Ingersoll-Rand XF 20, XF 30, EP 20, EP 30, HP 25 Operator's Instruction Manual

...
APDD 739
June 1999
XF 20 - 30 EP 20 - 30 HP 20 - 30 HXP 20 - 30
OPERATORS/ INSTRUCTION MANUAL OPTIONS
Before installation or starting the compressor for the first time, this manual should be studied careful­ly to obtain a clear knowledge of the unit and of the duties to be performed while operating and main­taining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFE­TY DATAand should be kept with the air compres-
®
©INGERSOLL-RAND COMPANY
AIR COMPRESSOR GROUP
BONDED WARRANTY & REGISTERED START UP

Warranty

The Company warrants that the equipment manufactured by it and delivered hereunder will be free of defects in material and workmanship for a period of twelve months (see extended airend warranty) from the date of placing the Equipment in operation or eighteen months (see extended airend warranty) from the date of shipment from Davidson, NC, whichever shall first occur. The Purchaser shall be obligated to promptly report any failure to con­form to this warranty, in writing to the Company in said period, whereupon the Company shall, at its option, correct such nonconformity, by suitable repair to such equipment or, furnish a replacement part F.O.B. point of shipment, provided the Purchaser has stored, installed maintained and operated such Equipment in accordance with good industry practices and has complied with specific recommendations of the Company. Accessories or equipment fur­nished by the Company, but manufactured by others, shall carry whatever warranty the manufacturers have con­veyed to the Company and which can be passed on to the Purchaser. The Company shall not be liable for any repairs, replacements, or adjustments to the Equipment or any costs of labor performed by the Purchaser or others without Company’s prior written approval.
The effects of corrosion, erosion and normal wear and tear are specifically excluded. Performance warranties are limited to those specifically stated within the Company’s proposal. Unless responsibility for meeting such perfor­mance warranties are limited to specified tests, the Company’s obligation shall be to correct in the manner and for the period of time provided above.
THE COMPANY MAKES NO OTHER WARRANTY OR REPRESENTATION OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES OF MERCHANTABILI­TY AND FITNESS FOR APARTICULAR PURPOSE, ARE HEREBY DISCLAIMED.
Correction by the Company of nonconformities whether patent or latent, in the manner and for the period of time provided above, shall constitute fulfillment of all liabilities of the Company for such nonconformities whether based on contract, warranty negligence, indemnity, strict liability or otherwise with respect to or arising out of such Equipment.
The purchaser shall not operate Equipment which is considered to be defective, without first notifying the Company
in writing of its intention to do so. Any such Equipment will be at Purchaser’s sole risk and liability.
Limitation or Liability
The remedies of the Purchaser set forth herein are exclusive, and the total liability of the Company with respect to this contract or the Equipment and services furnished hereunder, in connection with the performance or breach thereof, or from the manufacture, sale, delivery, installation, repair or technical direction covered by or furnished under this contract, whether passed on contract, warranty negligence, indemnity, strict liability or otherwise, shall not exceed the purchase price of the unit of Equipment upon which such liability is based.
The Company and its suppliers shall in no event be liable to the Purchaser, any successors in interest or any ben­eficiary or assignee of this contract for any consequential, incidental, indirect, special or punitive damages arising out of this contract or any breach thereof, or any defect in, or failure of, or malfunction of the Equipment hereunder, whether based upon loss of use, lost profits or revenue, interest, lost goodwill, work stoppage, impairment of other goods, loss by reason of shutdown or non-operation, increased expenses of operation, cost of purchase of replace­ment power or claims of Purchaser or customers of Purchaser for service interruption whether or not such loss or damage is based on contract, warranty, negligence, indemnity, strict liability or otherwise.
EXTENDED AIREND WARRANTY
The Ingersoll-Rand Company Rotary Screw Air Compressor that has been filled prior to its original shipment from Ingersoll-Rand Company with ULTRA COOLANT and which has been operated solely on ULTRA COOLANT there­after shall have its AIREND warranted for twenty four (24) months from the date of placing the COMPRESSOR in operation or thirty (30) months from the date of shipment, whichever occurs first.
Except for the above warranty period, the standard warranty provisions shall apply and the conditions outlined herein are understood to be a supplement to the standard Ingersoll-Rand Company warranty.
1
ROTARY SCREW AIR COMPRESSOR This unit was purchased from
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––– –––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Ingersoll-Rand Company reserves the right to make changes or add improvements without notice and without incurring any obligation to make such changes or add such improvements to products sold previously.
No. of units on order: Customer Order No: Ingersoll-Rand Co. Order No.:
For ready reference:
Record the serial number and model number of your unit here.
Serial Number: Model Number:
TYPICAL UNIT
2

