All parameter settings are described in detail in the chapter "Configuration".
EXIT
1
1. WLoad monitoring
(Over- or Undercurrent) isset in to Teach in “by Hand”.
2. Code-entry will only appear if, this level was locked previously with a code.
3. Will only appear in the user level
ill only appear if Teach-In for
The user level contains all marked parameters
of the configuration level.
They can be modified during the Operation
without a restart.
Temperature unit
Display contrast
Switch-off Display light
Apply factory settings
Mainsswitch variant
Thyristor control
Operating mode
Subordinate control
Cycle time
Min. ON period
astart
Angle a start
Soft start
Soft start type
Soft start duration
Current limiting
Current limiting value
Resistance limiting
Resistance limit value
Load type Resistance limit
Dual energy management
Current Measuring range
Current range Start
Current range End
Voltage Measuring range
Voltage range Start
Voltage range End
Setpoint input
a - input
a - value
input in the event of an error
value in the event of an error
Maximum output value
Basic load
Limit value monitoring
Limit value Min alarm
Limit value Max alarm
Limit value Hysteresis
Load monitoring
Limit value Load monitoring
Load type
Teach- in type Load monitoring
Load monitoring Teach- in
Mains voltage drop monitoring
Changeover phase control, setpoint input
Ext. Current limitation
Ext.Current Limit value
Key lock
Ext. deactvation display light
Control direction Inhibit input
Control direction Binäry input1
Control direction Binäry input2
Output mode, Control direction Binary output
Changing codes for Manual mode, User level
and Configuration level
Signal type actual value output
Output value
Signal range Start value
Signal range End value
Baud rate, Data format, Device adress,
Min. Response time
Data format, Device adress
PGM
PGM
PGM
PGM
PGM
PGM
EXIT
EXIT
PGM
EXIT
EXIT
Measured value
overview
Load voltage
Load current
Power
Load resistance
Output level
Setpoint
Process value
Phase angle width
Supply frequency
Device temperature
Current input
Voltage input
EXIT
PGM
VDN-No.
Order code
Rated voltage
Rated current
Option current meas.
Option P-Control
Interface
Production number
Te st-ID
2
2
2
3
Navigation principle
one level
back
one level
lower
decrease value/
parameter down
PGM
EXIT
increase value/
parameter up
Alias-device-adress
This operating overview shows all possible parameters of the device series.
Depending on the order specifications or current configuration, any parameters that are not required are hidden.
Read this operating manual before putting the device into service.
This operating manual is valid from device software version [256.02.01].
Keep the operating manual in a place that is accessible to all users at all times.
Your comments are appreciated and may assist us in improving this operating
manual.
Phone: +49 661 6003-727
Fax:+49 661 6003-508
The power controller produces the power that is needed at the analog input or
in manual mode. Safety systems independent of the power controller must be
installed. They should safely switch off the subsequent heating process in the
event of excess temperatures.
The power controller may only be operated using original JUMO semiconductor fuses.
In the event of replacement, please check that the correct spare part has been
used.
All necessary settings are described in this operating manual.
Manipulations not described in the operating manual or expressly forbidden
will jeopardize your warranty rights.
If you have any problems, please contact the nearest branch office or the head
office.
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]7
1 Introduction
E
V
E
When accessing the inner parts of the device and returning device plug-in
units, modules, or components, please observe the regulations according to
DIN EN 61340-5-1 and DIN EN 61340-5-2 "Protection of electronic devices
from electrostatic phenomena". Use only ESD packaging for shipment.
Please note that we cannot accept any liability for damage caused by ESD.
ESD=Electrostatic Discharge
1.2Typographical conventions
1.2.1 Warning symbols
Caution
This character is used if personal injury may result from failure to
follow instructions correctly or not at all!
Warning
ESD
Dangerous voltage
Hot
surface,
fire hazard
This symbol is used when damage to devices or data may result
from failure to follow instructions correctly or not at all!
This character is used if precautionary measures must be taken
when handling electrostatically sensitive components.
This symbol is used if dangerous voltages will cause an electric shock
in the event of contact with live parts.
This symbol is used if burns can result from touching a hot surface.
Do not install any heat-sensitive components or devices close to the
power controller.
8V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
1.2.2 Note symbols
v
V
Note
Reference
Footnote
abc
1 Introduction
This symbol is used to draw your attention to a particular issue.
This symbol refers to further information in other manuals, chapters, or sections.
1
Footnotes are remarks that refer to specific parts of the text. Footnotes consist of two parts:
An identification marking in the text, and the footnote text itself.
The markers in the text are arranged as continuous superscript
numbers.
