KEYENCE AP-C40P User Manual

Digital Pressure Sensor
WARNING
SET AP-C40 MODE
MPa
12
Pressure display units
*Apply the units sticker here.
Pressure display
Mode button
Manual adjustment button Set button
Wiring
connector
Sensor head
connector
Mounting screws (M3 x 2)
Operational indicator / Output 1, Output 2
1 2
About 25 mm
About 25 mm
Connector body
Connector
cover
Connector lock
Orange
Brown
Blue
Gray
Pressure
connection
Insert until you hear a clicking sound.
with 2-Color Display
AP-C40(P) Series
Instruction Manual

1. Safety Precautions

96M1402

3. Sensor Head Installation

1) Cut the cable to an appropriate length and strip away about 25 mm of the outermost insulation.
Note: It is not necessary to
remove insulation from the core wires.
2) Insert the cables after aligning them with the colors on the seal on top of the connector body.
3) Press together the body and the connector cover into which the cables were inserted to make a connection (use a pair of pliers or similar tool to press them to­gether).
4) Insert the sensor head connec­tor into the hole of the amp unit. To remove the connector, de­press the connector lock and pull it out.
* Do not reuse sensor head
connectors that have already been pressure-connected.
Do not use this product in safety circuits such as those designed to protect human workers.
This product does not employ an explosion-proof construction. Do not use it in the presence of flammable gasses, liquids, or powders.
This is a direct current power supply type sensor. Application of an alternating current may result in explosion or fire.
Accessories
1 connector cable (2 m)
1 instruction manual

2. Part Names

1 unit scale label
1 sensor head connector

4. About Sensor Head Installation

Common Do not subject the case to pressure sufficient to deform
AP-41(M) • Use a torque of 0.3 N 43 • 44 for the sensor head conduits.
AP-48 Use a torque of 5 N
its shape during installation.
m or lower to tighten the screws
the sensor head conduits. Take care that no foreign objects enter the sensor when opening one of the pressure ports to atmospheric air. Take care not to bend the pressure ports. Connect the “High” port to the high-pressure side of the system and the “Low” port to the low-pressure side.
m or lower to tighten the screws for

5. Mounting Brackets (option)

Dedicated mounting hardware is available for the sensor, allowing it to be installed in a range of locations.
Horizontal mounting bracket Wall mounting bracket
(AP-BO1) (AP-BO2)
Faceplate/ceiling mounting bracket Tilted mounting bracket
(AP-BO3) (AP-BO4)
1
<Output 1>
P1
0
Output 1
OFF ON OFF
P2
0
OFF ON OFF
<Output 2>
Output 2
<Output 1>
P1
H1
Output 1
OFF ON OFF
0
P2
OFF ON OFF
H2
0
<Output 2>
Output 2
Hi
Lo
Output1/Output2
OFF ON ONOFF OFF
<Output 1/Output 2>
0
<Output 1>
P1
Output 1
OFF ON OFF
0
<Output 2>
0
Output 2
OFF ON OFF
P2
0
0
Shift
Zero shift input
T1
<Zero shift>
<Output 1>
P1
Output1
Zero shift input
OFF ON OFF ON
0
<Output 2>
Hi
Lo
Output 2
OFFONOFF OFF
ON
Analog output (1 to 5 V)
0 V
Main
circuit
Blue
Pink
12 to 24 VDC
Main circuit
Pink
Brown
(Short-circuit current 5 mA or less)
AP-AO1 Panel mounting bracket
SET AP-C40 MODE
MPa
Panel mounting ring
Front protective cover
Panel-mounted bodyPanel-mounted bodyPanel-mounted body
Side where the metallic contacts are visible faces up.
Connector cable
12 to 24 VDC
5 to 40 VDC 5 to 40 VDC
0V
Main circuit
Overcurrent
protection circuit
Load Load
Input/output
circuit
Analog output/ zero shift input: switchable
Brown
Blue
Black White
Pink
12 to 24 VDC
0V
Load
Load
Main circuit
Overcurrent
protection circuit
Black White
Pink
Analog output/ zero shift input: switchable
Brown
Blue
Input/output
circuit
(Short-circuit current 5 mA or less)
Main
circuit
Blue
Pink
CAUTION

