Interlogix 60-620-01 User Manual

   
ITI Part No. 60-620-01

Document Number: 466-1031-01 Rev. A August 2000

Product Summary

The SuperBus 2000 Energy Saver Mod ule (ESM) pr ovides a money-saving and convenient way to monitor and control temperatures. The ESM uses low- and high-temperature limits to save energy by overriding the existing HVAC ther­mostat. When the ESM is on, temperature limits determine when the heat or air-conditioning turns on. When the ESM is off, the HVAC thermostat controls heat and air-condition­ing.
For example, if the thermostat is set for 68°F and the ESM high limit is 80°F, the ESM prevents the air-conditioner from turning on until the temperature reaches 80°F. The ESM limits may be set between 40° and 90°F.
A temperature sensor monitors the temperature and reports a freeze alarm to the panel if the temperature drops below the set freeze temperature (default = 42°F). A backup freeze stat provides additional protection by activating the fur nace if the temperature drops to 45°F (±6°F).
Note
Depending on where the ESM is located, additional freeze sensors may need to be placed throughout the residence to provide adequate freeze protection.
This device is backward compatible with Concord™ panels with software versions 1.0–1.6 and UltraGard™ panels.
vs.
SuperBus 2000
Compatible panels (SuperBus 2000) have the ability to auto-address module unit numbers. When the panel is pow­ered up, the panel automatically reads the unique SuperBus 2000 device ID number and assigns a unit number to the module. This eliminates manually setting DIP switches and the chance of identical unit number conflicts.
Non-Compatible panels (SuperBus) communicate with SuperBus 2000 modules but require the module unit num­ber to first be set manually using DIP switches.
SuperBus 2000 Panels
Concord (sof tware version s 2.0 and later)
SuperBus Panels
UltraGard Concord (software versions 1.0–1.6)
SuperBus
8841G01A.DS4
Installation Instructions
Figure 1 shows the main ESM components and Table 1 describes them.
BACKUP
FREEZE
STAT
SUPERBUS 2000
DEVICE ID
NUMBER LABEL
23456
1
TEMPERATURE
SENSOR
TERMINAL STRIP

Figure 1. ESM Component Locations

Table 1: ESM Component Descriptions

ESM Component Function

Backup Freeze Stat Activates furnace if temperature drops
to 45°F (±6°F).
SuperBus 2000 Device ID Number
Identifies unique device ID number (SuperBus 2000 pane l s).
Label ESM Software
Version Label
Identifies the installed software version.
Terminal Strip Used for panel and HVAC thermostat
connections. Temperature Sensor Monitors the premises temperature. Bus LED Flashes constantly to indicate normal
communication to the panel bus. Unit Number DIP
Switches
Used for manually setting unit
numbers (SuperBus panels).
ESM SOFTWARE VERSION LABEL
BUS LED
UNIT NUMBER DIP SWITCHES
8557G31C.DS4

SuperBus® 2000 Energy Saver Module

1

Installation Guidelines

PRESS DOWN
HERE
8857G46A.DS4
Installation Guide l ine s
Use the following guidelines when installing the ESM: For Concord systems, up to 16 bus devices can be
connected to the panel (alphanumeric touchpad, HIM, ESM, etc.). UltraGard systems support up to eight bus devices.
Each bus device must have a different unit number. Concord systems allow one ESM per partition. For
UltraGard systems, only one ESM can be connected to a panel.
The ESM maximum current draw is 30 mA. Do not exceed the panel total power when using panel
power for bus devices a nd hardwired sensors t hat require panel power (refer to the specific panel Instal- lation Instructions).
Use 4-conductor, 22-gauge or larger stranded wire
from the ESM to the panel.
Use 22-gauge or larger stranded wire from the ESM to
the thermostat.
Install the ESM on an inside wall next to or as close as
possible to the existing thermostat. This keeps th e tem­perature difference between the ESM and the thermo­stat to a minimum.
Programmable thermostats that use a battery to keep
time and other programmed settings may lose time and/ or programmed settings when the ESM is turned on. This can happen since the ESM relay is interrupting the thermostat main power, forcing the thermostat to rely on battery power to save time and programmed set­tings. As a result, the thermostat battery may need to be replaced more often depending on how often and how long the ESM is turned on.
Refer to the specific panel Installation Instructions for
wire length limits.

