Ingersoll Rand X8I User Manual

Page 1
Before installing or starting this unit for the first time, this manual should be studied carefully to obtain a working knowledge of the unit and/or the duties to be performed while operating and maintaining the unit. RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the unit at all times.
More Than Air Answers.
Online answers: http://www.air.irco.com
Ingersoll Rand
System Automation
X8I MODBUS RTU
User’s Manual
C.C.N. : 80444987 REV. B DATE: JUNE 2009
Page 2
SECTION 1 – TABLE OF CONTENTS
SECTION 1 – TABLE OF CONTENTS .................................................................................................................... 2
SECTION 2 - INTRODUCTION ................................................................................................................................ 3
SECTION 3 - SAFETY PRECAUTIONS .................................................................................................................. 3
SECTION 4 - MODBUS RTU ................................................................................................................................... 5
MODBUS TABLE(S) ............................................................................................................................................. 5
MODBUS RTU ...................................................................................................................................................... 5 U
COMMUNICATION LINK ...................................................................................................................................... 5
RS485 SERIAL DATA FORMAT ........................................................................................................................... 5
MESSAGE DATA FORMAT ................................................................................................................................. 5
SLAVE RESPONSE TIMEOUT ............................................................................................................................ 7
MESSAGE ANSWER FROM SLAVE TO MASTER .............................................................................................. 7
EXCEPTION RESPONSE .................................................................................................................................... 8
TROUBLESHOOTING ......................................................................................................................................... 8
SECTION 5 - MODBUS TABLE DESCRIPTION ..................................................................................................... 9
TABLE ITEM FORMAT ......................................................................................................................................... 9
NAME AND FUNCTION ....................................................................................................................................... 9
CODING ............................................................................................................................................................... 9
MENU REFERENCE .......................................................................................................................................... 10
‘ADV’ ADVISE FUNCTION ................................................................................................................................. 10
‘ADV’ ADVISE FUNCTION SINGLE ITEM FORMAT OPTION ........................................................................ 10
‘CMD’ COMMAND FUNCTION ........................................................................................................................... 12
‘GET’ FUNCTION ............................................................................................................................................... 13
‘SET’ FUNCTION ................................................................................................................................................ 13
DATA CODING DEFINITIONS: .......................................................................................................................... 14
DATA TYPES ...................................................................................................................................................... 14
DATA UNITS ....................................................................................................................................................... 15
SECTION 6 - X-SERIES AIR SYSTEM .................................................................................................................. 17
SMG BOX ........................................................................................................................................................... 18
GENERAL X-SERIES SYSTEM COMPONENTS .............................................................................................. 18
X-SERIES NETWORK ADDRESSES................................................................................................................. 19
COMMUNICATION LINK .................................................................................................................................... 19
MODBUS TIMING............................................................................................................................................... 19
RS485 MODBUS SERIAL DATA FORMAT ........................................................................................................ 19
SECTION 7 – X8I MODBUS RTU DEFINITIONS .................................................................................................. 20
2
Page 3
SECTION 2 - INTRODUCTION
System MODBUS Gateway (SMG Box) communication is RS485, RTU, Master-Slave configuration. The SMG Box acts as a transparent interface to enable a remote ‘master’ device to be able to communicate with the X-Series Units and th e Intellisys Controllers via the ir485 network ‘slave’ device(s). The MODBUS RTU data construction and formatting for a ‘master’ device is the subject of this document. This information is intended for a systems integrator to facilitate set-up of a ‘master’ device in order to communicate successfully with the X-Series Units and the Intellisys Controllers through a SMG Box.
SECTION 3 - SAFETY PRECAUTIONS
WARNING :
!
WARNING :
WARNING :
!
WARNING :
Before installing or operating the SYSTEM MODBUS GATEWAY (SMG) BOX, take time to carefully read all the instructions contained in this manual, all compressor manuals, and all manuals of any other peripheral devices that may be installed or connected to the unit.
Electricity and compressed air have the potential to cause severe personal injury or property damage.
The operator should use common sense and good working practices while operating and maintaining this system. All applicable codes should be strictly adhered to.
Maintenance must be performed by adequately qualified personnel that are equipped with the proper tools.
INSTALLATION
Installation work must only be carried out by a competent person under qualified supervision.
A fused isolation switch must be fitted between the main power supply and the SYSTEM MODBUS GATEWAY (SMG) BOX.
The SYSTEM MODBUS GATEWAY (SMG) BOX should be mounted in such a location as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times.
If raised platforms are required to provide access to the SYSTEM MODBUS GATEWAY (SMG) BOX, they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides.
Risk of Danger
Risk of Electric Shock
Risk of High Pressure
Consult Manual
OPERATION
The SYSTEM MODBUS GATEWAY (SMG) BOX must only be operated by competent personnel under qualified supervision.
Never remove or tamper with safety devices, guards or insulation materials fitted to the SYSTEM MODBUS GATEWAY (SMG) BOX.
The SYSTEM MODBUS GATEWAY (SMG) BOX must only be operated at the supply voltage and frequency for which it is designed.
When main power is switched on, lethal voltages are present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit.
Do not open access panels or touch electrical components while voltage is applied unless it is necessary for measurements, tests or adjustments. Such work should be carried out only by a qualified electrician equipped with the correct tools and wearing appropriate protection against electrical hazards.
All air compressors and/or other equipment connected to the unit should have a warning sign attached stating “THIS UNIT MAY START WITHOUT WARNING” next to the display panel.
If an air compressor and/or other equipment connected to the unit is to be started remotely, attach two warning signs to the equipment stating “THIS UNIT CAN BE STARTED REMOTELY”. Attach one sign in a prominent location on the outside of the equipment, and the other sign inside the equipment control compartment.
3
Page 4
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must only be carried out by competent personnel under qualified supervision.
If replacement parts are required, use only genuine parts from the original equipment manufacturer, or an alternative approved source.
Carry out the following operations before opening or removing any access panels or carrying out any work on the SYSTEM MODBUS GATEWAY (SMG) BOX:
i. Isolate the SYSTEM MODBUS
GATEWAY (SMG) BOX from the main electrical power supply. Lock the isolator in the “OFF” position and remove the fuses.
ii. Attach labels to the isolator
switch and to the unit stating “WORK IN PROGRESS - DO NOT APPLY VOLTAGE”. Do not switch on electrical power or attempt to start the SYSTEM MODBUS GATEWAY (SMG) BOX if such a warning label is attached.
Make sure that all instructions concerning operation and maintenance are strictly followed and that the complete unit, with all accessories and safety devices, is kept in good working order.
The accuracy of sensor devices must be checked on a regular basis. They must be calibrated when acceptable tolerances are exceeded. Always ensure any pressure within the compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device.
The SYSTEM MODBUS GATEWAY (SMG) BOX must only be cleaned with a damp cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis.
Do not paint the control faceplate or obscure any indicators, controls, instructions or warnings
4
Page 5
SECTION 4 - MODBUS RTU
MODBUS TABLE(S)
This document discusses generic MODBUS communications and how to implement the software specific ‘MODBUS Table’ information. MODBUS communication formatting may differ from controller to controller and you may require more than one ‘MODBUS Table’.
Always check the software variant identification and version number for a controller or unit with the variant and version of the ‘MODBUS Table’ supplied. In some instances the information contained in a ‘MODBUS Table’ may not be ap plicable to a controller or unit installed with the same software variant but a different version number.
MODBUS RTU
MODBUS RTU (Remote Terminal Unit) is a master-slave type protocol. An X-Series Automation System Controller or Intellisys Controller functions as the slave device. Information requests or commands are communicated from master to slave only through a System Modbus Gateway Box (SMG). The SMG Box will always respond to communications from a remote master device in accordance with the MODBUS RTU protocol standard.
The MODBUS protocol is used to communicate with personal computers (PC), Programmable Logic Controllers (PLC’s), or Distributed Control Systems (DCS) over the Network port. The SMG Box only responds to three MODBUS commands, Read Holding Register 03 (03 Hex), Preset Single Register 06 (06 Hex), and Preset Multip le Registers command 16 (10 Hex) (See Modicon MODBUS Protocol Reference Guide, PI-MBUS-300 Rev. J, for more details on MODBUS).
COMMUNICATION LINK
MODBUS is implemented using a two-wire RS485 industry standard communications link operating in master-slave mode.
Polarity of the two RS485 wires (L1+ and L2-) is important; reversal will disrupt communications.
RS485 SERIAL DATA FORMAT
The RS485 MODBUS port is a 2-wire operating with an asynchronous serial data format: 8 data bits / no parity / 1 stop - (8,N, 1) - transmitted at 9600 baud.
MESSAGE DATA FORMAT
The bytes of the MODBUS RTU message must be sent in one message package. The RTU protocol allows for a maximum pause of 1.5 byte-times between 2 consecutive bytes of a message.
A pause longer than 1.5 byte-times will render the message invalid and it will be ignored.
Message data format is dependant on function and will consist of a combination of the following elements:
1) Destination address (slave network address)
2) Function Code
3) Data start address (slave register start address)
4) Number of registers, number of bytes of data
5) Message data
6) CRC checksum
Message Destination Address
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
The ‘destination address’ must be correct for the ‘slave’ controller device for which the message is inten ded. An address can be from 01Hex to EFHex. The SMG Box is transparent and addresses must be for the destination ‘slave’ controller or unit. Each controller or unit must be set with a unique address.
5
Page 6
Message Function Codes
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
The message function code defines the required data processing operation of the slave controller. Although several types of message function codes are defined by the MODBUS standard, only the message function code types working directl y with registers are implemented on controller units:
03H Read Holding Register(s) – Get (Get Data) or Adv (Advise Data) (X-Series) and Read (Intellisys) 06H Preset Single Register - Write (Intellisys Only) 10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series only)
Any other message function code type will result in an EXCEPTION response.
Message Data Start Address
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
The message data start address (16bit word) designates the initial register address location in the contr oller from which the data is processed. Start address information is contained in the ‘MODBUS Table’.
Note: high-byte transmitted first followed by low-byte.
Message Data
The message data content depends on the message function code type.
03H Read Holding Register(s) – Get (Get Data), Adv (Advise Data) (X-Series) or Read (Intellisys)
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
Slave address + function code ’03 Hex’ + start address of registers in slave memory + 16bit integer value that determines the size (in 16bit ‘word’ registers) of the message data being requested (00 02 = 2 registers of data). This is the number of 16bit registers to read. A maximum of 32 registers can be read at one time. This information is contained in the ‘MODBUS Table’.
06H Preset Single Register - Write (Intellisys Only)
Slave
Address
Function
Code
Start
Address
DATA
byte 0 byte 1
CRC Check
Sum
01 06 00 6F 00 5F FE BC
Slave address + function code ’06 Hex’ + start address of register(s) in slave memory to be set then the ‘data’ itself. This information is contained in the ‘MODBUS Table’.
10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series only)
Slave
Address
Function
Code
Start
Address
Number of
Registers To
Be Set
Number of
Bytes of
Data
DATA
1st Register
byte 0 byte 1
DATA 2nd Register byte 2 byte 3
CRC Check
Sum
01 10 40 18 00 02 04 00 00 1B 5F 88 0E
Slave address + function code ’10 Hex’ + start address of register(s) in slave memory to be set + 16bit (integer valve of the number of registers to be set) + 8bit ‘byte’ (integer value for the number of following data bytes) then the ‘data’ itself. This information is contained in the ‘MODBUS Table’.
Note: A function ’10 Hex’ Set message also requires an additional byte defining the number of ‘data’ bytes in the data message. This will always be the number of ‘registers’ multiplied by 2 as each ‘data’ register consists of 2 bytes (if number of ‘data’ registers = 2 then number of ‘data’ bytes = 4).
