Ingersoll Rand System Automation VSD B Box Operator’s Manual

Before installing or starting this unit for the first time, this manual should be studied carefully to obtain a working knowledge of the unit and/or the duties to be performed while operating and maintaining the unit.
RETAIN THIS MANUAL WITH UNIT. This Technical manual contains IMPORTANT SAFETY DATA and should be kept with the unit at all times.
More Than Air, Answers.
Online answers: http://www.air.irco.com
Ingersoll Rand
System Automation
VSD B Box
Operator’s Manual
C.C.N. : 80445505 REV. A DATE JANUARY 2009
TABLE OF CONTENTS
TABLE OF CONTENTS ................................................. 2
SECTION 1 – INTRODUCTION ..................................... 3
SECTION 2 — SAFETY ................................................ 3
SAFETY PRECAUTIONS...............................................3
INSTALLATION.............................................................3
OPERATION.................................................................3
MAINTENANCE AND REPAIR.......................................4
SECTION 3 — COMPRESSOR CONNECTION AND
CONTROL ...................................................................... 5
STANDARD CONTROL FEATURES AND
FUNCTIONALITY..........................................................5
VSD B BOX OPERATION............................................6
SECTION 4 — INSTALLATION ..................................... 7
UNIT LOCATION..........................................................7
POWER SUPPLY.........................................................7
RS485 NETWORK......................................................7
VSD B BOX AND X8I OR X12I CONNECTIVITY..........9
IR-5000 DISCHARGE (DELIVERY) PRESSURE
SENSOR INTERCONNECT..........................................10
IR-302 DISCHARGE (DELIVERY) PRESSURE SENSOR
INTERCONNECT.........................................................11
IR485 GATEWAY CONNECTION...............................12
SPEED MONITORING INPUT (OPTION)......................12
REMOTE OUTPUTS...................................................12
SECTION 5 — DISPLAY AND MENU OPERATION ... 13
OPERATION...............................................................13
SECTION 8 — DIAGNOSTICS ..................................... 23
SECTION 9 — FAULT CODES .................................... 23
SECTION 10 — VSD B BOX STATUS BLOCK
DIAGRAM ..................................................................... 24
SECTION 11 — PARTS LIST ....................................... 25
SECTION 12 — TECHNICAL DATA ............................ 25
SECTION 13 — WIRING DIAGRAM ............................ 26
VSD B BOX SCHEMATIC...........................................26
XPM-TAC24 SCHEMATIC........................................27
XPM-VO2 (+VDC ANALOG OUTPUT)......................27
XPM-PSU24 (24VAC TO 24VDC)...........................27
SECTION 14 — COMMISSIONING FORM ................... 28
Refer to Section Indicated
Note
SECTION 6 — COMMISSIONING ............................... 15
COMMISSIONING PROCEDURE.................................15
PHYSICAL CHECKS...................................................15
SELECTING VSD-B MODE:......................................15
COMPRESSOR PRESSURE SET POINTS...................15
VSD B BOX CONFIGURATION..................................16
TARGET PRESSURE SET POINT...............................17
SECTION 7 — SYSTEM CONFIGURATION ............... 18
DISPLAY ITEM STRUCTURE......................................18
ACCESSING THE VSD B BOX CONFIGURATION
SCREENS..................................................................18
MENU ITEMS AND SETTINGS....................................20
Important or Caution, Safety
2
SECTION 1 – INTRODUCTION
The VSD B Box is intended to provide a method of system integration for an Ingersoll Rand Bolt-On VSD (Variable Speed Drive) air compressor equipped with a an Intellisys Controller. The VSD B Box will provide the
SECTION 2 — SAFETY
SAFETY PRECAUTIONS
WARNING :
!
WARNING :
WARNING :
!
WARNING :
Before installing or operating the VSD B Box, take time to carefully read all the instructions contained in this manual, all compressor manuals, and all manuals of any other peripheral devices that may be installed or connected to the unit.
Electricity and compressed air have the potential to cause severe personal injury or property damage.
The operator should use com m on sense and good working practices while operating and maintaining this system. All applicable codes should be strictly adhered to.
Maintenance must be performed b y adequately qualified personnel that are equipped with the proper tools.
INSTALLATION
Installation work must only be carried out by a competent person under qualified supervision.
