the double-character start pattern is regulated in the UPC/EAN128 standard. It means the combination of start character (CODE-C) and
FNC1 (function code 1). The standard specifies that the UPC/EAN-128 bar
codes should start with the double character start pattern.
Using this parameter, you can specify that reading will not start without the
double character start pattern.
3. You can use the same setting procedure as f or CODE39 f or Max code length
output and Direction. However, the setting range of Effective and Starting in
Max code length output is 1 to 64 if the start character is CODE-C.
• Although the check-digit parameter is not shown on the screen, the system
internally calculates it using modulus 10/Weight3. (The calculated data is not
sent.)
3.3.9Trigger input setting
3.3 Setup Software Operating Procedure
1. Place the mouse cursor at the item to be changed and click it, or move to the
target item by pressing [TAB]. Then, change the setting using [Space].
2. Select Level synchronization or One-shot synchronization as the scanning
method. When you select One-shot, the following information appears, asking you to set the scanning time:
Set the scanning time within the range from 1 to 255 (100 ms to 25.5 s).
3. When you select “Test mode initiated with trigger input ON” or “Test mode initiated at startup,” the following information appears, asking you which test
mode you want to start:
If you select both “Test mode initiated with trigger input ON” and “Test mode
initiated upon power-up,” “Test mode initiated with trigger input ON” is used.
4. In the Command for trigger input parameter, you can freely change the characters for the Trigger ON/OFF command (within 8 characters).
Normally, you should use the default setting (Lon, LOff).
5. Click the Return button or press [ENTER] to return to the main setting
screen.
Note
Scanning method --> Page 10
Starting the test mode --> Page 17
Trigger ON/OFF command --> Page 51
37
Page 46
3.3 Setup Software Operating Procedure
3.3.10 Communication setting
1. Place the mouse cursor at the item to be changed and click it, or move to the
target item by pressing [TAB]. Then, change the setting using [Space].
2. When setting the header string, delimeter, and read error, click [Communication strings] or press [ENTER] to move to the communication strings setting
screen.
3. Click the Return button or press [ENTER] to return to the main setting
screen.
Note
(Communication) protocol --> Page 47
The setup software does not allow you to set the baud rate to 19200 to 38400 bit/
s. If you want to set the baud rate within this range, use the serial commands (see
page 58).
3.3.11 Communication strings setup
1. Place the mouse cursor at the item to be changed and click it, or move to the
target item by pressing [TAB]. Then, change the setting using [Space].
2. Select appropriate values for Header string and Delimiter from among the
displayed items. When you select Custom, the following appears:
38
Then, you can enter the desired value from the keyboard (within 5 characters).
Page 47
3.3 Setup Software Operating Procedure
3. When you select Default[:] for Partition mark and Intermediate delimiter,
these parameters are set as below:
When you select Custom, the following appears:
Then, you can enter the desired value from the keyboard (using one character
for the partition mark and 5 characters or less for the intermediate delimiter).
4. Input the Read error using the keyboard.
You can change the code as desired (within 8 characters).
Normally, you should use the default setting (ERROR). You can chose not to
send the read error by selecting a null value for the read error.
5. Click the Return button or press [ENTER] to return to the communication
setting screen.
1. Place the mouse cursor at the item to be changed and click it, or move to the
target item by pressing [TAB]. Then, change the setting using [Space].
2. By setting Bepper for OK/NG output, the beeper beeps to indicate reading
stability during the normal reading operation.
3. To set OK/NG output duration, enter the appropriate numeric value from the
keyboard. The setting range is from 1 to 255 (10 ms to 2.55 s).
4. To set Compare with, enter the preset data to be registered from the keyboard.
Usually, specify the data within 32 characters. If you are using CODE128 and
the start character is CODE-C, you can set the data using up to 64 characters.
Note
5. Click the Return button or press [ENTER] to return to the main setting
screen.
STABILITY LED --> Page 19
OK/NG output duration --> Page 10
Preset data --> Page 20
39
Page 48
3.3 Setup Software Operating Procedure
3.3.13 Sending Settings
1. Choose Send from the menu bar. The following screen appears.
2. Set the baud rate, data bits, stop bit and parity according the BL-180’s settings. The BL-180’s default settings are shown above.
3. Specify whether the parameter settings are to be saved in the EEPROM or
not. If the current settings are not saved in the EEPROM, the setup software
will start with the previous settings when the power is turned on again.
4. After setting the communication parameters, click on OK. Data transmission
will begin. If a communication error occurs, the following message will
appear.
* The BL-180’s communication parameters are set as shown above for 5 seconds
after the power is turned ON. (see page 46.)(See p. 58 of the Users’ Manual.)
5. If the setup software is normally exited, it will return to the main setting
3.3.14 Version Display
1. Click on Info on the manu bar.
2. The following screen appears, where you can confirm the version of this
If you are not sure of the communication parameter settings of the BL-180,
turn ON the BL-180’s power switch before executing data transmission, and
set the communication parameters as shown in step 1.
screen.
setup software.
40
Page 49
3.4List of Error Messages
If an error occurs, the following messages will appear on the screen.
Click on OK and delete the error message. Then, take the necessary corrective
action.
Error messageCause of error
File not found.The file specified for Open Setting does not exist.
Drive is not ready.The specified disk is not prepared.
Write protected.Overwrite protection is set to the disk.
3.4 List of Error Messages
Insufficient disk space.
Illegal filename (must be in
format of xxxxxxxx.CFG.)
Illegal file.Use a correct file name.
Path not found.The pass for the specified file is invalid.
Device not ready.The specified drive is invalid.
Insufficient memory.The main memory capacity is insufficient.
Error during file operation
Device I/O errorThe disk may be damaged or unformatted.
This is not BL-180 setting file.
Error in detailed code data.
Communication error
Value out of range.
Min. code length is set larger
than Max. code length.
Error during setup
Device is unavailable.
The remaining disk capacity is insufficient. Replace
the disk.
The file name does not have extension CFG. Enter
the file name correctly.
The stored file data are incorrect. Specify a correct
file name.
Data of the BL-180 setup file are different from that
of the BL-180. These files are not for common use.
The stored file data are damaged. Specify a ne w file
name.
An error occurred during communication.
