The SuperBus 2000 Energy Saver Mod ule (ESM) pr ovides a
money-saving and convenient way to monitor and control
temperatures. The ESM uses low- and high-temperature
limits to save energy by overriding the existing HVAC thermostat. When the ESM is on, temperature limits determine
when the heat or air-conditioning turns on. When the ESM
is off, the HVAC thermostat controls heat and air-conditioning.
For example, if the thermostat is set for 68°F and the ESM
high limit is 80°F, the ESM prevents the air-conditioner
from turning on until the temperature reaches 80°F. The
ESM limits may be set between 40° and 90°F.
A temperature sensor monitors the temperature and reports
a freeze alarm to the panel if the temperature drops below
the set freeze temperature (default = 42°F). A backup freeze
stat provides additional protection by activating the fur nace
if the temperature drops to 45°F (±6°F).
Note
Depending on where the ESM is located, additional
freeze sensors may need to be placed throughout the
residence to provide adequate freeze protection.
This device is backward compatible with Concord™ panels
with software versions 1.0–1.6 and UltraGard™ panels.
vs.
SuperBus 2000
Compatible panels (SuperBus 2000) have the ability to
auto-address module unit numbers. When the panel is powered up, the panel automatically reads the unique SuperBus
2000 device ID number and assigns a unit number to the
module. This eliminates manually setting DIP switches and
the chance of identical unit number conflicts.
Non-Compatible panels (SuperBus) communicate with
SuperBus 2000 modules but require the module unit number to first be set manually using DIP switches.
SuperBus 2000 Panels
❑Concord (sof tware version s 2.0 and later)
SuperBus Panels
❑UltraGard
❑Concord (software versions 1.0–1.6)
SuperBus
8841G01A.DS4
Installation Instructions
Figure 1 shows the main ESM components and Table 1
describes them.
BACKUP
FREEZE
STAT
SUPERBUS 2000
DEVICE ID
NUMBER LABEL
23456
1
TEMPERATURE
SENSOR
TERMINAL STRIP
Figure 1. ESM Component Locations
Table 1: ESM Component Descriptions
ESM ComponentFunction
Backup Freeze StatActivates furnace if temperature drops
to 45°F (±6°F).
SuperBus 2000
Device ID Number
Identifies unique device ID number
(SuperBus 2000 pane l s).
Label
ESM Software
Version Label
Identifies the installed software
version.
Terminal StripUsed for panel and HVAC thermostat
connections.
Temperature SensorMonitors the premises temperature.
Bus LEDFlashes constantly to indicate normal
communication to the panel bus.
Unit Number DIP
Switches
Used for manually setting unit
numbers (SuperBus panels).
ESM SOFTWARE
VERSION LABEL
BUS
LED
UNIT NUMBER
DIP SWITCHES
8557G31C.DS4
SuperBus® 2000 Energy Saver Module
1
Installation Guidelines
PRESS DOWN
HERE
8857G46A.DS4
Installation Guide l ine s
Use the following guidelines when installing the ESM:
❑For Concord systems, up to 16 bus devices can be
connected to the panel (alphanumeric touchpad, HIM,
ESM, etc.). UltraGard systems support up to eight bus
devices.
❑Each bus device must have a different unit number.
❑Concord systems allow one ESM per partition. For
UltraGard systems, only one ESM can be connected to
a panel.
❑The ESM maximum current draw is 30 mA.
❑Do not exceed the panel total power when using panel
power for bus devices a nd hardwired sensors t hat
require panel power (refer to the specific panel Instal-lation Instructions).
❑Use 4-conductor, 22-gauge or larger stranded wire
from the ESM to the panel.
❑Use 22-gauge or larger stranded wire from the ESM to
the thermostat.
❑Install the ESM on an inside wall next to or as close as
possible to the existing thermostat. This keeps th e temperature difference between the ESM and the thermostat to a minimum.
❑Programmable thermostats that use a battery to keep
time and other programmed settings may lose time and/
or programmed settings when the ESM is turned on.
