Ingersoll Rand System Automation I-O Accessory Box User Manual

Ingersoll Rand
System Automation
I/O Accessory Box
Operator’s Manual
More Than Air. Answers.
Online answers: http://air.ingersollrand.com
C.C.N. : 80444110
: A
REV. DATE : DECEMBER 2008
SECTION 1  TABLE OF CONTENTS
Section 1 - table of contentS .............................2
Section 2 - intRoDUction ......................................
Section 3 - Safety pRecaUtionS .........................
INSTALLATION .............................................................................3
OPERATION ...................................................................................3
MAINTENANCE AND REPAIR .................................................4
Section 4 - inStallation .........................................5
UNIT LOCATION ..........................................................................5
POWER SUPPLY ...........................................................................
RS485 NETWORK ........................................................................
I/O BOX ANALOG CONDITIONING MODULE................... 5
TO CHANGE AN ACM DEVICE: ............................................... 6
TO REMOVE AN ACM DEVICE: ............................................... 7
TO INSTALL AN ACM DEVICE: ...................................
ACM IDENTIFICATION ...............................................
6.5 OPERATION ............................................................
6.6 DIGITAL INPUT STATUS INDICATIONS ................
3
6.7 ANALOG INPUT DISPLAY .........................................
3
6.8 POWER FAILURE AUTORESTART ..........................
6.9 I/O BOX FAULT ..............................................................
6.10 SHUTDOWN FAULTS ...................................................
MANAGEMENT UNIT FAULT CODES .................................
Section 8 - paRtS liSt ..............................................20
Section 9 - technical Data ..................................
5
Section 10 - WiRing DiagRam ..............................
5
XPMTAC24 .................................................................................22
Refer to Section Indicated
7
7
Note
17
17
18
18
18
18
19
20
21
Section 5 - commiSSioning ....................................9
PHYSICAL CHECKS .....................................................................9
NETWORK ID ................................................................................
REFERENCE SYSTEM PRESSURE DISPLAY ......................... 9
I/O CONFIGURATION ................................................................9
VIRTUAL RELAY AUTOMATION .............................................9
Section 6 - DiSplay anD menU opeRation .....10
MENU NAVIGATION .................................................................10
MENU ITEMS AND SETTINGS ..............................................
MENU S01  CONFIGURATION ...............................
MENU D01 THROUGH D08  DIGITAL INPUTS .......
MENUS A01 THROUGH A04  ANALOG INPUTS ....
DIAGNOSTICS ............................................................................16
11
11
12
13
Section 7 - opeRation ............................................17
Important or Caution, Safety
9
6.1 USER INTERFACE .........................................................17
6.2 DISPLAY ..........................................................................
6.3 STATUS SYMBOLS ....................................................
6.4 INDICATORS ..................................................................
17
17
17
2
SECTION 2  INTRODUCTION
1 2
A: 85%
Ingersoll Rand
IO
Ab.01
Ingersoll Rand
IO
Ab.02
!
!
An I/O Box provides additional general purpose I/O (input/output) for system enhancing monitoring capabilities and for providing distributed system automation via Virtual Relay.
More than one I/O Box can be installed in a system (up to a maximum of 2 on an X8I). Each I/O Box features:
8 Digital Inputs
5 4-20 mA Analog Inputs (1 is a dedicated
pressure input)
6 Relay Outputs
Digital inputs can be used to monitor switching contact devices. Each input can be set to act as an Alarm or Trip input or used for Virtual Relay Automation. Digital inputs can also be used for metering (for example m3, ft3, kWh) providing an accumulative count of pulses from a metering device.
Analog inputs can be used to monitor sensor devices (for example: pressure, differential pressure, temperature, dew point, flow, current, power, bearing condition). Each input is equipped with adjustable high or low level detection that can be used to activate an
Alarm or Trip or used for Virtual Relay Automation.
Relay outputs use the Virtual Relay Automation technology and are totally configurable with dual input logic functions. Relay functions can be assigned utilizing any status or condition information available on a system network from any compatible unit connected to the network.
The I/O Box is designed to connect to a management system using an industrial 2-wire RS485 data network,
with a total cable length up to 4000 ft (1219 m).
SECTION 3  SAFETY PRECAUTIONS
competent person under qualified supervision.
WARNING : Risk of Danger
WARNING : Risk of Electric Shock
WARNING : Risk of High Pressure
WARNING : Consult Manual
Before installing or operating the I/O Box, take time
to carefully read all the instructions contained in this manual, all compressor manuals, and all manuals of any other peripheral devices that may be installed or connected to the unit.
Electricity and compressed air have the potential to
cause severe personal injury or property damage.
The operator should use common sense and good
working practices while operating and maintaining this system. All applicable codes should be strictly adhered to.
Maintenance must be performed by adequately
qualified personnel that are equipped with the proper tools.
INSTALLATION
Installation work must only be carried out by a
A fused isolation switch must be fitted between the
main power supply and the I/O Box.
The I/O Box should be mounted in such a location
as to allow operational and maintenance access without obstruction or hazard and to allow clear visibility of indicators at all times.
If raised platforms are required to provide access
to the I/O Box they must not interfere with normal operation or obstruct access. Platforms and stairs should be of grid or plate construction with safety rails on all open sides.
OPERATION
The I/O Box must only be operated by competent
personnel under qualified supervision.
Never remove or tamper with safety devices, guards
or insulation materials fitted to the I/O Box.
The I/O Box must only be operated at the supply
voltage and frequency for which it is designed.
When main power is switched on, lethal voltages are
present in the electrical circuits and extreme caution must be exercised whenever it is necessary to carry out any work on the unit.
Do not open access panels or touch electrical
components while voltage is applied unless it is necessary for measurements, tests or adjustments.