The parameter settings (e.g. baud rate) may not be
matched, or the connection may be incorrect.
The specified value is exceeding the setting range.
Enter a correct value.
The minimum code length is set larger than the
maximum code length. Enter a correct number.
The serial port is being used for a device other than
the BL or else “Terminal” is running.
41
Page 50
3.5 How to Use Terminal Software
3.5How to Use Terminal Software
The terminal software allows bar code data to be displayed on a Windows-based
personal computer and allows serial commands to be sent to the BL-180.
You can use the standard terminal software included in Windows Ver. 3.1. This
section describes how to use the terminal software to confirm the operation of the
BL-180.
For more information on the terminal software and its functions, please refer to
theWindows manual.
1. Double-click on the Terminal icon in the Accessory Group.
The terminal software starts up.
2. When the terminal software is started, the following screen appears.
3. First, set the terminal software.
When you click on Settings, the following menu appears.
42
Page 51
3.5 How to Use Terminal Software
4. When you click on Terminal Preferences, the setting screen is displayed.
Set the displayed parameters as shown below. After setting the parameters,
click on OK.
5. Then, Click on Settings then Communications.
The following screen appears.
Note
After setting “Connector” to COM1 or COM2, set the baud rate, data bits, stop
bits and parity according to the BL-180’s settings. When the data bits is set to
“8 bits”, the parity can only be set to “None.”
After setting the communication parameters, click on [OK].
6. When the BL-180 reads a bar code, the read data is displayed on the screen.
(When the BL-180’s delimiter is set to CR, data will be displayed with carriage returns. Control codes cannot be displayed.)
7. To send a command, type TEST1/TEST2 using the keyboard, and then
press [ENTER]. All commands should be in entered in all uppercase characters. Refer to pages 51 to 52 for available commands and for descriptions of
each commnad.
In read rate display test mode (TEST 1 mode), the entered command is difficult to see on the screen because the BL-180 is displaying the read data.
However, the command will be correctly sent.
8. To exit the terminal software, click on F
Multi drop link commands cannot be sent.
RTS/CTS protocol commands cannot be confirmed.
When you start up “Terminal”, you cannot send the setting to BL using SETUP
software. Quit on close “Terminal” before you send the setting.
ile then Exit.
43
Page 52
3.5 How to Use Terminal Software
44
Page 53
Chapter 4
Serial Communication (RS-232C/RS-422A)
Page 54
4.1 Serial Communication
4.1Serial Communication
The BL-180 communicates with the PC via the RS-232C serial port. This enables
you to change the BL-180’s settings from your PC.
Communication T ypes
The BL-180 provides the following two communication types:
Data communication
Sends read bar code data from the BL-180 to the PC.
Command communication
Changes the BL-180’s settings by sending a command from the PC to the BL-
180.
All communication is performed using ASCII codes.
4.1.1
Communication Setup
Configure the setup for BL-180 and the PC before attempting serial communication.
Setup of BL-180
Set the following parameters for the BL-180 using the setup software.
Baud rate, Data bits, Parity, Stop bit, Communication protocol, Header/Delimiter,
Read error code
PC setup
Based on the BL-180’s settings, set the communication parameters on the PC using the “Ports” setting in the Windows Control Panel.
Note
The following communication parameters are the default settings for the BL-180:
Baud rate: 9600 bps
Data bits: 7 bits
Parity: Even
Stop bit: 1 bit
Set the PC according to the above settings before attempting communication.
The BL-180 is set, temporarily, to the default settings for 5 seconds after the pow-
er switch is turned on.
When the current settings of BL-180 is not certain, send the command “SSET”
and a [CR] to the BL-180 from your PC with 5 seconds after power-up. This causes the BL-180 to remain at its default settings and you can communicate with the
BL-180 at the default settings.
For information on checking the BL-180’s current settings, see “Details on Parameter Setting Commands” on page 52. For information on changing the above
communication parameters see “Description of Parameter Setting Commands”
on page 53.
Data communication can be performed with the current parameter settings even
for 5 seconds after the power is turned on.
46
Note
All commands should be entered in all uppercase characters. The BL cannot accept lowercase characters.
Page 55
4.2 Details on Data Communication
4.2Details on Data Communication
4.2.1
Communication Protocols(Hardware handshaking)
The BL-180 supports the following four handshaking protocols.
No Handshaking
The BL-180 sends read data to the PC without using any handshaking protocol.
PASS/RTRY Handshaking
After sending the read data, the BL-180 waits for a response from the PC. The
response is either a PASS command or a RTRY command.
Read data
Read data
Response
C
(PASS , RTRY)
C
R
R
Note
ACK/NAK Handshaking
The PASS command (quit) indicates that the PC has successfully received one
data packet. The BL-180 then prepares for the next data transmission.
The RTRY command (request to re-send) indicates that the data was not transmitted successfully. The command is a request to the BL-180 to re-send the data.
The BL-180 sends the same data again and then waits for the response.
After the BL-180 once receives PASS, the BL-180 sends back no data even if
RTRY is sent to the BL-180.
The BL-180 can continue to read while waiting for the PASS command. The data
is stored in the BL-180’s transmission buffer (For the capacity of the transmission
buffer, see page 48).
If the amount of stored data exceeds the capacity of the transmission buffer, the
BL-180 sends back <Header> OVER <Delimiter> to the PC, and clears all data
stored in the transmission buffer. For more information, see “Capacity of Transmission Buffer” on page 48.
The BL-180 can receives other commands while waiting for the PASS command.
In this case, the BL-180 sends back an immediate response (e.g. OK).
When the SSET command (see “4.3.3” on page 52) is sent to the BL-180 while
the BL-180 is waiting for the PASS command, the BL-180 clears the data stored
in the transmission buffer, and enters the setting mode.
The ACK/NAK handshaking uses ACK (06H) and NAK (15H) instead of PASS
and RTRY used in the PASS/RTRY handshaking, respectively. With these protocols, the BL-180 sends back different characters, but performs the same operation.
47
Page 56
4.2 Details on Data Communication
RTS/CTS Handshaking
When the PC’s RTS (BL-180’s CTS) signal turns off, the BL-180 becomes ready
for data transmission. When the PC’s RTS signal turns on, the BL-180 starts data
transmission.
