Before installing or starting this unit for the first
time, this manual should be studied carefully to
obtain a working knowledge of the unit and or the
duties to be performed while operating and
maintaining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical
manual contains IMPORTANT SAFETY DATA and
should be kept with the unit at all times.
More Than Air. Answers.
Online answers: http://www.air.irco.com
C.C.N. : 80444060
REV. : B
DATE : MAY 2008
Page 2
SECTION 1 TABLE OF CONTENTS
SECTION 1 TABLE OF CONTENTS ..........................2
The X8I is an advanced system controller designed to
provide safe, reliable, and energy-efficient management
of your compressed air system. The X8I is capable of
controlling up to eight (8) positive displacement air
compressors. The compressors may be fixed speed,
variable speed or multi-step and have electro-pneumatic
SECTION 3 SAFETY
WARNING : Risk of Danger
WARNING : Risk of Electric Shock
WARNING : Risk of High Pressure
WARNING : Consult Manual
Before installing or operating the X8I, take time to
•
carefully read all the instructions contained in this
manual, all compressor manuals, and all manuals of
any other peripheral devices that may be installed or
connected to the unit.
Electricity and compressed air have the potential to
•
cause severe personal injury or property damage.
The operator should use common sense and good
•
working practices while operating and maintaining
this system. All applicable codes should be strictly
adhered to.
Maintenance must be performed by adequately
•
qualified personnel that are equipped with the
proper tools.
INSTALLATION
Installation work must only be carried out by a
•
competent person under qualified supervision.
A fused isolation switch must be fitted between the
•
main power supply and the X8I.
The X8I should be mounted in such a location as to
•
allow operational and maintenance access without
obstruction or hazard and to allow clear visibility of
indicators at all times.
If raised platforms are required to provide access
•
to the X8I they must not interfere with normal
operation or obstruct access. Platforms and stairs
should be of grid or plate construction with safety
rails on all open sides.
or microprocessor based controls. The X8I is uniquely
configurable and customizable to meet the specific needs
of some of the most complex compressed air system.
Additionally, the X8I control network can expand to
include monitoring and control of various compressed air
system components.
OPERATION
The X8I must only be operated by competent
•
personnel under qualified supervision.
Never remove or tamper with safety devices, guards
•
or insulation materials fitted to the X8I.
The X8I must only be operated at the supply voltage
•
and frequency for which it is designed.
When main power is switched on, lethal voltages are
•
present in the electrical circuits and extreme caution
must be exercised whenever it is necessary to carry
out any work on the unit.
Do not open access panels or touch electrical
•
components while voltage is applied unless it is
necessary for measurements, tests or adjustments.
Such work should be carried out only by a qualified
electrician equipped with the correct tools and
wearing appropriate protection against electrical
hazards.
All air compressors and/or other equipment
•
connected to the unit should have a warning sign
attached stating ‘THIS UNIT MAY START WITHOUT
WARNING’ next to the display panel.
If an air compressor and/or other equipment
•
connected to the unit is to be started remotely,
attach warning signs to the equipment stating ‘THIS
UNIT CAN BE STARTED REMOTELY’ in a prominent
location, one on the outside of the equipment, the
other inside the equipment control compartment.
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must only be
•
carried out by competent personnel under qualified
supervision.
If replacement parts are required use only genuine
•
parts from the original equipment manufacturer, or
an alternative approved source.
Carry out the following operations before opening or
•
removing any access panels or carrying out any work
on the X8I:
Isolate the X8I from the main electrical power
i.
supply. Lock the isolator in the ‘OFF’ position
and remove the fuses.
3
Page 4
Attach a label to the isolator switch and to the
ii.
unit stating ‘WORK IN PROGRESS - DO NOT
APPLY VOLTAGE’. Do not switch on electrical
power or attempt to start the X8I if such a
warning label is attached.
Make sure that all instructions concerning operation
•
and maintenance are strictly followed and that
the complete unit, with all accessories and safety
devices, is kept in good working order.
The accuracy of sensor devices must be checked
•
on a regular basis. They must be calibrated when
acceptable tolerances are exceeded. Always ensure
any pressure within the compressed air system is
safely vented to atmosphere before attempting to
remove or install a sensor device.
The X8I must only be cleaned with a damp cloth,
•
using mild detergents if necessary. Avoid the use of
any substances containing corrosive acids or alkalis.
Do not paint the control faceplate or obscure any
•
indicators, controls, instructions or warnings.
4
Page 5
SECTION 4 COMPRESSOR CONNECTION AND CONTROL
ir-485
irV-485
Ingersoll Rand
102
psi
1 3
1
2 4
CAP
18:35 #2
5 7
6 8
COMPRESSOR CONNECTION AND
CONTROL
Each air compressor in your system must be interfaced to
the X8I. Interface methods may vary depending on the
compressor type and/or local control configuration. The
following are main methods for interfacing compressors
to the X8I:
1) The ir-PCB Interface module that is designed to
interface to any positive displacement air compressor
(regardless of make or manufacturer) with an available
control voltage of 12-250V (either 50Hz or 60Hz).
The ir-PCB interface module is installed within the
compressor control area and connected to the X8I using
a six (6) wire cable, (seven (7)-wire cable for Nirvana 7.5 to
15HP (5.5 to 11KW).
Each air compressor must be equipped with an online/
offline pressure regulation system capable of accepting a
remote load/unload signal through a volt-free switching
contact or a single electro-mechanical pressure switch.
Consult the air compressor manual or your air
compressor supplier/specialist for details before installing
the X8I.
2) The ir-485 Gateway Interface module that is designed
to interface to any Ingersoll Rand Intellisys controlled
(Non-Nirvana) compressor. The X8I communicates to the
ir-485 Gateway via a two wire, RS485 network utilizing the
ir485 protocol. All IR compressors equipped with Intellisys
controllers (Non-Nirvana) require this interface.
The irV-485 Gateway interface module is installed within
the compressor control cabinet and connected to the X8I
using Belden 9841 or equivalent RS485 cable.
Nirvana 7.5 to 15HP (5.5 to 11KW) connect via the
ir- PCB using seven (7)-wire cable.
4) Direct Connect via RS485 to any Ingersoll Rand
compressor that has an integrated RS485 network port
utilizing the ir485 protocol. The X8I communicates to
these compressors via a two wire, RS485 network. The
compressor is connected to the X8I using Belden 9841 or
equivalent RS485 cable.
4) Special Application Interface uses integration boxes
designed to accommodate various types of compressor
and regulation methods and system monitoring.
OPTIONAL CONNECTION METHODS
Expansion Module: EXP Box (Option)
As standard the X8I has four direct connect ‘ir-PCB’
terminal connections. This capability can be extended
with the use of an optional EXP Box. The EXP Box will add
another four direct connect ‘ir-PCB’ connection terminals.
This would allow a total of 8 compressors to connected
and controlled via ‘ir-PCB’ integration.
Compressors 1-4 connect via the X8I and Compressors 5-8
connect via the EXP Box
The EXP Box is suitable for wall mounting and must be
located adjacent to the X8I unit (max 33ft or 10m).
All Nirvana Compressors, 20 HP (15KW) and above
require the irV-485 Gateway.
The ir-485 Gateway interface module is installed within
the compressor control cabinet and connected to the X8I
using Belden 9841 or equivalent RS485 cable.
3) The irV-485 Gateway Interface module that is
designed to interface to any Ingersoll Rand Nirvana
compressor. The X8I communicates to the irV-485
Gateway via a two wire, RS485 network utilizing the ir485
protocol. All Nirvana Compressors, 20 HP (15KW) and
above, require this interface.
The EXP Box connects to the X8I controller via a two wire,
dedicated RS485 network
Use Belden 9841 or Equivalent In Grounded Conduit
No Greater Than 33ft (10m)
Up to four air compressors can be connected to the EXP
Box using a 6 or 7 wire cable and a compressor interface
ir-PCB (330ft (100m) max). The ‘ir-PCB’ connections are
identical to the X8I.
5
Page 6
Remote Compressor Management; EX Box (option)
Ingersoll Rand
102
psi
1
CAP
1
5
2
6
3
7
4
8
18:35 #2
4000ft (1219m) max
From VSD Pressure Transducer
30ft
max
ir-PCB
o VSD Pressure Transducer Input
Ingersoll Rand
102
psi
1 3
2 4
1
CAP
18:35 #2
5 7
6 8
4000ft (1219) max
Ingersoll Rand
102
psi
1 3
1
2 4
CAP
18:35 #2
5 7
6 8
The EX Box is an ‘EXtension’ to the X8I providing
additional ‘ir-PCB’ connectivity.
The EX Box will typically be used to provide ‘ir-PCB’
connectivity at a remote location beyond the maximum
distance specification of compressors that require ‘ir-PCB’
type connection; 330ft (100m). This effectively expands
the hardwire connection scheme of the ‘ir-PCB” to the full
RS485 distance specification.
The EX box is suitable for wall mounting and can be
located up to 4000ft (1219m) from the X8I unit.
The EX Box connects to the X8I controller via a two wire,
RS485 network utilizing the IR485 protocol
The VSD Box connects to the X8I controller via a two wire,
RS485 network utilizing the ir485 protocol
Each air compressor in a system, that requires VSD Box
integration, must be equipped with an individual VSD
Box. Multiple VSD Boxes can be connected to the X8I as
long as the number of compressors does not exceed the
maximum number of compressors (8).
Remote Input & Output: I/O Box (option)
An I/O Box provides additional general purpose I/O
(input/output) for a system enhancing monitoring
capabilities and providing distributed system automation.
Up to two I/O Boxes can be connected to the X8I
controller. Each I/O Box features:
8 Digital Inputs
5 Analog Inputs
6 Relay Outputs
Use Belden 9841 or Equivalent In Grounded Conduit
No Greater Than 4000ft (1219m)
One (1) or two (2) air compressors can be connected
to the EX Box using a 6-wire cable and a compressor
interface ir-PCB (330ft (100m) max). The ‘ir-PCB’
connections are identical to the X8I.
The EX Box also provides optional ‘local pressure sensor’
connections. The compressor delivery pressure, local
system pressure and air treatment differential pressure
can be displayed.
Multiple EX Boxes can be connected to the X8I as long
as the number of compressors does not exceed the
maximum number of compressors (8).
Bolt-On VSD Control Integration: VSD Box (optional)
The VSD Box is intended to provide a method of
system integration for a VSD (Variable Speed Drive) air
compressor that is not equipped with any accessible
means of remote connectivity (such as IR- Nirvana). The
VSD Box will provide required functionality to enable
system integration and efficient control using the X8I
automation system.
The I/O Box connects to the X8I controller via a two wire,
RS485 network utilizing the ir485 protocol
Digital inputs can be used to monitor switching contact
devices. Each input can be set to act as an Alarm or
High Level Alarm input. Digital inputs can also be used
for metering (for example m3, ft3, kWh) providing an
accumulative count of pulses from a metering device.
Analog inputs can be used to monitor sensor devices (for
example: pressure differential, temperature, dewpoint,
flow, current, power, bearing condition). Each input is
equipped with adjustable high or low level detection that
can be used to activate an Alarm or High Level Alarm.
Relay outputs use ‘Virtual Relay Automation’ technology
and are totally configurable with duel input logic
functions. Relay functions can be assigned utilizing any
status or condition information available on a system
network from any compatible unit connected to the
network.
PRESSURE DETECTION AND CONTROL
The X8I utilizes the signal from a 4-20 ma pressure sensor
that is mounted remotely from the X8I in a suitable
location in the compressed air system.
The factory default settings for the pressure sensor is
0–232 PSI (16 bar), but the X8I can accept any pressure
sensor with a 4–20 ma output and a range of up to 8700
PSI (600 bar).
Single Conductor Wire, 18 Gauge Stranded, Quantity (7)
In Grounded Conduit No Greater Than 330FT (100M)
24VAC Control Voltage
Reference X8I Application and Interconnect Guide For
Wiring Connections Between The X8I, The ir-PCB,
and The Compressor
EXP
EXP RS485 Network Cable
The Maximum Number of Compressors Controlled By
The X8I Is Eight (8).
The Maximum Number Of Direct ir-PCB Connections
To The X8I is Four (4)
.
Any Combination Of Compressor Connection Methods
May Be Used As Long As the Maximum Number Of
Compressors (8) Is Not Exceeded.
OPTIONAL
Ingersoll Rand
102
psi
13
24
1
CAP
18:35 #2
57
68
EXP RS485 NETWORK CABLE
Belden 9841 or Equivalent
In Grounded Conduit
No Greater Than 33FT (10)
RS485 NETWORK CABLE
Belden 9841 or Equivalent
In Grounded Conduit
No Greater Than 4000FT (1219M)
EX
Ingersoll
Rand
102 psi
ir-485
Direct To
S3
Ingersoll
Rand
102 psi
OR
Ingersoll
Rand
102 psi
LE
D
1
LE
D
2
ir-PCB
From VSD Pressure
Transducer
To VSD Pressure
Transducer Input
I/O
Ingersoll
Rand
102 psi
VSD
Reference X8I Application and Interconnect Guide For
Wiring Connections Between The X8I, The ir-485 or irV-
485 Gateway and The Compressor, S3 Direct Connects, and
Optional Special Application Interface Boxes
The EXP Will Add Another (4)
Direct ir-PCB connections. This
Would Allow A Total Of (8)
Compressors To Be Connected
And Controlled Via The ir-PCB.
ir-PCBir-PCB
The RS485 Network is a Serial, Point to Point
Communication Network Refer to the X8I Application and
Interconnect Guide For Wiring Details and Connectivity.
ir-485 Gateway
For All
IR (Non- Nirvana) Compressors
IntelliSys “Red Eye”, SG and SE
irV-485 Gateway
For All
Nirvana Compressors
20HP (15KW) and Above
irV-485
ir-485
8
Page 9
INSTALLATION
XPM-TAC24
1
P
P
2
1
P
2
P
1
P
2
P
P
It is recommended that installation and
commissioning be carried out by an authorized and
trained product supplier.