3
4
Such work should be carried out only by a qualified electrician equipped with the correct tools and wearing appropriate protection against electrical hazards.
All air compressors and/or other equipment
connected to the unit should have a warning sign attached stating “THIS UNIT MAY START WITHOUT WARNING” next to the display panel.
If an air compressor and/or other equipment
connected to the unit is to be started remotely, attach two warning signs to the equipment stating “THIS UNIT CAN BE STARTED REMOTELY”. Attach one sign in a prominent location on the outside of the equipment, and the other sign inside the equipment control compartment.
MAINTENANCE AND REPAIR
Maintenance, repairs or modifications must only
be carried out by competent personnel under qualified supervision.
If replacement parts are required, use only genuine
parts from the original equipment manufacturer, or an alternative approved source.
Carry out the following operations before opening
or removing any access panels or carrying out any work on the I/O Box:
i. Isolate the I/O Box from the main electrical power supply. Lock the isolator in the “OFF” position and remove the fuses. ii. Attach label to the isolator switch and to the unit stating “WORK IN PROGRESS - DO NOT APPLY VOLTAGE”. Do not switch on electrical power or attempt to start the I/O Box if such a warning label is attached.
Make sure that all instructions concerning
operation and maintenance are strictly followed and that the complete unit, with all accessories and safety devices, is kept in good working order.
The accuracy of sensor devices must be checked
on a regular basis. They must be calibrated when acceptable tolerances are exceeded. Always ensure any pressure within the compressed air system is safely vented to atmosphere before attempting to remove or install a sensor device.
The I/O Box must only be cleaned with a damp
cloth, using mild detergents if necessary. Avoid the use of any substances containing corrosive acids or alkalis.
Do not paint the control faceplate or obscure any
indicators, controls, instructions or warnings.
1
VOLTAGE SELECT
2 3 4
X04
1
VOLTAGE SELECT
2 3 4
X04
230Vac
115Vac
EELN
NLE
X01
1 2 3 4
XPM-TAC24
26
28
25
27
X07
L1
L2
RS485
SECTION 4  INSTALLATION
It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.
UNIT LOCATION
The I/O Box is wall mounted using conventional screws/ bolts. The maximum distance between the X8I and the I/O Box is 4000ft (1219 m) of cable length. The maximum distance between the I/O Box and each compressor is 330ft (100 m) of cable length and within 330ft (100 m) of cable length from any pressure sensor option (if applicable).
The cable used between the X8I and the I/O Box is Belden 9841 (or equivalent). It should be run in grounded conduit and should not be greater than 4000 feet (1219m) in length.
POWER SUPPLY
A fused switching isolator must be installed to the main incoming power supply, external to the I/O Box. The isolator must be fitted with a properly sized fuse to provide adequate protection to the power supply cable used (in accordance with local electrical and safety regulations).
Belden 9841 (or equivalent). It should be run in grounded conduit and should not be greater than 4000 feet (1219 m) in length.
RS485 data communications and other low voltage signals can be subject to electrical interference. This potential can result in intermittent malfunction or anomaly that is difficult to diagnose. To avoid this possibility always use earth shielded cables, securely bonded to a known good earth at one end. In addition, give careful consideration to cable routing during installation.
a) Never route an RS485 data communications or
low voltage signal cable alongside a high voltage or 3-phase power supply cable. If it is necessary to cross the path of a power supply cable(s), always cross at a right angle.
b) If it is necessary to follow the route of power
supply cables for a short distance (for example: from a compressor X8I to a wall along a suspended cable tray) attach the RS485 or signal cable on the outside of an earthed cable tray such that the cable tray forms an earthed electrical interference shield.
c) Where possible, never route an RS485 or signal
cable near to equipment or devices that may be a source of electrical interference (for example: 3-phase power supply transformer, high voltage switchgear unit, frequency inverter drive module, radio communications antenna).
POWER SUPPLY TERMINALS
Ensure that the voltage select input is properly jumpered for the incoming power. Default voltage configuration is 230Vac.
RS485 NETWORK
The I/O Box is equipped with an RS485 network communications capability using the IR485 protocol. The I/O Box is intended to operate as part of the X8I Management System. Connection to the system management unit is two-wire, twisted pair, earth shielded, RS485 data link. Connect the RS485 data cable wires to terminal X07.
Note: Polarity is important.
The cable used between the X8I and the I/O Box is
5
6
I/O BOX ANALOG CONDITIONING MODULE
1
2
34
4 3 1
X04
XPM-Ai4
XPM-Ai4
1234
30X20X10X
X04
ACM
XPM-Ai4
1
34
4 3 2
Ai1
Ai2
Ai1
Ai2Ai3Ai4
12345678
Ai1
Ai2Ai3Ai4
XPM-Ai4
3338
X10
3437 3235
X09
3136
Ai1
Ai2Ai3Ai4
CAi1CAi2CAi3CAi4
X03
I/O Box
The electrical input characteristics of the four adjustable analog inputs can be individually altered to suit a sensor or signal type using Analog Conditioning Modules
(ACM).
ACM devices are hardware modules that plug in to the analog input circuit and condition the incoming signal.
For a particular sensor type the correct ACM device must be selected and fitted.
TO CHANGE AN ACM DEVICE:
Remove the power from the unit.
ACM devices for analog inputs 1 to 4 are located within the unit’s XPM-Ai4 module.
To gain access to the ACM devices remove the cover of the XPM-Ai4 module. The ACM devices can be removed and inserted by hand without the use of a tool.
TO REMOVE AN ACM DEVICE:
2
1
1 2 3
4
1
2
34
#
Ai4 Ai3 Ai2 Ai1
ACM
Never use a metallic tool (screwdriver tip for example)
to remove an ACM device.