This can happen since the ESM relay is interrupting the
thermostat main power, forcing the thermostat to rely
on battery power to save time and programmed settings. As a result, the thermostat battery may need to be
replaced more often depending on how often and how
long the ESM is turned on.
❑Refer to the specific panel Installation Instructions for
wire length limits.
Installation
Installation consists of mounting the ESM (next to or as
close as possible to the existing thermostat) and wiring it to
the panel and existing HVAC thermostat.
To mount the ESM:
1.Press down on the top center of the cover and pull it
away from the base (see Figure 2). Set the cover aside.
Figure 2. Removing the Enclosure Cover
CAUTION
You must be free of all sta tic electricity when han dli ng
electronic components. Touch a grounded bare metal
surface before touching the circuit board.
2.Place the ESM on the wall at the desired location and
mark the upper-left and lower mounting holes (see Figure 3).
MOUNTING
HOLE
Tools and Supplies
❑Screwdrivers (Phillips and flat)
❑Screws and anchors (included)
❑Digital voltmeter
❑Drill with bits
❑Hammer
❑Wire cutters/strippers
❑4-conductor, 22- gauge or larger stranded wire
❑22-gauge or larger stranded wire
❑Pen or pencil
2
23456
1
MOUNTING HOLES
Figure 3. Mounting Hole Locations
8557G29C.DS4
3.Install anchors where studs are not present and secure
the ESM to the wall with the enclosed screws.
SuperBus® 2000 Energy Saver Module
Wiring
Wiring
Some thermostats control heating and cooling, others control only heating. A heating/cooling thermostat uses four
wires and a heating-only thermostat usually has two.
Table 2: Four-Wire Thermostat Color Code
WireFunction
RedPower feed to thermostat
GreenFan control
YellowCooling
WhiteHeating
Note
If the thermostat wire colors are different than those
described above, contact a qualified HVAC service
person for wiring information about the specific thermostat you are working with. Be sure to give the service person the manufacturer name and model
number of the thermostat.
To wire the ESM to a Concord panel:
1.Remove AC panel power and disconnect the backup
battery.
2.Turn off the thermostat and remove its cover.
3.Route a 4-conductor, 22-gauge or larger, stranded wire
from the ESM to the panel.
4.Connect terminals 3 t hro ugh 6 to the panel as sh own in
Figure 4.
ESM TERMINALS
125
TO FURNACE
Figure 4. ESM Wiring Connections to the Thermostat and
THERMOSTAT
CONCORD
PANEL TERMINALS
Concord Panel Terminals
346
3456
+12
VDC
BUSABUS
8573G09A.DSF
GND
B
To wire the ESM to the UltraGard panel:
1.Turn the power switch to off, unplug the AC power
transformer, and disconnect the backup battery.
2.Turn off the thermostat and remove its cover.
3.Route a 4-conductor, 22-gauge or larger, stranded wire
from the ESM to the panel.
4.Connect terminals 3 thro ugh 6 to the panel as shown in
Figure 5.
ESM TERMINALS
1
2345
TO FURNACE
Figure 5. ESM Wiring Connections to the Thermostat and
THERMOSTAT
ULTRAGARD
PANEL TERMINALS
UltraGard Panel Terminals
12
DC
OUT
131415
BUS
A
6
BUSBGND
8557G30A.DS4
5.Route 22-gauge or larger, stranded wire from the ESM
to the thermostat.
To connect a four-wire thermostat:
1.Remove the red wire (or power feed) from the thermostat and connect it to ESM terminal 1.
2.Connect a wire from ESM terminal 2, to the thermostat
terminal where the red wire (or power feed) was connected.
To connect a two-wire thermostat:
1.Remove one of the wires from the thermostat and connect it to ESM terminal 1.
2.Connect a wire from ESM terminal 2, to the terminal
on the thermostat where the original wire had been connected.
5.Route 22-gauge or larger, stranded wire from the ESM
to the thermostat.