UNIT LOCATION
The X8I can be mounted on a wall using conventional
bolts. The X8I can be located remotely from the
compressors as long as it is within 330 feet (100 meters)
of cable length when connecting compressors directly
with ir-PCB’s. When connecting the X8I over the RS485
communication network the distance is up to 4000 feet
(1219 meters) The X8I must be located within 330 feet
(100 meters) of the system pressure transducer.
POWER SUPPLY
A fused switching isolator must be installed to the main
incoming power supply, external to the X8I. The isolator
must be fitted with a properly sized fuse to provide
adequate protection to the power supply cable used (in
accordance with local electrical and safety regulations).
1
1 2 3 4
N L E
X04
X01
X04
Power Supply Terminals
2 3 4
VOLTAGE SELECT
1
2 3 4
VOLTAGE SELECT
230Vac
115Vac
Dry side pressure will be lower than the system
pressure due to pressure differential losses across air
treatment equipment. The nominal system pressure will
reduce as the air treatment differential pressure increases.
DEMAND (DRY) SIDE PRESSURE CONTROL
Pressure Sensor Located After Shared Cleanup
Equipment
Pressure Sensor Located After Individual Cleanup
Equipment
Ensure each compressor is equipped with
independent excess pressure shutdown. An increase in
pressure differential across air treatment equipment can
result in excess compressor discharge pressure.
Ensure that the voltage select input is properly
jumpered for the incoming power. Default voltage
configuration is 230Vac.
PRESSURE SENSOR LOCATION
The system pressure sensor (P) must be located where
it will see the air pressure that is common to all of the
compressors.
SUPPLY (WET) SIDE PRESSURE CONTROL
Pressure Sensor Located Before Cleanup Equipment
Regular routine monitoring of pressure differential
across air treatment equipment is recommended.
9
Page 10
PRESSURE SENSOR CONNECTION
Cable Earth Shield
The pressure sensor connects to terminal X05 of the X8I
terminal PCB using a shielded 18 AWG maximum 2conductor cable no more than 330 feet (100 meters) in
length. The transducer threads are BPT. It is the equivalent
of ¼” NPT.
Wire polarity is important.
For each compressor utilizing an ir-PCB, connection to
the X8I the signal wires must be made to the correct
X8I terminals for that compressor number. Compressor
1 should be wired to terminal X01 on the terminal PCB,
Compressor 2 should be wired to terminal X02 on the
terminal PCB, etc.
ir-PCB Interface Module
The ir-PCB is a DIN rail mountable module designed to be
installed within the compressor starter enclosure.
Pressure Sensor Wiring and Location
IRPCB INTERFACE MODULE
Each air compressor must be equipped with a load/
unload regulation system and, if not regulated with a
single electro-mechanical pressure switch, have a facility
for a remote load/unload control with the ability to
accept a volt-free switching contact input for remote
load/unload. Each air compressor must have Auto Restart
capability.
The ir-PCB accepts a 12V to 250V input voltage detection
system and utilizes universal relay contact control outputs
(250V “CE” / 115V “UL” @ 5A maximum) integrated directly
into the circuits of an air compressor. The ir-PCB avoids
the need for additional relays or remote inputs. The ir-PCB
also acts as an electrical barrier between the compressor
and the X8I providing protection and voltage isolation.
Consult the X8I Interconnect and Application Guide
prior to the installation of the X8I and the ir-PCB to the air
compressor.
The ir-PCB is designed to interface a compressor with
the X8I using a seven (7)-conductor shielded cable or
individual wires run through grounded conduit no
greater than 330 feet (100 meters) in length.
Each compressor in the system must be assigned a
unique identification number from 1 up to the number
of compressors in the system. The identification number
should be clearly indicated on each compressor for
operational reference.
10
Page 11
IR485 AND IRV485 GATEWAY MODULE
ir-485
irV-485
28
30
27
29
X06
Ingersoll Rand
102
psi
1 2 3 4
1
CAP
18:35 #2
5 7
6 8
4000ft (1219m) max
I/O
Ingersoll
Rand
102 psi
Ingersoll Rand
102
psi
1
CAP
1
5263748
18:35 #2
12
Ingersoll
Rand
102 psi
EX
Ingersoll
Rand
102 psi
EX
I/O
Ingersoll
Rand
102 psi
RS485 NETWORK
The ir-485 and irV-485 Gateways are designed to
interface the Intellisys Controller on the Ingersoll Rand
Compressors and the Nirvana compressors, 20 HP (15KW)
and above, with the X8I via the RS485 Network utilizing
the ir485 protocol. The ir-485 and irV-485 Gateways
are DIN Rail mounted and can be located within the
compressor control gear enclosure or remotely within a
separately enclosure.
ir-485 Gateway irV-485 Gateway
The cable used between the X8I and the ir-485 and irV485 Gateways is Belden 9841 (or equivalent). It should be
run in grounded conduit and should not be greater than
4000 feet (1219 meters) in length.
The cable used between the ir-485 Gateway and irV-485
Gateways and the Intellisys Controller is included with the
Installation Kit
The cable used between the ir-485 Gateway and the
Intellisys Controller is included with the Installation Kit
The X8I is equipped with an RS485 network
communications capability using the ir485 protocol. This
facility can be used for remote connectivity to optional
networked units and modules with ir485 communications
capabilities or compressor controllers equipped with the
ir485 capability.
L2
L
1
RS485
L
L1
2
The RS485 Network is a Serial, Point to Point
Communication Network. Refer to the X8I Application
and Interconnect Guide For Wiring Details and
Connectivity.
The following example details the “correct” method of
wiring the RS485 Network
Consult the X8I Interconnect and Application Guide
and the ir-485 or irV-485 Gateway Manual prior to the
installation of the X8I and the Compressor Gateway to the
air compressor.
The following example details the “incorrect” method of
wiring the RS485 Network
Correct RS485 Network Example
IR485 COMMUNICATION PROTOCOL
ir485 is a unique communication protocol designed
specifically for Compressor and Air System control. ir485
is a Multi-Master vs. a Master–Slave protocol that enables
faster, more effective control of network components.
ir485 also features distributed control capabilities and has
inherent resistance to communication faults due to noise
RS485 data communications and other low
voltage signals can be subject to electrical interference.
This potential can result in intermittent malfunction
or anomaly that is difficult to diagnose. To avoid this
possibility always use earth shielded cables, securely
bonded to a known good earth at one end. In addition,
give careful consideration to cable routing during
installation.
a) Never route an RS485 data communications or low
voltage signal cable alongside a high voltage or 3-phase
power supply cable. If it is necessary to cross the path of a
power supply cable(s), always cross at a right angle.
b) If it is necessary to follow the route of power
supply cables for a short distance (for example: from a
compressor X8I to a wall along a suspended cable tray)
attach the RS485 or signal cable on the outside of an
earthed cable tray such that the cable tray forms an
earthed electrical interference shield.
c) Where possible, never route an RS485 or signal cable
near to equipment or devices that may be a source of
electrical interference (for example: 3-phase power
supply transformer, high voltage switchgear unit,
frequency inverter drive module, radio communications
antenna).
12
Page 13
SECTION 6 CONTROL FEATURES AND FUNCTIONS
PH
PL
PT
a
b
PH
PL
PT
PH
PT
PL
PH + TO
PL - TO
TO
TO
STANDARD CONTROL FEATURES AND
FUNCTIONALITY
PRESSURE CONTROL
Pressure control is achieved by maintaining the system pressure
within an acceptable range, or pressure band, which is defined and
programmed by the user. Pressure will rise in the band when system
demand is less than the loaded compressor’s output. Pressure will
fall in the band when system demand is greater than the loaded
compressor’s output.
Simply stated, pressure control is achieved by unloading and
loading compressors to closely match compressor output with
system demand within a specified pressure band defined by PL and
PH. See Figure 1.
Variable speed compressors also operate within the pressure band
and actively match compressor output with system demand by
speeding up and slowing down around a target pressure defined by
the exact midpoint of the pressure band defined by PT. See Figure 2.
Figure 1 — Typical System Pressure vs. Time
As pressure rises to point “a”, the compressor will unload
based on the sequencing algorithm. System pressure is
then allowed to decrease due to the drop in supply until
point “b” is reached. Once point “b” is reached, the X8I will
load the next compressor in the sequence to match the
air demand. This cycle will repeat as long as the X8I is able
to keep the system air pressure between PH and PL.
ANTI-CYCLING CONTROL
The most efficient way to utilize most air compressors is
either fully loaded or off, with the exception of variable
speed compressors which can operate efficiently at
reduced loading. Compressor cycling (start-load-unloadstop, etc.) is essential to maintain pressure control.
Excessive cycling, however, can result in poor compressor
efficiency as well as increased maintenance.
Anti-cycling control is incorporated to help ensure
that only the compressors that are actually required
are started and operating while all others are kept off.
Anti-cycling control includes a pressure tolerance range
or band, defined by the user, which is outside of the
primary pressure band. Inside the tolerance band, an
active control algorithm continually analyzes pressure
dynamics to determine the last possible second to add or
cycle another compressor into the system. This control is
further enhanced by the ability to fine tune the tolerance
band settings and algorithm processing time (Damping).
TOLERANCE
Tolerance is a user adjustable setting that determines
how far above the PH setpoint and below the PL setpoint
system pressure will be allowed to stray. Tolerance
keeps the X8I from overcompensating in the event of
a temporary significant increase or decrease in system
demand.
Figure 2 — Typical VSD Pressure Control vs. Time
The variable speed compressors in the system will run
on their target pressure and smooth out the variations in
system pressure. This assumes that system demand does
not vary more than the capacity of the variable speed
compressor.
A variable speed compressor will be included in the
load/unload sequence and be controlled exactly as a
fixed speed machine with the exception of speed control
to maintain target pressure.
Figure 3 — Tolerance in Relation to PH and PL
Tolerance (TO) is expressed as a pressure defining the
width of the band above PH and below PL in which
energy efficient control will be in effect.
When system pressure is in the tolerance band, the
X8I will continuously calculate the moment at which
compressors will be loaded or unloaded based on the rate
of change of system pressure. When the system pressure
strays outside of the tolerance band, the X8I will abandon
energy efficiency and begin to protect the system air
pressure by loading or unloading the compressors.
Loading will be delay controlled.
13
Page 14
When the compressed air system storage is relatively
+
-
small compared to the system demand, and fluctuations
are large and quick, the tolerance band setting should
be increased to maintain energy efficient operation and
avoid a situation in which multiple compressors are
loaded just to be unloaded moments later.
When the compressed air system is relatively large
compared to system demand and fluctuations are
smaller and slower, the tolerance band can be reduced to
improve pressure control and maintain energy efficient
operation.
The factory default setting for tolerance is 3.0 PSI (0.2Bar).
This setting is user adjustable.
DAMPING
Any time the pressure is within the Tolerance band the
Anti-Cycling algorithm is active, sampling the rate of
pressure change and calculating when to load or unload
the next compressor. The damping (DA) setting is a user
adjustable setpoint that determines how quickly the
controller samples and recalculates, effectively speeding
up or slowing down the reaction time.
The X8I’s factory default DA setting of “1” is adequate for
the majority of compressed air systems but may need
to be adjusted in the following circumstances involving
aggressive and disproportionate system pressure
changes:
Inadequate air storage
•
High pressure differential across the air
•
treatment equipment
Incorrectly sized piping
•
Slow or delayed compressor response
•
In these circumstances, the X8I may overreact and
attempt to load additional compressors that may not
be necessary if the system was given time to allow the
system pressure to stabilize after the initial compressor
is given time to load. If the tolerance has already been
increased and the X8I is still overreacting, then increasing
the damping factor is the next step.
SYSTEM VOLUME
Assorted Receiver Tanks
System volume defines how fast system pressure will rise
or fall in reaction to either increased/decreased demand
or increased/decreased supply. The larger the system
volume, the slower the pressure changes in relation to
increased/decreased demand or supply. Adequate system
volume enables effective pressure control and avoids
system over-pressurization in response to abrupt pressure
fluctuations. Adequate system volume is created by
correctly sizing and utilizing air receivers.
The most accurate way to determine the size of air
receivers or the additional volume required would
be to measure the size and duration of the largest
demand event that occurs in the system, then size the
volume large enough to ride through the event with
an acceptable decrease in system pressure. Sizing the
volume for the worst event will ensure system stability
and effective control over all other normal operating
conditions.
If measurement is not available, then estimating the
largest event is a reasonable alternative. For example,
assume that the largest demand event could be equal to
the loss of the largest operating air compressor. System
volume would be sized to allow time for a back-up
compressor to be started and loaded with an acceptable
decrease in pressure.
The following formula determines the recommended
minimum storage volume for a compressed air system:
Damping is adjustable and is scaled from 0.1 to 10 with
a factory default of 1. A factor of 0.1 is a reaction time
10 times faster than the default and a factor of 10 is a
reaction time 10 times slower than the default.
NOTE: There are many variables that go into determining the stability and control of the system pressure, only some of which are able to be controlled by
the X8I. System storage, air compressor capacity, and
air demand all need to be analyzed by experienced
professionals to determine the best installation for
your system. Tolerance (TO) and damping (DA) can be
used for minor tuning of the system.