When the PC’s RTS signal is off, the BL-180 can still read. In this case, data is
stored in the BL-180’s transmission buffer (see 4.2.2 below).
If the amount of stored data exceeds the capacity of the transmission buffer, the
BL-180 sends back <Header>OVER<Delimiter> to the PC, and clears all data
stored in the transmission buffer.
4.2.2
Note
The RTS/CTS handshaking cannot be used for RS-422A communication.
The RTS/CTS protocol can be used together with other handshaking protocols.
When the PC’s RTS signal is off, the BL-180 does not sends back a response to
the PC.
Capacity of Transmission Buffer
The BL-180’ s transmission buffer can store 400 bytes (400 characters).
The number of characters stored in the transmission buffer for each data packet
is the number of characters in the data (including additional data such as the number of decoding match count) plus an additional five characters indicating the data’s attributes.
When multi label reading mode 2 or 3 is used, these five attribute characters are
added to each data packet.
Example 1
When the number of bar code digits is 10 (with no additional data)
400 ÷ (10 + 5) = 26
The transmission buffer can store 26 pieces of data.
Example 2
When the number of bar code digits is 20 (with no additional data)
400 ÷ (20 + 5) = 16
The transmission buffer can store 16 pieces of data.
4.2.3
48
Read Data Format
Set the data format of the Header and Delimiter, respectively.
HeaderRead dataDelimiter
With the setup software, the following formats can be selected. Other than the following formats, you can freely set up to 5 characters.
Header
ESC (1BH)/STX (02H)/None
Delimiter
CR (ODH)/CR (ODH) LF (OAH)/ETX (O3H)
Page 57
4.2 Details on Data Communication
4.2.4
Read Error Code
If the BL-180 fails to read a bar code, the B-500 sends back a read error code.
The initial setting of the read error code is as follows:
The read error code can freely be changed (within 8 characters).
The BL-180 can be set to send no error code (see page 38).
Header
ERRORDelimiter
49
Page 58
LF
4.3 Command Communication
4.3Command Communication
The BL-180 includes commands to directly operate the BL-180 (direct control
commands) and the commands used to change or confirm the BL-180’s settings
(parameter setting commands).
4.3.1
Setup of Direct Control Commands
Communication procedure
1. Send a direct control command from the PC to the BL-180.
2. After receiving the command, the BL-180 sends back an OK response and
3. When an incorrect command is sent to the BL-180, the BL-180 sends back
Note
can be added after the command being sent. In this case, however, LF is not
added to the response data.
When ESC is inserted before the command being sent, characters in the BL-
180’s command receiving buffer are cleared.
If the BL-180’s command receiving buffer contains erroneous characters due to
data transmission error during communication, add ESC to the command being
sent.
Command
Response
executes the required operation.
When the read operation control command or test mode control command is
sent to the BL-180, the BL-180 sends back no response.
no response.
Note
For command communication, set the time duration between transmission of
each character (byte) to up to 30 seconds. If this duration exceeds 30 seconds,
the BL-180 cancels the received characters.
50
Page 59
4.3 Command Communication
4.3.2
Explanation of Direct Control Commands
Read operation control
[LON]Trigger on
[LOFF]Trigger off
The following describe direct control commands in details.
This command specifies the data read timing.
Command: LON
Response: None
Command: LOFF
Response: None
• Even when the read operation is controlled with these commands, the BL-180
performs the same operation as with the trigger input (see page 10 to 12).
•“Trigger input: on” corresponds to LON , and “trigger input: off” corresponds to
LOFF .
• The BL-180 starts read operation on receipt of LON and stops it on receipt of
LOFF .
• When a bar code can be correctly read and the read data has already been
set, you need not send LOFF .
• The command characters can be freely changed (within 8 characters).
Test mode control
[TEST1]Reading rate check
[TEST2]Tact check
[QUIT]Resetting test
OK/NG output control
[OKON]Turning the OK output on
Starts or quits the test mode.
Command: TEST1
Response: None
Command: TEST2
Response: None
Command: QUIT
Response: None
• After using the test mode, be sure to reset it.
Directly turns on/off the OK/NG output.
This enables you to easily check wiring.
Command: OKON
Response: OK
[NGON]Turning the NG output on
Command: NGON
Response: OK
[ALLOFF]Turning the OK/NG outputs off
Command: ALLOFF
Response: OK
51
Page 60
4.3 Command Communication
Clearing transmission buffer
[BCLR] Clears data stored in the transmission buffer.
Command: BCLR
Response: OK
Shift to setting mode
[SSET] Enters the setting mode (see page 51).
Command: SSET
Response: OK
.
4.3.3
Details on Parameter Setting Commands
Communication Details
The following describes how to change the BL-180’s settings through command
communication.
You can use the setup software to change the BL-180’s settings instead of these
commands.
1. Send the direct control command SSET to the BL-180.
The BL-180 will shift to setting mode.
After successfully executing the command, the BL-180 sends back an OK .
2. After the BL-180 shifts to setting mode, send the command (setting change
command) corresponding to the item to be changed to the BL-180.
After successfully executing the command, the BL-180 sends back an OK .
If an error occurs with this command, the BL-180 sends back ERR
sttands for error code numbers.)
3. To confirm the current settings, send a setting confirmation command.
After successfully executing the command, the BL-180 sends back an OK .
If an error occurs with this command, the BL-180 sends back ERR
4. To save the current settings in the EEP-ROM, send SAVE to the BL-180.
Once you save the settings in the EEP-R OM, the BL-180 will start with these
settings when the BL-180 is turned on next.
After successfully executing the command, the BL-180 sends back an OK .
If an error occurs with this command, the BL-180 sends back ERR
5. To quit the setting mode and perform the normal bar code reading, send
SEND to the BL-180.
After successfully executing the command, the BL-180 sends back an OK .
If an error occurs with this command, the BL-180 sends back ERR
nn
nn
nn
nn
. (nn
.
.
52
Note [LF] can be added at the end of the command being sent. In this case, however,
[LF] is not added to the response data.
When [ESC] is added before the command being sent, characters in the BL-180’s
command receiving buffer are cleared.
If the BL-180’s command receiving buffer contains erroneous characters due to a
data transmission error during communication, add [ESC] to the command being
sent.