1.2.3 Performing an action
Action
instruction
Vital text
Command sequence
h Plug in the
connector
READ THE DOCUMENTATION!
This symbol, which is attached to the device, indicates that the associated device documentation must be observed. This is necessary in order to recognize the nature of the potential danger and
take the necessary measures to prevent it.
Config. level rPower controllerr
Operating mode
1.2.4 Display types
This symbol marks the description of a required action. The
individual steps are marked by this asterisk
Small arrows between words are designed
to make it easier to find parameters in the
configuration level.
Keys
Keys are displayed as symbols or text.
Key combinations are represented by a plus sign.
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]9
1 Introduction
Note:
Subordinate control loop U2, code 100: voltage control
Subordinate control loop I2, code 010: enables voltage control, current control, partial load failure detection, dual energy manage-
ment and current limiting, and energy meter
Subordinate control loop P, code 001: enables voltage control, current control, power control, partial load failure detection, dual
energy management, current limiting, r-control and energy meter
At a load current of 250 A, observe voltage supply for fan!
v Chapter 3.2.4 "Type 709061/X-0X-250-XXX-XXX-XX-25X"
1.3Order details
The nameplate is affixed to the right-hand side of the housing.
(1) Basic type
709061 TYA 201 single-phase thyristor power controller
(2) Version
8Standard with default settings
9Customer-specific programming according to specifications
(3) National language of device texts
01German (default setting)
02English
03French
(4) Load current
020 AC 20 A
032 AC 32 A
050 AC 50 A
100 AC 100 A
150 AC 150 A
200 AC 200 A
250 AC 250 A
(5) Subordinate control loop (see note below)
100 U, U
010 I, I
001 P (can be set to I, I
2
2
(can be set to U, U2)
024 AC 24 V -20 ... +15 %, 48 ... 63 Hz
042 AC 42 V-20 ... +15 %, 48 ... 63 Hz
115 AC 115 V-20 ... +15 %, 48 ... 63 Hz
230 AC 230 V-20 ... +15 %, 48 ... 63 Hz
265 AC 265 V-20 ... +15 %, 48 ... 63 Hz
400 AC 400 V-20 ... +15 %, 48 ... 63 Hz
460 AC 460 V-20 ... +15 %, 48 ... 63 Hz
500 AC 500 V-20 ... +15 %, 48 ... 63 Hz
2
or U, U2)
(6) Load voltage
00 None
54RS485/422
64PROFIBUS-DP
84JUMO mTRON T system interface or EtherCAT
a
(7) Interface
(8) Extra code
Relay (changeover contact) 3 A
252
257 Optocoupler
b
(1)(2)(3)(4)(5)(6)(7)(8)
/-----/Order code
709061 /8-01- 100 - 100 - 400 -00/ 252 Order example
a.Load voltage = Voltage supply for control electronics (always select phase voltage L1-L2 from the three-phase system for free-running
economy circuits)
b.Enables energy meter
10V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
1.3.1 Scope of delivery
1 operating manual
1 thyristor power controller in the version ordered
1.3.2 Accessories
ItemPart no.
Setup program 709061 (TYA 201) 00544869
USB cable A-connector B-connector 3 m00506252
Installation kits:
Installation kit for DIN rail 20 A TYA 20100555169
Installation kit for DIN rail 32 A TYA 20100555526
Installation kit for DIN rail 50 A TYA 20100600095
1.3.3 General accessories
1 Introduction
Semiconductor
fuses
A semiconductor fuse is fitted in the power controller to protect the thyristor
module. The "Fuse LED" lights up red in the event of a fault.
v Chapter 8.2 "Replacing a defective semiconductor fuse"
ItemLoad current
= I
I
Super fast semiconductor fuse 40 AI
Super fast semiconductor fuse 80 AI
Super fast semiconductor fuse 80 AI
Super fast semiconductor fuse 160 A I
Super fast semiconductor fuse 350 A I
Super fast semiconductor fuse 550 A I
Super fast semiconductor fuse 550 A I
nom.
= 20 A00513108
N
= 32 A00068011
N
= 50 A00068011
N
= 100 A00081801
N
= 150 A00083318
N
= 200 A00371964
N
= 250 A00371964
N
N
Part no.
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]11
1 Introduction
1.4Brief description
DeviceThe JUMO TYA 201 is an enhancement to JUMO power controller technology.
The microprocessor-controlled power controller shows all parameters on a
display with background lighting and is operated using 4 keys at the front.