TO INSTALL AN ACM DEVICE:
Antistatic Precaution
ACM devices contain electronic components; take all necessary antistatic precautions including:
Before handling an ACM device touch an exposed
1) earthed surface to discharge any body static.
Always store in an anti-static container or package;
2) never place on a non anti-static surface.
Handle the device by the edges; never touch the
3) electronic com[ponenets on the device.
ACM IDENTIFICATION
# ACM devices are classified by a number and can be
readily identified by color:
Any ACM type can be fitted to an analog input socket. ACM devices can be fitted in the XPM-Ai4 module in any required combination.
The I/O Box is shipped with four type 3 ACMs installed and two spare type 6 ACMs.
Example: for analog input 1 (Ai1):
Before inserting an ACM device check the pins of the ACM and the XPM-Ai4 socket.
ACM devices are designed to mount in the XPM-Ai4 socket at an angle. This is intended to retain the device securely in the socket in the instance of mechanical vibration.
When an ACM device is fitted the ‘AT: Input Type’ menu setting for the analog input must be adjusted to match the ACM type number.
Menu Items: Analog Inputs A01-A04
Digital Input:
Remote volt-free switching contact
Analog Signal:
DC Voltage or Current
wire polarity is important
Temperature Sensor
7
8
3: 0mA
0-20mA +24VDC
3: 4mA
4-20mA +24VDC
6: PT1
PT100
3
6
3
2
3
1
3
2
3
1
3
2
3
1
GREEN
RED (Blue)
1 2
A: 85%
Ingersoll Rand
IO
Ab.01
Ingersoll Rand
IO
Ab.02
SECTION 5  COMMISSIONING
When commissioning the I/O Box, carry out the following procedures before attempting to start.
It is recommended that an authorized and trained
service technician perform the commissioning.
PHYSICAL CHECKS
1. Before applying power to the I/O Box, ensure the power supply connections are correct and secure and the operating voltage selector is set correctly for the power supply voltage in use (115Vac or 230Vac (+-10%), 50/60Hz).
2. Open the front panel of the I/O Box and check the location of the link wire(s) connected to the “Voltage Selection” terminals of the power supply PCB. If necessary, change the link wire locations to those illustrated for the voltage in use.
See the section on Installation for more
information.
3. Check and ensure all sensor, input, relay and other connections are correctly installed and secure.
4. Close the front panel of the I/O Box.
5. Switch on the power supply to the I/O Box.
6. The control program identification will be displayed for a short period followed by the normal operational user display.
NETWORK ID
The network ID of each I/O Box connected to a system must be unique. The ID of an I/O Box can be adjusted from 1 to 12; this also sets the network ID. Assign each I/O Box a different ID number; starting at ‘1’ increasing sequentially up to the number of I/O Boxes connected to the network system.
S01 – Ad
ID and Network Address
sensor and carry out the pressure sensor commissioning and calibration procedure.
S01 - Po
S01 - Pr
Sensor Offset Calibration
Sensor Range Calibration
Menus and Menu Items
I/O CONFIGURATION
For each I/O function and feature to be utilized, configure the appropriate I/O configuration items in the associated menu. Each Input or Output has a dedicated menu.
Menus and Menu Items
Digital Inputs
Analog Inputs
Virtual Relay Automation
For analog inputs; check the type and location of the
ACM devices fitted.
ACM (Analog Conditioning Modules)
VIRTUAL RELAY AUTOMATION
The Ingersoll Rand Automation X8I system is equipped with virtual relay capability to expand the control of a compressed air system. Using virtual relay allows the X8I system to control and monitor ancillary equipment such as dryers, flow meters, dew point monitors, etc.
When virtual relay capability is activated all inputs and outputs in the X8I system can be utilized in much the same way a Programmable Logic Controller (PLC) would be used to control a system. Each component in the X8I system has a list of statuses and functions that can be used as input functions to trigger the virtual relays, which are logical constructs that are either true or false based on the input functions but are not necessarily connected to a physical relay output. Virtual relays can also be connected to a physical output and thus allow control of equipment in the system.
An I/O Box must be installed in the automation system to be able to use virtual relay automation. Please see the Virtual Relay Automation user’s guide for complete information.
Menus and Menu Items
REFERENCE SYSTEM PRESSURE DISPLAY
S01- PD Pressure Detect Enable
Check the displayed system pressure if the RP, ‘Reference Pressure’ , sensor function is utilized. If the pressure is incorrect, or inaccurate, check the type and range of the
9
10
SECTION 6  DISPLAY AND MENU OPERATION
MENU NAVIGATION
Display Item Structure:
All value, parameter or option selection displays are grouped into menu lists. Items are assigned to a list according to type and classification. Items that can be used to select options or modify functions are assigned to ‘menu mode’ lists. Items that a User may require to view during routine operation, detected pressure for example, are assigned to the normal operational mode list. Lists are identified by page number; the normal User display list is page ‘P00’. All parameters and options are assigned to menu mode pages ‘P01’ or higher. All page ‘P00’ items are view only and cannot be adjusted.
Normal Operational Mode (Page P00):
At controller initialisation, all display elements and LED indicators are switched on for three seconds, the display will then show the software version code for a further 3 seconds before initialisation is complete and the normal operating display (Page P0) is shown. In page P00 ‘normal operational display mode’ the main display will continuously show the detected delivery pressure and the Item display will show the first item of the ‘User’ menu. User menu ‘Items’ can be selected using the Up or Down buttons at any time. Pressing the Enter button will lock any selected Item display and inhibit return to the default display. When an Item display is locked the lock key symbol will slow flash. To unlock an Item display press Up or Down to view an alternative Item display or press Reset or Escape. No Item values, options or parameters can be adjusted in page ‘P00’. If a fault condition occurs the fault code becomes the first list item and the display will automatically jump to display the fault code. More than one active fault code item can exist at any one time.