6
Page 7
Message CRC Checksum
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 03 40 06 00 02 30 CA
The CRC (Cyclical Redundancy Check) is a check-sum generated by means of ‘A001H polynomial’. The CRC is two bytes containing a 16-bit binary value (word). The CRC value is calculated by the transmitting device that
appends the CRC to the end of the message. The receiving device recalculates the CRC value prior to processing of a received message and compares the result to the actual CRC value appended to the message. If the two values do n ot match the message is regarded as invalid. The CRC is initiated by first preloading a 16bit register to all 1's (FFFF Hex). Then a process begins of applying each consecutive 8bit byte of the message to the register contents us ing an exclusive ‘OR’ calculation. The result is shifted one bit in the direction of the least significant bit (LSB), with the most significant bit (MSB) set at ‘0’. The LSB is then examined; if ‘1’ the register content is applied to the polynomial value ‘A001’ Hex (101 0 0000 0000 0001) using an exclusive ‘OR’ calculation - if ‘0’ no exclusive OR takes place. This process is repeated until eight ‘bit’ shifts have been performed. After the eighth bit shift, the next 8bit message byte is applied to the register contents using an exclusive ‘OR’ calculation. The bit shift and re-calculation process is then repeated again. When all message bytes have been processed the final content of the 16bit register is the message CRC value.
Only the 8bits of ‘data’ in each message character is used for generating the CRC; start, stop and parity bits are ignored. Note: When the 16bit CRC value is appended to a message, the low order byte must be transmitted first followed by the high order byte. An incorrect or byte reversed check sum will render the message invalid and it will be ignored.
SLAVE RESPONSE TIMEOUT
A slave controller may not answer immediately. Ensure the ‘slave timeout’ setting of the ‘master’ device is set to a value no less than 500ms. If the ‘slave’ device fails to receive a valid message due to a communication disruption, parity error, CRC error or other reasons, no response is given and the master must process a timeout condition in this instance. If the ‘slave’ receives a valid message that cannot be processed an exception response will be returned.
MESSAGE ANSWER FROM SLAVE TO MASTER
The format of the ‘slave’ controller answer is similar to the original master request format; the message data content depends on the message function code type.
The ‘address’ and ‘code’ of the slave answer is identical to the original request message; the address is the ‘slave’ device address and the ‘code’ is a repeat of received function code type from the master. The remainder of the message is dependant on the requested function code type. The CRC checksum is re-calculated for the answer message character s using the specified CRC process.
03Hex – Get: read from register (or ‘Adv’ Advise)
Slave
Address
Function
Code
Start
Address
Number of
Bytes of
Data
DATA
1st Register
byte 0 byte 1
DATA 2nd Register byte 2 byte 3
CRC Check
Sum
01 03 40 18 04 00 00 1B 5F BE 61
1) slave address 1byte
2) function code 1byte
3) bytes of data 1byte (number of bytes in ‘data’ answer)
4) data (high byte of each register transmitted first)
5) CRC checksum 2bytes (low byte first followed by high byte)
06Hex - Preset Single Register: write to single register
Slave Address Function Code Start Address
DATA
byte 0 byte 1
CRC Check Sum
01 06 00 6F 00 5F FE BC
1) slave address 1byte
2) function code 1byte
3) bytes of data 1byte (number of bytes in ‘data’ answer)
4) data (high byte of each register transmitted first)
5) CRC checksum 2bytes (low byte first followed by high byte)
7
Page 8
10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series only)
Slave
Address
Function
Code
Start
Address
Number of
Registers
CRC Check
Sum
01 10 40 18 00 02 D4 0F
1) slave address 1byte
2) function code 1byte
3) number of registers set 2 bytes
4) CRC checksum 2 Bytes (low byte first followed by high byte)
EXCEPTION RESPONSE
If the ‘slave’ device receives a request that cannot be processed an ‘exception response’ is given. An exception response message consists of the following elements:
1) Slave Network Address (1 byte): Slave address identification
2) Function Code (1 byte): In a normal response, the slave repeats the function code of the original master request. All function codes have an MSB (most significant bit) of 0 (values are all below 80 hexadecimal). In an exception response, the slave sets the MSB of the function ‘code’ to 1. This makes the ‘code’ value 80 Hex greater than the received ‘code’ value from the master.
3) Data (1 byte): The ‘data’ response will contain a ‘1 byte’ value exception code.
4) CRC Checksum (2 byte).
CRC Check SumSlave Address Function Code Error Code
01 90 04 4D C3
Exception Codes:
01H Illegal Function Code
The requested ‘code’ function is not supported.
02H Illegal Data Address
The requested ‘data start address’ is not supported.
03H Illegal Data Value
The requested ‘data’ value is not supported.
04H Function Error
The slave cannot execute the request or the request type is inhibited.
TROUBLESHOOTING
Problem: No ‘slave’ response or corrupt MODBUS message Solution: Check that the ‘slave’ controller is set for the anticipated slave address
Check that all ‘slave’ controllers are set with a unique system address Check that the controller is set for MODBUS RTU mode (if applicable) Check that the ‘master’ is operating in MODBUS RTU mode Check that the ‘master’ baud rate, parity bit and number of s t op bits are correct Check that the ‘master ‘response timeout is set for a minimum of 500ms Check that the ‘master’ is implementing the specified CRC check sum process
Check RS485 wiring polarity and security of connections
Problem: Last character of MODBUS message is corrupted Solution: Add a delay of 2ms after last character received before releasing RTS signal
Problem: The MODBUS master message is reflected in the slave answer Solution: Inhibit RX/TX echo on ‘master’ device communications port
8
Page 9
SECTION 5 - MODBUS TABLE DESCRIPTION
A ‘MODBUS table’ describes the “items” used to access information in the memory registers of different types of controller, or similar controllers using different application software variants or versions. The MODBUS Table will contain the valid message items (“Name”) together with the Function Code (Function), Register Start Address (“Register Address”), Register Size (“Register Length”) and a definition for coding and decoding the item data (“Coding”). A ‘MODBUS Table’ order form, detailing the required order information, can be found on the last page of this document.
TABLE ITEM FORMAT
Each ‘item’ of a ‘MODBUS Table’ will define the massage format to read or set the information contained in the slave controller register(s):-
Name
Descriptive ‘name’ or ‘item tag’ for the data item. The ‘Name’ is not used in code or message formatting and serves only as a reference for the defined item.
Function
The Hex code required that instructs the slave (Intellisys controller) to perform a GET, ADV (Advise), CMD (command) or SET function.
Register Address Register Length Coding Menu
The slave controller register start address for the defined processing function. The number of registers to be processed. How to construct or interpret the data elements of a message. Controller menu item reference.
Note: see “MODBUS RTU” for a detailed description of ‘Function’, ‘Register Address’ and ‘Register Length’ formats.
NAME AND FUNCTION
The ‘name’ for each table item will always start with 3 characters that describe the function type:
Adv Advise Function (03Hex) – same format as a Get function, see ‘Advise Function’. Get Read from register (03Hex) Set Write to registe r (10Hex) Cmd Command (10Hex) – same format as a Set function; will instruct the slave to perform a defined action or
process
CODING
Item coding definitions specify the ‘number of data bytes’ and the ‘data conversion type’. In some instances a data message may contain multiple sets of data items; an ‘Advise’ message for example. In this instance the ‘start location of data’ within the message is also specified to enable extraction of the required data item from the entire message data.
Number of data bytes:
This specifies the length of the item data in bytes (6 = 6 bytes (3 registers) of data)
Start location of data bytes:
Number of Data Bytes to Follow
DATA
1st Register byte
0 byte 1
DATA 2nd Register byte 2 byte 3
DATA
3rd Register byte
4 byte 5
CRC Check SumSlave Address Function Code
01 03 06 09 00 00 65 00 A8 30 4D
If a data message consists of more than one set of data items (multiple item data message) the ‘start location’ specifies where the first byte of the data associated with in item begins. If, for example, a 6 byte (3 register) answer is returned that consists of three different ‘2 byte’ item data values, a ‘start location of data bytes’ = ‘2’ indicates that the item data starts with the 3rd byte (byte 2) of the data message. The 1st byte of a data message is regarded as byte 0(zero). In this instance the ‘number of data bytes’ will be ‘2’ indicating that the data associated with the item is 2 bytes of data in length. A ‘start location’ of byte ‘2’ and register length of ‘1’ (register = 2 bytes) means the data is contained in the 3rd and 4th bytes of the data message. If no ‘start location’ is specified then data associated with the item will start with the first byte (byte 0) of the message data.
Data Conversion Type:
This specifies how to interpret the data; refer to the ‘Data Conversion Type’ list in the Modbus Table. For example: If the ‘Data Conversion Type’ = CODED, STATUS then the decimal integer value of the data has a defined meaning; refer to the ‘STATUS’ Coded data list in the ‘MODBUS Table’ for definitions. If the ‘Data Conversion Type’ = PSI then the decimal integer value of the data is ‘pressure’ in ‘psi’ units.
9
Page 10
MENU REFERENCE
The menu structure of a controller has menu pages that contain a number of menu page ‘items’.
example menu and items For example: menu pages P00, P01, P02 > P’n’. Menu page P00 is the normal running list of display items that can be accessed and viewed on the controller displ ay without
access code. These items are ‘read only’ and consist of status, hours run and other general control or monitoring value (s). Menu pages other than P00 are setup and configuration items that require an ‘access code’ when accessing the items on
the controller display. Each menu page has a list of items that are referenced ‘1, 2, 3 > ‘n’.
a b c
P01
For example, a menu reference of P01.02 “AB” refers to menu item ‘2’ of menu page P01. Each menu page item reference also has a two or three alphanumeric character item identification that is displayed by the
controller. With a menu reference the controller manual can be examined to determine the exact function, definition, scope and limits for the specified item value.
Items that do not have a ‘Menu’ reference are general controller status or menu page P00 items.
‘ADV’ ADVISE FUNCTION
The ‘Advise’ function is a special type of ‘Get’ function. Each ‘Advise’ function item has an equivale nt ‘Get’ function; both functions will provide a similar result.
Controllers on a Multi485 network will routinely broadcast key value and status specific data to all other controllers on the network. This information is used, for example, by a system management unit for systems monitoring and control functions. A SMG Box will automatically capture, store and continuously update these information items for each controller on the network. Adv are Routine network broadcasts that occur every 2 seconds. Th transmission of this data consumes no network bandwidth. (The maximum recommended request rate is 1 request every 2 seconds.)
This facility provides a method of retrieving ‘Adv’ data items directly from the SMG Box resulting in a faster response time for information requests from a master. The method also has the advantage of reducing the amount of data traffic on the Multi485 network enabling system management controllers to perform there functions without potential communication delays. For this reason MODBUS ‘Adv’ functions are preferable to ‘Get’ functions when implemented on a Multi485 network that consists of a system management controller with multiple machine controllers.
‘ADV’ ADVISE FUNCTION – SINGLE ITEM FORMAT OPTION
Controllers or units on a Multi485 network routinely broadcast general status and key per formance information. The SMG Box will capture and store each ‘Broadcast’ detected. The Gateway ‘Broadcast’ registers will always contain the latest ‘broadcast’ information for each controller or unit on the Multi485 network. When a Modbus ‘Adv’ request is made the SMG Box will respond immediately with information from it’s own ‘Broadcast’ registers for the unit addr ess specified. This function reduces network activity and enables a faster Modbus response to commonly requested data.
