Interlogix NX-650N User Manual

319.5 Crystal MaxLife Door/Window Sensor Installation Instructions

Introduction

These are the 319.5 Crystal Maxlife Door/Window Sensor Installation Instructions for models 60-362N-10-319.5 and
60-362N-11-319.5. Install the sensor (Figure 1 windows, and other objects that open and close. The sensor transmits signals to the control panel when a magnet mounted near the sensor is moved away from or closer to the sensor. The sensor is equipped with a cover tamper microswitch for additional security.
Figure 1. Sensor
Use the following installation guidelines:
Mount the sensor on the door frame and the magnet on the door. For double doors, mount the sensor on the least­used door and the magnet on the most-used door.
Where possible, install sensors within 100 ft. (30 m) of the panel. While a transmitter may have an open-air range of 500 ft. (150 m) or more, the environment at the installation site may have a significant affect on operational range. Changing a sensor location may improve wireless communication.
Line up the alignment mark on the magnet to one of the alignment marks on the sensor.
Mount sensors at least 4.7 in. (12 cm) above the floor to avoid potential damage.
Avoid mounting sensors in areas where they will be exposed to moisture or where the operating temperature range will exceed the specified range.
If possible, mount directly to a stud. If a stud is not available, use plastic anchors.
Avoid mounting the sensor in areas with a large quantity of metal or electrical wiring.
Only one input can be used at any given time.
) on doors,
You must mount the magnet within 3/8 in. (0.95 cm) of the sensor.
Mount sensors with screws, not double-sided tape.
Only install the EOL resistor when an external contact is used.
You will need the following tools and materials:
Two #6 x 1.00 in. PPH (Phillips panhead) screws and two plastic anchors for mounting the sensor (included).
Two #6 x 0.625 in. PPH screws for mounting the magnet (included).
External contact 4.7 Kohm end-of-line (EOL) resistor (included).
• Phillips screwdriver
Caution: You must be free of all static electricity when
handling electronic components. Touch a grounded, bare metal surface before touching a circuit board or wear a grounded wrist strap.

Programming

This section describes general guidelines for programming (learning) the sensor into panel memory. Refer to the specific panel or receiver documentation for complete programming details.
To program the sensor:
1. Remove the sensor cover by squeezing the cover ends firmly releasing the tab (Figure 2
Figure 2. Sensor tab
2. If required, insert the battery into the battery holder, observing correct polarity (Figure 3
) from sensor base slot.
Tab
).
P/N 466-2298 • REV E • January 2011 1
Figure 3.
A
External
Contact Terminals
Battery
holder
Board components
Tamper switch
Positive
Reed B
Reed
Input
jumper
2. Take the sensor to the mounting location.
3. Hold the magnet next to the alignment mark on the sensor (Figure 5
Figure 5. Alignment marks
) and then pull the magnet away from the sensor.
Sensor end view
Sensor side view
3. Set the panel to program mode.
4. Proceed to the Learn sensors menu.
5. Set the external contact in the alarm condition (see
External contact wiring
6. Press and release the tamper switch (Figure 3
).
) on the
sensor until the panel responds.
7. Select the appropriate sensor group and number.
8. Exit program mode.

Input selection

Only one door/window input can be used at any given time. For example, if the external contact is used, internal reed switches (Reed A and Reed B in Figure 3
Note: Power down the device before positioning the input selection.
See Figure 4
and position the input selection jumper to select: Reed B. Left two pins covered (default). Reed A. Right two pins covered. External contact. Jumper removed.
) cannot be used.
Alignment marks
Magnet
4. Listen for siren beeps to determine appropriate response (refer to the specific panel/receiver documentation).
5. Exit sensor test mode.

Mounting

To mount the sensor:

1. Remove the sensor battery.
2. Remove the circuit board from the sensor base by pulling back on the plastic tab.
3. Mount the sensor base using the screws provided (Figure
6).
Figure 6. Mounting holes
Mounting
hole
Wire
entry
Figure 4 Input selection jumper
Mounting
Jumper
location
hole
4. Replace the circuit board.
5. Remove the magnet from its base.
6. Line up the magnet alignment mark with the sensor alignment mark, depending on the internal reed switch
Reed B
(default)
Reed A
External contact
being used (Figure 5
7. Mount the magnet base with the #6 x 0.625 in. PPH
).
screws no more than 3/8 in. (0.95 cm) away from the sensor base (Figure 7
). Replace the magnet cover.

Verifying RF communication

Before mounting the sensor, verify the sensor mounting location provides good RF panel communication.

To verify:

Put the panel/receiver into sensor test mode.
1.
2 319.5 Crystal MaxLife Door/Window Sensor Installation Instructions
7. Mounted sensor
Figure
Magnet Sensor
Door Door frame

Sensor test

The sensor test verifies proper communication between the sensor and the panel/receiver. To test the sensor, refer to the specific panel/receiver documentation and do the following:
1. Put the panel/receiver into sensor test mode.
2. Open the door/window the sensor is protecting. The
sensor transmits a signal.
3. Listen for siren beeps to determine the appropriate
response.
4. Exit sensor test mode.
8. Insert the sensor battery observing correct polarity (Figure
3).
9. Attach the sensor cover to the base.

