All parameter settings are described in detail in the chapter "Configuration".
This operating overview shows all possible parameters of the device series.
Depending on the order specifications or current configuration, any parameters that are not required are hidden.
10.6Binary output (fault signal output master only) ................................... 104
10.7 General characteristic data ................................................................. 105
10.8Approvals / approval marks .................................................................. 107
2012-12-31/00561073 [SCR power switch TYA202]5
Content
62012-12-31/00561073 [SCR power switch TYA202]
1.1Preface
1 Introduction
Please read this operating manual before starting up the device.
B
This operating manual is valid from device software version [256.01.05].
Keep the operating manual in a place that is accessible to all users at all times.
Your comments are appreciated and may assist us in improving this operating
manual.
Phone: +49 661 6003-727
Fax:+49 661 6003-508
The power controller produces the power that is needed at the analog input or
in manual mode. Safety systems independent of the power controller must be
installed. They should additionally switch off the following heating process in
the event of excess temperatures.
The power controller may only be operated using original JUMO semi-conductor fuses.
In the event of replacement, please check that the correct replacement part
has been used.
All necessary settings are described in this operating manual.
Manipulations not described in the operating manual or expressly forbidden
will jeopardize your warranty rights.
If you have any problems, please contact the nearest subsidiary or the head
office.
When accessing the inner parts of the device and returning device modules,
assemblies, or components, please observe the regulations according to DIN
EN 61340-5-1 and DIN EN 61340-5-2 "Protection of electrostatic sensitive devices from electrostatic phenomena". Use only ESD packaging for transport.
Please note that we cannot accept any liability for damage caused by ESD
(electrostatic discharge).
ESD=Electro Static Discharge
1.2Typographical conventions
1.2.1 Warning symbols
Caution
This symbol is used when danger to personnel may occur if the instructions are disregarded or not followed correctly.
Caution
ESD
Dangerous voltage
Hot
surface,
fire hazard
This symbol is used when damage to devices or data may occur
if the instructions are disregarded or not followed correctly.
This symbol is used if precautions must be taken when handling
components liable to damage through electrostatic discharge.
This symbol is used if dangerous voltages will cause an electric shock
if contact with live parts is made.
This symbol is used if burns can result from touching a hot surface.
Do not install any heat-sensitive components or devices close to the
power controller.
82012-12-31/00561073 [SCR power switch TYA202]
1.2.2 Note signs
v
B
Note:
Reference
Footnote
abc
1 Introduction
This symbol is used to indicate particularly important information.
This symbol refers to further information in other manuals, chapters, or sections.
1
Footnotes are remarks that refer to specific parts of the text. Footnotes consist of two parts:
An identification marking in the text, and the footnote text itself.
The identification markings in the text are arranged as sequential
superscript numbers.
1.2.3 Performing an action
Action
instruction
Vital text
Command sequence
h Plug in the
connector
Config. level rController
rOperating mode
1.2.4 Representation
Keys
This symbol indicates that an action to be performed is described. The individual steps are marked by this asterisk.
This text contains important information, and it is vital that you
read it before proceeding.
Small arrows between words are intended to
facilitate faster location of parameters in the
configuration level.
Keys are displayed as symbols or text.
Key combinations are represented by a plus sign.
2012-12-31/00561073 [SCR power switch TYA202]9
1 Introduction
1
UL approval in preparation
2
Load voltage = voltage supply for control electronics
Important information:
Subordinate control loop U
2
, code 100: voltage control.
Subordinate control loop I
2
, code 010: enables partial load failure detection, dual energy management, and current limiting.
Subordinate control loop P, code 001: enables partial load failure detection, dual energy management, current limiting, free-running
economy circuit, and R control.
At a load current of 250 A, observe voltage supply for fan!
vChapter 3.2.5 "Type 709062/X-0X-250-XXX-XXX-XX-25X"
1.3Order details
The nameplate is affixed to the right-hand side of the case.
