Ingersoll Rand X-iri User Manual

4.6 (19)

Ingersoll Rand

X-IRI Communications Gateway

Operators Manual

Before installing or starting this unit for the first time, this manual should be studied carefully to obtain a working knowledge of the unit and/or the duties to be performed while operating and maintaining the unit.

RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the unit at all times.

More Than Air. Answers.

Online answers: http://www.air.irco.com

C.C.N. :

80445596

REV.

A

DATE:

June 2009

SECTION 1 — TABLE OF CONTENTS

SECTION 1 — TABLE OF CONTENTS................................

1

SECTION 2 — INTRODUCTION .......................................

2

SECTION 3 — SAFETY.....................................................

2

SAFETY PRECAUTIONS ....................................................

2

INSTALLATION ................................................................

2

OPERATION ....................................................................

2

MAINTENANCE AND REPAIR...........................................

3

SECTION 4 — COMPRESSOR CONNECTION AND CONTROL

.....................................................................................

4

COMPRESSOR CONNECTION AND CONTROL..................

4

INTELLISYS SOFTWARE REQUIREMENTS.........................

4

MODBUS RTU .................................................................

5

SECTION 5 — INSTALLATION .........................................

8

UNIT LOCATION..............................................................

8

POWER SUPPLY ..............................................................

8

DCS OR PLC CONNECTION ..............................................

9

COMPRESSOR IR BUS CONNECTION ..............................

9

DCS OR PLC COMMUNICATIONS ..................................

10

COMPRESSOR COMMUNICATIONS: .............................

10

OPERATIONAL INDICATIONS ........................................

10

RS 485 NETWORK.........................................................

12

MODBUS ADDRESS SELECTION.....................................

13

MODBUS PORT SETUP SELECTION................................

14

GATEWAY SOFTWARE VERSION DISPLAY .....................

15

COMMISSIONING PROCEDURE ....................................

16

SECTION 6 PARTS LIST ...............................................

17

SECTION 7 TECHNICAL DATA .....................................

17

SECTION 8 – INTELLISYS MODBUS TABLES ....................

18

TABLE 1 SSR (REDEYE) CONTROLLER ............................

18

TABLE 2 SSR (SG) CONTROLLER ....................................

21

TABLE 3 SSR (SE) 15 100HP CONTROLLER ....................

26

TABLE 4 SIERRA (REDEYE) 125 200 HP CONTROLLER ...

29

TABLE 5 SIERRA (SE) 50 100 HP CONTROLLER..............

32

TABLE 6 SIERRA (SG) 125 400 HP CONTROLLER ...........

35

TABLE 7 SSR (SG) CONTACT COOLED RETROFIT

 

CONTROLLER................................................................

39

TABLE 8 RECIP (REDEYE) CONTROLLER.........................

44

TABLE 9 RECIP (SG) CONTROLLER.................................

48

TABLE 10 RECIP BOOSTER (REDEYE) CONTROLLER.......

52

TABLE 11 NIRVANA (SGN) CC (CONTACT COOLED)

 

CONTROLLER................................................................

56

TABLE 12 NIRVANA (SGNE) CC (CONTACT COOLED)

 

CONTROLLER................................................................

60

TABLE 13 NIRVANA SGNE OF (OIL FREE) CONTROLLER65

TABLE 14 SSR UP (SE) CONTROLLER.............................

69

TABLE 15 ESA (SE) 22 – 150 KW CONTROLLER .............

72

TABLE 16 R SERIES (S3) CONTROLLER..........................

75

TABLE 17 NIRVANA 15 30 KW (20 40 HP) DF

 

CONTROLLER................................................................

77

Refer to Section Indicated

Note

Important or Caution, Safety

1

SECTION 2 — INTRODUCTION

The X-IRI Communication Gateway is designed to interface the Intellisys Controllers on Ingersoll Rand Compressors with a Distributed Control System (DCS), Programmable Logic Controller (PLC), or any other device that is capable of communicating using the MODBUS RTU communications protocol.

The X-IRI provides MODBUS connectivity to Ingersoll Rand controllers that do not have built-in MODBUS capability. The X-IRI also provides address filtering and communication buffering capabilities to protect the integrity of the serial data network.

The X-IRI is designed to be DIN Rail mounted within the compressor control gear enclosure but can alternatively be mounted remotely within a separate enclosure.

SECTION 3 — SAFETY

SAFETY PRECAUTIONS

!WARNING : Risk of Danger

WARNING : Risk of Electric Shock

!

WARNING : Risk of High Pressure

 

 

WARNING : Consult Manual

Before installing or operating the X-IRI GATEWAY, take time to carefully read all the instructions contained in this manual, all compressor manuals, and all manuals of any other peripheral devices that may be installed or connected to the unit.

Electricity and compressed air have the potential to cause severe personal injury or property damage.

The operator should use common sense and good working practices while operating and maintaining this system. All applicable codes should be strictly adhered to.

Maintenance must be performed by adequately qualified personnel that are equipped with the proper tools.

INSTALLATION

Installation work must only be carried out by a competent person under qualified supervision.

A fused isolation switch must be fitted between the main power supply and the X-IRI GATEWAY.

The X-IRI GATEWAY should be mounted in such a location as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times.

If raised platforms are required to provide access to the X-IRI GATEWAY, they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides.

OPERATION

The X-IRI GATEWAY must only be operated by competent personnel under qualified supervision.

Never remove or tamper with safety devices, guards or insulation materials fitted to the X-IRI GATEWAY.

The X-IRI GATEWAY must only be operated at the supply voltage and frequency for which it is designed.

When main power is switched on, lethal voltages are present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit.

Do not open access panels or touch electrical components while voltage is applied unless it is necessary for measurements, tests or adjustments. Such work should be carried out only by a qualified electrician equipped with the correct tools and wearing appropriate protection against electrical hazards.

All air compressors and/or other equipment connected to the unit should have a warning sign attached stating “THIS UNIT MAY START WITHOUT WARNING” next to the display panel.

If an air compressor and/or other equipment connected to the unit is to be started remotely, attach two warning signs to the equipment stating “THIS UNIT CAN BE STARTED REMOTELY”. Attach one sign in a prominent location on the outside of the equipment, and the other sign inside the equipment control compartment.

2

MAINTENANCE AND REPAIR

Maintenance, repairs or modifications must only be carried out by competent personnel under qualified supervision.

If replacement parts are required, use only genuine parts from the original equipment manufacturer, or an alternative approved source.

Carry out the following operations before opening or removing any access panels or carrying out any work on the X-IRI GATEWAY:

i.Isolate the X-IRI GATEWAY from the main electrical power supply. Lock the isolator in the “OFF” position and remove the fuses.

ii.Attach labels to the isolator switch and to the unit stating “WORK IN PROGRESS - DO NOT APPLY VOLTAGE”. Do not switch on electrical power or attempt to start the X-IRI GATEWAY if such a warning label is attached.

Make sure that all instructions concerning operation and maintenance are strictly followed and that the complete unit, with all accessories and safety devices, is kept in good working order.

The accuracy of sensor devices must be checked on a regular basis. They must be calibrated when acceptable tolerances are exceeded. Always ensure any pressure within the compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device.

The X-IRI GATEWAY must only be cleaned with a damp cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis.

Do not paint the control faceplate or obscure any indicators, controls, instructions or warnings.

