Ingersoll Rand System Automation VSD B Box Operator’s Manual

Before installing or starting this unit for the first time, this manual should be studied carefully to obtain a working knowledge of the unit and/or the duties to be performed while operating and maintaining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the unit at all times.
More Than Air, Answers.
Online answers: http://www.air.irco.com
Ingersoll Rand
System Automation
VSD B Box
Operator’s Manual
C.C.N. : 80445505 REV. A DATE JANUARY 2009
TABLE OF CONTENTS
TABLE OF CONTENTS ................................................. 2
SECTION 1 – INTRODUCTION ..................................... 3
SECTION 2 — SAFETY ................................................ 3
SAFETY PRECAUTIONS...............................................3
INSTALLATION.............................................................3
OPERATION.................................................................3
MAINTENANCE AND REPAIR.......................................4
SECTION 3 — COMPRESSOR CONNECTION AND
CONTROL ...................................................................... 5
STANDARD CONTROL FEATURES AND
FUNCTIONALITY..........................................................5
VSD B BOX OPERATION............................................6
SECTION 4 — INSTALLATION ..................................... 7
UNIT LOCATION..........................................................7
POWER SUPPLY.........................................................7
RS485 NETWORK......................................................7
VSD B BOX AND X8I OR X12I CONNECTIVITY..........9
IR-5000 DISCHARGE (DELIVERY) PRESSURE
SENSOR INTERCONNECT..........................................10
IR-302 DISCHARGE (DELIVERY) PRESSURE SENSOR
INTERCONNECT.........................................................11
IR485 GATEWAY CONNECTION...............................12
SPEED MONITORING INPUT (OPTION)......................12
REMOTE OUTPUTS...................................................12
SECTION 5 — DISPLAY AND MENU OPERATION ... 13
OPERATION...............................................................13
SECTION 8 — DIAGNOSTICS ..................................... 23
SECTION 9 — FAULT CODES .................................... 23
SECTION 10 — VSD B BOX STATUS BLOCK
DIAGRAM ..................................................................... 24
SECTION 11 — PARTS LIST ....................................... 25
SECTION 12 — TECHNICAL DATA ............................ 25
SECTION 13 — WIRING DIAGRAM ............................ 26
VSD B BOX SCHEMATIC...........................................26
XPM-TAC24 SCHEMATIC........................................27
XPM-VO2 (+VDC ANALOG OUTPUT)......................27
XPM-PSU24 (24VAC TO 24VDC)...........................27
SECTION 14 — COMMISSIONING FORM ................... 28
Refer to Section Indicated
Note
SECTION 6 — COMMISSIONING ............................... 15
COMMISSIONING PROCEDURE.................................15
PHYSICAL CHECKS...................................................15
SELECTING VSD-B MODE:......................................15
COMPRESSOR PRESSURE SET POINTS...................15
VSD B BOX CONFIGURATION..................................16
TARGET PRESSURE SET POINT...............................17
SECTION 7 — SYSTEM CONFIGURATION ............... 18
DISPLAY ITEM STRUCTURE......................................18
ACCESSING THE VSD B BOX CONFIGURATION
SCREENS..................................................................18
MENU ITEMS AND SETTINGS....................................20
Important or Caution, Safety
2
SECTION 1 – INTRODUCTION
The VSD B Box is intended to provide a method of system integration for an Ingersoll Rand Bolt-On VSD (Variable Speed Drive) air compressor equipped with a an Intellisys Controller. The VSD B Box will provide the
SECTION 2 — SAFETY
SAFETY PRECAUTIONS
WARNING :
!
WARNING :
WARNING :
!
WARNING :
Before installing or operating the VSD B Box, take time to carefully read all the instructions contained in this manual, all compressor manuals, and all manuals of any other peripheral devices that may be installed or connected to the unit.
Electricity and compressed air have the potential to cause severe personal injury or property damage.
The operator should use com m on sense and good working practices while operating and maintaining this system. All applicable codes should be strictly adhered to.
Maintenance must be performed b y adequately qualified personnel that are equipped with the proper tools.
INSTALLATION
Installation work must only be carried out by a competent person under qualified supervision.
A fused isolation switch must be fitted between the main power supply and the VSD B Box.
The VSD B Box should be mounted in such a location as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times.
If raised platforms are required to provide access to the VSD B Box, they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides.
Risk of Danger
Risk of Electric Shock
Risk of High Pressure
Consult Manual
required functionality to enable system integration and efficient control using the X8I or X12I Automation System.
.
OPERATION
The VSD B Box must only be operated by competent personnel under qualified supervision.
Never remove or tamper with safety devices, guards or insulation materials fitted to the VSD B Box.
The VSD B Box must only be operated at the supply voltage and frequency for which it is designed.
When main power is switched on, lethal voltages are present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit.
Do not open access panels or touch electrical components while voltage is applied unless it is necessary for measurements, tests or adjustments. Such work should be carried out only by a qualified electrician equipped with the correct tools and wearing appropriate protection against electrical hazards.
All air compressors and/or other equipment connected to the unit should have a warning sign attached stating “THIS UNIT MAY START WITHOUT WARNING” next to the display panel.
If an air compressor and/or other equipment connected to the unit is to be started remotely, attach two warning signs to the equipment stating “THIS UNIT CAN BE STARTED REMOTELY”. Attach one sign in a prominent location on the outside of the equipment, and the other sign inside the equipment control compartment.
3
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must onl y be carried out by competent personnel under qualified supervision.
If replacement parts are required, use only genuine parts from the original equipment manufacturer, or an alternative approved source.
Carry out the following operations before opening or removing any access panels or carrying out any work on the VSD B Box:
o Isolate the VSD B Box from the main
electrical power supply. Lock the isolator in the “OFF” position and remove the fuses.
o Attach labels to the isolator switch and
to the unit stating “WORK IN PROGRESS - DO NOT APPLY VOLTAGE”. Do not switch on electrical power or attempt to start the VSD B Box if such a warning label is attached.
Make sure that all instructions concerning operation and maintenance are strictly followed and that the complete unit, with all accessories and safety devices, is kept in good working order.
The accuracy of sensor devices must be checked on a regular basis. They must be calibrated when acceptable tolerances are exceeded. Always ensure any pressure within the compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device.
The VSD B Box must only be cleaned with a damp cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis.
Do not paint the control faceplate or obscure any indicators, controls, instructions or warnings
4
SECTION 3 — COMPRESSOR CONNECTION AND CONTROL
The VSD B Box is designed to connect to an X8I or X12I Automation System unit, using a 2-wire RS485 data cable.
The VSD B Box is intended to provide a method of system integration Ingersoll Rand air compressors with an Intellisys Controller equipped with a Bolt-On VSD. The VSD B Box is used to integrate with VSD Air Compressors that are controlled by Current Pressure Sensors.