Installation

Installation consists of mounting the ESM (next to or as close as possible to the existing thermostat) and wiring it to the panel and existing HVAC thermostat.

To mount the ESM:

1. Press down on the top center of the cover and pull it away from the base (see Figure 2). Set the cover aside.
Figure 2. Removing the Enclosure Cover
CAUTION
You must be free of all sta tic electricity when han dli ng electronic components. Touch a grounded bare metal surface before touching the circuit board.
2. Place the ESM on the wall at the desired location and mark the upper-left and lower mounting holes (see Fig­ure 3).
MOUNTING
HOLE

Tools and Supplies

Screwdrivers (Phillips and flat) Screws and anchors (included) Digital voltmeter Drill with bits Hammer Wire cutters/strippers 4-conductor, 22- gauge or larger stranded wire 22-gauge or larger stranded wire Pen or pencil
2
23456
1
MOUNTING HOLES
Figure 3. Mounting Hole Locations
8557G29C.DS4
3. Install anchors where studs are not present and secure the ESM to the wall with the enclosed screws.
SuperBus® 2000 Energy Saver Module

Wiring

Wiring
Some thermostats control heating and cooling, others con­trol only heating. A heating/cooling thermostat uses four wires and a heating-only thermostat usually has two.

Table 2: Four-Wire Thermostat Color Code

Wire Function

Red Power feed to thermostat Green Fan control Yellow Cooling White Heating
Note
If the thermostat wire colors are different than those described above, contact a qualified HVAC service person for wiring information about the specific ther­mostat you are working with. Be sure to give the ser­vice person the manufacturer name and model number of the thermostat.

To wire the ESM to a Concord panel:

1. Remove AC panel power and disconnect the backup battery.

2. Turn off the thermostat and remove its cover.

3. Route a 4-conductor, 22-gauge or larger, stranded wire from the ESM to the panel.

4. Connect terminals 3 t hro ugh 6 to the panel as sh own in Figure 4.

ESM TERMINALS
1 2 5
TO FURNACE
Figure 4. ESM Wiring Connections to the Thermostat and
THERMOSTAT
CONCORD
PANEL TERMINALS
Concord Panel Terminals
3 4 6
3 456
+12
VDC
BUSABUS
8573G09A.DSF
GND
B

To wire the ESM to the UltraGard panel:

1. Turn the power switch to off, unplug the AC power transformer, and disconnect the backup battery.

2. Turn off the thermostat and remove its cover.

3. Route a 4-conductor, 22-gauge or larger, stranded wire from the ESM to the panel.

4. Connect terminals 3 thro ugh 6 to the panel as shown in Figure 5.

ESM TERMINALS
1
2 3 4 5
TO FURNACE
Figure 5. ESM Wiring Connections to the Thermostat and
THERMOSTAT
ULTRAGARD
PANEL TERMINALS
UltraGard Panel Terminals
12
DC
OUT
13 14 15
BUS
A
6
BUSBGND
8557G30A.DS4

5. Route 22-gauge or larger, stranded wire from the ESM to the thermostat.

To connect a four-wire thermostat:

1. Remove the red wire (or power feed) from the thermo­stat and connect it to ESM terminal 1.
2. Connect a wire from ESM terminal 2, to the thermostat terminal where the red wire (or power feed) was con­nected.

To connect a two-wire thermostat:

1. Remove one of the wires from the thermostat and con­nect it to ESM terminal 1.
2. Connect a wire from ESM terminal 2, to the terminal on the thermostat where the original wire had been con­nected.