3

SECTION 4 — COMPRESSOR CONNECTION AND CONTROL

COMPRESSOR CONNECTION AND CONTROL

The X-IRI Gateway module is designed to interface to any Ingersoll Rand Intellisys controlled compressor. All Ingersoll Rand compressors equipped with Intellisys controllers must use this interface when communicating with MODBUS masters.

The X-IRI gateway prevents the compressor controller from seeing any communications that aren’t directed toward the controller’s network address. Additionally, the X-IRI will buffer communications so that the compressor controller will not receive a command greater than once every 500 milliseconds.

Setting a MODBUS polling rate of less than 500 milliseconds will not cause a quicker response from X-IRI.

The PLC or DCS communicates to the X-IRI Gateway via a two wire, RS-485 network utilizing the MODBUS RTU protocol.

The X-IRI Gateway module is installed within the compressor control cabinet and connected to the PLC or DCS using Belden 9841 or equivalent RS-485 cable.

INTELLISYS SOFTWARE

REQUIREMENTS

Each Intellisys controller must have its controller software revision at or above a certain minimum level to work with the IRI.

The machine types and required software EPROM minimum version levels are listed below. Check the machine to be connected to an IRI for the appropriate EPROM. If the EPROM is not of the correct minimum version level, the appropriate EPROM may be ordered from your local Ingersoll Rand Distributor or Air Center.

Machine Type EPROM Minimum Version Level

 

SSR 50-450 Horsepower - 1 stage (Red Eye)

2.3

SSR 50-450 Horsepower - 2 stage (Red Eye)

2.3

SSR SG

1.0

15-50 Horsepower

1.4

Sierra 50-100 Horsepower (SE)

1.2

Sierra 100-200 Horsepower (Red Eye)

2.5

Sierra 125-400 HP SG

1.0

Recip (Red Eye)

1.6

Recip SG

1.0

Nirvana SGN

1.0

Nirvana SGNe CC

2.0

Nirvana SGNe OF

1.0

Pegasus

1.0

ESA SE 22-150 KW

1.6

When monitoring compressor data only, no options are required to be installed in the Intellisys controller. If machine control is desired, the Remote Start/Stop and Sequence options must be installed and turned "On".

4

MODBUS RTU

MODBUS Table(s)

This document discusses generic MODBUS communications and how to implement the software specific ‘MODBUS Table’ information. MODBUS communication formatting may differ from controller to controller and you may require more than one ‘MODBUS Table’.

Always check the software variant identification and version number for a controller with the variant and version of the ‘MODBUS Table’ supplied. In some instances the information contained in a ‘MODBUS Table’ may not be applicable to a controller installed with the same software variant but a different version number.

General

MODBUS RTU (Remote Terminal Unit) is a master-slave type protocol. An Intellisys Controller functions as the slave device. Information requests or commands are communicated from master to slave only through the X-IRI. The X-IRI will always respond to communications from a remote master device in accordance with the MODBUS RTU protocol standard.

The MODBUS protocol is used to communicate with personal computers (PC), Programmable Logic Controllers (PLC’s), or Distributed Control Systems (DCS) over the Network port. The X-IRI only responds to two MODBUS commands, Read Holding Register 03 (03 Hex) and Preset Single Register 06 (06 Hex). (See Modicon MODBUS Protocol Reference Guide, PI-MBUS-300 Rev. J or later, for more details on MODBUS).

Communication Link

MODBUS is implemented using a two-wire RS485 industry standard communications link operating in master-slave mode.

Polarity of the two RS485 wires (L1+ and L2-) is important; reversal will disrupt communications.

RS485 Serial Data Format

The RS485 MODBUS port is a 2-wire operating with an asynchronous serial data format: 8 data bits / no parity / 1 or 2 stop bits (8,N,1 or 8,N,2) - transmitted at 9600 baud.

Message Data Format

The bytes of the MODBUS RTU message must be sent in one message package. The RTU protocol allows for a maximum pause of 1.5 byte-times between 2 consecutive bytes of a message.

A pause longer than 1.5 byte-times will render the message invalid and it will be ignored.

Message data format is dependent on function and will consist of a combination of the following elements:

1)Destination address (slave network address)

2)Function Code

3)Data start address (slave register start address)

4)Number of registers, number of bytes of data

5)Message data

6)CRC checksum

Message Destination Address

The ‘destination address’ must be correct for the ‘slave’ controller device for which the message is intended. An address can be from 1 to 127 decimal (01Hex to 7FHex). The SMG Box is transparent and addresses must be for the destination ‘slave’ controller or unit. Each controller or unit must be set with a unique address.

Slave

Function

Start

Number of

CRC Check

Address

Code

Address

Registers

Sum

 

 

 

 

 

22

03

00 6F

00 02

F3 45

Slave Address = 22Hex = 34 Decimal

Message Function Codes

The message function code defines the required data processing operation of the slave controller. Although several types of message function codes are defined by the MODBUS standard, only the message function code types working directly with registers are implemented on controller units:

03H Read Holding Register(s) – Read

06H Preset Single Register - Write

Slave

Function

Start

Number of

CRC Check

Address

Code

Address

Registers

Sum

 

 

 

 

 

22

03

00 6F

00 02

F3 45

Function Code = 03 = Read Holding Register

Any other message function code type will result in an EXCEPTION response.

5

Message Data Start Address

The message data start address (16bit word) designates the initial register address location in the controller from which the data is processed. Start address information is contained in the ‘MODBUS Table’.

Slave

Function

Start

Number of

CRC Check

Address

Code

Address

Registers

Sum

 

 

 

 

 

22

03

00 6F

00 02

F3 45

Start Address = 6F = 40112

High-byte transmitted first followed by low-byte.

Message Data

The message data content depends on the message function code type.

03H Read Holding Register(s)

The Number of Registers designates the 16bit integer value that determines the size (in 16bit ‘word’ registers) of the message data being requested. This is the number of 16bit registers to read. This information is contained in the ‘MODBUS Table’.

A maximum of 32 registers can be read at one time.

Slave

Function

Start

Number of

CRC Check

Address

Code

Address

Registers

Sum

 

 

 

 

 

22

03

00 6F

00 02

F3 45

The example above is a request to read offline pressure (register 40112) and online pressure (register 40113) from X-IRI address 22(Hex)

06H Preset Single Register

The Data byte 0 byte 1 designates the value of the 16bit integer word to be written to the Intellisys controller. This information is contained in the ‘MODBUS Table’.

Slave

Function

Start

DATA

CRC Check

Address

Code

Address

byte 0 byte 1

Sum

 

 

 

 

 

22

06

00 6F

00 5F

FE BC

The example above is a request to set offline pressure (register 40112) to 95 through X-IRI address 22(Hex).

Message CRC Checksum

The CRC (Cyclical Redundancy Check) is a check-sum generated by means of ‘A001H polynomial’.

Slave

Function

Start

DATA

CRC Check

Address

Code

Address

byte 0 byte 1

Sum

 

 

 

 

 

22

06

00 6F

00 5F

FE BC

The CRC is two bytes containing a 16-bit binary value (word). The CRC value is calculated by the transmitting device that appends the CRC to the end of the message. The receiving device recalculates the CRC value prior to processing of a received message and compares the result to the actual CRC value appended to the message. If the two values do not match the message is regarded as invalid.