Each air compressor in a system that requires VSD B Box integration must be equipped with an individual VSD B Box and the IR485 Gateway. Any number of VSD B Boxes can be connected to the Automation System unit as long as the total number of compressors does not exceed the total number of compressors for the Automation System model.
The VSD-B Box also monitors the compressor status, as it is reported to the X8I or X12I Automation System unit, by the IR485 Gateway. This function enables the VSD-B Box to simulate all features of a standard X8I or X12I network compressor integration.
In conjunction with a ‘speed monitoring kit’ (available separately) the VSD B Box will provide all required functionality to maximize the ENER, Energy Control Mode, in the X8I or X12I Automation System.
STANDARD CONTROL FEATURES AND FUNCTIONALITY
The IR Bolt-On VSD must be equipped with a 4-20mA pressure sensor that is used for variable speed drive regulation or compressor pressure regulation control. A VSD B Box will accommodate a pressure sensor range of
14.5 psi (1.0bar) to 8702 psi (600bar). A VSD-B box also requires the use of an “IR485 Gateway” compressor device.
Compressor Configurations and Characteristics That Can Be Accommodated by the VSD B Box:
Ingersoll Rand air compressors with a Bolt-On VSD that are equipped with two pressure sensors that both monitor package discharge (delivery) pressure. One sensor is dedicated to Intellisys compressor controller for basic regulation functions; the other is dedicated to variable speed drive unit regulation. The VSD B Box is able to accommodate this requirement without affecting compressor control system functionality.
5
VSD B BOX OPERATION
All air compressors are equipped with a method of sensing pressure. An air compressor regulates using the compressor package delivery pressure as the control variable.
4-20mA
IR air compressors equipped with a Bolt-On VSD use two independent pressure sensors. The first provides the normal fixed speed compressor Intellisys Controller with pressure information for load/unload regulation and safety features. The second provides the VSD with pressure information for main motor variable speed regulation.
The VSD-B Box monitors the VSD pressure sensor as an input and simulates the pressure sensor signal as an output. The VSD-B Box uses this method to modify the pressure signal and manipulate the speed behavior of the VSD. The VSD-B Box becomes the Bolt-On VSD pressure sensor.
This functionality enables the management system to utilize the compressor in a coherent manner and optimize total system efficiency and maintain air quality.
VSD B Box Operation Example:
If the Automation System unit is detecting a network air pressure (PN) of 100psi (6.9bar), and the system target pressure requirement (P) is 103psi (7.1bar), the VSD B Box will immediately calculate that a pressure rise of 3psi (0.2bar) is required to achieve and maintain system target pressure (P). Due to pressure differential across a local compressed air treatment system (PD) the compressor is currently operating at 107psi (7.4bar). The VSD B Box will manipulate the compressor pressure signal (PS) to cause the compressor to increase discharge (delivery) pressure (PC) to 110psi (7.6bar). This action will increase system pressure to the required target pressure. The VSD B Box will continuously re­calculate and manipulate the compressor pressure signal (PS) to accommodate changes in demand and compensate for any local or compressed air network pressure differentials.
PC
PS
VSD
PD
P
PN
VSD Box
4-20mA
The VSD-B Box also monitors compressor status, as it is reported to the management system (Ready, Run, and Load/Unload), by the IR485 Gateway device. This function enables the VSD-B Box to simulate all features of a standard X8I or X12I network compressor integration.
Actual System pressure and Automation System ‘target’ pressure information is routinely transmitted from the X8I or X12I to the VSD-B Box. The VSD-B Box uses this information to calculate the difference between the compressor delivery pressure and the system ‘target’ pressure. The VSD B Box utilizes pressure signal manipulation to continuously re-align compressor output with system requirements.
This functionality also enables the VSD B Box to continuously compensate for any pressure differential that may occur across local air treatment, along air pipe work or between different locations in a compressed air network.
6
SECTION 4 — INSTALLATION
It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.
Information regarding the compressor control system, method of operation and regulation settings, is required. Knowledge of VSD compressor regulation methods, experience working with compressor control systems and basic principle knowledge of compressed air systems, is also required to be able to successfully install and commission this product.
Dependent on compressor type and installation environment additional fixings, wiring, cabling, terminations and terminals will be required for installation.
UNIT LOCATION
The VSD B Box is wall or panel mounting using conventional screw fixings. The maximum distance between the X8I or X12I and the VSD B Box is 4000ft (1219 meters) of cable length. The VSD B Box must be located adjacent to the compressor unit within 330ft (100m) of cable length from the VSD.
POWER SUPPLY
A fused switching isolator must be installed to the main incoming power supply, external to the VSD B Box. The isolator must be fitted with a properly sized fuse to provide adequate protection to the power supply cable used (in accordance with local electrical and safety regulations).
1 2 34
L
N
N L
XPM-TAC24
EE
X01
E
Power Supply Terminals
Ensure that the voltage select input is properly jumpered for the incoming power. Default voltage configuration is 230Vac.
X04
X04
1
3 4
2
VOLTAGE SELECT
1
3 4
2
VOLTAGE SELECT
230Vac
115Vac
The cable used between the X8I or X12I and the VSD B Box is Belden 9841 (or equivalent). It should be run in grounded conduit and should not be greater than 4000 feet (1219 meters) in length.
RS485 and Signal Cable Routing
RS485 data communications and other low voltage signals can be subject to electrical interference. This potential can result in intermittent malfunction or anomaly that is difficult to diagnose. To avoid this possibility always use ground (earth) shielded cables, securely bonded to a known good ground (earth) at one end. In addition, give careful consideration to cable routing during installation.
a) Never route an RS485 data communications or low voltage signal cable alongside a high voltage or 3-phase power supply cable. If it is necessary to cross the path of a power supply cable(s), always cross at a right angle.
b) If it is necessary to follow the route of power supply cables for a short distance (for example: from a compressor X8I to a wall along a suspended cable tray) attach the RS485 or signal cable on the outside of an grounded (earthed) cable tray such that the cable tray forms an grounded (earthed) electrical interference shield.
c) Where possible, never route an RS485 or signal cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications antenna).
RS485 NETWORK
The VSD B Box is equipped with an RS485 network communications capability using the ir485 protocol. The VSD B Box is intended to operate as part of the X8I or X12I Automation System. Connection to the system management unit is two-wire, twisted pair, ground (earth) shielded, RS485 data link. Connect the RS485 data cable wires to terminal X07 located on the VSD B Box controller.
L2
L1
Note: Polarity is important.