Access Code:
Access to page list displays higher than page ‘P00’ is restricted by access code. To access menu mode pages press MENU, an access code entry display is shown and the first code character will flash. Use PLUS or MINUS to adjust the value of the first code character then press ENTER. The next code character will flash; use UP or DOWN to adjust then press ENTER. Repeat for all four code characters.
Menu Mode Navigation:
In menu mode the main value display will flash and show the Page number. To select a page press UP or DOWN. For each page the display will show the first Item of the page list. To view a page list press ENTER, the Page number will stop flashing and the Item display will flash. Press UP or DOWN to view the selected page list items. To select an Item value for modification press ENTER, the Item display will stop flashing and the value display will flash. The value or option can now be modified by pressing UP(Plus) or DOWN(Minus). To enter a modified value or option in memory press ENTER; alternatively the modification can be abandoned, and the original setting maintained, by pressing ESCAPE.
Press ESCAPE at any time in menu mode to step backwards one stage in the navigation process. Pressing ESCAPE when the page number is flashing will exit menu mode and return the display to normal operational mode; page ‘P00’.
Press and hold RESET for two seconds at any time to immediately exit menu mode and return to the normal operational mode display. Any value or option adjustment that has not been confirmed and entered into memory will be abandoned and the original setting maintained.
A flashing Key symbol displayed with any Item indicates the Item is locked and cannot be modified. This will occur if the Item is view only (non adjustable) or in instances where the item cannot be adjusted while the I/O Box is in ‘Remote Mode’.
If the code number is less than 1000 then the first code character will be 0(zero). To return to a previous code character press ESCAPE. When all fourcode characters have been set to an authorized codenumber press ENTER. An invalid code will return the display to normal operational mode; page ‘P00’.
Access Code Timeouts:
When in menu mode, if no key activity is detected for a period of time the display will automatically reset to the normal operational display; Page ‘P00’.
MENU ITEMS AND SETTINGS
MENU S01CONFIGURATION
1 Ad ID and Network Address
2 PD Pressure Detect Enable
3 Po Pressure Sensor Calibration Offset
4 Pr Pressure Sensor Calibration Range
5 P> Pressure Display Units
6 ID User Menu Item Default
7 RP Pulse Counter Reset Enable
MENU D01 THROUGH D08DIGITAL INPUT FUNCTION
1 ST Normal State (NO or NC)
2 Fn Function (‘-’, A, T, S or P)
3 DT Delay Time
4 RF Reset Function
MENU A01 THROUGH A04ANALOG INPUT CONFIGURATION
1 AT Input Type
2 Ut Display units
3 Vo Value Offset
4 Vr Value Range
5 DF Display Function
6 FH Fault High Level Setpoint
7 FL Fault Low Level Setpoint
8 Fn
9 FI Fault Inhibit Enable
10 Dt Delay Time
11 RT Reset Function
Fault Function
MENU RP1 AND RP2PULSE RELAY
1 F1 Input Function #1
2 F2 Input Function #2
3 Fu Input Logic Function
4 On On Time
5 FS Function State (NO or NC)
6 CF Comms failure function
MENU RF1COMPRESSOR RUNNING RELAY
1 01 Compressor #1 Select
2 02 Compressor #2 Select
... ...
12 12 Compressor #12 Select
13 FN Logic Function
MENU LF1COMPRESSOR LOADED RELAY
1 01 Compressor #1 Select
2 02 Compressor #2 Select
... ...
12 12 Compressor #12 Select
13 FN Logic Function
MENU AF1COMPRESSOR NOT AVAILABLE RELAY
1 01 Compressor #1 Select
2 02 Compressor #2 Select
... ...
12 12 Compressor #12 Select
13 FN Logic Function
MENU R01 THROUGH R06PHYSICAL RELAY
CONFIGURATION
1 F1 Input Function #1
2 F2 Input Function #2
3 Fu Input Logic Function
4 On On Time
5 Of Off Time
6 ST Normal State (NO or NC)
7 CF Comms failure function
MENU R07 THROUGH R13VIRTUAL RELAY CONFIGURATION
Virtual relay will be implemented in a future release
MENU RT1 AND RT3TIME RELAY CONFIGURATION
1 F1 Input Function #1
2 F2 Input Function #2
3 Fu Input Logic Function
4 On On Delay Time
5 Of Off Dellay Time
6 SS
Start State (NO or NC)
7 CF Comms failure function
MENU F10SPM BEARING MONITORING
1 R1 Shaft Speed #1
2 D1 Shaft Diameter #1
3 A1 dBi #1 (View Only)
4 R2 Shaft Speed #2
5 D2 Shaft Diameter #2
6 A2 dBi #2 (View Only)
7 R3 Shaft Speed #3
8 D3
Shaft Diameter #3
9 A3 dBi #3 (View Only)
10 R4 Shaft Speed #4
11 D4 Shaft Diameter #4
12 A4 dBi #4
Analog Inputs: SPMTM Bearing Monitoring Function
MENU 7DIAGNOSTICS
See ‘Diagnostics’
Access Code = 0021
11
12
MENU S01  CONFIGURATION
Ad: Box Number and Network Address
I/O Box number and network address. For each I/O Box in a system assign an I/O Box number starting from ‘1’ increasing sequentially to the number of I/O Boxes in the system.
For example:
1=I/O Box 01
105=network address; decimal value
Network address values do not always sequentially follow the I/O Box number sequence; this is normal and can be ignored.
The I/O Box number must be unique; if two I/O Boxes are assigned the same number (same network address) the system will be disrupted.
PD: Pressure Detect Enable
Enables the dedicated reference pressure sensor input.
0 = Disable, no pressure sensor connected
1 = Enable
Po: Reference Pressure Offset Calibration
The value can be adjusted between –22 PSI and +22
PSI (-1.5 bar to +1.5 bar).