The CRC is initiated by first preloading a 16bit register to all 1's (FFFF Hex). Then a process begins of applying each consecutive 8bit byte of the message to the register contents using an exclusive ‘OR’ calculation. The result is shifted one bit in the direction of the least significant bit (LSB), with the most significant bit (MSB) set at ‘0’. The LSB is then examined; if ‘1’ the register content is applied to the polynomial value ‘A001’ Hex (1010 0000 0000 0001) using an exclusive ‘OR’ calculation - if ‘0’ no exclusive OR takes place.

This process is repeated until eight ‘bit’ shifts have been performed. After the eighth bit shift, the next 8bit message byte is applied to the register contents using an exclusive ‘OR’ calculation. The bit shift and re-calculation process is then repeated again. When all message bytes have been processed the final content of the 16bit register is the message CRC value.

Only the 8bits of ‘data’ in each message character is used for generating the CRC; start, stop and parity bits are ignored.

When the 16bit CRC value is appended to a message, the low order byte must be transmitted first followed by the high order byte. An incorrect or byte reversed check sum will render the message invalid and it will be ignored.

Slave Response Timeout

A slave controller may not answer immediately. Ensure the ‘slave timeout’ setting of the ‘master’ device is set to a value no less than 500ms. If the ‘slave’ device fails to receive a valid message due to a communication disruption, parity error, CRC error or other reasons, no response is given and the master must process a timeout condition in this instance. If the ‘slave’ receives a valid message that cannot be processed an exception response will be returned.

6

Message Answer From Slave to Master

The format of the ‘slave’ controller answer is similar to the original master request format; the message data content depends on the message function code type.

The ‘address’ and ‘code’ of the slave answer is identical to the original request message; the address is the ‘slave’ device address and the ‘code’ is a repeat of received function code type from the master. The remainder of the message is dependent on the requested function code type. The CRC checksum is re-calculated for the answer message characters using the specified CRC process.

03H

Read Holding Register(s)

 

 

Slave

Function

Number

DATA

DATA

 

of Data

CRC Check

1st Register

2nd Register

Address

Code

Bytes to

Sum

byte 0 byte 1

byte 2 byte 3

 

 

Follow

 

 

 

 

 

 

 

 

 

 

 

 

01

03

04

00 5F

00 55

F3 45

The example above is a request to read offline pressure 5FHex (95) (register 40112) and online pressure 55Hex (85) (register 40113) from X-IRI address 22(Hex)

06Hex - Preset Single Register

Slave

Function

Start

DATA

CRC Check

Address

Code

Address

byte 0 byte 1

Sum

 

 

 

 

 

22

06

00 6F

00 5F

FE BC

The example above is a request to set offline pressure (register 40112) to 95 through X-IRI address 22(Hex).

Exception Response

If the ‘slave’ device receives a request that cannot be processed an ‘exception response’ is given. An exception response message consists of the following elements:

oSlave Network Address (1 byte): Slave address identification

oFunction Code (1 byte): In a normal response, the slave repeats the function code of the original master request. All function codes have an MSB (most significant bit) of 0 (values are all below 80 hexadecimal). In an exception response, the slave sets the MSB of the function ‘code’ to 1. This makes the ‘code’ value 80 Hex greater than the received ‘code’

value from the master.

o Data (1 byte): The ‘data’ response will contain a ‘1 byte’ value exception code.

o CRC Checksum (2 byte).

Slave Address

Function Code

Error Code

CRC Check Sum

 

 

 

 

01

90

04

4D C3

Exception Codes:

01H Illegal Function Code -- The requested ‘code’ function is not supported.

02H Illegal Data Address -- The requested ‘data start address’ is not supported.

03H Illegal Data Value -- The requested ‘data’ value is not supported.

04H Function Error -- The slave cannot execute the request or the request type is inhibited.

Troubleshooting

Problem:

o No ‘slave’ response or corrupt MODBUS message

Solution:

o Check that the ‘slave’ controller is set for the anticipated slave address

o Check that all ‘slave’ controllers are set with a unique system address

o Check that the controller is set for MODBUS RTU mode (if applicable)

o Check that the ‘master’ is operating in MODBUS RTU mode

o Check that the ‘master’ baud rate, parity bit and number of stop bits are correct

o Check that the ‘master ‘response timeout is set for a minimum of 500ms

o Check that the ‘master’ is implementing the specified CRC check sum process

oCheck RS485 wiring polarity and security of connections

Problem:

o Last character of MODBUS message is corrupted

Solution:

oAdd a delay of 2ms after last character received before releasing RTS signal

Problem:

oThe MODBUS master message is reflected in the slave answer

Solution:

oInhibit RX/TX echo on ‘master’ device communications port

7

Ingersoll Rand X-iri User Manual

SECTION 5 — INSTALLATION

INSTALLATION

It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.

UNIT LOCATION

The X-IRI Gateway is DIN Rail mounted and can be located within the compressor control enclosure or remotely within a separate enclosure. X-IRI Gateway must be located within 33ft (10m) of the compressor controller.

Avoid mounting the X-IRI Gateway near high voltage cables, high voltage devices or equipment or motor starter contactors.

POWER SUPPLY

The X-IRI Gateway is powered by an external 24VDC power supply. The AC supply voltage for the 24VDC power supply is derived from the compressor’s 110VAC or 230VAC internal AC supply.

24VDC

DC

 

L

0VDC

+V.ADJ

N

 

 

E

+24VDC

100-240VAC 50/60Hz

N L

24VDC

DC

+V.ADJ

 

GATEWAY

 

24V

 

 

AC/DC

 

100-240VAC

1

2

 

 

 

 

50/60Hz

 

 

 

N L

 

X01

 

 

 

 

N L

 

 

 

 

 

1

2

 

 

 

X01

+24VDC

 

+

-

 

 

 

0VDC

 

 

 

The power specification for the X-IRI Gateway is 24VDC (+-10%) @ 35mA, 1W

It is possible to use the same 24VDC power supply to power multiple X-IRI Gateway devices.

Wire polarity is important

8

DCS OR PLC CONNECTION

 

COMPRESSOR IR-BUS CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wire polarity is important

Use 2-wire, 24 gauge (Belden 9841 or equivalent), twisted pair, earth shielded, data cable with a total system network length no greater than 4000ft (1219m).

Wire polarity is important

Use 2-wire, 24 gauge (Belden 9841 or equivalent), twisted pair, earth shielded, data cable with a length no greater than 33ft (10m).

For IntelliSys “Red Eye”, SG and SE equipped with an RJ11 RS-485 data communications connection port, use the RJ11 Modbus cable supplied with the X-IRI Gateway.

L1

2

2

 

L2

 

3

4

4

 

5

X02

RJ11

L1 (2)

 

1

 

2

 

 

3

 

 

4

 

 

5

L2 (4)

M4

6

 

 

Ring Tag

For IntelliSys SGN, SGNe and Nirvana 15-30kW (20-40HP) equipped with a Phoenix RS-485 data communications connector, use the RJ11 Modbus cable supplied with the X- IRI Gateway and modify as shown by removing the RJ11 Plug.

9

DCS OR PLC COMMUNICATIONS

50ms

RX – Data Received:

2

A valid MODBUS communication has just been

 

received from the DCS or PLC unit. In normal operation this event should occur periodically depending on the polling rate.