X07
L2 L1
7
VSD B BOX HARDWARE CONFIGURATION
VSD B Box Terminal PCB Type Selector
VSD B Box Terminal PCB has a jumper on it that determines the type of control box the PCB is being used in. Check to determine if jumper (J1), as shown below, is placed in the correct position for a VSD B Box.
VSD/EX
J1
X01
1
246
X02
7
53
X03
119
8 10 12 1416 182022 24 26282930
XPM-Ao2 Module 4-20mA Output Mode Selectors
Remove the top cover of the XPM-Ao2 module and check the 4-20mA output mode selectors are in the ‘PASSIVE’ mode position. (The default position as shipped from the factory.)
KC-
18 17 16 15 14 13 12
KC-
X04
19171513
21
28
27 26 25 24 23 22 21
10
98765
11
23
X07X06X05
2725
43
X09
X08
31 32 33 34
20 19
21
R05
R06
21
3213
1
n
2
L
e
L e
r
c
s
C
X01
D V
4
2
+
RS485
X04X05
V
0
1 D E L
21
-
+
3
3
A
A
N
N
A
A
X02
#1
4-20mA(1)
VDC
1 A N A
-
21
+
2 A N A
1 A N A
+
4-20mA(2)
-
2 A
X03X06
N A
Ao2
#2
X06 X03
4-20mA(2)
C010
PASSIVE MODE
C03
4-20mA(1)
X02
8
VSD B BOX AND X8I OR X12I CONNECTIVITY
Consult the X8I OR X12I Interconnect and Application Guide prior to the installation of the VSD B Box to the pressure sensor on the VSD and the compressor.
Pressure sensor connectivity is dependent on compressor and control system type.
1
Gateway
1
2
IR485
RS485
VSD-B Box
Belden 9841
Or Equivilant
2 + Ground (Earth) 115/230Vac, 5A
2
PRESSURE SENSOR CONNECTIONS
Pressure sensor connectivity is dependent on compressor and control system type.
1) Disconnect the VSD pressure sensor wires from the VSD and connect to the VSD-B Box terminals as indicated on the following connection diagrams.
2) Connect the VSD-B output pressure signal terminals to the VSD pressure sensor terminals as indicated on the following connection diagrams.
Pressure signal output terminals are located on the XPM­Ao2 module within the VSD-B Box. These terminals are not located on the main terminal PCB of the VSD-B Box
21
3213
1
n
2
L
e
L e
r
c
s
C
X01
D V
4
2
+
RS485
X04X05
V
0
1 D E L
21
-
+
3
3
A
A
N
N
A
A
#1
4-20mA(1)
VDC
X02
1 A N A
-
21
+
2 A N A
1 A N A
+
4-20mA(2)
-
2 A
X03X06
N A
Ao2
#2
Consult the X8I Interconnect and Application Guide
prior to the installation of the VSD B Box to the pressure sensor on the VSD and the compressor.
Pressure sensor connectivity is dependent on compressor and control system type.
Electrical Interference
Failure to protect low voltage pressure signals between the compressor and VSD-B Box will result in unstable and/or erratic pressure readings; resulting in unstable and/or erratic compressor regulation behaviour.
4 to 20mA Pressure Sensors
Always use shielded, 18 gauge, 2-conductor
cable no more than 330 feet (100 meters) in length. Ensure the shield wire is securely connected to earth ground at the VSD B Box end only.
9
IR-5000 DISCHARGE (DELIVERY) PRESSURE SENSOR INTERCONNECT
1
1
A
A
N
N
A
A
-
+
10
IR-302 DISCHARGE (DELIVERY) PRESSURE SENSOR INTERCONNECT
1
1
A
A
N
N
A
A
-
+
11
IR485 GATEWAY CONNECTION
The VSD-B Box requires the use of an IR485 Compressor Gateway.
The IR485 Gateway must be connected to the same RS485 management system network as the VSD-B Box and management system unit. There is no requirement to connect directly from the VSD-B Box to the IR485 Gateway. Both devices are autonomous and can be regarded as individual components of the common X8I or X12I Automation System network.
The IR485 Gateway must be set for the same
network address as the VSD-B Box; this will not cause a network conflict in this instance.
The cable used between the X8I or X12I and the IR485 Gateway is Belden 9841 (or equivalent). It should be run in grounded conduit and should not be greater than 4000 feet (1219 meters) in length.
Consult the IR485 & IRV485 Gateway Instruction Manual prior to the installation of the VSD B Box and the IR485 Gateway to the VSD and the compressor.
SPEED MONITORING INPUT (OPTION)
The VSD-B Box is equipped with a ‘speed detection’ input designed to function with an optional ‘VSD Speed Monitoring Kit’ (available separately). This optional feature will provide all required functionality to enable total synergy with the energy control, VSD compressor aware, functions of an X8I or X12I.
X05
2
2 1
2 0
2 9
1 8
1 7
1
rpm
+
REMOTE OUTPUTS
Compressor Running: The VSD-B Box is equipped with a volt-free relay contact
output (R5) to indicate when the compressor is detected as running. The output contacts will close when the compressor is running.
Group Alarm: The VSD-B Box is equipped with a volt-free relay contact
output (R6) to indicate Group Alarm. The Group Alarm relay contacts are normally closed and will open in the following conditions:-
1) VSD-B Box power failure
2) VSD-B Box internal fault condition
3) Input pressure sensor fault
4) Compressor ‘Not Ready’
X09
4
R6
R5
Relay contact rating: CE: 250V @ 5A max UL: 115V @ 5A max
3 3
3 2
3 1
3
X08
Group Alarm
Compressor Running
12
SECTION 5 — DISPLAY AND MENU OPERATION
OPERATION
User Interface
a
b
c
g
f
h
a) START Button
b) RESET Button
c) STOP Button
d) MENU Button
e) ENTER Button
f) CANCEL Button
g) UP, Plus Button
h) DOWN, Minus Button Display
The primary display value (A) will continuously show the detected ‘Delivery’ pressure. The pressure is derived from the compressor ‘Delivery’ pressure sensor and the displayed value is not manipulated or adjusted.
The compressor controller ‘Pressure Display’ may not represent the actual true local pressure(s) when VSD B Box ‘Pressure Control’ is active. Use the VSD B Box ‘Input’ pressure display(s) for local pressure reference.
The ‘User Menu’ item display (B) will show the selected user menu item. Press UP or DOWN to scroll through the display ‘items’ list.
d
e
psi
Status Symbols
The Status display (C) will continuously show the current state of the VSD B Box by using the following icons.
Power Failure Auto Restart (always on) Communicating with System Management Unit
Flashing - No Communications System
Management Unit
Compressor Running
Compressor Loaded
Compressor Not Ready Fault, Auxiliary Input Alarm/Trip
Pressure Control Active
Indicators
Run Indicator (Green LED)
OFF – Compressor stopped or not available.