Default = 0 PSI (0.0 bar).
The ‘offset’ value can be used for atmospheric (0psig)calibration; expose the reference pressure sensor to atmosphere and adjust until the display pressure shows 0 PSI. The main display value will show the actual detected pressure when this menu item is selected.
Pr: Reference Pressure Range Calibration
The value can be adjusted for any 4-20mA sensor range between 14.5 PSI (1 bar) and 9135 PSI (630 bar). Default = 232 PSI (16 bar).
If the sensor does not have a 0 (zero) PSI offset then the range value must be the same as the ‘maximum’ pressure value of the sensor.
For example: if the sensor is a –14.5 PSI (-1.0bar) to
217.5 PSI (15 bar) type then:
Offset = -14.5 PSI Range = 217.5 PSI
The ‘range’ value can be used for calibration: expose the senor to a known accurate pressure and adjust the ‘range’ value until the display pressure matches the applied pressure. The main display value will show the actual detected pressure when this menu item is selected.
P>: Pressure Display Units
0 = bar
1 = psi
2 = kPa
Only applicable to the Reference Pressure display value.
ID: User Menu Item Default
RP, D1-D8, A1-A4 or R1-R6
Default User menu display item.
After a short period of no keypad activity the User menu display item will automatically change to show the item defined by this setting.
RP: Pulse Counter Reset Enable
For any digital input set for ‘pulse count’ mode, this setting determines if the pulse count can be reset manually from the User menu.
0 = Remote serial communications reset only
1 = Allow manual reset from User menu
Digital Inputs: Pulse Count Mode
MENU D01 THROUGH D08  DIGITAL INPUTS
The I/O Box is equipped with 8 digital inputs. A digital input can be used to monitor the state of a remote volt­free contact that is rated for 24VDC @ 10mA minimum.
The state of a remote contact can be:
a)
Open Circuit (off or ‘0’ state)
Closed Circuit (on or ‘1’ state)
b)
ST Normal State NO/NC
This setting defines if the normal, or OK, state is ‘NO’ normally open circuit (0) or ‘NC’ normally closed circuit (1).
If the remote contact is detected to change state to the not normal, or not OK, state the I/O Box will respond in accordance with the set ‘Fn’ response function.
Fn Function
If the remote contact state is not normal, or not OK, the I/O Box will indicate:
‘-’ NOK (not OK) – no other action
A
Alarm Condition
T
Trip Condition
S
Signal Connection
The state of the digital input, and any associated Alarm or Trip condition, is available on remote communications.
The system management unit will also indicate the Alarm or Trip condition (dependant on model and configuration).
The ‘Signal’ state will not activate any alarm condition but can be detected remotely and used for local or remote automation.
Virtual Relay Automation
DT Delay Time
If the digital input state changes to the not normal, or not OK, state the I/O Box will delay any ‘A’, ‘T’ or ‘S’ function response until the state has remained constantly in the not OK condition for the set delay time.
RF Reset Function
> 0.5 sec > 0.5 sec > 0.5 sec
1
2
0: An ‘A’ Alarm or ‘T’ Trip condition will automatically reset when the digital input returns to the normal, or OK, state.
1: An ‘A’ Alarm or ‘T’ Trip condition must be reset manually by pressing the I/O Box RESET button. The condition will remain on the display, regardless of input state, until a manual reset occurs.
Digital Inputs 1 to 8, menus D01 to D08 are identical.
Pulse Count Mode:
Fn
(Function) = P
The function (Fn) of digital Inputs 2 to 7 (D02 to D07) can be set to monitor a remote volt-free switching contact and count the number of times the contact changes state from open circuit to closed circuit and back to open circuit again; a pulse.
Installation:
ACM - Analog Conditioning Modules
Ut Display Units
The display units item selects the ‘text’ that will be shown in the user menu item display together with the analog input value.
Ut = mBr, BAR, PSI, kPa, mPa, dP, oC, oF, m3m,
m3h, cfm, m3, ft3, L/s, L/m, L/h, rpm, SPM, dBn, kW,
kWh, mV, V, kV, mA, A, %
There are 27 ‘unit texts’, any of which can be selected.
Alternatively select “- - -“ (dashes) for no units text display; the analog input value will be displayed with no units.
For example:
If the displayed value for analog input #1is tempeature in degrees celsius; select “oC” as the units text.
The number of detected pulses is displayed in the User menu and will represent an accumulative metered value dependant on the device providing the pulses.
The pulse count is stored in non-volatile memory and will continue to accumulate until reset to zero. A pulse count can be reset to zero using remote communications.
If the ‘manual pulse count reset’ option is enabled (menu S01) each individual digital input pulse count can be manually reset from the keypad:
Press and hold ENTER then press CANCEL. The pulse count will be cleared and start immediately again from zero.
MENUS A01 THROUGH A04  ANALOG INPUTS
The I/O Box is equipped with 4 adjustable analog inputs. An analog input can be used to monitor the signal of a remote compatible device and display an associating value.
AT Input Type
The input type is dependent on the ACM (analog conditioning module - hardware) fitted in the I/O Box for the analog input.
ACM’s are defined by number (1 to 8).
3:0mA
3:4mA
6:PT1
The ‘Input Type’ must be set to match the ACM
device fitted. It is not possible to adjust input signal types from this setting alone.
0-20mA
4-20mA
PT100 type temperature sensor
The display units ‘text’ has no influence on the analog input or used in any calculation or remote communications.
Vo Value Offset
This is the ‘value’ that must be displayed when the signal is at minimum.
Example #1:
ACM type 3
AT: 3:4mA
Sensor: 4-20mA, 0-232 PSI
The display must show 0 (zero) when the signal is
4.0mA; set ‘Vo’ to 0 (zero).