V — “Volume of Required Storage” (Gal, Ft3, m3, L)
T — “Time to Start Back-up Compressor” (Minutes)
C — “Lost Capacity of Compressed Air” (CFM, m3/min)
Pa — “Atmospheric pressure” (PSIa, BAR)
∆P — “Allowable Pressure Drop” (PSI, BAR)
14
Page 15
Example 1: Find Required Storage Volume in Ft3 and US
20%
40%
80%
100%
100%
0%
0%
2
1
1234
#1
#2
#3
#4
ABCD
ACDB
ADBC
ABCD
1222
Gal.
(4) - 100 Hp Compressors at 450 CFM (12.7 m3) each /
15 seconds to start and load a compressor. 5PSIG is the
maximum allowable pressure drop.
T=15 Seconds (.25 minute)
C=450 ft3
Pa = 14.5 PSI
Delta P = 5 PSI
V = [.25 x (450 x 14.5)]/5
V = (.25 x 6525)/5
V = 1631/5
V = 326 Ft3
1 ft3 = 7.48 Gal
Gal= 326 Ft3 x 7.48
Gal = 2440
Example 2: Find Required Storage Volume in m3 and L.
(4) - 100 Hp Compressors at 450 CFM (12.7 m3) each / 15
seconds to start and load a compressor. 0.34 BAR is the
maximum allowable pressure drop.
T=15 Seconds (.25 minute)
C=12.7 m3
Pa = 1BAR
Delta P = .34 BAR
V = [.25 x (12.7 x 1)]/.34
V = (.25 x 12.7)/.34
V = 3.2/.34
V = 9.33m3
1m3 = 1000 L
L= 9.33 m3 x 1000
L = 933
STANDARD CONTROL FEATURES AND
FUNCTIONALITY
STANDARD SEQUENCE CONTROL STRATEGIES
The standard configuration of the X8I provides ENER
(Energy Control) sequence control strategy, Priority
Settings, Table Selection, Pressure Schedule, and Pre-fill
operation.
ENER: Energy Control Mode
Control and Rotation:
Compressor control and utilization is dynamically
automated with adaptive control logic and therefore
does not follow pre-determined schedules, rotation
configurations or time intervals. Energy Control mode
can, however be operator influenced by the Priority
functionality which is discussed later in this manual.
Energy Control mode is enabled by the ability of the
X8I to process individual compressor capacity, variable
capacity capabilities, and changes in system pressure to
dynamically implement and continuously review ‘best fit’
configurations as demand variations occur.
1: Demand
2: Supply
PRIORITY SETTINGS
The sequence assignment pattern can be modified by
using the priority settings.
Priority settings can be used to modify the rotation
sequence assignments. Compressors can be assigned
a priority of 1 to 8, where 1 is the highest priority. Any
compressor can be assigned any priority and any number
of compressors can share the same priority.
Priorities allow you to set up rotation groups. All
compressors that have the same priority number will
rotate inside their own group. The group with the highest
priority will always be in the front of the sequence.
For example, in a four compressor system including one
variable speed compressor in the compressor 1 position
you may want the variable speed compressor to always
be in the Lead position. By assigning compressor 1 a
priority of 1 and the other three compressors a priority
of 2, the variable speed compressor will always remain at
the front of the sequence:
The primary function of Energy Control mode is to:
1/ Dynamically match compressed air supply with
compressed air demand.
2/ Utilize the most energy efficient set/combination of air
compressors to achieve 1/.
Energy Control mode is designed to manage systems that
include compressors of different capacities and different
air compressor types (fixed speed, variable speed and
variable capacity) in any combination or configuration.
Compressor 1 has priority 1, all other compressors have
priority 2
15
Page 16
In another example, there is a four compressor system
1234
#1
#2
#3
#4
ABCD
BCAD
CABD
ABCD
1112
1234
#1
#2
#3
#4
ABCD
ACBD
ABCD
ACBD
1223
1234
#1
#2
#3
#4
ABCD
BADC
ABCD
BADC
1122
T01
PH
PL
Pm
SQ
- - - -
- - - -
- - - -
- - - -
that includes a compressor in the compressor 4 spot
that is used only as an emergency backup compressor.
To accomplish this, simply assign compressor 4 a lower
priority than any other compressor in the system:
Compressor 4 has priority 2, all other compressors have
priority 1
In a third example, there is a four compressor system
that includes a variable speed compressor designated
compressor 1 and a fixed speed compressor that is an
emergency backup assigned as compressor 4. To ensure
that compressor 1 is always at the front of the sequence
and compressor 4 is always at the end of the sequence,
set the priority as shown below:
Priority control will also work with ENER control mode. Recall that ENER control automatically selects
the most efficient set of compressors to dynamically
match compressed air demand. Priority will force the
X8I controller to select from all “priority 1” compressors
and make sure that they are loaded in the sequence
before utilizing any priority 2 compressors. All priority
2 compressors must be utilized before priority 3
compressors can be loaded and so on. Priority allows
a system to be segregated to backup and primary use
compressors when using ENER control.
Note: Using the Priority function with ENER Control can
affect system efficiency.
TABLES AND THE PRESSURE SCHEDULE
The X8I operates based on settings that are
configured into one of three tables. Each table defines
the operational settings and sequence control mode
of the X8I. The X8I can be instructed to change among
the tables at any time based on the configuration of the
pressure schedule.
This functionality allows the X8I to switch among
multiple different system configurations without any
disruption to control. This is particularly useful in the case
of shift changes, or weekends when the system is to be
deactivated.
Compressor 1 has priority 1, compressor 4 has priority 3
and all other compressors have priority 2
A last example involves another four compressor system
that will be assigned into two independently rotation
groups. Compressors 1 and 2 are given priority 1 and
compressors 3 and 4 are given priority 2. This results in
the rotation sequence shown below:
Each table consists of the following parameters which can
be set independently in each table:
PH – High Pressure Setpoint
•
PL – Low Pressure Setpoint
•
Pm – Minimum pressure warning level
•
SQ – Sequence Rotation Strategy
•
01 – Compressor 1 Priority
•
02 – Compressor 2 Priority
•
03 – Compressor 3 Priority
•
04 – Compressor 4 Priority
•
The “maximum” pressure fault level and the rotation
interval, or rotation time, are set independently in a
configuration menu and are unchanging regardless of the
table selected.
When the X8I is instructed to change between tables,
it will not abruptly change the system operating
parameters. The X8I will adjust the system target pressure
upward or downward to the next table’s settings.
This transition will occur gradually to preserve energy
efficiency and safe, reliable control:
Two independently rotating compressor groups
16
Page 17
PC
1
2
Changing Target Pressures
! X
A
CAP
The time the system is allotted to change the target
pressure is known as the Pressure Change Time (PC). This
is a value that is adjustable in the system settings screen.
See the Quick Setup Manual.
If the X8I is able to complete the transition in less time
than is allotted without threatening energy efficiency
then PC will be automatically shortened.
An aggressively short time setting will compromise
energy efficiency.
PRESSURE SCHEDULE
The X8I is equipped with a real-time clock feature
and pressure schedule functionality. The pressure
schedule function can be used to provide enhanced
system automation.
The pressure schedule consists of 28 individual settings
that instruct the system to change from one table to
another, or put the system into standby mode dependent
on the time of day and the day of the week. The pressure
schedule will cycle from 00:00 hours Monday (day #1) to
23:59 hours on Sunday (day #7) each calendar week.
The pressure schedule has the capability of changing
tables based on the time of day, once each day, or once
each day except weekends. Please see the Quick Setup
Manual for detailed information on how to configure the
pressure schedule.
At system start (manual start or automated start from
standby) the X8I will only load compressors that have
been pre-determined for prefill operation, for a pre-set
period of time. The prefill time (PT) can be adjusted to suit
system characteristics. The aim is to increase pressure to
normal operational levels, using only the pre-determined
compressors, prior to the prefill time expiring.
If normal operational pressure is reached prior to the
set prefill time, the prefill function will automatically
cease and normal operational control begin. If normal
operational pressure is not reached by the end of
the prefill time the P4 will utilize as many available
compressors as required to achieve normal operational
pressure as quickly as possible. Normal operational
control will then begin.
Three prefill modes are available. ‘Backup’ and ‘Standard’
modes require compressor pre-selection and function in
the same way; differing only in response to a failure, or
loss, of a prefill compressor. Automatic mode requires no
compressor pre-selection.
Backup Mode: Compressor(s) can be pre-selected
as ‘Primary Prefill’ compressor(s) or ‘Backup Prefill’
compressor(s). If a primary prefill compressor experiences
a shutdown, or is stopped, a pre-defined backup
compressor replaces it and prefill continues.
Standard Mode: If one or more of the predefined prefill compressors experiences a shutdown, or
is stopped, the prefill function is cancelled and normal
operation begins.
Automatic Mode: No Prefill compressor
selection is necessary; any selection set is ignored. The
management unit automatically selects compressor(s)
dynamically to achieve pressure in accordance with
the set Prefill time. If a compressor is stopped, or shuts
down, it is automatically substituted with an alternative
compressor.
The Prefill feature provides a controlled and energy
efficient method of increasing pressure to normal
operating levels at system start. This feature avoids the
inefficient potential for all available system compressors
to start and load before pressure reaches the normal
operating level.
To manually skip Prefill mode, press and hold Start
for several seconds.
Insufficient Capacity Alarm
The X8I is equipped with a dedicated ‘Insufficient
Capacity’ Advisory Alarm (Warning) indication.
This indication will illuminate if all available compressors
are loaded and system pressure is continuing to decrease.
The indication will generally occur prior to any set low
pressure Alarm (Warning) and is intended to provide an
advanced warning of a potential ‘Low Pressure’ situation.
17
Page 18
The ‘Insufficient Capacity’ advisory alarm is intended as an
CAP
1234
#1
#2
#3
#4
ABCD
DABC
CDAB
BCDA
advanced warning and is not recorded in the fault history
log but is included as a Group Alarm (Warning), or Group
Fault item.
‘Insufficient Capacity’ is available as a dedicated data
communications item.
ALTERNATE CONTROL FEATURES AND
FUNCTIONALITY
Energy Control Mode (ENER) is the STANDARD control
mode of the X8I. Alternate control strategies of the X8I are
the basic FILO (First in / Last Out) and EHR (Equal Hours
Run) EHR
The ‘Insufficient Capacity’ advisory alarm function
can be de-activated. In this instance the unit’s Alarm
indicator will still illuminate but no group alarm, group
fault, or a remote indication is generated.
Restricted Capacity Alarm
The X8I is equipped with a dedicated ‘Restricted Capacity’
Advisory Alarm (Warning) indication.
This indication will flash if all available compressors are
loaded and further capacity is required but one or more,
compressors are: 21
a) inhibited from use in a ‘Table’ priority setting
b) inhibited from use by the short-term Service/
Maintenance function
c) inhibited from use in the long term maintenance menu.
FILO: TIMER ROTATION MODE
The primary function of Timer Rotation mode is to
efficiently operate a compressed air system consisting of
fixed capacity output compressors. The routine rotation
assignments can be modified using ‘Priority’ settings
to accommodate for a differentially sized or variable
capacity output compressor(s).
Rotation:
Each time the rotation interval elapses, or the rotation
time is reached, a sequence rotation occurs and the
sequence assignment for each compressor is re-arranged.
The compressor that was assigned for duty (A) is reassigned as last standby (D) and all other compressor
assignments are incremented by one.
The ‘Restricted Capacity’ advisory alarm is intended to
indicate that all available compressors are already loaded
and further capacity is required but one or more, system
compressor(s) have been restricted from use.
The ‘Restricted Capacity’ advisory alarm is not recorded
in the fault history log but is included as a Group Alarm
(Warning), or Group Fault item.
‘Restricted Capacity’ is available as a dedicated data
communications item.
The ‘Restricted Capacity’ advisory alarm function can
be de-activated. In this instance the unit’s Alarm indicator
will still flash but no group alarm, group fault, or a remote
indication is generated.
The sequence assignment pattern can be modified by
‘Priority’ settings.
Tables; Priority Settings
Control:
Compressors are utilized, in response to changing
demand, using a ‘FILO’ (First In, Last Out) strategy.
The ‘duty’ compressor (A) is utilized first followed by (B)
if demand is greater than the output capacity of (A). As
demand increases (C) is utilized followed by (D) if demand
increases further.
As demand reduces (D) is the first compressor to be
unloaded, followed by (C) and then (B) if demand
continues to reduce.
The last compressor to be unloaded, if demand reduces
significantly, is (A). The compressor assigned as (A) in
the sequence is the first to be loaded and the last to be
unloaded.
18
Page 19
SEQUENCE ROTATION EVENTS
A sequence rotation event can be triggered in the
following ways: a periodic interval, a pre-determined
time each day, or a pre-determined time day and time
each week. Please refer to the Quick Setup Manual to
determine how to configure the rotation events.
EQUAL HOURS RUN MODE
The primary function of EHR mode is to keep the
running hours of all compressors in the system as close
as possible. This provides the opportunity to service
all of the compressors at the same time, given that the
expected service interval for the compressors is similar.
EHR is not an energy efficient focused mode of
operation.
Each time the rotation interval elapses, or the rotation
time is reached, the sequence order of compressors is
reviewed and re-arranged dependant on the running
hours recorded for each compressor. The compressor with
the least recorded running hours is assigned as the ‘duty’
compressor, the compressor with the greatest recorded
running hours is assigned as the ‘last standby’ compressor.
For systems with more than two compressors, the
remaining compressor(s) are assigned in accordance with
there recorded running hours in the same way.
