PROFIBUS DP
RS422/485
or
serial
70.9062
Power supply
Interfaces
USB interface
for setup program
Binary output
for centralized fault signals via relay or optocoupler
Master-slave communication
Standard signals:
0(2) – 10V, 0(1) – 5V or SSR
TYA 202
Setpoint, analog inputs
Firing pulse inhibit
via floating contact
Load output
Actual value output
- standard signals
LC-D with white backlighting
isplay
Binary inputs
Binary input 2
Power supply
Binäreingang 1 frei konfigurierbar
Binary input 1
freely configurable
Standard signal: 0(4) – 20mA
Extra code
JUMO TYA 202 SCR Power Controller in a three-phase economy circuit
For the continous control of ohmic-inductive loads
The JUMO TYA 202 represents a consistent further development of the JUMO power controller technology and switches ohmic-inductive loads in a rotary current economic circuit. The micro­processor controlled power controller displays all parameters in a back-lighted LCD display and is operated using the 4 keys on the front. SCR power controllers are employed where larger resistive and ohmic-inductive loads have to be switched, e.g. in industrial kiln construction and in plastics processing. The SCR power controller comprises two SCRs connected in anti-parallel, the insulated cooling body and the control electronics. SCR power controllers up to a load current of 32 A can either be clipped onto a 35 mm mounting rail or fitted to the wall with a mounting plate. Units with a load current greater than 32A have to be fitted to the wall. The TYA 202 works in burst-firing mode. In burst-firing mode, the phase angle can be cut back for the first half-cycle, for driving trans­former loads. Available subordinate controls are U, U Use of a subordinate control ensures that fluctuations in the supply voltage do not affect the control loop during the control process. It is possible to preset a base load. To avoid high starting or inrush currents, a soft start function is available. The SCR power controllers comply with the operating conditions according to DIN EN 50178. Grounding is required in conformity with the regulations of the responsible electrical utility company.
Block diagram
Approvals/approval marks (see "Technical data")
2012-12-31/00561069
2012-12-31/00561069
2
, I, I2 and P control.
Data sheet 709062
Page 1/17
Typ 709062/ …
Special features
k LCD display with info line k Simple configuration of the device via
clear text display in the operator's lan­guage
k Setup program for configuration via
USB interface
k Transmission of the setup data is also
possible without voltage supply to the unit (supply via USB port)
k Close installation is possible k Mains load optimization through dual
energy management
k RS422/485 interface or k PROFIBUS DP for connection to
process control systems
k Softstart function with Burst-firing k Burst-firing mode k Resistance monitoring and limitation for
MoSi
heating elements
2
k All versions in protection rating IP20 k Load monitoring for the detection of
partial load failure or load short circuit "teach-in"
k Integrated diagnosis systems such as
rotary-field detection
k UL Approval submitted
Data sheet 709062 Page 2/17
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard Canastota, NY 13032, USA Phone: 315-697-5866
1-800-554-JUMO Fax: 315-697-5867 E-mail: info.us@jumo.net Internet: www.jumousa.com
Control signal
P
Base load: 680 W
Maximum Output level: 3680 W
0 mA
20 mA
3000W 0...20mA
Base load
Technical data
Voltage supply, load current
Code Voltage supply for control electronics = max. load voltage Fan specifications
Type 709061/X-0X-250...
024 AC 24V -20%...+15%, 45 ...63 Hz AC 24V/30VA 042 AC 42V -20%...+15%, 45 ...63 Hz AC 24V/30VA 115 AC 115V -20%...+15%, 45 ...63 Hz AC 115V/30VA 230 AC 230V -20%...+15%, 45 ...63 Hz AC 230V/30VA 265 AC 265V -20%...+15%, 45 ...63 Hz AC 230V/30VA 400 AC 400V -20%...+15%, 45 ...63 Hz AC 230V/30VA 460 AC 460V -20%...+15%, 45 ...63 Hz AC 230V/30VA 500 AC 500V -20%...+15%, 45 ...63 Hz AC 230V/30VA Load current I
L rms
Load type Resistive and resistive/inductive loads Control section power consumption max. 40 VA
Analog inputs
Control signal 0(4) … 20mA R
0(2) … 10V R 0(1) … 5V R
Default set point value
Example P control:
Via standard signals (current, voltage) or interface Base load: Output as minimum control value Maximum control value: Output as maximum control value
AC 20, 32, 50, 100, 150, 200, 250A
= 50 Ω
i
= 25kΩ
i
= 25kΩ
i
Binary inputs
Binary input 1, 2 For connection to potential-free contact or optocoupler, voltage proof up to DC 12V
Binary outputs, actual value output
Relay (changeover contact) without contact suppression
Optocoupler output I Actual value output Switched off as standard.