TABLE OF CONTENTS

0.0 SAFETY AND WARNINGS
0.1 safety instructions
0.2 safety precautions
0.3 decals
1.0 RECEIPT OF EQUIPMENT
1.1 inspection
1.2 unpacking and handling
1.3 tools
2.0 INSTALLATION
2.1 ventilation
2.2 foundation requirements
2.3 piping
2.4 electrical installation
2.5 voltage conversion
2.6 rotation check
2.7 before starting - starting - stopping
2.8 outdoor sheltered installation
3.0 SYSTEMS
3.1 general system information
3.2 aircooled compressors
3.3 coolant system
3.4 air system
3.5 electrical system
3.6 capacity control
3.7 pressure switch adjustment
3.8 modulation control (optional)
3.9 ACS control (intellisys modulation option only)
3.10 modulate control valve adjustment (optional)
4.0 INTELLISYS
4.1 emergency stop switch
4.2 power indicator light
4.3 push buttons
4.4 setpoint procedure
4.5 warnings
4.6 alarms
5.0 MAINTENANCE
5.1 maintenance schedule
5.2 maintenance records
5.3 maintenance procedures
5.4 pressure relief valve check
5.5 sheave alignment
5.6 drive belt
5.7 belt tension
5.8 belt tension spring replacement
5.9 shaft seal replacement
5.10 inlet air filter element
5.11 coolant filter
5.12 coolant change
5.13 coolant hoses
5.14 airend discharge hose
5.15 coolant separator filter element
5.16 separator tank scavenge check valve/screen/orifice
4.17 cooler cores
4.18 motor lubrication
4.19 intellisys removal
6.0 TROUBLE SHOOTING
6.1 standard control
6.2 intellisys control
7.0 OPTIONS
7.1 remote start/stop
7.2 remote start/stop and power outage restart option
7.3 sequencer control
8.0 REFERENCE DRAWING
8.1 electrical schematic - full voltage - standard control
8.2 electrical schematic - star delta - standard control
8.3 electrical schematic - full voltage - intellisys control
8.4 electrical schematic - star delta - intellisys control
8.5 foundation plan - base mounted - unenclosed
8.6 foundation plan - base mounted -enclosed
8.7 foundation plan - 120 gal. tank mounted - unenclosed
8.8 foundation plan - 120 gal. tank mounted - enclosed
8.9 foundation plan - 240 gal. tank mounted - unenclosed
8.10 foundation plan - 240 gal. tank mounted - enclosed
8.11 basic flow schematic - standard control
8.12 basic flow schematic - intellisys control
8.13 typical system flow diagrams
9.0 MAINTENANCE RECORD
GENERAL INFORMATION
Cooling Air Flow:
60 Hz: 2060 cfm (3500m
3
/hr.)
50 Hz: 1710 cfm (2905m
3
/hr.) Ambient Temperature Limit: 35°F to 115°F (2°C to 46°C) Coolant: Factory Filled ULTRACOOLANT Coolant Change: 8,000 hours or two years, whichever comes first, when using ULTRACOOLANT Coolant Capacity: 3.2 GAL (12L) Discharge Temperature Limit: 228°F (109°C)
Tools: U.S. Standard and metric are required to perform maintenance
3

0.0 SAFETY AND WARNINGS

0.1 SAFETY INSTRUCTIONS Before you install this air compressor you should take the time to carefully read all the instructions contained in this manual.

Electricity and compressed air have the potential to cause severe personal injury or property damage.
Before installing, wiring, starting, operating or making any adjustments, identify the components of the air compressor using this manual as a guide.
The operator should use common sense and good working practices while operating and maintaining this unit. Follow all codes, pipe adequately, understand the starting and stopping sequence. Check the safety devices by following the proce­dure contained in this manual.
Maintenance should be done by qualified personnel, ade­quately equipped with proper tools. Follow the maintenance schedules as outlined in the operators manual to ensure prob­lem free operation after start up.
Safety instructions in the operators manual are bold-faced for emphasis. The signal words DANGER, WARNING and CAU­TION are used to indicate hazard seriousness levels as fol­lows:
Danger is used to indicate the presence of a hazard which will cause severe personal injury, death, or substantial property dam­age if the warning is ignored.
Warning is used to indicate the presence of a hazard which can cause severe personal injury, death, or substantial property dam­age if the warning is ignored.
Caution is used to indicate the presence of a hazard which will or can cause minor per­sonal injury or property damage if the warn­ing is ignored.
Notice is used to notify people of installa­tion, operation, or maintenance information which is important but not hazard-related.
D! DANGER
! WARNING
! CAUTION
NOTICE
SAFETY PRECAUTIONS
BEFORE PROCEEDING, READ CAREFULLY BEFORE INSTALLING THE
COMPRESSOR OR PERFORMING ANY MAINTENANCE
WARNING COMPRESSED AIR AND ELECTRICITY
ARE DANGEROUS. BEFORE DOING ANY WORK ON THIS
UNIT, BE SURE THE ELECTRICAL SUP­PLY HAS BEEN CUT OFF–LOCKED & TAGGED AND THE ENTIRE COMPRES­SOR SYSTEM HAS BEEN VENTED OF ALL PRESSURE.
1. Do not remove the covers, loosen or remove any fittings, connections or devices when this unit is in operation. Hot liquid and air under pressure that are contained within this unit can cause severe injury or death.
2. The compressor has high and dan­gerous voltage in the motor starter and control box. All installations must be in accordance with recognized electrical codes. Before working on the electrical system, be sure to remove voltage from the system by use of a manual-discon­nect-switch. A circuit breaker or fuse safety switch must be provided in the electrical supply line leading to the compressor.
Those responsible for installation of this equipment must provide suitable grounds, maintenance clearance and lightning arrestors for all electrical com­ponents as stipulated in O.S.H.A.
1910.308 through 1910.329.
3. Do not operate the compressor at higher discharge pressure than those specified on the Compressor Nameplate or motor overload will occur. This con­dition will result in compressor motor shutdown.
4. Use only safety solvent for cleaning the compressor and auxiliary equip­ment.
5. Install a manual shut off valve (isola­tion type) in the discharge line. When a safety valve is installed between the iso­lation valve and the compressor, it must have sufficient capacity to relieve the full capacity of the compressor(s).
6. Whenever pressure is released through the pressure relief valve, it is due to excessive pressure in the sys­tem. The cause for the excessive pres­sure should be investigated immediate­ly.
7. Before doing any mechanical work on the compressor:
a.) Shut the unit down. b.) Electrically isolate the compressor
by use of the manual disconnect switch in the power line to the unit. Lock and tag the switch so that it cannot be oper­ated.
c.) Vent pressure from the compressor and isolate the unit from any other source of air.
8. There can be adverse effects if com­pressor lubricants are allowed to enter plant air systems.
Air line separators, properly selected and installed, will minimize any liquid carry-over.
The use of plastic bowls on line filters without metal guards can be hazardous. From a safety standpoint, metal bowls should be used on any pressurized sys­tem. Review of your plant air line sys­tem is recommended.
9. When a receiver is installed, it is rec­ommended that occupational safety and health standards as covered in the Federal Register, Volume 36, number 105, part 11, paragraph 1910.169 be adhered to in the installation and main­tenance of this receiver.
10. Before starting the compressor, its maintenance instructions should be thoroughly read and understood.
11. After maintenance functions are completed, covers and guards must be replaced.