If a compressor is operated independently from
the X8I the running hours record may not be accurately
updated.
The running hours meter display on most
compressors are intended for approximate service
interval indication only and may deviate in accuracy over
a period of time.
Control:
Compressors are utilized, in response to changing
demand, using a ‘FILO’ (First In, Last Out) strategy. The
‘duty’ compressor (A) is utilized first followed by (B) if
demand is greater than the output capacity of (A).
As demand increases (C) is utilized followed by (D) if
demand increases further. As demand reduces (D) is the
first compressor to be unloaded, followed by (C) and then
(B) if demand continuous to reduce.
The last compressor to be unloaded, if demand reduces
significantly, is (A). The compressor assigned as (A) in
the sequence is the first to be loaded and the last to be
unloaded.
Example: The compressors in a four compressor system
have the following recorded running hours when a
rotation event occurs:
Compressor 1 = 2200 hours
•
Compressor 2 = 2150 hours
•
Compressor 3 = 2020 hours
•
Compressor 4 = 2180 hours
•
The new sequence order after the rotation event would
be:
Compressor 1 = D
•
Compressor 2 = B
•
Compressor 3 = A
•
Compressor 4 = C
•
Compressor 3, which has the fewest running hours, will
now be utilized more frequently in the new sequence,
allowing running hours to accumulate at a faster rate.
The X8I continuously monitors the running status of each
compressor and calculates the accumulated running
hours. These readings are viewable and adjustable
in the X8I C01 setting screens. The X8I will use these
values during EHR mode. The running hours on the X8I
should be routinely checked to see that they match the
compressors’ local calculations, and adjusted if necessary.
19
Page 20
SECTION 7 DISPLAY AND MENU OPERATION
a
b
c
d
f
g
h
e
Ingersoll Rand
102
psi
A: 85%
1
CAP
1
5
2
6
3
7
4
8
102
PSI
1
a
b
c
d
e
17:30#1
a
b
c
CAP
a
b
c
1
Keypad and Navigational Keys Functionality
a) Start
b) Reset
c) Stop
d) Menu
e) Enter
f) Escape
g) Up (Plus)
h) Down (minus)
Compressor Status Indicators :
a) Load Status
b) Run Status
c) Compressor Availability
System Alarms (Warning) :
a) Group Compressor Fault
b) Insufficient Capacity Alarm (Warning)
c) Restricted Capacity Alarm (Warning)
System Alarms (Warning) :
a) Unit Run Indicator (green LED)
b) Unit Alarm Indicator (Red LED)
User Interface :
a) System Pressure Value
b) System Pressure Units
c) Unit Status
d) Unit Active Functions
e) User Menu Item
The Main Display and the keypad and navigation buttons on the X8I are depicted below and provide the following
functionality:
20
Page 21
1
2
3
4
Unit Functions:
The following Icons are used by the X8I to
display the Controller Active Functions.
EHR - Equal Hours Run
Increasing to normal operational levels (Prefill,
target pressure change or at system start)
Below the active lower, or load, pressure set point
Above the upper, or unload, active pressure set point
The following Icons are used by the X8I to
display the Controller Status.
Stopped
Standby
Started and Running
Alarm (Warning)
Shutdown (Trip)
Day of the week
#1 = Monday
#2 = Tuesday
#3 = Wednesday
#4 = Thursday
#5 = Friday
#6 = Saturday
#7 = Sunday
Between the lower, or load, and upper, or unload,
active pressure set points
FILO - Timer Rotation
ENER - Energy Control
Active Functions :
Operating Mode :
System Pressure Status :
Units Status :
Power Failure Auto-Restart
Table #1
Table #2
Table #3
Table #4
Standby Mode Active
Prefill Function
Pressure Schedule
Function Inhibited (Manual Override)
Remote Manual Override
System Pressure Value
System Pressure Units
Real Time Clock
24 Hour Format
21
Page 22
17:30 #1
A: 100%
1
#
102 psi
00:00 #1
Main Manu
Real Time Clock
Compressor Detailed Status:
Compressor Status Symbols
Primary Detected Pressure
Next Scheduled Sequence Rotation
The Pressure detected on the unit’s
primary pressure sensor.
The next scheduled sequence rotation:
00 : 00 Time (24 hr system)
#1 Monday
A setting of zero hundred hours (00:00hrs)
on Monday (#1) equates to a sequence
rotation at one second past midnight on
Sunday.
17.30 (24r system)
# 1 = Monday to # 7 = Sunday
Standby (or Auto restart)
Running Offload
Running Loaded
Removed From Service in Table Priority Selection (# = Table Number)
Removed From Service in Long Term Maintenance Menu
Alarm (Warning) Standby (or Auto Restart)
Not Available(Stopped Shutdown, Trip Standby (or Auto Restart)
Network Communication Error (RS485 Connectivity Only)
A number of User menu information displays are
available that can be accessed directly from the
front panel using the Up and Down navigation
buttons.
User Manu
22
Page 23
INDICATORS
1sec
1sec
1sec
a
b
c
1
a
b
c
CAP
Indicators
The X8I indicators are as follows.
ON – Loaded
b) Run Status
OFF – Not Running
Off
On
Intermittent:
Slow Flash:
Fast Flash:
Unit Indicators
Unit Run Indicator (Green LED)
Slow Flash – The compressor has been requested
to load but is not running (blowdown delay or
other start delay)
ON – Running
c) Compressor Availability
OFF – No Compressor Connected
Fast Flash – Not Available, Shutdown Fault or
Stopped
Slow Flash – Alarm (Warning)
Intermittent Flash – The compressor has been
intentionally removed from service.
Available, OK
System Alarms (Warnings):
OFF – Not Active, Stopped
Slow Flash: Active, Standby Mode
ON – Active, Running
Unit Fault Indicator (Red LED)
Fast Flash: Shutdown (Trip)
Slow Flash: Alarm (Warning)
The X8I fault indicator does not indicate compressor
fault states; see Compressor Status Indicators.
Compressor Status Indicators:
Each compressor in the system has a set of dedicated
status indicators. The indicators will continuously show
the status of each compressor at all times.
a) Load Status
OFF – Not Loaded, Offload
a) Group Compressor Fault
OFF – All Compressors OK
Fast Flash – One or more compressors Not
Available, Shutdown Fault or Stopped
Slow Flash – One or more compressors Alarm
(Warning)
b) Insufficient Capacity Alarm (Warning)
On – Insufficient Capacity
c) Restricted Capacity Alarm (Warning)
Slow Flash – Restricted Capacity
Slow Flash – The compressor has been requested
to load but is not loaded (load or re-load delay
period)
23
Page 24
Information Displays
P00
#1 18:30
T2
3
4
1
1
2
P00
IRV-485
100 %
1
4
20 %
30 %
5
6
7
1
1
1
3
2
P00
1
102
98
80
psi
psi
psi
2
3
4
1
P00
#418:00
18 / 05 / 2006
A B C D
To view detailed information applicable to the
selected User menu display item press Enter.
To view detailed information applicable to the
selected User menu display item press Enter.
Real Time Clock:
Shows the next Pressure Schedule event.
1: The Current Active Table
2: Day (#1=Monday, #7=Sunday)
3: Time (24hr system)
4: Table
Primary Detected Pressure:
1: Active Table
2: Upper (Unload) Pressure Set Point
3: Lower (Load) Pressure Set Point
4: Minimum Pressure Alarm (Warning)
Sequence Rotation:
Items 2 and 3 show the day and time that the unit
will change to use the ‘Table’ shown in item 4.
Compressor Status:
1: Compressor Number
2: Priority Setting
3: Zone Allocation Setting
4: Compressor/Connection Type
5: Maximum Capacity % Setting
6: Minimum Capacity % Setting
7: Minimum Efficiency % Setting
Item values 6 and 7 are only shown if compressor
type is IRV-485 (variable capacity/speed).
Day of the week (#4: Thursday), the time of day
(18:00) and the date (18/05/2006) of the next automated
sequence rotation event.
The active ‘mode’ of operation
“ABCD” The current active rotation sequence assignment.
Manual Sequence Rotation:
The sequence assignment can be manually rotated at any
time. When viewing the ‘Sequence Rotation’ information
screen press Enter:
The manual rotation symbols will appear and
flash. Press Enter again to execute a manual rotation or
Escape to abandon the manual rotation.
Automated sequence rotation is not disrupted by
a manual rotation; the next scheduled automated
sequence rotation event will still occur.
Compressor Identification
Each compressor connected to the X8I will have a unique
assigned compressor identification number; starting at
compressor 1 increasing sequentially to the number of
compressors connected to the X8I.
24
Page 25
1234
A: 85%
Stop:
To stop the X8I press Stop.
The X8I will respond dependant on the setup of item ‘CF’
in menu S02:
Pressure regulation control is automatically transferred
back to each compressor. The compressor(s) will continue
to operate using the pressure settings programmed or set
in the individual compressor controller(s).
The X8I will hold each compressor in an offload state.
If the compressor is equipped with a main motor run-ontime function the compressor will run offload for a period
of time and then stop in to a ‘standby’ or ‘auto restart’
state.
Power Failure Auto-Restart
If the power failure auto-restart function is enabled
the X8I will automatically start, when power is restored
after a disruption or failure, if the X8I was in a ‘started’
state when the power disruption or failure occurred.
The X8I will not automatically restart if the X8I was in
a stopped state when the power disruption or failure
occurred.
Failure Mode
If the X8I experiences a disruption to normal control, or
an X8I shutdown fault occurs, pressure regulation control
is automatically transferred back to each compressor. The
compressor(s) will continue to operate using the pressure
settings programmed or set in the individual compressor
controller(s).
Reset
To reset an X8I Alarm (Warning) or Shutdown
condition press Reset.
The design of some air compressor control systems
may inhibit automatic transfer of pressure regulation
control to local operation mode. In this instance the
compressor will not continue production of compressed
air – consult the air compressor manual or your air
compressor supplier / specialist for details before
installing the IAX4.
Start:
To start the X8I press Start.
If the Prefill function is enabled, and system pressure is
below the set prefill pressure, the system will enter Prefill
mode for the set Prefill time.
Prefill
To manually skip the Prefill function, press and hold
Start for several seconds.
When Prefill is complete, if applicable, the X8I will enter
normal operating mode.
The X8I will operate in accordance with the parameters
and options set in the active ‘Table’.
Tables
Each compressor in the system must be started
(running or in a standby or auto restart condition) before
X8I control of the compressor can be established. The X8I
will not start a compressor that is in a stopped condition.
25
Page 26
SECTION 8 COMMISSIONING
When commissioning the X8I, carry out the following
procedures before attempting to start.
It is recommended that an authorized and trained
service technician perform the commissioning.
PHYSICAL CHECKS
1. Before applying power to the X8I, ensure the
power supply connections are correct and secure
and the operating voltage selector is set correctly
for the power supply voltage in use (115Vac or
230Vac (+-10%), 50/60Hz).
2. Open the front panel of the X8I and check the
location of the link wire(s) connected to the
“Voltage Selection” terminals of the power supply
PCB. If necessary, change the link wire locations to
those illustrated for the voltage in use.
See the section on Installation for more
information.
3. Switch on the power supply to the X8I.
4. The control program identification will be
displayed for a short period followed by the normal
operational user display.
PRESSURE DISPLAY
Check the displayed system pressure. If the pressure is
incorrect, or inaccurate, check the type and range of the
sensor and carry out the pressure sensor commissioning
and calibration procedure. If the display shows an error,
this will need to be corrected before continuing. See the
Operator’s Manual for troubleshooting and correcting the
fault/error condition.
X8I QUICK SETUP CONFIGURATION
Before successful basic operation can be established
specific parameters must be entered prior to startup.
Please refer to the X8I Quick Setup Manual for instruction
to accomplish this.
OPTIONAL FEATURES AND FUNCTIONS
Installation requirements may involve the
implementation of additional or optional functions and
features. Please refer to the appropriate Guide or Manual
as required.
26
Page 27
SECTION 9 SYSTEM CONFIGURATION
Access Code Accepted
Access Code Rejected
Access Code = 0032
P00
DISPLAY ITEM STRUCTURE
Operational system status and values are accessible from
the normal user display. To view status or values that are
not normally visible on the default screen, press UP or
DOWN. All standard user display items are viewable only
and cannot be adjusted. The standard user display items
are regarded as “Menu Page 00” items.
All adjustable value, parameter or option item displays
are grouped into “menu mode” lists. Items are assigned
to a list according to type and classification. Item lists
are identified by page number (or menu number). All
adjustable parameters and options are assigned to menu
mode pages “P01” or higher.
NORMAL OPERATIONAL DISPLAY MENU
PAGE P00
At controller initialization, all display elements and LED
indicators are switched on for three seconds and then the
normal operating display is shown. In normal operational
display mode, the main display will continuously show
the detected system pressure and the Item display will
show the first item of the “Page 00” menu. User menu
“items” can be selected using the UP or DOWN buttons at
any time. Pressing the ENTER button will lock any selected
item display and inhibit return to the default display.
When an item display is locked, the “lock key” symbol
will be shown. To unlock an item display, press UP or
DOWN to view an alternative item display or press RESET
or ESCAPE. No item values, options or parameters can
be adjusted in “Page P00”. If a fault condition occurs, the
fault code becomes the first list item and the display will
automatically jump to display the fault code. More than
one active fault code item can exist at any one time and
can be viewed by pressing UP or DOWN. The most recent
“active” fault will be at the top of the list.
ACCESSING THE X8I CONFIGURATION
SCREENS
Access Code:
Access to adjustable menu page items is restricted by
access code. To access menu mode pages press MENU (or
UP and DOWN together); an access code entry display is
shown and the first code character will flash.
