Before installing or starting this unit for the first time, this
manual should be studied carefully to obtain a working
knowledge of the unit and/or the duties to be performed while
operating and maintaining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical
manual contains IMPORTANT SAFETY DATA and should
be kept with the unit at all times.
More Than Air Answers.
Online answers: http://www.air.irco.com
Ingersoll Rand
System Automation
VSD Box MODBUS RTU
User’s Manual
C.C.N. : 80445000
REV. A
DATE: JUNE 2008
TABLE OF CONTENTS
INTRODUCTION 3
SAFETY PRECAUTIONS 3
MODBUS RTU 5
1. MODBUS Table(s) 5
2. General 5
3. Communication Link 5
4. RS485 Serial Data Format 5
5. Message Data Format 5
6. Slave Response Timeout 7
7. Message Answer from Slave to Master 7
8. Exception Response 7
9. Troubleshooting 8
MODBUS Tables 9
1. Table Item Format 9
2. Name and Function 9
3. Coding 9
4. Menu Reference 10
5. ‘Adv’ Advise Function 10
6. ‘Adv’ Advise Function – Single Item Format Option 10
7. ‘Cmd’ Command Function 12
8. ‘Get’ Function 12
9. ‘Set’ Function 13
10. Data Coding Definitions 13
MODBUS: X-Series Air Systems 16
1. General X-Series System Components 16
2. X-Series System Network Addresses 17
3. Communication Link 17
4. MODBUS Timing 17
5. RS485 Serial Data Format 17
MODBUS RTU Definitions For VSD Box 18
2
INTRODUCTION
System MODBUS Gateway communication is RS485, RTU, Master-Slave configuration. The Gateway acts as a transparent
interface to enable a remote ‘master’ device to be able to communicate with the X-Series Units and the Intellisys Controllers
via the ir485 network ‘slave’ device(s). The MODBUS RTU data construction and formatting for a ‘master’ device is the subject
of this document. This information is intended for a systems integrator to facilitate set-up of a ‘master’ device in order to
communicate successfully with the X-Series Units and the Intellisys Controllers throug h a System Modbus Gateway.
SAFETY PRECAUTIONS
WARNING :
!
WARNING :
WARNING :
!
WARNING :
•Before installing or operating the
SYSTEM MODBUS GATEWAY (SMG)
BOX, take time to carefully read all the
instructions contained in this manual, all
compressor manuals, and all manuals
of any other peripheral devices that may
be installed or connected to the unit.
•Electricity and compressed air have the
potential to cause severe personal injury
or property damage.
•The operator should use common sense
and good working practices while
operating and maintaining this system.
All applicable codes should be strictly
adhered to.
•Maintenance must be performed by
adequately qualified personnel that are
equipped with the proper tools.
INSTALLATION
•Installation work must only be carried
out by a competent person under
qualified supervision.
•A fused isolation switch must be fitted
between the main power supply and the
SYSTEM MODBUS GATEWAY (SMG)
BOX.
•The SYSTEM MODBUS GATEWAY
(SMG) BOX should be mounted in such
a location as to allow operational and
maintenance access without obstruction
or hazard and to allow clear visibility of
indicators at all times.
•If raised platforms are required to
provide access to the SYSTEM
MODBUS GATEWAY (SMG) BOX,
they must not interfere with normal
operation or obstruct access. Platforms
and stairs should be of grid or plate
construction with safety rails on all open
sides.
Risk of Danger
Risk of Electric Shock
Risk of High Pressure
Consult Manual
OPERATION
•The SYSTEM MODBUS GATEWAY
(SMG) BOX must only be operated by
competent personnel under qualified
supervision.
•Never remove or tamper with safety
devices, guards or insulation materials
fitted to the SYSTEM MODBUS
GATEWAY (SMG) BOX.
•The SYSTEM MODBUS GATEWAY
(SMG) BOX must only be operated at
the supply voltage and frequency for
which it is designed.
•When main power is switched on, lethal
voltages are present in the electrical
circuits and extreme caution must be
exercised whenever it is necessary to
carry out any work on the unit.
•Do not open access panels or touch
electrical components while voltage is
applied unless it is necessary for
measurements, tests or adjustments.
Such work should be carried out only by
a qualified electrician equipped with the
correct tools and wearing appropriate
protection against electrical hazards.
•All air compressors and/or other
equipment connected to the unit should
have a warning sign attached stating
“THIS UNIT MAY START WITHOUT
WARNING” next to the display panel.
•If an air compressor and/or other
equipment connected to the unit is to be
started remotely, attach two warning
signs to the equipment stating “THIS
UNIT CAN BE STARTED REMOTELY”.
Attach one sign in a prominent location
on the outside of the equipment, and the
other sign inside the equipment control
compartment.
3
MAINTENANCE AND REPAIR
•Maintenance, repairs or modifications
must only be carried out by competent
personnel under qualified supervision.
•If replacement parts are required, use
only genuine parts from the original
equipment manufacturer, or an
alternative approved source.
•Carry out the following operations
before opening or removing any access
panels or carrying out any work on the
SYSTEM MODBUS GATEWAY (SMG)
BOX:
i. Isolate the SYSTEM MODBUS
GATEWAY (SMG) BOX from
the main electrical power
supply. Lock the isolator in the
“OFF” position and remove the
fuses.
ii. Attach labels to the isolator
switch and to the unit stating
“WORK IN PROGRESS - DO
NOT APPLY VOLTAGE”. Do
not switch on electrical power
or attempt to start the SYSTEM
MODBUS GATEWAY (SMG)
BOX if such a warning label is
attached.
•Make sure that all instructions
concerning operation and maintenance
are strictly followed and that the
complete unit, with all accessories and
safety devices, is kept in good working
order.
•The accuracy of sensor devices must be
checked on a regular basis. They must
be calibrated when acceptable
tolerances are exceeded. Always
ensure any pressure within the
compressed air system is safely vented
to atmosphere before attempting to
remove or install a sensor device.
•The SYSTEM MODBUS GATEWAY
(SMG) BOX must only be cleaned with
a damp cloth, using mild detergents if
necessary. Avoid the use of any
substances containing corrosive acids
or alkalis.
•Do not paint the control faceplate or
obscure any indicators, controls,
instructions or warnings.
•
4
MODBUS RTU
1. MODBUS Table(s)
This document discusses generic MODBUS communications and how to implement the software specific ‘MODBUS Table’
information. MODBUS communication formatting may differ from controller to controller and you may require more than one
‘MODBUS Table’.
Always check the software variant identification and version number for a controller or unit with the variant and version of the
‘MODBUS Table’ supplied. In some instances the information contained in a ‘MODBUS Table’ may not be applicabl e to a
controller or unit installed with the same software variant but a different version number.