Flashing - Compressor running
ON – Compressor loaded.
Fault Indicator (Red LED) OFF – No fault
Flashing – VSD B Box Fault Condition
(see Fault Codes) The VSD B Box will report that the compressor is ‘Not
Available’ to the system management unit when the VSD B Box is in a stopped or fault condition.
Start
The START button has no function. All compressor status data is derived from data received on the RS485 port.
The compressor must be in a started state (running or in standby) before VSD B Box pressure control will function.
When the compressor is running loaded, the VSD-B Box will begin to manipulate the pressure signal to the frequency inverter.
‘Pressure Control’ is active
Pressure Control will de-activate automatically if communications with the system management unit is disrupted or not connected; the detected pressure from the pressure sensor(s) is re­transmitted to the compressor control directly.
When communications are re-established the VSD B Box will automatically re-activate ‘Pressure Control’.
13
Stop
The STOP button has no function. When the compressor is stopped, unloaded or unavailable to the X8I or X12I, the VSD-B Box will not manipulate or adjust the pressure signal to the VSD; the detected pressure from the pressure sensor is re-transmitted to the VSD directly.
Compressor Status
The detected status of the compressor is indicated by the VSD B Box display status symbols (see Status Symbols)
VSD B Box Status
VSD B Box operation is indicated by the ‘Run’ LED indicator (see Indicators). Pressure Control status is indicated by the ‘pressure’ status symbols (see Status Symbols).
User Menu Items
To view the ‘User Menu Items’, press UP or DOWN. The ‘Item’ display value will scroll through the available items.
P1 ‘Delivery’ output pressure transmitted to the
compressor controller.
SP* Percent motor speed C> VSD B Box Status
(*) The percentage motor speed item is only shown if a ‘Speed Monitoring Kit’ is fitted and the function is activated (Menu P08).
Delivery Output Pressure:
The delivery output pressure is manipulated during ‘Pressure Control’ and will differ from the actual ‘Input Delivery’ pressure displayed as the main display value. Pressure control function can be observed by comparing the ‘Output’ discharge (delivery) pressure with the actual detected ‘Input’ discharge (delivery) pressure. The two pressures will be identical when ‘Pressure Control’ is not active.
Percentage Motor Speed:
The percentage of detected motor speed compared to maximum motor speed. This value provides a direct indication of variable speed compressor output regulation.
VSD B Box Status:
Power Failure Auto-Restart
Power failure auto restart is always active and cannot be de-activated.
The VSD B Box will re-start if the VSD B Box was in an operational started status before the break or failure of the main power supply occurred.
The VSD B Box will not re-start if it was not in an operational started status before the break or failure of the main power supply occurred.
For Example: Network Address = 1 (Compressor 1)
States = 5 (Ready)
The central ‘item’ display value (B) is the compressor system identification number (network address number). This is the same as the compressor system identification number shown on the system management unit.
The ‘right hand’ display value indicates the VSD B Box status condition (see Status Block Diagram).
4: Not Ready, Stopped, Not Available 5: Ready, motor not running 7: Running Offload 9: Running Onload; Pressure Control Active.
14
SECTION 6 — COMMISSIONING
COMMISSIONING PROCEDURE
It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.
Information regarding the compressor control system, method of operation and regulation settings, is required. Knowledge of VSD compressor regulation methods, experience working with compressor control systems and basic principle knowledge of compressed air systems, is also required to be able to successfully install and commission this product.
PHYSICAL CHECKS
Before applying power to the VSD B Box ensure that the power supply connections are correct and secure and that the operating voltage selector is set correctly for the power supply voltage in use; 115Vac or 230Vac (+-10%), 50/60Hz; see ‘Installation’.
Check and ensure all pressure sensor, output pressure signal and ir-PCB connections are correctly installed and secure.
SELECTING VSD-B MODE:
IMPORTANT
If equipped with software version S1IRVSDC (E01 or higher) the VSD mA box hardware can support two different operating modes:
a) Standard “VSD-mA” mode (default) b) VSD-B mode
The VSD B Box will be delivered in VSD mA mode as default, it is important to select VSD-B mode prior to any other configuration adjustments.
For standard VSD mA mode see VSD mA Box Operators Manual
TO CHANGE MODE:
1) Enter access code “1215” and navigate to menu ‘PCt’.
2) Select “tYPE-b” from the ‘Ct’ menu item and enter.
To change back to standard VSD mA mode set ‘Ct’ to “tYPE-mA”.
When using the “1215” access code only the ‘PCt’ menu is visible and accessible.
The ‘PCt’ menu is not visible, or accessible, when using normal access code types.
VSD-B software ‘S1IRVSDC’ will not function with a
VSD Voltage Box.
COMPRESSOR PRESSURE SET POINTS
Establish the following pressure set point values from the compressor control system.
Establishing the correct compressor pressure set point values is critical to successful VSD B Box operation.
1) Compressor ‘Target’ pressure set point.
For VSD type compressors this is the pressure that the variable speed drive is set to maintain.
For fixed speed compressors with the IR Bolt-On VSD, the ‘target’ pressure can be set at the mid-point between the Intellisys controller ‘load’ and ‘unload’ pressure set points.
With the Bolt-ON VSD, the ‘target’ pressure is set separately from the compressor controller (in the variable speed drive controller menu or using a potentiometer connected to the variable speed drive controller). In this instance, the ‘target’ pressure may have to be determined by observation and/or experiment.
COMPRESSOR
Pressure Set Points
Excess or Alarm Pressure
7psi (0.5bar) min
Unload Pressure
Pressure
Target Pressure
Load Pressure
If the compressor pressure set points have been set with small differentials then the pressure set points of the compressor will require adjustment before proceeding.
It is recommended that the pressure differential between the ‘load’ and ‘unload’ (or ‘target’ and ‘controlled stop’) pressures is a minimum of 7psi (0.5bar).
It is recommended that the pressure differential between the ‘unload’ and ‘excess’ (or ‘controlled stop’ and ‘immediate stop’) pressures is a minimum of 7psi (0.5bar).
7psi (0.5bar) min
15
VSD B BOX CONFIGURATION
If the VSD-B Box automatically starts (the green started indicator illuminates or flashes) stop the compressor. The VSD-B is then ready for configuration and pressure input and output calibration.
VSD B Box Network Address
Each VSD compressor connected to the Automation System unit must be assigned a unique compressor identification number (1 to the maximum number of compressors support by the X-Series controller). This number will be the ‘network address’ number for the compressor. The number should be clearly marked on the compressor for identification purposes.
When connecting a compressor(s) to the VSD B Box, always use the Automation System unit’s unique identification number as the compressor ‘network address’ number.