TX – Data Transmitted:

3

A MODBUS broadcast or message has just been

 

sent. To keep the link active, a MODBUS message must be sent at least once every 10 seconds.

COMPRESSOR COMMUNICATIONS:

50ms

RX – Data Received:

4

A valid IRBUS communication has just been

 

received from the compressor controller. In normal

operation this event should occur at least once every ½ second.

TX – Data Transmitted:

5

An IRBUS message has just been sent to the

 

compressor controller. In normal operation this event should occur at least once every ½ second.

OPERATIONAL INDICATIONS

6

7

8

9

X04

#2

#3

 

#5

#4

X03

ulti485

 

IRMODBUS-

MODBUS

LED

LED

LED#6 LED#7 LED#8 LED#9

LED

LED

 

 

1s

OFF

Slow Flash

ON

Fast Flash

At power on initialization, or when power has been removed, all operational indicators will fast flash for several seconds.

10

Normal Operation Example:

When there is valid communication with a MODBUS master and an IR-BUS compatible compressor controller the main operation indicators will light up as shown below.

6 7 8 9

Normal operation function:

6Modbus Communications with MODBUS master.

OFF

No valid communications with a MODBUS master

ON: Valid communication with a MODBUS master, at least one read/write operation once every 10 seconds.

7

No function

 

Always OFF: no other defined function

8

No function

 

Always OFF: no other defined function

9IR-BUS communication with a compressor controller

OFF

No valid communications with the compressor controller.

ON: IR-BUS compressor controller detected and communication link established.

Led#2: Every flash indicates reception of a valid MODBUS messsage from the MODBUS master.

Led#3: Every flash indicates transmission of a valid MODBUS messsage to the MODBUS master.

Led#5: Every flash indicates transmission of a valid IRBUS messsage to the IR-BUS compressor controller.

Led#4: Every flash indicates reception of a valid IR-BUS message from the IR-BUS compressor controller.

11

RS-485 NETWORK

RS-485 data communications and other low voltage signals can be subject to electrical interference. This potential can result in intermittent malfunction or anomaly that is difficult to diagnose. To avoid this possibility always use earth shielded cables, securely bonded to a known good earth at one end. In addition, give careful consideration to cable routing during installation.

1)Never route an RS-485 data communications or low voltage signal cable alongside a high voltage 3-phase power supply cable. If it is necessary to cross the path of a power supply cable(s), always cross at a right angle.

2)If it is necessary to follow the route of power supply cables for a short distance (for example: from a compressor unit to a wall along a suspended cable tray) attach the RS485 or signal cable on the outside of an earthed cable tray such that the cable tray forms an earthed electrical interference shield.

3)Where possible, never route an RS-485 or signal cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications antenna).

12

MODBUS ADDRESS SELECTION

Each compressor connected to the MODBUS network will have a unique assigned address, starting at compressor 1 increasing sequentially to the number of compressors connected to the MODBUS network. The MODBUS address is selected by using DIP switches 1, 2, 3, and 4 on SW1, and switches 1, 2, and 3 on SW2 on the X-IRI Gateway.

SW1, 1 to4 and SW2, 1 to 3: Address Selection

SW1 SW2 SW3

The addresses are selected as shown in the following table: (Note: ON = 1, OFF = 0 )

 

 

 

 

 

 

 

 

 

MODBUS

MODBUS

 

SW1

 

 

SW2

 

Address

Address

1

2

3

4

1

 

2

 

3

(Decimal)

(Hexl)

0

0

0

0

0

 

0

 

0

1

1

1

0

0

0

0

 

0

 

0

1

1

0

1

0

0

0

 

0

 

0

2

2

1

1

0

0

0

 

0

 

0

3

3

0

0

1

0

0

 

0

 

0

4

4

1

0

1

0

0

 

0

 

0

5

5

0

1

1

0

0

 

0

 

0

6

6

1

1

1

0

0

 

0

 

0

7

7

0

0

0

1

0

 

0

 

0

8

8

1

0

0

1

0

 

0

 

0

9

9

0

1

0

1

0

 

0

 

0

10

A

1

1

0

1

0

 

0

 

0

11

B

0

0

1

1

0

 

0

 

0

12

C

1

0

1

1

0

 

0

 

0

13

D

0

1

1

1

0

 

0

 

0

14

E

1

1

1

1

0

 

0

 

0

15

F

0

0

0

0

1

 

0

 

0

16

10

1

0

0

0

1

 

0

 

0

17

11

0

1

0

0

1

 

0

 

0

18

12

1

1

0

0

1

 

0

 

0

19

13

0

0

1

0

1

 

0

 

0

20

14

1

0

1

0

1

 

0

 

0

21

15

0

1

1

0

1

 

0

 

0

22

16

1

1

1

0

1

 

0

 

0

23

17

0

0

0

1

1

 

0

 

0

24

18

1

0

0

1

1

 

0

 

0

25

19

0

1

0

1

1

 

0

 

0

26

1A

1

1

0

1

1

 

0

 

0

27

1B

0

0

1

1

1

 

0

 

0

28

1C

 

 

 

 

 

 

 

 

 

MODBUS

MODBUS

 

SW1

 

 

SW2

 

Address

Address

1

2

3

4

1

 

2

 

3

(Decimal)

(Hexl)

1

0

1

1

1

 

0

 

0

29

1D

0

1

1

1

1

 

0

 

0

30

1E

1

1

1

1

1

 

0

 

0

31

1F

0

0

0

0

0

 

1

 

0

32

20

1

0

0

0

0

 

1

 

0

33

21

0

1

0

0

0

 

1

 

0

34

22

1

1

0

0

0

 

1

 

0

35

23

0

0

1

0

0

 

1

 

0

36

24

1

0

1

0

0

 

1

 

0

37

25

0

1

1

0

0

 

1

 

0

38

26

1

1

1

0

0

 

1

 

0

39

27

0

0

0

1

0

 

1

 

0

40

28

1

0

0

1

0

 

1

 

0

41

29

0

1

0

1

0

 

1

 

0

42

2A

1

1

0

1

0

 

1

 

0

43

2B

0

0

1

1

0

 

1

 

0

44

2C

1

0

1

1

0

 

1

 

0

45

2D

0

1

1

1

0

 

1

 

0

46

2E

1

1

1

1

0

 

1

 

0

47

2F

0

0

0

0

1

 

1

 

0

48

30

1

0

0

0

1

 

1

 

0

49

31

0

1

0

0

1

 

1

 

0

50

32

1

1

0

0

1

 

1

 

0

51

33

0

0

1

0

1

 

1

 

0

52

34

1

0

1

0

1

 

1

 

0

53

35

0

1

1

0

1

 

1

 

0

54

36

1

1

1

0

1

 

1

 

0

55

37

0

0

0

1

1

 

1

 

0

56

38

1

0

0

1

1

 

1

 

0

57

39

0

1

0

1

1

 

1

 

0

58

3A

1

1

0

1

1

 

1

 

0

59

3B

0

0

1

1

1

 

1

 

0

60

3C

1

0

1

1

1

 

1

 

0

61

3D

0

1

1

1

1

 

1

 

0

62

3E

1

1

1

1

1

 

1

 

0

63

3F

0

0

0

0

0

 

0

 

1

64

40

1

0

0

0

0

 

0

 

1

65

41

0

1

0

0

0

 