Use UP(plus) or DOWN(minus) to adjust the value of the
first code character then press ENTER. The next code
character will flash; use UP or DOWN to adjust then press
ENTER. Repeat for all four code characters.
If the code number is less than 1000 then the first code
character will be 0(zero). To return to a previous code
character press ESCAPE. When all four code characters
have been set to an authorized code number press
ENTER. An invalid code will return the display to normal
operational mode; page ‘P00’.
Access Code Timeout:
When in menu mode, if no key activity is detected for
a period of time the access code is cancelled and the
display will automatically reset to the normal operational
display.
Menu Mode Navigation:
In menu mode the menu ‘page’ number will be
highlighted at the top of the display.
To select a menu ‘page’ press UP or DOWN. To enter the
highlighted menu ‘page’ press ENTER; the first item of the
menu ‘page’ will be highlighted. Press UP or DOWN to
scroll though the selected menu ‘page’ items.
27
Page 28
To select an item value or parameter for modification’
press ENTER; an adjustment screen for the item will be
displayed.
The value or option can now be modified by pressing
UP(Plus) or DOWN(Minus). To enter a modified value or
option in to memory press, ENTER.
Press ESCAPE at any time in menu mode to step
backwards one stage in the navigation process. Pressing
ESCAPE when the page number is flashing will exit menu
mode and return the display to normal operational mode.
All menu items have a unique reference consisting of the
menu page ID (a) and the menu page item number (b).
Each item in a menu also has a unique two alphanumeric
character code (c). All three references are visible at the
top of every menu item display.
Some menu items may consist of several individual
settings. Each setting of the menu item is also referenced
as a sub-item number. For example: P01-01.02 references
sub-item ‘02’ of menu item ‘01’ in menu page ‘P01’. Subitem settings, where applicable, are always displayed
together on the same ‘Item’ adjustment display screen.
Most menu items are single value or single option only
in which case the single item is referenced as sub-item
number ‘01’ (for example: P01-01.01).
Press and hold RESET for several seconds at any time
to immediately exit menu mode and return to the normal
operational display. Any value or option adjustment that
has not been confirmed and entered into memory will be
abandoned and the original setting maintained.
The X8I will retain an ‘access code’ for a short period
after menu exit allowing the menu structure to be reentered without the need to re-enter the access code
again. To immediately clear access code retention press
and hold RESET for several seconds.
A ‘locked’ symbol displayed with any item indicates
the item is locked and cannot be modified. This will occur
if the Item is view only (not adjustable) or in instances
where the item cannot be adjusted while the X8I is in an
operational state; stop the X8I first.
28
Page 29
USER LEVEL MENUS
1
TABLE #1
T01
TABLE #2 to #4 (as Table #1)
Pressure Schedule
P01
Prefill
P02
User Configuration
S01
Compressor Running Hours
C01
Compressor Maintenance
C02
Fault Log
E01
01 PH High Pressure Set Point
02 PL Low Pressure Set Point
03 Pm Minimum Pressure Alarm
04 SQ Sequence Algorithm
05 01 Compressor #1 Priority
to
12 08Compressor #8 Priority
01 Ct Real Time Clock Set
02 PS Pressure Schedule Enable
03 AR Auto Restart Enable
04 RP Rotation Interval
05 TS Default Table Select
06 BL Display Backlit Adjust
01 01 Schedule Setting #1
to
28 28 Schedule Setting #28
01 PF Prefill Function
02 PT Prefill Time
03 PP Prefill Pressure
04 01 Compressor #1
to
11 08Compressor #8
01 01Compressor #1 Running Hours
to
08 08 Compressor #8 Running Hours
01 01 Compressor #1 Maintenance
to
8 08Compressor #8 Maintenance
0
01 01Fault Log #1 (most recent)
to
15 15 Fault Log #15
29
Page 30
SERVICE LEVEL MENUS
Configuration
S02
Auxiliary Box Monitoring
S03
Sensor Calibration
S04
Compressor Configuration
C03
Diagnostic Menu 1
D01
Diagnostic Menu 2
D02
D05
High Level Menus
01 P> Pressure Units
02 NC Number Of Compressors
03 PM Maximum Pressure Alarm
04 CF Stop Control Function
05 TO Tolerance
06 DA Damping
07 PC Pressure Change Time
08 CA CAP Alarm Inhibit
09 MA Max Cap Restricted Alarm Inhibit
10 AI Auxiliary Input Function
11 AO Auxiliary Output Function
12 ER Error Log Reset
01 01 Auxiliary Box #1 Enable
02 02 Auxiliary Box #2 Enable
03 BT RS485 Timeout
01 D1 Digital Input #1 (Di 1)
to
08 D8 Digital Input #8 (Di 8)
09 R1 Output Relay #1 (R1)
to
14 R6 Output Relay #6 (R6)
15 A1 Analog Input #1 (Ai1)
16 A2 Analog Input #2 (Ai2)
17 A3 Analog Input #3 (Ai3)
18 Ao Analog Output (Ao)
01 SI Screen Invert
02 LT LED Panel Test
D03 and D04
Diagnostic menus D03 and D04 have no standard
function and are not shown.
01 1O Pressure Offset
02 1R Pressure Range
01 Compressor #1 Configuration
to 8 Compressor #8 Configuration
Diagnostic Menu 5
XPM Expansion Module C:5-8 Diagnostic Menu
only available when applicable EXP Expansion Box is
installed and registered (detected) by the X8I.
01 D1 Digital Input #1 (Di 1)
to
08 D8 Digital Input #8 (Di 8)
09 R1 Output Relay #1 (R1)
to
14 R6 Output Relay #6 (R6)
15 Ao Analog Output (Ao)
30
Page 31
X8I CONFIGURATION SCREENS
T01
08
02
03
04
04
PL
Pm
S
Q
04
psi
psi
1
98
0
ENER ( % )
01 PHpsi102
Tables
# = Table T01 to T04
T0# – PH High Pressure Set Point
The ‘upper’ or ‘unload’ pressure set point that will be
used when the ‘Table’ is active. The default setting for this
parameter is 102 PSI. The values for this parameter are:
The highest value for the High Pressure setpoint = PM
“Maximum Pressure Alarm” minus 2 times TO “Tolerance”.
If PM is set for 145 PSI and TO is set for 3.0 PSI, then the
highest value for the High Pressure setpoint would be 139
PSI.
The lowest value for the High Pressure setpoint = PL “Low
Pressure” setpoint plus TO “Tolerance”
If PL is set for 98 PSI and TO is set for 3.0 PSI, then the
lowest value for the High Pressure setpoint would be 101
PSI.
T0# - PL Low Pressure Set Point
If PL in Table 1 (T01) is set for 100 PSI and TO is set for 3.0
PSI, then the highest Minimum Pressure setpoint would
be 94 PSI.
T0# - SQ Sequence Strategy
The sequence control strategy mode that will be used
when the table is active. The default setting for this
parameter is ENER.
The values for this parameter are:
ENER – Energy Control Mode. The Rotation and
Control functionality of the ENER mode is to achieve
and maintain demand matched to optimum system
efficiency.
FILO – First In Last Out. The Rotation and Control
functionality of the FILO mode is the first compressor
loaded is the last compressor to be unloaded
EHR – Equal Hours Mode. The Rotation and Control
functionality of the EHR mode is to equalize the Run
Hours on all compressors
T0# - 01 Compressor #1 Priority
The ‘priority’ setting for compressor number 1 that will be
used when the table is active.
T0# - 02 Compressor #2 Priority
The ‘priority’ setting for compressor number 2 that will be
used when the table is active.
T0# - ‘n’ Compressor #’n’ Priority
The ‘priority’ setting for compressor number ’n’ that will be
used when the table is active.
The ‘lower’ or ‘load’ pressure set point that will be used
when the ‘Table’ is active. The default setting for this
parameter is 98 PSI. The values for this parameter are:
The highest value for the Low Pressure setpoint = PH
“High Pressure” setpoint minus TO “Tolerance”.
If PH is set for 102 PSI and TO is set for 3.0 PSI, then the
highest value for the Low Pressure setpoint would be 99
PSI.
The lowest value for the Low Pressure setpoint = Pm
“Minimum Pressure Alarm” setpoint plus 2 times TO
“Tolerance”
If Pm is set for 80 PSI and TO is set for 3.0 PSI, then the
lowest value for the Low Pressure setpoint would be 86
PSI...
T0# - Pm Minimum Pressure Alarm
The miniumum pressure ‘Warning’ or ‘Alarm’ level that will
be used when the ‘Table’ is active. The default setting for
this parameter is 80 PSI. The values for this parameter are:
The lowest Minimum Pressure Alarm setpoint = “The
minimum range of the pressure transducer used.“
The highest Minimum Pressure Alarm setpoint = “The
value from the Table PL – Low Pressure Setpoint” minus 2
times TO “Tolerance””
‘n’ = number of compressors in the system. 8 is the
maximum number of compressors for the X8I
Priority Settings:
: compressor(s) can be inhibited from use while a
table is active by selecting “X” priority. The compressor
will be held offload and will not be utilised under any
circumstances.
31
Page 32
P01
28
02
03
04
28
02
03
04
- . - - : - - - - -
- . - - : - - - - -
- . - - : - - - - -
- . - - : - - - - -
0101- . - - : - - - - -
Pressure Schedule
P02
11
02
03
04
08
PT
PP
01
MIN
psi
X
-
0
X
01PFX
A
! X
A
P01 – 01 to 28
The ‘Pressure Schedule’ items 01 to 28. The Pressure
Schedule consists of 28 individual settings that instruct
the X8I to change from one Table to another, or put
the system into Standby mode, dependant on time of
day and day of the week. The default setting for this
parameter is -. --:-- - - - . (Represents the Pressure Schedule
is disabled)
The values for this parameter are: (from left to right)
Day of the Week. The values for this parameter are:
“1” for Monday to “7” for Sunday (a specific day
of the week)
“8” for every working day of the week (every
day, Monday through Friday, excluding
Saturday and Sunday)
“9’” for every working day of the week (every
day, Monday through Sunday)
“–“ represents the Pressure Schedule is
disabled.
Hours (Military Time). The values for this parameter
are:
“00” to “23” the hours in a day
Prefill
P02 - PF Prefill Function
Determines the ‘Prefill’ strategy or function that will
be used at system startup. The default setting for this
parameter is A .
(Represents the pre-fill function is in Automatic
Mode)
The values for this parameter are:
= Prefill function OFF
“ ” = Prefill, Back-up Mode
Compressor(s) can be pre-selected as ‘Primary
Pre-fill’ compressor(s) or ‘Backup Pre-fill’
compressor(s). If a primary pre-fill compressor
experiences a shutdown, or is stopped, it is
replaced by a pre-defined backup compressor
and pre-fill continues.
= Prefill, Standard Mode
If one or more of the pre-defined pre-fill
compressors experiences a shutdown, or is
stopped, the pre-fill function is cancelled and
normal operation begins.
“–-“ represents the Pressure Schedule is
disabled.
Minutes. The values for this parameter are:
“0” to “59”. the minutes in the hour
“__“ represents the Pressure Schedule is
disabled.
Table / Standby mode selection. This instructs the system
to change from one ‘Table’ to another, or put the system
in to ‘Standby’ mode for the Pressure Schedule. The values
for this parameter are:
“T01”, “T02”, “T03” or “T04” for the 4 different
Tables
“–
– “ for Standby Mode
“ __ “ represents the Pressure Schedule is
disabled.
= Prefill, Automatic Mode
No Prefill compressor selection is necessary;
any selection set is ignored. The management
unit automatically selects compressor(s)
dynamically to achieve pressure in accordance
with the set Prefill time. If a compressor is
stopped, or shuts down, it is automatically
substituted with an alternative compressor.
P02 - PT Prefill Time
The Pre-fill Time Setpoint (in minutes) sets the maximum
time allowed for a system to start and load the
designated Compressor/s to increase system pressure
to normal operational levels. The default setting for this
parameter is – . (Represents the Prefill is disabled)
The values for this parameter are:
“–” the Pre-fill Time is Off
“1 to 120” the number of minutes
32
Page 33
P02 - PP Prefill Pressure
S01
06
08
08
08
BL
PS
A
R
RP
5
X
1 . 00:00
08Ct1 . 18:00
The Pressure Setpoint used by the X8I to determine if the
Pre-fill Function is required at start up. If pressure is at, or
above, this setting at system startup, the prefill function
will be abandoned immediately and normal pressure
control and sequence strategy will be implemented. This
setting is intended to inhibit ‘Prefill’ operation if pressure
is already at an acceptible level at system startup. The
default setting for this parameter is 0 PS.
The values for this parameter are:
0 to 232 (or the maximum scaled pressure
value used by the X8I if a different Pressure
Transducer range is used)” the PSI value for the
Pre-fill Pressure
P02 – 01 to ‘n’ Compressor 1 to ‘n’
‘n’ = number of compressors in the system. 8 is the
maximum number of compressors for the X8I
This parameter set the function of compressor 1 to ‘n’
during the ‘Prefill’ period. The default for this parameter is
. (Represents this compressor is not used by the
Prefill Function) The values for this parameter are:
” for this compressor will not be used by the Pre-
“
fill Function
” for this compressor will be used as a primary
“
compressor by the Pre-fill Function
“!” for this compressor will be used as an emergency
Backup compressor by the Pre-fill Function
These settings are applicable to Prefill – Standard
and Prefill - Back-up modes only. In Automatic mode
the system management unit dynamically utilizes
compressors as required.