Note
For command communication, set the time duration between transmission of
each character (byte) to up to 30 seconds. If this duration exceeds 30 seconds,
the BL-180 cancels the received characters.
Page 61
4.3.4Response Error Code
When an incorrect command is sent to set parameters, the BL-180 sends back
data indicating the cause of the error (error code). For the commands corresponding to the error codes, see the error code column given in the table on the following pages.
Error codeCause of error
00Undefined command.
01Command format is incorrect.
02Nothing corresponds to the number in the command.
03“m” value (codes 1 to 4) is other than 0 to 3.
04
05The number in the command is too long.
06“hhh...” data is too short.
07“n” value is not 0 or 1.
08“n” value is exceeding the setting range.
09“nnn” or “nn” value is exceeding the setting range.
10“hhh...” is not specified in HEX (hexadecimal) code.
11“hhh...=FF” cannot be set.
12
13Characters of “aaa...” are invalid.
14
15
17 \ is not followed by !, ? or \ in preset data. (See page 70.)
18Two !s exist in preset data. (See page 20.)
99The BL-180 may malfunction. Contact KEYENCE.
4.3 Command Communication
“Bar code type setting command” was not sent first.
Sending “No. of readable digits setting command” is invalid
for JAN code.
“hhh...” or “aaa...” contains more than the specified number
of characters.
Data in the EEPROM may be damaged. Perform initial
setup.
Error in the area storing initial settings.
Settings are automatically initialized.
Initializes settings.DFLTOKReturns to the default-settings, and saves the set-
Quits the setting mode.SENDOKSee page 51.-
SAVEOKSee page 51.-
Respons
e
Description
tings in the EEP-ROM.
Error
Code
00,05
14,15
53
Page 62
4.3 Command Communication
Setting Bar Code Type and Number of Readable Digits for Codes 1 to 4
The following describes the parameter setting commands for Codes 1 to 4.
Be sure to send “Bar code type setting command” first before setting other param-
eters.
Note
Functioncommand being sent
Setting bar code type for
codes 1 to 4.
Setting Max. No. of readable
digits
Setting Min. No. of readable
digits
CODE39
Sending start/stop character.
CODE39
Inspection of check digit
(Modulus 43)
When “Bar code type setting command” is newly sent, all other parameters for the
specified code will return to the default settings.
In this case, set all other parameters again.
Setting change commands and setting confirmation commands are described on
the following pages.
Respons
e
ChangeCODEm=nOKm= 0 to 3:Codes 1 to 4
ConfirmCODEmmn
ChangeMAXm=nnOKm= 0 to 3: Codes 1 to 4
ConfirmMAXmmnn
ChangeMINm=nnOK
ConfirmMINmmnn
ChangeWCm00nOKm= 0 to 3: Codes 1 to 4
ConfirmRCm0000n
2. Readable bar width indicates the range of the narrowest readable bar.
3. 60 mm when the narrowest bar is less than 0.19 mm.
Output type
Leakage current (at off)
Residual voltage (at on)
OK/NG output
Ambient temperature
Relative humidity
Vibration
Power supply voltage
Applied standard
Synchronization
Transmission code
Baud rate
Data length
Serial interface
Parity check
Stop bit
1. Use a stable power supply of 5 VDC
10 to 55 Hz, Double amplitude in X, Y and Z directions, 2 hours
5%. The BL-U1 Special Power Unit is available as an option.
±
NPN open collector output
0.1 mA max.
0.5 V max.
0 to 40°C
35 to 85%
respectively
5 VDC±5%
EIA RS-232C port
Start-stop
ASCII
600 to 38,400 bps
7 bits/8 bits
None/even/odd
1/2 bit
1
62
Note
The internal settings of the BL-180 series are stored in the EEPROM. (Rewritable
up to 10,000 times)
Page 71
A.2 Reading Range Characteristics (Typical)
A.2Reading Range Characteristics (Typical)
Mount the BL-180 referring to the figure below. (The BL-185 provides the same
characteristics as the BL-180.)
* The readable label width means the bar code length including the bar code margins (quiet zones).
Readable label width (mm)
OK/NG
BL-180
•••Reading range when narrow bar width is not less than 0.125, less than 0.19 mm.
•••Reading range when narrow bar width is 0.19 to 1.0 mm.
(Measuring conditions)
•The KEYENCE standard bar code is used.
•Skew :-10°
•Pitch : 0°
•Tilt : 0°
STABILITY
10
33
60
10
Reading distance (mm)
55
80
CAUTION
Narrow bar widthReading distanceMaximum readable label width
0.125 to 0.19 mm
(less than 0.19 mm)
0.19 to 1.0 mm33 ±10 mm80 mm
33 ±5 mm60 mm
The above range may be reduced depending on the bar code quality. Set the optimum reading position based on enough reading tests.
63
Page 72
0°
Receiver axis
_
+
OK/NG
STABILITY
0°
–
+
+
0°
Receiver axis
_
A.3 Angular Characteristics (Typical)
A.3Angular Characteristics (Typical)
Mount the BL-180 referring to the data given below. (The BL-185 provides the
same characteristics as the BL-180.)
CAUTION
Narrow bar width
0.125 to 0.19 mm(less than 0.19 mm)
0.19 to 1.0 mm-40° to -5°, +10° to +40°±15°±15°
(Measuring conditions)
• The KEYENCE standard bar code is used.
• Reading distance: 33 mm
-40° to -5°, +10° to +40°±15°±10°
SkewPitchTilt
The skew angles of -5° to +10° are the specular reflection range (dead angles).
In this range, bar codes cannot be read, or reading error may occur. Avoid mounting the BL-180 series at the above skew angles.