0

 

1

66

42

1

1

0

0

0

 

0

 

1

67

43

0

0

1

0

0

 

0

 

1

68

44

1

0

1

0

0

 

0

 

1

69

45

0

1

1

0

0

 

0

 

1

70

46

1

1

1

0

0

 

0

 

1

71

47

0

0

0

1

0

 

0

 

1

72

48

13

 

 

 

 

 

 

 

 

 

MODBUS

MODBUS

 

SW1

 

 

SW2

 

Address

Address

1

2

3

4

1

 

2

 

3

(Decimal)

(Hexl)

1

0

0

1

0

 

0

 

1

73

49

0

1

0

1

0

 

0

 

1

74

4A

1

1

0

1

0

 

0

 

1

75

4B

0

0

1

1

0

 

0

 

1

76

4C

1

0

1

1

0

 

0

 

1

77

4D

0

1

1

1

0

 

0

 

1

78

4E

1

1

1

1

0

 

0

 

1

79

4F

0

0

0

0

1

 

0

 

1

80

50

1

0

0

0

1

 

0

 

1

81

51

0

1

0

0

1

 

0

 

1

82

52

1

1

0

0

1

 

0

 

1

83

53

0

0

1

0

1

 

0

 

1

84

54

1

0

1

0

1

 

0

 

1

85

55

0

1

1

0

1

 

0

 

1

86

56

1

1

1

0

1

 

0

 

1

87

57

0

0

0

1

1

 

0

 

1

88

58

1

0

0

1

1

 

0

 

1

89

59

0

1

0

1

1

 

0

 

1

90

5A

1

1

0

1

1

 

0

 

1

91

5B

0

0

1

1

1

 

0

 

1

92

5C

1

0

1

1

1

 

0

 

1

93

5D

0

1

1

1

1

 

0

 

1

94

5E

1

1

1

1

1

 

0

 

1

95

5F

0

0

0

0

0

 

1

 

1

96

60

1

0

0

0

0

 

1

 

1

97

61

0

1

0

0

0

 

1

 

1

98

62

1

1

0

0

0

 

1

 

1

99

63

0

0

1

0

0

 

1

 

1

100

64

1

0

1

0

0

 

1

 

1

101

65

0

1

1

0

0

 

1

 

1

102

66

1

1

1

0

0

 

1

 

1

103

67

0

0

0

1

0

 

1

 

1

104

68

1

0

0

1

0

 

1

 

1

105

69

0

1

0

1

0

 

1

 

1

106

6A

1

1

0

1

0

 

1

 

1

107

6B

0

0

1

1

0

 

1

 

1

108

6C

1

0

1

1

0

 

1

 

1

109

6D

0

1

1

1

0

 

1

 

1

110

6E

1

1

1

1

0

 

1

 

1

111

6F

0

0

0

0

1

 

1

 

1

112

70

1

0

0

0

1

 

1

 

1

113

71

0

1

0

0

1

 

1

 

1

114

72

1

1

0

0

1

 

1

 

1

115

73

0

0

1

0

1

 

1

 

1

116

74

 

 

 

 

 

 

 

 

 

MODBUS

MODBUS

 

SW1

 

 

SW2

 

Address

Address

1

2

3

4

1

 

2

 

3

(Decimal)

(Hexl)

1

0

1

0

1

 

1

 

1

117

75

0

1

1

0

1

 

1

 

1

118

76

1

1

1

0

1

 

1

 

1

119

77

0

0

0

1

1

 

1

 

1

120

78

1

0

0

1

1

 

1

 

1

121

79

0

1

0

1

1

 

1

 

1

122

7A

1

1

0

1

1

 

1

 

1

123

7B

0

0

1

1

1

 

1

 

1

124

7C

1

0

1

1

1

 

1

 

1

125

7D

0

1

1

1

1

 

1

 

1

126

7E

1

1

1

1

1

 

1

 

1

127

7F

MODBUS PORT SETUP SELECTION

SW1 SW2 SW3

The MODBUS port setup is determined by means of DIP switch 4 on SW2 and DIP switches 2,3 and 4 on SW3. The selectable items are: baudrate and number of stop bits. Parity is not selectable and fixed at “no parity”

SW2-4: Stop Bit Selection

1 stop bit

2 stop bits

SW3-2...4: Baudrate Selection

1200 baud

2400 baud

4800 baud

9600 baud

19200 baud

38400 baud

57600 baud

115200 baud

14

GATEWAY SOFTWARE VERSION DISPLAY

SW3-1

When DIP Switch 1 on SW3 is set to the ‘on’ possition the LED indicators (LED 2 to 9) will show the software version:

 

6

7

8

9

 

2

3

 

 

 

5

4

X04

#2 #3

 

 

#5

#4

X03

Multi485

LED#6 LED#7

LED#8 LED#9

MODBUS

 

LED LED

LED

LED

 

To establish the software version number (01 to 255) add together the ‘value’ associated with each illuminated LED.

LED #

Value

6= 1

7= 2

8= 4

9= 8

2= 16

3= 32

5

= 64

4

= 128

Ignore LED 1 (power on indicator), located adjacent to X01; this LED will always be on when power is applied.

For example:

1) LED 6 and 8 = ON; all others off

LED 6

= 1

LED 8

= 4

total

= 5

Software Version = ‘E05

2) LED 7 and 8 = ON; all others off

LED 7

= 2

LED 8

= 4

total

= 6

Software Version = ‘E06

3) LED 6, 7, 9 and 2 = ON; all others off

LED 6

= 1

LED 7

= 2

LED 9

= 8

LED 2

= 16

total

= 27

Software Version = ‘E27

The LED indicators will continue to display the the software version, regardless of operation, until switch 1 on SW3 is set to the ‘off’ possition.

DIP Switch 1 on SW3 must always be set to the ‘off’ position for normal operation.

DIP Switch 1 on SW3 has no function with earlier software versions; if the LED indicators continue to operate normally when SW3-1 is switched on, the software is an earlier version; update the software.

Please refer to the table on the following page to assist in decoding the software version number.

15

Decoding The Software Version Number

LED#2

LED#3

LED#6

LED#7

LED#8

LED#9

LED#5

LED#4

Version

 

 

 

 

 

 

 

 

 

