JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
E-mail: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
E-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax: 315-437-5860
E-mail: info.us@jumo.net
Internet: www.jumousa.com
Panel-mounted Thermostats
ETH Series
Special features
• Version according to DIN EN 14597
• Pressure Equipment Directive 97/23/EC
Brief description
Panel-mounted thermostats ETH monitor thermal processes. The devices are available as
safety-temperature monitors STW (STB) and safety temperature limiters STB. In the event of a
malfunction, the STB switches the monitored machine to a safe operating status.
Panel-mounted thermostats operate according to the fluid expansion principle; a microswitch
is used as an electrical switching element.
Data Sheet 602010
Page 1/7
Approvals/approval marks (see "Technical Data")
Typ e E TH - 2 0
Typ e E TH - 7 0
2013-06-20/00073220
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
E-mail: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
E-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax: 315-437-5860
E-mail: info.us@jumo.net
Internet: www.jumousa.com
Technical data
Switching function
Data Sheet 602010 Page 2/7
Safety temperature monitor
STW
If the temperature on the temperature probe exceeds the set limit value, the electrical circuit is opened
by a snap-action switch. If the temperature falls below the selected limit value
(by the amount of the switching differential), the switch is reset to its initial position.
Restart lock of the safety
temperature limiter STB
If the temperature on the temperature probe exceeds the set limit value, the electrical circuit is opened and the
microswitch is mechanically locked.
The microswitch can be manually unlocked once the dangerous temperature drops by approx. 10 % of the
scale range (approx. 15 % with a limit value setting > + 350 °C).
Use of the safety
The switching circuit following the thermostat must comply with DIN EN 14597 and VDE 0116.
temperature monitor STW
as a safety temperature
limiter STB
Self-monitoring for the
safety temperature limiter
STB and safety temperature
limiter STW (STB)
If the measuring system is destroyed (i.e. if the expansion fluid escapes) the pressure in the membrane of the
STB and STW (STB) drops and permanently opens the electrical circuit. Unlocking is no longer possible.
If the probe has cooled down to a temperature below approx. -20 °C, the electrical circuit is also opened;
when the temperature rises above approx. -20 °C, the STB must be unlocked manually using the restart knob.
The STW (STB) automatically restarts.
Control ranges and temperature probes
Type Control ranges /
limit value ranges
in °C
ETH-20
ETH-70
+30 to +110
+60 to +130
+20 to +150
+50 to +250
+50 to +300
ETH-20
ETH-70
+20 to +400
+20 to +500
+20 to +500
Max. allowable
probe temperature
Liquid-filled
in °C
135
150
175
290
345
Gas-filled
460
575
575
Maximum
capillary length
in mm
5000
1000
2000
4000
Probe length, dimension "L" in mm
Probe−∅ "d" in mm, ∅ "6" = in standard
68
108
116
77
64
55
176
127
202
75
79
60
49
- -
106
81
119
Capillary and temperature probe
Type Scale limit value Capillary Temperature probe Comments
ETH- ..
Up to 200 °C
Up to 350 °C
Up to 500 °C
Up to 350°C
Capillary length Standard 1,000 mm, maximum 5,000 mm
Minimum bending radius of
the capillary
2013-06-20/00073220
Copper (Cu)
ø 1.5mm
Material no. 2.0090
Copper (Cu)
ø 1.5mm
Material no. 2.0090
Stainless steel (CrNi)
ø 1.5mm
Stainless steel (CrNi)
ø 1.5mm
Copper (Cu)
Material no. 2.0090
Hard soldered
Stainless steel (CrNi)
Material No. 1.4571
Stainless steel (CrNi)
Material no. 1.4571
Stainless steel (CrNi)
Material no. 1.4571
5 mm
ø 1.5mm
ø 1.5mm
ø 1.5mm
- -
- -
- -
Available at extra cost
Data Sheet 602010 Page 3/7
JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
E-mail: mail@jumo.net
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
E-mail: sales@jumo.co.uk
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax: 315-437-5860
E-mail: info.us@jumo.net
Internet: www.jumousa.com
Technical data
Electrical data
Switching element ETH-20 ETH-70 ETH-70/U
Microswitch with changeover
contact
Maximum switching capacity AC 230 V +10 %, 10 (2) A, cos ϕ = 1 (0.6), DC 230 V +10 %, 0.25 A
With switching differential 2%
AC 230 V +10 %, 6 (1.2) A,
cos ϕ = 1 (0.6),
Microswitch, gold-plated, extra code /au
AC/DC24V, 0.1A
Contact resistance 2.5 to 10 m
Contact reliability To ensure a high switching reliability, we recommend a minimum load of:
With silver contacts:
AC / DC = 24 V, 100 mAt
Approvals/approval marks
Microswitch with N/C contact and
restart lock
- - - -
Ω
With gold-plated contacts (abbreviation "au":
AC / DC = 10 V, 5 mA
Microswitch with N/C contact,
restart lock, and additional signal
contact
- -
Type Switching
DIN register no. Tests Important note !
function
ETH-20 STW (STB) STW (STB) 799S Pressure Equipment
ETH-70 STB STB 800
Directive 97/23/EC
CE0036
Operating data
Switching differential in %
from the control range / limit
value range
Switching point accuracy in
% of the limit value range
Ambient temperature
influence referring to
the control range / limit value
range
Allowable storage
temperature
Allowable ambient
temperature when in use:
Rated position (NL)
2013-06-20/00073220
Switching function With liquid-filled measuring system
Nominal value Possible actual value
STW (STB) 5 4 max. 6 Standard
9 8 max. 11 Upon request
2 1 max. 3 Extra cost
With liquid-filled measuring system
75 max. 12Standard
9 8 max. 16 Upon request
2 1.5 max. 3 Extra cost
In the upper third of the scale +0/-5 %, at scale beginning +0/-10 %
When the ambient temperature on the switching head deviates from the calibration
ambient temperature of +22 °C, a switching point offset occurs.
Higher ambient temperatures = lower switching point
Lower ambient temperature = higher switching point
Panel-mounted thermostats with scale limit value
< 200 °C ÷ 200 °C ≤ 350 °C > 350 °C ≤ 500 °C
Influence on the switching head
0.17%/K 0.13%/K 0.12%/K
Influence on the capillary per meter
0.054%/K 0.11%/K 0.03%/K
-50 to +50°C
Max. +80 °C
Any
The DIN registry no. will
become null and void if
thermowells are used that are
not specified in our data sheet
606710.