2. General
MODBUS RTU (Remote Terminal Unit) is a master-slave type protocol. An X-Series Automation System Controller or
Intellisys Controller functions as the slave device. Information requests or commands are communicated from master to slave
only through a System Modbus Gateway Box (SMG). The SMG Box will always respond to communications from a remote
master device in accordance with the MODBUS RTU protocol standard.
The MODBUS protocol is used to communicate with personal computers (PC), Programmable Logic Controllers
(PLC’s), or Distributed Control Systems (DCS) over the Network port. The SMG Box only responds to three MODBUS
commands, Read Holding Register 03 (03 Hex), Preset Single Register 06 (06 Hex), and Preset Multiple Registers command
16 (10 Hex) (See Modicon MODBUS Protocol Reference Guide, PI-MBUS-300 Rev. J, for more details on MODBUS).
3. Communication Link
MODBUS is implemented using a two-wire RS485 industry standard communications link operating in master-slave mode.
Polarity of the two RS485 wires (L1+ and L2-) is important; reversal will disrupt communications.
4. RS485 Serial Data Format
The RS485 MODBUS port is a 2-wire operating with an asynchronous serial data format: 1 start bit / 8 data bits / 1 stop / no
parity (1,8,1,N) - transmitted at 9600 baud.
5. Message Data Format
The bytes of the MODBUS RTU message must be sent in one message package. The RTU protocol allows for a maximum
pause of 1.5 byte-times between 2 consecutive bytes of a message.
A pause longer than 1.5 byte-times will render the message invalid and it will be ignored.
Message data format is dependant on function and will consist of a combination of the following elements:
1) Destination address (slave network address)
2) Function Code
3) Data start address (slave register start address)
4) Number of registers, number of bytes of data
5) Message data
6) CRC checksum
5.1 Message Destination Address
The ‘destination address’ must be correct for the ‘slave’ controller device for which the message is inten ded. An address can
be from 01Hex to EFHex. The SMG Box is transparent and addresses must be for the destination ‘slave’ controller or unit.
Each controller or unit must be set with a unique address.
5.2 Message Function Codes
Numbe r of
Registers
CRC Check SumSlave Address Function CodeStar t Address
010340 0600 0230 CA
The message function code defines the required data processing operation of the slave controller. Although several types of
message function codes are defined by the MODBUS standard, only the message function code types working directl y with
registers are implemented on controller units:
03H Read Holding Register(s) – Get (Get Data) or Adv (Advise Data) (X-Series) and Read (Intellisys)
06H Preset Single Register - Write (Intellisys Only)
10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series only)
Any other message function code type will result in an EXCEPTION response.
5
5.3 Message Data Start Address
Numbe r of
Registers
CRC Check SumSlave AddressFun cti on CodeStart Address
010340 0600 0230 CA
The message data start address (16bit word) designates the initial register address location in the contr oller from which the
data is processed. Start address information is contained in the ‘MODBUS Table’.
Note: high-byte transmitted first followed by low-byte.
5.4 Message Data
The message data content depends on the message function code type.
03H Read Holding Register(s) – Get (Get Data), Adv (Advise Data) (X-Series) or Read (Intellisys)
Numbe r of
Registers
010340 0600 0230 CA
CRC Check SumSlave AddressFun cti on CodeStart Address
Slave address + function code ’03 Hex’ + start address of registers in slave memory + 16bit integer value that determine s the
size (in 16bit ‘word’ registers) of the message data being requested (00 02 = 2 registers of data). This is the number o f 16bit
registers to read. A maximum of 32 registers can be read at one time. This information is contained in the ‘MODBUS Table’.
06H Preset Single Register - Write (Intellisys Only)
DATA
byte 0 byte 1
010600 6F00 5FFE BC
CRC Check SumSlave Address Function CodeStar t Address
Slave address + function code ’06 Hex’ + start address of register(s) in slave memory to be set then the ‘data’ itself. This
information is contained in the ‘MODBUS Table’.
10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series onl y)
Numbe r of
Registers To Be
Set
Number of Bytes
of Da t a
DATA
1st Register byte
0 byte 1
DATA
2nd Register
byte 2 byte 3
CRC Check Su mSlave AddressF unction CodeStart Address
011040 1800 020400 001B 5F88 0E
Slave address + function code ’10 Hex’ + start address of register(s) in slave memory to be set + 16bit (integer valve of the
number of registers to be set) + 8bit ‘byte’ (integer value for the number of following data bytes) then the ‘data’ itself. This
information is contained in the ‘MODBUS Table’.
Note: A function ’10 Hex’ Set message also requires an additional byte defining the number of ‘data’ bytes in the data
message. This will always be the number of ‘registers’ multiplied by 2 as each ‘data’ register consists of 2 bytes (if number of
‘data’ registers = 2 then number of ‘data’ bytes = 4).
5.5 Message CRC Checksum
Numbe r of
Registers
010340 0600 0230 CA
CRC Check SumSlave Address Function CodeStar t Address
The CRC (Cyclical Redundancy Check) is a check-sum generated by means of ‘A001H polynomial’.
The CRC is two bytes containing a 16-bit binary value (word). The CRC value is calculated by the transmitting device that
appends the CRC to the end of the message. The receiving device recalculates the CRC value prior to processing of a
received message and compares the result to the actual CRC value appended to the message. If the two values do not match
the message is regarded as invalid. The CRC is initiated by first preloading a 16bit register to all 1's (FFFF Hex). Then a
process begins of applying each consecutive 8bit byte of the message to the register contents using an exclusive ‘OR’
calculation. The result is shifted one bit in the direction of the least significant bit (LSB), with the most significant bit (MSB) set
at ‘0’. The LSB is then examined; if ‘1’ the register content is applied to the polynomial value ‘A001’ Hex (1010 0000 0000
0001) using an exclusive ‘OR’ calculation - if ‘0’ no exclusive OR takes place. This process is repeated until eight ‘bit’ shifts
have been performed. After the eighth bit shift, the next 8bit message byte is applied to the register contents using an
exclusive ‘OR’ calculation. The bit shift and re-calculation process is then repeated again. When all message bytes have been
processed the final content of the 16bit register is the message CRC value.
Only the 8bits of ‘data’ in each message character is used for generating the CRC; start, stop and parity bits are ignored.
Note: When the 16bit CRC value is appended to a message, the low order byte must be transmitted first followed by the high
order byte. An incorrect or byte reversed check sum will render the message invalid and it will be ignored.
6
6. Slave Response Timeout
A slave controller may not answer immediately. Ensure the ‘slave timeout’ setting of the ‘master’ device is set to a value no
less than 500ms. If the ‘slave’ device fails to receive a valid message due to a communication disruption, parity error, CRC
error or other reasons, no response is given and the master must process a timeout condition in this instance. If the ‘slave’
receives a valid message that cannot be processed an exception response will be returned.
