The Light Tower Alarm Kit is designed to work in conjunction with the Con TROLL PRO
System to provide visual and audible indication of the state of the Con TROLL PRO
relay outputs from a distance.
The light tower is controlled via one or both of the Con TROLL PRO low-voltage relays.
Proper operation of the light tower requires correct wiring per one of the application
diagrams in this document as well as relay output programming to match the
configuration.
It is possible to damage the Con TROLL PRO if the light tower is wired incorrectly.
Make sure that you read this document, the Con TROLL PRO Installation Manual, and
the Con TROLL PRO Operator's Manual before installing this product.
Safety Information
Please read this manual and the Con TROLL PRO Installation Manual before
unpacking or installing any part of this kit.
WARNING: This is a low-voltage product and is only to be wired to the
Con TROLL PRO low-voltage relay terminals. This product must not be
wired to the high-voltage terminals in the Con TROLL PRO.
WARNING: Never use this product as a sensing device for personnel
protection. Doing so could lead to serious injury or death. This product
does NOT include the self-checking redundant circuitry necessary to allow its
use in personnel safety applications. A sensor failure or malfunction can cause
either an energized or de-energized relay output condition.
DANGER: Make sure that power to the Con TROLL PRO is disconnected
before making any wiring connections.
DANGER: There is reference in this document to using the Light Tower
functions in conjunction with high-voltage control functions. Only
properly trained and qualified personnel should wire the high-voltage control
functions while observing the precautions in the Con TROLL PRO Installation
Manual.
Compatibility and Reference Manuals
The light tower is compatible with all versions of the Con TROLL PRO: AC, AC-L, and
DC-L.
For Con TROLL PRO units purchased before May 2012, refer to the installation manual
(document number 0087612) and the operator's manual (document number 0087602).
For Con TROLL PRO units purchased after May 2012, refer to the installation manual
(document number 0085660) and the operator's manual (document number 0085670).
Manuals are available on the In-Situ website www.in-situ.com/Manuals.
800-446-74882www.in-situ.com
Light Tower Cable Wiring Overview
The light tower is not polarity sensitive and can be wired one of two ways:
1. The common wire connected to POWER and the other wires switched by relay to
GND.
2. The common wire connected to GND and the other wires switched by relay to
POWER.
All of the examples provided in this document use the first method. If you want to install
additional accessories with the light tower, the second method might be used. Consult
a qualified technician for additional configurations.
Cable Wire Colors
Wire ColorFunction
BlueCommon
BlackGreen Light
BrownYellow Light
WhiteRed Light
GrayAudible Indicator
Installation Procedure
Refer to the Con TROLL PRO Installation Manual as needed.
1. Install the light tower using the supplied bracket, making sure the cable reaches the
Con TROLL PRO without strain.
2. Disconnect power from the Con TROLL PRO.
3. Loosen the four screws on the front panel and open the front panel.
4. If necessary, remove a wiring port plug on the Con TROLL PRO and replace it with
a dome connector.
5. Insert the light tower cable and pull it inside the enclosure far enough for the wires to
reach the terminal block without strain.
6. Tighten the dome connector to seal the enclosure and to provide strain relief for the
cable.
7. Wire the light tower cable according to the appropriate diagram for the intended
application. See pages 4 through 7.
8. Trim the exposed ends of any unused light tower wires.
9. Secure unused light tower wires to the light tower cable with zip ties.
800-446-74883www.in-situ.com
10. Close the front panel and tighten the four front panel screws.
11. Apply power to the Con TROLL PRO.
12. Program the relay outputs to match the selected configuration.
Configuring a Single-Parameter Light Alarm
In this scenario, the Con TROLL PRO monitors a tank using an RDO®PRO Probe. The
Con TROLL PRO turns on an aerator when the dissolved oxygen (DO) concentration
falls below 4 mg/L. The light tower shows green when the DO is above 4 mg/L (aerator
off), and yellow when the DO is below 4 mg/L (aerator on).
The RDO PRO Probe is wired as Probe A. Relay 1 is used to implement the control
and display function.
800-446-74884www.in-situ.com
Programming Sequence
On the Con TROLL PRO, select Menu, Settings, Outputs, Relays, Relay 1.
Enable the relay.
Mode = Low Alarm
Parameter = A-Concentration
Setpoint = 4 mg/L
Deadband = 0.2 mg/L (This value is recommended to prevent relay chatter.)
Adjust the Setpoint and Deadband to optimize aerator
performance and minimize aerator cycling.
Configuring a Single-Parameter Light and Audible Alarm
In this scenario, the Con TROLL PRO monitors a tank using an RDO PRO Probe or
RDO PRO-X Probe. The Con TROLL PRO turns on an aerator when the DO
concentration falls below 4 mg/L.
The light tower shows green when the DO is above 4 mg/L (aerator off), yellow when
the DO is below 4 mg/L but above 3 mg/L (aerator on), or red when the DO is below 3
mg/L (aerator on). As an option, the audible alarm can turn on when the red light turns
on.
The RDO PRO Probe is wired as Probe A. Relay 1 is used to implement the control
function, Relay 2 is used to implement the alarm function.
You can add an external switch in the gray wire that will allow you
to turn off the audible alarm when you service the system.
800-446-74885www.in-situ.com
800-446-74886www.in-situ.com
Programming Sequence (Relay 1)
On the Con TROLL PRO, select Menu, Settings, Outputs, Relays, Relay 1.
l Enable the relay.
l Mode = Low Alarm
l Parameter = A-Concentration
l Setpoint = 4 mg/L
l Deadband = 0.2 mg/L (This value is recommended to prevent relay chatter.)
Adjust the Setpoint and Deadband for Relay 1 to optimize aerator
performance and minimize aerator cycling.
Programming Sequence (Relay 2)
On the Con TROLL PRO, select Menu, Settings, Outputs, Relays, Relay 2.
l Enable the relay.
l Mode = Low Alarm
l Parameter = A-Concentration
l Setpoint = 3 mg/L
l Deadband = 0.2 mg/L (This value is recommended to prevent relay chatter.)
Configuring a Dual-Parameter Light Alarm
In this scenario, the Con TROLL PRO monitors two independent tanks, each with an
RDO PRO Probe or RDO PRO-X Probe.
Probe A is placed in Tank A. The Con TROLL PRO turns on aerator A and the yellow
light when the DO falls below 4 mg/L.
Probe B is placed in Tank B. The Con TROLL PRO turns on aerator B and the red light
when the DO falls below 5 mg/L.
Relay 1 is used to implement the Tank A control function, Relay 2 is used to implement
the Tank B control function.
800-446-74887www.in-situ.com
800-446-74888www.in-situ.com
Programming Sequence (Relay 1)
On the Con TROLL PRO, select Menu, Settings, Outputs, Relays, Relay 1.
Enable the relay.
Mode = Low Alarm
Parameter = A-Concentration
Setpoint = 4 mg/L
Deadband = 0.2 mg/L (This value is recommended to prevent relay chatter.)
Adjust the Setpoint and Deadband to optimize aerator
performance and minimize aerator cycling.
Programming Sequence (Relay 2)
On the Con TROLL PRO, select Menu, Settings, Outputs, Relays, Relay 2.
l Enable the relay.
l Mode = Low Alarm
l Parameter = B-Concentration
l Setpoint = 5 mg/L
l Deadband = 0.2 mg/L (This value is recommended to prevent relay chatter.)
Adjust the Setpoint and Deadband to optimize aerator
performance and minimize aerator cycling.
800-446-74889www.in-situ.com