5. Route 22-gauge or larger, stranded wire from the ESM to the thermostat.

SuperBus® 2000 Energy Saver Module
3

Setting the Module Unit Number

M
M
M
M
M
M
Setting the Module Unit Number

Setting the Unit Number on Concord Panels with Software Version 2.0 or Later

Setting the Unit Number On Concord (software versions 1.0–1.6) and UltraGard Panels

Module dip switches can be set to any unit number 0–15. The default setting 0 can be used if no o ther bus dev ices are installed in the system. When using one module per partition (Concord only), the lower unit number will be assigned to partition 1, while the higher unit number will be assigned to partition 2.
Note
Do not use modu le number 15 if it is installed in a Concord RF system since the built-in receiver is fac­tory set to unit number 15 and cannot be changed.
To set the module unit number:
Locate the DIP switches on the ESM circuit board (see Figure 1) and set them to the desired unit number (0–15) before applying power (see Figure 6).
CAUTION
Do not change DIP switch settings once the panel is powered up.
0-15 for Concord 0-7 for UltraGard
UNIT NUMBER 0
ON
A
1234
567
UNIT NUMBER 3
ON
A
1234
567
UNIT NUMBER 6
ON
A
1234
567
UNIT NUMBER 9
ON
A
1234
567
UNIT NUMBER 12
ON
A
1234
567
UNIT NUMBER 15--Do not use in Concord RF systems.
ON
A
1234
567
Figure 6. ESM Unit Number DIP Switch Settings
UNIT NUMBER 1
ON
M A
1
234567
8
UNIT NUMBER 4
ON
M A
1
34
2
8
UNIT NUMBER 7
ON
M A
1234
8
UNIT NUMBER 10
ON
M A
1
34
2
8
UNIT NUMBER 13
ON
M A
1
34
2
8
8
56
56
56
56
UNIT NUMBER 2
ON
M A
1
8
UNIT NUMBER 5
ON
M A
1
8
7
UNIT NUMBER 8
ON
M A
1
8
7
UNIT NUMBER 11
ON
M A
1
8
7
UNIT NUMBER 14
ON
M A
1
8
7
4
3
2
567
234567
34
2
56
234567
234567
9712G09A.DSF
8
8
8
7
8
8
The unit number will be automatically set when powering up the system. No action is required by the installer. When using one module per partition, the panel automatically assigns each module with a partition number.

Power Up and Bus Communication

Use the following procedures for powering up the system and verifying bus communication.

On Concord Panels (all software ver sions)

Note
In order to enter panel program mode to verify unit numbers (optional), an alphanumeric touchpad must be connected to Concord panels. Refer to the specific
Installation Instructions
1. Verify that all wiring at the panel and module is correct.
2. Connect the panel battery and plug in the panel AC power transformer. Alphanumeric touchpad displays should come on.
3. Verify that the ESM red bus LED is flashing.
4. If desired, enter panel program mode to verify the unit number was learned and enrolled into the correct parti­tion (see panel Installation Instructions for more infor­mation).
Note
If the ESM red bus LED does not flash, remove AC panel power, disconnect the battery, and see Table 3 “Troubleshooting.”

On UltraGard Panels

1. Verify that all wiring at the panel and module are cor­rect.
2. Connect the panel battery and plug in the panel AC power transformer.
3. Turn the panel power switch to on.
4. Set the panel RUN/PROGRAM switch to PROGRAM.
If the alphanumeric display reads 1-OFF and the 1 is flash- ing, you must enter the installer code to place the p anel into the program mode. Refer to the panel Installation Instructions for more information.
The ESM red bus LED should be flashing continuously which indicates successful communication to the panel.
for more information.
Note
If the ESM red bus LED is not flashing continuously, set the RUN/PROGRAM switch to RUN, turn off the panel power switch, unplug the panel AC power trans­former, disconnect the backup battery, and see Table 3 “Tr oubleshooting.”
4
SuperBus® 2000 Energy Saver Module

Additional Information

Additional Information
For information on operating, programming, testing, and deleting an ESM from panel memory, please refer to the specific panel Installation Instructions or User’s Manual.
Note
The ESM must be installed and powered up for a min­imum of 15 minutes before adjusting the ESM room temperature to ensure consistent readings between the ESM and house thermostat.
For best results, wait an hour before adjusting the ESM room temperature.