A fused isolation switch must be fitted between the main power supply and the VSD B Box.
The VSD B Box should be mounted in such a location as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times.
If raised platforms are required to provide access to the VSD B Box, they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides.
Risk of Danger
Risk of Electric Shock
Risk of High Pressure
Consult Manual
required functionality to enable system integration and efficient control using the X8I or X12I Automation System.
.
OPERATION
The VSD B Box must only be operated by competent personnel under qualified supervision.
Never remove or tamper with safety devices, guards or insulation materials fitted to the VSD B Box.
The VSD B Box must only be operated at the supply voltage and frequency for which it is designed.
When main power is switched on, lethal voltages are present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit.
Do not open access panels or touch electrical components while voltage is applied unless it is necessary for measurements, tests or adjustments. Such work should be carried out only by a qualified electrician equipped with the correct tools and wearing appropriate protection against electrical hazards.
All air compressors and/or other equipment connected to the unit should have a warning sign attached stating “THIS UNIT MAY START WITHOUT WARNING” next to the display panel.
If an air compressor and/or other equipment connected to the unit is to be started remotely, attach two warning signs to the equipment stating “THIS UNIT CAN BE STARTED REMOTELY”. Attach one sign in a prominent location on the outside of the equipment, and the other sign inside the equipment control compartment.
3
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must onl y be carried out by competent personnel under qualified supervision.
If replacement parts are required, use only genuine parts from the original equipment manufacturer, or an alternative approved source.
Carry out the following operations before opening or removing any access panels or carrying out any work on the VSD B Box:
o Isolate the VSD B Box from the main
electrical power supply. Lock the isolator in the “OFF” position and remove the fuses.
o Attach labels to the isolator switch and
to the unit stating “WORK IN PROGRESS - DO NOT APPLY VOLTAGE”. Do not switch on electrical power or attempt to start the VSD B Box if such a warning label is attached.
Make sure that all instructions concerning operation and maintenance are strictly followed and that the complete unit, with all accessories and safety devices, is kept in good working order.
The accuracy of sensor devices must be checked on a regular basis. They must be calibrated when acceptable tolerances are exceeded. Always ensure any pressure within the compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device.
The VSD B Box must only be cleaned with a damp cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis.
Do not paint the control faceplate or obscure any indicators, controls, instructions or warnings
4
SECTION 3 — COMPRESSOR CONNECTION AND CONTROL
The VSD B Box is designed to connect to an X8I or X12I Automation System unit, using a 2-wire RS485 data cable.
The VSD B Box is intended to provide a method of system integration Ingersoll Rand air compressors with an Intellisys Controller equipped with a Bolt-On VSD. The VSD B Box is used to integrate with VSD Air Compressors that are controlled by Current Pressure Sensors.
Each air compressor in a system that requires VSD B Box integration must be equipped with an individual VSD B Box and the IR485 Gateway. Any number of VSD B Boxes can be connected to the Automation System unit as long as the total number of compressors does not exceed the total number of compressors for the Automation System model.
The VSD-B Box also monitors the compressor status, as it is reported to the X8I or X12I Automation System unit, by the IR485 Gateway. This function enables the VSD-B Box to simulate all features of a standard X8I or X12I network compressor integration.
In conjunction with a ‘speed monitoring kit’ (available separately) the VSD B Box will provide all required functionality to maximize the ENER, Energy Control Mode, in the X8I or X12I Automation System.
STANDARD CONTROL FEATURES AND FUNCTIONALITY
The IR Bolt-On VSD must be equipped with a 4-20mA pressure sensor that is used for variable speed drive regulation or compressor pressure regulation control. A VSD B Box will accommodate a pressure sensor range of
14.5 psi (1.0bar) to 8702 psi (600bar). A VSD-B box also requires the use of an “IR485 Gateway” compressor device.
Compressor Configurations and Characteristics That Can Be Accommodated by the VSD B Box:
Ingersoll Rand air compressors with a Bolt-On VSD that are equipped with two pressure sensors that both monitor package discharge (delivery) pressure. One sensor is dedicated to Intellisys compressor controller for basic regulation functions; the other is dedicated to variable speed drive unit regulation. The VSD B Box is able to accommodate this requirement without affecting compressor control system functionality.
