Ingersoll-Rand TEM6A0B24H21S, TEM6A0C48H41S, TEM6A0B30H21S, TEM6A0D48H41S, TEM6A0D60H51S Installer's Manual

...
Installer’s Guide
Convertible Air Handlers 2 — 5 Ton
TEM6A0B24H21S TEM6A0B30H21S TEM6A0C36H31S TEM6A0C42H41S TEM6A0C48H41S TEM6A0D48H41S TEM6A0C60H51S TEM6A0D60H51S
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
January 2016
The TEM6 series air handler is designed for installation in a closet, utility room, alcove, basement, crawlspace or attic. These versatile units are applicable to air conditioning and heat pump applications. Several models are available to meet the specific requirements of the outdoor equipment. Field installed electric resistance heaters are available.
SSAAFFEETTYY WWAARRNNIINNGG
18-GF74D1-1F-EN
SAFETY SECTION AIR HANDLERS
IImmppoorrttaanntt:: This document contains a wiring diagram,
a parts list, and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
IImmppoorrttaanntt:: These instructions do not cover all
variations in systems nor provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
WWAARRNNIINNGG
HHAAZZAARRDDOOUUSS VVOOLLTTAAGGEE!!
FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinn pprrooppeerrttyy ddaammaaggee,, sseevveerree ppeerrssoonnaall iinnjjuurryy,, oorr ddeeaatthh.. DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaannnnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd..
CCAAUUTTIIOONN
GGRROOUUNNDDIINNGG RREEQQUUIIRREEDD!!
FFaaiilluurree ttoo iinnssppeecctt oorr uussee pprrooppeerr sseerrvviiccee ttoooollss mmaayy rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy.. RReeccoonnnneecctt aallll ggrroouunnddiinngg ddeevviicceess.. AAllll ppaarrttss ooff tthhiiss pprroodduucctt tthhaatt aarree ccaappaabbllee ooff ccoonndduuccttiinngg eelleeccttrriiccaall ccuurrrreenntt aarree ggrroouunnddeedd.. IIff ggrroouunnddiinngg wwiirreess,, ssccrreewwss,, ssttrraappss,, cclliippss,, nnuuttss,, oorr wwaasshheerrss uusseedd ttoo ccoommpplleettee aa ppaatthh ttoo ggrroouunndd aarree rreemmoovveedd ffoorr sseerrvviiccee,, tthheeyy mmuusstt bbee rreettuurrnneedd ttoo tthheeiirr oorriiggiinnaall ppoossiittiioonn aanndd pprrooppeerrllyy ffaasstteenneedd..
WWAARRNNIINNGG
LLIIVVEE EELLEECCTTRRIICCAALL CCOOMMPPOONNEENNTTSS!!
FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinn pprrooppeerrttyy ddaammaaggee,, sseevveerree ppeerrssoonnaall iinnjjuurryy,, oorr ddeeaatthh.. FFoollllooww aallll eelleeccttrriiccaall ssaaffeettyy pprreeccaauuttiioonnss wwhheenn eexxppoosseedd ttoo lliivvee eelleeccttrriiccaall ccoommppoonneennttss.. IItt mmaayy bbee nneecceessssaarryy ttoo wwoorrkk wwiitthh lliivvee eelleeccttrriiccaall ccoommppoonneennttss dduurriinngg iinnssttaallllaattiioonn,, tteessttiinngg,, sseerrvviicciinngg,, aanndd ttrroouubblleesshhoooottiinngg ooff tthhiiss pprroodduucctt..
WWAARRNNIINNGG
PPRREESSSSUURRIIZZEEDD RREEFFRRIIGGEERRAANNTT!!
FFaaiilluurree ttoo ffoollllooww tthhiiss WWaarrnniinngg ccoouulldd rreessuulltt iinn ppeerrssoonnaall iinnjjuurryy SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghh pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. DDoo nnoo uussee nnoonn-­aapppprroovveedd rreeffrriiggeerraannttss oorr rreeffrriiggeerraanntt ssuubbssttiittuutteess oorr rreeffrriiggeerraanntt aaddddiittiivveess..