(1) Basic type
709062 TYA 202 - Three-phase SCR Power Controller in Three-phase Economy Circuit
(2) Version
8Standard with factory settings
9Customer-specific programming according to specifications
(3) National language of display texts
01German (set at factory)
02English
03French
(4) Load current
020 AC 20 A
032 AC 32 A
050 AC 50 A
100 AC 100 A
150 AC 150 A
200 AC 200 A
250 AC 250 A
100 U, U
010 I, I
001 P (can be set to I, I
1
(5) Subordinate control loop
2
2
(can be set to U, U2)
2
or U, U2)
(6) Load voltage
024 AC 24 V
042 AC 42 V
115 AC 115 V
230 AC 230 V
265 AC 265 V
400 AC 400 V
460 AC 460 V
500 AC 500 V
00None
54RS485/422
64PROFIBUS-DP
(1)(2)(3)(4)(5)(6)(7)(8)
/------Order code
709062 /8-01- 100 - 100 - 400 -00- 252 Order example
2
-20 to +15 %, 45 to 63 Hz
-20 to +15 %, 45 to 63 Hz
-20 to +15 %, 45 to 63 Hz
-20 to +15 %, 45 to 63 Hz
-20 to +15 %, 45 to 63 Hz
-20 to +15 %, 45 to 63 Hz
-20 to +15 %, 45 to 63 Hz
-20 to +15 %, 45 to 63 Hz
(7) Interface
(8) Extra codes
252
Relay (changeover contact) 3 A
257 Optocoupler
102012-12-31/00561073 [SCR power switch TYA202]
1.3.1 Scope of delivery
1 operating manual B709062.0
1 SCR power controller in the version ordered
1:1 patch cable
1.3.2 Accessories
ArticlePart no.
Setup program 709061 TYA201
(can also be run for TYA202 power controllers)
USB cable A-connector B-connector 3 m00506252
Mounting set for DIN rail installation:
Type 709062/X-01-20...00555172
Type 709062/X-01-32...00555527
1.3.3 General accessories
1 Introduction
00544869
Semi-conductor
fuses
A semi-conductor fuse is fitted in the power controller to protect the SCR
module. The "LED Fuse" is lit red in the event of a fault.
vChapter 8.2 "Replacing a defective semi-conductor fuse"
ArticleLoad current
I
= I
Super fast semi-conductor fuse 50 AI
Super fast semi-conductor fuse 80 AI
Super fast semi-conductor fuse 80 AI
Super fast semi-conductor fuse 160 AI
Super fast semi-conductor fuse 350 AI
Super fast semi-conductor fuse 550 AI
Super fast semi-conductor fuse 550 AI
nom.
= 20 A00513108
N
= 32 A00068011
N
= 50 A00068011
N
= 100 A00081801
N
= 150 A00083318
N
= 200 A00371964
N
= 250 A00371964
N
N
Part no.
2012-12-31/00561073 [SCR power switch TYA202]11
1 Introduction
1.4Brief description
DeviceThe JUMO TYA 202 represents the consistent development of the JUMO pow-
er controller technology. It switches ohmic-inductive loads using a threephase current economy circuit in star-delta three-phase operation. The microprocessor-controlled power controller shows all parameters in an LCD display
with background lighting and is operated by 4 keys at the front.
ApplicationSCR power controllers are used where larger resistive and ohmic-inductive
loads have to be switched (e.g. in industrial kiln construction and plastics processing). The SCR power controller consists of SCRs connected in anti-parallel, the insulated cooling body, and the control electronics.
MountingSCR power controllers up to a load current of 32 A can either be clipped to a
35 mm mounting rail or fitted to the wall on a mounting plate. Devices with a
load current greater than 32 A can only be mounted on the wall.
Operating
modes
Load typesAll resistive loads and transformer loads are permitted.
Subordinate
control loop
StandardsThe SCR power controllers are in accordance with VDE 0160 5.5.1.3 (5/88)
Advantages- Teach In function for the detection of partial load failure
The TYA 202 works in burst firing mode.
In burst firing mode, the first half-wave can be optimally cut with an adjustable
phase angle so that transformer loads can also be operated.
It is possible to specify a base load or, depending on the device type, set current limiting or resistance limitation for the load.
To avoid high starting currents, a softstart can be set.
Depending on the device type, U, U
dinate control loops. Fluctuations in the mains voltage therefore have no effect
on the control-loop regulation during operation.
and VDE 0106 Part 100 (3/83). The system must be grounded as specified by
the competent energy supplier.
- Network load optimization through dual energy management
- Transmission of the setup data is possible even without voltage supply to
the device (power supply via USB port)
2
, I, I2, or P controls are available as subor-
122012-12-31/00561073 [SCR power switch TYA202]
1.5Standards, approvals, and conformity
Test basis for the device properties is the Low Voltage Directive DIN EN 50178.
Test basis for the EMC Directive is DIN EN 61326-1.
Standard
Electrical connectionDIN VDE 0100
1 Introduction
Protection type IP20 panel-mounting devices
Climatic ambient conditionsClass 3K3
Air temperature and rel. humidityDIN EN 60721-3-3
Storage temperature Class 1K5DIN EN 60721-3-1
Operating conditions
Pollution degree
Overvoltage category
Test voltagesDIN EN 50178
Residual current circuit breakerDIN EN 50178
Electromagnetic compatibility
Emitted interference
Interference resistance
Mechanical tests:
Vibration test 3M2
Toppling test Class 2M1
Labels, identification markingDIN EN 50178, DIN EN 61010-1
ApprovalsStandard
SubmittedUL 508 (Category NRNT)
C22.2 NO. 14-10 Industrial Control Equipment
(Category NRNT7)
DIN EN 60529
DIN EN 50178
2
III
DIN EN 61326-1
Class A - only for industrial use
Industrial requirements
DIN EN 60068-2-6, DIN EN 60721-3-3
DIN EN 60068-2-31, DIN EN 60721-3-2
Can be used for current circuits with a short-circuit current capacity of
≤ 100 kA (the admissible supply voltage must correspond to the nominal
voltage of the SCR power controller).
