Interlogix 60-836 Installation Guide

Page 1
SuperBus® 2000 Voice Module
Installation Instructions
466-1718 Rev. B
January 2005

Product Summary

The SuperBus® 2000 Voice Module provides voice functions for Concord Concord Express
Using an onboard, digital voice chip, the panel announces status messages through each phone and speaker connected to the module. In addition, a vocabulary of more than 220 words provides easy to understand messages.
The voice module provides feedback for single or muliple-parti­tion panels. For multiple partitions, a module can be used for each partition and connected to a separate speaker.
The module communicates with the panel through the SuperBus 2000
DC supply or an auxiliary 12V DC power supply with backup battery.
Features
The Voice Module includes the following features:

Figure 1. Voice Module Components and Mounting Holes

(v2.0-later), Concord 4™, Concord Express™, and
(v4) panels.
digital databus and may be powered by the panel’s 12V
• User-adjustable, speaker volume control.
• Extensive, 220-plus word vocabulary.
Current Jumper
Status LED

Installation Guidelines

• Use four-conductor, 22-gauge or larger diameter stranded wire to connect the module to the panel.
• Install the module inside the panel cabinet or as close to the cabinet as possible.
• For Concord Express systems, leave the current jumper installed; when installing a Concord (v2.0-later), Concord 4, or Concord Express (v4) panel, remove the current jumper.
• When the current jumper is installed, the voice module draws a maximum 300 mA from panel power supply. When the current jumper is removed, the module draws a maximum of 600 mA from panel power supply.
• When using panel power to supply bus or hardwired devices, do not exceed the panel’s total power output. Refer to specific panel Installation Instructions for further detail.

Tools and Supplies Needed

• Slotted screwdriver
• 3/8”-drive drill and drill bits
• Wire cutter/stripper
• Screws and anchors (included)
• Four-conductor, 22-gauge or larger stranded wire
• Support standoff (included with Concord cabinets)
• 1/4” press-fit reed switch and magnet (not included)

Installation

The module can be mounted...
• On a wall.
• Inside a Concord, Concord 4, Concord Express, or Concord Express (v4) cabinet.
• Inside a Concord Expansion Enclosure. Refer to specific cabinet Installation Instructions for procedures.
SuperBus Device
ID Label
J 2
+ 1 2 V
B U S B
B U S A
G N D S P K 1
Magnet Clip
Mounting Holes (3)

Table 1. Module Component Descriptions

Component Function
Device ID Label Identifies a unique device ID number.
Status LED Flashes to indicate normal panel communication.
Wiring Terminals Provides panel and speaker connections.
Current Jumper Reduces current consumption to 300 mA.
S P K 2 A U D 1
A U D 2
Wiring Terminals
Reed Switch
Holder
CAUTION
CAUTION
To prevent damage to the panel or module, remove the panel’s AC power transformer and disconnect the backup battery before installation.
You must be free of static electricity when handling electronic components. Touch a bare metal surface before touching the circuit board.
Mounting the Module on a Wall
1. Remove the module cover (see Figure 2).

Figure 2. Removing the Module Cover

Press down and
pull away from base
Page 2
2
SuperBus® 2000 Voice Module Installation Instructions
2. Place the backplate on the wall and mark the three mounting holes (see Figure 1).
3. Drill for the mounting holes and insert appropriate anchors.
4. Secure the backplate to the wall with the included screws.
Mounting a Module in a Concord, Concord 4, or Concord Express (v4) Panel
1. Remove the panel’s AC power transformer and disconnect the backup battery.
2. Remove and discard the module cover (see Figure 2).
3. Insert support standoffs on to the panel circuit board (see Figure 3).

Figure 3. Support Standoff

Panel End
Module End
4. Slide the module backplate on to the clips located in the cabinet’s center or top-left corner (see Figure 4).
Note: The mounting clips in the top-right corner of the cabinet
are designed for a receiver module. If a receiver module is not in use, the mounting clips may be used for the voice module.
5. Push the lower-right corner of the module on to the support standoff (see Figure 4).

Figure 4. Mounting the Module in a Concord, Concord 4, or Concord Express (v4) Cabinet

Mounting Clips (6)
Mounting the Module in a Concord Express Panel
1. Remove the panel’s AC power transformer and disconnect the backup battery.
2. Remove and discard the module cover (see Figure 2).
3. Position the module over the cabinet mounting holes so the terminals are to the left (see Figure 5).
4. Secure the module to the cabinet with the mounting screws.