SkewPitch
Tilt
64
Page 73
A.4Dimensions
BL-180
10
A.4 Dimensions
4
2 x 2-M3
2617
4720
Depth: 5 mm or less
BL-185
55
5
10
4
4
6
55
2617
1536
55
ø10
29
80
Readable
width
3310
15.3
Receiver axis
2 x 2-M3
Depth: 5 mm or less
80
Readable
width
ø4.5
Cable length: 1.8 m
20
12.5
5
37
Receiver axis
ø10
6
4
3615
33
ø4.5
Cable length: 1.8 m
10
65
Page 74
A.4 Dimensions
66
BL-180 (with mounting bracket)
820
80 (Readable width)
33
47
t=1.6
Receiver
axis
7
33
10°
23.3
BL-185 (with mounting bracket)
820
33
80 (Readable width)
31
9
16
55
31
(38)
55
31
(36)
9
16
9
16
31
55
31
33
47
7
33
10°
4.4
Note: Detail of slot
80 (Readable width)
Receiver
axis
15.7
4
1120
12.5
7
8
(37)
33
47
Receiver axis
10°
31
t=1.6
Page 75
A.5 Example Program for Serial Communication
A.5Example Program for Serial Communication
The following is a example program that allows data communication and command communication. Type in a command and press [Enter] to send the data to
the BL-180.
Only the QUIT command can be sent by pressing [Q] .
Set the BL-180 as follows:
• Header: [STX] Delimiter: [ETX]
• Handshaking protocol: No handshaking or PASS/RTRY handshaking
100 ‘***BL-180 SAMPLE PROGRAM*********************************************
110 CLS 3
120 DAT$=””:RD$=””:CM$=””
130 OPEN “COM1:” AS #1
140 *BUFFCLR :’***CLEAR BUFFER********************************************
150 A=LOC(1)
160 IF A<>0 THEN R$=INPUT$(1,#1) :GOTO *BUFFCLR
200 ‘
210 *MAIN :’***MAIN ROUTINE***********************************************
220 K$=INKEY$
230 IF K$<>”” THEN GOSUB *COMMAND
240 A=LOC(1)
250 IF A<>0 THEN GOSUB *RECEIVE
260 GOTO *MAIN
300 ‘
310 *Receive :’***RECEIVE DATA
320 RD$=INPUT$(1,#1)
330 IF RD$=CHR$(&H02) THEN RD$=”” :’RECEIVE STX
340 IF RD$=CHR$($H03) THEN GOSUB *BARCODE :RETURN :’RECEIVE ETX
350 IF RD$=CHR$($H0D) THEN GOSUB *RESPONSE :RETURN :’RECEIVE CR
360 DAT$=DAT$+RD$
370 RETURN
400 ‘
410 *COMMAND :’***SEND COMMAND********************************************
420 IF K$=CHR$(&H0D) THEN *SEND
430 IF K$=”Q” AND CM$=”” THEN CM$=”QUIT”:GOTO *SEND
440 PRINT K$;
450 CM$=CM$+K$
460 RETURN
470 *SEND
480 PRINT #1, CM$;CHR$(&H0D); :’SEND COMMAND
490 PRINT:PRINT CM$;”COMMAND IS SENT”
500 CM$=””
510 RETURN
600 ‘
610 *RESPONSE :’***DISPLAY RESPONSE DATA TO THE COMMAND*******************
620 PRINT DAT$ ;”IS SENT BACK”
630 DAT$=””
640 RETURN
700 ‘
710 *BARCODE :’***DISPLAY BAR CODE DATA***********************************
720 PRINT DAT$ ;”IS READ”
730 DAT$$=””
740 RETURN
67
Page 76
A.6 Troubleshooting
A.6Troubleshooting
If a problem occurs during operation, please check the following troubleshooting
notes first. If you cannot fix the problem, contact KEYENCE or your nearest dealer.
Bar codes cannot be read.
Check whether the light source LED is ON.
When using a power supply other than the BL-U1 special power supply unit, confirm that the power supply voltage and capacity is within 5 VDC±5% and 300 mA.
Check the wiring of the power supply unit and the timing input terminal (see p. 11).
CAUTION
Note
Connecting the power supply unit with the reverse polarity may damage the BL
series.
If the BL-180 does not operate, contact KEYENCE.
Check the bar code setting (type, No. of digits).
Check the following parameters using the setup software.
• Bar code type, No. of digits.
• Setting of the check digit inspection (enabled or disabled)
• Setting of the label orientation-specified reading
when using CODE39 or Codabar, include the start/stop characters and check digit in the number of digits.
For Code128, see page 70.
Check the distance and angle between the BL-180 and bar code.
Check the distance and angle while referring to “Mounting angle and mounting
distance” on page 7.
Check the bar code margins (quiet zones).
A bar code requires the right and left margins to be at least 10 times wider than
the narrow bar width.
If the bar code margins are too narrow, it may not be read.
68
Check the bar code label length.
The bar code label length is the lateral length of a bar code including the right and
left margins (quiet zones).
When the narrow bar width (the minimum bar width) is 0.125 to 0.19 mm (less
than 0.19 mm), the readable label length is up to 60 mm length. When the narrow
bar width is 0.19 to 1.0 mm, the readable label length is up to 80 mm.
Check the bar code.
A bar code with blurred sections, defects or stains may not be read correctly.
Bar codes printed with dot matrix or ink jet printers are prone to such problems.
Page 77
Check whether the transmitter (light source) and the receiver (optical
pickup) are clean.
If moisture, oil or dust adheres to the transmitter or the receiver, wipe the units
using a soft cloth and a mild plastic cleaner.
Check whether the protective label is attached to the transmitter or the
receiver.
Remove the protective label before using the BL series.
Check whether the protective label is attached to the transmitter or the receiver.
Check the environmental conditions.
See “Hints on correct use” on page 4.
Reading rate check mode is not 100%.
Check the previous item “Bar codes cannot be read”.
69
A.6 Troubleshooting
Note
The Read rate indicates the number of acceptable decodings (reads) during 10
scans of a bar code. When a bar code has stains or defects, the read rate is reduced.
However, even when the read rate is 20%, 2 decodings are possible during 10
scans. Therefore, if the number of decode matches is 2, the bar code can be read.
If the trigger input can be set enough long, the read operation is not affected.
Initial settings cannot be sent to the BL-180 series using the setup software.
• Check whether the communication parameters such as baud rate and data
length conform to the settings of the BL-180.
• Check whether the pin assignment of RS-232C cable conf orms to those of the
BL-180 and the PC. Check that the cable isn’t disconnected. Also check the
BL-U1’s connection.
• Check whether the BL-180’s or BL-U1’s power switch is on.
• Check whether the PC’s RS-232C interface is “enabled”.
• If you are using the BL-U1, check that its DIP switches are set to RS-232C.