Using the VSD B Box menu routines, set the ‘Ad’ (Network Address) in menu P03 to the Automation System unit’s compressor identification number.
The VSD-B and the associating IR485 Gateway must be set to the same system network address (compressor number).
Input Pressure Sensor(s)
The offset and range of the pressure sensor(s) used on the compressor must be established for VSD B Box pressure sensor calibration. Generally this information is indicated on the pressure sensor label.
The majority of pressure sensor(s) have a minimum pressure (offset) of 0(zero) bar gauge with a ‘range’ applicable to the application. For example 0 to 232 psi (0.0 to 16.0 bar) - where 0(zero) psi (0.0(zero) bar) is the ‘offset’ minimum and 232 psi (16.0 bar) is the ‘range’ or maximum.
Some pressure sensor(s) have non-zero offset. For example -14.5 psi (minus -14.5), (-1.0 bar) (minus 1bar) to 218 psi, 15bar; this type of pressure sensor can measure negative or vacuum pressure. In this instance the ‘offset’ is -14.5 psi (minus -14.5), (-1.0 bar) (minus 1bar)) and the ‘range’ is 232 psi (16.0 bar). Remember the ‘range’ is the difference between the minimum and maximum values and not the maximum value referenced to 0(zero) bar ‘atmospheric’.
The correct ‘offset’ and ‘range’ values of each pressure sensor are required for VSD B Box ‘input’ pressure sensor calibration.
The main value display should show a pressure value; for example 0 psi (0.0 bar).
If the display shows dashes (- - - -) check the ‘Delivery‘ pressure sensor connections.
At this stage the displayed pressure values will probably be incorrect; this is normal.
Calibrate the input ‘Delivery’ pressure sensor, and input ‘Internal’ pressure sensor if used, following the input ‘Pressure Sensor Calibration’ procedure below:
Input and Output pressure calibration is critical for
successful VSD B Box operation.
Input Pressure Sensor Calibration
Using the VSD B Box menu navigation procedure, select menu page P04 (Input Pressure Calibration). The ‘items’ of this menu enable calibration of the pressure sensor(s) connected to the VSD B Box.
Enter the ‘OFFSET’ value for the ‘Delivery’ pressure sensor in the ‘Do’ menu item.
For example: if the VSD pressure sensor is 0 tom 200 psi (0 to 13.79 bar), enter 0 psi (0.0 bar) as the offset value.
Enter the ‘RANGE’ value for the ‘Delivery’ pressure sensor in the ‘Dr’ menu item.
For example: if the VSD pressure sensor is 0 tom 200 psi ( 0 to 13.79 bar) enter 200 psi (13.79 bar) as the range value.
When the ‘Delivery’ pressure sensor offset and range menu items are selected the menu page display value will change to show the actual detected ‘Delivery’ pressure measurement. This value can be used to compare with a ‘known’ pressure applied to the ‘Delivery’ pressure sensor for accurate calibration purposes. An independent and accurate means of measuring the applied pressure is required.
1) Subject the ‘Delivery’ pressure sensor to atmosphere (0bar).
2) Adjust the ‘Do’ pressure ‘offset’ value until the ‘Delivery’ pressure displayed by the VSD B Box sho ws 0(zero) bar.
3) Apply a known pressure to the ‘Delivery’ pressure sensor. It is recommended that the applied pressure is representative of normal working pressure levels. It is not important if the applied pressure is static or continuously fluctuating.
4) Adjust the ‘Dr’ pressure ‘range’ value until the ‘Delivery’ pressure displayed by the VSD B Box sho ws the same as the ‘known’ applied pressure.
Wire polarity is important.
16
Output Pressure Signal Calibration
Using the VSD B Box menu navigation procedure, select menu page P05 (Output Pressure Calibration). The ‘items’ of this menu enable calibration of the pressure signal(s) transmitted to the compressor controller.
Enter the ‘OFFSET’ value for the ‘Delivery’ pressure signal in the ‘Do’ menu item. Set this value will to same as the initial ‘Delivery’ pressure sensor input ‘offset’.
Enter the ‘RANGE’ value for the ‘Delivery’ pressure signal in the ‘Dr’ menu item. Set this value to the same as the initial ‘Delivery’ pressure sensor input ‘range’.
When the output ‘Delivery’ pressure signal offset and range menu items are selected the menu page display value will change to show the actual detected input ‘Delivery’ pressure measurement. This value represents the pressure the VSD B Box is attempting to transmit to the compressor controller and can be used to compare with the compressor controller’s displayed pressure value.
1) Subject the input ‘Delivery’ pressure sensor to atmosphere (0bar).
2) Adjust the ‘Do’ pressure signal ‘offset’ value until the compressor controller’s discharge (delivery) pressure display value shows 0(zero) bar.
3) Apply a known pressure to the input ‘Delivery’ pressure sensor. It is recommended that the applied pressure is representative of normal working pressure levels. It is not important if the applied pressure is static or continuously fluctuating.
4) Adjust the ‘Dr’ pressure signal ‘range’ value until the compressor controller’s discharge (delivery) pressure display value shows the same as the VSD B Box discharge (delivery) pressure.
TARGET PRESSURE SET POINT
Establishing and implementing the correct target pressure set point is critical for successful VSD-B Box operation.
Using VSD-B Box menu navigation, select menu page P01 (Target Pressure Set Point).
Set the ‘Pt’ (Target) pressure set point to exactly match the ‘target’ pressure setting established for the compressor’s VSD.
It is recommended that Input and Output pressure calibration is examined, and adjusted if necessary, on a routine periodic basis.
17
SECTION 7 — SYSTEM CONFIGURATION
DISPLAY ITEM STRUCTURE
All value, parameter or option selection displays are grouped into menu lists. Items are assigned to a list according to type and classification. Items that can be used to select options or modify functions are assigned to ‘menu mode’ lists. Items that a User may require to view during routine operation, detected pressure for example, are assigned to the normal operational mode list. Lists are identified by page number; the normal User display list is page ‘P00’. All parameters and options are assigned to menu mode pages ‘P01’ or higher. All Page ‘P00’ items are view only and cannot be adjusted.
Normal Operational Mode (Page P00)
At controller initialization, all display elements and LED indicators are switched on for three seconds, the display will then show the software version code for a further 3 seconds before initialization is complete and the normal operating display (Page P0) is shown. In page P00 ‘normal operational display mode’ the main display will continuously show the detected discharge (delivery) pressure and the Item display will show the first item of the ‘User’ menu. User menu ‘Items’ can be selected using the Up or Down buttons at any time. Pressing the Enter button will lock any selected Item display and inhibit return to the default display. When an Item display is locked the lock key symbol will slow flash. To unlock an Item display press Up or Down to view an alternative Item display or press Reset or Escape. No Item values, options or parameters can be adjusted in page ‘P00’. If a fault condition occurs the fault code becomes the first list item and the display will automatically jump to display the fault code. More than one active fault code item can exist at any one time.