Press and hold ‘Start’ for 5 seconds to manually skip
Prefill mode at start up.
Features and Functions
S01 - Ct Real Time Clock Set
Adjustment for the internal real time clock.
(Hours, Minutes, Date, Month, Year)
The ‘Day of the Week’ (1= Monday to 7=Sunday) is
automatically calculated and set in accordance with
the Day, Month and Year. The default setting for this
parameter is - --.--. (Represents the clock has not been
initialized))
The values for this parameter are:
“1” to “7” the ‘Day of the Week’ (1= Monday to
7=Sunday) which is automatically calculated and set
in accordance with the Day, Month and Year entered.
“00” to “23” the Hour for the Real Time Clock.
“0” to “59” the Minutes for the Real Time Clock.
“1” to “31” the Day for the Real Time Clock.
“1” to “12” the Month for the Real Time Clock.
“2005” to “2100” the Year for the Real Time Clock.
S01 - PS Pressure Schedule Enable
This parameter enables or disables the Pressure Schedule
function in the X8I. The default setting for this parameter
. (Represents the Pressure Schedule is disabled)
is
The values for this parameter are:
= inhibit Pressure Schedule
“ ” = enable Pressure Schedule
S01 - AR Auto Restart Enable
This parameter enables or disables X8I restart function
after a power loss. When enabled, after a power
disruption or failure, the X8I will automatically restart
when power is restored if the X8I was in an operational
‘Started’ state when the power loss or disruption
occurred. The X8I will not automatically restart if the X8I
was in a “Stopped” state when the power disruption or
failure occurred. The default setting for this parameter is
. (Represents the Auto Restart is enabled)
The values for this parameter are:
= inhibit Power Failure Auto Restart
“ ” = enable Power Failure Auto Restart
33
Page 34
S01 - RP Rotation Interval
S01 - TS Default Table Select
The X8I provides a Timed rotation event that can be
automatically triggered on a routine basis using a
pre-determined interval, a pre-determined time each
day, or a pre-determined day and time each week. The
default setting for this parameter is 1 00:00. (Represents a
rotation at Monday (1) at 00:00 hours)
The values for this parameter are:
“1” for Monday to “7” for Sunday (a specific day of the
week)
“8” for every working day of the week (every day,
Monday through Friday, excluding Saturday and
Sunday)
“9’” for every day of the week (every day, Monday
through Sunday)
“t” for an interval of time (more than 1 or more
rotations per 24 hours)
“–“ for disabling the Rotation Interval
If the parameter chosen above is “1” to “9”, you will need
to set the time for the rotation to occur. It is in a Military
Time format.
The values for this parameter are:
“00” to “23” the Hour
“0” to “59” the Minutes
“–“ the Rotation Interval is disabled.
This parameter determines the ‘Table’ that will be used
by default when ‘Pressure Schedule’ is not active and no
table is selected remotely on a digital input. The default
setting for this parameter is T01.
The values for this parameter are:
“T01” for Table T01
“T02” for Table T02
“T03” for Table T03
“T04” for Table T04
S01 - BL Display Backlight Adjust
This parameter adjusts the backlight level for the display.
The display will temporarily increase brightness by 2
levels when a key is pressed and return to normal setting
after a period of no keypad activity. The default display
backlight level has been set to enable a ‘continuous use
service life’ in excess of 90000 hours while providing good
readability in all ambient light conditions. LCD display
‘service life’ is defined as the time period before the
backlight reduces to 50% of initial brightness. Typically
the display will remain usable for a much longer period
of time. Adjusting the backlight to high levels will reduce
service life. The default setting for this parameter is 5. The
values for this parameter are:
“1” to “7” 1 being the least amount of backlight and 7
being the most.
If the parameter chosen above is “t”, you will need to
set the Interval Time. This sets the required number of
rotation events per day (1 to 96).
The values for this parameter are:
A value of 1 = rotate every 24 hours
A value of 2 = rotate every 12 hours
A value of 3 = rotate every 8 hours
A value of 4 = rotate every 6 hours
A value of 6 = rotate every 4 hours
A value of 8 = rotate every 3 hours
A value of 12 = rotate every 2 hours
A value of 24= rotate every 1 hours
A value of 48 = rotate every 30 minutes
A value of 72 = rotate every 20 minutes
A value of 96 = rotate every 15 minutes
“–“ the Rotation Interval is disabled.
34
Page 35
S02
12
02
03
04
ER
NC
PM
CF
psi
X
4
145
X
01P>
psi
S02 - CF Stop Control Function
This parameter determines if the X8I maintains control of
the compressors when the X8I is stopped. The default
Pressure Control; Tables
S02 - P> Pressure Units
This parameter selects the display and operating pressure
units: The default setting for this parameter is PSI. The
values for this parameter are:
“PSI”
“BAR”
“kPA”
S02 - NC Number of Compressors
This parameter sets the number of compressors
connected to, and controlled by, the X8I. This value
must be set to match the system at commissioning. The
default setting for this parameter is 4. The values for this
parameter are:
“1” for 1 compressor
“2” for 2 compressors
“3” for 3 compressors
“4” for 4 compressors
To
“8” for 8 compressors
S02 - PM Maximum Pressure Alarm
This parameter sets the High pressure ‘Fault’ level. This
value remains active at all times and is the same for all
‘Tables’. It should be set just below system pressure relief
value(s) and below the maximum system pressure rating
of all air system components. The default setting for this
parameter is 145. The values for this parameter are:
The highest value for the Maximum Pressure Alarm
setpoint = “The maximum range of the pressure
transducer used”
The lowest value for the Maximum Pressure Alarm
setpoint = “The highest value from any Table “PH
- Pressure High” Setpoint plus 2 times the “To
– Tolerance”
If PH in Table 1 (T01) is set for 100 PSI, and PH
in Table 2 (T02) is set for 110 and TO is set for
3.0 PSI, then the lowest Maximum Pressure
setpoint would be 116 PSI.
setting for this parameter is
Stop Control Function is disabled) The values for this
parameter are:
= Stop: return pressure control to the
compressors.
” = Standby: maintain control and continouosly
“
hold compressors ‘off load’.
S02 - TO Tolerance
This parameter sets the pressure control ‘Tolerance’ band
setting. The Tolerance Band setting is a pressure band
above and below the Load and Unload pressure band.
This accommodates for an instance of abrupt and/or
significant increase or decrease in demand without
compromise to optimal energy efficient control. The X8I
incorporates a Rate of Change algorithm in the Tolerance
Band to determine when a compressor should be Loaded
or Unloaded. The default setting for this parameter is 3.0
PSI (.2 Bar) The values for this parameter are:
“1.4 PSI (.1 Bar)” for the minimum Tolerance Band
“29.0 PSI (2 Bar)” for the maximum Tolerance Band
If air system storage is generous, the rate of the
•
pressure change is slow, and/or demand fluctuations
are insignificant and gradual, then the ‘Tolerance’
band can be decreased to improve pressure control
without compromise to optimum energy efficiency.
As the Tolerance Band is decreased, the Loading and
Unloading of compressors while in the band is more
rapid.
If air system storage is inadequate, the rate of the
•
pressure change is fast, and/or demand fluctuations
are significantly large, the ‘Tolerance’ band can be
increased to maintain optimum energy efficiency,
and reduce over-reaction, during such transition
periods. As the Tolerance Band is increased, the
Loading and Unloading of compressors while in the
band is less rapid.
S02 - DA Damping
This parameter sets the pressure control ‘Damping’
setting. Changing this parameter adjusts the time before
an additional compressor is loaded in accordance with
the urgency of the situation to increase air system
capacity further. The X8I has a dynamic reaction algorithm
that is pre-set by default to accommodate for the majority
of installation characteristics. If an increase or decrease in
the Tolerance band is insufficient, the reaction response
can be influenced by increasing or decreasing the
‘Damping’ factor. The default setting for this parameter is
1.0. The values for this parameter are: .1 TO 10
“.1”, the fastest Damping reaction time (10 times faster
than the default of 1.0)
“10.0”, the slowest Damping reaction time (10 times
slower than the default of 1.0).
35
. (Represents the
Page 36
If air system storage is generous and the rate of the
•
pressure change is slow to rise, then the ‘Damping’
can be increased to improve pressure control
without compromise to optimum energy efficiency.
As the Dampening value is increased, the Loading of
additional compressors is less rapid.
If air system storage is inadequate and the rate of
•
the pressure change is fast to fall, then the ‘Damping’
can be decreased to improve pressure control
without compromise to optimum energy efficiency.
As the Damping value is decreased, the Loading of
additional compressors is more rapid.
Damping also performs one more important function
that can arise in a system. When the system pressure
achieves stability in a position that may be outside of
the dead band but inside the tolerance band it will
be allowed to remain in this situation for a predefined
amount of time. This time limit depends on how far away
from the dead band the system pressure has stabilized.
This time limit is calculated as 30 min times the damping
constant at the top of the tolerance band and as 1
min times the damping constant at the bottom of the
tolerance band.
S02 - PC Pressure Change Time
This parameter adjusts the time that the X8I will
implement a smooth and controlled change from one
‘target’ pressure level to another when a table change is
made. The default setting for this parameter is 4 Min. The
values for this parameter are:
“1”, 1 minute between Table target pressure setpoint
changes
TO
“120”, 120 minutes between Table target pressure
setpoint changes.
S02 – CA Capacity Alarm Enable
This parameter sets the functionality of the Capacity
Alarm. The default setting for this parameter is
(Represents the Capacity Alarm is enabled) The values for
this parameter are:
= inhibit Capacity Alarm
= enable Capacity Alarm
When inhibited the Capacity Alarm panel indication
will still function; alarm code generation and remote
alarm indications are inhibited.
S02 – MA Restricted Cap. Alarm Enable
This parameter sets the functionality of the Restricted
Capacity Alarm. The default setting for this parameter is
. (Represents the Restricted Capacity Alarm is enabled)
The values for this parameter are:
= inhibit Restricted Capacity Alarm
= enable Restricted Capacity Alarm
When inhibited the Restricted Capacity Alarm panel
indication will still function; alarm code generation and
remote alarm indications are inhibited.
.
36
Page 37
S02 – AI Auxiliary Digital Input
S02
10.01
A
I
01:D1
NO
S02
11.01
A
O
01:AF
NO
S02 – AO Auxiliary Output Function
The function of the Auxiliary input.
01:DI Digital Input
No defined function but status (0=normal,
1=activated)
02:T1 Override > Table 1
03:T2 Override > Table 2
04:T3 Override > Table 3
05:T3 Override > Table 4
06:TS Override > Standby
07:AA Remote Alarm (always active)
08:AR Remote Alarm (active when unit running,
inhibited when unit stopped or in Standby)
09:TA Remote Trip (always active)
10:TR Remote Trip (active when unit running, inhibited
when unit stopped or in Standby)
11:SS Remote Start/Stop
NO (Normally Open)
The selected function is activated when the input is
closed circuit (input terminals are connected together by
remote volt-free contacts)
NC (Normally Closed)
The selected function is activated when the input is open
circuit (input terminals are open circuit)
The function of the Auxiliary output ‘volt-free’ relay
contacts.
01:AF Any Fault
Any Alarm (Warning), Shutdown (Trip) or Compressor Not
Available.
02:AT Any Trip
Any Shutdown (Trip) or Compressor Not Available.
03:CF Compressor Fault
Any compressor Alarm (Warning), Shutdown (Trip) or Not
Available
04:CA Compressor Alarm
Any compressor Alarm (Warning)
05:CT Compressor Trip
Any compressor Shutdown (Trip) or Not Available
06:SF System Fault
Any unit Alarm (Warning) or Shutdown (Trip)
07:ON System On
Unit Started and Active, including Pre-Fill period and
Standby mode (not active when unit stopped)
08:SA System Active
Unit Active, including Pre-Fill period (not active when unit
stopped or in standby mode)
09:LP Low Pressure Alarm
10:HP High Pressure Alarm
11:PO Pressure Control Override
Normal, or Pressure Schedule’ operation is being manually
overriddenThe function of the Auxiliary output ‘volt-free’
relay contacts.
S02 - ER Error Log Reset
This parameter clears and resets the ‘Error Log’. The
default setting for this parameter is
Error Log Reset is disabled)
The values for this parameter are:
” Error log reset is disabled
“
“ “ Error log reset enabled. Adjust the item setting to
‘ ’ and press ENTER. The display will return to the main
menu and all existing entries in the error log will be
permanently deleted.
37
. (Represents the
Page 38
S03
020302
BT
60
0101
sec
S03 – 01/02 I/O Box Monitoring
S04
021Rpsi232
011Opsi0
This parameter determines if the X8I will monitor the
selected I/O Box and display any ‘Fault’ detected on the
I/O Box inputs; dependant on I/O Box set-up. The default
setting for this parameter is
monitoring is disabled) The values for this parameter are:
= Disabled
= Enabled
Refer to I/O Box manual for details.
S03 – BT Communications Timeout
This parameter determines the Communication Broadcast
Timeout between the X8I and the I/O box. If the I/O Box
fails to communicate on the RS485 network within the
set ‘Communications Broadcast Timeout’ (BT), the X8I
will display an I/O Box RS485 communications Error.
The default setting for this parameter is 60 seconds. The
values for this parameter are:
“10 to 300” the number of seconds
. (Represents I/O Box
The pressure transducer must be vented to
atmosphere when setting the 0 or offset.
S04 - 1R Pressure Sensor Range
This parameter will be the maximum range of the
pressure transducer, 232 PSI, 16 BAR, or 1600 kPA. It can
also be used to create an ‘Offset’ if there is a difference in
the range value being displayed. The default setting for
this parameter is 232 PSI. The values for this parameter
are:
“232” when using the maximum value of the
pressure transducer range
A value greater than or less than 232 if the display
does not read 232.