Thyristor firing re­quest:
setpoint specification Current input
(current proof up to 25mA)
continous The power controller provides the power for the load conti-
nuously depending on the default setpoint value.
logic (Solid State Relais SSR)
2012-12-31/00561069
The power controller acts like a switch and provides the power by either switching ON or OFF. The switching level is always in the middle of the selected input range. At 4 to 20mA it is 12mA, at 0 to 10V it is 5V.
150000 switching actions at a contact rating of 3A/230V 50Hz (resistive load)
Cmax
= 2mA, U
CEOmax
= 32V
For standard signal, voltage: 0 … 10V , 2 … 10 V, 0 … 5V to 1 … 5V For standard signal, current: 0 … 20mA to 4 … 20mA (burden max. 500Ω) Depending on the device type, the output of various internal measuring values such as load current, load voltage or power is possible.
setpoint specification Voltage input (voltage proof up to DC 32V)
setpoint specification Binary input1, 2
(voltage proof up to DC 32V)
-possible
OFF logic level „0“ = 0 to +0,8V; ON logic level 1 = +2 to 3,3V
via Interface
possible
Data sheet 709062 Page 3/17
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard Canastota, NY 13032, USA Phone: 315-697-5866
1-800-554-JUMO Fax: 315-697-5867 E-mail: info.us@jumo.net Internet: www.jumousa.com
General characteristic data
Circuit options - Three-phase economy circuit in master/slave operation Operating modes - Impulsgruppenbetrieb für ohmsche Last oder Trafolast mit Softstart Special features - Dual energy management
- Burst-firing mode with softstart
Subordinate control loop U² control as standard
Can be switched over to U, I, I², P control depending on device type
Electrical connection For type 709062/X -0X-020...
Control and load leads are connected via screw terminals. For type 709062/X -0X-032... Control leads are connected via screw terminals and load leads via cable lugs DIN 46235 and DIN46234 or tubular cable lugs.
Operating conditions The controller is designed as a panel-mounting device according to: EN 50 178,
pollution degree 2, overvoltage category Ü III
Electromagnetic compatibility
Protection rating All device types IP20 according to EN 60 529 Protection rating Protection rating I, with isolated control circuitry for connection to SELV circuits Permissible
ambient temperature range
Permissible storage temperature range
Cooling - Natural convection up to a load current of 200A
Environmental performance Rel. humidity ≤ 85 % annual average, no condensation 3K3 according to EN 60 721 Installation position Vertical Test voltage According to EN 50178 Creepage distances 8 mm between supply current circuit and SELV circuits for type 709062/X -0X-020...