A standard ‘Advise’ function defined in the ‘MODBUS Table’ will show the entire ‘broadcast’ being returned as a response. The table will define for each ‘name’ item where in the returned data message the actual requ ested data can be found. The ‘master’ must then extract the required data from the returned data message. This method is very efficient as the master can extract all ‘broadcast’ data from the single returned data message without the need to perform multiple requests for each individual data item contained in a single slave controller ‘broadcast’ message.
01.02 AB
10
Page 11
Some ‘master’ devices may not be equipped with the necessary data message memory to handle a large message of many bytes or have the ability to extract multiple data items from a single data message item. In this instance an alternativ e ‘Advise’ function request method can be implemented.If the ‘Advise’ items of a ‘MODBUS Table’ are examined it will be seen that the ‘Register Address’ for each individual ‘Advise’ item contained in a single slave controller ‘broadcast’ message will have the same start address (Register Address). If the entire ‘broadcast’ data message is 7 registers (14 bytes) in length and only the 2nd register (2 bytes) of item data is required, it is possible to specify a ‘Register Address’ that is 2 bytes higher (skip the first 2 bytes of the broadcast data message) with a ‘Register Length’ that is consistent with the required item data length. This will instruct the MODBUS Gateway to extract the 2 bytes of required item data from the entire broadcast data message and only return the required 2 bytes of data as a response. Using this method an ‘Advise’ fu nction can be handled by a ‘master’ in exactly the same way as a ‘Get’ function.
For Example: (AdvDeliveryPressure): The ‘broadcast’ of an example slave controller may be 6 bytes of data (3 registers) in length starting at register address
location ‘F000’ Hex. The 1st byte (byte 0) is 8bits coded status, the 2nd byte (byte 1) is 8bits status flags which together form a single 16bit status register (1st register). The 3rd and 4th bytes (byte 2 and byte 3) are a single16bit register (2nd register) containing a ‘delivery pressure’ value. The 5th and 6th b ytes (byte 4 and byte 5) are a single 16bit register (3rd register) containing a ‘delivery temperature’ value. From an example ‘MODBUS Table’ it may be seen that the ‘Register Address’ for all four of these separate ‘Adv’ items is ‘F000 Hex’ (the start address of the entire ‘Broadcast’ message that contains the data specified).
An entire ‘Broadcast’ message may, for example, contain 3 registers (6 bytes) of data. For a particular item the ‘Modbus Table’ may show the ‘start address’ for the entire broadcast to be ‘F000’ with a length of 3 registers (6 bytes). The Modbus Table will indicate that the required data is 2 bytes long (number of data bytes) starting at the 2nd byte of data in the entire broadcast (start location of data bytes).
Name AdvDeliveryPressure Modbus Function 03 Modbus Register Address F000 (start address of entire Broadcast message) Modbus Register Length 0003 (length of entire Broadcast message) Coding Number of data bytes = 2 (length of AdvDeliveryPressure data)
Start location of data bytes = 2 (the 2 data bytes of the AdvDeliveryPressure data item start at byte 2 in the Broadcast message = bytes 2 and 3 of the message) Data Conversion Type = PSI
Master Request Message “01 03 F000 00 03 36CB” (36CB = CRC check sum) Slave Answer Message “01 03 06 09 00 00 65 00 A8 304D” (304D = CRC) Coding = PSI ‘00 65’Hex = 101 decimal = 101 psi
Register addresses shown are examples only
Status Register
Delivery
Pressure
Delivery
Temperature
Slave Address Function Code
Number of Data Bytes to Follow
DATA
1st Register byte
0 byte 1
DATA 2nd Register byte 2 byte 3
DATA
3rd Register byte
4 byte 5
CRC Check Sum
01 03 06 09 00 00 65 00 A8 30 4D
F000 F001 F002
Message Data
11
Page 12
If only the ‘delivery pressure’ (AdvDeliveryPressure) data value is required a new ‘Advise’ req uest message format can be constructed from the Modbus Table definition:
Name AdvDeliveryPressure Modbus Function 03 Modbus Register Address F001 (start at the second regi ster, byte 2, of the Broadcast) Modbus Register Length 0001 (only return one register, 2 bytes, of data)
Using the new ‘Advise’ message format the SMG Box will return only the 2nd Broadcast message register (2 bytes) containing the ‘delivery pressure’ data value.
Master Request Message “01 03 F001 0001 E6CA” (E6CA = CRC check sum) Slave Answer Message “01 03 02 00 65 786F” (786F = CRC check sum) Coding = PSI ’00 6 5’Hex = 101 decimal = 101 psi
Status Register
Delivery
Pressure
Delivery
Temperature
Modbus Register Address F000 Modbus Register Length 0003
Slave Address Function Code
Number of Data Bytes to Follow
DATA
1st Register byte
0 byte 1
01 03 06 09 00 00 65 00 A8 30 4D
DATA 2nd Register byte 2 byte 3
DATA
3rd Register byte
4 byte 5
CRC Check Sum
F000 F001 F002
Number of Data Bytes to Follow
Modbus Register Address F001 Modbus Register Length 0001
Slave Address Function Code
01 03 02 00 65 78 6F
It is only possible to manipulate a Modbus message format using ‘registers’ (1 register = 2 bytes = 1 word = 16bits); it is not possible to manipulate addresses or register lengths to a single byte of data. At least one register (2 bytes) of data must be specified even if only one byte of information is required. The ‘master’ must extract the required byte of data from the returned message.
The data type (the definition of the returned data) may be different when using an ‘Advise’ function than it is when using a ‘Get’ function for the same information. The ‘delivery pressure’ returned by an ‘Advise’ function will be 2 bytes in length and will represent pressure as an integer value in ‘psi’ units (PSI). The ‘delivery pressure’ returned by a ‘Get’ function may, for example, be 4 bytes (2 registers) in length and represent a 32bit signed integer value in miliBar units (mBAR). Always check the item ‘Coding’ definition to establish the data definition type.
Register addresses shown are examples only
‘CMD’ COMMAND FUNCTION
A ‘Command’ function will instruct the ‘slave’ controller or unit to execute a pre-defined action or process. With a command type message the content of the ‘message data’ from the ‘master’ must always be the same value as the ‘lower byte’ of the command register address. For example: if the command item ‘Register Address’ = 3302 then the ‘data’ value must be ’00 02’ Hex.
Slave Address Function Code Start Address
Number of
Registers To Be
Set
Number of Bytes
of Data
DATA
DATA 2nd Register byte 2 byte 3
CRC Check Sum
CRC Check Sum
01 10 33 02 00 01 02 00 02 25 70
It is the act of setting the specified register in the ‘slave’ controller with the defined ‘data’ value that initiates the action or process. An incorrect ‘data’ value will result in an exception response. If the ‘command’ is accepted the ‘slave’ will answer with a normal ‘Set’ register response. If the slave is unable to execute the command it will give a code ‘04’ exception response.
12
Page 13
Example: Using a command function item to set the specified item register to the correct value, the ‘slave’ controller is instructed to perform the defined action or process. In the case of a ‘CmdStart’ item, for example, the ‘slave’ controller is instructed to start the machine. The implementation of a ‘Cmd’ function message by the ‘master’ is identical to a ‘Set’ function message; both operations use function code ‘10 Hex’ to write data to a slave controller register.
Name CmdStart Modbus Function 10 Modbus Register Address 3300 Modbus Register Length 0001 Coding Number of data bytes = 1
CmdStart (to slave at address ‘01’ Hex) Master Command Message “01 10 3300 0001 02 0000 A553” (A553 = CRC check sum)
Slave Answer Message “01 10 3300 0001 0E8D” if start command executed or “01 90 04 4D C3” exception
response if not executed, ‘90’ = repeat of ‘10’ function code with MSB set to ‘1’ and ‘04’ = exception error code.
Register addresses shown are examples only
Names that begin with CMD are Non-routine. This data must be written to the device. (The maximum recommended
request rate is 2 requests per second up to 32 words per request.)
‘GET’ FUNCTION
Using the MODBUS Table a read data (Get) function message can be constructed: Name GetDeliveryPressure Modbus
Function 03 Modbus Register Address 4006 Modbus Register Length 0002 Coding Number of data bytes = 4
Data Conversion Type = mBAR GetDeliveryPressure (request to slave at address ‘01’ Hex) Master Request Message “01 03 400 6 0002 31CA” (31CA = CRC check sum)
Slave Answer Message “01 03 04 00 00 1B 58 F139” (F139 = CRC check sum) Coding = mBAR 1B 58Hex = 7000 decimal = 7000 miliBar (7.0 bar)
Register addresses shown are examples only Note: Names that begin with Get are Non-routine. This data must be requested from the device. (The maximum recommended request rate is 2 requests per second up to 32 words per request.)
‘SET’ FUNCTION
Using the MODBUS Table a write data (Set) function message can be constructed: Name SetLoadPressure Modbus
Function 10 Modbus Register Address 4018 Modbus Register Length 0002 Coding Number of data bytes = 4
SetLoadPressure (to slave at address ‘01’ Hex) Master Write Message “01 10 4018 0002 04 0000 1B58 C9CC” (C9CC = CRC)
Slave Answer Message “01 10 4018 0002 D40F” (D40F = CRC check sum) Coding = mBAR 0000 1B58Hex = 7000 decimal = 7000 miliBar (7.0 bar)
Register addresses shown are examples only Names that begin with Set are Non-routine. This data must be written to the device. (The maximum recommended
request rate is 2 requests per second up to 32 words per request.)
Data Conversion Type = mBAR
13
Page 14
DATA CODING DEFINITIONS:
Definitions for ‘data units’ and ‘data conversion types’ are listed for each ‘item’ in the “MODBUS Table” document. All ‘data’ values are ‘whole’ numbers (integers); decimal places are not permitted in MODBUS data messages. All ‘data’ values are unsigned (always positive) unless otherwise stated. Values specified as ‘SIGNED’ in the MODBUS
Table can be negative in accordance to the standard data conventio n for ‘sign ed’ number values.
DATA TYPES
Each standard definition will start with a “key” word that defines the data type:-
The following are selected examples; data types not included below are detaile d in individual ‘Modbus Tables’
Type Description
Coded a decimal value that has a defined definition; see the ‘Coded’ lists in the ‘MODBUS Table’ for value definitions Value a ‘whole’ number or value in the specified units Pressure a ‘whole’ number defining a pressure in the specified units Temperature a ‘whole’ number defining a temperature in the specified units Time a ‘whole’ number defining a time period in the specified units Electrical a ‘whole’ number defining a volt, amp, power, or speed value in the specified units Clock Clock values are relevant to real time clock functions; for example pressure schedules. These ‘whole number’ unsigned values are ‘packaged’ multiple values and must be interpreted as follows.
Clock Data Type Coding
HH_MM 1) Divide the value by 60 = Hours (0 to 23)
2) The remainder (modulus) = Minutes (0 to 59)
Example for a value of ‘1050’ Hours = 1050 / 60 = 17.5 = 17 Hours Minutes = remainder = 30 = 30 Minutes Time = 17:30 (5:30pm)
D_HH_MM 1) Divide the value by 10000 = Day (1 = Monday, 7 = Sunday)
2) Divide the remainder (modulus) by 60 = Hours (0 to 23)
3) The remainder (modulus) = Minutes
Example for a value of ‘31050’ Day = 31050 / 10000 = 3.105 = 3 = Wednesday Hours = = remainder / 60 = 17.5 = 17 Hours Minutes = remainder = 30 = 30 Minutes Day/Time = Wednesday 17:30 (5:30pm)
YYYY_DD_MO 1) Divide the value by 10000 = Year
2) Divide the remainder (modulus) by 100 = Day (1 to 31)
3) The remainder (modulus) = Month (1 to 12)
Example for a value of ‘20051605’ Year = 20051605 / 10000 = 2005.1605 = Year 2005 Day = remainder / 100 = 16.05 = Day 16 Month = remainder = 5 = Month 5 Date = 16th May 2005
14
Page 15
DATA UNITS
The ‘MODBUS Table’ will define the ‘data units’ for each item. Data unit definitions are specified in the ‘M ODBUS Table’ as a separate list; for example:
The following are selected examples; data types not included below are detailed in the ‘Modbus Tables’
Value The engineering units will differ dependant on unit set-up or item definition.