0

0

0

0

0

0

0

0

0

0

0

1

0

0

0

0

0

1

0

0

0

1

0

0

0

0

2

0

0

1

1

0

0

0

0

3

0

0

0

0

1

0

0

0

4

0

0

1

0

1

0

0

0

5

0

0

0

1

1

0

0

0

6

0

0

1

1

1

0

0

0

7

0

0

0

0

0

1

0

0

8

0

0

1

0

0

1

0

0

9

0

0

0

1

0

1

0

0

10

0

0

1

1

0

1

0

0

11

0

0

0

0

1

1

0

0

12

0

0

1

0

1

1

0

0

13

0

0

0

1

1

1

0

0

14

0

0

1

1

1

1

0

0

15

1

0

0

0

0

0

0

0

16

1

0

1

0

0

0

0

0

17

1

0

0

1

0

0

0

0

18

1

0

1

1

0

0

0

0

19

1

0

0

0

1

0

0

0

20

1

0

1

0

1

0

0

0

21

1

0

0

1

1

0

0

0

22

1

0

1

1

1

0

0

0

23

1

0

0

0

0

1

0

0

24

1

0

1

0

0

1

0

0

25

1

0

0

1

0

1

0

0

26

1

0

1

1

0

1

0

0

27

1

0

0

0

1

1

0

0

28

1

0

1

0

1

1

0

0

29

1

0

0

1

1

1

0

0

30

1

0

1

1

1

1

0

0

31

0

0

0

0

0

0

0

0

32

0

0

1

0

0

0

0

0

33

0

0

0

1

0

0

0

0

34

0

0

1

1

0

0

0

0

35

0

0

0

0

1

0

0

0

36

0

0

1

0

1

0

0

0

37

0

0

0

1

1

0

0

0

38

0

0

1

1

1

0

0

0

39

0

0

0

0

0

1

0

0

40

0

0

1

0

0

1

0

0

41

0

0

0

1

0

1

0

0

42

0

0

1

1

0

1

0

0

43

0

0

0

0

1

1

0

0

44

0

0

1

0

1

1

0

0

45

0

0

0

1

1

1

0

0

46

0

0

1

1

1

1

0

0

47

1

1

0

0

0

0

0

0

48

1

1

1

0

0

0

0

0

49

COMMISSIONING PROCEDURE

1)Before applying power to the X-IRI Gateway ensure:

a)The MODBUS address is set to the correct value (switches 1-4 on SW1 and switches 1- 3 on SW2)

b)The MODBUS port setup matches the MODBUS master’s requirements. Switches 4 on SW2 and switches 2-4 on SW3.

c)The communication link wires from the Gateway to the compressor controller and the MODBUS master are connected, secure and the wire polarities are correct (L1, L2)

2)Apply power to the X-IRI Gateway

3)Ensure communications with the compressor controller is established – ensure indicator (9) is ON permanently.

4)Once the IR-BUS compressor controller communication link is established the MODBUS master unit can start operating. Any attempt from the MODBUS master to communicate before the IR-BUS link is established will simply result in the gateway not responding to the MODBUS master.

5)Once the MODBUS master communicates with the compressor controller through the gateway it should keep on doing so at least once every 10 seconds to keep indicator (6) from flashing.

6)In case the MODBUS master does not communicate at least once every 10 seconds the communication link is considered inactive: indicator

(6) flashes and any earlier commands for the compressor controller to operate in “Host” mode are cancelled => the machine reverts back to local start/stop and load/unload control mode.

16

SECTION 6 - PARTS LIST

X-IRI Communication Gateway

Item Part No.

Description

-

23461908

KIT, X-IRI Gateway

-

80445604

Manual, User CD

-

23462005

DIN Rail, Mounting

1

23461890

Module, X-IRI Gateway

2

39266101

Module, PSU-24VDC

3

39266135

Cable, RJ11 Modbus

1

 

 

2

 

 

24VDC

 

 

DC

 

 

 

L

0VDC

+V.ADJ

N

 

 

E

+24VDC

100-240VAC

 

 

50/60Hz

 

 

N L

 

 

3

 

 

RJ11

L1 (2)

 

2

2

1

 

 

2

 

 

 

3

3

 

 

4

4

4

 

 

5

5

L2 (4)

M4

 

 

6

 

 

 

 

Ring Tag

SECTION 7 - TECHNICAL DATA

Module, Gateway

Dimensions

3.8” x 3.4” x 2.2”

 

96mm x 85mm x 55mm

Weight

0.6Ib (0.25kg)

Mounting

DIN, 35mm

Enclosure

IP20

Supply

24VDC/ac +/-15%

Power

1.0VA

Temperature

0°C to 46°C (32°F to 115°F)

Humidity

95% RH non-condensing

17

SECTION 8 – INTELLISYS MODBUS TABLES

TABLE 1 SSR (REDEYE) CONTROLLER

Register

Variable

Read/Write

Range

Notes

(40XXX)

 

 

 

 

 

 

1

Status/Control

 

 

R/W

 

See FIGURE 1-1

3

Discharge Pressure

 

 

R

 

 

4

Sump Pressure

 

 

R

 

 

5

Inlet Vacuum

 

 

R

 

 

6

Coolant Temperature

 

 

R

 

 

7

Airend Temperature

 

 

R

 

 

8

Discharge Temperature

 

 

R

 

 

9

Low Ambient Coolant Temp.

 

 

R

 

Low Ambient Option

64

Total Hours (hours)

 

 

R

 

 

65

Loaded Hours (hours)

 

 

R

 

 

96

Language Selection

 

 

R

 

See FIGURE 1-2

97

Units of Measure

 

 

R

 

See FIGURE 1-2

98

Rated Pressure

 

 

R

 

 

99

Rated Horse Power

 

 

R

 

See FIGURE 1-2

112

Offline Pressure

 

 

R/W

75 - (rated+3)

rated = rated pressure

113

Online Pressure

 

 

R/W

65-(offline-10)

offline = offline pressure

114

Display Timer (seconds)

 

 

R/W

10-600

 

115

Star-Delta Time (seconds)

 

 

R

 

 

116

Auto Start/Stop (AS/S) Time (minutes)

 

 

R/W

Feb-60

No Write if AS/S is off

117

Auto Start/Stop (AS/S) On/Off

 

 

R

0 or 1

0=Off, 1=On

118

Sequence Control On/Off

 

 

R

0 or 1

0=Off, 1=On

119

Remote Start/Stop On/Off

 

 

R

0 or 1

0=Off, 1=On

120

Mod Only On/Off

 

 

R/W

0 or 1

0=Off, 1=On

121

Power Out Restart Option (PORO)On/Off

 

 

R

0 or 1

0=Off, 1=On

122

PORO Time (seconds)

 

 

R/W

10-120

No Write if PORO is off

123

Load Delay Time (seconds)

 

 

R/W

0-60

 

124

Min. Cooler Out Load Temp

 

 

R/W

30-150

Low Ambient Option

125

Unloaded Stop Time

 

 

R/W

10-30

 

255

Warning Code

 

 

R

 

See FIGURE 1-4

256-270

Alarm Code History

 

 

R

 

See FIGURE 1-4

272-286

Inlet Vacuum Alarm History

 

 

R

 

 

288-302

Sump Pressure Alarm History

 

 

R

 

 

304-318

Discharge Pressure Alarm History

 

 

R

 

 

320-334

Coolant Temperature Alarm History

 

 

R

 

 

336-350

Airend Temperature Alarm History

 

 

R

 

 

352-366

Discharge Temperature Alarm History

 

 

R

 

 

368-382

Low Ambient Coolant Temp. History

 

 

R

 

Low Ambient Option

384-398

Run Hours Alarm History

 

 

R

 

 

400-414

Load Hours Alarm History

 

 

R

 

 

512-526

Status Alarm History

 

 

R

 

See FIGURE 1-3

999

IRI Version Number

 

 

R

 

Reads from IRI only

 

 

 

 

 

 

 

18

FIGURE 1-1

REGISTER 40001 STATUS / CONTROL

Bit 0: Host/Local (R/W)

Bit 6: Alarm (R)

0

= Local

 

0

= No Alarms

1

= Host

 

1

= Alarms

Bit 1: Run/Stop (R/W)

Bit 7: Warning (R)

0

= Stop

 

0

= No Warnings

1

= Run

 

1

= Warnings

Bit 2: Load/Unload (R/W)

Bit 8: On/Off Line Mode (R)