CCAAUUTTIIOONN
SSHHAARRPP EEDDGGEE HHAAZZAARRDD!!
FFaaiilluurree ttoo ffoollllooww tthhiiss CCaauuttiioonn ccoouulldd rreessuulltt iinn pprrooppeerrttyy ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy.. BBee ccaarreeffuull ooff sshhaarrpp eeddggeess oonn eeqquuiippmmeenntt oorr aannyy ccuuttss mmaaddee oonn sshheeeett mmeettaall wwhhiillee iinnssttaalllliinngg oorr sseerrvviicciinngg..
CCAAUUTTIIOONN
HHAAZZAARRDDOOUUSS VVAAPPOORRSS!!
FFaaiilluurree ttoo ffoollllooww tthhiiss ccaauuttiioonn ccoouulldd rreessuulltt iinn pprrooppeerrttyy ddaammaaggee oorr ppeerrssoonnaall iinnjjuurryy.. EEqquuiippmmeenntt ccoorrrroossiioonn ddaammaaggee.. TToo pprreevveenntt sshhoorrtteenniinngg iittss sseerrvviiccee lliiffee,, tthhee aaiirr hhaannddlleerr sshhoouulldd nnoott bbee uusseedd dduurriinngg tthhee ffiinniisshhiinngg pphhaasseess ooff ccoonnssttrruuccttiioonn oorr rreemmooddeelliinngg.. TThhee llooww rreettuurrnn aaiirr tteemmppeerraattuurreess ccaann lleeaadd ttoo tthhee ffoorrmmaattiioonn ooff ccoonnddeennssaattee.. CCoonnddeennssaattee iinn tthhee pprreesseennccee ooff cchhlloorriiddeess aanndd fflluuoorriiddeess ffrroomm ppaaiinntt,, vvaarrnniisshh,, ssttaaiinnss,, aaddhheessiivveess,, cclleeaanniinngg ccoommppoouunnddss,, aanndd cceemmeenntt ccrreeaatteess aa ccoorrrroossiivvee ccoonnddiittiioonn wwhhiicchh mmaayy ccaauussee rraappiidd ddeetteerriioorraattiioonn ooff tthhee ccaabbiinneett aanndd iinntteerrnnaall ccoommppoonneennttss..
CCAAUUTTIIOONN
CCOOIILL IISS PPRREESSSSUURRIIZZEEDD!!
•• CCooiill iiss pprreessssuurriizzeedd wwiitthh aapppprrooxxiimmaatteellyy 88––1122 ppssii ddrryy aaiirr aanndd ffaaccttoorryy cchheecckkeedd ffoorr lleeaakkss..
•• CCaarreeffuullllyy rreelleeaassee tthhee pprreessssuurree bbyy rreemmoovviinngg tthhee rruubbbbeerr pplluugg oonn tthhee lliiqquuiidd lliinnee..
•• IIff nnoo pprreessssuurree iiss rreelleeaasseedd,, cchheecckk ffoorr lleeaakkss..
©2016 Trane
18-GF74D1-1F-EN
SSAAFFEETTYY SSEECCTTIIOONN AAIIRR HHAANNDDLLEERRSS
WWAARRNNIINNGG
SSAAFFEETTYY HHAAZZAARRDD!!