PSI BAR FAH CEL HRS % BOOLEAN BINARY
The value must be interpreted in terms of each ‘bit’ as a set of sixteen Boolean (0 or 1) flags. These values are compressor related or I/O Box Input related. For compressor related items the least significant bit (Bit 0) represents compressor 1. For unit inputs the least significant bit (Bit 0) generally represents input 1.
The number is the value in the specified engineering units
Pressure in ‘psi’ Pressure in ‘Bar’ Temperature in oF Temperature in oC Hours Percentage 0 to 100 The number will be 0 or greater than 0, (Boolean: 0 = False, 1 = True) The number represents a 16bit (two byte) binary value of 16bit flags.
16 bit Register
1st Byte (byte 0) 2nd Byte (byte 1)
15141312111098 76543210
Bit
MSB
The example illustrates the bit pattern for a value of ’00 81 Hex’. This value is interpr eted as a ‘true’ condition with respect to the item definition for compressors 1 and 8. If the ‘item’ definition is ‘Compressors Running’ then com pressors 1 and 8 are in a ‘running’ condition.
00000000 10000001
Compressor 8 Compressor 1
LSB
15
Page 16
The example illustrates the bit pattern for a value of "1A 04 C2 01" Hex. A reference to ‘Bit 18’ equates to bit ‘2’ of byte ‘1’ in the answer data message. If the ‘bit’ is ‘1’ then the condition is ‘TRUE’.
2nd Register1st Register
1st Byte (byte 0) 2nd Byte (byte 1) 3rd Byte (byte 2) 4th Byte (byte 3)
3130292827262524 2322212019181716 15141312111098 76543210
Bit
00011010 00000100 11000010 00000000
MSB
BIT ‘n’
Note: The LSB (least significant bit) of a register or byte is regarded as Bit 0(zero)
A Boolean (true/false) can be established from examining the specified ‘bit’ of the 16bit register. If the item specifies ‘Bit 4’ then the 4th bit should be examined:
LSB
16 bit Register
1st Byte (byte 0) 2nd Byte (by te 1)
15141312111098 76543210
Bit
MSB
00011010 10010001
LSB
AND
00000000 00010000
EQUALS
00000000 00010000
= 16 Decimal (Condition is TRUE) The 4th bit of a register can be extracted by ‘masking’ the register content with “10 Hex”; if the resulting value is greater than
0(zero) then the condition is ‘True’, if the result is 0(zero) then the condition is ‘False’.
Decimal Places:
Numbers with decimal places (eg 20.55) are not permissible in MODBUS data transfer – all numbers must be integer ‘whole’ numbers. To provide ‘decimal place’ accuracy some data values are multiplied by 10, 100 or 1000 and transmitted as a ‘whole’ number (integer). In this instance the ‘Data Units’ will specify that the number represe nts a value to one or more decimal places.
For example: PERCENT_DP2 = Percent to 2 decimal places
“2055” divided by 100 = 20.55%
If the ‘Data Units’ specifies “to 1 decimal place”, divide the number by 10 to convert to the correct engineering units. If the ‘Data Units’ specifies “to 2 decimal places”, divide the number by 100; if 3 decimal places divide by 1000.
16
Page 17
SECTION 6 - X-SERIES AIR SYSTEM
Note: example only; systems will differ from installation to installation
17
Page 18
SMG BOX
For Remote Monitoring/Control of X-Series Units and Boxes. The SMG Box provides a RS485 Modbus connection to the X8I Automation System. A system will only contain one SMG Box.
GENERAL X-SERIES SYSTEM COMPONENTS
The following Components can be monitored by the SMG Box. X8I Series Controller or X12I Series Controller: Automation System Unit
Monitors and controls the air compressors, all general system and air compressor related information is governed and available from this unit. A system will only contain one X-Series Automation System controller.
EX Box: Extension to the X-Series Unit For connection to remote compressor(s) or other specialized compressor integration. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple EX Boxes.
I/O Box: Monitoring/Control of Auxiliary Equipment and/or Sensors For monitoring and/or control of auxiliary compressed air equipment (for exam ple: dryer, auto drain, filtration differential, isolation valves, cooling water towers/pumps, ventilation) or sensors (for example: pressure, pressure differential, dewpoint, air flow, temperature). A system may contain multiple IO Boxes.
VSD Box: Extension to the X-Series Unit For connection to variable speed compressor(s) or other specialized compressor integration. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple VSD Boxes.
CX Box: Extension to the X-Series Unit For connection to non-Ingersoll Rand air compressors that are not equipped with any accessible means of remote connectivity. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple CX Boxes.
DX Box: Extension to the X-Series Unit For connection to two fixed speed online/offline air compressors to be seen as one compressor by the X8I or X12I. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple DX Boxes.
ir-485 Gateway / irV-485 Gateway
For connection to all Ingersoll Rand Intellisys based compressors. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple Gateways.
ir-485 Direct
For connection to all Ingersoll Rand R Series (S3) based compressors. All common air compressor status information is sent to, and available from, the X-Series system management unit. A system may contain multiple R series compressors.
18
Page 19
X-SERIES NETWORK ADDRESSES
UNIT X8I or X12I EX, VSD B / mA / V, CX, DX, ir485 / irV485, S3
(As It Relates To The Compressor Number Assigned) Compressor 1 1 (01) Compressor 2 2 (02) Compressor 3 3 (03) Compressor 4 4 (04) Compressor 5 5 (05) Compressor 6 6 (06) Compressor 7 7 (07) Compressor 8 8 (08) Compressor 9 9 (09) X12I ONLY Compressor 10 10 (0A) X12I ONLY Compressor 11 11 (0B) X12I ONLY Compressor 12 12 (0C) X12I ONLY
I/O
I/O Box 1 105(69) I/O Box 2 112(70) I/O Box 3 106(6A) X12I ONLY I/O Box 4 107(6B) X12I ONLY I/O Box 5 108(6C) X12I ONLY I/O Box 6 109(6D) X12I ONLY I/O Box 7 110(6E) X12I ONLY I/O Box 8 111(6F) X12I ONLY I/O Box 9 113(71) X12I ONLY I/O Box 10 114(72) X12I ONLY I/O Box 11 115(73) X12I ONLY I/O Box 12 116(74) X12I ONLY
Note: I/O Unit 2 address (70Hex) is intentionally out of sequence; this is not a print error.
DECIMAL (HEX) ADDRESS NOTES
101(65)
COMMUNICATION LINK
To Interface with a X-Series product that is equipped with a Multi485 enabled network port, or to interface with multiple X­Series products operating on a single Multi485 system network, a SMG Box unit is required. The SMG Box forms the interface between the Multi485 protocol and MODBUS RTU master/slave communications link.
SMG Box connectivity is implemented using a two-wire RS485 industry standard commun ications link operating in point-to­point, master-slave mode. In use the SMG Box is transparent and each X-Series system unit is accessible using individual system device addresses.
Polarity of the two MODBUS RS485 wires (L1+ or ‘A’ and L2- or ‘B’) is important; reversal will inhibit communications
and result in error.
MODBUS TIMING
The SMG will handle ONE (1) MODBUS request at a time from the customer’s port. The maximum recommended request rate is 2 requests per second. When a MODBUS request is received for any device connected to the XI Automation System, that request will be forwarded to the device between sequencer broadcasts and the response from the device will then be relayed back to the customer’s port. If a second MODBUS command is sent before the first command has been responded to, the second command will be ignored.
RS485 MODBUS SERIAL DATA FORMAT
The SMG supports only the RTU transmission mode. The user must configure their serial port communication parameters (baud rate, parity mode, etc.) during configuration to match those of the SMG Box. The SMG Box port operates with an asynchronous serial data format:
SMG Communication Parameters: 8-N-1-9600 Data Bits: 8 Parity: None Stop Bit: 1 Baud Rate: 9600
19
Page 20
SECTION 7 – X8I MODBUS RTU DEFINITIONS
Name : AdvAvailableStatus Modbus Function : 03 Modbus Register Address : F020 Modbus Register Length : 0007 Coding : Number of data bytes = 2 16 bit value: compressor available status Bitvalue = 0 => compressor available => . operational AND remote control activated Bitvalue = 1 => compressor not available => . not operational OR remote control deactivated Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => available status for compressors 1...8 . Bits 8..15 => unused, always 0 MODBUS: register address = F020, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F020...F026 is acceptable.
Name : AdvRunningStatus Modbus Function : 03 Modbus Register Address : F020 Modbus Register Length : 0007 Coding : Number of data bytes = 2 : Start location of data bytes = 2 16 bit value: compressor running status Bitvalue = 0 => compressor motor stopped Bitvalue = 1 => compressor motor running Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => running status for compressors 1...8 . Bits 8..15 => unused, always 0 MODBUS: register address = F021, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F020...F026 is acceptable.
Name : AdvLoadedStatus Modbus Function : 03 Modbus Register Address : F020 Modbus Register Length : 0007 Coding : Number of data bytes = 2 : Start location of data bytes = 4 16 bit value: compressor loaded status Bitvalue = 0 => compressor is unloaded AND/OR stopped Bitvalue = 1 => compressor is running AND loaded Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => loaded status for compressors 1...8 . Bits 8..15 => unused, always 0 MODBUS: register address = F022, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F020...F026 is acceptable.
20
Page 21
Name : AdvAlarmStatus Modbus Function : 03 Modbus Register Address : F020 Modbus Register Length : 0007 Coding : Number of data bytes = 2 : Start location of data bytes = 6 16 bit value: compressor alarm/trip status Bitvalue = 0 => compressor reports no alarm OR trip Bitvalue = 1 => compressor reports alarm AND/OR trip error Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => alarm/trip status for compressors 1...8 . Bits 8..15 => unused, always 0 MODBUS: register address = F023, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F020...F026 is acceptable.
Name : AdvSystemStatus Modbus Function : 03 Modbus Register Address : F020 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 8 8 bit value Lower 4 bits: Sequencer alarm/trip conditions code (Bits 0...3) . 0 = no fault or current error code is higher than 15 . 1 = Pressure sensor probe fault . 2 = (unused in this application) . 3 = (unused in this application) . 4 = Internal 24V error . 5 = External 24V error . 6 = Real time clock error . 7 = LED board error (no communication) . 8 = (unused in this application) . 9 = (unused in this application) . 10 = (unused in this application) . 11 = (unused in this application) . 12 = 8DI/4R XPM 3 communication error (I-PCB box 5...8) . 13 = 8DI/4R XPM 3 short circuit error (I-PCB box 5...8) . 14 = (unused in this application) . 15 = (unused in this application) Upper 4 bits: status flags, 0 => OFF, 1=> ON . Bit 4 => Sequencer operational (switched ON) status . Bit 5 => Sequencer trip condition status . Bit 6 => Sequencer alarm condition status . Bit 7 => Insufficient compressor capacity status MODBUS: register address = F024, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F020...F026 is acceptable. . Data is located in low order byte of register F024
Name : AdvTargetPressure Modbus Function : 03 Modbus Register Address : F020 Modbus Register Length : 0007 Coding : Number of data bytes = 2 : Start location of data bytes = 10 16 bit value: System target pressure (unit: PSI) MODBUS: register address = F025, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F020...F026 is acceptable.