0.2 SAFETY PRECAUTIONS

4
There is a high discharge air temperature shutdown function built into the Intellisys on each compressor. It is factory pre-set at 228°F (109°C). This function should be checked at regular intervals for proper oper­ation, once a month is recommended. PROCEDURE:
1. Block off the cooling air discharge.
2. The compressor discharge temperature will rise at a rapid rate. Shutdown should occur when the dis­charge temperature reaches the pre-set maximum discharge air temperature setting.
Failure to adhere to these recommendations can result in mechanical failure, property damage and serious injury or death.
All air and water inlet, and air and water discharge pipework to and from the inlet and discharge port con­nections must take into account vibration, pulsations, temperature, maximum pressure applied, corrosion and chemical resistance. In addition, it should be noted that lubricated compressors will discharge some oil into the air stream; therefore, compatibility between discharge piping, system accessories and software must be assured.
For the foregoing reasons, the use of plastic piping, soldered copper fittings and rubber hose as discharge piping is not recommended. In addition, flexible joints and/or flex lines can only be considered for such pur­poses if their specifications fit the operating parameters of the system.
It is the responsibility of the installer and owner to provide the appropriate service pipework to and from the machine.
“Ingersoll-Rand air compressors are not designed, intended, or approved for breathing air applications. Ingersoll-Rand does not approve specialized equipment for breathing air application and assumes no responsibility or liability for compressors used for breathing air services.”
! WARNING
! WARNING
! SAFETY SHUTDOWN CHECK HIGH AIR TEMPERATURE
5

0.3 DECALS

This section contains representative examples of decals which will be appearing throughout this manual and are applied to the compressor unit.
If for some reason a decal is defaced, parts are replaced or painted over, we recommend that you obtain a replacement (See Parts manual APDD 742 for Decal Kit Number).
39264734
REV A
6
3954190
39540232
39540174
39540166*
39540257*
3
1
2
7
5
6
4
8
9
39540158
39540240
39540265
39540273
NOTICE
To obtain satisfactory compressor operation and maintenance a minimum of 3 feet clearance on 3 sides is required 3-1/2 feet is required in front of the control panel (or minimum required by latest National Electrical code or applicable local codes).
Refer to the Instruction / Operators Manual before performing any maintenance.
INGERSOLLrAND ®
!
DANGER
!
CAUTION
Incorrect lifting of machine can cause injury or property damage.
Lift only from base channels.
I
!
WARNING
Discharge air. Can contain carbon monoxide or other contaminants.Will cause severe injury or death.
Do not breathe this air.
INGERSOLLrAND ®
!
WARNING
Hazardous voltage. Can cause severe injury or death.
Disconnect power before servicing. Lockout/Tagout machine.
INGERSOLLrAND ®
!
WARNING
High pressure air. Can cause severe injury or death.
Relieve pressure before removing filter plugs / caps, fittings or covers.
INGERSOLLrAND ®
NOTICE
Air discharge.
INGERSOLLrAND®
!
CAUTION
Use of incorrect coolant can cause system contamination.
Use only SSR ULTRA COOLANT.
INGERSOLLrAND ®
Exposed fan blade. Can cause severe injury.
Do not operate with covers removed. Disconnect power.Lock and tag.
INGERSOLLrAND ®
NOTICE
Lift here.
INGERSOLLrAND®
7
39859236
39541362
39544143
39557095
INGERSOLLrAND®
39544150
NOTICE
Filler Cap.
Use only recommended
coolant.
Read instruction book
before servicing.
39543921
39540281
12
10
11
16
14
15
13
!
WARNING
Hot surface. Can cause severe injury.
Do not touch. Allow to cool before servicing.
INGERSOLLrAND ®
!
CAUTION
Improper coolant filter replacement will cause compressor damage.
Replace filter element after first 150 hours of operation and every 2000 hours thereafter or when coolant is changed.
INGERSOLLrAND ®
! WARNING
Exposed moving belts and sheaves.
Can cause severe injury or death.
Do not operate with guards removed. Disconnect power, lock and tag out machine before servicing.
NOTICE
Before installing, operating, or performing any maintenance on this unit, read and understand the instructions in the Operators/Instruction Manual.
Before Starting
1. Check coolant level and add coolant if necessary.
2. Verify that main isolation valve is open.
3. Close main disconnect switch.
39859236
NOTICE
Rotation.
INGERSOLLrAND ®
Starting
1. Push START button. Compresor will start and load automatically.
2. Air Pressure will rise if there is sufficient demand for air.
Stopping
1. Pushing STOP button. Compressor will stop after 7-10 seconds.
2. Open main disconnect switch.
INGERSOLLrAND ®
39919246

1.0 RECEIPT OF EQUIPMENT

1.1 INSPECTION

When you receive the compressor please inspect it closely. Any indication of careless handling by the carrier should be noted on the delivery receipt especially if the compressor will not be immediately uncrated. Obtaining the delivery man’s signed agreement to any noted dam­ages will facilitate any future insurance claims.

1.2 UNPACKING AND HANDLING

The compressor package has been mounted on a base which provides for forklifting between the two side chan­nels to facilitate handling during shipment. Care in posi­tioning the forklifts is important because the location of the center of gravity is strongly affected by the location of the compression module and drive motor.
Slings can be used to lift the crates, but spreader bars must be used to prevent the slings from exerting a force against the sides of the crates.