FFiibbeerrggllaassss dduusstt aanndd cceerraammiicc ffiibbeerrss aarree bbeelliieevveedd bbyy tthhee ssttaattee ooff CCaalliiffoorrnniiaa ttoo ccaauussee ccaanncceerr tthhrroouugghh iinnhhaallaattiioonn.. GGllaasssswwooooll ffiibbeerrss mmaayy aallssoo ccaauussee rreessppiirraattoorryy,, sskkiinn,, oorr eeyyee iirrrriittaattiioonn.. PPRREECCAAUUTTIIOONNAARRYY MMEEAASSUURREESS
•• AAvvooiidd bbrreeaatthhiinngg ffiibbeerrggllaassss dduusstt
•• UUssee aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr
•• AAvvooiidd ccoonnttaacctt wwiitthh tthhee sskkiinn oorr eeyyeess.. WWeeaarr lloonngg-­sslleeeevveedd,, lloooossee ffiittttiinngg ccllootthhiinngg,, gglloovveess,, aanndd eeyyee pprrootteeccttiioonn
•• WWaasshh ccllootthheess sseeppaarraatteellyy ffrroomm ootthheerr ccllootthhiinngg,, rriinnssee wwaasshheerr tthhoorroouugghhllyy
•• OOppeerraattiioonnss ssuucchh aass ssaawwiinngg,, bblloowwiinngg,, tteeaarr--oouutt,, aanndd sspprraayyiinngg mmaayy ggeenneerraattee ffiibbeerr ccoonncceennttrraattiioonnss rreeqquuiirriinngg aaddddiittiioonnaall rreessppiirraattoorryy pprrootteeccttiioonn.. UUssee tthhee aapppprroopprriiaattee NNIIOOSSHH aapppprroovveedd rreessppiirraattoorr iinn tthheessee ssiittuuaattiioonnss FFIIRRSSTT AAIIDD MMEEAASSUURREESS
•• EEYYEE CCOONNTTAACCTT:: FFLLUUSSHH EEYYEESS WWIITTHH WWAATTEERR TTOO RREEMMOOVVEE DDUUSSTT.. IIFF SSYYMMPPTTOOMMSS PPEERRSSIISSTT,, SSEEEEKK MMEEDDIICCAALL AATTTTEENNTTIIOONN..
•• SSKKIINN CCOONNTTAACCTT:: WWAASSHH AAFFFFEECCTTEEDD AARREEAA GGEENNTTLLYY WWIITTHH SSOOAAPP AANNDD WWAARRMM WWAATTEERR AAFFTTEERR HHAANNDDLLIINNGG.. TThhiiss wwaarrnniinngg ccoommpplliieess wwiitthh ssttaattee ooff CCaalliiffoorrnniiaa llaaww,, PPrrooppoossiittiioonn 6655..
NNoottee:: Air handlers have been evaluated in accordance
with the Code of Federal Regulations, Chapter XX, Part 3280 or the equivalent.“SUITABLE FOR MOBILE HOME USE.”
NNoottee:: Condensation may occur on the surface of the air
handler when installed in an unconditioned space. When units are installed in unconditioned spaces, verify that all electrical and refrigerant line penetrations on the air handler are sealed completely.
NNoottee:: The manufacturer recommends installing ONLY
A.H.R.I approved, matched indoor and outdoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance, and the best overall system reliability.
WWAARRNNIINNGG
SSAAFFEETTYY HHAAZZAARRDD!!
TThhiiss aapppplliiaannccee iiss nnoott ttoo bbee uusseedd bbyy ppeerrssoonnss ((iinncclluuddiinngg cchhiillddrreenn)) wwiitthh rreedduucceedd pphhyyssiiccaall,, sseennssoorryy,, oorr mmeennttaall ccaappaabbiilliittiieess,, oorr llaacckk ooff eexxppeerriieennccee aanndd kknnoowwlleeddggee,, uunnlleessss tthheeyy hhaavvee bbeeeenn ggiivveenn ssuuppeerrvviissiioonn oorr iinnssttrruuccttiioonn..
WWAARRNNIINNGG
SSAAFFEETTYY HHAAZZAARRDD!!
CChhiillddrreenn sshhoouulldd bbee ssuuppeerrvviisseedd ttoo eennssuurree tthhaatt tthheeyy ddoo nnoott ppllaayy wwiitthh tthhee aapppplliiaannccee..
IImmppoorrttaanntt:: Installation of this unit shall be made in
accordance with the National Electric Code, NFPA No. 90A and 90B, and any other local codes or utilities requirements.
IImmppoorrttaanntt:: Air handlers do not require repositioning of
the coil or drain pan for upflow or horizontal left applications. See the downflow and horizontal right installation sections for application instructions.