8. Detection Mode Operation

General-purpose mode (F-1)
This mode allows the user to configure 2 detection points. Control output 1: Turns ON when pressure exceeds setting P1. Control output 2: Turns ON when pressure exceeds setting P2.
SET AP-C33 MODE
MPa

6. Connection Method and Diagrams

Insert the included connector-tipped cable into the sensor's connector. Position the connector so that the side of the connector where the metallic contacts are visible is facing up.
Input/output circuit (AP-C40) Input/output circuit (AP-C40P)
*Hysteresis when operating in general-purpose mode and application
modes 1 and 2 is 0.5% of F.S. in the standard and high-speed modes. During focus mode operation, it is 0.1% of F.S.
Variable hysteresis mode (F-2)
Two detection points may be user-configured, and hysteresis for both may also be set. Control output 1
: Turns ON when pressure exceeds setting P1. Turns OFF
when pressure drops the selected hysteresis amount below P1.
Control output 2:
Turns ON when pressure exceeds setting P2. Turns OFF
when pressure drops the selected hysteresis amount below P2.
Window mode (F-3)
The user may select a pair of upper (Hi) and lower (Lo) thresholds, and the sensor turns OFF when the pressure falls outside of the resulting range. *Control output 1 is 0.5% of F.S. during standard and high-speed
operation, it has a hysteresis of 0.1% of F.S. in the focus mode, and control output 2 has a hysteresis of 0.
Analog output circuit

7. Precautions for Safe Use

Follow these guidelines. Failure to do so may result in product damage.
Zero shift input circuit Zero shift input circuit (AP-C40) (AP-C40P)
Connections
Always ground the frame ground terminal when using an off-the-shelf switching regulator.
Use separate conduits for power line and high voltage lines , since use of a common conduit may result in device malfunction caused by noise .
Improper wiring may result in the device becoming excessively hot or in device damage.
Notice about CE marking
Attach the ferrite core (OP-87505) if you extend a sensor head cable/ amplifier power cable to 3 m or more to use. (Attachment position: within 100 mm from the amplifier unit of a power cable, Number of turns: 2)
Other
Do not use this sensor with corrosive gasses or liquids.
Do not insert objects such as wire into the pressure insertion area. Doing so may result in the device failing to operate properly due to damage to the pressure-sensitive elements.
Do not use sharp-tipped objects to press the setting keys.
Application mode 1 (A-1)
This detection mode is optimum for use in suction detection applica­tions. Recommended heads: AP-41/41M/44 Control output 1:
Control output 2:
Zero shift: Shifts the zero point immediately after setting the zero
P1: Pressure setting for control output 1. T1: Zero shift timer setting (ms) < Variable between 0 and 1,999 ms P2: Pressure setting for control output 2. *P2 is unrelated to zero shift and is always based on the current ambi-
ent pressure.
Application mode 2 (A-2)
This mode is optimum for use in leak test applications. Recommended head: AP-43 Control output 1
Control output 2:
P1: Pressure setting for control output 1. Hi: Upper threshold setting for control output 2. Lo: Lower threshold setting for control output 2. *The Hi and Lo values are unrelated to zero shift and are always based
on the current ambient pressure.
2
Suction pressure detection. Turns ON when pressure exceeds setting P1. Detection of vacuum burst pressure (or confirmation of vacuum arrival pressure). Turns ON when the pressure falls below setting P2. May be set during focus mode operation, although there are restrictions on the setting range.
shift timer once zero shift input is received.
: Leak pressure detection.
Turns ON when pressure falls below setting P1. *Output only when receiving zero shift input. Window comparator output for detection of fill pressure. Turns OFF when pressure falls outside the range deter­mined by upper (Hi) and lower (Lo) thresholds. Fill pres­sure values are displayed with the center pressure as 0 during focus mode operation.
Detection mode
Operating mode
Standard
Focus mode High-speed
Zero shift input Analog output
N.O./N.C.
2.5 msec 5 msec 100 msec 500 msec
General-purpose mode Variable hysteresis mode Window mode Application mode 1 Application mode 2
Analog/zero shift
Standard Eco mode
Power-save
Chatter prevention Sets response time.
* F-1 and F-2 mode only
Values that fall between the P1 and P2 settings will be displayed in green, while values outside that range will be displayed in red.
When
A-1/A-2 is
selected during fixed mode operation
When
operating
mode is
• Two-point tuning
• Active tuning
* High-speed mode provides a 1-ms
high-speed response.
Current value
Reference value
Hold value
Increase the setting.
Decrease the setting.
For other
than
Focus center pressure
After 4 sec
of no key
operation.
Reference value*
Press for 3 sec or more.
+
+
Toggling the display
Manual configuration
Settings are manually configured. The display changes for each mode. * Toggling the
display of settings (see the diagram below).
*
Manual configuration only during F-3/A-2 mode operation.
Current value
Peak hold
Bottom hold
* The reference value is
the pressure value when zero shift input is received and is replaced only when zero shift input is selected.
Mode configuration
* See the Focus Mode section
of Part 10 for the center pressures that can be selected.
N.O. N.O. N.C. N.C.
N.O. N.C.
N.C.
N.O.
Control output 1
Control output 2
• N.O. = normal open.
• N.C. = normal close.
Display color (7-segment)
ON: Red, OFF: Green ON: Green, OFF: Red Normally red Normally green
Within set value: Green Outside set value: Red
()