7. Message Answer From Slave to Master
The format of the ‘slave’ controller answer is similar to the original master request format; the message data content depends
on the message function code type.
The ‘address’ and ‘code’ of the slave answer is identical to the original request message; the address is the ‘slave’ device
address and the ‘code’ is a repeat of received function code type from the master. The remainder of the message is
dependant on the requested function code type. The CRC checksum is re-calculated for the answer message character s
using the specified CRC process.
3) bytes of data 1byte (number of bytes in ‘data’ ans wer)
4) data (high byte of each register transmitted first)
5) CRC checksum 2bytes (low byte first followed by high byte)
06Hex - Preset Single Register: write to single register
Slave Address Function CodeStart Address
010600 6F00 5FFE BC
DATA
byte 0 byte 1
CRC Check Sum
1) slave address 1byte
2) function code 1byte
3) bytes of data 1byte (number of bytes in ‘data’ ans wer)
4) data (high byte of each register transmitted first)
5) CRC checksum 2bytes (low byte first followed by high byte)
10H Preset Multiple Registers – Set (Set Data) or Cmd (Command Instruction) (X-Series onl y)
Number of
Registers
011040 1800 02D4 0F
CRC Check SumSlave AddressFuncti on CodeStart Address
1) slave address 1byte
2) function code 1byte
3) number of registers set 2 bytes
4) CRC checksum 2 Bytes (low byte first followed by high byte)
8. Exception Response
If the ‘slave’ device receives a request that cannot be processed an ‘exception response’ is given. An exception response
message consists of the following elements:
2) Function Code (1 byte): In a normal response, the slave repeats the function code of the original master request. All
function codes have an MSB (most significant bit) of 0 (values are all below 80 hexadecimal). In an exception response,
the slave sets the MSB of the function ‘code’ to 1. This makes the ‘code’ value 80 Hex greater than the received ‘code’
value from the master.
3) Data (1 byte): The ‘data’ response will contain a ‘1 byte’ value exception code.
4) CRC Checksum (2 byte).
CRC Check SumSlave Address Function CodeError Code
0190044D C3
7
Exception Codes:
01H Illegal Function Code
The requested ‘code’ function is not supported.
02H Illegal Data Address
The requested ‘data start address’ is not supported.
03H Illegal Data Value
The requested ‘data’ value is not supported.
04H Function Error
The slave cannot execute the request or the request type is inhibited.
9. Troubleshooting
Problem: No ‘slave’ response or corrupt MODBUS message
Solution: Check that the ‘slave’ controller is set for the anticipated slave address
Check that all ‘slave’ c ontrollers are set with a unique system address
Check that the controller is set for MODBUS RTU mode (if applicable)
Check that the ‘master’ is operating in MODBUS RTU mode
Check that the ‘master’ baud r ate, parity bit and number of stop bits are correct
Check that the ‘master ‘response timeout is set for a minimum of 500ms
Check that the ‘master’ is implementing the specified CRC check sum process
Check RS485 wiring polarity and security of connections
Problem: Last character of MODBUS message is corrupted
Solution: Add a delay of 2ms after last character received before relea s ing RTS signal
Problem: The MODBUS master message is reflected in the slave answer
Solution: Inhibit RX/TX echo on ‘master’ device communicati ons port
8
MODBUS Tables X-Series
A ‘MODBUS table’ describes the “items” used to access information in the memory registers of different types of controller, or
similar controllers using different application software variants or versions. The MODBUS Table will contain the vali d message
items (“Name”) together with the Function Code (Function), Register Start Address (“Register Address”), Register Size
(“Register Length”) and a definition for coding and decoding the item data (“Coding”). A ‘MODBUS Table’ order form, detailing
the required order information, can be found on the last page of this document.
1. Table Item Format
Each ‘item’ of a ‘MODBUS Table’ will define the massage format to read or set the information contained in the slave
controller register(s):-
Name
Descriptive ‘name’ or ‘item tag’ for the data item. The ‘Name’ is not used in code or message
formatting and serves only as a reference for the defined item.
Function
The Hex code required that instructs the slave (Intellisys controller) to perform a GET, ADV
(Advise), CMD (command) or SET function.
Register Address
Register Length
Coding
Menu
The slave controller register start address for the defined processing function.
The number of registers to be processed.
How to construct or interpret the data elements of a message.
Controller menu item reference.
Note: see “MODBUS RTU” for a detailed description of ‘Function’, ‘Register Address’ and ‘Register Length’ formats.
2. Name and Function
The ‘name’ for each table item will always start with 3 characters that describe the function type:
Adv Advise Function (03Hex) – same format as a Get function, see ‘Advise Function’.
Get Read from register (03Hex)
Set Write to register (10Hex)
Cmd Command (10Hex) – same format as a Set function; will instruct the slave to perform a defined action or
process
3. Coding
Item coding definitions specify the ‘number of data bytes’ and the ‘data conversion type’. In some instances a data message
may contain multiple sets of data items; an ‘Advise’ message for example. In this instance the ‘start location of data’ within the
message is also specified to enable extraction of the required data item from the entire message data.
Number of data bytes:
This specifies the length of the item data in bytes (6 = 6 bytes (3 registers) of data)
Start location of data bytes:
Number of Data
Bytes to Follow
DATA
1st Register byte
0 byte 1
DATA
2nd Register
byte 2 byte 3
DATA
3rd Register byte
4 byte 5
CRC Check SumSlave Address Function Code
01030609 0000 6500 A830 4D
If a data message consists of more than one set of data items (multiple item data message) the ‘start location’ specifies where
the first byte of the data associated with in item begins. If, for example, a 6 byte (3 register) answer is returned that consists of
three different ‘2 byte’ item data values, a ‘start location of data bytes’ = ‘2’ indicates that the item data starts with the 3rd byte
(byte 2) of the data message. The 1st byte of a data message is regarded as byte 0(zero). In this instance the ‘number of data
bytes’ will be ‘2’ indicating that the data associated with the item is 2 bytes of data in length. A ‘start location’ of byte ‘2’ and
register length of ‘1’ (register = 2 bytes) means the data is contained in the 3rd and 4th bytes of the data message. If no ‘start
location’ is specified then data associated with the item will start with the first byte (byte 0) of the message data.
Data Conversion Type:
This specifies how to interpret the data; refer to the ‘Data Conversion Type’ list in the Modbus Table.
For example: If the ‘Data Conversion Type’ = CODED, STATUS then the decimal integer value of the data has a defined
meaning; refer to the ‘STATUS’ Coded data list in the ‘MODBUS Table’ for definitions. If the ‘Data Conversion Type’ = PSI
then the decimal integer value of the data is ‘pressure’ in ‘psi’ units.