Page 78
A.7 CODE128 Specifications
A.7CODE128 Specifications
Setting No. of Digits
• The start/stop character and check digit are not included in the number of digits.
• FNC1 to 4 (Function codes), SHIFT, and CODE-A to -C should not be added to
the number of digits.
• The number of digits setting range varies depending on the start character
(CODE-A to -C).
CODE-A, B: 1 to 32
CODE-C: 2 to 64
One digit of CODE-A or CODE-B represents two digits of CODE-C.
Data T ransmission
• The start/stop character and check digit cannot be sent.
• FNC1 to 4 (Function codes), SHIFT, and CODE-A to -C cannot be sent.
• Control codes are sent.
Registration of Preset Data
The number of characters that can be registered as preset data is up to 32 digits
for CODE-A or CODE-B, and up to 64 digits for CODE-C, as described above.
When ! or ? is registered as preset data, it functions as the Preset “!” “?” Function,
as described on page 20 .
Since CODE128 can represent all ASCII codes as bar code data, ! or ? can also
be represented as bar code data.
To register ! or ? as preset data, send \! or \? to differentiate it from the Preset “!”
“?” function.
To register \ as preset data, send \\.
Example: To register 123 \!?ABC as preset data, send the following command (see
page 57).
WP68123 \\\!\?ABC
Control codes (00h to 2Fh of the ASCII code table, such as and <STX>), start/
stop character, check digit, FNC1 to 4 (function codes), SHIFT or CODE-A to-C
cannot be registered as preset data. (Data comparison is also impossible.)
This User’s Manual describes the operation and functions of the BL-U1. Read this
manual carefully to ensure safe use and maximum performance from your BL-U1.
Note: No part of this document is to be reproduced or utilized in any form or by any
means without the written consent of KEYENCE Corporation.
The contents of this document are subject to revision without notice.
If you have any problems or questions regarding this document, please contact
one of the KEYENCE offices listed on the last page of this document.
KEYENCE is not responsible for any results of the application of the product.
If the document contains incomplete printing, it can be exchanged for a complete
one.
• MS-DOS is a registered trademark of Microsoft U. S. A.
• MS-Windows is a trademark of Microsoft U. S. A.
• Other company names and product names are registered trademarks or trademarks of the respective companies.
Conventions
This document uses the following conventions to help you easily recognize important and useful information.
CAUTION
Note
Important information which must be read to avoid damaging the unit.
Provides information for effective use of the unit. Read as required.
Page 87
System Configuration
Using the RS-232C and RS-422A
BL series
Trigger input
Timing sensor
BL-U1 Power supply unit
OK/NG
output
PLC etc.
RS-232C null modem cable
OP-22149 (1.5 m) + OP-25057
(25- to 9-pin adapter)
RS-232C
BL-18H1E
Setup software
3.5-inch version
WINDOWS 3.1
RS-422A
Equipment with
IBM PC/AT
or compatible
RS-422A*
• If not using the BL-U1, prepare an equivalent 5 VDC power supply unit separately.
• To communicate through the RS-422A, you need a BL-U1 in your system.
Using the RS-485 multidrop link
BL series
L-U1
• To communicate through the RS-485, you need a BL-U1 in your system.
• Prepare a RS-485/RS-232C convertor separately.
• When using the RS-485 multidrop link, you cannot use the Windows™ Setup
software.
Other Options
Maximum number of connected units: 31
Maximum extension distance: 1.2 km
RS-485/RS-232C
convertor
RS-485
RS-232C
PC
OP-22149
RS-232C null modem cable with D-sub 25-pin connector (1.5 m).
To connect the BL-U1 to a IMB PC/AT compatible using the RS-232C port, use a
25- to 9-pin adapter (OP-25057).
79
Page 88
123
OK/NG LED
OK output: Lights in green.
NG output: Lights in red.
TIMING LED
Lights when trigger input turns ON.
POWER LED
Communication status indicator LEDs
Indicate the communication status of
each communication signal line. Each
LED lights when the corresponding
signal turns ON. Show SD, RD, RS,
and CS from the top.
I/O terminal block
Contains I/O terminals and
RS-422A/RS-485 terminals.
DIP switches
Power switch
Power cable (2 m)
Use 100 to 240 VAC (50/60 Hz).
RS-232C port
Connects to a PC.
READER port
Connects to a bar-code reader
BL-U1
80
Page 89
CAUTION
1BL-U1 Connections
1.1
Connecting the AC power supply
Plug the BL-U1 power cable into the power receptacle. At the same time, ground
the frame ground wire.
Make sure that the power supply provides 100 to 240 VAC ± 10%.
1.2
Connecting the BL-U1 to a BL series
Power Supply BL-U1
FG line
Use the READER port on the BL-U1.
The pin assignment is shown in the table below:
Trigger input
Send data through RS-232C
Receive data through RS-232C
OK uotput
Ground (common ground for respective sig-
nals)
NG uutput
Enable to send data through RS-232C
(always ON)
Request to send data through RS-232C
(control method can be selected by DIP
switches)
+ 5VDC power supply
Signal
direction
Output
Output
Input
Input
——
Input
Input
Output
Output
83
Page 90
84
Ω
Ω
Power Supply BL-U1
Prepare the BL series for connection to the BL-U1 by soldering a D-sub 9-pin connector to the BL series cable. Then connect the cable to READER port of the BLU1.
Prepare the D-sub 9-pin connector and its connector case separately.
BL series
Shield
Yellow
Blown
Purple
White
Black
Gray
Pink
Blue
Red
D-sub 9-pin (female)
Use a metallic connector case for the D-sub 9-pin connector and connect the
shielded line to the connector case. This allows connection to the earth ground of
the AC power cable.
-
Connector case
1
TIM
2
RD
3
SD
4
OK
5
GND
6
NG
7
RS
8
CS
9
+5VDC
#4-40 screw
BL-U1
READER port
CAUTION
Take special care when soldering pin 5 (GND) and pin 9 (+5VDC). A wrong connection will damage the unit.
Do not use a power cable over 2 meters long. A long power cable can cause a
drop in voltage, preventing the BL series from starting up properly.
1.3
Setting the BL-U1 DIP switches
According to the selected interface and timing input, change the DIP switch settings.
