Interlogix 60-758 Installation Guide

Page 1
4 Output Expansion
CAUTION
CAUTION
MOUNTING
SCREW
HOLES (2)
8543117A.DSF
RELAYS (4)
WIRING
TERMINALS
PANEL
CONNECTOR
4 RELAY OUTPUT
EXPANSION SNAPCARD
OPTIONAL
EXPANSION CARD
CONNECTOR
OPTIONAL
EXPANSION CARD
CONTROL PANEL
CIRCUIT BOARD
(2)
ALIGN BOARD
HOLES WITH STANDOFFS
SnapCard
ITI Part No. 60-758
Document Number: 466-1366 Rev. C November 2000

Product Summary

The Four Output Expansion SnapCard™ lets you control devices by adding hardwire outputs to a Concord, Concord Express, or Advent panel.
This card can be installed into the Concord and Concord Express expansion connector. On Advent panels this card can be installed into the primary or secondary expansion connector and in combination with other expansion cards.
The card includes four “Form C” dry contact relays. The relays are controlled by a touchpad or a combination of states and events in the system.
Outputs may be programmed to turn on lights, open drapes and garage doors, turn on a closed-circuit-TV (CCTV) cam­era during a burglary ala rm, turn exi t ligh ting on duri ng fire alarms, and activate backup cellular phones or long-range radios if primary communications are inoperable.

Installation Guidelines

8543122A.DSF
Installation Instructions

Installation

Use the following instructions to install the card, wire the output devices, and program the panel.

Figure 1. Card Components

Refer to the specific panel Installation Instructions for Use 4-conductor, 22-gauge or larger stranded wire from All Advent fire panel wiring shall be in accordance

Tools Needed (optional)

Screwdrivers 22-gauge or larger stranded hookup wire Mounting screws (included)
wire length limits.
the terminals to the devices.
with NFPA codes and standards.
Important !
On Advent panels SnapCard expansion connectors must be used fo r either fire or bu rglary applicatio ns. Do not mix fire and burglary applications on SnapCard inputs and outputs.
To prevent damag ing the pane l or card, disc onnect the panel AC Power and the backup battery(s) before installation.

1. Unplug the panel AC power transformer and disconnect the backup battery(s).

You must be free of all static electricity when handling electronic components. Touch a grounded bare metal surface before touching the circuit board.
2. Align the card holes with the standoffs and connector pins as shown in Figure 2, 3 or 4 (depending on panel type).

Figure 2. Installing the Card in a Concord Panel

1
Page 2
Installation
)
D
Table 1 describes each SnapCard terminal. Terminals are numbered left to right. Figure 5 shows how to wire the card.
Note
All terminals are Class 2 power limited. Auxiliary power supplies must be power limited.
Table 1: Wiring Terminal Descriptions
PUSH SNAPCARD CONNECTOR ONTO PANEL HEADER
SECURE SNAPCARD WITH TWO SCREWS
Figure 3. Installing the Card in a Concord Express
Panel
SECONDARY EXPANSION
CARD CONNECTOR
PRIMARY EXPANSION
CARD CONNECTOR
CONTROL PANEL
CIRCUIT BOARD
ALIGN BOAR
HOLES WITH STANDOFFS
EXPANSION CARD

Figure 4. Installing the Card in Advent panel

(2
8543G86B.DSF
Terminal
Number

Description

Use
1 Relay 1 NC Normally closed (N/C) (ope ns on
activation) output 1 dry relay contact connection.
2 Relay 1
COM
Common (C) side of output 1 dry relay N/C and N/O contacts (terminals 1 and 3). Contacts rated 4A @ 24VDC, 4A @ 24VAC, 1A @ 70VAC maximum.
3 Relay 1 NO Normally open (N/O) (closes on
activation) output 1 dry relay contact connection.
4 Relay 2 NC Normally closed (N/C) (ope ns on
activation) output 2 dry relay contact connection.
5 Relay 2
COM
Common (C) side of output 2 dry relay N/C and N/O contacts (terminals 4 and 6). Contacts rated 4A @ 24VDC, 4A @ 24VAC, 1A @ 70VAC maximum.
6 Relay 2 NO Normally open (N/O) (closes on
activation) output 2 dry relay contact connection.

3. Press firmly to secure the card to the connector.

4. Secure the card to the cabinet with the two supplied screws.

Wiring

Note
A) Class 2, Class 3, and power-limited fire alarm cir­cuits must be installed using FPL, FPLR, FPLP, or substitute cable permitted by the National Electrical Code ANSI/NFPA 70. Wire that extends beyond the cable jacket m ust be separated from all other conduc­tors by a minimum of 1/4-inch or by a nonconductive barrier. OR (B) Class 2, Class 3, and power-limited fire alarm cir­cuit conductors must be installed as Class 1 or higher circuits.
2
7 Relay 3 NC Normally closed (N/C) (ope ns on
activation) output 3 dry relay contact connection.
8 Relay 3
COM
Common (C) side of output 3 dry relay N/C and N/O contacts (terminals 7 and 9). Contacts rated 4A @ 24VDC, 4A @ 24VAC, 1A @ 70VAC maximum.
9 Relay 3 NO Normally open (N/O) (closes on
activation) output 3 dry relay contact connection.
10 Relay 4 NC Normally closed (N/C) (opens on
activation) output 4 dry relay contact connection.
11 Rela y 4
COM
Common (C) side of output 4 dry relay N/C and N/O contacts (terminals 10 and 12). Contacts rated 4A @ 24VDC, 4A @ 24VAC, 1A @ 70VAC maximum.
12 Relay 4 NO Normally open (N/O) (closes on
activation) output 4 dry relay contact connection.
Page 3