ApplicationThyristor power controllers are used where larger resistive and inductive loads
have to be switched (e.g. in industrial furnace construction and plastics processing). The thyristor power controller consists of two anti-parallel switched
thyristors, the insulted heat sink, and the control electronics.
MountingAll thyristor power controllers up to a load current of 32 A can be either
clipped to a 35 mm mounting rail or fitted to the wall on a mounting plate. Devices with a load current greater than 32 A can only be mounted on the wall.
Operating
modes
Load typesAll resistive loads through to inductive loads are permitted.In the case of trans-
Subordinate
control loop
StandardsThe thyristor power controllers comply with VDE 0160 5.5.1.3 (5/88) and VDE
The keypad or setup program is used to select the phase-angle operation
mode with adjustable current limiting, burst-firing operation, or half-wave operation.
In burst-firing mode, the phase angle of the first half-wave can be cut so that
transformer loads can also be operated. In phase-angle operation mode, the
phase angle specified by the controller is slowly reduced, starting from 180
degrees, in order to avoid high inrush currents (soft start).
Users are able to specify a base load or, depending on the device type, select
current limiting or resistance limitation for the load.
former loads, the nominal induction of 1.2 tesla must not be exceeded (value
is 1.45 T in the case of mains overvoltage).
Depending on the device type, U, U
dinate control loops. Variations in the mains voltage therefore have no effect
on the control-loop regulation during operation.
0106 Part 100 (3/83). The devices must be grounded as specified by the responsible energy supplier.
2
, I, I2, or P controls are available as subor-
Advantages- Teach-In function for the detection of partial load failure
- Network load optimization through dual energy management
- Transmission of the setup data is possible even without voltage supply to
the device (power supply via USB port)
-Energy meter
12V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
1.5Standards, approvals, and conformity
Device properties are inspected on the basis of the Low Voltage Directive DIN
EN 50178.
The EMC Directive is inspected on the basis of DIN EN 61326-1.
Standard
Electrical connectionDIN VDE 0100
Protection type IP20 built-in devic-esDIN EN 60529
Climatic ambient conditionsClass 3K3
Air temperature and rel. humidityDIN EN 60721-3-3
Storage temperature class 1K5DIN EN 60721-3-1
Operating conditions
Pollution degree
Overvoltage category
Test voltagesDIN EN 50178
Residual current circuit breakerDIN EN 50178
Electromagnetic compatibility
Interference emission
Interference immunity
Mechanical tests:
Vibration test 3M2
Toppling test class 2M1
Labels, identification markingDIN EN 50178, DIN EN 61010-1
DIN EN 50178
2
III
DIN EN 61326-1
Class A- For industrial applications only
Industrial requirements
DIN EN 60068-2-6, DIN EN 60721-3-3
DIN EN 60068-2-31, DIN EN 60721-3-2
1 Introduction
ApprovalsStandardType
UL 508 (Category NRNT), pollution degree 2
C22.2 NO. 14-10 Industrial Control Equipment (Category NRNT7)
UL 508 (Category NRNT)
C22.2 NO. 14-10 Industrial Control Equipment (Category NRNT7)
Can be used for current circuits with a short-circuit current capacity of
≤ 100 kA (the admissible mains voltage must correspond to the nominal voltage of
the thyristor controller).
For plant protection, a fuse up to class RK5 may be used.
709061/X-XX-032...
709061/X-XX-050...
709061/X-XX-100...
709061/X-XX-150...
709061/X-XX-200...
709061/X-XX-250...
Load current
32 to 250 A
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]13
1 Introduction
14V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
2.1Important installation notes
V
2 Mounting
Safety
regulations
Fuse protectionk Fuse protection of the voltage supply in accordance with the VDE regula-
k The choice of cable material, the installation, and the electrical connection
of the device must conform to the requirements of VDE 0100 "Regulations
on the Installation of Power Circuits with Nominal Voltages below AC
1000 V" or the appropriate local regulations.
k The electrical connection must only be carried out by qualified personnel.
k An isolating switch should be wired between the voltage supply and the de-
vice to be able to disconnect the device from the voltage supply on all
poles prior to accessing the inner parts of the device.
k Inside the device, safety clearances meet the requirements for double insu-
lation.
When mounting the connecting cable, ensure that the cables are fitted according to regulations and that the safety clearances are maintained.
tions must be installed when wiring the voltage supply in the power section.
The supply can also be protected with a circuit-breaker in the supply lead.
