Ultra-compact Digital
Hold in place
with wrench
(12mm).
Pressure Sensor
AP-C30K (P) Series
Instruction Manual
1. Safety Precautions
WARNING
●
Do not use this product in safety circuits such as those designed to
protect human workers.
●
This product does not employ an explosion-proof construction. Do not
use it in the presence of flammable gasses, liquids, or powders.
●
This is a direct current power supply type sensor. Application of an
alternating current may result in explosion or fire.
???
96M1038
3. Pipe Connections
You can select from one of two pressure ports: one on the back of the
sensor that can accommodate a pipe leading directly away from the back
of the sensor, and one on the side of the sensor to accommodate a pipe
leading away from the sensor at a right angle.
1) The pressure port is 1/8 of NPT. Commercially available air pressure
joints and nipples can be used with the port.
When attaching the joint, use a wrench to hold the pressure port in
place as illustrated below.
2) Attach the included valve plug to the pressure port not being used.
Valve plug with
hexagonal hole
Hexagonal
wrench (5mm)
Hold in place with
wrench (12 mm).
■ Accessories
●
1 connector cable (2 m)
●
1 valve plug with hexagonal hole
2. Part Names
21
SET AP-C33K MODE
MPa
Operational indicator
1 2
Output 1 Output 2
Pressure display unit
*Apply the units sticker here.
Pressure display
Mode button
Manual adjustment button
Set button
Mounting screws
(M3 x 2)
Wiring
connector
Pressure
port (rear)
●
1 unit scale label
●
1 instruction
manual
• Do not use a torque in excess of 10 Nm when tightening the joint.
Doing so may damage the joint.
• Apply sealing tape when attaching the joint in order to prevent air leaks.
4. Mounting Brackets (option)
Dedicated mounting hardware is available for the sensor, allowing it to be
installed in a range of locations.
Horizontal mounting bracket Wall mounting bracket
(AP-BO1) (AP-BO2)
Faceplate/ceiling mounting bracket Tilted mounting bracket
(AP-BO3) (AP-BO4)
Pressure port
(side)
Approx. ± 90°
Substitution bracket (AP-BO5)
1
* Distance between arms is same as the AP-30/40 Series brackets.
AP-AO1 Panel mounting bracket
<Output 1>
P1
H1
Output 1
OFF ON OFF
0
Hi
Lo
Output1/Output2
OFF ON ONOFF OFF
<Output 1/Output 2>
0
<Output 1>
P1
Output1
Zero shift input
OFF ON
OFF ON
0
Panel mounting ring
SET
Front protective
MPa
AP-C33
MODE
cover
Panel-mounted sample
Panel-mounted sample
5. Connection Method and Diagrams
Insert the included connector-tipped cable into the sensor’s connector.
Position the connector so that the side of the connector where the metallic
contacts are visible is facing up.
Side where the metallic
contacts are visible faces up.
Connector cable
7. Detection Mode Operation
■ General-purpose mode (F-1)
This mode allows the user to configure 2 detection points.
Control output 1: Turns ON when pressure exceeds setting P1.
Control output 2: Turns ON when pressure exceeds setting P2.
<Output 1>
P1
0
OFF ON OFF
Output 1
*Hysteresis is a standard 0.5% of F.S. when operating in general-pur-
pose mode and application modes 1 and 2. During focus mode operation, it is 0.2% of F.S.
■ Variable hysteresis mode (F-2)
Two detection points may be user-configured, and hysteresis for both
may also be set.
Control output 1
: Turns ON when pressure exceeds setting P1. Turns OFF
when pressure drops the selected hysteresis amount
below P1.
Control output 2:
Turns ON when pressure exceeds setting P2. Turns OFF
when pressure drops the selected hysteresis amount
below P2.
■ Window mode (F-3)
The user may select a pair of upper (Hi) and lower (Lo) thresholds, and
the sensor turns OFF when the pressure falls outside of the resulting
range.