Example #2:
ACM type 2
AT: 2
Sensor: 1-5 VDC, 0-232 PSI
The display must show 0 (zero) when the signal is 1.0 VDC.
In this instance the analog input (AMC type) is 0-10VDC. A 0(zero)VDC signal will represent a minus pressure and a signal voltage greater than 5.0VDC will represent a pressure greater than 232 PSI. Calculate what the ‘value’ at 0.0VDC must be to achieve a display value of 0(zero) at 1.0VDC. This will depend on a required ‘value’ of 232 PSI at a signal of 5.0VDC.
To achieve a display ‘value’ of 0(zero)PSI at 1.0VDC, and 232 PSI at 5.0VDC, the ‘Vo’ offset must be set to:
232 PSI divided by (5 – 1)VDC = 58 PSI per 1.0VDC: therefore 0VDC must be (0 PSI – 58 PSI) = -58 PSI.
Set Vo to “–58”
It is not possible to directly implement decimal point values. In this instance set a value that is ‘10x’ the required display value then set ‘DF’ to display the value
13
14
at “divide by 10 and show to one decimal place” - see DF setting.
Vr Value Range
This is the ‘value’ that must be displayed when the signal is at maximum.
Example #1:
ACM type 3
AT: 3:4mA
Sensor: 4-20mA, 0-232 PSI
The display must show 232 when the signal is 20.0mA; set Vr to “232”
It is not possible to directly implement decimal point values. In this instance set a value that is ‘10x’ the required display value then set ‘DF’ to display the value at “divide by 10 and show to one decimal place” - see DF setting.
Example #2:
ACM type 2
AT: 2
Sensor: 1-5 VDC, 0-232 PSI
The display must show 232 when the signal is 5.0 VDC.
In this instance the analog input (AMC type) is 0-10VDC. A 5.0VDC signal is half the input range. Calculate what the ‘value’ at 5.0VDC must be to achieve a display value of 232 at 5.0VDC. This will depend on a required ‘value’ of 0(zero) at a signal of 1.0VDC.
To achieve a display ‘value’ of 232 PSI at 5.0VDC, and 0 PSI at 1.0VDC, the ‘Vr’ offset must be to:
232 PSI divided by (5 – 1)VDC = 58 PSI per 1.0VDC: therefore 10.0VDC must be 522 to achieve a value of 232 at 5.0VDC.
Set Vr to “522”
It is not possible to directly implement decimal point values. In this instance set a value that is ‘10x’ the required display value then set ‘DF’ to display the value at “divide by 10 and show to one decimal place” - see DF setting.
DF Display Function
The display function determines how the resulting ‘value’ (as determined by the ‘Vo’ and ‘Vr’ settings) is displayed in the User menu.
Standard DF Functions:
01: Show value directly
Value: 155 = Display: 155
02: Divide ‘value’ by 10
Display to one decimal place
Value: 155 = Display: 15.
03: Divide ‘value’ by 100
Display to one decimal places
Value: 155 = Display: 1.6
04: Divide ‘value’ by 1000
Display to one decimal place
Value: 155 = Display: 0.2
05: Divide ‘value’ by 100
Display to two decimal place
Value: 155 = Display: 1.55
06: Divide ‘value’ by 1000
Display to two decimal places
Value: 155 = Display: 0.16
For DF = 01 to 06 the value transmitted in remote communications is always the direct result of the set ‘Vo’ and ‘Vr’ settings; any display DF function is ignored.
Any set FH (Fault High Level Set Point) or FL (Fault Low Level Set Point) is referenced to the direct result of the set ‘Vo’ and ‘Vr’ settings; any display DF function is ignored.
Special DF Functions:
F07: oC to oF Conversion
‘Value’ is assumed to be degrees Celsius multiplied by ten (oC x 10). ‘Value’ is divided by 10, converted to degrees Fahrenheit, and displayed with no decimal places.
The value transmitted in remote communications is the original ‘value’.
F08: oC Dewpoint @ atmosphere to oC Dewpoint @
pressure conversion.
‘Value’ is assumed to be Dewpoint in degrees Celsius multiplied by ten (oC x 10) sampled at atmospheric pressure.
‘Value’ is referenced to the RP (reference pressure sensor input) and converted to Dewpoint @ pressure in exact accordance with the detected RP pressure value. An RP pressure sensor must be fitted and activated.
Resulting ‘value’ is transmitted in remote communication as oC x 10 (Dewpoint @ pressure x 10).
Display is resulting ‘value’ divided by 10 to one decimal place = oC (Dewpoint @ Pressure).
Any set FH (Fault High Level Set Point) or FL (Fault Low Level Set Point) is referenced to the resulting value (Dewpoint @ pressure x10).
F09: Differential Pressure (mBar)
The differential pressure is between the analog input and the RP reference pressure sensor.
‘Value’ is assumed to be pressure in milliBar (1.0bar = 1000milliBar).
‘Value’ is referenced to the RP (reference pressure sensor input). Resulting value is the difference between ‘value’ and RP expressed in milliBar; always positive.
Resulting ‘value’ is transmitted in remote communication as positive integer milliBar (differential between analog input and RP reference pressure).
Display is resulting ‘value’ in milliBar; always positive.
Any set FH (Fault High Level Set Point) or FL (Fault Low Level Set Point) is referenced to the resulting value in milliBar.
F10: SPMTM Bearing Monitoring
22
24
X06
21
23
A
B
‘Value’ is assumed to be ‘dBsv’ (0 to 100) from a compatible SPMTM bearing monitoring 4-20mA unit and sensor.