External contact wiring

Use the following specifications for the external contact:
• Maximum wire length: 26 ft. (8 m).
Wire: Stranded, 22-gauge (0.7112 mm).
Switches: Hermetically sealed external switches (sealed reed switches) that supply a minimum 250 ms open or close on alarm.
Note: Do not connect more than five external contacts to a door/window sensor.
You can wire the sensor terminal blocks with leads from an external contact (Figure 8 alarm and tamper indication. Wire the external contact with one end-of-line (EOL) resistor in series with the external contact.
Caution: You must install the EOL resistor at the external
detection device for proper supervision. For UL listed installations, the EOL resistor must be UL listed, manufactured by Edwards part number EOL-4k7L, and rated 4.7Kohm.
). The door/window sensor provides

Battery replacement

Note: Battery replacement should be done by trained
personnel only. When the system indicates low sensor battery, replace it
immediately. Use the recommended replacement batteries (see Specifications
).

To replace the batteries:

1.
Remove the sensor cover.
2. Remove the battery. Follow local laws for battery disposal.
3. Insert the replacement battery, observing correct polarity (Figure 3
4. Perform a sensor test with the panel. See Sensor test
).
.
Caution: The battery used in this device may present a fire or
chemical burn hazard if improperly handled. Do not recharge, disassemble, heat above 100°C (212°F), or dispose of in fire. Use only batteries listed in the Specifications
section. Use of
another battery may present a risk of fire or explosion.

Troubleshooting

This gives the following readings for each configuration:
Normally closed Zero ohm/short = Tamper
4.7 Kohm = Normal Open = Alarm
Normally open Zero ohm/short = Tamper
4.7 Kohm = Alarm Open = Normal
Figure 8 shows external contact wiring (normally closed and
normally open). For UL listed installations, use only UL listed accessories/contacts.
Figure 8. External contact wiring
Door/Window Sensor
EOL resistor
4.7 Kohm
319.5 Crystal MaxLife Door/Window Sensor Installation Instructions 3
Contacts
This information is provided to help you diagnose and solve various problems that may arise while configuring or using the door/window sensor.

Power up / battery

If the unit does
not power up properly:
Make sure the battery is fully seated within the battery bucket and the polarity is correct.
Check the battery voltage (3.0 VDC nominal).

RF communication

If the control pane
l does not respond:
Use the 60-401 RF Sniffer to make sure the transmitter is sending messages for activation.
Move or rotate the sensor position.

Tamper (cover/external contact)

If a tamper condition does not restore:
Make sure the cover tamper spring is properly installed. The tamper spring must be properly seated into the switch post groove.
Figure 9. Tamper spring
Switch post groove for proper
tamper spring installation
Make sure the proper value end-of-line (EOL) resistor is installed (4700 ohms series resistor).
Figure 10. External contact wiring
Door/Window Sensor
EOL resistor
4.7 Kohm
Contacts
Make sure the EOL resistor is properly seated in the terminal block.
Make sure the terminal block contacts are securely fastened.
Make sure the external contact wiring meets required specification.

Open (reed switch/external contact)

If an open co
ndition does not restore:
Make sure the input selection jumper is in the correct position.
Make sure the arrow on the magnet and the guide line on the transmitter are aligned and within 3/8 in. (0.95 cm) of each other.
Verify that the external contact is operating properly in all conditions of operation.

Specifications

Model number Brown: 60-362N-11-319.5 (NX-651N)
White: 60-362N-10-319.5 (NX-650N) Frequency 319.5 MHz Compatibility Interlogix 319.5 MHz control panels/receivers Battery type 3.0 V, 1300 mAh lithium
Required batteries Duracell DL 123A, Energizer EL123, Sanyo
CR123A
Estimated battery life 5 to 10 years at 20°C (68°F) depending on
the number of activations per day Magnet gap 3/8 in. (max.) Supervisory interval 64 minutes End-of-line resistor 4.7 Kohm Typical RF output
power Operating temperature 32 to 120°F (0 to 49°C) Storage temperature -30 to 140°F (-34 to 60°C) Relative humidity 0 to 85% noncondensing Dimensions (LxWxD) 3.02 x 1.5 x 1.02in. (81 x 38 x 26 mm) Weight 44 g Listings UL 1023, UL 634 Replacement plastics
600-1063-60-362N-10
600-1063-60-362N-11
0.25mW EIRP
D/W sensor 60-362N-10 - 319..5
replacement enclosure, 5 pack, white
D/W sensor 60-362N-11 - 319..5
replacement enclosure, 5 pack, brown

Regulatory information

Manufacturer UTC Fire & Security Americas Corporation, Inc.
1275 Red Fox Rd., Arden Hills, MN 55112-6943, USA
FCC compliance This device complies with part 15 of the FCC
Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
FCC ID: B4Z-914D-DWS IC: 1175C-914EDWS

Contact information

www.utcfireandsecurity.com or www.interlogix.com
For customer support, see www.interlogix.com/customer-
support
Copyright © 2011 UTC Fire & Security. All rights reserved.
4 319.5 Crystal MaxLife Door/Window Sensor Installation Instructions
Loading...