DIP switch setting
RS-232CONOFFOFF
Interface select
RS-422A terminator
(terminal resistance 100
)
RS-485 terminator
(terminal resistance 100
)
READER port CS control
method select
RS-422AOFFONOFF
RS-485 multidropOFFOFFON
OFFOFF
ONON
OFFOFF
ONON
Reflect ON/OFF of CS
at RS-232C port
Always ONON
OFF
ON
123456
123456
The switch settings at left are the
factory default settings.
OFF
Page 91
1.4
Function and wiring on the I/O terminal block
TIM+12V OUT– COMOKNGSDASDBSGRDARDB
Power Supply BL-U1
Trigger
input
Symbol
TIM
+12V OUT
COM
OK
NG
SDA
SDB
SG
RDA
RDB
Power supply
for sensors
(12 VDC, 300 mA)
Timing input
Power supply for sensors (+) (+12 VDC,
300 mA)
Power supply for sensors (-) (0 V)
Common for OK/NG output
OK output
NG output
Send RS-422A data (+)/RS-485 (+)
Send RS-422A data (-)/RS-485 (-)
Signal ground
Receive RS-422A data (+)
Receive RS-422A data (-)
OK/NG output
DescriptionSignal Direction
RS-422A/RS-485
Input
Input
Output
Output
——
Output
Output
Output/Input and output
Output/Input and output
——
Input
Input
The above list starts from the left edge terminal on the terminal block and sequentially goes to the right.
• M 3.0 screws are used on the terminal block.
• Use the clips shown below when wiring.
Wiring the trigger
input
6.0 mm or
less
Round-shape
6.0 mm or
less
Fork-shape
The trigger input signals the BL series to start reading.
Turn on the trigger input by supplying 8.5 to 30 VDC between the trigger input ter-
minals.
You can use the “power supply for sensors” terminals of the BL-U1 as the input
power supply.
TIM+12V OUT–
Contact or
+
+
8.5~30VDC
non-contact
85
Page 92
Power Supply BL-U1
TIM
2.4
KΩ
3.3KΩ
Internal circuit
Load
OK/NG
COM
+
Internal circuit
13
25
1
14
D-sub 25-pin connector (female)
DTE specification (defined as terminal)
N 2.6 screw (female)
Wiring the OK/NG
output
Input/output circuit
diagram
Use this output to determine OK/NG status by comparing the readout data with
the preset data. It is NPN open-collector output.
COMOKNG
*Rated load: 30 V max. (100 mA)
Load
Load
+
Input circuitOutput circuit
1.5
RS-232C port pin assignment
Pin No.
1
2
3RD (RXD)
4RS(RTS)
5CS(CTS)
6DR(DSR)
7GND(SG)
20
SymbolDescription
Shield
SD (TXD)
ER(DTR)
Shield
Send data through RS-232C
Receive data through RS-232C
Request to send data through RS-232C
(Always ON)
Enable to send to RS-232C
Connect to pin 20 internally
Signal Ground——
Connect to pin 6 internally
Signal
direction
——
Output
Input
Output
Input
Input
Output
86
Page 93
1.6
RS-232C port wiring
Power Supply BL-U1
When you want to connect the BL-U1 to a PC through the RS-232C port, the wiring is as shown below.
You can use the optional OP-22149 cable (1.5 m) and OP-25057 (25- to 9-pin
adapter).
1.7
RS-422A port wiring
BL-U1
1
2
SD
3
RD
4
RS
5
CS
7
GND
6
DR
20
ER
D-sub 25-pin (male)
M 2.6 screw
PC/AT
1
Shield
2
SD
3
RD
4
RS
5
CS
7
SG
6
DR
20
ER
D-sub 25-pin (male)
M 2.6 screw
When you want to communicate using the RS-422A port, the wiring is as shown
below. Use the BL-U1 input/output terminal block.
Twisted pair cable
BL-U1
SDA
SDB
RDA
RDB
GND
External unit
Shield
RDA
RDB
SDA
SDB
SG
• Set both terminators (terminal resistance 100 Ω ) of the BL-U1 and external
unit to ON (see P. 13).
• The extended cable length must be within 1.2 km.
You can prepare an equivalent cable which meets the following specifications:
Item
Cable type
Logarithm3P
Conductor resistance (20°C)88.0 Ω /km or less
Insulator resistance 10,000 M Ω .km or more
Withdraw voltage500 VDC/minute
Static capacity (1 kHz)60 nF/km or less (average)
Characteristic impedance (100 kHz)110 ± 10 Ω
Shielded cable
Specification
87
Page 94
Power Supply BL-U1
SDA
SDB
SDA
SDB
SDA
SDB
SD/RD+
SD/RD-
RS-232C
PC
*
*
BL-U1BL-U1BL-U1
RS-485/RS-232C convertor
GND
SGSG
SG
Twisted
Shielded cable
BL
BLBL
Convertor
BL
BLBL
Convertor
**
Not applicable
(Connection with branch)
Applicable
(Connection without branch)
Terminator ON
1.8
Wiring the RS-485 (multidrop link)
Multidrop link is a method to connect multiple BL series units to a single PC. See
P. 82 of this document for details. Use the terminal blocks SDA and SDB.
Twisted pair cable
CAUTION
• Up to 31 BL-U1 (BL series) units can be connected in multidrop link.
• The extended cable length must be within 1.2 km.
• Connect the BL-U1 (BL series) to a PC using a commercially available RS-
485/RS-232C convertor.
• For units between the RS-485 (those marked with * in the above figure), turn
ON the terminator.
You can turn the BL-U1 terminator on and off using DIP switch 5. For the terminator of the RS-485/RS-232C convertor, see the instruction manual for the
convertor.
• Do not connect the RS-485 cable through the terminal block.
• Do not connect the multidrop link cables together with the power cable.
• Avoid connection including branch of the BL-U1 and RS-485/RS-232C conver-
tor as shown below.
88
Page 95
2Installation
2.1
Precautions before use
Power Supply BL-U1
Operating environment
Installing the BL-U1
The BL-U1 is a precision instrument. Be sure to install the unit in the proper operating environment, and avoid using the unit under any of the following conditions.
• Exposed to direct sunlight, or where the ambient temperature is below 0°C or
above 50°C for the BL-U1.