1.3 TOOLS

Remove compressor unit from wooden skid. Acrowbar and hammer will be needed.
IMPORT ANT
READ THIS
LOST OR DAMAGED GOODS
THOROUGHLY INSPECT THIS SHIPMENT
IMMEDIA TELY UPON ARRIV AL
OUR RESPONSIBILITY FOR THIS SHIPMENT
CEASED WHEN THE CARRIER SIGNED
BILL OF LADING
If goods are received short or in damaged condition, it is important that you notify the carrier and insist on a notation of the loss or damage across the face of the freight bill. Otherwise no claim can be enforced against the transportation company.
If concealed loss or damage is discovered, notify your carrier at once and request an inspection. This is absolutely necessary. Unless you do this the carrier will not entertain any claim for loss or damage. The agent will make an inspection and grant a concealed damage notation. If you give the transportation company a clear receipt for goods that have been damaged or lost in transit, you do so at your own risk and expense.
WE, ATI-R, ARE WILLING TO ASSIST YOU IN EVERY POSSIBLE MANNER TO COLLECT CLAIMS FOR LOSS OR DAMAGE, BUT THE WILLINGNESS ON OUR PARTDOES NOT MAKE US RESPONSIBLE FOR COLLECTION OF CLAIMS OR REPLACEMENT OF MATERIAL. THE ACTUALFILING AND PROCESSING OF THE CLAIM IS YOUR RESPONSIBILITY.
Ingersoll-Rand Company Davidson, North Carolina
APDDGFO-99-79
FORKLIFT PADDING
WILL REDUCE SCRATCHES
AND MARS
SPREADER BARS
8

2.0 INSTALLATION

2.1 VENTILATION

Oil flooded rotary air compressors produce large amounts of heat. Because of this large heat production, the compressor must be placed in a room with adequate ventilation. Aroom in which the amount of air that is drawn in and exhausted is equal to or greater than the cooling fan air flow requirement for the compressor that is installed.
If heated air from the compressor exhaust is allowed to recirculate back to the compressor, the compressor will overheat and shut down. This heat must be exhausted from the room. You should take this into consideration when you decide where to place the compressor within your plant. Consider that the required maintenance clear­ance is 3 ft (.9 m) all around the compressor. However 42” (1.06m), or minimum required by latest NEC or applicable local codes, must be maintained in front of control panel.
Ambient temperatures higher than 115°F (46°C) should be avoided as well as areas of high humidity.
Consider also the environment surrounding or near the compressor. The area selected for the location of the compressor should be free of dust, chemicals, metal filings, paint fumes and overspray.

2.2 FOUNDATION REQUIREMENTS

Refer to the foundation plan for the particular model com­pressor to be installed. See Section 8.0.
The compressor can be installed on any level floor that is capable of supporting it. Compressor weights are listed on the foundation plans.
When sound transmission is of particular importance it is often helpful to install a sheet of rubber-fabric-matting, or cork under the compressor to reduce the possibility of resonant sounds being transmitted or amplified through the floor.

2.3 PIPING

The use of plastic bowls on line filters without metal guards can be hazardous. Their safety can be affected by either synthetic lubricants or the additives used in min­eral oil. From a safety standpoint, metal bowls should be used on any pressurized system. Review of your plant air line system is recommended.
The built-in aftercooler reduces the discharge air temper­ature well below the dew point (for most ambient condi­tions), therefore, considerable water vapor is condensed. To remove this condensation, each compressor with built-in aftercooler is furnished with a combination con­densate separator/trap.
DUST
CHEMICALS
METAL
FILINGS
PAINT
SPRAY
OVERSPRAY
Do not use plastic pipe, soldered copper
fittings or rubber hose for discharge piping.
WARNING
Never elevate the compressor unit
above the floor level. This may allow air
to enter the cabinet under the base.
Performance will be affected.
NOTICE
!
!
36”
(.9 m)
36” (.9 m)
42” (1.06 m) OR
CODE MINIMUM
9
AIR INTAKE
10
DISCHARGE PIPING WITH AFTERCOOLER
ROTARY-RECIP IN PARALLEL
Do not use the compressor
to support the discharge pipe.
Careful review of piping size from the compressor con­nection point is essential. Length of pipe, size of pipe, number and type of fittings and valves must be consid­ered for optimum efficiency of your compressor.
It is essential when installing a new compressor to review the total plant air system. This is to ensure a safe and effective total system.
Liquid water occurs naturally in air lines as a result of compression. Moisture vapor in ambient air is concentrat­ed when pressurized and condenses when cooled in downstream air piping.
Moisture in compressed air is responsible for costly prob­lems in almost every application that relies on com­pressed air. Some common problems caused by mois­ture are rusting and scaling in pipelines, clogging of instruments, sticking of control valves, and freezing of outdoor compressed air lines. Any of these could result in partial or total plant shutdown.
Compressed air dryers reduce the water vapor con­centration and prevent liquid water formation in com­pressed air lines. Dryers are a necessary companion to filters, aftercoolers, and automatic drains for improving the productivity of compressed air systems.
NOTICE
!
2.3 PIPING (Continued)
A dripleg assembly and isolation valve should be mount­ed near the compressor discharge. Adrain line should be connected to the condensate drain in the base.
IMPORT ANT: The drain line must slope downward from the base to work properly.
NOTE: For ease of inspection of the automatic drain trap operation, the drain piping should include an open funnel.
It is possible that additional condensation can occur if the downstream piping cools the air even further and low points in the piping systems should be provided with dri­plegs and traps.
IMPORT ANT: Discharge piping should be at least as large as the discharge connection at the compressor enclosure. All piping and fittings must be suitable for the maximum operating temperature of the unit and, at a minimum, rated for the same pressure as the compres­sor sump tank.
MOISTURE CONTENT OF COMPRESSED AIR
200
160
120
80
40
0
DEW POINT
without Aftercooling
100°F/38°C (with Aftercooler)
35°F /1.7°C (Refrigerated Dryer)
-40°F/-40°C (Desiccant Dryer)
Gallons of Water/24
hours/1000 acfm
ROTARY
COMPRESSOR
ISOLATION
VALVE
DRIP LEG
SAFETY
VALVE
PRESSURE
GAUGE
ISOLATION
VALVE
DRIP
LEG
SAFETY
VALVE
RECIPROCATING
COMPRESSOR
TRAP
ISOLATION
VALVE
ISOLATION
STRAINER
NOTE: SEPARATE LINES GOING TO THE RECEIVER
VALVE
DRIP
LEG
ROTARY
COMPRESSOR
11