ACCESSING THE VSD B BOX CONFIGURATION SCREENS
Access Code
Access to page list displays higher than page ‘P00’ is restricted by access code. To access menu mode pages press UP and DOWN together, an access code entry display is shown and the first code character will flash. Use PLUS or MINUS to adjust the value of the first code character then press ENTER. The next code character will flash; use UP or DOWN to adjust then press ENTER. Repeat for all four code characters.
If the code number is less than 1000 then the first code character will be 0(zero). To return to a previous code character press ESCAPE. When all four code characters have been set to an authorized code number press ENTER. An invalid code will return the display to normal operational mode; page ‘P00’.
Access Code Timeout
When in menu mode, if no key activity is detected for a period of time the display will automatically reset to the normal operational display; Page ‘P00’.
Menu Mode Navigation
In menu mode the main value display will flash and show the Page number. To select a page press UP or DOWN. For each page the display will show the first Item of the page list. To view a page list press ENTER, the Page number will stop flashing and the Item display will flash. Press UP or DOWN to view the selected page list items. To select an Item value for modification press ENTER, the Item display will stop flashing and the Value display will flash. The value or option can now be modified by pressing UP(Plus) or DOWN(Minus). To enter a modified value or option in memory press ENTER; alternatively the modification can be abandoned, and the original setting maintained, by pressing ESCAPE.
Page 0
Item 1 Value Item 2 Value Item 3 Value Item 4 Value Item 5 Value Item 6 Value
Page 1
Page 2
Page 3
Page 4
Page 5
Item 1 Value Item 2 Value Item 3 Value
Item 4 Value
Item 5 Value
18
Press ESCAPE at any time in menu mode to step backwards one stage in the navigation process. Pressing ESCAPE when the page number is flashing will exit menu mode and return the display to normal operational mode; page ‘P00’.
Page 0
to immediately exit menu mode and return to the normal operational mode display. Any value or option adjustment that has not been confirmed and entered into memory will be abandoned and the original setting maintained.
indicates the Item is locked and cannot be modified. This will occur if the Item is view only (non adjustable) or in instances where the item cannot be adjusted while the VSD B Box is in the operational STARTED state.
Item 1 Value
Item 2 Value Item 3 Value Item 4 Value Item 5 Value Item 6 Value
Press and hold RESET for two seconds at any time
A flashing Key symbol displayed with any Item
Page 1 Page 2
Page 3 Page 4 Page 5
Item 1 Value Item 2 Value Item 3 Value Item 4 Value Item 5 Value
19
MENU ITEMS AND SETTINGS
MENU P00 - User 1 P1 Discharge Pressure - Output (view only) 2 SP Percent Speed (view only)
MENU P01 - Pressure Set Points 1 Pt Target Pressure
MENU P02 – Error Log 1 Hr VSD B Box Operating Hours 2 01 Error Log #1
to
16 15 Error Log #15
MENU P03 - Configuration 1 P> Pressure Units Select 2 Ad Network Address (Compressor No.) 3 PA Pressure Averaging Factor
MENU P04 – Input Pressure Calibration 1 Do Discharge Pressure ‘Offset’ 2 Dr Discharge Pressure ‘Rang e’
MENU P05 – Output Pressure Calibration 1 Do Discharge Pressure ‘Offset’ 2 Dr Discharge Pressure ‘Rang e’
MENU P06 / Diagnostics
See ‘Diagnostics’
MENU P08 – Speed Monitoring 1 FL Frequency at Minimum Speed 2 FH Frequency at Maximum Speed 3 C> Control Percentage (view only)
MENU P10 – Unit Configuration 1 Er Error Log Reset 2 Hr VSD B Box Operating Hours Adjust
MENU P16 – Analog Output Diagnostic
See ‘Diagnostics’
Note: Menus P07, 9 and 11 to 15 are not used.
Access Code = 0021
MENU P01 - Pressure Set Points
Pt: Target Pressure
Compressor ‘Target’ pressure set point. For VSD type compressors this is the pressure that the variable speed drive is set to maintain. Set the ‘Pt’ (Target) pressure set point to the ‘target’ pressure setting established for the compressor.
Establishing and maintaining the correct pressure set point values ( Pt ) is critical to the successful operation of VSD B Box control functions. See ‘Commissioning - Pressure Set Points’
MENU P02 - Error Log
The first item of the log error menu is the VSD B Box operational hours (Hr). This is an indication of the accumulated hours the VSD B Box has been operational and is used to time-stamp fault codes in the error log. The hours counter has no other function.
The VSD B Box operating hours counter is NOT intended as a measure of compressor operation or running hours; the hours counter will differ from, and operate independently from, the compressor hours counter.
Each error log item will show the fault code alternating with the VSD B Box operational hours when the fault occurred. The error log stores the last 15 faults in chronological order; item ‘01’ is the most recent fault.
MENU P03 – Configuration P>: Pressure Units Select
Selects the display pressure units (bar, psi or kPa)
Ad: Net work Address
Network address; must be set to the compressor identification number used by the Automation System unit for the compressor (1 to the maximum number of compressors). Each compressor in a system must have a unique identification number.
PA: Pressure Averaging Factor
Pressure corrections supplied by the Automation System unit are averaged to prevent abrupt changes and enable smooth and controlled pressure adjustments. The Automation System updates pressure information approximately every two seconds. The ‘Pressure Averaging Factor’ is the number of previous pressure corrections that are used for averaging. For example: a factor of ‘2’ will average the most recent pressure correction value received with the previous two values received.
If system volume is large and/or pressure variations are slow a higher ‘Pressure Averaging Factor’ can be used to dampen response and smooth control pressure changes. If system volume is small and/or pressure variations are fast a lower ‘Pressure Averaging Factor’ should be used to enable a faster response. In some instances pressure differential across air treatment and/or small diameter pipe work can result in sudden and abrupt changes in detected pressure.
A higher ‘Pressure Averaging Factor’ can be used to dampen this effect.
20
MENU P04 – Input Pressure Calibration Do: Discharge Pressure Offset
This parameter will be the minimum value of the pressure transducer, 0 PSI, 0 BAR, or 0 kPA. It can also be used to create an ‘Offset’ if there is a difference in the zero value being displayed. The default setting for this parameter is 0 PSI. The values for this parameter are:
“0” when using the minimum value of the pressure transducer range
A value greater than or less than 0 if the display does not read 0 or when using an Offset pressure transducer (an example of an Offset pressure transducer would be one where the range was minus PSI (-25) to a positive PSI (200).