9. Sensor Configuration

Flashes
for 3 sec.
Setting
Target object
present
Target object
absent
Toggling the display of settings
General-purpose mode/F1
Variable hysteresis mode/F-2
Window mode/F-3
Application mode 1/A-1
Application mode 2/A-2
Two-point tuning (F-1/F-2)
The sensor is made to detect the pressures when the target object is present and then absent for confirmation of target suction pick-up, and the intermediate value is used. Control output 1 configuration: When P1 (H1) is selected on the settings display. Control output 2 configuration: When P2 (H2) is selected on the settings display.
Active tuning (A-1)
See Section 11.
Note:• Press and hold the MODE button ( ) for at least 3 seconds to return to the current
value/reference value/hold value display from each of the mode setting screens.
• Press the left side on the manual adjustment button ( ) while holding down the mode button ( ) to return to the previous display.
• The current value will be displayed based on the ambient pressure conditions prevalent at that time without regard to zero shift input when the P2 setting display is selected for A-1 mode or when the HI and Lo setting displays are selected for A-2 mode.
• The sensor must be configured manually when operating in the F-3/A-2 modes. The SET button ( ) will not function.
3
10
41 43 44 48
-20.0 / -30.0 / -40.0 / -50.0/ -60.0 / -70.0 / -80.0 200 / 300 / 400 / 500/ 600 / 700 / 800
80.0 / 60.0 / 40.0 / 20.0/ 0.0 / -20.0 / -40.0 /-60.0 / -80.0
-80.0 / -60.0 / -40.0 / -20.0/ 0.0 / 20.0 / 40.0 /60.0 / 80.0
0
-0.1MPa O.K.
Zero shift input
Zero shift input
-0.5MPa N.G.
1MPa
Head 1 V to 5 V AP-41/41M 0to-101.3 kPa AP-43 0to+1 MPa AP-44/48 -101.3 to +101.3 kPa
Active 2 point tuning
Active 1 point tuning
Suction
Vacuum burst
P1 P2 T1
Automatic
configuration
_
_
Automatic
configuration
Manual
configuration
_
ApplicationType
P2
P1
Time
Zero shift input
T1
Vacuum
Step 1)
Step 2)
Device operation
with no target object present
Operation
for several
cycles
Operation
for several
cycles
Device operation
with target
object present
Sensitivity difference
display
Sampling
Sampling
Start
Start
Finish
Finish
Target object
present
Setting
display
Sampling
Start Finish
.Explanation of Features
Focus mode
Focus mode increases all display resolutions by a factor of 10.
Normal mode Focus mode
The following focus center pressures can be selected for the models noted in the table below. (Unit: kPa)
* The current value is displayed as ±20% of the F.S. range with the
focus center pressure as the reference value (0).
Zero shift
Zero shift input forces the pressure at that time to be defined as zero. This feature is useful in applications that require the detection of a cer­tain amount of pressure fluctuation without being influenced by changes in the original pressure.
(Example: leak testing) Zero shift input received when a container is filled with air will allow the amount of leak after a certain time to be displayed as negative pressure. This approach eliminates the influence of small variations in the final fill pressure of the container.
The pressure value (reference value) when zero shift input is received can be verified from the current value display by pressing the button to switch to the reference value display. ( ) Press the button once more to return to the current value display.
Analog output
A voltage corresponding to the pressure value is output. * Ambient pressure compensation is also applied to analog output.
Power-save
The value display will be turned off during power-save operation to re­duce the amount of power consumed.
Use of any keys during eco mode operation will revert the sensor to its normal display. The sensor will return to the eco display when there is no key input for a period of 3 minutes.