For system protection, a fuse up to Class RK5 may be used.
Fuse protectionk Fuse protection of the supply lead in accordance with the VDE regulations
k The choice of cable material, the installation, and the electrical connection
of the device must conform to the requirements of VDE 0100 "Regulations
on the Installation of Power Circuits with Nominal Voltages below AC
1000 V" or the appropriate local regulations.
k The electrical connection must only be carried out by qualified personnel.
k An isolating switch should be wired between the voltage supply and the de-
vice to be able to disconnect the device from the voltage supply on all
poles prior to starting internal work.
k Inside the device, safety clearances meet the requirements for double insu-
lation.
When fitting the connecting cable, ensure that the cables are fitted according to regulations and that the safety clearances are maintained.
must be installed when wiring the voltage supply in the power section. The
supply protection can also be achieved by a circuit-breaker in the supply
lead. The circuit-breaker must correspond to the power consumption of the
power controller.
k For UL application, it must be ensured that the fuse for the supply protec-
tion of the control electronics is between 2 A and a maximum of 5 A. This
also applies to the fan connection.
k To protect the power controller in the event of an earth fault, a semi-con-
ductor fuse is installed. In the event of a defect, these may only be replaced
with original JUMO semi-conductor fuses.
vChapter 8.2 "Replacing a defective semi-conductor fuse"
WiringSupply voltage and control cables are to be wired isolated from one another.
For supply protection, fuses (e.g. 2 A Neozed) must also be installed in the
control circuit.
PE connectionh A direct connection must be provided between the PE conductor of the
power controller and the PE conductor of the supply network. Connection
takes place at the PE connection terminal.
The cross section of the PE conductor must be at least as large as the cross
section of the voltage supply conductors to the power section. In the event
that the protective conductor is not a component of the supply lead or its encasement, the selected conductor cross section may not be less than
2.5 mm
conductor is not protected mechanically).
vSee VDE 0100 Part 540
Checkh That the data given on the nameplate (rated load voltage, load current) cor-
2
(for mechanical protection) or not less than 4 mm2 (if the protection
responds to the data for the system.
h That, if the economy circuit configuration is used, the rotary electrical field
has clockwise phasing.
2012-12-31/00561073 [SCR power switch TYA202]15
2 Installation
h That the configuration of the analog inputs, for example, corresponds to the
h The analog input for the default setpoint value only needs to be connected
wiring.
to the master. The slave receives its information via the patch cable.
However, the slave power controller can be disconnected separately by
means of its own inhibit input.
Load connection
PhasingThe voltage supply of the control electronics and the load voltage
Control inputsThe terminal strips for control connections (inputs and outputs) have been laid
h The electronic switch (2 anti-parallel SCRs) is located between the U1 and
U2 terminals.
h Load wiring and cables for control inputs should be routed separately, if
possible.
h Perform connection of supply voltage - SCR power controller - load in ac-
cordance with the wiring diagram and check.
must have the same phase.
out for safe isolation from the voltage supply (SELV). In order not to diminish
this safety isolation, all connected electrical circuits must also have safety isolation. The required auxiliary voltages must be safe extra-low voltages.
2.1.1 Ambient conditions
Incorrect useThe device is not suitable for installation in potentially explosive atmospheres.
Mounting siteThe power controller must be installed in a fire-proof control cabinet.
The cabinet should be vibration-free, free from aggressive media, and free
from dust to prevent the ventilation slots from becoming blocked.
Climatic
conditions
Avoid additional
sources of heat
Power dissipation
- Relative humidity: 5 to 85 % no condensation (3K3 according to EN 60721)
- Ambient temperature range: 0 to 45 °C (3K3 according to EN 60721-3-3)
- Storage temperature range: -30 to 70 °C class 1K5
- Ensure that the ambient temperature at the installation site is not increased
by other sources of heat or heat accumulation.
- Do not mount the power controller too close to the heating process (kiln)
- Avoid direct sunlight.
Occurs as waste heat on the cooling body of the master and slave device and
must be dissipated at the mounting site (e.g. in the control cabinet) in accordance with the climatic conditions.