2.4 ELECTRICAL INSTALLATION

Before proceeding further, we recommend that you review the safety data in the front of this manual.
Locate the compressor data plate on the left end of the cooler box next to the control box.
The data plate lists the rated operating pressure, the maximum discharge pressure and the electric motor characteristics and power.
Confirm that the line voltage and compressor nameplate voltage are the same and that the standard starter box meets the intent of NEMA 1 guidelines.
A hole is provided for incoming power connection. If it is necessary to make a hole in the control box in a different location, care should be taken to not allow metal shav­ings to enter the starter and other electrical components within the box. After making the power inlet hole, all shavings and debris must be removed from inside of control box before power is turned on.
Incoming power should be connected per the electrical schematic on the starter box door. Confirm that all electri­cal connections are made and tightened. Confirm that the control transformer is wired correctly for supply volt­age (See Figure 2.5-1).
Inspect the motor and control wiring for tightness. Close the panel front.
Two types of dryers, refrigerated or desiccant, are used to correct moisture related problems in a compressed air system. Refrigerated dryers are normally specified where compressed air pressure dew points of 33°F (1°C) to 39°F (4°C) are adequate. Desiccant dryers are required where pressure dew points must be below 33°F (1°C).
Contact your local Ingersoll-Rand distributor for assis­tance in selecting correct Ingersoll-Rand filtration or dry­ing products.
NOTE: Screw type compressors should not be installed in air systems with reciprocating compressors without a means of pulsation isolation, such as a common receiver tank. We recommend both types of compressor units be piped to a common receiver utilizing individual air lines.
When two rotary units are operated in parallel, provide an isolation valve and drain trap for each compressor before the common receiver.
ROT ARY TWO COMPRESSOR SYSTEM
SAFETY
VALVE
PRESSURE
GAUGE
ISOLATION
VALVE
ROTARY
COMPRESSOR
TRAP
DRIP
LEG
ISOLATION
STRAINER
VALVE
ISOLATION
VALVE
DRIP
LEG
COMPRESSOR
ROTARY
12

2.5 VOLTAGE CONVERSION

IMPORTANT: This procedure should only be carried out by a qualified electrician, electrical contractor or your local Ingersoll Rand Distributor or Air Center
NOTE: This procedure applies only to units manufac­tured to multi-voltage specifications. Motor nameplate must indicate multiple voltatges.
FIGURE 2.5-1 TYPICAL CONTROL TRANSFORMER WIRING
110V
LINE VOLTS HZ LINE SEC VOLTS LINE
200 60 H4-H5 120 X1-X2
8 X3-X4 8 X4-X5
220/230 60 H3-H5 120 X1-X2
8 X3-X4 8 X4-X5
380 60 H3-H5 120 X1-X2
8 X3-X4 8 X4-X5
440/460 60 H2-H5 120 X1-X2
8 X3-X4 8 X4-X5
575 60 H1-H5 120 X1-X2
8 X3-X4 8 X4-X5
LINE VOLTS HZ LINE SEC VOLTS LINE
220 50 H5-H6 110 X1-X2
8 X3-X4 8 X4-X5
380 50 H4-H6 110 X1-X2
8 X3-X4 8 X4-X5
415 50 H2-H6 110 X1-X2
8 X3-X4 8 X4-X5
550 50 H1-H6 110 X1-X2
8 X3-X4 8 X4-X5
LINE VOLTS HZ LINE SEC VOLTS LINE REFERENCE
200 60 H4-H5 120 X1-X2 Quad Type
220/230 50/60 H1-H2 120 X1-X4 Universal Type
380 50/60 H1-H3 120 X1-X4 Universal Type
415 50 H1-H3 120 X1-X4 Universal Type
440/460 50/60 H1-H4 120 X1-X4 Universal Type
550/575 60 H1-H5 120 X1-X4 Universal Type
*TYPICAL 60 HZ
CONTROL TRANSFORMER
(INTELLISYS OPTION)
*TYPICAL 50 HZ
CONTROL TRANSFORMER
(INTELLISYS OPTION)
H4
H5
H6
HIGH VOLTAGE PRIMARY
SIDE
HIGH
VOLTAGE
PRIMARY
SIDE
LOW
VOLTAGE
SECONDARY
SIDE
LOW
VOLTAGE
SECONDARY
SIDE
UNIVERSAL TYPE TRANSFORMER
(ALL VOLTAGES EXCEPT 200V/60 HZ)
QUAD TYPE TRANSFORMER (200V/60 HZ)
*TYPICAL CONTROL TRANSFORMER
(STANDARD OPTION)
If the compressor is operated in the
opposite direction of rotation, airend damage
can result and is not warrantable.
CAUTION
Open the motor junction box on the side of the motor. Reconnect the motor to the desired voltage. Use the con-
nection decal provided on the motor as a guide. Reconnect the primary side of the control transformer for
the desired voltage, as shown on the control transformer wiring decal.
Refer to the motor nameplate for full load amps. Set main fan the dial position of the overload relay to the cor­responding setting.
Make sure all wiring connections are tight. Put main disconnect in the ON position and check main
motor and fan motor rotation, as outlined in Section 2.6 of this manual.

2.6 ROTATION CHECK

Locate the rotation decal on the motor and check for cor­rect rotation. The correct rotation when viewed from the non-drive end of the motor is clockwise (See Figure 2.6-
1).
!
FIGURE 2.6-1 DRIVE MOTOR ROTATION
NON-DRIVE
END
DRIVE
END
FIGURE 2.5-2 MAIN DISCONNECT
LOCKED AND TAGGED
DANGER
Procedure:
Put main disconnect in the OFF position, lock and tag (See Figure 2.5-2).
For the compressor motor and fan rotation check, the motor jogging should be as short a time as possible.
1. Assure that the Emergency Stop button is in the stop (depressed) position.
2. Check coolant level. To check coolant level, slowly loosen the fill plug one complete turn. As the fill plug is unscrewed approximately one complete turn, a small amount of pressure may be released. Do not remove the fill plug until all pressure has been vented. Once pressure is vented, finish removing the fill plug. The proper coolant level is when the coolant is even with the top of the fill port. Add coolant if necessary.
3. Replace and tighten fill plug.
4. Close the main disconnect switch (ON position).
5. Verify that the main isolation valve is open.
6. Open the canopy enclosure if machine is so equipped. Push the red unloaded Stop/Reset Button. Push the Start button to start the unit and immediately depress (push) the Emergency Stop button to stop the unit (See Figure 2.7-1 for Control Panel layout).
NOTE: Do not use the Unloaded Stop Button for this procedure; it is equipped with a time delayed stop cir­cuit and damage may occur to the compression mod­ule if operated in wrong direction.
Observe the compressor drive motor shaft. The rota­tion should be in accordance with the directional arrow decal on the motor. Observe the cooling fan (s). The rotation of the main fan should be counter-clockwise. The auxiliary fan rotation should be clockwise. (See Figures 2.6-2 and 2.6-3.
Should the main motor or fan rotation be incorrect, put the main disconnect in the OFF position, lock and tag.
Interchange any two line connections (L1, L2, or L3) at the starter panel for the appropriate component. Close the control box cover. Recheck for correction rotation.
13
DANGER
HASP
KEY LOCK
HIGH VOLTAGE
LEVER
DANGER
TAG
14

