These are the 319.5 Crystal Maxlife Door/Window Sensor
Installation Instructions for models 60-362N-10-319.5 and
60-362N-11-319.5. Install the sensor (Figure 1
windows, and other objects that open and close. The sensor
transmits signals to the control panel when a magnet mounted
near the sensor is moved away from or closer to the sensor.
The sensor is equipped with a cover tamper microswitch for
additional security.
Figure 1. Sensor
Use the following installation guidelines:
• Mount the sensor on the door frame and the magnet on
the door. For double doors, mount the sensor on the leastused door and the magnet on the most-used door.
• Where possible, install sensors within 100 ft. (30 m) of the
panel. While a transmitter may have an open-air range of
500 ft. (150 m) or more, the environment at the installation
site may have a significant affect on operational range.
Changing a sensor location may improve wireless
communication.
• Line up the alignment mark on the magnet to one of the
alignment marks on the sensor.
• Mount sensors at least 4.7 in. (12 cm) above the floor to
avoid potential damage.
• Avoid mounting sensors in areas where they will be
exposed to moisture or where the operating temperature
range will exceed the specified range.
• If possible, mount directly to a stud. If a stud is not
available, use plastic anchors.
• Avoid mounting the sensor in areas with a large quantity of
metal or electrical wiring.
• Only one input can be used at any given time.
) on doors,
• You must mount the magnet within 3/8 in. (0.95 cm) of the
sensor.
• Mount sensors with screws, not double-sided tape.
• Only install the EOL resistor when an external contact is
used.
You will need the following tools and materials:
• Two #6 x 1.00 in. PPH (Phillips panhead) screws and two
plastic anchors for mounting the sensor (included).
• Two #6 x 0.625 in. PPH screws for mounting the magnet
(included).
Caution: You must be free of all static electricity when
handling electronic components. Touch a grounded, bare
metal surface before touching a circuit board or wear a
grounded wrist strap.
Programming
This section describes general guidelines for programming
(learning) the sensor into panel memory. Refer to the specific
panel or receiver documentation for complete programming
details.
To program the sensor:
1. Remove the sensor cover by squeezing the cover ends
firmly releasing the tab (Figure 2
Figure 2. Sensor tab
2. If required, insert the battery into the battery holder,
observing correct polarity (Figure 3
) from sensor base slot.
Tab
).
P/N 466-2298 • REV E • January 2011 1
Figure 3.
A
External
Contact
Terminals
Battery
holder
Board components
Tamper switch
Positive
Reed B
Reed
Input
jumper
2. Take the sensor to the mounting location.
3. Hold the magnet next to the alignment mark on the sensor
(Figure 5
Figure 5. Alignment marks
) and then pull the magnet away from the sensor.
Sensor end view
Sensor side view
3. Set the panel to program mode.
4. Proceed to the Learn sensors menu.
5. Set the external contact in the alarm condition (see
External contact wiring
6. Press and release the tamper switch (Figure 3
).
) on the
sensor until the panel responds.
7. Select the appropriate sensor group and number.
8. Exit program mode.
Input selection
Only one door/window input can be used at any given time. For
example, if the external contact is used, internal reed switches
(Reed A and Reed B in Figure 3
Note: Power down the device before positioning the input
selection.
See Figure 4
and position the input selection jumper to select:
Reed B. Left two pins covered (default).
Reed A. Right two pins covered.
External contact. Jumper removed.
) cannot be used.
Alignment marks
Magnet
4. Listen for siren beeps to determine appropriate response
(refer to the specific panel/receiver documentation).
5. Exit sensor test mode.
Mounting
To mount the sensor:
1. Remove the sensor battery.
2. Remove the circuit board from the sensor base by pulling
back on the plastic tab.
3. Mount the sensor base using the screws provided (Figure
6).
Figure 6. Mounting holes
Mounting
hole
Wire
entry
Figure 4 Input selection jumper
Mounting
Jumper
location
hole
4. Replace the circuit board.
5. Remove the magnet from its base.
6. Line up the magnet alignment mark with the sensor
alignment mark, depending on the internal reed switch
Reed B
(default)
Reed A
External contact
being used (Figure 5
7. Mount the magnet base with the #6 x 0.625 in. PPH
).
screws no more than 3/8 in. (0.95 cm) away from the
sensor base (Figure 7
). Replace the magnet cover.
