Ingersoll Rand System Automation VSD V Box Operator’s Manual

Before installing or starting this unit for the first time, this manual should be studied carefully to obtain a working knowledge of the unit and/or the duties to be performed while operating and maintaining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the unit at all times.
More Than Air, Answers.
Online answers: http://www.air.irco.com
Ingersoll Rand
System Automation
VSD V Box
Operator’s Manual
C.C.N. : 80444136 REV. A DATE DECEMBER 2008
TABLE OF CONTENTS
TABLEOFCONTENTS..................................................2
SECTION1–INTRODUCTION......................................3
SECTION2—SAFETY.................................................3
S
AFETYPRECAUTIONS.......................................................3
NSTALLATION.................................................................3
I
PERATION....................................................................3
O
AINTENANCEANDREPAIR..............................................4
M
SECTION3—COMPRESSORCONNECTIONAND
CONTROL...................................................................5
S
TANDARDCONTROLFEATURESANDFUNCTIONALITY............5
VBOXOPERATION...................................................6
VSD
SECTION4—INSTALLATION......................................7
U
NITLOCATION..............................................................7
OWERSUPPLY...............................................................7
P
NETWORK...........................................................7
RS485
VBOXANDPRESSURESENSORCONNECTIVITY...............8
VSD
RESSURESENSORCONNECTIONS.....................................10
P
ISCHARGE(DELIVERY)PRESSURESENSORINTERCONNECT....10
D
ISCHARGE(DELIVERY)PRESSURESENSORANDINTERNAL
D
PRESSURESENSORINTERCONNECT....................................11
COMPRESSORWITHPRESSURESWITCHREGULATED
VSD
COMPRESSORINTERCONNECT..........................................12
VANDIR‐PCBCOMPRESSORCONNECTIVITY...............13
VSD
COMPRESSORSTATUSMONITORING......................13
IRPCB
RESSURESWITCHREGULATIONCONTROL.........................15
P
SECTION5—DISPLAYANDMENUOPERATION........19
OPERATION...............................................................19
SECTION6—COMMISSIONING................................21
C
OMMISSIONINGPROCEDURE..........................................21
HYSICALCHECKS..........................................................21
P
OMPRESSORPRESSURESETPOINTS.................................21
C
VBOXCONFIGURATION..........................................22
VSD
RESSURESETPOINTS....................................................24
P
SECTION7—SYSTEMCONFIGURATION...................25
D
ISPLAYITEMSTRUCTURE...............................................25
CCESSINGTHEX12ICONFIGURATIONSCREENS.................25
A
ENUITEMSANDSETTINGS............................................27
M
SECTION8—DIAGNOSTICS.....................................31
SECTION9—FAULTCODES......................................32
SECTION10—VSDVBOXSTATUSBLOCKDIAGRAM32
SECTION11—PARTSLIST........................................34
SECTION12—TECHNICALDATA..............................34
SECTION13—WIRINGDIAGRAM............................35
VSD
VBOXSCHEMATIC..................................................35
XPMTAC24 XPM‐V XPM‐PSU24
SCHEMATIC...............................................36
O2(+VDCANALOGOUTPUT)................................36
(24VACTO24VDC)....................................36
SECTION14—COMMISSIONINGFORM...................37
Refer to Section Indicated
Note
Important or Caution, Safety
2
SECTION 1 – INTRODUCTION
The VSD V (Voltage) Box is intended to provide a method of system integration for a VSD (Variable Speed Drive) air compressor equipped with a Voltage Pressure Sensor that is not equipped with any accessible means of remote connectivity (such as the Ingersoll Rand Nirvana).
SECTION 2 — SAFETY
SAFETY PRECAUTIONS
WARNING :
!
WARNING :
WARNING :
!
WARNING :
Before installing or operating the VSD V Box, take time to carefully read all the instructions contained in this manual, all compressor manuals, and all manuals of any other peripheral devices that may be installed or connected to the unit.
Electricity and compressed air have the potential to cause severe personal injury or property damage.
The operator should use com m on sense and good working practices while operating and maintaining this system. All applicable codes should be strictly adhered to.
Maintenance must be performed b y adequately qualified personnel that are equipped with the proper tools.
INSTALLATION
Installation work must only be carried out by a competent person under qualified supervision.
A fused isolation switch must be fitted between the main power supply and the VSD V Box.