9
4. Menu Reference
The menu structure of a controller has menu pages that contain a number of menu page ‘items’.
example menu and items
For example: menu pages P00, P01, P02 > P’n’.
Menu page P00 is the normal running list of display items that can be accessed and viewed on the controller displ ay without
access code. These items are ‘read only’ and consist of status, hours run and other general control or monitoring value (s).
Menu pages other than P00 are setup and configuration items that require an ‘access code’ when accessing the items on the
controller display.
Each menu page has a list of items that are referenced ‘1, 2, 3 > ‘n’.
abc
P01
For example, a menu reference of P01.02 “AB” refers to menu item ‘2’ of menu page P01.
Each menu page item reference also has a two or three alphanumeric character item identification that is displayed by the
controller. With a menu reference the controller manual can be examined to determine the exact function, definition, scope
and limits for the specified item value.
Items that do not have a ‘Menu’ reference are general controller status or menu page P00 items.
5. ‘Adv’ Advise Function
The ‘Advise’ function is a special type of ‘Get’ function. Each ‘Advise’ function item has an equivale nt ‘Get’ function; both
functions will provide a similar result.
Controllers on a Multi485 network will routinely broadcast key value and status specific data to all other controllers on the
network. This information is used, for example, by a system management unit for systems monitoring and control functions. A
SMG Box will automatically capture, store and continuously update these information items for each controller on the network.
Adv are Routine network broadcasts that occur every 2 seconds. Th transmission of this data consumes no network
bandwidth. (The maximum recommended request rate is 1 request every 2 seconds.)
This facility provides a method of retrieving ‘Adv’ data items directly from the SMG Box resulting in a faster response time for
information requests from a master. The method also has the advantage of reducing the amount of data traffic on the Multi485
network enabling system management controllers to perform there functions without potential communication delays. For this
reason MODBUS ‘Adv’ functions are preferable to ‘Get’ functions when implemented on a Multi485 network that consists of a
system management controller with multiple machine controllers.
6. ‘Adv’ Advise Function – Single Item Format Option
Controllers or units on a Multi485 network routinely broadcast general status and key performance information. The SMG Box
will capture and store each ‘Broadcast’ detected. The Gateway ‘Broadcast’ registers will always contain the latest ‘broadcast’
information for each controller or unit on the Multi485 network. When a Modbus ‘Adv’ request is made the SMG Box will
respond immediately with information from it’s own ‘Broadcast’ registers for the unit address specified. This function reduces
network activity and enables a faster Modbus response to commonly requested data.
A standard ‘Advise’ function defined in the ‘MODBUS Table’ will show the entire ‘broadcast’ being returned as a response.
The table will define for each ‘name’ item where in the returned data message the actual requ ested data can be found. The
‘master’ must then extract the required data from the returned data message. This method is very efficient as the master can
extract all ‘broadcast’ data from the single returned data message without the need to perform multiple requests for each
individual data item contained in a single slave controller ‘broadcast’ message.
Some ‘master’ devices may not be equipped with the necessary data message memory to handle a large message of many
bytes or have the ability to extract multiple data items from a single data message item. In this instance an alternative ‘Ad vise’
function request method can be implemented.If the ‘Advise’ items of a ‘MODBUS Table’ are examined it will be seen that the
‘Register Address’ for each individual ‘Advise’ item contained in a single slave controller ‘broadcast’ message will have the
same start address (Register Address). If the entire ‘broadcast’ data message is 7 registers (14 bytes) in length and only the
2nd register (2 bytes) of item data is required, it is possible to specify a ‘Register Address’ that is 2 bytes higher (skip the first
2 bytes of the broadcast data message) with a ‘Register Length’ that is consistent with the required item data length. This will
instruct the MODBUS Gateway to extract the 2 bytes of required item data from the entire broadcast data message and only
return the required 2 bytes of data as a response. Using this method an ‘Advise’ function can be handled by a ‘master’ in
exactly the same way as a ‘Get’ function.
01.02AB
10
For Example: (AdvDeliveryPressure):
The ‘broadcast’ of an example slave controller may be 6 bytes of data (3 registers) in length starting at register address
location ‘F000’ Hex. The 1st byte (byte 0) is 8bits coded status, the 2nd byte (byte 1) is 8bits status flags which together form
a single 16bit status register (1st register). The 3rd and 4th bytes (byte 2 and byte 3) are a single16bit register (2nd regist er)
containing a ‘delivery pressure’ value. The 5th and 6th bytes (byte 4 and byte 5) are a sin gle 16bit register (3rd register)
containing a ‘delivery temperature’ value. From an example ‘MODBUS Table’ it may be seen that the ‘Register Address’ for all
four of these separate ‘Adv’ items is ‘F000 Hex’ (the start address of the entire ‘Broadcast’ message that contains the data
specified).
An entire ‘Broadcast’ message may, for example, contain 3 registers (6 bytes) of data. For a particular item the ‘Modbus
Table’ may show the ‘start address’ for the entire broadcast to be ‘F000’ with a length of 3 registers (6 bytes). The Modbus
Table will indicate that the required data is 2 bytes long (number of data bytes) starting at the 2nd byte of data in the entire
broadcast (start location of data bytes).
Name AdvDeliveryPressure
Modbus Function 03
Modbus Register Address F000 (start address of entire Broadcast message)
Modbus Register Length 0003 (length of entire Broadcast message)
Coding Number of data bytes = 2 (length of AdvDeliveryPressure data)
Start location of data bytes = 2 (the 2 data bytes of the AdvDeliveryPressure data item
start at byte 2 in the Broadcast message = bytes 2 and 3 of the message)
Data Conversion Type = PSI
If only the ‘delivery pressure’ (AdvDeliveryPressure) data value is required a new ‘Advise’ req uest message format can be
constructed from the Modbus Table definition:
Name AdvDeliveryPressure
Modbus Function 03
Modbus Register Address F001 (start at the second register, byte 2, of the Broadcast)
Modbus Register Length 0001 (only return one register, 2 bytes, of data)
Using the new ‘Advise’ message format the SMG Box will return only the 2nd Broadcast message register (2 bytes) containing
the ‘delivery pressure’ data value.
It is only possible to manipulate a Modbus message format using ‘registers’ (1 register = 2 bytes = 1 word = 16bits); it is
not possible to manipulate addresses or register lengths to a single byte of data. At least one register (2 bytes) of data must
be specified even if only one byte of information is required. The ‘master’ must extract the required byte of data from the
returned message.
The data type (the definition of the returned data) may be different when using an ‘Advise’ function than it is when using a
‘Get’ function for the same information. The ‘delivery pressure’ returned by an ‘Advise’ function will be 2 bytes in length and
will represent pressure as an integer value in ‘psi’ units (PSI). The ‘delivery pressure’ returned by a ‘Get’ functio n may, for
example, be 4 bytes (2 registers) in length and represent a 32bit signed integer value in miliBar units (mBAR). Always check
the item ‘Coding’ definition to establish the data definition type.