21
Page 22
Name : AdvSystemPressure Modbus Function : 03 Modbus Register Address : F020 Modbus Register Length : 0007 Coding : Number of data bytes = 2 : Start location of data bytes = 12 16 bit value: System pressure reading (unit: PSI) MODBUS: register address = F026, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F020...F026 is acceptable.
Name : AdvCompressor1Percentage Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0004 Coding : Number of data bytes = 1 : Start location of data bytes = 0 MODBUS: register address = F000, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F000...F005 is acceptable. High order byte of 16 bit register F000 =>
. operating percentage for COMPRESSOR 1 (0....100)
Name : AdvCompressor2Percentage Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0004 Coding : Number of data bytes = 1 : Start location of data bytes = 1 MODBUS: register address = F000, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F000...F005 is acceptable. Low order byte of 16 bit register F000 =>
. operating percentage for COMPRESSOR 2 (0....100)
Name : AdvCompressor3Percentage Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0004 Coding : Number of data bytes = 1 : Start location of data bytes = 2 MODBUS: register address = F001, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F000...F005 is acceptable. High order byte of 16 bit register F001 =>
. operating percentage for COMPRESSOR 3 (0....100)
Name : AdvCompressor4Percentage Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0004 Coding : Number of data bytes = 1 : Start location of data bytes = 3 MODBUS: register address = F001, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F000...F005 is acceptable. Low order byte of 16 bit register F001 =>
. operating percentage for COMPRESSOR 4 (0....100)
22
Page 23
Name : AdvCompressor5Percentage Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0004 Coding : Number of data bytes = 1 : Start location of data bytes = 4 MODBUS: register address = F002, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F000...F005 is acceptable. High order byte of 16 bit register F002 =>
. operating percentage for COMPRESSOR 5 (0....100)
Name : AdvCompressor6Percentage Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0004 Coding : Number of data bytes = 1 : Start location of data bytes = 5 MODBUS: register address = F002, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F000...F005 is acceptable. Low order byte of 16 bit register F002 =>
. operating percentage for COMPRESSOR 6 (0....100)
Name : AdvCompressor7Percentage Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0004 Coding : Number of data bytes = 1 : Start location of data bytes = 6 MODBUS: register address = F003, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F000...F005 is acceptable. High order byte of 16 bit register F003 =>
. operating percentage for COMPRESSOR 7 (0....100)
Name : AdvCompressor8Percentage Modbus Function : 03 Modbus Register Address : F000 Modbus Register Length : 0004 Coding : Number of data bytes = 1 : Start location of data bytes = 7 MODBUS: register address = F003, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F000...F005 is acceptable. Low order byte of 16 bit register F003 =>
. operating percentage for COMPRESSOR 8 (0....100)
23
Page 24
Name : AdvSelectedCompressor Modbus Function : 03 Modbus Register Address : F080 Modbus Register Length : 0008 Coding : Number of data bytes = 1 : Start location of data bytes = 4
8 bit value (1....8) defining compressor number for
which running hours data is provided MODBUS: register address = F082, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F080...F087 is acceptable. High order byte of 16 bit register F082 => . compressor number of AdvRunningHours value (F080 and F081). Remark: to ensure compressor number and running hour data correspond to the same compressor it is essential to request registers F080,F081 and F082 in a single data request
Name : AdvRunningHours Modbus Function : 03 Modbus Register Address : F080 Modbus Register Length : 0008 Coding : Number of data bytes = 4 : Start location of data bytes = 0 Numeric value (32 bit) defining running hours for indicated compressor. MODBUS: addresses = F080, F081, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F080...F087 is acceptable. 16 bit register F080 => high order 16 bits of 32 bit compressor running hours value 16 bit register F081 => low order 16 bits of 32 bit compressor running hours value Remark: to ensure compressor number and running hour data correspond to the same compressor it is essential to request registers F080,F081 and F082 in a single data request
24
Page 25
Name : AdvSystemStatusFlags Modbus Function : 03 Modbus Register Address : F080 Modbus Register Length : 0008 Coding : Number of data bytes = 2 : Start location of data bytes = 8 16 bit value: system status flags Bitvalue = 0 => flag inactive Bitvalue = 1 => flag active Lowest order bit of 16 bit value = Bit 0 . Bit 0 => start time function active condition . Bit 1 => zoning mode active . Bits 2...4: rotation type selection . value = 1 => FIFO control mode . value = 2 => energy control mode . value = 3 => time rotation . value = 4 => EQUAL HOURS mode . Bit 5 => Auxiliary pressure mode active . Bit 6 => system active . Bit 7 => schedule mode active . Bit 8 => low pressure condition . Bit 9 => high pressure condition . Bit 10 => insufficient capacity condition . Bit 11 => restricted capacity condition . Bits 12...14: selected table number (1...6) . Bit 15 => prefill busy condition MODBUS: register address = F084, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F080...F087 is acceptable.
Name : AdvRelayStatusFlags Modbus Function : 03 Modbus Register Address : F080 Modbus Register Length : 0008 Coding : Number of data bytes = 3 : Start location of data bytes = 10 24 bit value: virtual relay condition flags Bitvalue = 0 => flag inactive Bitvalue = 1 => flag active Lowest order bit of 24 bit value = Bit 0 . Bits 0..15 => (unused in this application) . Bit 16 => start time function error condition . Bit 17 => Delta P alarm condition . Bit 18 => alarm override condition . Bit 19 => Auxiliary box alarm condition . Bit 20 => Auxiliary box trip condition . Bit 21 => Auxiliary box signal condition . Bit 22 => Auxiliary box communication failure condition . Bit 23 => system producing air condition MODBUS: addresses = F085,F086, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F080...F087 is acceptable. Register F085 contains 8 highest order bits of 24 bit data Register F086 contains 16 lowest order bits of 24 bit data in register's highest order byte.
25
Page 26
Name : AdvCompressorMaintenance Modbus Function : 03 Modbus Register Address : F080 Modbus Register Length : 0008 Coding : Number of data bytes = 2 : Start location of data bytes = 14 16 bit value: compressor maintenance status Bitvalue = 0 => no maintenance Bitvalue = 1 => maintenance ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => maintenance status for compressors 1...8 . Bits 8..15 => unused, always 0 MODBUS: register addres = F087, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F080...F087 is acceptable.
Name : AdvErrorCode Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 2 : Start location of data bytes = 2 16 bit value: current error, see "CODED,ERROR" table for list of error code numbers <=> definitions. MODBUS: register address = F061, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable.
Name : AdvFaultRegister Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 2 : Start location of data bytes = 4 16 bit value: bit flags for first 16 error codes, see "CODED,ERROR" table for error code numbers <=> definitions. Bitvalue = 0 => error inactive Bitvalue = 1 => error active Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => flags for errors 9...16 . Bits 8...15 => flags for errrors 1...8 MODBUS: register address = F062, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable.
26
Page 27
Name : AdvCompressor1Sequence Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 6 8 bit value: Sequence assignment for compressors 1 and 2 Lowest order bit of 8 bit value = Bit 0 4 bit value => Sequence assignment for compressors .Value<=> Seq: 0 <=> 'A', 1 <=> 'B',...,11 <=> 'L' . Bits 0...3: Sequence assignment for compressor 1 MODBUS: register address = F063, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in high order byte of register F063
Name : AdvCompressor2Sequence Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 6 8 bit value: Sequence assignment for compressors 1 and 2 Lowest order bit of 8 bit value = Bit 0 4 bit value => Sequence assignment for compressors .Value<=> Seq: 0 <=> 'A', 1 <=> 'B',...,11 <=> 'L' . Bits 4...7: Sequence assignment for compressor 2 MODBUS: register address = F063, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in high order byte of register F063
Name : AdvCompressor3Sequence Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 7 8 bit value: Sequence assignment for compressors 3 and 4 Lowest order bit of 8 bit value = Bit 0 4 bit value => Sequence assignment for compressors .Value<=> Seq: 0 <=> 'A', 1 <=> 'B',...,11 <=> 'L' . Bits 0...3: Sequence assignment for compressor 3 MODBUS: register address = F063, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in low order byte of register F063
27
Page 28
Name : AdvCompressor4Sequence Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 7 8 bit value: Sequence assignment for compressors 3 and 4 Lowest order bit of 8 bit value = Bit 0 4 bit value => Sequence assignment for compressors .Value<=> Seq: 0 <=> 'A', 1 <=> 'B',...,11 <=> 'L' . Bits 4...7: Sequence assignment for compressor 4 MODBUS: register address = F063, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in low order byte of register F063
Name : AdvCompressor5Sequence Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 8 8 bit value: Sequence assignment for compressors 5 and 6 Lowest order bit of 8 bit value = Bit 0 4 bit value => Sequence assignment for compressors .Value<=> Seq: 0 <=> 'A', 1 <=> 'B',...,11 <=> 'L' . Bits 0...3: Sequence assignment for compressor 5 MODBUS: register address = F064, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in high order byte of register F064
Name : AdvCompressor6Sequence Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 8 8 bit value: Sequence assignment for compressors 5 and 6 Lowest order bit of 8 bit value = Bit 0 4 bit value => Sequence assignment for compressors .Value<=> Seq: 0 <=> 'A', 1 <=> 'B',...,11 <=> 'L' . Bits 4...7: Sequence assignment for compressor 6 MODBUS: register address = F064, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in high order byte of register F064
28
Page 29
Name : AdvCompressor7Sequence Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 9 8 bit value: Sequence assignment for compressors 7 and 8 Lowest order bit of 8 bit value = Bit 0 4 bit value => Sequence assignment for compressors .Value<=> Seq: 0 <=> 'A', 1 <=> 'B',...,11 <=> 'L' . Bits 0...3: Sequence assignment for compressor 7 MODBUS: register address = F064, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in low order byte of register F064
Name : AdvCompressor8Sequence Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 9 8 bit value: Sequence assignment for compressors 7 and 8 Lowest order bit of 8 bit value = Bit 0 4 bit value => Sequence assignment for compressors .Value<=> Seq: 0 <=> 'A', 1 <=> 'B',...,11 <=> 'L' . Bits 4...7: Sequence assignment for ompressor 8 MODBUS: register address = F064, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in low order byte of register F064
Name : AdvExtraSystemFlags Modbus Function : 03 Modbus Register Address : F060 Modbus Register Length : 0007 Coding : Number of data bytes = 1 : Start location of data bytes = 12 8 bit value: Lowest order bit of 8 bit value = Bit 0 . Bit 0: Compressor control active. (system on or switched . off but retaining control => compressors unloaded) . bits 1...7: unused MODBUS: register address = F066, can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within address range F060...F066 is acceptable. Remark: 8 bit data described above is located in high order byte of register F066
29
Page 30
Name : GetSoftwareVersionIdString Modbus Function : 03 Modbus Register Address : 3400 Modbus Register Length : 0003 Coding : Number of data bytes = 6 Data Conversion Type = STRING
Name : GetSoftwareVersionRevString Modbus Function : 03 Modbus Register Address : 3403 Modbus Register Length : 0003 Coding : Number of data bytes = 6 Data Conversion Type = STRING
Name : CmdStart Modbus Function : 10 Modbus Register Address : 3300 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : CmdStop Modbus Function : 10 Modbus Register Address : 3301 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : CmdReset Modbus Function : 10 Modbus Register Address : 3306 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : CmdClearLog Modbus Function : 10 Modbus Register Address : 3307 Modbus Register Length : 0001 Coding : Number of data bytes = 1
Name : GetAnalogInput1 Modbus Function : 03 Modbus Register Address : 3100 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = ADSTEPS
Name : GetAnalogInput2 Modbus Function : 03 Modbus Register Address : 3101 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = ADSTEPS
Name : GetAnalogInput3 Modbus Function : 03 Modbus Register Address : 3102 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = ADSTEPS
30
Page 31
Name : GetAnalogOutput1 Modbus Function : 03 Modbus Register Address : 310C Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = ADSTEPS
Name : GetDigitalInputs Modbus Function : 03 Modbus Register Address : 310E Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = BINARY bitvalue = 0 = digital input INACTIVE bitvalue = 1 = digital input ACTIVE bit = Name (Config, Delay in ms) 0 = EXTERNAL_24V (Normal Closed, 100) 1 = READY_RUN_1 (Pulsed, 200) 2 = READY_RUN_2 (Pulsed, 200) 3 = READY_RUN_3 (Pulsed, 200) 4 = READY_RUN_4 (Pulsed, 200) 5 = ALARM_SERVICE_1 (Pulsed, 200) 6 = ALARM_SERVICE_2 (Pulsed, 200) 7 = ALARM_SERVICE_3 (Pulsed, 200)
Name : GetDigitalInputsConfiguration Modbus Function : 03 Modbus Register Address : 310F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = BINARY bitvalue = 0 = digital input NO bitvalue = 1 = digital input NC bit = Name 0 = EXTERNAL_24V 1 = READY_RUN_1 2 = READY_RUN_2 3 = READY_RUN_3 4 = READY_RUN_4 5 = ALARM_SERVICE_1 6 = ALARM_SERVICE_2 7 = ALARM_SERVICE_3
Name : GetDigitalOutputs Modbus Function : 03 Modbus Register Address : 3110 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = BINARY bitvalue = 0 = digital output OFF bitvalue = 1 = digital output ON bit = Name 0 = RELAY_1 1 = RELAY_2 2 = RELAY_3 3 = RELAY_4 4 = RELAY_5 5 = RELAY_6
31
Page 32
Name : GetPressure Modbus Function : 03 Modbus Register Address : 401C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = DB1.01 'Pd' Menu = DB2.01 'Pd'
Name : GetPressureUnitsSel Modbus Function : 03 Modbus Register Address : 4026 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = CODED,P_UNIT Conversion table for CODED,P_UNIT can be found at the end of this document Data Units = LONG_VAL Menu = S02.01 'P>'
Name : SetPressureUnitsSel Modbus Function : 10 Modbus Register Address : 4026 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Conversion Type = CODED,P_UNIT Conversion table for CODED,P_UNIT can be found at the end of this document Data Units = LONG_VAL Menu = S02.01 'P>'
32
Page 33
Name : GetFaultErrorLog1Index Modbus Function : 03 Modbus Register Address : 4028 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.01 '01'
Name : GetFaultErrorLog1Fault Modbus Function : 03 Modbus Register Address : 4029 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.01 '01' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog1RunningState Modbus Function : 03 Modbus Register Address : 402A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.01 '01' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
33
Page 34