18-GF74D1-1F-EN
3
Table of Contents
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation Instructions . . . . . . . . . . . . . . . . . . . 5
Field Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Electrical Data . . .. . . . . . . . . . . . . . . . . . . . . . . . . . 11
Performance and Electrical Data . . . . . . . . . . . 12
Minimum Airflow CFM . . . . . . . . . . . . . . . . . . . . 19
Outline Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Heater Pressure Drop Table . . . . . . . . . . . . . . . . 22
Subcooling Adjustment . . . . . . . . . . . . . . . . . . 22
Subcooling Adjustment for
TEM6A0C48H41 & TEM6A0C60H51 . . . . . . . 22
Coil Conversion Instructions. . . . . . . . . . . . . . . 23
Coil Conversion . . . . . . . . . . . . . . . . . . . . . . . . . 28
Checkout Procedures . . . . . . . . . . . . . . . . . . . . . . 36
4
18-GF74D1-1F-EN
Features
Table 1. Standard Features
MULTI-POSITION UPFLOW, DOWNFLOW, HORIZONTAL LEFT AND HORIZONTAL RIGHT
PAINTED FINISH ON GALVANIZED STEEL EXTERIOR WITH FULLY INSULATED CABINET THAT MEETS R4.2 VALUE
STURDY POLYCARBONATE DRAIN PANS
The TEM air handler has factory installed drain pans and
is shipped for upflow and horizontal left applications
208/230 VAC OPERATION
VARIABLE-SPEED DIRECT DRIVE BLOWER.
FACTORY INSTALLED R-410A THERMAL EXPANSION VALVE
ALL ALUMINUM COIL
BOTTOM RETURN
MEETS THE MINIMUM LEAKAGE REQUIREMENTS FOR THE FLORIDA AND CALIFORNIA BUILDING CODES
Table 2. Optional Accessories
4,5,8,10,15,20, and 25 KW SINGLE PHASE ELECTRIC HEATERS
Circuit breakers available on single phase 4, 5, 8, 10,
15, 20, and 25 KW heaters
Lugs available on single phase 4, 5, 8, and 10 KW
heaters
Lugs available on three phase 10 and 15 KW heaters
SINGLE POINT POWER ENTRY KIT (for 15 and 20 KW heaters)
SUPPLY DUCT FLANGE KIT
DOWNFLOW SUB-BASE KITS - TAYBASE185, TAYBASE235, TAYBASE260
SLIM FIT FILTER BOX KIT — BAYSF1185AAA, BAYSF1235AAA, BAYSF1265AAA
Installation Instructions
1. UUnnppaacckkiinngg
Carefully unpack the unit and inspect the contents for damage. If any damage is found at the time of delivery, proper notification and claims should be made with the carrier.
Check the rating plate to assure model number and voltage, plus any kits match with what you ordered. The manufacturer should be notified within 5 days of any discrepancy or parts shortage.
2. LLooccaattiioonn
The air handler should be centrally located and may be installed in a closet, alcove, utility room, basement, crawl space or attic. Minimum clearances must be met.
IIMMPPOORRTTAANNTT:: The downflow sub-base may be
required with electric heat applications. See minimum clearance table.
The unit must be installed in a level position to ensure proper condensation drainage. Make sure the unit is level in both directions within 1/8" on either side.
When the unit is installed in a closet or utility room, the room should be large enough, and have an opening to allow replacement of the unit. All servicing is done from the front and a clearance of 21" is needed for service unless the closet door aligns with the front of the air handler.
If you are installing the unit in an unconditioned space such as an attic or crawl space, you must ensure that the area provides sufficient air circulation to prevent moisture collection on the cabinet during high dew point conditions. A drain pan must be installed under the entire unit when it is installed in or above a finished ceiling or in an unconditioned space.
3. DDuucctt WWoorrkk
The duct work should be installed in accordance with the NFPA No. 90A "Installation of Air Conditioning and Ventilating systems" and No. 90B "Residential Type Warm Air Heating and Air Conditioning Installation."
The duct work should be insulated in accordance with the applicable requirements for the particular installation as required by HUD, FHA, VA the applicable building code, local utility or other governing body.