The VSD V Box should be mounted in such a location as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times.
If raised platforms are required to provide access to the VSD V Box, they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides.
Risk of Danger
Risk of Electric Shock
Risk of High Pressure
Consult Manual
The VSD V Box will provide the required functionality to enable system integration and efficient control using the X8I or X12I Automation System.
.
OPERATION
The VSD V Box must only be operated by competent personnel under qualified supervision.
Never remove or tamper with safety devices, guards or insulation materials fitted to the VSD V Box.
The VSD V Box must only be operated at the supply voltage and frequency for which it is designed.
When main power is switched on, lethal voltages are present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit.
Do not open access panels or touch electrical components while voltage is applied unless it is necessary for measurements, tests or adjustments. Such work should be carried out only by a qualified electrician equipped with the correct tools and wearing appropriate protection against electrical hazards.
All air compressors and/or other equipment connected to the unit should have a warning sign attached stating “THIS UNIT MAY START WITHOUT WARNING” next to the display panel.
If an air compressor and/or other equipment connected to the unit is to be started remotely, attach two warning signs to the equipment stating “THIS UNIT CAN BE STARTED REMOTELY”. Attach one sign in a prominent location on the outside of the equipment, and the other sign inside the equipment control compartment.
3
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must onl y be carried out by competent personnel under qualified supervision.
If replacement parts are required, use only genuine parts from the original equipment manufacturer, or an alternative approved source.
Carry out the following operations before opening or removing any access panels or carrying out any work on the VSD V Box:
o Isolate the VSD V Box from the main
electrical power supply. Lock the isolator in the “OFF” position and remove the fuses.
o Attach labels to the isolator switch and
to the unit stating “WORK IN PROGRESS - DO NOT APPLY VOLTAGE”. Do not switch on electrical power or attempt to start the VSD V Box if such a warning label is attached.
Make sure that all instructions concerning operation and maintenance are strictly followed and that the complete unit, with all accessories and safety devices, is kept in good working order.
The accuracy of sensor devices must be checked on a regular basis. They must be calibrated when acceptable tolerances are exceeded. Always ensure any pressure within the compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device.
The VSD V Box must only be cleaned with a damp cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis.
Do not paint the control faceplate or obscure any indicators, controls, instructions or warnings
4
SECTION 3 — COMPRESSOR CONNECTION AND CONTROL
The VSD V (Voltage) Box is designed to connect to an X8I or X12I Automation System unit, using a 2-wire RS485 data cable.
The VSD V Box is intended to provide a method of system integration for 3 not equipped with any accessible means of remote connectivity. The VSD V Box is used to integrate with VSD Air Compressors that are controlled by Voltage Pressure Sensors.
Each air compressor in a system that requires VSD V Box integration must be equipped with an individual VSD V Box. Any number of VSD V Boxes can be connected to the Automation System unit as long as the total number of compressors does not exceed the total number of compressors for the Automation System model.
In conjunction with a ‘speed monitoring kit’ (available separately) the VSD V Box will provide all required functionality to maximize the ENER, Energy Control Mode, in the X8I or X12I Automation System.
rd
party air compressors that are
STANDARD CONTROL FEATURES AND FUNCTIONALITY
The air compressor must be equipped with a 0-5VDC, 1­5VDC or 0.5-4.5VDC type pressure sensor that is used for regulation control. For VSD type air compressors; the compressor must be equipped with a 0-5VDC, 1-5VDC or
0.5-4.5VDC type pressure sensor that is used for variable speed drive regulation. The VSD V Box will accommodate a pressure sensor range of 1.0bar to 600bar.
Various Compressor Configurations and Characteristics Can Be Accommodated by the VSD V Box. These include::
Air compressors that are equipped with a package discharge (delivery) pressure sensor and a second internal pressure sensor. The internal pressure sensor is generally used for internal air/oil filtration differential pressure monitoring and/or internal pressure safety functions. The VSD V Box is able to accommodate this requirement without affecting functionality of the compressor control system internal pressure sensor feature(s).
VSD air compressors that are equipped with t wo pressure sensors that both monitor package discharge (delivery) pressure. One sensor is dedicated to compressor control system basic regulation functions; the other is dedicated to variable speed drive unit regulation. The VSD V Box is able to accommodate this requirement without affecting compressor control system functionality.