Name : GetFaultErrorLog1CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 402C Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.01 '01' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog1CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 402D Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.01 '01' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog1CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 402E Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.01 '01' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog1WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 402F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.01 '01' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
34
Page 35
Name : GetFaultErrorLog1YearDayMonth Modbus Function : 03 Modbus Register Address : 4031 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.01 '01' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
35
Page 36
Name : GetFaultErrorLog2Index Modbus Function : 03 Modbus Register Address : 4033 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.02 '02'
Name : GetFaultErrorLog2Fault Modbus Function : 03 Modbus Register Address : 4034 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.02 '02' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog2RunningState Modbus Function : 03 Modbus Register Address : 4035 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.02 '02' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
36
Page 37
Name : GetFaultErrorLog2CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 4037 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.02 '02' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog2CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 4038 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.02 '02' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog2CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 4039 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.02 '02' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog2WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 403A Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.02 '02' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
37
Page 38
Name : GetFaultErrorLog2YearDayMonth Modbus Function : 03 Modbus Register Address : 403C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.02 '02' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
38
Page 39
Name : GetFaultErrorLog3Index Modbus Function : 03 Modbus Register Address : 403E Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.03 '03'
Name : GetFaultErrorLog3Fault Modbus Function : 03 Modbus Register Address : 403F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.03 '03' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog3RunningState Modbus Function : 03 Modbus Register Address : 4040 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.03 '03' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
39
Page 40
Name : GetFaultErrorLog3CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 4042 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.03 '03' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog3CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 4043 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.03 '03' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog3CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 4044 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.03 '03' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog3WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 4045 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.03 '03' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
40
Page 41
Name : GetFaultErrorLog3YearDayMonth Modbus Function : 03 Modbus Register Address : 4047 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.03 '03' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
41
Page 42
Name : GetFaultErrorLog4Index Modbus Function : 03 Modbus Register Address : 4049 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.04 '04'
Name : GetFaultErrorLog4Fault Modbus Function : 03 Modbus Register Address : 404A Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.04 '04' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog4RunningState Modbus Function : 03 Modbus Register Address : 404B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.04 '04' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
42
Page 43
Name : GetFaultErrorLog4CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 404D Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.04 '04' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog4CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 404E Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.04 '04' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog4CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 404F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.04 '04' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog4WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 4050 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.04 '04' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
43
Page 44
Name : GetFaultErrorLog4YearDayMonth Modbus Function : 03 Modbus Register Address : 4052 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.04 '04' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
44
Page 45
Name : GetFaultErrorLog5Index Modbus Function : 03 Modbus Register Address : 4054 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.05 '05'
Name : GetFaultErrorLog5Fault Modbus Function : 03 Modbus Register Address : 4055 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.05 '05' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog5RunningState Modbus Function : 03 Modbus Register Address : 4056 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.05 '05' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
45
Page 46
Name : GetFaultErrorLog5CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 4058 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.05 '05' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog5CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 4059 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.05 '05' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog5CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 405A Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.05 '05' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog5WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 405B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.05 '05' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
46
Page 47
Name : GetFaultErrorLog5YearDayMonth Modbus Function : 03 Modbus Register Address : 405D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.05 '05' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
47
Page 48
Name : GetFaultErrorLog6Index Modbus Function : 03 Modbus Register Address : 405F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.06 '06'
Name : GetFaultErrorLog6Fault Modbus Function : 03 Modbus Register Address : 4060 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.06 '06' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog6RunningState Modbus Function : 03 Modbus Register Address : 4061 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.06 '06' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
48
Page 49
Name : GetFaultErrorLog6CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 4063 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.06 '06' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog6CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 4064 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.06 '06' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog6CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 4065 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.06 '06' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog6WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 4066 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.06 '06' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
49
Page 50
Name : GetFaultErrorLog6YearDayMonth Modbus Function : 03 Modbus Register Address : 4068 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.06 '06' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
50
Page 51
Name : GetFaultErrorLog7Index Modbus Function : 03 Modbus Register Address : 406A Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.07 '07'
Name : GetFaultErrorLog7Fault Modbus Function : 03 Modbus Register Address : 406B Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.07 '07' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog7RunningState Modbus Function : 03 Modbus Register Address : 406C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.07 '07' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
51
Page 52
Name : GetFaultErrorLog7CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 406E Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.07 '07' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog7CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 406F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.07 '07' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog7CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 4070 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.07 '07' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog7WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 4071 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.07 '07' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
52
Page 53
Name : GetFaultErrorLog7YearDayMonth Modbus Function : 03 Modbus Register Address : 4073 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.07 '07' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
53
Page 54
Name : GetFaultErrorLog8Index Modbus Function : 03 Modbus Register Address : 4075 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.08 '08'
Name : GetFaultErrorLog8Fault Modbus Function : 03 Modbus Register Address : 4076 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.08 '08' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog8RunningState Modbus Function : 03 Modbus Register Address : 4077 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.08 '08' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
54
Page 55
Name : GetFaultErrorLog8CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 4079 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.08 '08' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog8CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 407A Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.08 '08' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog8CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 407B Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.08 '08' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog8WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 407C Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.08 '08' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
55
Page 56
Name : GetFaultErrorLog8YearDayMonth Modbus Function : 03 Modbus Register Address : 407E Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.08 '08' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
56
Page 57
Name : GetFaultErrorLog9Index Modbus Function : 03 Modbus Register Address : 4080 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.09 '09'
Name : GetFaultErrorLog9Fault Modbus Function : 03 Modbus Register Address : 4081 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.09 '09' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog9RunningState Modbus Function : 03 Modbus Register Address : 4082 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.09 '09' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
57
Page 58
Name : GetFaultErrorLog9CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 4084 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.09 '09' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog9CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 4085 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.09 '09' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog9CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 4086 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.09 '09' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog9WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 4087 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.09 '09' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
58
Page 59
Name : GetFaultErrorLog9YearDayMonth Modbus Function : 03 Modbus Register Address : 4089 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.09 '09' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
59
Page 60
Name : GetFaultErrorLog10Index Modbus Function : 03 Modbus Register Address : 408B Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.10 '10'
Name : GetFaultErrorLog10Fault Modbus Function : 03 Modbus Register Address : 408C Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.10 '10' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog10RunningState Modbus Function : 03 Modbus Register Address : 408D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.10 '10' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
60
Page 61
Name : GetFaultErrorLog10CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 408F Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.10 '10' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog10CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 4090 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.10 '10' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog10CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 4091 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.10 '10' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog10WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 4092 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.10 '10' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
61
Page 62
Name : GetFaultErrorLog10YearDayMonth Modbus Function : 03 Modbus Register Address : 4094 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.10 '10' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
62
Page 63
Name : GetFaultErrorLog11Index Modbus Function : 03 Modbus Register Address : 4096 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.11 '11'
Name : GetFaultErrorLog11Fault Modbus Function : 03 Modbus Register Address : 4097 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.11 '11' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog11RunningState Modbus Function : 03 Modbus Register Address : 4098 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.11 '11' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
63
Page 64
Name : GetFaultErrorLog11CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 409A Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.11 '11' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog11CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 409B Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.11 '11' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog11CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 409C Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.11 '11' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog11WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 409D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.11 '11' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
64
Page 65
Name : GetFaultErrorLog11YearDayMonth Modbus Function : 03 Modbus Register Address : 409F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.11 '11' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
65
Page 66
Name : GetFaultErrorLog12Index Modbus Function : 03 Modbus Register Address : 40A1 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.12 '12'
Name : GetFaultErrorLog12Fault Modbus Function : 03 Modbus Register Address : 40A2 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.12 '12' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog12RunningState Modbus Function : 03 Modbus Register Address : 40A3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.12 '12' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
66
Page 67