Troubleshooting

Table 3 describes what to do if the module does not work correctly.

Table 3: Troubleshooting

Problem Action/Solution

The red bus LED stays off.
1. Check fo r incorrect wiring con­nections.
2. Make sure the panel AC power transformer is plugged in and the backup battery is connected. For UltraGard panels make sure the panel power switch is on.
3. Verify that the panel recog­nizes the ESM and is enrolled in the correct partition by enter­ing program mode (see panel Installation Instructions).

4. If the LED still remains off, replace the module.

Table 3: Troubleshooting (Continued)

Problem Action/Solution

The red bus LED doesn’t flash.
Concord

1. Check fo r incorrect wiring connections.

2. For Concord (soft ware ver­sions 1.0–1.6) panels make sure that all bus devices are set with different unit numbers.
3. If th e unit number dip switches were changed, remove pa ne l power and reapply it for the panel and ESM to communicate successfully. You will have to go into panel programming to delete the unit number previ­ously assigned to the ESM (see panel Installation Instructions).

4. If the LED still doesn’t flash, replace the module.

UltraGard

1. Set the RUN/PROGRAM switch to RUN and turn off the panel power switch.

2. Check fo r incorrect wiring connections.

3. Check that all bus dev ices are set with different unit numbers.

4. If th e unit number dip switches were changed, turn off the panel power switch, turn it back on, then enter the program mode for the pane l and E S M t o communicate successfully. You will have to go into panel programming to delete the unit number previously assigned to the ESM (see panel Installa- tion Instructions).

5. If the module still malfunctions, replace the module.

SuperBus® 2000 Energy Saver Module
The temperature is incorrect or the wrong furnace/AC unit is being controlled.

1. Check fo r incorrect wiring connections.

2. Verify the module is learned into the correct partition by entering program mo de (see panel Installation Instructions).
3. Make sure that the ESM is turned on (see panel Installa- tion Instructions)
5

Specifications

0
Specifications
Compatibility: Concord and UltraGard panels Power Requirements: 12 VDC, 30 mA maximum
(from panel) Storage Temperature: -30° to 140°F (-34° to 60°C) Operating Temperature: 32° to 140°F (0° to 60°C) Color: Belgian gray Case Material: ABS plastic Dimensions: 2.60" x 2.60" x 0.90" (L x W x D) Installation: Wall mounting UL Listings: UL 2017 General Purpose
Signaling Device

Notices

FCC Part 15 Information to the User
Changes or modifications not expressly approved by Interactive Technolo­gies, Inc. can void the user’s authority to operate the equipment.
FCC Part 15 Class B
This equipment has been tested and found to comply with the lim its for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against interference in a resi­dential installation.
This equipment generates, uses, and can radiate radio frequency energy and, if not install ed and used in accordance with the i n s tructions, may cause harmful interference to radio communications. However, there is no guarantee that interference wi ll not occur in a particular installatio n .
If this equipment does ca use harmful interferenc e t o radio or television reception, whic h ca n be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna.
Increase the separation betwee n the equipment and receiver.
Connect the affected equipment a nd the panel receiv er t o s epa rate
outlets, on different branch circuits. Consult the dealer or an experienced radio/T V technician for help.
I
nteractive Technologies, Inc.
2266 Second Street North North Saint Paul, MN 55109-290 T: 651/777-2690 F: 651/779-4890 1-800-777-1415 www.ititechnologies.com
Security
Automation
Fire Protection
©2000 Interactive Technologies, Inc. an Int e r logix™ company. Interlogix is a trademark of Interlogix, Inc. ITI, UltraGard, and SuperBus are registered trademarks of Interactive Technologies, Inc. Concord is a trademark of Inte ractive Technologies, Inc.
6
Access Control
SuperBus® 2000 Energy Saver Module
Loading...