0

= Unload

 

0

= Not in On/Off Line Mode

1

= Load

 

1

= On/Off Line Mode

Bit 3: Modulating (R)

Bit 9: Mod/ACS or Mod Only (R)

0

= Not Modulating

0

= Not in Mod/ASC Mode

1

= Modulating

 

1

= Mod/ASC Mode

Bit 4: Unused

 

Bits 10-12: Unused

Bit 5: Stopped in Auto Restart (R)

Bits 13-15: Unit Type (R)

0

= Not Stopped in Auto Restart

001 = SSR controller

FIGURE 1-2

REGISTER CODES

 

Register 096: Language

Register 097: Units of Measure

0

= English

 

0 = °F and PSI

1

= Spanish

 

1 = °C and PSI

2

= French

 

2 = °C and Bar

3

= Portuguese

 

3 = °C and kPa

 

 

 

4 = °C and kg/cm2

Register 99: Rated Horse Power/Kilowatt

0

= 50hp

 

7 = 250hp

1

= 60hp

 

8 = 300hp

2

= 75hp

 

9 = 350hp

3

= 100hp

 

10 = 400hp

4

= 125hp

 

11 = 450hp

5

= 150hp

 

12 = 500hp

6

= 200hp

 

 

 

 

 

 

FIGURE 1-3

REGISTER STATUS ALARM HISTORY

Bit 0: Run/Stop (R)

Bit 4: Stopped Auto Restart (R)

0

= Stop

 

0 = Not Stopped in Auto Restart

1

= Run

 

1= Stopped in Auto Restart

Bit 1: On/Off Line Mode (R)

Bit 5: Unused

0

= Not in On/Off Line Mode

 

1

= On/Off Line Mode

 

Bit 2: MOD/ACS Mode (R)

Bit 6: Unused

0

= Not in Mod/ACS Mode

 

1

= Mod/ACS Mode

 

Bit 3: Load/Unload (R)

Bit 7: Unused

19

FIGURE 1-4

REGISTER ALARM / WARNING CODES

 

 

SSR (Redeye) Controller

 

Code

Description

 

01

Sensor Failure 1AVPT

 

02

Sensor Failure 3APT

 

03

Sensor Failure 4APT

 

04

Sensor Failure P4 (Spare)

 

05

Sensor Failure P5 (Spare)

 

06

Sensor Failure P6 (Spare)

 

07

Sensor Failure P7 (Spare)

 

08

Sensor Failure P8 (Spare)

 

09

Sensor Failure 2CTT

 

10

Sensor Failure 2ATT

 

11

Sensor Failure 4ATT

 

12

Sensor Failure 3CTT (Optional)

 

13

Sensor Failure T5 (Spare)

 

14

Sensor Failure T6 (Spare)

 

15

Sensor Failure T7 (Spare)

 

16

Sensor Failure T8 (Spare)

 

17

Starter Fault

 

18

Motor Overload (Main)

 

19

Fan Motor Overload

 

20

Door Open (Starter)

 

21

Stepper Limit Switch

 

22

Check Motor Rotation

 

23

Check Inlet Control System

 

25

Remote Stop Failure

 

26

Remote Start Failure

 

27

Check Inlet Control

 

28

Low Unload Sump Pressure

 

29

High Air Pressure

 

30

Low Sump Air Pressure

 

31

High A/E Discharge Temperature

 

32

Emergency Stop

 

33

Change Inlet Filter

 

34

Change Separator Element

 

35

Change Coolant Filter

 

36

1AVPT Sensor Error (Calibration)

 

37

Memory Fault

 

20

TABLE 2 SSR (SG) CONTROLLER

Register

Variable

Read/Write

Range

Notes

(40XXX)

 

 

 

 

1

Status/Control

R/W

 

See FIGURE 2-1

3

Discharge Pressure

R

 

 

4

Sump Pressure

R

 

 

5

Inlet Vacuum

R

 

Divided by 10

6

Coolant Temperature

R

 

 

7

Airend Temperature

R

 

 

8

Discharge Temperature

R

 

 

9

Low Ambient Coolant Temp.

R

 

Low Ambient Option

10

Separator Pressure Drop

R

 

 

11

Spare Pressure Input 4

R

 

 

12

Dry Side Sump Pressure

R

 

Spare Pressure Input #5 if no

 

 

 

 

separator delta-p sensor option

13

Spare Pressure Input 6

R

 

 

14

Spare Pressure Input 7

R

 

 

15

Remote Pressure

R

 

Spare Pressure Input #8 if no

 

 

 

 

remote sensor option

16

Spare Temperature Input 5

R

 

 

17

Spare Temperature Input 6

R

 

 

18

Spare Temperature Input 7

R

 

 

19

Spare Temperature Input 8

R

 

 

20

% Load Modulation

R

 

 

64

Total Hours (hours)

R

0 – 9999

Less Than 10000

65

Loaded Hours (hours)

R

0 – 9999

Less Than 10000

66

Ten Thousand Total Hours

R

 

Multiply by 10000

67

Ten Thousand Loaded Hours

R

 

Multiply by 10000

96

Language Selection

R

0 – 11

See FIGURE 2-2

97

Units of Measure

R

0 – 4

See FIGURE 2-2

98

Rated Pressure

R

 

 

99

Rated Horse Power/Kilowatt

R

0 – 21

See FIGURE 2-2

100

Starter Type

R

0 - 4

See FIGURE 2-2

101

Service Level

R

0 or 1

0=Level 1, 1=Level 2

102

Service Type

R

0 or 1

0=Hours, 1=Months

103

Service Interval

R

0 - 3

3, 6, 9, or 12 months

112

Offline Pressure

R/W

75 - (rated+3)

rated = rated pressure

113

Online Pressure

R/W

65-(offline-10)

offline = offline pressure

114

Mode of Operation

R/W

0 – 2

See FIGURE 2-2

115

Star-Delta Time (seconds)

R

5 – 20

 

116

Auto Start/Stop (AS/S) Time (minutes)

R/W

2 – 60

No Write if AS/S is off

117

Auto Start/Stop (AS/S) On/Off

R

0 or 1

0=Off, 1=On

118

Sequence Control On/Off

R

0 or 1

0=Off, 1=On

119

Remote Start/Stop On/Off

R

0 or 1

0=Off, 1=On

120

Solenoid Delta-P

R

0 or 1

0=Off, 1=On

121

Power Out Restart Option (PORO)On/Off

R

0 or 1

0=Off, 1=On

122

PORO Time (seconds)

R/W

10 - 120

No Write if PORO is off

123

Auto Start/Stop Delay Time (seconds)

R/W

0 - 60

 

124

Min. Cooler Out Load Temp

R/W

30 - 150

Low Ambient Option

125

Unloaded Stop Time

R/W

10-30t

 

126

Low Ambient Option On/Off

R

0 or 1

0=Off, 1=On

127

Contrast

R

0 - 10

 

128

Lead/Lag

R/W

0 or 1

0=Off, 1=On

129

Lag Offset

R/W

0 - 10

 

130

Max Modulation Pressure

R/W

(Online+10) –

 

 

 

 

(Offline + 7)

 

131

Lead/Lag Cycle Length (Hours)

R/W

0 – 750

 

132

Scheduled Start (Hour)

R/W

0 – 23

 

133

Scheduled Start (Minute)