Name : GetFaultErrorLog12CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 40A5 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.12 '12' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog12CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 40A6 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.12 '12' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog12CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 40A7 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.12 '12' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog12WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 40A8 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.12 '12' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
67
Page 68
Name : GetFaultErrorLog12YearDayMonth Modbus Function : 03 Modbus Register Address : 40AA Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.12 '12' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
68
Page 69
Name : GetFaultErrorLog13Index Modbus Function : 03 Modbus Register Address : 40AC Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.13 '13'
Name : GetFaultErrorLog13Fault Modbus Function : 03 Modbus Register Address : 40AD Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.13 '13' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog13RunningState Modbus Function : 03 Modbus Register Address : 40AE Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.13 '13' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
69
Page 70
Name : GetFaultErrorLog13CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 40B0 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.13 '13' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog13CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 40B1 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.13 '13' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog13CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 40B2 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.13 '13' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog13WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 40B3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.13 '13' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
70
Page 71
Name : GetFaultErrorLog13YearDayMonth Modbus Function : 03 Modbus Register Address : 40B5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.13 '13' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
71
Page 72
Name : GetFaultErrorLog14Index Modbus Function : 03 Modbus Register Address : 40B7 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.14 '14'
Name : GetFaultErrorLog14Fault Modbus Function : 03 Modbus Register Address : 40B8 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.14 '14' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog14RunningState Modbus Function : 03 Modbus Register Address : 40B9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.14 '14' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
72
Page 73
Name : GetFaultErrorLog14CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 40BB Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.14 '14' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog14CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 40BC Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.14 '14' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog14CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 40BD Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.14 '14' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog14WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 40BE Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.14 '14' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
73
Page 74
Name : GetFaultErrorLog14YearDayMonth Modbus Function : 03 Modbus Register Address : 40C0 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.14 '14' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
74
Page 75
Name : GetFaultErrorLog15Index Modbus Function : 03 Modbus Register Address : 40C2 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Menu = E01.15 '15'
Name : GetFaultErrorLog15Fault Modbus Function : 03 Modbus Register Address : 40C3 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Conversion Type = CODED,ERROR Conversion table for CODED,ERROR can be found at the end of this document Menu = E01.15 '15' 16 bit value: fault log error entry, see "CODED,ERROR" table for list of error numbers <=> error definitions. MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog15RunningState Modbus Function : 03 Modbus Register Address : 40C4 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = LONG_VAL Menu = E01.15 '15' 32 bit value: system state flags/conditions at time of error Bitvalue = 0 => flag/cond. = OFF, 1 => flag/cond. = ON Lowest order bit of 32 bit value = Bit 0 . Bits 0...7 => Internal digital inputs state (inp 1...8) . Bits 8...15 => External digital inputs state (inp 1...8) . Bits 16...18 => Numerical value for control mode: . 1 = FIFO CONTROL MODE . 2 = ENERGY CONTROL MODE . 3 = TIME ROTATION . 4 = EQUAL HOURS CONTROL MODE . Bit 19: system in standby (pressure schedule) . Bits 20...23 => selected table number (1...6) . Bit 24: schedule override on . Bit 25: auto restart on . Bit 26: double zoning on . Bit 27: triple zoning on . Bits 28...31: unused,always 0 MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable. (start = Fault, end = YearDayMonth)
75
Page 76
Name : GetFaultErrorLog15CompressorStateBits0 Modbus Function : 03 Modbus Register Address : 40C6 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.15 '15' 16 bit value: state bits (0) for compressors 1...8 Bitvalue = 0 => state bit = OFF, 1 => state bit = ON Lowest order bit of 16 bit value = Bit 0 . Bits 0...7 => state bits 0 for compressors 1...8 . Bits 8...15: unused,always 0 State bits 0, 1 and 2 for each compressor yield a 3 bit value representing the compressor status at the time of error . 0 => COMPRESSOR UNAVAILABLE . 1 => COMPRESOOR INACTIVE . 2 => COMPRESSOR MAINTENANCE . 3 => COMPRESSOR STANDBY . 4 => COMPRESSOR RUNNING . 5 => COMPRESSOR LOADED MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
Name : GetFaultErrorLog15CompressorStateBits1 Modbus Function : 03 Modbus Register Address : 40C7 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.15 '15' 16 bit value: state bits (1) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog15CompressorStateBits2 Modbus Function : 03 Modbus Register Address : 40C8 Modbus Register Length : 0001 Coding : Number of data bytes = 2 Data Units = UINT_VAL Menu = E01.15 '15' 16 bit value: state bits (2) for compressors 1...8 Data structure/MODBUS notes: see previous item
Name : GetFaultErrorLog15WeekdayHoursMinutes Modbus Function : 03 Modbus Register Address : 40C9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = D_HH_MM Menu = E01.15 '15' 32 bit value: weekday/ hours/minutes at time of error Value/60 => integer remainder = minutes Value/6000 => integer remainder/60 => result = hours Value/10000 => result = day of week MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
76
Page 77
Name : GetFaultErrorLog15YearDayMonth Modbus Function : 03 Modbus Register Address : 40CB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = YYYY_DD_MO Menu = E01.15 '15' 32 bit value: year/day/month at time of error Value/100 => integer remainder = month Value/10000 => integer remainder/100 => result = day of month Value/10000 => result = year MODBUS: register can be requested individually or as part of a multiple register data request. Any request for register data with a base address and number of registers that falls within the address range for this fault error log data block is acceptable.(start = Fault, end = YearDayMonth)
77
Page 78
Name : GetMaximumPressure Modbus Function : 03 Modbus Register Address : 40CD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = S02.03 'PM'
Name : SetMaximumPressure Modbus Function : 10 Modbus Register Address : 40CD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = S02.03 'PM'
Name : GetHighPressureSetting1 Modbus Function : 03 Modbus Register Address : 40CF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T01.01 'PH'
Name : SetHighPressureSetting1 Modbus Function : 10 Modbus Register Address : 40CF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T01.01 'PH'
Name : GetHighPressureSetting2 Modbus Function : 03 Modbus Register Address : 40D1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T02.01 'PH'
Name : SetHighPressureSetting2 Modbus Function : 10 Modbus Register Address : 40D1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T02.01 'PH'
Name : GetHighPressureSetting3 Modbus Function : 03 Modbus Register Address : 40D3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T03.01 'PH'
Name : SetHighPressureSetting3 Modbus Function : 10 Modbus Register Address : 40D3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T03.01 'PH'
78
Page 79
Name : GetHighPressureSetting4 Modbus Function : 03 Modbus Register Address : 40D5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T04.01 'PH'
Name : SetHighPressureSetting4 Modbus Function : 10 Modbus Register Address : 40D5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T04.01 'PH'
Name : GetLowPressureSetting1 Modbus Function : 03 Modbus Register Address : 40DB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T01.02 'PL'
Name : SetLowPressureSetting1 Modbus Function : 10 Modbus Register Address : 40DB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T01.02 'PL'
Name : GetLowPressureSetting2 Modbus Function : 03 Modbus Register Address : 40DD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T02.02 'PL'
Name : SetLowPressureSetting2 Modbus Function : 10 Modbus Register Address : 40DD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T02.02 'PL'
Name : GetLowPressureSetting3 Modbus Function : 03 Modbus Register Address : 40DF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T03.02 'PL'
Name : SetLowPressureSetting3 Modbus Function : 10 Modbus Register Address : 40DF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T03.02 'PL'
79
Page 80
Name : GetLowPressureSetting4 Modbus Function : 03 Modbus Register Address : 40E1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T04.02 'PL'
Name : SetLowPressureSetting4 Modbus Function : 10 Modbus Register Address : 40E1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T04.02 'PL'
Name : GetMinimumPressure1 Modbus Function : 03 Modbus Register Address : 40E7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T01.03 'Pm'
Name : SetMinimumPressure1 Modbus Function : 10 Modbus Register Address : 40E7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T01.03 'Pm'
Name : GetMinimumPressure2 Modbus Function : 03 Modbus Register Address : 40E9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T02.03 'Pm'
Name : SetMinimumPressure2 Modbus Function : 10 Modbus Register Address : 40E9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T02.03 'Pm'
Name : GetMinimumPressure3 Modbus Function : 03 Modbus Register Address : 40EB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T03.03 'Pm'
Name : SetMinimumPressure3 Modbus Function : 10 Modbus Register Address : 40EB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T03.03 'Pm'
80
Page 81
Name : GetMinimumPressure4 Modbus Function : 03 Modbus Register Address : 40ED Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T04.03 'Pm'
Name : SetMinimumPressure4 Modbus Function : 10 Modbus Register Address : 40ED Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = T04.03 'Pm'
Name : GetDampingFactorSetting Modbus Function : 03 Modbus Register Address : 40F3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = S02.06 'DA'
Name : SetDampingFactorSetting Modbus Function : 10 Modbus Register Address : 40F3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = S02.06 'DA'
Name : GetTolerance Modbus Function : 03 Modbus Register Address : 40F5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = S02.05 'TO'
Name : SetTolerance Modbus Function : 10 Modbus Register Address : 40F5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = S02.05 'TO'
Name : GetStartDelay1 Modbus Function : 03 Modbus Register Address : 40F7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetStartDelay1 Modbus Function : 10 Modbus Register Address : 40F7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
81
Page 82
Name : GetStartDelay2 Modbus Function : 03 Modbus Register Address : 40F9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetStartDelay2 Modbus Function : 10 Modbus Register Address : 40F9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetStartDelay3 Modbus Function : 03 Modbus Register Address : 40FB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetStartDelay3 Modbus Function : 10 Modbus Register Address : 40FB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetStartDelay4 Modbus Function : 03 Modbus Register Address : 40FD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetStartDelay4 Modbus Function : 10 Modbus Register Address : 40FD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetStartDelay5 Modbus Function : 03 Modbus Register Address : 40FF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetStartDelay5 Modbus Function : 10 Modbus Register Address : 40FF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
82
Page 83
Name : GetStartDelay6 Modbus Function : 03 Modbus Register Address : 4101 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetStartDelay6 Modbus Function : 10 Modbus Register Address : 4101 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetStartDelay7 Modbus Function : 03 Modbus Register Address : 4103 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetStartDelay7 Modbus Function : 10 Modbus Register Address : 4103 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetStartDelay8 Modbus Function : 03 Modbus Register Address : 4105 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetStartDelay8 Modbus Function : 10 Modbus Register Address : 4105 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetRunOnTimeSetting1 Modbus Function : 03 Modbus Register Address : 410F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetRunOnTimeSetting1 Modbus Function : 10 Modbus Register Address : 410F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
83
Page 84
Name : GetRunOnTimeSetting2 Modbus Function : 03 Modbus Register Address : 4111 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetRunOnTimeSetting2 Modbus Function : 10 Modbus Register Address : 4111 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetRunOnTimeSetting3 Modbus Function : 03 Modbus Register Address : 4113 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetRunOnTimeSetting3 Modbus Function : 10 Modbus Register Address : 4113 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetRunOnTimeSetting4 Modbus Function : 03 Modbus Register Address : 4115 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetRunOnTimeSetting4 Modbus Function : 10 Modbus Register Address : 4115 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetRunOnTimeSetting5 Modbus Function : 03 Modbus Register Address : 4117 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetRunOnTimeSetting5 Modbus Function : 10 Modbus Register Address : 4117 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
84
Page 85
Name : GetRunOnTimeSetting6 Modbus Function : 03 Modbus Register Address : 4119 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetRunOnTimeSetting6 Modbus Function : 10 Modbus Register Address : 4119 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetRunOnTimeSetting7 Modbus Function : 03 Modbus Register Address : 411B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetRunOnTimeSetting7 Modbus Function : 10 Modbus Register Address : 411B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetRunOnTimeSetting8 Modbus Function : 03 Modbus Register Address : 411D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : SetRunOnTimeSetting8 Modbus Function : 10 Modbus Register Address : 411D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mSEC
Name : GetPrefillCompressor1 Modbus Function : 03 Modbus Register Address : 4143 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.04 '01'
Name : SetPrefillCompressor1 Modbus Function : 10 Modbus Register Address : 4143 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.04 '01'
