Quick Reference Guide
Voyager ™
12.5 to 25 Tons Packaged Rooftop Units
Cooling & Gas/Electric
Table 1. Model number description
T*D Cooling Only (Electric Heat Optional), Downflow
T*H Cooling Only (Electric Heat Optional), Horizontal
Y*D Gas Heat Unit, Downflow
Y*H Gas Heat Unit, Horizontal
* Standard (S) or High (H) Efficiency
March 2017
RT-PRC038K-EN
© 2017 Ingersoll Rand
1
Table 2. List of factory installed options (FIOPs)
2” MERV 8 or MERV 13 Pleated Filters w/ Removal Tool Hinged Access Panels
Air-Fi™ Wireless Communication Interface (WCI) Horizontal Side Access with Circuit Breaker
BACnet™ Communication Interface (BCI) Horizontal Side Access with Disconnect Switch
Barometric Relief
Clogged Filter/Fan Failure Switch
Complete Coat™ Microchannel Condenser Coil Motor Shaft Grounding Ring
Condensate Overflow Switch Oversized Motors
DCV Harness Powered/Unpowered Convenience Outlet
Dehumidification Stainless Steel Drain Pan
Delivered VAV
Discharge Air Sensing Kit
Economizer - Low Leak/Downflow
Economizer - Standard/Downflow
Electric Heaters Through the Base Gas Provision
Fault Detection & Diagnostics (FDD) Tool-less Hail Guard
Frostat™
High Efficiency Motors Two Speed Fan Provision
High Short Circuit Current Rated (SCCR) Electrical
Subsystem
(a) Most Factory Installed Options are available for downflow air discharge units only. Verify with ordering system
for availability.
(b)Requires an Economizer.
(c) Some field set up required.
(d)Requires ReliaTel Options Module.
(e) Available with Two Speed Fan or Variable Speed Fan.
(f) Must be ordered with Through the Base Electrical option or Horizontal Side Access, and either Unit Mounted
Disconnect switch or Circuit Breaker.
(g)Standard on high efficiency units.
(h)TCI is for use with non-VariTrac™ systems and VariTrac systems.
(i) Available on 208V/60 Hz, 230V/60 Hz, and 480V/60 Hz only.
(d)(g)
(i)
(b) (c)
(d)
(d)
(d)
(c)
Through the Base Electrical with Circuit Breaker
(c)
(a)
LonTalk® Communication Interface (LCI)
Modulating Gas Heat Furnace w/ a 2.5:1 T urndown Ratio
Stainless Steel Heat Exchanger
Supply & Return Air Smoke Detectors
Through the Base Electrical with Disconnect Switch
Trane® Communication Interface (TCI)
Variable Speed Fan Provision for Single Zone VAV
(e)
(f)
(d)
(h)
(d)
2
Table 3. 12½-25 ton packaged rooftop performance data (gas or electric heat)
Cooling Performance
Nominal Airflow CFM / ARI Rated CFM 5,000/4,000 6,000/5,400 7,000/6,125 8,000/6,400 10,000/7,750 5,000/4,000 6,000/5,250 7,000/5,600 8,000/6,400 10,000/8,000
Tot / Sens Cap (MBh)
EER
IEER (One Speed Fan / Multi or Variable
Speed Fan)
Gas Heating Performance
Low Heat (Input/output) - (MBh) 150.0/120.0 250.0/200.0 250.0/200.0 250.0/200.0 250.0/200.0 150.0/120.0 250.0/200.0 250.0/200.0 250.0/200.0 250.0/200.0
Medium Heat (Input/output) - (MBh) 350.0/280.0 350.0/280.0 350.0/280.0 350.0/280.0 350.0/280.0 350.0/280.0 350.0/280.0 350.0/280.0 350.0/280.0 350.0/280.0
High Heat (Input/output) - (MBh) 250.0/200.0 350.0/280.0 350.0/280.0 400.0/320.0 400.0/320.0 250.0/200.0 350.0/280.0 350.0/280.0 400.0/320.0 400.0/320.0
Weight
Net Weight (Lbs) - Gas Heat 1448 1838 1894 1977 2020 1 971 2222 2186 2257 2291
Net Weight (Lbs) - Electric Heat 1373 1763 1819 1902 1945 1868 2076 2037 2107 2108
Roof curb BAYCURB026B BAYCURB027B
Unit Cabinet Size BC C+
Filters
Downflow - Number & Size Recommended (2) 20x20x2
Horizontal - Number & Size Recommended (2) 20x20x2
(a)Cooling performance is rated at 80/67/95 & 400 cfm/ton.
(b)Short orifice metering device.
(c) EER is rated at ARI conditions and in accordance with ARI standard 210/240 or 340/360.
(d)Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
(e)T/YS*211 = 11.8/12.9. T/YS*301 = 10.4/12.0
(f) Verify option availability in product data catalog.
(g)Optional 2” MERV 8 and MERV 13 filters also available.