Switching the display color
Corresponds to either output 1 or output 2 based on which setting dis­play has been selected. * rGr can only be set when either the F-1 or F-2 mode is selected.
Values that fall between the P1 and P2 settings will be displayed in green, while values outside that range will be displayed in red.
11
.Active Tuning
Perform these steps first
Select the setting display as indicated below before performing the tuning procedures. Active 2 point tuning: Select either P1 or T1 for the setting display. Active 1 point tuning: Select P2 from the settings display.
Active 2 point tuning / a tuning method suited for auto­matically configuring suction pick-up detection pressures
The zero shift timer setting is manually configured, and the sensor au­tomatically selects the best pressure setting (P1) for this value.
* When focus mode is being used, the analog output will not be focused.
Peak/bottom hold display
The maximum (minimum) values are displayed continuously after power to the sensor is turned on. The active hold display indicated below is used when the A-1 mode is selected.
How to display hold values/
From current value/reference value display
+ / Activates peak hold display.
+ /Activates bottom hold display. The minimum value during zero shift input is displayed for the bottom hold during A-2 mode operation.
Resetting the peak/bottom hold values/
Pressing for 3 seconds or more while the peak and bottom hold values are being displayed will reset the values. *The values will also be reset when power to the sensor is turned off,
and when the device's detection mode or operating mode is changed.
During A-1 mode operation (active hold display)
The hold values are reset each time the pressure value exceeds (or falls below) the setting, and the peak hold (bottom hold) will then vary from this point.
Peak hold value:
Bottom hold value:
The peak hold value will be reset once a value is encountered that exceeds setting P1, and new peak values will be held from that point.
The bottom hold value will be reset once a value is encountered that falls below setting P2, and new bottom values will be held from that point.
Active 1 point tuning / tuning optimized for vacuum burst detection
The sensor automatically selects the best pressure setting (P2) for vacuum burst detection.
12
.Ambient Pressure Compensation
Open the applied pressure to the surrounding air so that it equals the ambient pressure and press the button for 3 seconds or more while the current value or reference value is being displayed. The ambient pressure point will be corrected. *1 Ambient pressure can be corrected within a range of ±5 % of F.S.
When atmospheric pressure compensation has been performed, the settings will be saved even when power to the sensor is turned off.
*2 Can also be used when operating in focus mode, although for some
center pressures the display will read FFF. (Atmospheric pressure compensation is being performed.)
13
.Key Lock
Disables operations that would modify the sensor’s configuration. Display content can be toggled.
Pressing and holding either or for at least 3 seconds while pressing
button will lock the keypad and cause the display to flash.
* The same key combination will deactivate the key lock feature.
4
14
Detection mode Operating mode N.O./N.C. switching Analog/zero shift
*
Chatter prevention Display color Power-save
Model Rated pressure
range
Pressure resistance Adaptive fluids Pressure type Temperature
characteristics
Pressure port
Ambient temperature Relative humidity Vibration
Shock Resistance
Housing material
Weight
AP-41M/41
AP-43 AP-44 AP-48