SuperBus® 2000 Energy Saver Module
3
Setting the Module Unit Number
M
M
M
M
M
M
Setting the Module Unit Number
Setting the Unit Number on Concord
Panels with Software Version 2.0 or Later
Setting the Unit Number On Concord
(software versions 1.0–1.6) and
UltraGard Panels
Module dip switches can be set to any unit number 0–15.
The default setting 0 can be used if no o ther bus dev ices are
installed in the system. When using one module per
partition (Concord only), the lower unit number will be
assigned to partition 1, while the higher unit number will be
assigned to partition 2.
Note
Do not use modu le number 15 if it is installed in a
Concord RF system since the built-in receiver is factory set to unit number 15 and cannot be changed.
To set the module unit number:
Locate the DIP switches on the ESM circuit board (see
Figure 1) and set them to the desired unit number (0–15)
before applying power (see Figure 6).
CAUTION
Do not change DIP switch settings once the panel is
powered up.
❑0-15 for Concord
❑0-7 for UltraGard
UNIT NUMBER 0
ON
A
1234
567
UNIT NUMBER 3
ON
A
1234
567
UNIT NUMBER 6
ON
A
1234
567
UNIT NUMBER 9
ON
A
1234
567
UNIT NUMBER 12
ON
A
1234
567
UNIT NUMBER 15--Do not use in Concord RF systems.
ON
A
1234
567
Figure 6. ESM Unit Number DIP Switch Settings
UNIT NUMBER 1
ON
M
A
1
234567
8
UNIT NUMBER 4
ON
M
A
1
34
2
8
UNIT NUMBER 7
ON
M
A
1234
8
UNIT NUMBER 10
ON
M
A
1
34
2
8
UNIT NUMBER 13
ON
M
A
1
34
2
8
8
56
56
56
56
UNIT NUMBER 2
ON
M
A
1
8
UNIT NUMBER 5
ON
M
A
1
8
7
UNIT NUMBER 8
ON
M
A
1
8
7
UNIT NUMBER 11
ON
M
A
1
8
7
UNIT NUMBER 14
ON
M
A
1
8
7
4
3
2
567
234567
34
2
56
234567
234567
9712G09A.DSF
8
8
8
7
8
8
The unit number will be automatically set when powering
up the system. No action is required by the installer. When
using one module per partition, the panel automatically
assigns each module with a partition number.
Power Up and Bus Communication
Use the following procedures for powering up the system
and verifying bus communication.
On Concord Panels (all software ver sions)
Note
In order to enter panel program mode to verify unit
numbers (optional), an alphanumeric touchpad must
be connected to Concord panels. Refer to the specific
Installation Instructions
1.Verify that all wiring at the panel and module is correct.
2.Connect the panel battery and plug in the panel AC
power transformer. Alphanumeric touchpad displays
should come on.
3.Verify that the ESM red bus LED is flashing.
4.If desired, enter panel program mode to verify the unit
number was learned and enrolled into the correct partition (see panel Installation Instructions for more information).
Note
If the ESM red bus LED does not flash, remove AC
panel power, disconnect the battery, and see Table 3
“Troubleshooting.”
On UltraGard Panels
1.Verify that all wiring at the panel and module are correct.
2.Connect the panel battery and plug in the panel AC
power transformer.
3.Turn the panel power switch to on.
4.Set the panel RUN/PROGRAM switch to PROGRAM.
If the alphanumeric display reads 1-OFF and the 1 is flash-
ing, you must enter the installer code to place the p anel into
the program mode. Refer to the panel Installation Instructions for more information.
The ESM red bus LED should be flashing continuously
which indicates successful communication to the panel.
for more information.
Note
If the ESM red bus LED is not flashing continuously,
set the RUN/PROGRAM switch to RUN, turn off the
panel power switch, unplug the panel AC power transformer, disconnect the backup battery, and see
Table 3 “Tr oubleshooting.”
4
SuperBus® 2000 Energy Saver Module
Additional Information
Additional Information
For information on operating, programming, testing, and
deleting an ESM from panel memory, please refer to the
specific panel Installation Instructions or User’s Manual.