The pressure transducer must be vented to atmosphere when setting the 0 or offset.
Dr: Discharge Pressure Range
This parameter will be the maximum range of the pressure transducer, 232 PSI, 16 BAR, or 1600 kPA. It can also be used to create an ‘Offset’ if there is a difference in the range value being displayed. The default setting for this parameter is 232 PSI. The values for this parameter are:
“232” when using the maximum value of the pressure transducer range
A value greater than or less than 232 if the display does not read 232.
The pressure transducer must have a known, accurate pressure applied to it when changing this value to a value other than 232.
Calibration Checks
When the ‘Discharge’ pressure sensor offset and range menu items are selected the menu page display value will change to show the actual detected ‘Discharge’ pressure measurement. This value can be used to compare with a ‘known’ pressure applied to the ‘Discharge’ pressure sensor for accurate calibration purposes. An independent and accurate means of measuring the applied pressure is required.
1) Subject the ‘Discharge’ pressure sensor to atmosphere 0psi (0bar).
2) Adjust the ‘Do’ pressure ‘offset’ value until the ‘Discharge’ pressure displayed by the VSD B Box shows 0psi ((0) bar.
3) Apply a known pressure to the ‘Discharge’ pressure sensor. It is recommended that the applied pressure is representative of normal working pressure levels. It is not important if the applied pressure is static or continuously fluctuating.
4) Adjust the ‘Dr’ pressure ‘range’ value until the ‘Discharge’ pressure displayed by the VSD B Box shows the same as the ‘known’ applied pressure.
The detected pressure is displayed with the calibration menu item and will change to match the new calibration setting as the setting is adjusted.
There is no need for the applied pressure to be static; it can be dynamic and changing. This enables calibration to be carried out on a fully operational system where changing system pressure can be accurately verified from another source.
Correct pressure sensor set-up and calibration is critical for successful system operation. It is recommended that pressure sensor calibration is examined, and adjusted if necessary, annually or a pre­determined routine periodic basis.
Input and Output pressure calibration is critical to the successful operation of VSD B Box functions and must be examined, and adjusted if necessary, periodically on a routine basis.
MENU P05 – Output Pressure Calibration Do: Discharge Pressure Offset
Enter the ‘OFFSET’ value for the ‘Discharge’ pressure signal in the ‘Do’ menu item. Set this value will to same as the initial ‘Discharge’ pressure sensor input ‘offset’.
Dr: Discharge Pressure Range
Enter the ‘RANGE’ value for the ‘Discharge’ pressure signal in the ‘Dr’ menu item. Set this value to the same as the initial ‘Discharge’ pressure sensor input ‘range’.
Calibration Checks
When the output ‘Discharge’ pressure signal offset and range menu items are selected the menu page display value will change to show the actual detected input ‘Discharge’ pressure measurement. This value represents the pressure the VSD B Box is attempting to transmit to the compressor controller and can be used to compare with the compressor controller’s displayed pressure value.
1) Subject the input ‘Discharge’ pressure sensor to atmosphere 0psi (0bar).
2) Adjust the ‘Do’ pressure signal ‘offset’ value until the compressor controller’s discharge pressure display value shows 0psi (0) bar.
3) Apply a known pressure to the input ‘Discharge’ pressure sensor. It is recommended that the applied pressure is representative of normal working pressure levels. It is not important if the applied pressure is static or continuously fluctuating.
4) Adjust the ‘Dr’ pressure signal ‘range’ value until the compressor controller’s discharge pressure display value shows the same as the VSD B Box discharge pressure.
Input and Output pressure calibration is critical to the successful operation of VSD B Box functions and must be examined, and adjusted if necessary, periodically on a routine basis.
21
FL: Frequency at Minimum Speed
set to 0(zero) if speed detection is not in use.
Intended for VSD type compressors.
The VSD output frequency at the compressor’s minimum operating speed.
When this menu item is selected the menu page number display will change to show the actual detected frequency. By restricting the output air from the compressor the compressor VSD can be forced to minimum speed. Set the value to the lowest frequency detected.
The frequency setting must represent the lowest VSD output frequency that will occur in normal operation.
FH: Frequency at Maximum Speed
Used for optional ‘Speed Monitoring Kit’ if fitted. Must be set to 0(zero) if speed detection is not in use. Intended for VSD type compressors.
The VSD output frequency at the compressor’s maximum operating speed. When this menu item is selected the menu page number display will change to show the actual detected frequency. By creating a demand for air the compressor VSD can be forced to maximum speed. Set the value to the highest frequency detected.
The frequency setting must represent the maximum (100%) VSD output frequency that will occur in normal operation.
C>: Control Percentage
This menu item value is view only and cannot be adjusted. The value represents the variation in VSD output frequency; where 0% is minimum speed and 100% is maximum speed.
Note: The ‘Control Percentage’ value represents the percentage of speed variation from minimum speed to maximum speed and differs from the ‘User’ menu percent motor speed value. This value is used internally by the VSD B Box for Automation System unit functions and is only active when an optional ‘Speed Monitoring Kit’ is installed.
Er: Error Log Reset MENU P08 – Speed Monitoring
Adjust to ‘RST’ and press ENTER to clear and reset the ‘Error Log’ menu. Used for optional ‘Speed Monitoring Kit’ if fitted. Must be
Hr: VSD B Box Operating Hours Adjust
Allows adjustment of the VSD B Box operating hours counter. The accumulated hours counter is used for ‘Error Log’ time-stamp only and has no other function.
22
SECTION 8 — DIAGNOSTICS
The VSD B Box controller is equipped with comprehensive diagnostic functions. Each input can be examined individually and each output can be manually activated or manipulated individually.
MENU P06 / Diagnostics
Controller Diagnostics:
MENU P06 / Diagnostics D1 Digital Input 1 D2 Digital Input 2 D3 Digital Input 3 D4 Digital Input 4 D5 Digital Input 5 D6 Digital Input 6 D7 Digital Input 7 D8 Digital Input 8
-------------------------------------------------------------
R1 Relay Output 1 R2 Relay Output 2
OFF
R3 Relay Output 3 R4 Relay Output 4 R5 Relay Output 5
ON
R6 Relay Output 6
-------------------------------------------------------------
A1 Analog Input 1 psi (bar) <> mA A2 Analog Input 2 psi (bar) <> mA A3 Analog Input 3 psi (bar) <> +VDC
-------------------------------------------------------------
Ao Analog Output 4.0 to 20.0mA
Digital Inputs:
D4 is the only digital input that will detect a pulsing signal. (in case speed monitoring kit is installed and compressor is running).
The pulse signal is 24VDC at 50/60Hz. A DC voltage meter will detect this as 12VDC +-4V.