The pressure transducer must have a known,
accurate pressure applied to it when changing
this value to a value other than 232.
Pressure Sensor Calibration Procedure:
a) Offset: Expose the sensor to atmosphere and adjust
the ‘offset’ setting (if necessary) until the detected
pressure display shows 0 PSI (0.0 BAR).
b) Range: Apply an accurately know pressure to the
pressure sensor and adjust the ‘Range’ setting until
the detected pressure display matches the applied
pressure. An applied pressure equal too, or greater
than, the nominal system working pressure is
recommended.
The detected pressure is displayed with the
calibration menu item and will change to match the new
calibration setting as the setting is adjusted.
The general operation of the selected I/O Box is also
monitored.
S04 - 1O Pressure Sensor Offset
This parameter will be the minimum value of the pressure
transducer, 0 PSI, 0 BAR, or 0 kPA. It can also be used to
create an ‘Offset’ if there is a difference in the zero value
being displayed. The default setting for this parameter is 0
PSI. The values for this parameter are:
“0” when using the minimum value of the pressure
transducer range
A value greater than or less than 0 if the display
does not read 0 or when using an Offset pressure
transducer (an example of an Offset pressure
transducer would be one where the range was minus
PSI (-25) to a positive PSI (200).
There is no need for the applied pressure to be static;
it can be dynamic and changing. This enables calibration
to be carried out on a fully operational system where
changing system pressure can be accurately verified from
another source.
Correct pressure sensor set-up and calibration
is critical for successful system operation. It is
recommended that pressure sensor calibration is
examined, and adjusted if necessary, annually or a predetermined routine periodic basis.
38
Page 39
C01
02
03
04
02
03
04
hrs
hrs
hrs
0
08
08
hrs
0
0
0
01010srh
Control - Equal Hours Run Mode
C02
02
03
04
02
08
08
03
04
0101
C01 – 01 to C01 – ‘n’ Run Hours’
‘n’ = number of compressors in the system. 8 is the
maximum number of compressors for the X8I
This parameter is set to match the running hours of
each compressor. Record of detected ‘running’ hours for
each compressor. The run hours value can be manually
adjusted, at any time, to match the running hours meter/
display value of each compressor. The default setting for
this parameter is 0 hours. The values for this parameter
are:
“0 to x” where x = the actual run hours for the
compressor
C02 – 01 to C02 – ‘n’ Compressor Maintenance
‘n’ = number of compressors in the system. 8 is the
maximum number of compressors for the X8I
This parameter is set for a compressor(s) that is
unavailable for use for a prelonged period for time due to
maintenance or repair. The compressor will not be utilised
under any circumtances; any Alarm (Warning) or Trip
(shutdown) fault will be ignored. The default setting
for this parameter is
available) The values for this parameter are:
= Remove compressor from operation
= Compressor can be utilised
. (Represents the compressor is
39
Page 40
C03
02
03
04
02
03
04
ir-PCB
0808ir-PCB
ir-PCB
ir-PCB
0101ir-PCB
Installation – Compressor Connections
ir-PCB:
C03
01.01
01
IR-PCB
100 %
1
1
+V=!
10 s
2
5
4
IRV-PCB:
C03
01.0101
1
IRV-PCB
100 %
10 s
10 s
+V=!
1
2
3
5
4
IR-485:
C03
01.01
01
1
IR-485
100 %
10 s
1
2
5
IR V- 485:
C03
01.01
01
1
IRV-485
100 %
10 s
60 %
50 %
1
2
5
6
7
C03 – 01 to C03 – ‘n’ Compressor Connection’
‘n’ = number of compressors in the system. 8 is the
maximum number of compressors for the X8I
This parameter sets the type, method of connection, and
the control functionality, of each compressor connected
to the X8I.
Dependant on the regulation and connection type
selected the set-up screen will change to show applicable
settings.
40
Page 41
X8I COMPRESSOR CONNECTIVITY AND
1
2
3
4
5
6
FUNCTIONAL SETTINGS
For ‘ir-PCB’ connectivity applications the voltage
detection function for the ‘ir-PCB’ Alarm (Warning) input
can be inverted.
Compressor Connectivity:
ir-PCB Fixed speed, load/unload; connected to X8I using
‘ir-PCB’ module using 6-wire method.
(0/100%) 0% or 100% regulation
IRV-PCB Variable Speed; connected to X8I using ‘ir-PCB’
module using the 7-wire ‘V’ terminal method.
(variable speed regulation)
IR-485
Fixed speed, load/unload; connected to X8I on
IR485 network.
(0/100%) 0% or 100% regulation
IRV-485
Variable Capacity/Speed; connected to X8I on
IR485 network.
(0 . . 100%) variable %Load regulation
Compressor Start Sequence Time:
Set to match the time that the compressor takes to
start it’s main motor and load. This time will typically be
equivalent to the compressors ‘Star/Delta’ time.
If unknown, the time can be established by experiment;
manually start the compressor, from a stopped condition,
and determin the time from pressing the start button
until the compressor loads and contributes capacity
output to the system.
This time is used by the unit for ‘staggered starting’ of
multiple compressors and other operational calculations.
An accurate time is important for successful unit
operation.
+V=! An Alarm (Warning) condition is generated if the ‘irPCB’ Alarm input detects a voltage between 12-250Vac/dc
(default).
0V=! An Alarm (Warning) condition is generated if the ‘irPCB’ Alarm input detects no voltage.
% Maximum Output Capacity
The maximum output capacity of each compressor must
be set as a percentage with reference to the highest
output capacity (the largest) compressor in the system.
The highest output capacity compressor must be
assigned with 100% capacity. Equal capacity (equal sized)
compressors should be assigned the same % capacity
value. Calculate the output capacity of compressor(s) that
are smaller than the largest in the system as a percentage
of the largest in the system.
For example:
Compressor 1 700 cfm 100%
Compressor 2 700 cfm 100%
Compressor 3 420 cfm 60%
Compressor 4 420 cfm 60 %
Compressor 5 350 cfm 50%
Compressor 6 175 cfm 25%
% Minimum Output Capacity
Only applicable for a variable output compressor
(IRV-485). Not shown for other types.
Compressor Run-On Stop Time:
This setting is only applicable to ‘IRV-PCB’
connectivity and is not displayed for other connectivity
options.
The time that the compressor main motor will continue to
run when the compressor is offload (main motor run-ontime).
If unknown, the time can be established by experiment;
start and load the compressor then arrange a condition
that will unload the compressor for a period of time.
Determine the time from the moment the compressor
unloads until the main motor stops and the compressor
enters a ‘Standby’ or ‘Auto Restart’ condition.
This time is used by the X8I for accurate recording
of ‘run hours’ (EHR mode), operational calculations and
other data recording applications. An accurate time is
important for successful X8I operation.
ir-PCB Alarm (Warning) Input:
Only applicable for ir-PCB connectivity. Not shown
for ‘485’ network types.
The minimum output capacity of a variable output
compressor must be set as a percentage of the
compressor’s maximum output scaled in accordance with the % maximum capacity output value. Minimum
output capacity is regarded as the output capacity at the
lowest possible speed (variable speed compressor) or the
minimal output achievable (stepping or other variable
regulation control).
For example 1:
For a variable speed compressor that has been assigned
a maximum capacity output percentage of 100%, and is
able to reduce speed to 30% of maximum speed:
Minimum Output Capacity = 30% (related to the largest
capacity)
Example Compressor 1 is a VSD:
Max CFM = 700
Max Output Capacity 700/700 = 100%
Min CFM = 210 (30% or 700 x .30)
Min Output Capacity 210/700 = 30% (or 30% x 100% =
30%)
41
Page 42
For example 2:
7
For a variable speed compressor that has been assigned a
maximum capacity output percentage of 60% (related to
the largest capacity), and is able to reduce speed to 30%
of maximum speed:
Example Compressor 4 is a VSD:
Max CFM = 420
Max Output Capacity 420/700 = 60%
Min CFM = 127 (30% or 420 x .30)
Min Output Capacity 127/700 = 18% (or 30% x 60% =
18%)
For example 3:
For a 3-step (0/50/100%) reciprocating compressor
that has been assigned a maximum capacity output
percentage of 60%, the minimum output capacity is the
half-output regulation step:
Minimum Output Capacity = 30%
% Minimum Efficiency
The intent of this feature is to always operate the smallest,
most efficient compressor and to prevent a variable
output capacity compressor operating at minimal
speed, or minimal output, for prolonged periods of time.
Generally a variable output compressor operating at
minimal capacity is less efficient than a smaller capacity
compressor that is able to achieve the same output at
higher, or maximum, output capacity.
Only applicable for a variable output compressor
(IRV-485). Not shown for other types.
The minimum efficiency point is regarded as the speed, or
step, below which another smaller capacity compressor
in the system could achieve the equivalent output at a
higher efficiency.
The percentage value is directly related, and scaled, to the
maximum and minimum output percentage values.
For example:
Example: A Compressor is a VSD: Max CFM = 420 (Largest
Compressor is 700 CFM)
Max Output Capacity 420/700 = 60%
Min CFM = 127 (30% or 420 x .30)
Min Output Capacity 127/700 = 18% (or 30% x 60% =
18%)
If another compressor in the system is able to provide
40% of the compressor’s full speed output more
efficiently, set the % Minimum Efficiency value to 24%
(40% x 60%). This percentage value represents 40% of
the full speed output of the compressor scaled to System
capacity.
When the compressor is detected as operating below the
% Minimum Efficiency value for a period of time the X8I
will immediately re-evaluate utilization and re-configure,
if possible, to utilize a the smaller capacity, more efficient
compressor, or combination of compressors. This process
is automatic and executed dynamically in accordance
with prevailing operational conditions at the time. The
ENER control mode algorithms will eventually conclude
the best compressor fit without this parameter; the %
Minimum Efficiency input will speed up this process.
42
Page 43
E01
02
03
04
- : - - - . - -
- : - - - . - -
- : - - - . - -
01E : ERR . 01
15
- : - - - . - -
E01
01.01
E: ERR.01
16/05/200614:25
1
To return to the main error log menu screen press the
E01
01.01
1234
ESCAPE button.
To view the second information screen press ENTER.
button
E01 – 01 to 15
The error log is presented in chronological order. Entry 01
is the most recent, whereas entry 15 is the oldest. Each
error log item will show the error code. To view details for
the selected error log item, press the ENTER button.
The first error information display shows:
The error code • Error code symbols (if applicable)
•
The date the error occurred
•
The time the error occurred
•
The active operational functions of the X8I at the
•
time the error occurred; (see: X8I Status Display for
Icons)
The operational status of each compressor, at the time the
error occurred, is displayed symbolically. See Compressor
Status Displays for Icons.
To return to the first information screen press ENTER
button or the ESCAPE.button. To return to the main error
log menu screen press the ESCAPE button.
43
Page 44
D01 Diagnostics - Controller
D01
02
03
04
D2
D3
D4
0
1
2
01D10
18Ao00.4Am
D02
02LT0
01SI
0
0
Relay Outputs:
Each relay output can be energized and de-energized
manually by selecting the item. Use Up(plus) and
Down(minus) to adjust and Enter.
Analog Inputs:
The Analog Inputs will alternate between the detected
value and the electrical measurement on the controller
input terminals. An independent measuring device can
be used to check the displayed electrical measurement.
The X8I is equipped with comprehensive diagnostic
functions. Each input can be examined individually and
each output can be manually activated or manipulated
individually.
The analog output can be manually adjusted. Use
Up(plus) and Down(Minus) to adjust and Enter. The
output will return to normal operational value upon
menu exit.
The analog output is utilized on the Terminal PCB to
switch the ir-PCB V outputs. Set the analog output to the
following to switch each ‘V’ output as required.
The pulse signal from an ‘ir-PCB’ is 0V to 24VDC at
50/60Hz. A typical DC voltage meter, or multimeter, will
detect this as 12VDC +-4V.
SI: Screen Invert
LT: LED Panel Test
0 = on test
1 = all on
2 = control test
D03 and D04
Diagnostic menus D03 and D04 have no standard
function and are not shown.
44
Page 45
D05
02
03
04
D2
D3
D4
0
1
2
01 D1
0
15
A
o
mA
4.00
Diagnostics: XPM Expansion Module C:5-8
o only available when applicable EXP Expansion Box
is installed and registered (detected) by the X8I.
X8I Controller Diagnostics:
D1 Digital Input 1
D2 Digital Input 2 ON
D3 Digital Input 3
D4 Digital Input 4
Relay Outputs:
Each relay output can be energized and de-energized
manually by selecting the item. Use Up(plus) and
Down(minus) to adjust and Enter.
Ao: Analog Output:
The analog output can be manually adjusted. Press
Up(plus) and Down(Minus) to adjust and Enter. The
output will return to normal operational value upon
menu exit.
The analog output is utilized on the Terminal PCB to
switch the ir-PCB V outputs. Set the analog output to the
following to switch each ‘V’ output as required.
X8I COMPRESSOR FAULT INDICATIONS,
TYPES, AND CODES:
In the event of a unit or system “fault” the X8I will display
a fault code. The fault code becomes an item in the user
operational display menu. If more than one “active” fault
occurs, each will be displayed as a separate item in the
operational user menu. Press UP or DOWN to view all
active fault codes or to view the normal status display.
Alarm (Warning)
Shutdown (Trip)
Fault codes are separated into unit faults (ERR) and
system alarms (warning) (SYS).