The circuit-breaker must correspond to the power consumption of the power controller.
k The connecting cables used for the terminals U1, U2, N/L2, V, and L1 must
have an electric strength of AC 500 V.
k For UL applications, the fuse for the supply protection of the control elec-
tronics must be between 2 A and a maximum of 5 A. This also applies to
the fan connection.
k A semiconductor fuse is installed to protect the power controller in the
event of a ground fault. In the event of a defect, these may only be replaced
with original JUMO semiconductor fuses.
v Chapter 8.2 "Replacing a defective semiconductor fuse"
WiringControl cables (SELV potential) must be routed so that they are isolated from
cables with mains voltage potential. For supply protection, fuses (e.g. 2 A,
Neozed type) must also be installed in the control circuit.
PE connectionh A direct protection conductor connection must be provided between the
power controller and the PE conductor of the supply network. Connection
takes place at the PE connection terminal.
The cross section of the PE conductor must be at least as large as the cross
section of the voltage supply cables in the power section. In the event that the
protective conductor is not a component of the supply lead or its encasement,
the selected conductor cross section may not be less than 2.5 mm
2
chanical protection) or not less than 4 mm
protected mechanically).
v See VDE 0100 Part 540
(if the protection conductor is not
2
(for me-
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]15
2 Mounting
Checkh That the data on the nameplate (rated load voltage, load current) corre-
sponds to the data for the plant.
h That the rotary electrical field has clockwise phasing if the economy circuit
configuration is used.
h That the configuration of the analog inputs, for example, corresponds to the
wiring.
h The analog input for the default setpoint specification in "Master-slave op-
eration" only needs to be connected to the master. The slave receives its information via the 1:1 patch cable.
However, the slave power controller can be disconnected separately by
means of its own inhibit input.
Load connection
PhasingThe voltage supply of the control electronics and the load voltage
Control inputsThe terminal strips for control connections (inputs and outputs) have been laid
h The electronic switch (2 anti-parallel thyristors) is located between the U1
and U2 terminals.
h Where possible, load cables and cables for control inputs should be routed
so that they are isolated.
h Connect the mains voltage - thyristor power controller - load in accordance
with the connection diagram and check.
must have the same phase.
out for safe isolation from the mains voltage (SELV). To prevent the safe isolation from being impaired, ensure that all connected current circuits are also
safely isolated. The required auxiliary supplies must be SELV voltages.
2.1.1 Environmental conditions
Incorrect useThe device is not suitable for installation in potentially explosive areas.
Mounting siteThe power controller must be installed in a fire-proof control cabinet.
The cabinet should be vibration-free, free from aggressive media, and free
from dust to prevent the ventilation slots from becoming blocked.
Climatic
conditions
Avoid additional
sources of heat
Power lossOccurs as waste heat on the power controller's heat sink and must be dissi-
- Relative humidity: 5 to 85 %, no condensation (3K3 according to EN 60721)
- Ambient temperature range: 0 to 45 °C (3K3 according to EN 60721-3-3)
- Storage temperature range: -30 to +70 °C class 1K5
- Ensure that the ambient temperature at the installation site is not increased
by other sources of heat or heat accumulation.
- Do not mount the power controller too close to the heating process (furnace)
- Avoid direct sunlight.
pated at the mounting site (e.g. in the control cabinet) in accordance with the
climatic conditions.
16V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
2.1.2 Filtering and interference suppression
455060
75
20
200
T/°C
150
Load current in A
Reduction at a temperature of 45 °C:
2 %/kelvin
70 %
250
100
50
To prevent radio-frequency interference, generated with a soft start in phaseangle operation for example, electrical apparatus and plants must have interference suppression implemented.
The control electronics of the thyristor power controller comply with the EMC
requirements of EN 61326.
However, electrical modules such as thyristor power controllers do not have
any purpose by themselves. They only serve as a component function within a
plant.
Where applicable, the power controllers's entire load circuit must also have
suitable interference suppression filters fitted by the plant provider.
There are a number of specialist companies that provide appropriate ranges of
interference suppression filters to deal with any interference problems. These
filters are normally supplied as complete modules that are ready to be connected.
2.1.3 Admissible load current depending
on the ambient temperature and the site altitude
2 Mounting
Ambient temperature
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]17
2 Mounting
10002000
40
20
100
site altitude in m
above sea level
80
Ampacity in %
91,4%
60
300040005000
Reduction over 1000m above sea level: 0,86 %/100m
Destruction through overheating:
In the event of operation at maximum load current over an extended period,
the heat sink and its surroundings heat up.
For this reason, at ambient temperatures above 45 °C, the maximum load current must be reduced as shown in the image, as the thyristor module would
otherwise be destroyed.
The device temperature shown on the display may not exceed 100 °C.
At a device temperature of >100 °C, the message "Warning - high temperature" is displayed.