85
Page 86
Name : GetPrefillCompressor2 Modbus Function : 03 Modbus Register Address : 4145 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.05 '02'
Name : SetPrefillCompressor2 Modbus Function : 10 Modbus Register Address : 4145 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.05 '02'
Name : GetPrefillCompressor3 Modbus Function : 03 Modbus Register Address : 4147 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.06 '03'
Name : SetPrefillCompressor3 Modbus Function : 10 Modbus Register Address : 4147 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.06 '03'
Name : GetPrefillCompressor4 Modbus Function : 03 Modbus Register Address : 4149 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.07 '04'
Name : SetPrefillCompressor4 Modbus Function : 10 Modbus Register Address : 4149 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.07 '04'
Name : GetPrefillCompressor5 Modbus Function : 03 Modbus Register Address : 414B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.08 '05'
Name : SetPrefillCompressor5 Modbus Function : 10 Modbus Register Address : 414B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.08 '05'
86
Page 87
Name : GetPrefillCompressor6 Modbus Function : 03 Modbus Register Address : 414D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.09 '06'
Name : SetPrefillCompressor6 Modbus Function : 10 Modbus Register Address : 414D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.09 '06'
Name : GetPrefillCompressor7 Modbus Function : 03 Modbus Register Address : 414F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.10 '07'
Name : SetPrefillCompressor7 Modbus Function : 10 Modbus Register Address : 414F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.10 '07'
Name : GetPrefillCompressor8 Modbus Function : 03 Modbus Register Address : 4151 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.11 '08'
Name : SetPrefillCompressor8 Modbus Function : 10 Modbus Register Address : 4151 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.11 '08'
Name : GetPrefillDelaySetting Modbus Function : 03 Modbus Register Address : 415B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = SEC Menu = P02.02 'PT'
Name : SetPrefillDelaySetting Modbus Function : 10 Modbus Register Address : 415B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = SEC Menu = P02.02 'PT'
87
Page 88
Name : GetPrefillFunction Modbus Function : 03 Modbus Register Address : 415F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.01 'PF'
Name : SetPrefillFunction Modbus Function : 10 Modbus Register Address : 415F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = P02.01 'PF'
Name : GetPressureChangeSetting Modbus Function : 03 Modbus Register Address : 4167 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = SEC Menu = S02.07 'PC'
Name : SetPressureChangeSetting Modbus Function : 10 Modbus Register Address : 4167 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = SEC Menu = S02.07 'PC'
Name : GetAuxiliaryInput Modbus Function : 03 Modbus Register Address : 4169 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = S02.10 'AI'
Name : SetAuxiliaryInput Modbus Function : 10 Modbus Register Address : 4169 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = S02.10 'AI'
Name : GetAuxiliaryOutput Modbus Function : 03 Modbus Register Address : 416B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = S02.11 'AO'
Name : SetAuxiliaryOutput Modbus Function : 10 Modbus Register Address : 416B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = S02.11 'AO'
88
Page 89
Name : GetNominalPower1 Modbus Function : 03 Modbus Register Address : 416D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetNominalPower1 Modbus Function : 10 Modbus Register Address : 416D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetNominalPower2 Modbus Function : 03 Modbus Register Address : 416F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetNominalPower2 Modbus Function : 10 Modbus Register Address : 416F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetNominalPower3 Modbus Function : 03 Modbus Register Address : 4171 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetNominalPower3 Modbus Function : 10 Modbus Register Address : 4171 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetNominalPower4 Modbus Function : 03 Modbus Register Address : 4173 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetNominalPower4 Modbus Function : 10 Modbus Register Address : 4173 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
89
Page 90
Name : GetNominalPower5 Modbus Function : 03 Modbus Register Address : 4175 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetNominalPower5 Modbus Function : 10 Modbus Register Address : 4175 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetNominalPower6 Modbus Function : 03 Modbus Register Address : 4177 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetNominalPower6 Modbus Function : 10 Modbus Register Address : 4177 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetNominalPower7 Modbus Function : 03 Modbus Register Address : 4179 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetNominalPower7 Modbus Function : 10 Modbus Register Address : 4179 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetNominalPower8 Modbus Function : 03 Modbus Register Address : 417B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetNominalPower8 Modbus Function : 10 Modbus Register Address : 417B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
90
Page 91
Name : GetMinimumPower1 Modbus Function : 03 Modbus Register Address : 4185 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetMinimumPower1 Modbus Function : 10 Modbus Register Address : 4185 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetMinimumPower2 Modbus Function : 03 Modbus Register Address : 4187 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetMinimumPower2 Modbus Function : 10 Modbus Register Address : 4187 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetMinimumPower3 Modbus Function : 03 Modbus Register Address : 4189 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetMinimumPower3 Modbus Function : 10 Modbus Register Address : 4189 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetMinimumPower4 Modbus Function : 03 Modbus Register Address : 418B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetMinimumPower4 Modbus Function : 10 Modbus Register Address : 418B Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
91
Page 92
Name : GetMinimumPower5 Modbus Function : 03 Modbus Register Address : 418D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetMinimumPower5 Modbus Function : 10 Modbus Register Address : 418D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetMinimumPower6 Modbus Function : 03 Modbus Register Address : 418F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetMinimumPower6 Modbus Function : 10 Modbus Register Address : 418F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetMinimumPower7 Modbus Function : 03 Modbus Register Address : 4191 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetMinimumPower7 Modbus Function : 10 Modbus Register Address : 4191 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetMinimumPower8 Modbus Function : 03 Modbus Register Address : 4193 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetMinimumPower8 Modbus Function : 10 Modbus Register Address : 4193 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
92
Page 93
Name : GetRunningHours1 Modbus Function : 03 Modbus Register Address : 419D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.01 '01'
Name : SetRunningHours1 Modbus Function : 10 Modbus Register Address : 419D Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.01 '01'
Name : GetRunningHours2 Modbus Function : 03 Modbus Register Address : 419F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.02 '02'
Name : SetRunningHours2 Modbus Function : 10 Modbus Register Address : 419F Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.02 '02'
Name : GetRunningHours3 Modbus Function : 03 Modbus Register Address : 41A1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.03 '03'
Name : SetRunningHours3 Modbus Function : 10 Modbus Register Address : 41A1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.03 '03'
Name : GetRunningHours4 Modbus Function : 03 Modbus Register Address : 41A3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.04 '04'
Name : SetRunningHours4 Modbus Function : 10 Modbus Register Address : 41A3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.04 '04'
93
Page 94
Name : GetRunningHours5 Modbus Function : 03 Modbus Register Address : 41A5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.05 '05'
Name : SetRunningHours5 Modbus Function : 10 Modbus Register Address : 41A5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.05 '05'
Name : GetRunningHours6 Modbus Function : 03 Modbus Register Address : 41A7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.06 '06'
Name : SetRunningHours6 Modbus Function : 10 Modbus Register Address : 41A7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.06 '06'
Name : GetRunningHours7 Modbus Function : 03 Modbus Register Address : 41A9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.07 '07'
Name : SetRunningHours7 Modbus Function : 10 Modbus Register Address : 41A9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.07 '07'
Name : GetRunningHours8 Modbus Function : 03 Modbus Register Address : 41AB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.08 '08'
Name : SetRunningHours8 Modbus Function : 10 Modbus Register Address : 41AB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = ULONG_VAL Menu = C01.08 '08'
94
Page 95
Name : GetAlarmSignalType1 Modbus Function : 03 Modbus Register Address : 41B5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetAlarmSignalType1 Modbus Function : 10 Modbus Register Address : 41B5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetAlarmSignalType2 Modbus Function : 03 Modbus Register Address : 41B7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetAlarmSignalType2 Modbus Function : 10 Modbus Register Address : 41B7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetAlarmSignalType3 Modbus Function : 03 Modbus Register Address : 41B9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetAlarmSignalType3 Modbus Function : 10 Modbus Register Address : 41B9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetAlarmSignalType4 Modbus Function : 03 Modbus Register Address : 41BB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetAlarmSignalType4 Modbus Function : 10 Modbus Register Address : 41BB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
95
Page 96
Name : GetAlarmSignalType5 Modbus Function : 03 Modbus Register Address : 41BD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetAlarmSignalType5 Modbus Function : 10 Modbus Register Address : 41BD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetAlarmSignalType6 Modbus Function : 03 Modbus Register Address : 41BF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetAlarmSignalType6 Modbus Function : 10 Modbus Register Address : 41BF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetAlarmSignalType7 Modbus Function : 03 Modbus Register Address : 41C1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetAlarmSignalType7 Modbus Function : 10 Modbus Register Address : 41C1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : GetAlarmSignalType8 Modbus Function : 03 Modbus Register Address : 41C3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
Name : SetAlarmSignalType8 Modbus Function : 10 Modbus Register Address : 41C3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL
96
Page 97
Name : GetNoMaintenance1 Modbus Function : 03 Modbus Register Address : 41CD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.01 '01'
Name : SetNoMaintenance1 Modbus Function : 10 Modbus Register Address : 41CD Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.01 '01'
Name : GetNoMaintenance2 Modbus Function : 03 Modbus Register Address : 41CF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.02 '02'
Name : SetNoMaintenance2 Modbus Function : 10 Modbus Register Address : 41CF Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.02 '02'
Name : GetNoMaintenance3 Modbus Function : 03 Modbus Register Address : 41D1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.03 '03'
Name : SetNoMaintenance3 Modbus Function : 10 Modbus Register Address : 41D1 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.03 '03'
Name : GetNoMaintenance4 Modbus Function : 03 Modbus Register Address : 41D3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.04 '04'
Name : SetNoMaintenance4 Modbus Function : 10 Modbus Register Address : 41D3 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.04 '04'
97
Page 98
Name : GetNoMaintenance5 Modbus Function : 03 Modbus Register Address : 41D5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.05 '05'
Name : SetNoMaintenance5 Modbus Function : 10 Modbus Register Address : 41D5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.05 '05'
Name : GetNoMaintenance6 Modbus Function : 03 Modbus Register Address : 41D7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.06 '06'
Name : SetNoMaintenance6 Modbus Function : 10 Modbus Register Address : 41D7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.06 '06'
Name : GetNoMaintenance7 Modbus Function : 03 Modbus Register Address : 41D9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.07 '07'
Name : SetNoMaintenance7 Modbus Function : 10 Modbus Register Address : 41D9 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.07 '07'
Name : GetNoMaintenance8 Modbus Function : 03 Modbus Register Address : 41DB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.08 '08'
Name : SetNoMaintenance8 Modbus Function : 10 Modbus Register Address : 41DB Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = C02.08 '08'
98
Page 99
Name : GetAuxiliaryBoxOn1 Modbus Function : 03 Modbus Register Address : 41E5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = S03.01 '01'
Name : SetAuxiliaryBoxOn1 Modbus Function : 10 Modbus Register Address : 41E5 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = S03.01 '01'
Name : GetAuxiliaryBoxOn2 Modbus Function : 03 Modbus Register Address : 41E7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = S03.02 '02'
Name : SetAuxiliaryBoxOn2 Modbus Function : 10 Modbus Register Address : 41E7 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = UCHAR_VAL Menu = S03.02 '02'
Name : GetPrefillPressure Modbus Function : 03 Modbus Register Address : 4203 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P02.03 'PP'
Name : SetPrefillPressure Modbus Function : 10 Modbus Register Address : 4203 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = mBAR Menu = P02.03 'PP'
Name : GetLowestEfficientSpeed1 Modbus Function : 03 Modbus Register Address : 4211 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetLowestEfficientSpeed1 Modbus Function : 10 Modbus Register Address : 4211 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
99
Page 100
Name : GetLowestEfficientSpeed2 Modbus Function : 03 Modbus Register Address : 4213 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetLowestEfficientSpeed2 Modbus Function : 10 Modbus Register Address : 4213 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetLowestEfficientSpeed3 Modbus Function : 03 Modbus Register Address : 4215 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetLowestEfficientSpeed3 Modbus Function : 10 Modbus Register Address : 4215 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetLowestEfficientSpeed4 Modbus Function : 03 Modbus Register Address : 4217 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetLowestEfficientSpeed4 Modbus Function : 10 Modbus Register Address : 4217 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : GetLowestEfficientSpeed5 Modbus Function : 03 Modbus Register Address : 4219 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
Name : SetLowestEfficientSpeed5 Modbus Function : 10 Modbus Register Address : 4219 Modbus Register Length : 0002 Coding : Number of data bytes = 4 Data Units = PERCENT
100
Loading...