2.7 BEFORE STARTING - STARTING - STOPPING Read and understand the following instructions

before operating or performing any maintenance on this unit
Before Starting:
1. Ensure that Emergency Stop push button is in the OFF (depressed) position (See Figure 2.7-1).
2. Check coolant level. To check coolant level, slowly loosen the fill plug one complete turn. As the fill plug is unscrewed approximately one turn, a small amount of pressure may be released. Do not remove the fill plug until all pressure has been vented. Once pressure is vented, finish removing the fill plug. The proper coolant level is when the coolant is even with the top of the fill port. Add coolant if necessary.
3. Replace and tighten fill plug.
4. Close the main disconnect switch (ON position).
5. Verify that the main isolation valve is open.
Starting
1. Push the unloaded Stop/Reset Button (red fault indicator will go out).
2. Push the Start button and release. The compressor­will start and then load automatically if line pressure is below the lower setting of the pressure switch.
FIGURE 2.6-2 MAIN FAN
FIGURE 2.6-3 AUXILIARY FAN
CORRECT ROTATION CORRECT ROTATION
Stopping
1. Depress the Stop button to the OFF position. Compressor will unload for approximately 7 seconds and then stop.
2. Open the main disconnect switch (OFF position).
FIGURE 2.7-1 CONTROL PANEL
EMERGENCY
STOP
BUTTON
CONTROL
PANEL
HOUR
METER
START
BUTTON
PRESSURE
GAUGE
UNLOADED
STOP/RESET
BUTTON
POWER ON
INDICATOR
AUTO
RESTART
INDICATOR
FAULT
ALARM
INDICATOR
TEMP
GAUGE
15

2.8 OUTDOOR SHELTERED INSTALLATION

Many times a compressor must be installed outside due to jobsite conditions or limited space within a manufactur­ing facility. When this occurs there are certain items that should be incorporated into the installation to help ensure trouble free operation. These items have been listed below plus Figure 2.8-1 has been included to show a typ­ical outdoor sheltered installation. The unit must be pur­chased with the Outdoor Modification Option to provide watertight electrics and a TEFC motor.
The compressor should be on a concrete pad
designed to drain water away. If the concrete pad is sloped, then the compressor must be leveled. In order to properly pull cooling air through the aftercooler, the base/skid must be sealed to the concrete pad.
The roof of the shelter should extend a minimum of
4 ft (1.2 m) around all sides of the compressor to pre­vent direct rain and snow from falling on the unit.
Air-cooled machines must be arranged under the
shelter in a way that prevents air recirculation (i.e. hot exhaust back to the package inlet).
If the installation includes more than one compressor,
the hot air exhaust should not be directed towards the fresh air intake of the second unit or an Air Dryer.
If a standard machine is to be installed outside, the
ambient temperature must never drop below 35°F (1.7°C).
Arrange the machine with the Intellisys con-
troller/starter enclosure facing away from the sun as radiant heat can affect starter/lntellisys performance. Also direct sunlight and UV rays will degrade the membrane touch panel. This is not a warrantable situ­ation.
Power disconnect switch should be within line of sight
and in close proximity to the unit. N.E.C. and local electrical codes must be followed when installing the power disconnect switch.
Condensate drains must never be allowed to dump on
the ground. Run to a suitable sump for future collec­tion and disposal or separation of lubricant and water mixture.
Incoming power connections must use suitable con-
nectors for outdoor weather tight service.
A minimum of 3 ft (.9 m) clearance must be allowed
on all four sides of the unit for service access. However 42 (1.06m), or minimum required by latest NEC or applicable local code, must be maintained in front of control panel.
If possible, access by a forklift and/or an overhead
beam hoist should be kept in mind (for eventual ser­vice to airend or motor).
If the area around the installation contains fine air-
borne dust or lint and fibers etc., then the unit should be purchased with the High Dust Filter Option and TEFC motor option.
Some type of protection such as a fence or security
system, should be provided to prevent unauthorized access.
16
FIGURE 2.8-1 TYPICAL OUTDOOR SHELTERED INSTALLATION
17

3.0 SYSTEMS

3.1 GENERAL SYSTEM INFORMATION

The compressor is an electric motor driven, single stage, rotary screw compressor, complete with support­ing components to make a fully functional unit. Astan­dard compressor is composed of the following: Inlet air filter Drive motor Airend Pressurized coolant system with cooler & filter Cooling fan (s) Capacity control Instruments Safety devices
Compression in the rotary screw type air compressor is created by the meshing of two helical rotors (male and female) on parallel shafts, enclosed in a heavy duty iron housing, with air inlet and outlet ports located on opposite ends. The grooves of the female rotor mesh with and are driven by the male rotor. Bearings on both ends of the rotors are used to support the rotor both laterally and axially.