Register addresses shown are examples only
7. ‘Cmd’ Command Function
A ‘Command’ function will instruct the ‘slave’ controller or unit to execute a pre-defined action or process. With a command
type message the content of the ‘message data’ from the ‘master’ must always be the same value as the ‘lower byte’ of the
command register address. For example: if the command item ‘Register Address’ = 3302 then the ‘data’ value must be ’00 02’
Hex.
Slave Address Function CodeStart Address
Number of
Registers To Be
Set
Number of Bytes
of Data
DATA
CRC Check Sum
011033 0200 010200 0225 70
It is the act of setting the specified register in the ‘slave’ controller with the defined ‘data’ value that initiates the action or
process. An incorrect ‘data’ value will result in an exception response. If the ‘command’ is accepted the ‘slave’ will answer with
a normal ‘Set’ register response. If the slave is unable to execute the command it will give a code ‘04’ exception response.
Example:
Using a command function item to set the specified item register to the correct value, the ‘slave’ controller is instructed to
perform the defined action or process. In the case of a ‘CmdStart’ item, for example, the ‘slave’ controller is instructed to start
the machine. The implementation of a ‘Cmd’ function message by the ‘master’ is identical to a ‘Set’ function message; both
operations use function code ‘10 Hex’ to write data to a slave controller register.
Name CmdStart
Modbus Function 10
Modbus Register Address 3300
Modbus Register Length 0001
Coding Number of data bytes = 1
Slave Answer Message “01 10 3300 0001 0E8D” if start command executed or “01 90 04 4D C3” exception
response if not executed, ‘90’ = repeat of ‘10’ function code with MSB set to ‘1’ and ‘04’ =
exception error code.
Register addresses shown are examples only
Note: Names that begin with CMD are Non-routine. This data must be written to the device. (The maximum recommended
request rate is 2 requests per second up to 32 words per request.)
8. ‘Get’ Function
Using the MODBUS Table a read data (Get) function message can be constructed:
Name GetDeliveryPressure Modbus
Function 03
Modbus Register Address 4006
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Conversion Type = mBAR
GetDeliveryPressure (request to slave at address ‘01’ Hex)
Master Request Message “01 03 400 6 0002 31CA” (31CA = CRC check sum)
Register addresses shown are examples only
Note: Names that begin with Get are Non-routine. This data must be requested from the device. (The maximum
recommended request rate is 2 requests per second up to 32 words per request.)
12
9. ‘Set’ Function
Using the MODBUS Table a write data (Set) function message can be constructed:
Name SetLoadPressure Modbus
Function 10
Modbus Register Address 4018
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Conversion Type = mBAR
SetLoadPressure (to slave at address ‘01’ Hex)
Master Write Message “01 10 4018 0002 04 0000 1B58 C9CC” (C9CC = CRC)
Register addresses shown are examples only
Note: Names that begin with Set are Non-routine. This data must be written to the device. (The maximum recommended
request rate is 2 requests per second up to 32 words per request.)
10. Data Coding Definitions:
Definitions for ‘data units’ and ‘data conversion types’ are listed for each ‘item’ in the “MODBUS Table” document.
All ‘data’ values are ‘whole’ numbers (integers); decimal places are not permitted in MODBUS data messages.
All ‘data’ values are unsigned (always positive) unless otherwise stated. Values specified as ‘SIGNED’ in the MODBUS Table
can be negative in accordance to the standard data convention for ‘signed’ number values.
10.1 Data Types
Each standard definition will start with a “key” word that defines the data type:-
The following are selected examples; data types not included below are detaile d in individual ‘Modbus Tables’
Type Description
Coded a decimal value that has a defined definition; see the ‘Coded’ lists in
the ‘MODBUS Table’ for value definitions
Value a ‘whole’ number or value in the specified units
Pressure a ‘whole’ number defining a pressure in the specified units
Temperature a ‘whole’ number defining a temperature in the specified units
Time a ‘whole’ number defining a time period in the specified units
Electrical a ‘whole’ number defining a volt, amp, power, or speed value in the
specified units
Clock Clock values are relevant to real time clock functions; for example
pressure schedules. These ‘whole number’ unsigned values are
‘packaged’ multiple values and must be interpreted as follows.
13
Clock Data Type Coding
HH_MM 1) Divide the value by 60 = Hours (0 to 23)
2) The remainder (modulus) = Minutes (0 to 59)
Example for a value of ‘1050’ Hours = 1050 / 60 = 17.5 = 17 Hours Minutes = remainder = 30 = 30 Minutes Time = 17:30 (5:30pm)
D_HH_MM 1) Divide the value by 10000 = Day (1 = Monday, 7 = Sunday)
2) Divide the remainder (modulus) by 60 = Hours (0 to 23)
3) The remainder (modulus) = Minutes
Example for a value of ‘31050’ Day = 31050 / 10000 = 3.105 = 3 = Wednesday
Hours = = remainder / 60 = 17.5 = 17 Hours
Minutes = remainder = 30 = 30 Minutes Day/Time = Wednesday 17:30 (5:30pm)
YYYY_DD_MO 1) Divide the value by 10000 = Year
2) Divide the remainder (modulus) by 100 = Day (1 to 31)
3) The remainder (modulus) = Month (1 to 12)
Example for a value of ‘20051605’ Year = 20051605 / 10000 = 2005.1605 = Year 2005
Day = remainder / 100 = 16.05 = Day 16 Month = remainder = 5 = Month 5 Date = 16th May 2005
10.2 Data Units
The ‘MODBUS Table’ will define the ‘data units’ for each item. Data unit definitions are specified in the ‘MODBUS Table’ as a
separate list; for example:
The following are selected examples; data types not included below are detailed in the ‘Modbus Tables’
Value The engineering units will differ dependant on unit set-up or item definition.
PSI
BAR
FAH
CEL Temperature in oC
HRS Hours
% Percentage 0 to 100
BOOLEAN The number will be 0 or greater than 0, (Boolean: 0 = False, 1 = True)
BINARY The number represents a 16bit (two byte) binary value of 16bit flags.
The value must be interpreted in terms of each ‘bit’ as a set of sixteen Boolean (0 or 1) flags. These values
are compressor related or I/O Box Input related. For compressor related items the least significant bit (Bit 0)
represents compressor 1. For unit inputs the least significant bit (Bit 0) generally represents input 1.