Case Plastic, flammability class UL94 V0, color: Cobalt blue RAL 5013 Power dissipation The power dissipation can be calculated using the following empirical formula:
Maximum temperature of the cooling body
According to DIN 61326-1 Emitted interference: Class B Interference resistance: Industrial requirements
35°C with forced air cooling (250A controller) 0 … 45°C with natural air cooling (extended temperature range class 3K3 according to EN 60 721-3-3) At higher temperatures, operation with reduced type current is possible. (from 45°C with type current -2%/°C)
-30 … +70°C (1K5 according to EN 60 721-3-1)
- For a load current of 250A, forced convection with built-in ventilator
12.7 mm between supply current circuit and SELV circuits from type 709062/X -0X-032... SELV = Separate Extra Low Voltage (safe low voltage)
P
= 2 x (20W + 1.3V x I
v
Load
A)
110°C
Type
20A 32A 50A 100A 150A 200A 250A
(Load current)
Weight approx. 2.2 kg approx. 4.2 kg approx. 5.4 kg approx. 7.6 kg approx. 17 kg approx. 19 kg approx. 20.4 kg
Approvals/approval marks
Approval mark
c UL us Underwriters Laboratories submitted UL 508 All device Versions
2012-12-31/00561069
Testing agency Certificates / certification
numbers
Inspection basis Valid for
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard Canastota, NY 13032, USA Phone: 315-697-5866
1-800-554-JUMO Fax: 315-697-5867 E-mail: info.us@jumo.net Internet: www.jumousa.com
Display and measuring accuracy
12
11
+
Note:
At a device temperature of 105°C, the load current is reduced for each degree of temperature increase. The power controller current is switched off completely at a device temperature of >115°C.
45 50 60
75
20
200
T/°C
150
Load current in A
Reduction at a temperature of 45 °C: 2 %/kelvin
70 %
250
100
50
Note:
In the case of air cooling, it must be noted that the effectiveness of the cooling is reduced the higher up the device is installed. As a result, the current carrying capacity of the SCR power controller decreases with such a cooler as the installation height increases as shown in the image.
All specifications refer to the controller nominal data.
Supply voltage: ± 2,5% Load current: ± 1% Load voltage: ± 1% Power: ± 2%
Data sheet 709062 Page 4/17
Analog input Voltage/current: ±
1%
Analog output
Voltage/current: ± 1%
Load resistance: ±
(for resistive load)
2%
Permissible load current depending on the ambient temperature and installation height
2012-12-31/00561069
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard Canastota, NY 13032, USA Phone: 315-697-5866
1-800-554-JUMO Fax: 315-697-5867 E-mail: info.us@jumo.net Internet: www.jumousa.com
Electrical isolation
AC 3800 V
AC 3800 V
AC 350 V
AC 350 V
PROFIBUS-DP RS422/485orserial interface
Actual value output
standard signal
Voltage output
DC 10 V
Binary output
Relay or optocoupler
Load connection
U1, U2
Display and keypad
Binary input 1, 2
floating contact
USB Interface
Analog input
0(4) 20 mAto
Analog input
0(2) to 10 V, 0 5 V or SSR
to
Voltage supply
»
»
»
»
»
(1)
(2)
(3) (4)
(5)
(7)
(6)
(7)
Display, operation and connection elements
Data sheet 709062 Page 5/17
Legend Remark Fig.
1 LED Power (green) is lit when the voltage supply is connected 2 LCD display with white background lighting (96 x 64 pixels).
3 The LED Fuse (red) is lit when the semi-conductor fuse is blown 4 LED K1 (yellow) fault signal output 5 Keys:
6 USB setup interface
7 Release clip for removing the plastic case (push to the right)
(no LCD display on Slave device) The info line at the bottom of the display indicates current settings and error messages.
Increase value / parameter up
Decrease value / parameter down
Abort / one level back
Programming / one level lower
(no Keys on Slave device)
Konfiguration data is set on the left device and will be transmitted au­tomtaically via 1:1 Patch cable to the right device.
2012-12-31/00561069
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany Phone: +49 661 6003-0 Fax: +49 661 6003-607 E-mail: mail@jumo.net Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House Temple Bank, Riverway Harlow, Essex CM20 2DY, UK Phone: +44 1279 635533 Fax: +44 1279 635262 E-mail: sales@jumo.co.uk Internet: www.jumo.co.uk
JUMO Process Control, Inc.
8 Technology Boulevard Canastota, NY 13032, USA Phone: 315-697-5866
1-800-554-JUMO Fax: 315-697-5867 E-mail: info.us@jumo.net Internet: www.jumousa.com
Dimensions
Type 709062/X-0X-20A-XXX-XXX-XX-25X
Data sheet 709062 Page 6/17
Type 709062/X-0X-032-XXX-XXX-XX-25X
2012-12-31/00561069