3.2 AIRCOOLED COMPRESSORS

Design Temperatures
The standard compressor is designed for operation in an ambient range of 35°F. to 115°F. (1.7°C. to 46°C.). When conditions other than design levels described are encountered, we recommend you contact your nearest Ingersoll-Rand representative for additional information.
The standard maximum temperature 115°F. (46°C) is applicable up to an elevation of 3300 ft. (1000 meters) above sea level. Above this altitude, signifi­cant reductions in ambient temperature are required if a standard drive motor is to be used.
Coolant Cooler
The cooler is an integral assembly of core, fan and fan-motor, mounted in the compressor. The cooling air flows in through the front corners of the enclosure, through the vertically mounted cooler core, and dis­charges upward through the top of the enclosure.
Aftercooler
The discharge air aftercooling system consists of a heat exchanger (located at the cooling air discharge of the machine), a condensate separator, and an automatic drain trap.
By cooling the discharge air, much of the water vapor naturally contained in the air is condensed and eliminated from the downstream plant-piping and equipment.

3.3 COOLANT SYSTEM

The coolant system consists of a separator tank, thermostatic element, coolant filter, coolant cooler with fans, and a separator element. When the unit is operating, the coolant is pressurized and forced to the compressor bearings. The compressor is provided with a temperature switch which will shut the unit down in case of excessive temperature, 228°F (109°C). Effective coolant filtration is provid­ed by the use of a screw on, automotive type, heavy duty coolant filter.
The compressor is designed for operation in an ambient range of 35°F to 115°F (2°C to 46°C).
Coolant
Rotary screw compressor fluids have a triple func­tion to perform. They lubricate the bearings and contacting surfaces of the rotors, seal internal clearances within the rotor chamber, and provide for the cooling of the compression process. The bulk of the fluid is actually used for cooling, with only small amouts used for lubrication and sealing.
SSR air compressors are factory filled with SSR ULTRA COOLANT which is designed to operate for 8,000 hours or two years, whichev­er comes first. The coolant must be changed at these intervals to avoid breakdown and equip­ment damage.
Circulation of Coolant
Coolant is forced by air pressure from the separa­tor tank to the thermostatic element. The position of the element (a direct result of coolant tempera­ture) will determine whether the coolant circulates through the cooler, bypasses the cooler, or mixes the two paths together to maintain an optimum compressor injection temperature. This tempera­ture is controlled to preclude the possibility of water vapor condensing. By injecting coolant at a sufficiently high temperature, the discharge air coolant mixture temperature will be kept above the dew point.
18
Before being injected into the airend, all coolant flows through the coolant filter. If tis an aubomotive type full flow filter with a single replacement spin-on element, rated at 4 micron. There is a differential-pressure bypass valve set to open in the event that the pres­sure drop across the filter rises to as high as 15 psi (1 bar), which indicates an excessively fouled element as well as poor maintenance practice.
Coolant/Air Separation System
The coolant/air separation system is composed of a separator tank with specially designed internals and a coslescing type separator element located inside the tank.
The air-coolant mixture discharges from the airend into the separator tank. The majority of coolant is separted while in the separator tank and the coalescing separa­tor filter element is used for final cleaning of the air prior to the customers system. The system removes nearly all of the coolant from the discharge air. The separated coolant is returned to the coolant system and the air passes to the compressed air system.

3.4 AIR SYSTEM

Components and Flow
The air system is composed of: Inlet air filter Inlet control valve (ICV) Airend (rotors) Coolant/Air separator Minimum pressure check valve (MPCV) Aftercooler Moisture separator/drain trap (optional)
The direction of flow is from the inlet filter to the after­cooler. Refer to procedure and instrumentation dia­grams in Section 8.0.
Functions of Components
Inlet air filter, filters the incoming air, trapping 99.9% of particles 3 micron and larger.
Inlet valve opens full for on-line opeation. The valve closes in the off-line mode and at shutdown
which prevents back flow of the compressed air. The airend compresses the air. The separator tank removes most of the coolant from
the air.
The separator element performs the final separation of coolant and cleaning of the air prior to leaving the compressor.
The minimum pressure check valve keeps the separa­tor tank and separator element at a minimum pressure to ensure adequate oil flow and proper coolant/air sep­aration. It also prevents line pressure from exhausting back through the airend at shutdown and during peri­ods of unloaded operation.
The aftercooler cools the air prior to leaving the pack­age.

3.5 ELECTRICAL SYSTEM

The electrical system of each SSR compressor is built with electro-pneumatic controls as standard, or with the micro-processor based Intellisys controller as an option.
The standard electrical/electronic components, enclosed in a readily accessible enclosure include:
1. Push buttons control w/analog gauges
2. Neon indicators
3. Switching relays/timers
4. Control transformers and fuses
5. Compressor motor starter, with auxiliary contacts and overload relays
6. Optional Intellisys controller in place of #1, 2, and 3
By use of a built-in Automatic Across-The-Line type starter, the compressor can be started using full volt­age electric current. The starter is completely automat­ic and controlled by the Intellisys controller. Refer to the electrical schematic, Section 8.0 schematic 8.1 (Standard controller) or 8.3 (Intellisys controller).
By use of an optional built-in Star-Delta type starter, the compressor motor can be started and accelerated using a greatly reduced inrush electric current. The starter is completely automatic and controlled by the Intellisys controller. Refer to the electrical schematic, Section 8.0 schematic 8.2 (Standard control) or 8.4 (Intellisys control).
Options such as remote start/stop or power outage restart with remote start/stop can be added by installing a plug-in module in the controller.

3.6 CAPACITY CONTROL

The SSR compressor is supplied with on-line/off-line and automatic start/stop controls as standard. Optional modulation control enables the compressor to operate with a throttled inlet flow for air systems which have a relatively high constant demand relative to compressor capacity.
On-Line/Off-Line With Automatic Start/Stop Control
The compressor will deliver air at full capacity, (the compressor maximum efficiency condition) or will operate at zero capacity with high receiver pressure (the compressor minimum power condition), while the unit continues to run.
When the compressor starts and line pressure is below the lower setting of the line pressure switch, control solenoid 1SV will be energized (close), inlet control valve ICV will open, and the compressor will load. When the line pressure reaches the upper set­ting of the pressure switch, the compressor will unload by de-energizing (opening) 1SV and closing ICV. Solenoid 1SV relieves the internal pressure of the compressor back to the inlet filter. The only adjustment required is setting of the pressure switch.
A time delay relay is energized and begins to time out. The timer, mounted in the control box, is factory set at 10 minutes. It will continue to operate for as long as its time setting, after which a relay contact opens to de-energize the compressor starter coil. At the same time, an amber light (1LT) on the control box is lit to indicate the compressor has shut down automatically and will restart automatically. The auto­matic restart will take place when the line pressure drops to the lower setting of the pressure switch.
Adjusting the adjustable timer below the 10 minute factory setting may shorten the life of the compressor drive motor.