Verifying RF communication
Before mounting the sensor, verify the sensor mounting
location provides good RF panel communication.
The sensor test verifies proper communication between the
sensor and the panel/receiver. To test the sensor, refer to the
specific panel/receiver documentation and do the following:
1. Put the panel/receiver into sensor test mode.
2. Open the door/window the sensor is protecting. The
sensor transmits a signal.
3. Listen for siren beeps to determine the appropriate
response.
4. Exit sensor test mode.
8. Insert the sensor battery observing correct polarity (Figure
3).
9. Attach the sensor cover to the base.
External contact wiring
Use the following specifications for the external contact:
• Maximum wire length: 26 ft. (8 m).
• Wire: Stranded, 22-gauge (0.7112 mm).
• Switches: Hermetically sealed external switches (sealed
reed switches) that supply a minimum 250 ms open or
close on alarm.
Note: Do not connect more than five external contacts to a
door/window sensor.
You can wire the sensor terminal blocks with leads from an
external contact (Figure 8
alarm and tamper indication. Wire the external contact with one
end-of-line (EOL) resistor in series with the external contact.
Caution: You must install the EOL resistor at the external
detection device for proper supervision. For UL listed
installations, the EOL resistor must be UL listed, manufactured
by Edwards part number EOL-4k7L, and rated 4.7Kohm.
). The door/window sensor provides
Battery replacement
Note: Battery replacement should be done by trained
personnel only.
When the system indicates low sensor battery, replace it
immediately. Use the recommended replacement batteries
(see Specifications
).
To replace the batteries:
1.
Remove the sensor cover.
2. Remove the battery. Follow local laws for battery disposal.
3. Insert the replacement battery, observing correct polarity
(Figure 3
4. Perform a sensor test with the panel. See Sensor test
).
.
Caution: The battery used in this device may present a fire or
chemical burn hazard if improperly handled. Do not recharge,
disassemble, heat above 100°C (212°F), or dispose of in fire.
Use only batteries listed in the Specifications
section. Use of
another battery may present a risk of fire or explosion.
Troubleshooting
This gives the following readings for each configuration:
Normally closed
Zero ohm/short = Tamper
4.7 Kohm = Normal
Open = Alarm
Normally open
Zero ohm/short = Tamper
4.7 Kohm = Alarm
Open = Normal
Figure 8 shows external contact wiring (normally closed and
normally open). For UL listed installations, use only UL listed
accessories/contacts.
Estimated battery life 5 to 10 years at 20°C (68°F) depending on
the number of activations per day
Magnet gap 3/8 in. (max.)
Supervisory interval 64 minutes
End-of-line resistor 4.7 Kohm
Typical RF output
power
Operating temperature 32 to 120°F (0 to 49°C)
Storage temperature -30 to 140°F (-34 to 60°C)
Relative humidity 0 to 85% noncondensing
Dimensions (LxWxD) 3.02 x 1.5 x 1.02in. (81 x 38 x 26 mm)
Weight 44 g
Listings UL 1023, UL 634
Replacement plastics
600-1063-60-362N-10
600-1063-60-362N-11
0.25mW EIRP
D/W sensor 60-362N-10 - 319..5
replacement enclosure, 5 pack, white
D/W sensor 60-362N-11 - 319..5
replacement enclosure, 5 pack, brown
Regulatory information
Manufacturer UTC Fire & Security Americas Corporation, Inc.
1275 Red Fox Rd., Arden Hills, MN 55112-6943,
USA
FCC compliance This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
Changes or modifications not expressly approved
by the party responsible for compliance could
void the user’s authority to operate the
equipment.
FCC ID: B4Z-914D-DWS
IC: 1175C-914EDWS
Contact information
www.utcfireandsecurity.com or www.interlogix.com
For customer support, see www.interlogix.com/customer-