4. CCoonnddeennssaattee DDrraaiinn
The unit is supplied with primary and auxiliary condensate drains that have 3/4" NPT connections. The primary drain must be trapped outside the unit and piped in accordance with applicable building codes. Do not reduce the drain line size less than the connection size on the drain pan. Condensate should be piped to an open drain or to the outside. All drains must pitch downward away from the unit a minimum of 1/4" per foot of line to ensure proper drainage.
IIMMPPOORRTTAANNTT:: If cleanout Tee is used, stand pipe
must be sealed/capped.
Insulate the primary drain line to prevent sweating where dew point temperatures may be met. (Insulation is optional depending on climate and application needs.)
18-GF74D1-1F-EN
5
CFM SELECTION LIGHT
DIP SWITCHES
DIP SWITCHES (TYPICAL SETTINGS)
COOLING
HEATING
AIRFLOW
FAN OFF
DELAY
AUXILARY
HEAT SPEEDS
OFF OFF
50%
80%
100% if necessary
50%
Dehumidify Warm Air Heating
Fast Coil Cooling Fast Coil Heating
Efficiency
7.5
minutes
3
minutes
1
minute
FAN OPERATION (CFM)
as required
COMPRESSOR OPERATION ON
OFF
FFeeaattuurreess
5. RReeffrriiggeerraanntt PPiippiinngg
Refrigerant piping external to the unit shall be sized in accordance with the instructions of the manufacturer of the outdoor equipment.
6. MMeetteerriinngg DDeevviiccee
All units are shipped and installed with an internally-checked, non-bleed TXV designed for air conditioning or heat pump operation. Some outdoor models may require a start assist kit. See outdoor unit for more information.
7. BBlloowweerr
This unit is supplied with a variable speed motor with a direct drive blower wheel which can obtain various air flows. The unit is shipped with factory set cooling and heating air flows. Performance tables are available for additional airflow settings. Disconnect all power to the unit before making any adjustments to the airflow settings. Be sure to check the air flow and the temperature drop across the evaporator coil to ensure sufficient air flow.
8. AAiirrffllooww AAddjjuussttmmeenntt
CCAAUUTTIIOONN
EEQQUUIIPPMMEENNTT DDAAMMAAGGEE!!
FFaaiilluurree ttoo ffoollllooww tthhiiss pprroocceedduurree mmaayy rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee.. DDiissccoonnnneecctt ppoowweerr ttoo tthhee aaiirr hhaannddlleerr bbeeffoorree cchhaannggiinngg ddiipp sswwiittcchh ppoossiittiioonnss..
Blower speed changes are made on the ECM Fan Control. The ECM Fan Control controls the variable speed motor.
There is a bank of 8 dip switches. The dip switches work in pairs to match the airflow for the outdoor unit size (tons). cooling airflow adjustment, Fan off­delay options, and heating airflow adjustment. The switches appear as shown in Figure 2, p. 6
Figure 1. ECM Fan Control
Figure 2. Dip Switches
If the airflow needs to be increased or decreased, see the Airflow Label on the air handler or Blower Performance Table.
Be sure to set the correct airflow for cooling and heating.
Switches 1–4 Cooling Airflow
Switches 5–6 Fan Off Delay Options
Switches 7–8 Auxiliary Heat
IInnddoooorr BBlloowweerr TTiimmiinngg
IIMMPPOORRTTAANNTT:: Leave dip switches 5 and 6 in the “as-
shipped” positions during system start­up and check out. Afterwards, adjust as desired.
Table 3. Cooling Off — Delay Options
SWITCH SETTINGS SELECTION NOMINAL
5 — OFF 6 — OFF NONE SAME
5 — ON 6 — OFF 1.5 MINUTES 100%
5 — OFF 6 — ON 3 MINUTES 50%
5 — ON 6 — ON ENHANCED
(a)
Default setting
(b)
This ENHANCED MODE selection provides a ramping up and ramping down of the blower speed to provide improved comfort, quietness, and potential energy savings. The graph shows the ramping process.
(b)
AIRFLOW
50–100%
(a)
6
Figure 3. Enhanced Mode
9. WWiirriinngg
18-GF74D1-1F-EN
FFeeaattuurreess
Consult all schematic and pictorial wiring diagrams of this unit and the outdoor equipment to determine compatibility of wiring connections and to determine specific requirements.