At a device temperature of >105 °C, the output level is gradually reduced by
10 % of the nominal current each time the temperature increases by one degree.
At a device temperature of >115 °C, the power controller is completely
switched off.
v Chapter 8 "Error messages and alarms"
Site altitudeIn the case of air cooling, it must be noted that the effectiveness of the cooling
is reduced as the site altitude increases. As a result, the ampacity of the thyristor power controller decreases with such a cooler as the site altitude increases, as shown in the diagram.
18V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
2.1.4 Wall mounting with screws (default)
TYA201
20A
TYA201
32A
TYA201
50A
Power controllers with a load current between 20 and 50 A are affixed to a fireproof control cabinet wall with 2 screws. The left-hand hole is more easily accessible in the upper section.
Power controllers with a load current between 100 and 250 A are affixed with 4
screws.
2 Mounting
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]19
2 Mounting
TYA201 100A
TYA201 150/200A
20V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
2 Mounting
TYA201250A
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]21
2 Mounting
Hot
surface
During operation, the power controller heats up to a maximum of
110 °C, depending on the load.
Ensure that the lamellae of the heat sink are vertically aligned to allow
the heat to be dissipated through natural convection.
Fire hazard:
Do not install any heat-sensitive components or devices close to the
power controller.
Integrated fan for 250 A power controller:
The intake air at the fan's ventilation grid may not exceed a maximum inlet air temperature of 35 °C. Ensure that the intake air for the
integrated fans can be taken in from below and escape at the top
without obstruction!
2.1.5 Mounting on DIN rail (accessories)
Power controllers up to 50 A can be affixed to a DIN rail using the corresponding accessories.
v Chapter 1.3.2 "Accessories"
h Hook the spring saddle into the DIN rail from above.
h Swivel the power controller downward until the lug engages with the DIN
rail with an audible click.
22V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
2.2Dimensions
2.2.1 Type 709061/X-0X-020-XXX-XXX-XX-25X
2 Mounting
2.2.2 Type 709061/X-0X-032-XXX-XXX-XX-25X
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]23
2 Mounting
2.2.3 Type 709061/X-0X-050-XXX-XXX-XX-25X
2.2.4 Type 709061/X-0X-100-XXX-XXX-XX-25X
24V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
2.2.5 Type 709061/X-0X-150-XXX-XXX-XX-25X
Type 709061/X-0X-200-XXX-XXX-XX-25X
2 Mounting
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]25
2 Mounting
2.2.6 Type 709061/X-0X-250-XXX-XXX-XX-25X
2.2.7 Clearances (all types)
h Allow a clearance of 10 cm from the floor.
h Allow a clearance of 15 cm from the ceiling.
h When fitted next to each other, no spacing between the devices is required.
26V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
3 Electrical connection
(2)X2_
(X2_1)
(X8)
()X3
(U1)
(U2)
(N/L2)
(V)
(L1)
(PE)
Voltage supply
Control electronics
Control section
Power section
Dangerous voltage
3.1Plug-in screw terminals with 20 A
Tools- Flat-blade screwdriver, blade width 2, 3, and 5 mm
3.1.1 Type 709061/X-0X-20-XXX-XXX-XX-25X
The device with a load current of 20 A is connected via plug-in screw terminals.
The electrical connection must only be carried out by qualified personnel! Dangerous voltages will cause an electric shock in the event
of contact with live parts!
h Disconnect the plant from the mains voltage on all poles.
All screw terminals supplied ex works must be inserted and
screwed tight during operation!
V1.04/EN/00561071 [Thyristor Power Switch TYA 201]27
3 Electrical connection
TerminalVersionConductor cross
section
X2_1 and X2_2Slotted screws, blade width 2 mm
X3Slotted screws, blade width 3 mm
U2, N/L2, V, L1, U1Slotted screws, blade width 5 mm
For applications according to UL, only 60 °C or 60 °C / 75 °C copper conductors may be used!
Ground terminal PEM4 setscrew with hexagon
nut
Width across flats 7 mm
0.2-1.5 mm
0.5-2.5 mm
0.5-6 mm
Cable lug with
hole: 4 mm
2
2
2
Maximum
tightening
torque
0.25 Nm
0.5 Nm
0.6 Nm
3Nm
3.2Cable lugs and plug-in screw terminals as of 32 A
Tools- Flat-blade screwdriver, blade width 2, 3, and 5 mm
- Ring or open-end wrench, width across flats 7, 10, 13 mm
28V1.04/EN/00561071 [Thyristor Power Switch TYA 201]
Loading...
+ 95 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.