Note
The ESM must be installed and powered up for a minimum of 15 minutes before adjusting the ESM room
temperature to ensure consistent readings between
the ESM and house thermostat.
For best results, wait an hour before adjusting the
ESM room temperature.
Troubleshooting
Table 3 describes what to do if the module does not work
correctly.
Table 3: Troubleshooting
ProblemAction/Solution
The red bus LED
stays off.
1.Check fo r incorrect wiring connections.
2.Make sure the panel AC power
transformer is plugged in and
the backup battery is connected.
For UltraGard panels make sure
the panel power switch is on.
3.Verify that the panel recognizes the ESM and is enrolled
in the correct partition by entering program mode (see panel
Installation Instructions).
4.If the LED still remains off,
replace the module.
Table 3: Troubleshooting (Continued)
ProblemAction/Solution
The red bus LED
doesn’t flash.
Concord
1.Check fo r incorrect wiring
connections.
2.For Concord (soft ware versions 1.0–1.6) panels make sure
that all bus devices are set with
different unit numbers.
3.If th e unit number dip switches
were changed, remove pa ne l
power and reapply it for the
panel and ESM to communicate
successfully. You will have to
go into panel programming to
delete the unit number previously assigned to the ESM (see
panel Installation Instructions).
4.If the LED still doesn’t flash,
replace the module.
UltraGard
1.Set the RUN/PROGRAM
switch to RUN and turn off the
panel power switch.
2.Check fo r incorrect wiring
connections.
3.Check that all bus dev ices are
set with different unit numbers.
4.If th e unit number dip switches
were changed, turn off the
panel power switch, turn it back
on, then enter the program
mode for the pane l and E S M t o
communicate successfully. You
will have to go into panel
programming to delete the unit
number previously assigned to
the ESM (see panel Installa-tion Instructions).
5.If the module still malfunctions,
replace the module.
SuperBus® 2000 Energy Saver Module
The temperature is
incorrect or the
wrong furnace/AC
unit is being
controlled.
1.Check fo r incorrect wiring
connections.
2.Verify the module is learned
into the correct partition by
entering program mo de (see
panel Installation Instructions).
3.Make sure that the ESM is
turned on (see panel Installa-tion Instructions)
5
Specifications
0
Specifications
Compatibility: Concord and UltraGard panels
Power Requirements: 12 VDC, 30 mA maximum
(from panel)
Storage Temperature: -30° to 140°F (-34° to 60°C)
Operating Temperature: 32° to 140°F (0° to 60°C)
Color: Belgian gray
Case Material: ABS plastic
Dimensions: 2.60" x 2.60" x 0.90" (L x W x D)
Installation: Wall mounting
UL Listings:UL 2017 General Purpose
Signaling Device
Notices
FCC Part 15 Information to the User
Changes or modifications not expressly approved by Interactive Technologies, Inc. can void the user’s authority to operate the equipment.
FCC Part 15 Class B
This equipment has been tested and found to comply with the lim its for a
Class B digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against interference in a residential installation.
This equipment generates, uses, and can radiate radio frequency energy
and, if not install ed and used in accordance with the i n s tructions, may
cause harmful interference to radio communications. However, there is no
guarantee that interference wi ll not occur in a particular installatio n .
If this equipment does ca use harmful interferenc e t o radio or television
reception, whic h ca n be determined by turning the equipment off and on,
the user is encouraged to try to correct the interference by one or more of
the following measures:
Reorient or relocate the receiving antenna.
❑
Increase the separation betwee n the equipment and receiver.
❑
Connect the affected equipment a nd the panel receiv er t o s epa rate
❑
outlets, on different branch circuits.
Consult the dealer or an experienced radio/T V technician for help.
❑
I
nteractive Technologies, Inc.
2266 Second Street North
North Saint Paul, MN 55109-290
T: 651/777-2690
F: 651/779-4890
1-800-777-1415
www.ititechnologies.com