The number is the value in the specified engineering units
Pressure in ‘psi’
Pressure in ‘Bar’
Temperature in oF
14
16 bit Register
1st Byte (byte 0)2nd Byte (byte 1)
1514131211109876543210
Bit
MSB
0000000010000001
LSB
Co m pres s or 8C om p res s o r 1
The example illustrates the bit pattern for a value of ’00 81 Hex’. This value is interpr eted as a ‘true’ condition with respect to
the item definition for compressors 1 and 8. If the ‘item’ definition is ‘Compressors Running’ then com pressors 1 and 8 are in a
‘running’ condition.
The example illustrates the bit pattern for a value of "1A 04 C2 01" Hex. A reference to ‘Bit 18’ equates to bit ‘2’ of byte ‘1’ in
the answer data message. If the ‘bit’ is ‘1’ then the condition is ‘TRUE’.
2nd Regi st er1st Reg i ster
1st Byte (by t e 0)2nd Byte (by te 1)3rd B y te (byte 2)4th B yte (by te 3)
Note: The LSB (least significant bit) of a register or byte is regarded as Bit 0(zero)
A Boolean (true/false) can be established from examining the specified ‘bit’ of the
16bit register. If the item specifies ‘Bit 4’ then the 4th bit should be examined:
LSB
16 bit Register
1st Byte (byte 0)2nd Byte (byte 1)
1514131211109876543210
Bit
MSB
0001101010010001
LSB
AND
0000000000010000
EQUALS
0000000000010000
= 16 Decimal (Condition is TRUE)
The 4th bit of a register can be extracted by ‘masking’ the register content with “10 Hex”; if the resulting value is greater than
0(zero) then the condition is ‘True’, if the result is 0(zero) then the condition is ‘False’.
Decimal Places:
Numbers with decimal places (eg 20.55) are not permissible in MODBUS data transfer – all numbers must be integer ‘whole’
numbers. To provide ‘decimal place’ accuracy some data values are multiplied by 10, 100 or 1000 and transmitted as a
‘whole’ number (integer). In this instance the ‘Data Units’ will specify that the number represents a value to one or more
decimal places.
For example: PERCENT_DP2 = Percent to 2 decimal places
“2055” divided by 100 = 20.55%
If the ‘Data Units’ specifies “to 1 decimal place”, divide the number by 10 to convert to the correct engineering units. If the
‘Data Units’ specifies “to 2 decimal places”, divide the number by 100; if 3 decimal places divide by 1000.
15
X-SERIES AIR SYSTEM
1. General X-Series System Components
Note: example only; systems will differ from installation to installation
X8I Series Controller: Automation System Unit
Monitors and controls the air compressors, all general system and air compressor related information is governed and
available from this unit. A system will only contain one X-Series Automation System controller.
EX Box: Extension to the X-Series Unit
For connection to remote compressor(s) or other specialized compressor integration. All common air compressor status
information is sent to, and available from, the X-Series system management unit. A system may contain multiple EX Boxes.
I/O Box: Monitoring/Control of Auxiliary Equipment and/or Sensors
For monitoring and/or control of auxiliary compressed air equipment (for exam ple: dryer, auto drain, filtration differential,
isolation valves, cooling water towers/pumps, ventilation) or sensors (for example: pressure, pressure differential, dewpoint,
air flow, temperature). A system may contain multiple IO Boxes.
VSD Box: Extension to the X-Series Unit
For connection to variable speed compressor(s) or other specialized compressor integration. All common air compressor
status information is sent to, and available from, the X-Series system management unit. A system may contain multiple VSD
Boxes.
SMG Box: Remote Monitoring/Control of X-Series Units and Boxes
To provide a RS485 Modbus connection to the X8I Automation System. A system will only contain one SMG Boxes.
16
2. X-Series Network Addresses
Network Address:- Decimal (Hexadecimal)
UnitDecimal (Hex) Address
X8I 101(65)
EX, VSD, ir485/irV485, S3
(As It Relates To The
Compressor Number Assigned)
Note: I/O Unit 2 address (70Hex) is intentionally out of sequence; this is not a print error.
3. Communication Link
To Interface with a X-Series product that is equipped with a Multi485 enabled network port, or to interface with multiple XSeries products operating on a single Multi485 system network, a SMG Box unit is required. T he SMG Box forms the interface
between the Multi485 protocol and MODBUS RTU master/slave communications link.
SMG Box connectivity is implemented using a two-wire RS485 industry standard commun ications link operating in point-topoint, master-slave mode. In use the SMG Box is transparent and each X-Series system unit is accessible using individual
system device addresses.
Polarity of the two MODBUS RS485 wires (L1+ or ‘A’ and L2- or ‘B’) is important; reversal will inhibit communications and
result in error.
4. MODBUS TIMING
The SMG will handle ONE (1) MODBUS request at a time from the customer’s port. The maximum recommended request
rate is 2 requests per second. When a MODBUS request is received for any device connected to the XI Automation System,
that request will be forwarded to the device between sequencer broadcasts and the response from the device will then be
relayed back to the customer’s port. If a second MODBUS command is sent before the first command has been responded to,
the second command will be ignored.