• Where the relative humidity is below 35% or above 85%, or where the temperature changes drastically, causing condensation.
• Where corrosive gases, flammable gases, dust, salt, iron particles or oily
smoke may be present.
• Where shock or vibration may occur to the BL unit.
• Where water, oil or chemicals may be spilled or splashed.
• Near any strong magnetic field.
When installing the BL-U1 at the site, consider the following points:
• Reserve sufficient ventilation space at the site.
• If the ambient temperature rises above 50°C during operation, be sure to
install a ventilation fan or cooler.
• Avoid installing the BL-U1 near any high-voltage equipment.
• Keep the BL-U1 away from the power cable.
89
Page 96
Power Supply BL-U1
2.2
Installing the BL-U1
There are two methods for installing the BL-U1:
When installing the BL-U1 directly
Pull out the four screw slots on the rear panel and screw them to the base.
When installing the BL-U1 to the DIN rail
1. Hook the BL-U1 to the DIN rail groove from its top. Push the BL-U1 bottom
4-ø5
150
against the DIN rail until you hear a click.
98
2. Check that the DIN rail mounting notch is shaped like notch A below. If not,
push the BL-U1 further.
OKInsufficient
Fig. AFig. B
3. To remove the BL-U1 from the DIN rail, pull out the notch until its shape turns
from Fig. B to Fig. A. Then, disengage the BL-U1 from the DIN rail.
4. When you want to re-install the BL-U1 to the DIN rail, return the notch from
that of Fig. A to Fig. B.
90
Page 97
3Outline of Multidrop Link
3.1
Multidrop Link
The multidrop link is a communication method to control several BL series readers simultaneously with one host computer as shown in the system configuration
on page 79.
Using the RS-485 cable as the communication path, the multidrop link offers high
noise immunity and enables long-distance transmission. The multidrop link allows
easy wiring using twisted-pair cables (2-wire).
3.2
System Configuration
To use the multidrop link, a BL series reader plus the following equipment is required.
BL-U1
To use the multidrop link, be sure to use this power supply unit.
RS-485/RS-232C converter
To connect a BL series reader to the host computer, the RS-485 signal must be
converted into an RS-232C signal.
Power Supply BL-U1
Host computer
Use a personal computer with an RS-232C interface.
When several BL readers are reading several bar codes, the amount of data to
be processed may exceed the host computer’s capacity.
To prevent this, reduce the number of the BLs connected to the host computer,
or replace the host computer with another one which provides higher data
throughput (including processing of the programming language).
2-wire twisted-pair cable for the RS-485 interface.
Prepare the specified cable (see page 88).
RS-232 cable
Cable used to connect the host computer to the RS-485/RS-232C converter.
Use a cable whose pin assignment conforms to those of the RS-232C connector
of the host computer and the RS-485/RS-232C converter.
91
Page 98
Power Supply BL-U1
4Setup and Connection Procedures
1. BL series setup
Using the Setup software, set the BL series as described below:
• Set the multidrop link to “Enable”.
• Assign ID number 1 to 31 to the connected BL series. Do not assign the
same ID number to different BL series.
• Set the baud rate, data length, parity and stop bit length.
2. RS-485/RS-232C converter setup
Referring to the instruction manual of your RS-485/RS-232C converter, set
the following parameters.
Example
Example
Baud rate: Conforms to the setting of the BL series.
Driver active: AUTO
Terminater: See p. 17.
DTE/DCE selector switch: DTE
3. PC setup
Set the baud rate, data length, parity and stop bit length according to the BL
series’ settings.
4. Connection between the BL series (BL-U1) and the RS-485/RS-232C converter.
To connect the equipment, use the specified cable (see page 88).
5. Connection between the RS-485/RS-232C converter and the host computer
Use a cable whose pin assignment conforms to those of the RS-232C con-
nector of the host computer and the RS-485/RS-232C converter.
When the host computer is an IBM PC/AT compatible, use the KEYENCE
OP-22149 cable (1.5 m).
6. Confirmation of operation
Send a command to the BL series to confirm its operation.
92
Page 99
5Communication
5.1 Outline of Communication types
You can perform all multidrop link communication by sending commands from the
host computer to the BL series.
The communication of the multidrop link is classified into the following two types:
Data communication
For sending read data from the BL-series to the host computer. When data receive commands (polling commands) are sequentially sent to each BL series connected to the host computer, the read data is sent to the host computer.
The read data is stored in the BL series’ transmission buffer, and the data stored
in the transmission buffer is called using the polling command.
Command communication
Using serial communication commands allows direct control of the BL series or
change/confirmation of the BL series’ settings.
Power Supply BL-U1
5.2 Communication Format
All multidrop link communication is done in the following format. Send any command in this format and the BL Series will respond in the format shown below.
<Communication format>
STXmmmnnData/Command/ResponseccETX
DelimiterNo. of dataID No.Contents of dataChecksumDelimiter
123456
Detail of each data:
1, 6 Delimiter: All the data should start with [STX](02h) and should end with
[ETX](03h). This cannot be changed.
2mmm/No. of data: Total number of characters of above data 2 to 5
should be entered. (Do not count [STX] and [ETX].)
When you send [STX][mmm][03][SSET][cc][ETX], for example, the number of characters will be; 3+2+4+2=11Thus, [mmm] is 011.
3nn/ID No.: Specify the ID No. of the BL Series reader you want to send/
receive. ID Nos. should be from 01 to 31.
4Data/Command/Response: Two commands can be used for multidrop
link communication. [P] for polling and [C] for clearing data.
NameCommandResponseDescription
Polling command
Data clear
command
Data is
returned
P
C
if any
data is
stored.
[OK] is returned if
the data is cleared.
[e] is
returned
if no data
is stored.
[OVER] is
returned if
the buffer is
full.
[NG] is
returned if
the data has
been
already
cleared.
Command to ask
whether the BL series’
transmission buffer contains any data.
This command clears
one piece of the sent
data, and completes a
series of data communication.
5cc/Checksum: Add the checksum when you send the data. When the re-
sponse is returned from BL, the checksum follows the data. Determine
the checksum by calculating the Exclusive OR of each data from 2 to 4
as follows.
93
Page 100
Power Supply BL-U1
Example: Data to send is
[STX][008][01][P][cc][ETX]