Compressor Alarm (Warning) conditions are automatically
reset when the condition has been resolved and reset on
the compressor.
Compressor Not Available (Shutdown, Trip) conditions are
automatically reset when the condition has been resolved
and reset on the compressor; and the compressor has
been restarted.
Compressor fault conditions are displayed by the
compressor indicators and in the user menu status screen.
Compressor fault conditions are not regarded as X8I unit
fault conditions.
Compressor Status Sysmbols and Comressor Status
Indicators
Fault Codes
Fault codes are separated in to unit faults ‘ERR’ and system
Alarms (Warning) ‘
ERR: Unit faults are errors with the X8I controller itself and
are all conditions that prevent normal operation from
continuing.
SYS: System faults are items that arise from conditions
external to the X8I controller; the X8I itself continues to
function correctly.
There are two types of Fault condition:
Alarm (Warning):
SYS’.
Trip (Shutdown):
The Fault LED will ‘fast flash’ to indicate a Trip (Shutdown)
condition. A Trip (Shutdown) condition will stop normal
operation of the X8I. Pressure regulation control will
automatically revert to the individual compressors that
will continue to operate using the pressure settings for
their own control systems. All Trip (Shutdown) conditions
are registered in the X8I Error Log. All Trip (Shutdown)
conditions must be manually reset.
Fault Codes:
Each individual fault has a unique numeric code.
ERR.01 Pressure Sensor Fault
The signal from the control pressure sensor is out-ofrange (<3.5mA or >21.8mA).
ERR.04 Internal 24V Fault
The 24VDC power supply, internal to the unit’s controller,
is below 19.2V (internal controller fault)
ERR.05 Emergency Stop
The wire link between terminals ‘+C’ and ‘C1’ of the unit’s
controller is open circuit. These terminals are permanently
connected together on the X8I Terminal PCB: this error
will never occur in normal operational circumstances.
ERR.06 Real Time Clock Error
The Real Time Clock device, internal to the unit’s
controller, has failed.
ERR.07 XPM-LED Module Error
Data communications with the internal XPM-LED (Status
LED Display) module have been disrupted or lost.
ERR.12 ir-PCB Expansion Module C5-8
Data communications with the external ir-PCB Expansion
module ‘C:5-8’ have been disrupted or lost.
ERR.13 ir-PCB Expansion Module C5-8
Short Circuit condition detected on external ir-PCB
Expansion module ‘C:5-8’.
The Fault LED will ‘slow flash’ to indicate an Alarm
(Warning) condition. An Alarm (Warning) indicates that
the X8I is continuing with normal operation but user
attention is required. All Alarm (Warning) conditions are
registered in the X8I Error Log. All Alarm (Warning)
SYS.01 Excess Pressure (PM)
Pressure has exceeded the set Maximum Pressure Limit.
SYS.02 Min Pressure (Pm)
Pressure has fallen below the set Minimum Pressure Limit
(see ‘Tables’)
SYS.04 Capacity Alarm (Warning)
Insufficient Capacity; all available compressors are loaded
and pressure is still decreasing.
46
Page 47
SYS.05 Remote Alarm (Warning)
Auxiliary Input Function ‘AA’
The auxiliary Input is set for ‘Alarm (always active)’
function and is in a Fault condition.
SYS.06 Remote Alarm (Warning)
Auxiliary Input Function ‘AR’
The auxiliary Input is set for ‘Alarm (active when unit
running)’ function and is in a Fault condition.
SYS.07 Remote Trip (Shutdown)
Auxiliary Input Function ‘TA’
The auxiliary Input is set for ‘Trip/Shutdown (always
active)’ function and is in a Fault condition.
SYS.08 Remote Trip (Shutdown)
Auxiliary Input Function ‘TR’
The auxiliary Input is set for ‘Trip/Shutdown (active when
unit is running)’ function and is in a Fault condition.
Internal Controller Fault ‘E’ Codes:
‘E’ code errors are specific to the unit’s ‘internal to
controller’ digital logic circuits and will only occur in the
most exceptional of circumstances.
The controller’s main power supply must be removed and
re-applied to reset this condition.
E5001: Internal memory failure
The unit’s controller has detected disruption to the
internal permanent application memory storage (FLASH).
The integrity of the FLASH memory contents is suspect.
Re-load the main application software in the first
instance; re-new the controller if the condition persists.
The controller’s main power supply must be removed and
re-applied to reset this condition.
To Display the Software Version:
Press and hold Reset then press Escape.
The user menu display item will show the software
version ID (example: “E01”).Fault Codes:
All ‘E’ code conditions are Trip (Shutdown) type faults.
The ‘Fault’ (red) LED will ‘fast flash’ and the condition is
registered in the Error Log. If an ‘E’ code fault condition
persists, consult your product supplier for advise or renew
the unit’s controller.
E0836: PLL Unlock; Internal failure or excessively high
external electrical interference detected.
The main timing circuit (processor clock) has been
disrupted and the processor is running on an ‘internal
to chip’ back-up clock. The back-up clock is intended to
keep the processor running, at a much slower processing
speed, to enable emergency actions to be taken. The
controller is unable to continue running the main
software application in this condition.
The unit will Shutdown; compressors will continue to
operate using local pressure regulation.
The controller’s main power supply must be removed and
re-applied to reset this condition.
E0866: Controller internal power supply fault
The low voltage logic processing power supply, internal
to the unit’s controller, is below minimum operational
levels; internal to controller fault. Renew the controller if
this fault condition persists. The Trip must be manually
reset from the keypad.
E5000: Internal memory map error
The unit’s controller has detected disruption to the
internal operational memory storage (RAM). The integrity
of the RAM memory contents are suspect; the controller
must be reset to clear and re-map the memory. Renew
the controller if this fault condition persists.
47
Page 48
20mm
5mm
IEC
6
2
1
4
7
5
3
Mounting Dimensions:
27mm
286mm
27mm
188mm
8mm Ø
SECTION 11 — PARTS LIST
-
-
ItemPart No.
Description
ItemPart No.Description
-42659250X8I, Kit
-23242159Unit, X8I
-80444086Manual, User CD
142659268Unit, Controller
242659284Unit, XPM-PSU24
3 39265913Unit, XPM-TAC24
439265905PCB, Terminal
542659276Unit, XPM-LED
638036703Gland, Set - Pg13.5
739265939Sensor, Pressure
4-20mA, 232psi (16bar)
ItemPart No.Description
1039265962IEC Fuse T1.0A
1039265970IEC Fuse T1.6A
1039265988IEC Fuse T1.6A
TECHNICAL DATA
22194773XI Installation Kit
80444078Quick Setup Guide
Dimensions 13.4” x 9.45” x 6.0”
340mm x 241mm x 152mm
Weight 16.5lb (7.5kg)
Mounting wall, 4 x screw fixings
Enclosure IP65, NEMA 4
Supply 230Vac +/- 10%
115Vac +/- 10%
Power 100VA
Temperature 32°F to 115°F (0°C to 46°C)
Humidity 95% RH, non-condensing
48
Page 49
SECTION 12 — DIAGRAMS
N L E
T1-46-321-R6-DiC-CG
A
m
0
2
4
C031
C032
XPM-LED
X02
1
2
2
#
5
8
4
S
R
5
8
7
i4
0
lt
u
X
M
C09
C010
N L E
230Vac 10%
115Vac 10%
6
0
X
8
0
X
5
8
4
M
P
X
1
0
X
1
1
A-GND
Ao
9
0
X
1
L
2
L
1
#
5
8
4
S
R
1
L
2
L
c
a
V
4
2
2
2
X8I
6
3
5
3
4
3
3
3
2
3
1
3
0
3
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
2
9
1
4
V
8
1
7
1
6
1
5
1
4
1
3
1
3
V
2
1
1
1
0
1
9
8
0
X
7
0
X
6
0
X
5
0
X
4
0
X
3
0
X
2
0
X
8
7
2
V
6
5
4
3
1
0
X
2
1
1
V
C029
C028
Terminal PCB
C03
C04
C05
C06
C07
C08
C09
C010
C011
C012
C013
C014
C015
C016
C017
C018
C019
C020
C021
C022
C023
C024
C025
C026
C027
C028
C029
C030
C033
C034
C031
C032
c
a
V
4
2
D
N
G
C01
4
3
SEQ
2
GND
1
Q
E
S
-
+
D
N
G
C034
24Vac
SEQ
R-SEQ
C06
C08
C07
C010
C09
C04
C03
C019
C024
10k
150k
150k
C012
10k
C023
C027
C018
10k
C022
C026
-
4-20mA
+
R-V4
R-V3
R-V2
R-V1
C016
10k
C021
C025
C015
C03
C04
C05
C06
C07
C08
C019
C020
C021
C022
C023
C024
C025
C026
C027
C011
5
0
X
+VDC
Ai1
+VDC
Ai2
+VDC
Ai3
C+
4
0
X
1
2
3
4
5
6
7
8
R5
2
0
X
R6
C012
C01/3
C01/4
C013
R1
R2
3
R3
0
X
C014
C015
C016
C017
R4
C018
0VDC
2
4
0
2
X
C
A
0Vac - earthed
T
M
1
0
P
X
X
4
2
U
S
X02
P
-
24VDC
M
1
P
X
2
2
24Vac
21
X03
X01
24Vac
1
X03
24VDC
1
0Vac
24Vac
2
XPM485
1
2
XPM-LED
X02
L1
1
2
L2
X03
2
1
L1
1
2
L2
Wiring Diagram
49
Page 50
Connection Diagram
Terminal PCB
6
3
5
3
4
3
3
3
2
3
1
3
8
0
X
7
0
X
115V 'UL' @ 5A maximum.
R1
Auxiliary Output #1
Auxiliary Input #1
D1
330ft (100m) max
0
3
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
2
9
1
4
V
8
1
7
1
6
1
5
1
4
1
3
1
3
V
2
1
1
1
0
1
9
8
7
2
V
6
5
4
3
2
1
1
V
L2
6
L
0
X
5
0
X
4
0
X
3
0
X
2
0
X
1
0
X
1
L2
L
1
-
Ai1
+20VDC
Ready/Run
Di5
Alarm/Serv.
Ai2
-
GND
LOAD
R5
SEQ
R1
VFD
V4
+20VDC
Ready/Run
Di4
Alarm/Serv.
Di8
-
GND
LOAD
R4
SEQ
R1
VFD
V3
+20VDC
Di3
Ready/Run
Alarm/Serv.
Di7
-
GND
LOAD
R3
SEQ
R1
VFD
V2
+20VDC
Ready/Run
Di2
Alarm/Serv.
Di6
-
GND
LOAD
R2
SEQ
R1
VFD
V1
Multi485
System
Pressure
330ft (100m) max
+
6
5
4
B
4
C
3
P
i-
2
1
6
5
3
B
4
C
3
P
i-
2
1
6
5
2
B
4
C
3
P
i-
2
1
6
5
1
B
4
C
3
P
i-
2
1
330ft (100m) max
V
IRV-PCB 7-core
330ft (100m) max
V
IRV-PCB 7-core
330ft (100m) max
V
IRV-PCB 7-core
330ft (100m) max
V
IRV-PCB 7-core
IR-PCB 6-core
IR-PCB 6-core
IR-PCB 6-core
IR-PCB 6-core
-
+
4-20mA
L2
L
1
4
V
3
V
2
V
1
V
50
Page 51
XPM-TAC24
230V
115V
24Vac/1
isolated
24Vac/2
earthed
EE
L
N
N L E
BLUE
BROWN
RED
GREEN
VIOLET
WHITE
ORANGE
BLACK
FH1
FH2FH3FH4
FH5
1
VOLTAGE SELECT
2 3 4
X04
212
X03
X02
X01
T3.15A
T1.6A
T1.6A
T1.0A
T1.0A
1 2 3 4
115V +-10%
230V +-10%
1 2 3 4
IEC
5x20mm
51
Page 52
X8I COMMISSIONING FORM
#1
#2
psi
VA
Hz
cfm
kW
VA
Hz
kW
#3
#4
VA
Hz
kW
VA
Hz
kW
psi
cfm
psi
cfm
psi
cfm
#5
#6
VA
Hz
kW
VA
Hz
kW
#7
#8
VA
Hz
kW
VA
Hz
kW
psi
cfm
psi
cfm
psi
cfm
psi
cfm
CustomerContactCustomer Ref:
PhoneInternal Ref:
Installation/SiteCommission Date
SoftwareSer No.Commission Engineer
Comp #1 Manufacturer
Comp #1 Model/Type
Comp #1 Working Pressurebar/psi
Comp #1 Full Load Capacitycfm
Comp #2 Manufacturer
Comp #2 Model/Type
Comp #2 Working Pressurebar/psi
Comp #2 Full Load Capacitycfm
Comp #3 Manufacturer
Comp #3 Model/Type
Comp #3 Working Pressurebar/psi
Comp #3 Full Load Capacitycfm
Comp #4 Manufacturer
Comp #4 Model/Type
Comp #4 Working Pressurebar/psi
Comp #4 Full Load Capacitycfm
Comp #5 Manufacturer
Comp #5 Model/Type
Comp #5 Working Pressurebar/psi
Comp #5 Full Load Capacitycfm
Comp #6 Manufacturer
Comp #6 Model/Type
Comp #6 Working Pressurebar/psi
Comp #6 Full Load Capacitycfm
Comp #7 Manufacturer
Comp #7 Model/Type
Comp #7 Working Pressurebar/psi
Comp #7 Full Load Capacitycfm
Comp #8 Manufacturer
Comp #8 Model/Type
Comp #8 Working Pressurebar/psi
Comp #8 Full Load Capacitycfm