5. RS485 MODBUS Serial Data Format
The SMG supports only the RTU transmission mode. The user must configure their serial port communication parameters
(baud rate, parity mode, etc.) during configuration to match those of the SMG Box. The SMG Box port operates with an
asynchronous serial data format:
SMG Communication Parameters
Start Bit: 1
Data Bits: 8
Stop Bit: 1
Parity: None
Baud Rate: 9600
1-8-1-N-9600
17
MODBUS RTU Definitions For VSD Box
Name AdvStatusRegister
Modbus Function 03
Modbus Register Address F000
Modbus Register Length 0003
Coding Number of data bytes = 1
Data Conversion Type = CODED,STATUS
Conversion Table for CODED,STATUS can be found at the end of this document
Name AdvStatusFlags
Modbus Function 03
Modbus Register Address F000
Modbus Register Length 0003
Coding Number of data bytes = 1
Start location of data bytes = 1
Name AdvDeliveryPressure
Modbus Function 03
Modbus Register Address F000
Modbus Register Length 0003
Coding Number of data bytes = 2
Start location of data bytes = 2
Data Units = PSI
Name AdvDeliveryAirTemperature
Modbus Function 03
Modbus Register Address F000
Modbus Register Length 0003
Coding Number of data bytes = 2
Start location of data bytes = 4
Data Units = FAH
Name GetSoftwareVersionIdString
Modbus Function 03
Modbus Register Address 3400
Modbus Register Length 0003
Coding Number of data bytes = 6
Data Conversion Type = STRING
Name GetSoftwareVersionRevString
Modbus Function 03
Modbus Register Address 3403
Modbus Register Length 0003
Coding Number of data bytes = 6
Data Conversion Type = STRING
Name CmdStart
Modbus Function 10
Modbus Register Address 3300
Modbus Register Length 0001
Coding Number of data bytes = 1
Name CmdStop
Modbus Function 10
Modbus Register Address 3301
Modbus Register Length 0001
Coding Number of data bytes = 1
18
Name CmdReset
Modbus Function 10
Modbus Register Address 3306
Modbus Register Length 0001
Coding Number of data bytes = 1
Name CmdClearLog
Modbus Function 10
Modbus Register Address 3307
Modbus Register Length 0001
Coding Number of data bytes = 1
Name GetStatus
Modbus Function 03
Modbus Register Address 3406
Modbus Register Length 0003
Coding Number of data bytes = 6
Data Conversion Type = CODED,STATUS
Conversion Table for CODED,STATUS can be found at the end of this document
Name GetAnalogInput1
Modbus Function 03
Modbus Register Address 3100
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Units = ADSTEPS
Name GetAnalogInput2
Modbus Function 03
Modbus Register Address 3101
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Units = ADSTEPS
Name GetAnalogInput3
Modbus Function 03
Modbus Register Address 3102
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Units = ADSTEPS
Name GetAnalogOutput1
Modbus Function 03
Modbus Register Address 310C
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Units = ADSTEPS
19
Name GetDigitalInputs
Modbus Function 03
Modbus Register Address 310E
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Units = BINARY
bit value = 0 = digital input INACTIVE
bit value = 1 = digital input ACTIVE
bit = (Config, Delay in ms)
0 = EMERGENCY_STOP (Normal Closed, 0)
1 = READY_RUN (Pulsed, 0)
2 = SPARE_1 (Normal Open, 0)
3 = SPEED_DETECT (Normal Open, 100)
4 = SPARE_2 (Normal Open, 200)
5 = LOAD_MAINTENANCE (Pulsed, 0)
6 = AUXILIARY_ALARM (Pulsed, 0)
7 = AUXILIARY_TRIP (Normal Closed, 100)
Name GetDigitalInputsConfiguration
Modbus Function 03
Modbus Register Address 310F
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Units = BINARY
bit value = 0 = digital input NO
bit value = 1 = digital input NC
bit =
0 = EMERGENCY_STOP
1 = READY_RUN
2 = SPARE_1
3 = SPEED_DETECT
4 = SPARE_2
5 = LOAD_MAINTENANCE
6 = AUXILIARY_ALARM
7 = AUXILIARY_TRIP
Name GetDigitalOutputs
Modbus Function 03
Modbus Register Address 3110
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Units = BINARY
bit value = 0 = digital output OFF
bit value = 1 = digital output ON
bit =
0 = RELAY_SEQUENCE
1 = RELAY_SPARE1
2 = RELAY_SPARE2
3 = RELAY_LOAD
4 = RELAY_FUNCTION_1
5 = RELAY_FUNCTION_2
Name GetRunningHours
Modbus Function 03
Modbus Register Address 400A
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.01 'H1'
Menu = P10.06 'H1'
20
Name GetParUnloadPressure
Modbus Function 03
Modbus Register Address 4010
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = mBAR
Menu = P01.01 'Pu'
Name GetParLoadPressure
Modbus Function 03
Modbus Register Address 4012
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = mBAR
Menu = P01.03 'PL'
Name GetFaultErrorLog1Fault
Modbus Function 03
Modbus Register Address 4017
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.02 '01'
Name GetFaultErrorLog1RunningHours
Modbus Function 03
Modbus Register Address 4018
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.02 '01'
Name GetFaultErrorLog2Fault
Modbus Function 03
Modbus Register Address 401B
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.03 '02'
Name GetFaultErrorLog2RunningHours
Modbus Function 03
Modbus Register Address 401C
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.03 '02'
Name GetFaultErrorLog3Fault
Modbus Function 03
Modbus Register Address 401F
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.04 '03'
21
Name GetFaultErrorLog3RunningHours
Modbus Function 03
Modbus Register Address 4020
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.04 '03'
Name GetFaultErrorLog4Fault
Modbus Function 03
Modbus Register Address 4023
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.05 '04'
Name GetFaultErrorLog4RunningHours
Modbus Function 03
Modbus Register Address 4024
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.05 '04'
Name GetFaultErrorLog5Fault
Modbus Function 03
Modbus Register Address 4027
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.06 '05'
Name GetFaultErrorLog5RunningHours
Modbus Function 03
Modbus Register Address 4028
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.06 '05'
Name GetFaultErrorLog6Fault
Modbus Function 03
Modbus Register Address 402B
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.07 '06'
Name GetFaultErrorLog6RunningHours
Modbus Function 03
Modbus Register Address 402C
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.07 '06'
22
Name GetFaultErrorLog7Fault
Modbus Function 03
Modbus Register Address 402F
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.08 '07'
Name GetFaultErrorLog7RunningHours
Modbus Function 03
Modbus Register Address 4030
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.08 '07'
Name GetFaultErrorLog8Fault
Modbus Function 03
Modbus Register Address 4033
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.09 '08'
Name GetFaultErrorLog8RunningHours
Modbus Function 03
Modbus Register Address 4034
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.09 '08'
Name GetFaultErrorLog9Fault
Modbus Function 03
Modbus Register Address 4037
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.10 '09'
Name GetFaultErrorLog9RunningHours
Modbus Function 03
Modbus Register Address 4038
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.10 '09'
Name GetFaultErrorLog10Fault
Modbus Function 03
Modbus Register Address 403B
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.11 '10'
23
Name GetFaultErrorLog10RunningHours