All field wiring to the air handler should be installed in accordance with the latest edition of the National Electric Code NFPA No. 70 and any local codes. Check rating plates on unit for rated volts, minimum circuit ampacity and maximum over current protection. Supply circuit power wiring must be 75 degree C (167 degree F) minimum copper conductors only. Copper supply wires shall be sized to the National Electric Code or local code requirements, whichever is more stringent.
The unit is shipped wired for 230/240 Volt AC 60 HZ 1 Phase Operation. If the unit is to be operated at 208 VAC 60HZ, follow the instructions on the indoor unit wiring diagram to change the low voltage transformer to 208 VAC operation (Ensure unit is properly grounded).
Class 2 low voltage control wiring should not be run in conduit with power wiring and must be separated from power wiring unless class 1 wire with proper voltage rating is used.
Low voltage control wiring should be 18 Awg, color coded (105 degree C minimum). For lengths longer than 100ft., 16 Awg wire should be used. Make certain that separation of control wiring and power wiring has been maintained.
10. AAiirr FFiilltteerr
To protect the coil, blower and other internal parts from excessive dirt and dust an air filter must be installed before air enters the evaporator coil. A remote filter must be installed. Consult the filter manufacturer for proper sizing and maximum velocity requirements.
IImmppoorrttaanntt:: Air filters shall meet the test requirements
in UL 900.
11. TThheerrmmoossttaatt
Select a thermostat that is commonly used with HP
or AC single stage heating/cooling with electric heat. The thermostat will energize the fan on a demand for heat or cool.
Install the thermostat on an inside wall, away from drafts, lights or other heat sources in a location that has sufficient air circulation from other rooms being controlled by the thermostat.
12. SSeeqquueennccee ooff OOppeerraattiioonn CCoooolliinngg ((CCoooolliinngg oonnllyy))
When the thermostat calls for cooling, the circuit from R to G is completed. The blower motor is energized directly by the ECM fan control, which receives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizing the compressor contactor of the outdoor unit. The contactor will close and start the compressor and condenser fan motor.
CCoooolliinngg ((hheeaatt ppuummpp))
When the thermostat calls for cooling, the circuit from R to G is completed. The blower motor is energized directly by the ECM fan control, which receives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizing the compressor contactor of the outdoor unit. The contactor will close and start the compressor and condenser fan motor.
Circuit R to O energizes the reversing valve to the cooling position.
HHeeaattiinngg ((hheeaatt ppuummpp))
When the thermostat calls for heating, the circuit from R to G is completed and the blower motor is energized directly by the ECM fan control, which receives the 24VAC signal from the thermostat.
The circuit from R to Y is also complete energizing the compressor contactor of the outdoor unit. The contactor will close and start the compressor and condenser fan motor.
18-GF74D1-1F-EN
7
FFeeaattuurreess
In the heating mode, the reversing valve of the outdoor unit is not energized.
If the indoor temperature continues to fall, the R to W circuit is completed energizing the electric heat contactor(s).
HHeeaattiinngg ((eelleeccttrriicc hheeaatt oonnllyy))
NNoottee:: The thermostat must be setup to bring the
blower on when the electric heat is energized.
When the thermostat calls for heating, the circuit from R to G is completed and the blower motor is energized directly by the ECM fan control, which receives the 24VAC signal from the thermostat. The circuit from R to W is completed energizing the heating contactor(s).
DDeeffrroosstt
Supplemental heat during defrost can be provided by connecting the X2 (black) wire from the outdoor unit to W1 or W2 at the indoor unit. This will prevent cold air from being discharged from the indoor unit during defrost.
13. OOppeerraattiioonnaall aanndd CChheecckkoouutt PPrroocceedduurreess
To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts document of the outdoor unit. After installation has been completed, it is recommended that the entire system be checked against the checkout list located at the back of this document. See “Checkout Procedures,” p. 36
14. MMaaiinntteennaannccee
The system air filter(s) should be inspected, cleaned or replaced at least monthly. Make certain that the access panels are replaced and secured properly before placing the unit back in operation. This product is designed for dependable service; however, periodic maintenance should be scheduled and conducted by trained professional service personnel. This service should be conducted at least annually, and should include testing and inspection of electrical and refrigerant components. The heat transfer surface should be cleaned. The blower motor is permanently lubricated for normal operating conditions.