Programming

Table 1: Wiring Terminal Descriptions
Terminal
Number
13 GND Common ground return
14 +12VDC Auxiliary output regulated DC
Description
Use
connection for 12 VDC supply output.
power supply. 12 VDC @ 0.5A maximum.
Note: If this output is used, it will draw up to 500 mA from the panel. Remember to include this current draw when calculating total panel power.

To wire the card:

1. Unplug the panel AC power transformer and disconnect the backup battery(s).

2. Wire output devices to the card as shown in Figure 5.

3. Connect the backup battery(s) and plug in the panel AC power transformer.

Programming
Outputs must be programmed to communicate with the panel and to function as desired. For specific output pro­gramming information, refer to the panel Installation Instructions.

Testing

Once installed, the card becomes an integral part of the panel. W e recommend that you test all hardwire output devices after programming is completed and whenever an output device-related problem occurs. Refer to the panel Installation Instructions or User’ s Manual for output testing information.

Troubleshooting (all panels)

Table 2: Troubleshooting Hardwire Outputs

Problem Action/Solution

No outputs activate
One output never activates.
Wrong output activates.

1. Check panel/card programming.

2. Check output wiring and connections.

3. Check panel/card power supplies.

4. If used, check the optional external supply powering the output devices.

1. Check panel/card programming for that output.

2. Check output wiring and connections.

3. Check that the outpu t p ro gr ammed tr ig­ger event actually occurs.
4. An output relay may have failed or been overloaded. Reprogram to use a different (unused) output or replace the card.

1. Check panel output programming.

2. Check output device wiring and con­nections.
4 OUTPUT EXPANSION
SNAPCARD TERMINALS
NC
4
RELAY 2
NO
COM
6
5
NOTE: DO NOT EXCEED OUTPUT RELAY CONTACT R ATINGS
RELAY 3
NC
* 0.5 AMP MAX. DO NOT EXCEED POWER SUPPLY CAPACITY.
RELAY 1
NC
1
OUTPUT DEVICE
TYPICAL OUTPUT DEVICE
APPLICATION
8588G01B.DSF

Figure 5. Typical 4 Output Expansion SnapCard Wiring

COM
2
CONTROL
(NO)
NO
3
NO
12
limiting resistor)
0.5A MAX
2.0k Ohm 1/2 W
(current
RELAY 4
NC
COM GND
NO
COM
11
10987
TYPICAL LED
INDICATOR APPLICATION
+12V
1413
*
LED
3
Page 4

Specifications

Specifications
Compatibility: Concord, Concord Express, and
Advent panels.
Power Requirements: (From host panel/module) 12 VDC
@ 142 mA typical with all relays energized (34 mA per relay ener­gized).
Outputs:
Storage Temp: -40° to 140° F (-40° to 60° C). Operating Temp: 32° to 140° F (0° to 60° C) under
Maximum Humidity: 90% relative humidity,
Dimensions: 2.0” x 5.25” x 0.75” (H x W x D). Installation: In panel cabinet mounting. Listings
(for ancillary use only):
Four, panel prog rammab le outputs wi th “Form-C” relay contacts (COMMON, N/C, N/O). Relay contacts rated 4A @
24VDC, 4A @ 24VAC, 1A @ 70VAC maximum.
One 12 VDC, 500 mA regulated power output (from the panel) Power limited to 6 watts.
temporary conditions.
noncondensing.
UL 985 Household Fire Warning System Units

Notices

FCC Part 15 Information to the User
Changes or modifications not expressly approved by Interactive Tech­nologies, Inc. can void the user’s authority to operate the equipment.
FCC Part 15 Class A
This equipment has been tested and found to comply with the limits for a class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environ­ment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instru ctio n manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interfer­ence in which case users will be required to correct the interference at their own expense.
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protectio n against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and receiver. Connect the affected equipment and the panel receiver to separate
outlets, on different branch circuits.
Consult the dealer or an experienced radio/TV technician for help.
UL 864 Control Units for Fire Protective Signaling Devices.
UL 1023 Household Burglar-Alarm System Units
UL 1610 Central-Station Burglar­Alarm Units (Commercial Burglary)
ULC Canada Commercial Fire/B ur­glary Warning System
CSFM California State Fire Marshall
Note
See specific panel complete UL installation requirements for the system you are installing.
Installation In st ruct ions
for
2266 Second Street North North Saint Paul, MN 55109-2900 T: 651/777-2690 F: 651/779-4890 1-800-777-1415 www.itii.com
© 2000 Interlogix, inc. Interlogix, SnapCard, Concord, and C oncord Express are trademarks of Interlogix, Inc. ITI, SuperBus, and Advent are registered trademarks of Interlogix, inc.
4
Loading...