‘Value’ is processed in accordance with SPMTM bearing monitoring specification to provide resulting ‘dBn’ value.
dBn = dBsv – dBi
‘dBi’ is calculated in accordance with SPMTM specification from ‘shaft speed (rpm)’ and shaft diameter (mm) entered in menu F10.
dBi = 20 * (LOG(rpm) + 0.6*LOG(shaft diameter in mm) – LOG(2150))
R1 = shaft speed: analog input 1
D1 = shaft diameter: analog input 1
A1 = ‘dBi’ value (view only)
to
R4 = shaft speed: analog input 4
D4 = shaft diameter: analog input 4
A4 = ‘dBi’ value (view only)
The calculated ‘dBi’ value can be seen in the F10 bearing monitoring menu (items A1 - analog input #1, to A4 - analog input #4).
Any set FH (Fault High Level Set Point) or FL (Fault Low Level Set Point) is referenced to the resulting value (dBn).
TM
SPM
guidelines for dBn Alarm settings:
OK: <20dBn
Warning 20 to 34dBn
Alarm 35dBn+
Due to the nature of rotary screw or vane compression elements a serviceable bearing may exhibit a higher than expected base dBsv level. In this instance the trend over time of dBsv should be monitored to establish a true dBi level for the bearing.
Alternatively consult the air compressor supplier/ manufacturer for SPMTM bearing monitoring base level details and appropriate Warning/Alarm dBn levels.
FH Fault High Level Set Point
If ‘Value’ exceeds this setting the ‘Fault Function’ (Fn) is triggered.
The setting must be referenced to the same value, or resulting value, units as the set ‘Vo’ and ‘Vr’ settings.
For example:
If the analog input is Temperature the ‘Value’ will be oC x 10. If a fault condition needs to be triggered when temperature exceeds 85oC the FH level should be set to 850 (850 / 10 = 85 oC).
If not required set to, or above, the ‘Vr’ setting.
FL Fault Low Level Set Point
If ‘Value’ decreases below this setting the ‘Fault Function’ (Fn) is triggered.
The setting must be referenced to the same value, or
resulting value, units as the set ‘Vo’ and ‘Vr’ settings.
For example:
If the analog input is Temperature the ‘Value’ will be oC x 10. If a fault condition needs to be triggered when temperature reduces below -10oC (minus 10oC) the FLlevel should be set to -100 (-100 / 10 = -10 oC).
If not required set to, or below, the ‘Vr’ setting.
Fn Fault Function
If ‘Value’ reduces below the set ‘FL’ level or increases above the set ‘FH’ level the fault function is triggered:
“-“ no action
A Alarm
T Trip
S Signal
All analog input Alarm or Trip fault conditions, are available on remote communications.
The system management unit will also indicate the Alarm or Trip condition (dependent on model and configuration).
The ‘Signal’ state will not activate any alarm condition but can be detected remotely and used for local or remote automation.
FI Fault Inhibit Enable
If the analog input is set with an Alarm (A) or Trip (T) function the alarm condition can be inhibited by activating digital input ‘FI’ when the FI setting is ‘1’.
0: ‘A’ or ‘T’ condition always active regardless of ‘FI’ digital input state.
1:
‘A’ or ‘T’ condition inhibited if digital input ‘FI’ is
active (closed circuit).
Digital Input ‘FI’
A) not active; open circuit
B) active; closed circuit
Dt Delay Time
If the set ‘FH’ or ‘FL’ fault levels are exceeded the I/O Box will delay any ‘A’, ‘T’ or ‘S’ function response until the condition has remained constantly in the fault condition for the set delay time.
RF Reset Function
0: An ‘A’ Alarm or ‘T’ Trip condition will automatically
reset when the ‘value’ returns to normal, or OK, level.
1: An ‘A’ Alarm or ‘T’ Trip condition must be reset manually by pressing the I/O Box RESET button. The condition will remain on the display, regardless of the ‘value’, until a manual reset occurs.
Analog Inputs 1 to 4, menus A01 to A04 are identical.
15
16
DIAGNOSTICS
The I/O Box controller is equipped with comprehensive diagnostic functions. Each input can be examined individually and each output can be manually activated or manipulated individually.
I/O Box Controller Diagnostics:
Menu P06 Box Controller Diagnostics
D1
Digital Input 1
D2 Digital Input 2 ON
D3 Digital Input 3
D4
Digital Input 4
D5 Digital Input 5
D6 Digital Input 6
D7 Digital Input 7
D8 Digital Input 8
R1 Relay Output 1
R2 Relay Output 2 OFF
R3 Relay Output 3
R4 Relay Output 4 ON
R5 Relay Output 5
R6 Relay Output 6
A1 Analog Input 1 bar <> mA
A2 Analog Input 2
A3 Analog Input 3
state <> V
state <> V
Relay Outputs:
Each relay output can be energized and de-energized manually by selecting the item. Use PLUS and MINUS to adjust ‘on’ (1) or ‘off (0) and then ENTER.
OFF
Analog Inputs:
The item will alternate between the detected value and the electrical measurement on the input terminals. An independent measuring device can be used to check the displayed electrical measurement.
A1: Reference Pressure, 4-20mA
A2: Digital Input #1, voltage
A3: Fault Inhibit Digital Input, voltage
Analog inputs 2 and 3 are equipped with Digital ACM modules designed to function as standard specification digital inputs.
D02 Diagnostics – XPM-Ai4 Module
A1 Analog Input 1 as ACM
A2 Analog Input 2 as ACM
A3 Analog Input 3 as ACM
A4 Analog Input 4 as ACM
Configurable Analog Inputs A01 to A04:
The four configurable analog inputs are located in the XPM-Ai4 module.
The item will alternate between the detected value and the electrical measurement on the input terminals. An independent measuring device can be used to check the displayed electrical measurement.
The detected value and the electrical measurement for each input will be dependant on the ACM type fitted.