Nominal Size (Tons) 12.5 15 17.5 20 25 12.5 15 17.5 20 25
(c)
(d)
(g)
- Type Furnished
(a) (b)
(f)
150.1/116.0 186.1/139.1 210.3/165.0 258.9/197.3 296.4/228.4 149.6/113.4 181.5/138.0 212.7/165.5 259.0/192.5 295.3/234.2
11 11 11 10.0 10.0 12.1 12.1 11.8 11.0 10.6
TS*=12.4/13.5
YS*=12.2/13.5
Throwaway Throwaway Throwaway Throwaway Throwaway Throwaway Throwaway Throwaway Throwaway Throwaway
(4) 20x25x2
(4) 20x25x2
TS*=12.4/13.2
YS*=12.2/13.2
(4) 20x20x2
(4) 20x25x2
(8) 20x25x2 (8) 20x25x2 (8) 20x25x2 (8) 20x25x2 (8) 20x25x2 (12) 20x20x2 (12) 20x20x2 (12) 20x20x2 (12) 20x20x2
Standard Efficiency High Efficiency
TS*=12.4/13.2
YS*=12.2/13.2
(4) 20x20x2
(4) 20x25x2
TS*=11.6/12.4
(e)
YS*=11.4/12.4
(4) 20x20x2
(4) 20x25x2
TS*=11.6/12.4
YS*=11.4/12.4
(4) 20x20x2
(4) 20x25x2
13.5/15.0 14.0/15.0 13.0/14.0 12.4/14.0 12.4/15.0
(e)
(4) 20x20x2
(4) 20x25x2
(8) 20x20x2
(4) 20x16x2
(8) 20x20x2
(4) 20x16x2
(8) 20x20x2
(4) 20x16x2
(8) 20x20x2
(4) 20x16x2
3
Table 4. Unit MCA & MOP electrical data (standard indoor fan motor)
T/YS* Volts MCA MOP T/YH* Volts MCA MOP
150 208-230/3 61 80 150 208-230/3 64 90
460/3 29 40 460/3 30 40
575/3 22 30 575/3 23 30
380/3 36 45 180 208-230/3 68 90
180 208-230/3 69 90 460/3 33 45
460/3 34 45 575/3 25 35
575/3 31 40 210 208-230/3 83 110
380/3 45 60 460/3 41 50
210/211 208-230/3 77 100 575/3 33 45
460/3 37 50 240 208-230/3 96 125
575/3 34 45 460/3 44 60
380/3 52 70 575/3 38 50
240 208-230/3 105 125 300 208-230/3 117 150
460/3 50 70 460/3 54 70
575/3 43 60 575/3 44 50
380/3 60 80
300/301
208-230/3 112 150
460/3 53 70
575/3 45 60
380/3 69 90
5
Table 6. Unit dimensional data
Unit Length UL 106 11/16 122 5/16 122 5/16
Unit Width UW 70 13/16 84 3/16 84 3/16
Unit Height UH 52 1/4 56 1/8 66 1/4
Clearance C1 60 60 60
Clearance C2 48 48 48
Clearance C3 36 1/8 36 1/8 36 1/8
Clearance C4 38 38 38
Clearance C5 72 72 72
Curb Length CL 102 1/2 116 7/8 116 7/8
Curb Width CW 67 81 81
Supply Length SL
Supply Width SW
Return Length RL
Return Width RW
BCC+
(a)
28 1/2 28 9/16 28 9/16
(a)
55 1/2 69 1/2 69 1/2
(a)
20 7/8 22 1/4 22 1/4
(a)
63 77 77
RL
RW
CL
SL
SW
CW
4
Table 5. Unit indoor fan data
Standard
HP - RPM
208-230/3 208-230/3
150
460/3 3 - 1740 5 - 3450
575/3 575/3
380/3 5 - 3450 N/A 208-230/3
180 208-230/3
460/3 3 - 1740 5 - 3450 575/3
575/3 208-230/3
380/3 5 - 3450 N/ A
208-230/3 575/3
210/
211
240
300/
301
Ingersoll Rand (NYSE:IR) advances the quality of life by creating comfortable, sustainable and efficient environments.
Our people and our family of brands—including Club Car
to enhance the quality and comfort of air in homes and buildings; transport and protect food and perishables; and
increase industrial productivity and efficiency. We are a global business committed to a world of sustainable progress
and enduring results.
460/3 5 - 3450 7.5 - 3470 208-230/3
575/3
380/3 7.5 - 3470 N/A 575/3
208-230/3 208-230/3
460/3 5 - 3450 7.5 - 3470
575/3 575/3
380/3 7.5 - 3470 N/A
208-230/3
460/3 7.5 - 3470 N/A
575/3
380/3
Oversized
HP - RPM T/YH* Volts
150
180
210
240
300
®
, Ingersoll Rand®, Thermo King® and Trane®—work together
460/3 3 - 1740 5 - 3450
460/3 3 - 1740 5 - 3450
460/3 5 - 3450 7.5 - 3470
460/3 5 - 3450 7.5 - 3470
460/3 7.5 - 3470 N/A
Standard
HP - RPM
Oversized
HP - RPMT/YS* Volts
Ingersoll Rand has a policy of continuous product and product data improvement and reserves the right to change design and specifications without
notice.
We are committed to using environmentally conscious print practices.
(a) Dimensions are for curb openings and not duct inserts. Reference the product catalog for duct insert
dimensions.
RT-PRC038K-EN 17 Mar 2017
Supersedes RT-PRC038J-EN (24 Feb 2017)