*Control output 1 is a standard 0.5% of F.S. During focus mode opera-
tion, it has a hysteresis of 0.2% of F.S., and control output 2 has a
hysteresis of 0.
Output 2
P2
Output 2
<Output 2>
P2
0
<Output 2>
0
OFF ON OFF
OFF ON OFF
H2
Input/output circuit Input/output circuit
(AP-C30K/C31K/C33K) (AP-C30KP/C31KP/C33KP)
Brown
Black
Load
White
Load
Blue
Analog output/
zero shift input: switchable
Pink
12 to 24 VDC
5 to 40 VDC
5 to 40 VDC
0V
protection circuit
Main circuit
Overcurrent
Input/output
circuit
protection circuit
Main circuit
Overcurrent
Input/output
circuit
Analog output circuit
Pink
Blue
Analog
output (1 to 5 V)
0 V
circuit
Main
Zero shift input circuit Zero shift input circuit
(AP-C30K/C31K/C33K) (AP-C30KP/C31KP/C33KP)
circuit
Main
circuit
Main
(Short-circuit current 5 mA max.)
Pink
Blue
(Short-circuit current 5 mA max.)
6. Precautions for Safe Use
Follow these guidelines. Failure to do so may result in product damage.
CAUTION
■
Connections
Input/output circuit
●
Always ground the frame ground terminal when using an off-the-shelf
switching regulator.
●
Use separate conduits for power line and high voltage lines, since use
of a common conduit may result in device malfunction.
●
Improper wiring may result in the device becoming excessively hot or
in device damage.
■
Other
●
Do not use this sensor with corrosive gasses or liquids.
●
Do not insert objects such as wire into the pressure insertion area.
Doing so may result in the device failing to operate properly due to
damage to the pressure-sensitive elements.
●
Do not use sharp-tipped objects to press the setting keys.
Brown
Black
White
Load
Load
Blue
Analog output/
zero shift input: switchable
Pink
12 to 24 VDC
Brown
Pink
12 to 24 VDC
0V
■ Application mode 1 (A-1)
This detection mode is optimum for use in suction detection applications.
Recommended sensor heads: AP-C30K/C30KP/C31K/C31KP
Control output 1:
Control output 2:
Zero shift: The zero point is shifted immediately after the zero
P1: Pressure setting for control output 1.
T1: Zero shift timer setting (ms) < Variable between 0 and 1,999 ms>
P2: Pressure setting for control output 2.
*P2 is unrelated to zero shift and is always based on the current ambi-
ent pressure.
<Output 1>
P1
0
OFF ON OFF
Output 1
■ Application mode 2 (A-2)
This mode is optimum for use in leak test applications.
Recommended sensor head: AP-C33K/C33KP
Control output 1
Control output 2:
P1: Pressure setting for control output 1.
Hi: Upper threshold setting for control output 2.
Lo: Lower threshold setting for control output 2.
* The Hi and Lo values are unrelated to zero shift and are always based
on the current ambient pressure.
2
Suction pressure detection.
Turns ON when pressure exceeds setting P1.
Detection and confirmation of vacuum burst pressure
detection (or vacuum ultimate pressure).
Turns ON when the pressure falls below setting P2.
*Cannot be used to detect vacuum burst pressure with
the AP-C31K/C31KP when operating in focus mode.
Standard mode operation only.
shift timer is set following the activation of zero shift
input.
<Output 2>
0
P2
OFF ON OFF
Output 2
Shift
<Zero shift>
0
0
Zero shift input
T1
: Leak pressure detection.
Turns ON when pressure falls below setting P1.
*Output only when receiving zero shift input.
Window comparator output for detection of fill pressure.
Turns OFF when pressure falls outside the range determined by upper (Hi) and lower (Lo) thresholds.
*Fill pressure values are displayed with the center pres-
sure as 0 during focus mode operation.
<Output 2>
Hi
Lo
OFFONOFF OFF
Output 2
ON