3.7 PRESSURE SWITCH ADJUSTMENT

Locate the pressure switch as shown in Figure 3.7-1. The pressure switch can be adjusted using the follow­ing procedure:
1. Open, lock and tag the main electrical disconnect. Do not adjust the pressure switch with power on or machine operating.
FIGURE 3.7-1 PRESSURE SWITCH ADJUSTMENT
5
2
3
4
2. Remove pressure switch cover by turning the cover screw counterclockwise. NOTE: It is required that the load or on-line pressure be set first, before the unload or off-line pressure is set.
3. Set the on-line pressure by turning screw 5 (See Figure 3.7-1). Turn clockwise to increase setting or counter-clockwise to decrease setting (indicated by pointer 4).
4. Set the off-line pressure by turning screw 2. Turn screw counter-clockwise to increase setting or clock­wise to decrease setting (indicated by pointer 3).
CAUTION: DO NOT EXCEED NAMEPLATE RATING OF THE COMPRESSOR.
5. Start compressor and test adjustment(s) made. If necessary, readjust according to steps 1-4 above.
19
3.8 MODULATION/ACS CONTROL (OPTIONAL)
For those plants which have relatively high constant air demand, relative to the compressor capacity, the recommended control mode is modulation.
The modulation control system retains the features of the on-line/off-line control, but also provides for throttling of the inlet flow up to the off-line air pres­sure setpoint value.
By applying line pressure to an adjustable modulator valve, the throttling position of the inlet valve is con­trolled, thus allowing the modulator to "trim" the inlet valve position as dictated by the line pressure.
The modulating pressure range is about 4 psig (0.3 BAR) and the modulator is factory set to straddle the compressor rated pressure. Modulation begins when the line pressure reaches about 99 percent of the compressor rated pressure and continues as/if the line pressure rises. Modulation becomes stable when the compressor output equals the plant air demand. When the modulation is at the factory set­ting, the maximum capacity reduction will be approx­imately 60 percent of the compressor rated capacity (as indicated in Figure 3.8-1).
FIGURE 3.8-1
Capacity control of machines supplied with standard electro-pneumatic controls and the modulation option can be manually switched from on-line/off-line with auto start/stop to modulation via a rotary selector switch located adjacent to the pressure switch.
3.9 ACS CONTROL (INTELLISYS MODULATION OPTION ONLY)
For compressors supplied with Intellisys control and modulation options, ACS control will allow the com­pressor to automatically switch between on-line/off­line and modulation control, depending on air demand.
If the air demand has decreased to a level below the 60 percent modulated output, the line pressure will increase slightly to actuate the Intellisys. The compressor will then shift to the off-line control position, and operate unloaded with the compressor vented.
20
It is sometimes desirable to begin modulation at a higher pressure than the standard factory setting, thereby increasing the modulated capacity at the time the Intellisys is actuated. Refer to Figure 3.8­1 for modulated capacities available when this is done.
The compressor will then operate to deliver full capacity air to the plant system. If the plant air system pressure rises to that of the Intellisys off­line set point, pressurized air will be sent to the inlet valve causing it to close, and to the blow­down valve, causing it to open.
The compressor will continue to run unloaded, but since pressure levels have reduced, it will do so with a minimum power draw.
The Intellisys®has a fixed minimum differential of 10 psi between the off-line air pressure setting and the on-line air pressure setting. The differential may be increased by adjusting the on-line air pressure set­ting of the Intellisys
®
. Refer to Section 4.4 for instructions. The automatic control selector (ACS) is designed to
continuously monitor the plant air demand and select either the on-line/off-line, or the modulate control mode - whichever is most desirable at any­time during an operating day.
It allows the compressor to operate in its most efficient mode without attendance, thereby reducing power costs to a minimum.
When the compressor operates in the on-line/off-line control mode, the length of time the compressor remains in the "off-line" condition is an indication of the plant air demand. Intellisys controller is sensing and awaiting a sufficient line pressure decrease before signaling a shift to the on-line mode. If the "off-line" time period is relatively short, thereby indi­cating a high demand for air, it is preferable to shift the control system to upper range modulation.
The Intellisys
®
does this, and does it automatically if the compressor unloads 3 times within a 3 minute time period.
If later, the plant demand decreases, and even under modulate control the line pressure reaches the setting of the Intellisys
®
controller, and the control shifts to the "off-line" mode, the time in this mode will still be monitored. Along "off-line" time­period indicates a low plant air demand, indicating the desirability of operating in the on-line/off-line mode.
The Intellisys
®
then does this, and does it automatically if the compressor operates unloaded for more than 3 minutes.
Modulation Only
If MODULATION ONLY is turned on in the setpoint routine, the unit will shift to Modulation control mode immediately when the unit is running. The 3 cycles within 3 minutes time period required for ACS to change to Modulation mode is bypassed. The unit will stay in Modulation mode until the unit runs unloaded for 3 minutes (the unit then returns to ACS control) or MODULATION ONLY is turned off via the set routine.
Delay Load Time
This is the amount of time the line pressure must remain below the on-line setpoint before the com­pressor will load or start (if the unit was stopped due to an auto start/stop situation). Setting the load delay time to 0 will cause no delay. When the delay load timer becomes active, the display will switch to pack­age discharge pressure (if not displaying package discharge pressure at that time) and then display the delay load count down. Once the count down reach­es 0, the unit will load or start and the display will return to line pressure. The display select button is inactive during the delay load count down.
21
Loading...
+ 51 hidden pages