162012-12-31/00561073 [SCR power switch TYA202]
2.1.2 Filtering and interference suppression
455060
75
20
200
T/°C
150
Load current in A
Reduction at a temperature of 45 °C:
2 %/kelvin
70 %
250
100
50
To prevent radio-frequency interference, such as occurs with a soft start in
phase angle control, electrical apparatus and systems must have interference
suppression implemented.
The control electronics of the SCR power controller correspond to the EMC requirements of EN 61326.
However, electrical modules such as SCR power controllers do not have any
purpose by themselves. They provide a function as part of a complete system
or installation.
Where applicable, the entire load circuit of the power controller must also have
suitable interference suppression filters fitted by the system provider.
There are a number of specialist companies that provide appropriate ranges of
filters to deal with any interference problems. Such filters are normally supplied as complete modules that are ready to be connected.
2.1.3 Permissible load current depending
on the ambient temperature and the installation height
2 Installation
Ambient temperature
2012-12-31/00561073 [SCR power switch TYA202]17
2 Installation
Destruction through overheating:
In the event of operation over a long period at maximum load current, the cooling body and its environment heats up.
For this reason, at ambient temperatures above 45 °C, the maximum load current must be reduced as shown in the image, as the SCR module could otherwise be destroyed.
The master or slave device temperature shown on the display may not exceed
100 °C.
If a device temperature exceeds 100 °C, the message "Warning - high temperature" is displayed.
If a device temperature exceeds 105 °C, the load current is gradually reduced
by 10 % of the rated current each time the temperature increases by one degree.
If a device temperature exceeds 115 °C, the power controller current is completely switched off.
vChapter 8 "Fault messages and alarms"
Installation
height
In the case of air cooling, it must be noted that the effectiveness of the cooling
is reduced the higher up the device is installed. As a result, the current carrying
capacity of the SCR power controller decreases with such a cooler as the installation height increases as shown in the image.
182012-12-31/00561073 [SCR power switch TYA202]
2.1.4 Wall mounting with screws (ex works)
TYA202
20A
TYA202 32A
TYA202 50A
Power controllers with a load current between 20 and 50 A are affixed to a fireproof control cabinet wall with 4 screws. The left-hand hole is more easily accessible in the upper section. Power controllers with a load current between
100 and 250 A are affixed with 6 screws.
2 Installation
2012-12-31/00561073 [SCR power switch TYA202]19
2 Installation
TYA202100A
TYA202
150/200A
TYA202
150/200A
202012-12-31/00561073 [SCR power switch TYA202]
2 Installation
TYA202 250ATYA202 250A
2012-12-31/00561073 [SCR power switch TYA202]21
2 Installation
Hot
surface
The power controller heats up during operation to a maximum of
110 °C, depending on the load.
Ensure that the lamellae of the cooling body are vertically aligned to
allow the heat to be dissipated through natural convection.
Fire hazard:
Do not install any heat-sensitive components or devices close to the
power controller.
Integrated ventilator for 250 A power controller:
The intake air at the ventilation grid of the ventilator may not exceed a maximum supply air temperature of 35 °C. Ensure that the
inlet air for the built-in ventilators can be taken in from below and
escape at the top without obstruction!
2.1.5 Mounting on DIN rail (accessories)
Power controllers up to 32 A can be affixed to a DIN rail using the corresponding accessories.
vChapter 1.3.2 "Accessories"
h Hook the spring clip into the DIN rail from above
h Swivel the power controller downward until the lug engages with the DIN
rail with an audible click.
222012-12-31/00561073 [SCR power switch TYA202]
2.2Dimensions
2.2.1 Type 709062/X-0X-020-XXX-XXX-XX-25X
2 Installation
2012-12-31/00561073 [SCR power switch TYA202]23
2 Installation
2.2.2 Type 709062/X-0X-250-XXX-XXX-XX-25X
242012-12-31/00561073 [SCR power switch TYA202]
2.2.3 Type 709062/X-0X-050-XXX-XXX-XX-25X
2 Installation
2012-12-31/00561073 [SCR power switch TYA202]25
2 Installation
2.2.4 Type 709062/X-0X-100-XXX-XXX-XX-25X
262012-12-31/00561073 [SCR power switch TYA202]
2.2.5 Type 709062/X-0X-150-XXX-XXX-XX-25X
Type 709062/X-0X-200-XXX-XXX-XX-25X
2 Installation
2012-12-31/00561073 [SCR power switch TYA202]27
2 Installation
2.2.6 Type 709062/X-0X-250-XXX-XXX-XX-25X
2.2.7 Clearances (all types)
h Allow a clearance of 10 cm from the floor.
h Allow a clearance of 15 cm from the ceiling.
h When fitted next to each other, no spacing between the units is required.
282012-12-31/00561073 [SCR power switch TYA202]
Loading...
+ 82 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.