R/W

0 – 59

 

21

134

Scheduled Stop (Hour)

R/W

0 – 23

 

135

Scheduled Stop (Minute)

R/W

0 – 59

 

136

Modbus Protocol

R

0 or 1

0=Off, 1=On

137

Modbus Address

R

1 – 247

 

138

High Dust Filter

R

0 or 1

0=Off, 1=On

139

Integral Sequencing Lead

R/W

0 – 3

0=Off, 1=On, 2=Always, 3=Never

140

Integral Sequencing Address

R/W

1 – 4

 

141

Integral Sequencing Total

R/W

2 – 4

 

142

Integral Sequencing Load Delay

R/W

10 – 60

 

143

Integral Sequencing Lead Change (Hours)

R/W

0 – 750

 

144

Integral Sequencing Lead Change – Day

R/W

0 – 9

See FIGURE 2-2

145

Integral Sequencing Lead Change – Hour

R/W

0 – 23

 

146

Integral Sequencing Lead Change – Min

R/W

0 - 45

Steps of 0, 15, 30, 45

147

Separator Delta-P Sensor

R

0 or 1

0=Off, 1=On

148

Variable Frequency Drive

R

0 or 1

0=Off, 1=On

149

Scheduled Start (Day)

R/W

0 - 9

See FIGURE 2-2

150

Scheduled Stop (Day)

R/W

0 - 9

See FIGURE 2-2

151

Remote Sensor

R

0 or 1

0=Off, 1=On

250

Options

R

 

See FIGURE 2-2

251

Unloaded Inlet Vacuum

R

 

 

252

Software Part Number – Most Significant

R

 

High Digits

253

Software Part Number – Least Significant

R

 

Low Digits

254

Software Version Number

R

 

 

255

Warning Code

R

 

See FIGURE 2-4

256-270

Alarm Code History

R

 

See FIGURE 2-4

272-286

Inlet Vacuum Alarm History

R

 

 

288-302

Sump Pressure Alarm History

R

 

 

304-318

Discharge Pressure Alarm History

R

 

 

320-334

Coolant Temperature Alarm History

R

 

 

336-350

Airend Temperature Alarm History

R

 

 

352-366

Discharge Temperature Alarm History

R

 

 

368-382

Low Ambient Coolant Temp. History

R

 

Low Ambient Option

384-398

Total Hours Alarm History

R

 

Less Than 10000 Hours

400-414

10000 Total Hours Alarm History

R

 

Multiply by 10000

416-430

Loaded Hours Alarm History

R

 

Less Than 10000 Hours

432-446

10000 Loaded Hours Alarm History

R

 

Multiply by 10000

448-462

Unloaded Inlet Vacuum Alarm History

R

 

 

464-478

Coolant Pressure Alarm History

R

 

 

480-494

Dry Side Sump Pressure Alarm History

R

 

 

496-510

Remote Pressure Alarm History

R

 

 

512-526

Status Alarm History

R

 

See FIGURE 2-3

528-542

Real Time Clock Alarm History – Hours

R

 

 

544-558

Real Time Clock Alarm History – Minutes

R

 

 

560-574

Real Time Clock Alarm History – Month

R

 

 

576-590

Real Time Clock Alarm History – Date

R

 

 

592-606

Real Time Clock Alarm History – Year

R

 

 

999

IRI Version Number

R

 

Reads from IRI only

 

 

 

 

 

22

FIGURE 2-1

REGISTER 40001 STATUS / CONTROL

Bit 0: Host/Local (R/W)

Bit 6: Alarm (R)

0

= Local

 

0

= No Alarms

1

= Host

 

1

= Alarms

Bit 1: Run/Stop (R/W)

Bit 7: Warning (R)

0

= Stop

 

0

= No Warnings

1

= Run

 

1

= Warnings

Bit 2: Load/Unload (R/W)

Bit 8: On/Off Line Mode (R)

0

= Unload

 

0

= Not in On/Off Line Mode

1

= Load

 

1

= On/Off Line Mode

Bit 3: Modulating (R)

Bit 9: Mod/ACS or Mod Only (R)

0

= Not Modulating

0

= Not in Mod/ASC Mode

1

= Modulating

 

1

= Mod/ASC Mode

Bit 4: Unused

 

Bits 10-12: Unused

Bit 5: Stopped in Auto Restart (R)

Bits 13-15: Unit Type (R)

0

= Not Stopped in Auto Restart

001 = SSR controller

1

= Stopped in Auto Restart

 

 

23

 

FIGURE 2-2

REGISTER CODES

 

 

 

 

 

 

 

Register 096: Language

Register 097: Units of Measure

 

0

= English

 

0

= °F and PSI

1

= Spanish

 

1

= °C and PSI

2

= Portuguese

 

2

= °C and Bar

3

= French

 

3

= °C and kPa

4

= Italian

 

4

= °C and kg/cm2

5

= Dutch

 

 

 

 

6

= German

 

 

 

 

7

= Danish

 

 

 

 

8

= Norwegian

 

 

 

 

9

= Swedish

 

 

 

 

 

10 = Finnish

 

 

 

 

 

11 = Turkish

 

 

 

 

Register 99: Rated Horse Power/Kilowatt

Register 100: Starter Type

0

= 50hp

11

= 450hp

0 = Star-Delta

1

= 60hp

12

= 500hp

1 = Full Voltage

2

= 75hp

13

= 75kw

2 = Remote Star-Delta

3

= 100hp

14

= 90kw

3 = Remote Full Voltage

4

= 125hp

15

= 110kw

4 = Soft Starter

5

= 150hp

16

= 132kw

 

 

6

= 200hp

17

= 150kw

 

 

7

= 250hp

18

= 200kw

 

 

8

= 300hp

19

= 250kw

 

 

9

= 350hp

20

=300kw

 

 

10 = 400hp

21

= 250kw

 

 

Register 114: Mode of Operation

Register 144: Integral Sequencing Lead Change - Day

0

= MOD/ACS

 

 

Register 149: Schedule Start - Day

1

= On/Off Line

 

 

Register 150: Schedule Stop - Day

2

= Modulation Only

 

 

0= Sunday

 

 

 

 

1

= Monday

 

 

 

 

2

= Tuesday

 

 

 

 

3

= Wednesday

 

 

 

 

4

= Thursday

 

 

 

 

5

= Friday

 

 

 

 

6

= Saturday

 

 

 

 

7

= Daily

 

 

 

 

8

= Weekdays

 

 

 

 

9

= Weekends

Register 250: Options

Bit 0: Power Out Restart and Scheduled Start/Stop

0 = Off

1 = On

FIGURE 2-3

REGISTER STATUS ALARM HISTORY

Bit 0: Run/Stop (R)

Bit 4: Stopped Auto Restart (R)

0

= Stop

 

0 = Not Stopped in Auto Restart

1

= Run

 

1 = Stopped in Auto Restart

Bit 1: On/Off Line Mode (R)

Bit 5: Unused

0

= Not in On/Off Line Mode

 

1

= On/Off Line Mode

 

Bit 2: MOD/ACS Mode (R)

Bit 6: Unused

0

= Not Modulating

 

1

= Modulating

 

 

Bit 3: Load/Unload (R)

Bit 7: Unused

0

= Unload

 

 

1

= Load

 

 

24

Loading...
+ 56 hidden pages