8
18-GF74D1-1F-EN
Field Wiring
Sing le St age, C o o lin g On ly
The rm ostat Air H andler
Outdoor
Unit
R
G
B
W1
W2
B
Y
R
G
B
Y
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
EMERGENCY HEAT
White
White
W2
O
Y1
1. * Uni ts wi th pi gtai ls re quire wirenut s for conn ections.
2. Cap al l unu sed wire s.
3. F or BK ena b led com fort control, do not conn e ct Y1 or Y2 at the air handl e r
Y2
BK
WH/BLK
4. F or BK ena b led com fort control, cut the jumpe r wire betw een R and BK on the control board. See wi ring schematic for d e tails.
5. In AC s yst em s for mult iple s tages of e lectric heat , jumper W1 a n d W2 tog ether if c o m fort control h as o nly one sta g e of heat.
Sing le St age, HP
The rm ostat Air H andler
Outdoor
Unit
R
G
B
W1
W2
R
B
O
Y
X2
R
G
B
O
Y
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
EMERGENCY HEAT
White
Black
White
W2
O
Y1
Y2
BK
Optional
WH/BLK
1. * Uni ts wi th pi gtai ls re quire wirenut s for conn ections.
2. Cap al l unu sed wire s.
3. F or BK ena b led com fort control, do not conn e ct Y1 or Y2 at the air handl e r
4. F or BK ena b led com fort control, cut the jumpe r wire betw een R and BK on the control board. See wi ring schematic for d e tails.
5. In s ystem s fo r m u ltiple stage s of electric he a t, jum per W1 a n d W2 tog ether if c o m fort control h as o nly one sta g e of heat.
18-GF74D1-1F-EN
9
2 St age, 2 Step, Coo lin g O n ly
The rm o
stat
Air H andler
Outdoor
Unit
R
G
B
W1
W2
B
Y1
R
G
B
Y1
W1
Blue
24 VAC HOT
FAN
24 VAC Common
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
EMERGENCY HEAT
White
White
W2
O
Y1
Y2
BK
Y2
Y2
WH/BLK
1. * Uni ts wi th pi gtai ls re quire wirenut s for conn ections.
2. Cap al l unu sed wire s.
3. F or BK ena b led com fort control, do not conn e ct Y1 or Y2 at the air handl e r
4. F or BK ena b led com fort control, cut the jumpe r wire betw een R and BK on the control board. See wi ring schematic for d e tails.
5. In AC s yst em s for mult iple s tages of e lectric heat , jumper W1 a n d W2 tog ether if c o m fort control h as o nly one sta g e of heat.
2 St age, 2 Step, HP
The rm ostat Air H andler
Outdoor
Unit
R
G
B
W1
W2
R
B
O
Y1
X2
R
G
B
O
Y1
W1
Blue
24 VAC HOT
FAN
24 VAC Common
SOV
COOL/HEAT 1st STAGE
HEATING 2nd STAGE
EMERGENCY HEAT
White
Black
White
W2
O
Y1
Y2
BK
Optional
Y2Y2
WH/BLK
1. * Uni ts wi th pi gtai ls re quire wirenut s for conn ections.
2. Cap al l unu sed wire s.
3. F or BK ena b led com fort control, do not conn e ct Y1 or Y2 at the air handl e r
4. F or BK ena b led com fort control, cut the jumpe r wire betw een R and BK on the control board. See wi ring schematic for d e tails.
5. In s ystem s fo r m u ltiple stage s of electric he a t, jum per W1 a n d W2 tog ether if c o m fort control h as o nly one sta g e of heat.
FFiieelldd WWiirriinngg
10
18-GF74D1-1F-EN
Electrical Data
18-GF74D1-1F-EN
11
Loading...
+ 25 hidden pages