VSD air compressors that are equipped with a pressure switch dedicated to basic compressor control system load/unload regulation; and a pressure sensor dedicated to variable speed drive unit regulation. The VSD V Box is able to accommodate pressure switch regulation in conjunction with variable speed drive pressure sensor regulation without affecting compressor control system functionality.
VSD air compressor types that are unable to maintain maximum speed operation for a prolonged period of time. In these instances the controller may automatically reduce speed regardless of demand. The VSD V Box and management system unit will recognize this if it occurs and will, if necessary, utilize an additional compressor to meet demand.
VSD air compressor types are unable to maintain minimum speed operation for a prolonged period of time. In these instances the controller may automatically stop the compressor regardless of demand. The VSD V Box will recognize and accommodate this behavior. The management system unit will indicate and record the compressor status correctly without fault indication.
5
VSD V BOX OPERATION
All air compressors are equipped with a method of sensing pressure. An air compressor regulates using the compressor package discharge pressure as the control variable.
The VSD V Box monitors the compressor pressure sensor as an input and simulates the pressure sensor signal as an output. The VSD V Box uses this method to modify the pressure signal and manipulate the behavior of the air compressor. In other words, the VSD V Box becomes the air compressor pressure sensor. This functionality enables the Automation System unit to utilize the compressor effectively and optimize total system efficiency and maintain air quality.
The VSD V Box also monitors compressor status (Ready, Run, and Load/Unload) and continuously reports this information to the Automation System unit. This function enables the VSD V Box to simulate all features of a standard X8I or X12I network compressor integration.
Actual System pressure and the Automation System ‘target’ pressure information is routinely transmitted from the X8I or X12I to the VSD V Box. The VSD V Box uses this information to calculate the difference between the compressor discharge pressure and the system ‘target’ pressure. The VSD V Box utilizes pressure signal manipulation to continuously re-align compressor output with system requirements.
This functionality also enables the VSD V Box to continuously compensate for any pressure differential that may occur across local air treatment, along air pipe work or between different locations in a compressed air network.
VSD V Box Operation Example:
If the Automation System unit is detecting a network air pressure (PN) of 100psi (6.9bar), and the system target pressure requirement (P) is 103psi (7.1bar), the VSD V Box will immediately calculate that a pressure rise of 3psi (0.2bar) is required to achieve and maintain system target pressure (P). Due to pressure differential across a local compressed air treatment system (PD) the compressor is currently operating at 107psi (7.4bar). The VSD V Box will manipulate the compressor pressure signal (PS) to cause the compressor to increase discharge (delivery) pressure (PC) to 110psi (7.6bar). This action will increase system pressure to the required target pressure. The VSD V Box will continuously re­calculate and manipulate the compressor pressure signal (PS) to accommodate changes in demand and compensate for any local or compressed air network pressure differentials.
PC
PS
VSD
PD
P
PN
6
SECTION 4 — INSTALLATION
It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.
Information regarding the compressor control system, method of operation and regulation settings, is required. Knowledge of VSD compressor regulation methods, experience working with compressor control systems and basic principle knowledge of compressed air systems, is also required to be able to successfully install and commission this product.
Dependent on compressor type and installation environment additional fixings, wiring, cabling, terminations and terminals will be required for installation.
UNIT LOCATION
The VSD V Box is wall or panel mounting using conventional screw fixings. The maximum distance between the X8I or X12I and the VSD V Box is 4000ft (1219 meters) of cable length. The VSD V Box must be located adjacent to the compressor unit within 6ft (2m) with total length of interconnecting cables not exceeding 10ft (3m).
POWER SUPPLY
A fused switching isolator must be installed to the main incoming power supply, external to the VSD V Box. The isolator must be fitted with a properly sized fuse to provide adequate protection to the power supply cable used (in accordance with local electrical and safety regulations).
1 2 3 4
L
N
N LE
XPM-TAC24
EE
X01
X04
VOLTAGE SELECT
X04
VOLTAGE SELECT
1
234
1
234
230Vac
115Vac
Power Supply Terminals
Ensure that the voltage select input is properly jumpered for the incoming power. Default voltage configuration is 230Vac.
RS485 NETWORK
The VSD V Box is equipped with an RS485 network communications capability using the ir485 protocol. The VSD V Box is intended to operate as part of the X8I or X12I Automation System. Connection to the system management unit is two-wire, twisted pair, ground (earth) shielded, RS485 data link. Connect the RS485 data cable wires to terminal X07 located on the VSD V Box controller.