0 to 0 to +101.3 to -101.3 to
-101.3 kPa 1.000 MPa -101.3 kPa +101.3 kPa 500 kPa 1.5 MPa 500 kPa 500 kPa
Air, non-corrosive gasses
Gage pressure
Differential pressure
Within ±2 % of F.S. (at 25 °C)
(in temperature range of 0 to 50 °C)
M5 male screw/
PT1/8
M3 male screw (AP-41M)
0 to +50 °C (No freezing)
35 to 85 % RH (No condensation)
10 to 55 Hz, compound amplitude 1.5 mm, 4 hours for each of XYZ axes
1,000 m/s2, 10 times for each of XYZ axes, total 60 times
Case: PBT; Screws: SUS303
7 g (not including cables) / 70 g (including
35 g/98 g
3-m cable) (4.8 g / 67.8 g for AP-41M)
Environmental resistance
Model
Head combination
Power supply voltage
Current consumption
Display method
Configuration/display range *1 Operating status indicators
Standard mode
High-resolution mode Repeatability Hysteresis *2 Display temperature
characteristics Response
(chatter
prevention feature) Zero shift input
Analog output
Ambient temperature
Relative humidity
Vibration
Housing material
Weight Accessories
AP-C40
AP-C40P
AP-41M/41 AP-43 AP-44 AP-48
12 to 24 VDC±10% Ripple (P-P) 10% or less
12 V operation 24 V operation Normal 780 mW (65 mA) or less 1080 mW (45 mA) or less Eco mode 540 mW (45 mA) or less 840 mW (35 mA) or less
3.5 digit two-color 7 segment LED (11 mm character height) Display cycle: 10 times/second
-15 to +110 % of F.S.
Red LED x 2 (supports control output 1 / control output 2)
0.1 kPa
0.001 MPa
0.1 kPa 0.1kPa
0.01 kPa 0.1 kPa 0.02 kPa 0.02 kPa
±0.2 % of F.S.
Variable (standard 0.5% of F.S.)
±1 % of F.S. or less
Selectable from 1, 2.5, 5, 100, 500 ms
(1 ms during high-speed mode operation)
Input time 2 ms or greater (Switchable with analog output.)
NPN open collector Max. 100 mA (40 V or less)
Residual voltage 1 V or less, 2 outputs (NO/NC switchable)
PNP open collector Max. 100 mA (30 V or less)
Residual voltage 1 V or less, 2 outputs (NO/NC switchable)
1to 5 V Output impedance 1 k or less (Switchable with zero shift input.)
0 to +50 °C (No freezing)
35 to 85 % RH (No condensation)
10 to 55 Hz, compound amplitude 1.5 mm, 2 hours for each of XYZ axes
Front case: polysarfun; Rear case: PBT; Front sheet:
polycarbonate; Pressure port: die-cast zinc
Approx. 19 g (not including cables) / Approx. 74 g (including 2-m cable)
Power cord (2-m, connector type) Head connectors, units sticker
Rating
Resolution
Environmental
resistance
NPN output PNP output
NPN output
PNP output
Control output
• No difference in sensitivity (during 2 point tuning/active tuning).
• There is an applied pressure of ±5 % of F.S. during ambient pressure compensation.
• There is no sensor head connected.
• The connection to the sensor head is broken.
• An excess current is flowing to the control output.
• Reading is falling below (exceeding) configuration/display pressure range.
• Reading is exceeding (falling below) configuration/display pressure range.
• When there were not at least 2 shift inputs during active 2 point tuning.
Adjust the air pressure device so that there will be a difference in sensitivity.
(Return to atmospheric pressure.) Repeat atmospheric compensation.
Verify that a sensor head is connected and turn the power on again.
Repair the sensor head disconnection and turn the power to the sensor back on.
Check the load and return it to the rated range.
Return the pressure to the rated pressure range.
Return the pressure to the rated pressure range.
Repeat the active tuning procedure so that there are at least 2 shift inputs.
Display Cause Solution
(1) KEYENCE warrants the Products to be free of defects in materials and