5
VSD B BOX OPERATION
All air compressors are equipped with a method of sensing pressure. An air compressor regulates using the compressor package delivery pressure as the control variable.
4-20mA
IR air compressors equipped with a Bolt-On VSD use two independent pressure sensors. The first provides the normal fixed speed compressor Intellisys Controller with pressure information for load/unload regulation and safety features. The second provides the VSD with pressure information for main motor variable speed regulation.
The VSD-B Box monitors the VSD pressure sensor as an input and simulates the pressure sensor signal as an output. The VSD-B Box uses this method to modify the pressure signal and manipulate the speed behavior of the VSD. The VSD-B Box becomes the Bolt-On VSD pressure sensor.
This functionality enables the management system to utilize the compressor in a coherent manner and optimize total system efficiency and maintain air quality.
VSD B Box Operation Example:
If the Automation System unit is detecting a network air pressure (PN) of 100psi (6.9bar), and the system target pressure requirement (P) is 103psi (7.1bar), the VSD B Box will immediately calculate that a pressure rise of 3psi (0.2bar) is required to achieve and maintain system target pressure (P). Due to pressure differential across a local compressed air treatment system (PD) the compressor is currently operating at 107psi (7.4bar). The VSD B Box will manipulate the compressor pressure signal (PS) to cause the compressor to increase discharge (delivery) pressure (PC) to 110psi (7.6bar). This action will increase system pressure to the required target pressure. The VSD B Box will continuously re­calculate and manipulate the compressor pressure signal (PS) to accommodate changes in demand and compensate for any local or compressed air network pressure differentials.
PC
PS
VSD
PD
P
PN
VSD Box
4-20mA
The VSD-B Box also monitors compressor status, as it is reported to the management system (Ready, Run, and Load/Unload), by the IR485 Gateway device. This function enables the VSD-B Box to simulate all features of a standard X8I or X12I network compressor integration.
Actual System pressure and Automation System ‘target’ pressure information is routinely transmitted from the X8I or X12I to the VSD-B Box. The VSD-B Box uses this information to calculate the difference between the compressor delivery pressure and the system ‘target’ pressure. The VSD B Box utilizes pressure signal manipulation to continuously re-align compressor output with system requirements.
This functionality also enables the VSD B Box to continuously compensate for any pressure differential that may occur across local air treatment, along air pipe work or between different locations in a compressed air network.
6
SECTION 4 — INSTALLATION
It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.
Information regarding the compressor control system, method of operation and regulation settings, is required. Knowledge of VSD compressor regulation methods, experience working with compressor control systems and basic principle knowledge of compressed air systems, is also required to be able to successfully install and commission this product.
Dependent on compressor type and installation environment additional fixings, wiring, cabling, terminations and terminals will be required for installation.
UNIT LOCATION
The VSD B Box is wall or panel mounting using conventional screw fixings. The maximum distance between the X8I or X12I and the VSD B Box is 4000ft (1219 meters) of cable length. The VSD B Box must be located adjacent to the compressor unit within 330ft (100m) of cable length from the VSD.
POWER SUPPLY
A fused switching isolator must be installed to the main incoming power supply, external to the VSD B Box. The isolator must be fitted with a properly sized fuse to provide adequate protection to the power supply cable used (in accordance with local electrical and safety regulations).
1 2 34
L
N
N L
XPM-TAC24
EE
X01
E
Power Supply Terminals
Ensure that the voltage select input is properly jumpered for the incoming power. Default voltage configuration is 230Vac.
X04
X04
1
3 4
2
VOLTAGE SELECT
1
3 4
2
VOLTAGE SELECT
230Vac
115Vac
The cable used between the X8I or X12I and the VSD B Box is Belden 9841 (or equivalent). It should be run in grounded conduit and should not be greater than 4000 feet (1219 meters) in length.
RS485 and Signal Cable Routing
RS485 data communications and other low voltage signals can be subject to electrical interference. This potential can result in intermittent malfunction or anomaly that is difficult to diagnose. To avoid this possibility always use ground (earth) shielded cables, securely bonded to a known good ground (earth) at one end. In addition, give careful consideration to cable routing during installation.
a) Never route an RS485 data communications or low voltage signal cable alongside a high voltage or 3-phase power supply cable. If it is necessary to cross the path of a power supply cable(s), always cross at a right angle.
b) If it is necessary to follow the route of power supply cables for a short distance (for example: from a compressor X8I to a wall along a suspended cable tray) attach the RS485 or signal cable on the outside of an grounded (earthed) cable tray such that the cable tray forms an grounded (earthed) electrical interference shield.
c) Where possible, never route an RS485 or signal cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications antenna).