The cable used between the X8I or X12I and the VSD V Box is Belden 9841 (or equivalent). It should be run in grounded conduit and should not be greater than 4000 feet (1219 meters) in length.
RS485 data communications and other low voltage signals can be subject to electrical interference. This potential can result in intermittent malfunction or anomaly that is difficult to diagnose. To avoid this possibility always use ground (earth) shielded cables, securely bonded to a known good ground (earth) at one end. In addition, give careful consideration to cable routing during installation.
a) Never route an RS485 data communications or low voltage signal cable alongside a high voltage or 3-phase power supply cable. If it is necessary to cross the path of a power supply cable(s), always cross at a right angle.
b) If it is necessary to follow the route of power supply cables for a short distance (for example: from a compressor X8I to a wall along a suspended cable tray) attach the RS485 or signal cable on the outside of an grounded (earthed) cable tray such that the cable tray forms an grounded (earthed) electrical interference shield.
c) Where possible, never route an RS485 or signal cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications antenna).
L2
L1
Note: Polarity is important.
X07
L2 L1
7
VSD V BOX AND PRESSURE SENSOR CONNECTIVITY
Consult the X8I OR X12I Interconnect and Application Guide prior to the installation of the VSD V Box to the pressure sensor on the VSD and the compressor.
Pressure sensor connectivity is dependent on compressor and control system type.
Electrical Interference
0-5VDC, 1-5VDC, or 0.5-4.5VDC Pressure Sensors
Voltage sensors and cables carrying low voltage analog pressure signals are highly susceptible to interference.
C0 4
C0 2
C0 1
i-PCB
6ft,2m
max
LE D LE 2 D 1
C0 3
1 2 3
VSD Box
2 3
1
2
3
4
i-PCB
6wire : 18-20 Gau (1.0-1.5mm)ge Ground (earth) shielded
Delivery Pressure 2wire, twisted pair, 20 gauge
#1
(0.5-1.0mm
?
Internal Pressure
2wire, twisted pair, 20 gauge
#2
(0.5-1.0mm ) 2wire + Ground (earth)
115/230Vac, 5A
2
2
,
Ground (earth) shielded
)
2
,
Ground (earth) shielded
Cables identified as ‘3’ are only required for a two pressure sensor type compressor installation.
4
Always use shielded, braided (armored), foil
wrapped with a drain wire, 18 / 20 AWG (0.5-1.0mm) maximum, 2-conductor cable no more than 10 feet (3 meters) in length. Ensure the braided steel wire is securely connected to a known good earth ground at both ends. Ensure the internal drain wire is securely connected to a known good earth ground at the VSD V Box end only.
Failure to protect low voltage pressure signals between the compressor and VSD V Box will result in unstable and/or erratic pressure readings; resulting in unstable and/or erratic compressor regulation behavior.
8
Compressor Ground (earth) Circuit Issues
An air compressor that uses an electrical induction main motor may experience voltage interference generated in the compressor’s ground (earth) circuits. An induction motor will generate induction currents in the ground (earth) circuit when changing state from loaded to unloaded, or vice versa, condition. Induction motors that are driven from a variable frequency drive will continuously induce ground (earth) currents during normal load and unload operation.
In some instances the induced current flow in the ground (earth) circuits may manifest as a small voltage difference between various parts of the compressor’s ground (earth) system.
Generally this has no consequence and can be ignored. As the compressor controller experiences minor ground (earth) reference fluctuations, all parts of the controller and control circuits will fluctuate with the same induced ground (earth) voltage simultaneously. The controller will be unaffected.
In the case of a low voltage signal that is referenced to a different ground (earth), remote from the compressor, the situation may represent an issue. As the compressor’s ground (earth) reference fluctuates the 0V reference for any voltage signal will also fluctuate. If a remotely generated voltage signal (from the VSD V Box for example) does not fluctuate in the same way simultaneously the compressor controller will detect a voltage difference in the signal. This will be seen as a fluctuating pressure display that will generally indicate a pressure that fluctuates to a lower pressure than actual.
To avoid this situation the VSD V Box must be securely bonded too, and referenced too, the same ground (earth) as the compressor controller.