Relay Outputs:
Each relay output can be energized and de-energized manually by selecting the item. Use PLUS and MINUS to adjust and ENTER.
Analog Inputs:
The item will alternate between the detected value and the electrical measurement on the input terminals. An independent measuring device can be used to check the displayed electrical measurement.
A1: Delivery Pressure 4-20mA A2: Internal Pressure 4-20mA A3: Discharge (delivery) pressure 0.5-4.5VDC
Analog Output:
The output can be manually adjusted by selecting the item. Use PLUS and MINUS to adjust and ENTER. The output will return to normal operational value upon menu exit.
XPM-Ao2 Module Diagnostics:
MENU P16 / XPM-Ao2 Diagnostics A1 Analog Output 1 4-20mA #1 A2 Analog Output 2 4-20mA #2 A3 Analog Output 3 0.5-4.5VDC
Analog Outputs:
Each output can be manually adjusted by selecting the item. Use PLUS and MINUS to adjust and ENTER. The output will return to normal operational value upon menu exit.
A1: Discharge (delivery) pressure +VDC Output A2: Internal Pressure +VDC Output A3: Delivery Pressure 0.5-4.5VDC
SECTION 9 — FAULT CODES
If a VSD B Box fault, or auxiliary input fault, occurs the ‘Item’ display will show a fault code:
0115E 4-20mA Delivery P. Sensor Fault 0821E Short Circuit Condition Detected
Check all inputs and outputs. 0845E S1 Controller Communications with XPM-
Ao2 unit disrupted
Press RESET to reset the fault code display when the fault condition is resolved.
23
SECTION 10 — VSD B BOX STATUS BLOCK DIAGRAM
The VSD B Box User menu ‘Status’ display item (C>) continuously shows the network address and the VSD B Box status block number.
For Example: Network Address = 1 (Compressor 1) State Block = 3 (Ready To Start) The ‘status block number’ enables VSD B Box
operational status to be established from the status block diagram.
.
VSD B Box Status Block Diagram
VSD Box
VSD Box
Fault
Fault State
1
No Fault
PRESSURE CONTROL:
The compressor is running loaded and the VSD-B Box is regulating the frequency inverter pressure signal.
If communications with the management system are disrupted, or lost, the VSD-B Box will not manipulate the pressure signal. The detected pressure is transmitted directly to the frequency inverter.
If the appropriate compressor status signals are re­established the VSD-B Box will automatically reset the ‘not available’ condition and pressure control will resume. The management system unit will automatically reset and accept the compressor back into sequence.
Power On
2
Initialise
Initialisation Complete
NO RESPONSE
Ready
= False
No RUN
STOP
Ready
= False
Run
= False
Response
No LOAD
STOP
Response
STOP
STOP
Ready = True
Run Response Timeout
No Load
6
Request
Run = True
STOP
Ready
Load Response Timeout
AND
No Load
8
Request
Load = True
Run = True
STOP
Ready
To Start
Compressor
NOT READY
Ready
= False
Compressor
READY
Run
= False
Compressor
RUNNING
Load
= False
Compressor
LOADED
Start
OR
AutoStart
Ready = True
Ready = True
Run = True
Ready = True
Run = True
Load = True
3
4
PRESSURE
CONTROL
5
AND
7
Ready = False
AND
AND
9
Ready = False
STARTED
Run = False
24
SECTION 11 — PARTS LIST
VSD B Box
Item Part No. Description
- 23410780 VSD B Box Kit
- 23242225 VSD mA / B Box Unit
- 80444086 Manual, User CD
1 42659490 Controller, VSD mA / B 2 42659284 Unit, XPM-PSU24 3 23242282 Unit, XPM-Ao2 4 39265913 Unit, XPM-TAC24 5 23242993 PCB, Terminal VSD 6 38036703 Gland, Set - Pg13.5 7 39266085 KIT, ir485 Gateway
Optional Accessories:
Item Part No. Description 6 39265939 Sensor, Pressure
4-20mA, 0-16.0bar
20mm
IEC
5mm
Qty Part No. Description 10 39265962 IEC Fuse T1.0A
10 39265970 IEC Fuse T1.6A 10 39265988 IEC Fuse T3.15A
X
P
M
-
XPM-Ao2
XPM-PSU24
TA
3
4
C
2
4
5 2 1
6
7
IR485
SECTION 12 — TECHNICAL DATA
Dimensions 291mm x 241mm x 152mm
11.45” x 9.45” x 6.0” Weight 6.5kg (14Ib) Mounting wall, 4 x screw fixings Enclosure IP54, NEMA 12 Supply 230Vac +/- 10% 115Vac +/- 10% Power 50VA Temperature 0°C to 46°C (32°F to 115°F) Humidity 95% RH non-condensing
24mm
188mm
Mounting Dimensions:
24mm
8mm Ø
238mm
236mm
286mm
25
SECTION 13 — WIRING DIAGRAM
VSD B BOX SCHEMATIC
26
XPM-TAC24 SCHEMATIC
T3.15A
FH5
IEC
5x20mm
BLUE
T1.6A
BROWN
RED
FH4
X03
2 1 2
24Vac/2 earthed
GREEN
T1.6A
24Vac/1
isolated
BLACK
ORANGE
WHITE
VIOLET
1
2 3 4
X04
T1.0A
FH2FH3
1 2 3 4
X02
L
N
N L E
VOLTAGE SELECT
T1.0A
X01
EE
230V 115V
FH1
1 2 3 4
230V +-10%
115V +-10%
XPM-VO2 (+VDC ANALOG OUTPUT)
21
3213
1
n
2
L
e
L
e
r
X05
c
s
C
X01
D V 4 2 +
RS485
X04
V 0
21
1 D E
L
+
3 A N A
#1
4-20mA(1)
ACTIVE
C03
-
+
PASSIVE
X02
4-20mA(1)
21
VDC
-
3 A N A
+
2 A N A
4-20mA(2)
-
2 A
X03X06
N A
#2
Ao2
1
1
A
A
N
X02
N
A
A
-
+
X03
4-20mA(2)
-
+
ACTIVE
PASSIVE
C010
XPM-PSU24 (24VAC TO 24VDC)
32
1
c
c
a
a
V
V
X01
0
4
ACTIVE MODE
-
500R max
+
+24VDC
2
C D V 4 2
X02
X03
1
0VDC
+24VDC
2
X04
PASSIVE MODE
+
+- +- +-
2
1
XPM-Ao2
+
-
­+
1
+12-30VDC
500R
X05
C D V 0
1 D E
L
2
1
-
max
0VDC
PSU24
C
C
D
D
V
V
8
0
+
2
+-
D E
L
2
LED 1
LED 2
27
SECTION 14 — COMMISSIONING FORM
28
Loading...