workmanship for a period of one (1) year from the date of shipment. If any models or samples were shown to Buyer, such models or samples were used merely to illustrate the general type and quality of the Products and not to represent that the Products would necessarily conform to said models or samples. Any Products found to be defective must be shipped to KEYENCE with all shipping costs paid by Buyer or offered to KEYENCE for inspection and examination. Upon examination by KEYENCE, KEYENCE, at its sole option, will refund the purchase price of, or repair or replace at no charge any Products found to be defective. This warranty does not apply to any defects resulting from any action of Buyer, including but not limited to improper installation, improper interfacing, improper repair, unauthorized modification, misapplication and mishandling, such as exposure to excessive current, heat, coldness, moisture, vibration or outdoors air. Components which wear are not warranted.
(2) KEYENCE is pleased to offer suggestions on the use of its various Products. They
are only suggestions, and it is Buyer's responsibility to ascer tain the fitness of the Products for Buyer’s intended use. KEYENCE will not be responsible for any damages that may result from the use of the Products.
(3) The Products and any samples ("Products/Samples") supplied to Buyer are not to
be used internally in humans, for human transportation, as safety devices or fail­safe systems, unless their written specifications state otherwise. Should any Products/Samples be used in such a manner or misused in any way, KEYENCE assumes no responsibility, and additionally Buyer will indemnify KEYENCE and hold KEYENCE harmless from any liability or damage whatsoever arising out of any misuse of the Products/Samples.
(4)
OTHER THAN AS STATED HEREIN, THE PRODUCTS/SAMPLES ARE
PROVIDED WITH NO OTHER WARRANTIES WHATSOEVER. ALL EXPRESS, IMPLIED, AND STATUTORY WARRANTIES, INCLUDING, WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PA RTICULAR PURPOSE, AND NON-INFRINGEMENT OF PROPRIETARY RIGHTS, ARE EXPRESSLY DISCLAIMED. IN NO EVENT SHALL KEYENCE AND ITS AFFILIATED ENTITIES BE LIABLE TO ANY PERSON OR ENTITY FOR ANY DIRECT, INDIRECT, INCIDENTAL, PUNITIVE, SPECIAL OR CONSEQUENTIAL DAMAGES (INCLUDING, WITHOUT LIMITATION, ANY DAMAGES RESULTING FROM LOSS OF USE, BUSINESS INTERRUPTION, LOSS OF INFORMATION, LOSS OR INACCURACY OF DATA, LOSS OF PROFITS, LOSS OF SAVINGS, THE COST OF PROCUREMENT OF SUBSTITUTED GOODS, SERVICES OR TECHNOLOGIES, OR FOR ANY MATTER ARISING OUT OF OR IN CONNECTION WITH THE USE OR INABILITY TO USE THE PRODUCTS, EVEN IF KEYENCE OR ONE OF ITS AFFILIATED ENTITIES WAS ADVISED OF A POSSIBLE THIRD PARTY’S CLAIM FOR DAMAGES OR ANY OTHER CLAIM AGAINST BUYER.
In some jurisdictions, some of the foregoing warranty
disclaimers or damage limitations may not apply.
BUYER'S TRANSFER OBLIGATIONS:
If the Products/Samples purchased by Buyer are to be resold or delivered to a third party, Buyer must provide such third party with a copy of this document, all specifications, manuals, catalogs, leaflets and written information provided to Buyer pertaining to the Products/Samples.
E 1101-3

WARRANTIES AND DISCLAIMERS

.Default Mode Settings (Initialization)
The sensor ships with the following configuration.
*Press button 5 times while holding down the button to return the
sensor to its default configuration.
15
.Specifications
Sensor head
16
.Error Displays and Corrective Actions
Error displays during normal operation
* Contact KEYENCE for information about error displays other than those
described above.
Amplifier
*1 During focus mode operation, restricted to focus range. *2 During focus mode operation, standard 0.1% of F.S.
5
Copyright (c) 2002 KEYENCE CORPORATION. All rights reserved. 1402E 1022-2 96M1402 Printed in Japan
6