If the VSD V Box is mounted remote from the compressor, and pressure signal fluctuations are experienced, the use of a length of ground (earth) cable, or the ground (earth) of a steel wire cable, will reduce, but may not resolve, the issue. Any length of conductive cable or cable screen will have a small resistance to high frequency current flow. This will generate a minor voltage differential alone the cable or cable screen resulting in a voltage difference between the two ends of the cable or cable screen. The pressure display may continue to fluctuate.
This situation can be avoided by mounting the VSD V Box on, or directly adjacent to, the compressor and connecting the VSD V Box ground (earth) to the compressor controller ground (earth) with a large cross section ground (earth) cable or braided conductor.
VSD Box
VSD Box
This action will ensure the VSD V Box experiences the same ground (earth) circuit fluctuations simultaneously with the compressor controller.
The necessity to avoid radiated electrical interference from the compressor still remains, particularly in the instance of a variable frequency drive. The use of twisted pair, ground (earth) shielded cable for low voltage signals internal to the compressor remains important.
9
PRESSURE SENSOR CONNECTIONS
Pressure sensor connectivity is dependent on compressor and control system type.
21
1) Disconnect the compressor pressure sensor wires from the compressor controller and connect to the VSD V Box terminals as indicated on the following connection diagrams.
2) Connect the VSD output pressure signal terminals to the compressor control system pressure sensor terminals as indicated on the following connection diagrams.
3213
1
n
2
L
e
L
e
r
X05
c
s
C
X01
D V
4
2
+
RS485
X04
V
0
Pressure signal output terminals are located on the XPM­Vo2 module within the VSD Voltage Box.
These terminals are not located on the main terminal
PCB of the VSD V Box
DISCHARGE (DELIVERY) PRESSURE SENSOR INTERCONNECT
1 D E L
#1
+VDC(1)
X02
21
+VDC(2)
-
+
2
2
A
A
X03
#2
N
N
A
A
Vo2
1
1
A
A
N
N
A
A
-
+
+
-
IP = 0
1
+VDC
1
VSD Box
IC = 1 0 to 5VDC IC = 2 1 to 5VDC IC = 3 0.5 to 4.5VDC
X07
26 28
25 27
29
30
+VDC
+
-
XPM-Vo2
#1
X02
+VDC signal
0VDC
+ v
-
Delivery Pressure Sensor
1
+
-
+VDC
signal
0VDC
+VDC
signal 0VDC
+ v
-
Delivery Pressure Sensor
10
DISCHARGE (DELIVERY) PRESSURE SENSOR AND INTERNAL PRESSURE SENSOR INTERCONNECT
Internal = Sump
+VDC
1
+VDC
2
1
IP = 1
+
-
+
-
2
VSD Box
X07
25
26
IC = 1 0 to 5VDC IC = 2 1 to 5VDC IC = 3 0.5 to 4.5VDC
l
y
r
a
e
n
v
r
i
l
e
t
e
n
I
D
28 30
27 29
#1
+VDC
+
+VDC
signal
0VDC
+VDC
signal
0VDC
XPM-Vo2
+ v
-
+ v
-
Delivery Pressure Sensor
Internal Pressure Sensor
#2
+VDC
-
X02
-
+
X03
1
+
-
+
-
+VDC
signal 0VDC
+VDC
signal
0VDC
+VDC signal
0VDC
+VDC signal
0VDC
+ v
-
+ v
-
Delivery Pressure Sensor
Internal Pressure Sensor
2
11
VSD COMPRESSOR WITH PRESSURE SWITCH REGULATED COMPRESSOR INTERCONNECT
Compressor controller loads and unloads using a pressure switch; VSD unit regulates using +VDC discharge (delivery) pressure sensor.
See “i-PCB” Interface Connection
1
+
-
IC = 1 0 to 5VDC IC = 2 1 to 5VDC IC = 3 0.5 to 4.5VDC
1
4-20mA
P
Delivery Pressure Switch
+VDC
signal
0VDC
+ v
-
Delivery Pressure Sensor
VSD Box
6 5 4
1 0 X
3 2 1
IP = 0
+
-
VSD Box
25 27
X07
26 28
29
+VDC
30
XPM-Vo2
-
+
#1
X02
1
+VDC
signal 0VDC
+VDC signal
0VDC
+ v
-
Delivery Pressure Sensor
P
Delivery
i-PCB
LED 1 LED 2
Pressure Switch
12
Loading...
+ 25 hidden pages