RS485 NETWORK
The VSD B Box is equipped with an RS485 network communications capability using the ir485 protocol. The VSD B Box is intended to operate as part of the X8I or X12I Automation System. Connection to the system management unit is two-wire, twisted pair, ground (earth) shielded, RS485 data link. Connect the RS485 data cable wires to terminal X07 located on the VSD B Box controller.
L2
L1
Note: Polarity is important.
X07
L2 L1
7
VSD B BOX HARDWARE CONFIGURATION
VSD B Box Terminal PCB Type Selector
VSD B Box Terminal PCB has a jumper on it that determines the type of control box the PCB is being used in. Check to determine if jumper (J1), as shown below, is placed in the correct position for a VSD B Box.
VSD/EX
J1
X01
1
246
X02
7
53
X03
119
8 10 12 1416 182022 24 26282930
XPM-Ao2 Module 4-20mA Output Mode Selectors
Remove the top cover of the XPM-Ao2 module and check the 4-20mA output mode selectors are in the ‘PASSIVE’ mode position. (The default position as shipped from the factory.)
KC-
18 17 16 15 14 13 12
KC-
X04
19171513
21
28
27 26 25 24 23 22 21
10
98765
11
23
X07X06X05
2725
43
X09
X08
31 32 33 34
20 19
21
R05
R06
21
3213
1
n
2
L
e
L e
r
c
s
C
X01
D V
4
2
+
RS485
X04X05
V
0
1 D E L
21
-
+
3
3
A
A
N
N
A
A
X02
#1
4-20mA(1)
VDC
1 A N A
-
21
+
2 A N A
1 A N A
+
4-20mA(2)
-
2 A
X03X06
N A
Ao2
#2
X06 X03
4-20mA(2)
C010
PASSIVE MODE
C03
4-20mA(1)
X02
8
VSD B BOX AND X8I OR X12I CONNECTIVITY
Consult the X8I OR X12I Interconnect and Application Guide prior to the installation of the VSD B Box to the pressure sensor on the VSD and the compressor.
Pressure sensor connectivity is dependent on compressor and control system type.
1
Gateway
1
2
IR485
RS485
VSD-B Box
Belden 9841
Or Equivilant
2 + Ground (Earth) 115/230Vac, 5A
2
PRESSURE SENSOR CONNECTIONS
Pressure sensor connectivity is dependent on compressor and control system type.
1) Disconnect the VSD pressure sensor wires from the VSD and connect to the VSD-B Box terminals as indicated on the following connection diagrams.
2) Connect the VSD-B output pressure signal terminals to the VSD pressure sensor terminals as indicated on the following connection diagrams.
Pressure signal output terminals are located on the XPM­Ao2 module within the VSD-B Box. These terminals are not located on the main terminal PCB of the VSD-B Box
21
3213
1
n
2
L
e
L e
r
c
s
C
X01
D V
4
2
+
RS485
X04X05
V
0
1 D E L
21
-
+
3
3
A
A
N
N
A
A
#1
4-20mA(1)
VDC
X02
1 A N A
-
21
+
2 A N A
1 A N A
+
4-20mA(2)
-
2 A
X03X06
N A
Ao2
#2
Consult the X8I Interconnect and Application Guide
prior to the installation of the VSD B Box to the pressure sensor on the VSD and the compressor.
Pressure sensor connectivity is dependent on compressor and control system type.
Electrical Interference
Failure to protect low voltage pressure signals between the compressor and VSD-B Box will result in unstable and/or erratic pressure readings; resulting in unstable and/or erratic compressor regulation behaviour.
4 to 20mA Pressure Sensors
Always use shielded, 18 gauge, 2-conductor
cable no more than 330 feet (100 meters) in length. Ensure the shield wire is securely connected to earth ground at the VSD B Box end only.
9
Loading...
+ 19 hidden pages