Figure 5. Mounting the Module in a Concord Express Cabinet

Wiring

Wiring the Voice Module includes the following:
• Running required wires for power, bus, and speaker communications.
• Connecting module wires for use in a Concord system.
For power and bus connections, route a four-conductor, 22-gauge or larger diameter stranded wire from the module to the panel (see Table 2 for wire length limits). Route a two-conductor, 22­gauge or larger stranded wire cable from the module to the speaker.
Side Tab
Mounted Module
Panel Cabinet
Support
Standoff

Table 2. Maximum Bus and Power Wire Lengths

Wire Gauge Maximum Length
18 120 feet
22 40 feet

Table 3. Maximum Speaker Wire Lengths

Wire Gauge Maximum Length
18 440 feet
22 175 feet
Page 3
3
Wiring Connections for Concord, Concord 4, and Concord Express (v4) Panels

Figure 6. Wiring Module and Speaker - Concord, Concord 4, or Concord Express (v4) Panels

Concord Module Wiring Connections
Module Terminals
B U S
+ 1 2 V
A
1 2
4 5
3
G N D + 1 2 V
Panel Terminals
B U S
B
3 4
B U S
A
Hardwire Interior Speaker (60-528)
S P K 1
G N D
6
B
S P K 2 A U D 1
5 6
Not Used
7 8
7
* for Partition 1 Only
Wiring Connections for Concord Express Panels

Figure 7. Wiring Module and Speaker in a Concord Express Panel

Concord Express Module Wiring Connections
Hardwire Interior Speaker (60-528)
Not Used
A U D 2
Once programmed, if someone opens the module cover, the tamper switch opens and causes an alarm.
The reed switch holder and magnet clip are located on the bottom of the backplate (see Figure 1).
1. On the module’s backplate, place the reed switch into the reed switch holder.
2. Remove the magnet clip from the module backplate and insert the magnet into the tabs on the module cover. Next, press the magnet clip over the magnet until the clip locks into place (see Figure 8).
3. Connect the normally closed reed switch (in series with a 2k Ohm EOL resistor) to any zone input and zone common terminal (see Figure 8). The resistor should be located inside the module cover at the reed switch.

Figure 8. Installing the Reed Switch

8
To Input
Zone
Module Backplate
Magnet Clip
Reed Switch
2k Ohm EOL Resistor
(49-467)
Module Cover
Magnet

Power Up and Bus Communication

Module Terminals
+ 1 2 V
1 2 3 4 5 6 7 8
3
G N D + 1 2 V
Panel Terminals
B U S
B U S
B S P K 1
A
4 5
G N D
6
B
B U S
A
S P K 2 A U D 1
A U D 2

Installing a Cover Tamper Switch

If you do not mount the module inside a cabinet, it is recom­mended that you add a cover tamper switch.
To mount a tamper switch, first install a UL listed 1/4-inch press­fit reed switch on the module backplate. Next, wire the switch to any unused panel, module, or SnapCard™ zone input terminal.
For Concord, Concord 4, and Concord Express (v4) Panels
Note: To enter the panel’s program mode and verify unit
numbers, an alphanumeric touchpad must be connected to all Concord panels.
When powering the system and verifying bus communication, follow the procedures listed below.
1. Verify that panel, touchpad, and module wiring is correct.
2. Connect the panel’s backup battery and plug in the AC power transformer. An alphanumeric touchpad display appears.
3. Verify the module’s status LED flashes.
4. If desired, enter the panel’s program mode to verify if a device ID exists (see panel specific panel Installation Instructions for further detail).
Note: If the status LED does not flash, unplug the panel’s AC
power transformer and disconnect the backup battery.
Replacing Module Cover/Closing Cabinet
• If the Voice Module is mounted on a wall, replace the cover.
• If the Voice Module is mounted in a cabinet, close the cabinet door.
Page 4
4
SuperBus® 2000 Voice Module Installation Instructions

Testing and Troubleshooting

If the module’s status LED remains off:
1. Enter the panel’s program mode to verify the panel recog­nizes the module (see specific panel Installation Instruc- tions).
2. Inspect for proper wire connections.
3. Ensure the panel’s AC power transformer is plugged in and the backup battery is connected.
4. If the status LED remains off, replace the module.

Specifications

Compatibility Concord, Concord 4, Concord Express, and
Power Requirements 12V DC nominal; 600 mA maximum; 300 mA
Operating temperature 32° to 120°F (0° to 49°C) Storage temperature 30° to 140°F (-34° to 60°C) Max. relative humidity 90%, non-condensing Dimensions 5.25” x 4.125” x 1.0” (L x W x D) UL Listings (Ancillary use only) UL 985 Household Fire Warning System Units
Concord Express (v4) panels.
with Jumper installed.
UL 1023 Household Burglar Alarm System Units

Notices

FCC Part 15 Information to the User
Changes or modifications not expressly approved by GE Security can void the user’s authority to operate the equipment.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy, and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does not cause harmful interference to radio or televi­sion reception (which can be determined by turning the equipment off and on), the user is encouraged to correct the interference by one or more of the followig measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the affected equipment and the panel receiver to separate outlets on different branch circuits.
• Consult a dealer or experienced radio/TV technician for help.
GE Security 1275 Red Fox Road Arden Hills, MN 55112
www.gesecurity.com
Technical Support T: 800.777.2624 F: 651.779.4890
Loading...