Modbus Function 03
Modbus Register Address 403C
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.11 '10'
Name GetFaultErrorLog11Fault
Modbus Function 03
Modbus Register Address 403F
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.12 '11'
Name GetFaultErrorLog11RunningHours
Modbus Function 03
Modbus Register Address 4040
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.12 '11'
Name GetFaultErrorLog12Fault
Modbus Function 03
Modbus Register Address 4043
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.13 '12'
Name GetFaultErrorLog12RunningHours
Modbus Function 03
Modbus Register Address 4044
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.13 '12'
Name GetFaultErrorLog13Fault
Modbus Function 03
Modbus Register Address 4047
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.14 '13'
Name GetFaultErrorLog13RunningHours
Modbus Function 03
Modbus Register Address 4048
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.14 '13'
24
Name GetFaultErrorLog14Fault
Modbus Function 03
Modbus Register Address 404B
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.15 '14'
Name GetFaultErrorLog14RunningHours
Modbus Function 03
Modbus Register Address 404C
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.15 '14'
Name GetFaultErrorLog15Fault
Modbus Function 03
Modbus Register Address 404F
Modbus Register Length 0001
Coding Number of data bytes = 2
Data Conversion Type = CODED,ERROR
Conversion Table for CODED,ERROR can be found at the end of this document
Menu = P02.16 '15'
Name GetFaultErrorLog15RunningHours
Modbus Function 03
Modbus Register Address 4050
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = HRS
Menu = P02.16 '15'
Name GetVsdSpeedPercentActual
Modbus Function 03
Modbus Register Address 408C
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = PERCENT_DP2
Name GetDeliveryPressureOut
Modbus Function 03
Modbus Register Address 40A4
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = mBAR
NameGetInternalPressureOut
Modbus Function 03
Modbus Register Address 40A6
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = mBAR
25
Name GetParSetpointPressure
Modbus Function 03
Modbus Register Address 40A8
Modbus Register Length 0002
Coding Number of data bytes = 4
Data Units = mBAR
Menu = P01.02 'Pt'
Name GetFaultRegister
Modbus Function 03
Modbus Register Address 3409
Modbus Register Length 0003
Coding Number of data bytes = 6
Data Units = BINARY
bit value = 0 = fault INACTIVE
bit value = 1 = fault ACTIVE
bit = fault
40 = (E0010) Trip - Emergency Stop
41 = (E0020) Trip - Oil Filter
42 = (E0040) Trip - Air/Oil Separator High DP
43 = (E0080) Trip - Motor Overload
44 = (E0115) Trip - Delivery Pressure Sensor
45 = (E0119) Trip - Delivery Pressure High
46 = (E0125) Trip - Delivery Temperature Sensor
47 = (E0129) Trip - Delivery Temperature High
32 = (E0131) Trip - Internal Rotation Pressure Check
33 = (E0135) Trip - Internal Pressure Sensor
34 = (E0139) Trip - Internal Pressure High
35 = (E0506) Trip - Analog Input Short Circuit On Expansion Module Ai4-1
36 = (E0507) Trip - Analog Input Short Circuit On Expansion Module Ai4-2
37 = (E0508) Trip - Digital Input Short Circuit On Expansion Module Di8R4-1
38 = (E0509) Trip - Digital Input Short Circuit On Expansion Module Di8R4-2
39 = (E0809) Trip - Differential Pressure High
24 = (E0814) Trip - Blowdown Timeout
25 = (E0821) Trip - Short Circuit
26 = (E0836) Trip - PLL Unlocked Trip
27 = (E0840) Trip - Communication Error With Expansion Module 1
28 = (E0841) Trip - Communication Error With Expansion Module 2
29 = (E0842) Trip - Communication Error With Expansion Module 3
30 = (E0843) Trip - Communication Error With Expansion Module 4
31 = (E0844) Trip - Communication Error With Expansion Module 5
16 = (E0845) Trip - Communication Error With Expansion Module 6
17 = (E0846) Trip - Delivery Pressure Sensor Problem With Selected Model
18 = (E0856) Trip - Internal Pressure Sensor Problem With Selected Model
19 = (E5000) Trip - Parameter Table Index Corrupt
20 = (E5001) Trip - IO-config Table Corrupt
21 = (A2070) Alarm - Auxiliary trip
22 = (A2118) Alarm - Delivery Pressure High
23 = (A2128) Alarm - Delivery Temperature High
8 = (A2138) Alarm - Internal Pressure High
9 = (A2808) Alarm - Differential Pressure High
10 = (A2816) Alarm - Power Failure
11 = (R3123) Run Inhibit - Delivery Temperature Low
12 = (R3137) Run Inhibit - Internal Pressure High
13 = (A4804) Service Alarm - Service Due
26
Table 1. Conversion table for 'Data Conversion Type = CODED,STATUS'
1 : Shutdown
2 : Initializing
3 : Ready to Start
4 : Standby
5 : Standby
6 : Standby
7 : Running
8 : Not responding
9 : On Load
Table 2. Conversion table for 'Data Conversion Type = CODED,ERROR'
0 : No Error
10 : (E0010) Trip - Emergency Stop
20 : (E0020) Trip - Oil Filter
40 : (E0040) Trip - Air/Oil Separator High DP
80 : (E0080) Trip - Motor Overload
115 : (E0115) Trip - Delivery Pressure Sensor
119 : (E0119) Trip - Delivery Pressure High
125 : (E0125) Trip - Delivery Temperature Sensor
129 : (E0129) Trip - Delivery Temperature High
131 : (E0131) Trip - Internal Rotation Pressure Check
135 : (E0135) Trip - Internal Pressure Sensor
139 : (E0139) Trip - Internal Pressure High
809 : (E0809) Trip - Differential Pressure High
814 : (E0814) Trip - Blowdown Timeout
821 : (E0821) Trip - Short Circuit
836 : (E0836) Trip - PLL Unlocked Trip
846 : (E0846) Trip - Delivery Pressure Sensor Problem With Selected Model
856 : (E0856) Trip - Internal Pressure Sensor Problem With Selected Model
2070 : (A2070) Alarm - Auxiliary trip
2118 : (A2118) Alarm - Delivery Pressure High
2128 : (A2128) Alarm - Delivery Temperature High
2138 : (A2138) Alarm - Internal Pressure High
2808 : (A2808) Alarm - Differential Pressure High
2816 : (A2816) Alarm - Power Failure
3123 : (R3123) Run Inhibit - Delivery Temperature Low
3137 : (R3137) Run Inhibit - Internal Pressure High
4804 : (A4804) Service Alarm - Service Due
5000 : (E5000) Trip - Parameter Table Index Corrupt
5001 : (E5001) Trip - IO-config Table Corrupt
506 : (E0506) Trip - Analog Input Short Circuit On Expansion Module Ai4-1
507 : (E0507) Trip - Analog Input Short Circuit On Expansion Module Ai4-2
508 : (E0508) Trip - Digital Input Short Circuit On Expansion Module Di8R4-1
509 : (E0509) Trip - Digital Input Short Circuit On Expansion Module Di8R4-2
840 : (E0840) Trip - Communication Error With Expansion Module 1
841 : (E0841) Trip - Communication Error With Expansion Module 2
842 : (E0842) Trip - Communication Error With Expansion Module 3
843 : (E0843) Trip - Communication Error With Expansion Module 4
844 : (E0844) Trip - Communication Error With Expansion Module 5
845 : (E0845) Trip - Communication Error With Expansion Module 6
Data Conversion Type
STRING : String of ASCII characters (1 byte represents 1 ASCII character)
SIGNED,NUMERIC Value is signed numeric
27
Data Units
mBAR Pressure in milliBar
HRS Time in Hours
UCHAR_VAL Value unsigned byte (8bit)
LONG_VAL Value signed long (32bit)
BINARY Value bitwise represented
PERCENT_DP2 Percentage to 2 decimal places
ADSTEPS AD-steps
HZ Frequency in Hertz
PSI Pressure in PSI
FAH Temperature in Fahrenheit
28
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.