ACM (Analog Conditioning Modules)
a
b
c
d
f
g
h
e
SECTION 7  OPERATION
6.1 USER INTERFACE
a) Start b) Reset c) Stop d) Menu e) Enter f) Escape g) Up (Plus) h) Down (Minus)
6.2 DISPLAY
Flashing - No Communications
Input Alarm Condition
Input High Level Alarm Condition
Input Alarm or High Level Alarm conditions do not stop or inhibit I/O Box operation. Examine the User menu item list to identify the source of an Alarm indication.
6.4 INDICATORS
Run Indicator (Green LED)
OFF I/O Box Shutdown Fault
ON I/O Box Active
Slow Flash I/O Box Network Fault
Fault Indicator (Red LED)
OFF - No fault
Slow Flash:
RP Sensor fault (display “_ _ _ _”)
Flash Flash:
I/O Box Shutdown Fault
6.5 OPERATION
The I/O Box is always active and cannot be stopped.
The upper display will continuously show the assigned I/O Auxiliary Box number.
If the ‘Reference Pressure’ function is active the upper display item will continuously show the detected pressure instead of the I/O Auxiliary Box number.
The lower display will show the default, or selected, user menu item.
User menu items show the value being detected on analog input(s) and the state or condition of digital input(s) and relay outputs.
After a period of no keypad activity the User menu item will automatically default to show the set ‘default item’ (adjustable in menu S01).
Digital or analog inputs that have not been activated will not be shown in the User menu item list.
User Menu Items:
A01-A04 Analog Inputs 1 to 4
D01-D08 Digital Inputs 1 to 8
R01-R06
Relay Outputs 1 to 6
The Start and Stop buttons (if fitted) DO NOT affect the operation of the I/O Box.
The start and stop buttons do have uses in Virtual Relay Automation, however. Please see the virtual relay automation manual for details.
6.6 DIGITAL INPUT STATUS INDICATIONS
When activated a ‘Digital Input’ will show the input status and condition in the User menu item list.
0 = remote contact is open circuit
1 = remote contact is closed circuit
Dependent on the input setup, the display will also show:
OK OK Condition
NOT Not OK Condition
A Alarm State Condition
T
Trip State Condition
S Signal State Condition
6.3 STATUS SYMBOLS
I/O Box Status (always displayed):
Power Failure Auto Restart (always on)
Network communications established
Digital Inputs: Configuration
Pulse Count Mode:
If the digital input is setup in pulse count mode, the User menu item will show the ‘pulse count’ since last reset.
17
18
The number of detected pulses will represent an
1sec
accumulative metered value dependant on the device providing the pulses.
For example: 1627384 may represent ft3 of air produced or kWh of power consumed.
If the ‘manual pulse count reset’ option is enabled each individual digital input pulse count can be reset from the keypad:
Press and hold ENTER then press CANCEL. The pulse count will be cleared and start immediately again from zero.
6.7 ANALOG INPUT DISPLAY
When activated, an ‘Analog Input’ will show a value in the User menu item list. The value displayed will be dependant on analog input setup and configuration.
6.10 SHUTDOWN FAULTS
The Fault LED will ‘fast flash’ to indicate a Shutdown condition. A Shutdown condition will stop normal operation of the I/O Box. All Shutdown conditions must be manually reset.
Fault Codes:
Each individual fault has a unique numeric code.
E0010
The wire link between terminals ‘+C’ and ‘C1’ of the unit’s controller is open circuit. These terminals are permanently connected together on the IO Box Terminal PCB: this error will never occur in normal operational circumstances.
Emergency Stop
Analog inputs can be set to indicate an Alarm, High Level Alarm or Signal condition.
If one of these conditions occurs the analog input Usermenu item will also display:
A Alarm Condition
T High Level Alarm Condition
S Signal Condition
Analog Inputs: Configuration
Relay Output Display
When activated, a ‘Relay Output’ will show the output status of the contacts in the User menu item list.
Relay Off: contacts open circuit
Relay On: contacts closed circuit
The function and activation of each relay output is dependant on setup and configuration.
Virtual Relay Automation
6.8 POWER FAILURE AUTORESTART
The I/O Box will always automatically start when power is re-applied after a power supply disruption or failure.
6.9 I/O BOX FAULT
If an RP pressure sensor fault is detected (if the RP pressure sensor option is enabled) the I/O Box will display “- - - -“ dashes on the upper display and indicate the condition with an Alarm symbol. The I/O Box will continue to operate normally without interruption.
E0506
Short circuit condition has been detected on the XPMAi4 module (Analog inputs 1 to 4).
E0821
Short Circuit condition detected on the main controller unit (digital inputs).
E0836
Internal failure or excessively high external electrical interference detected.
The main timing circuit (processor clock) has been disrupted and the processor is running on an ‘internal to chip’ back-up clock.
The controller’s main power supply must be removed and re-applied to reset this condition.
E0840
Data communications with the XPM-Ai4 module (analog inputs 1 to 4) have been disrupted or lost.
E5000
The unit’s controller has detected disruption to the internal operational memory storage (RAM). The integrity of the RAM memory contents are suspect; the controller must be reset to clear and re-map the memory. Renew the controller if this fault condition persists.
The controller’s main power supply must be removed and re-applied to reset this condition.
E5001
The unit’s controller has detected disruption to the internal permanent application memory storage (FLASH). The integrity of the FLASH memory contents is suspect. Reload the main application software in the first instance; renew the controller if the condition persists.
The controller’s main power supply must be removed and reapplied to reset this condition.
XPM-Ai4 Short Circuit
Short Circuit
PLL Unlock
XPM-Ai4 Communications
Internal Memory Map Error
Internal Memory Failure
MANAGEMENT UNIT FAULT CODES
The X8I unit can be set to monitor an IO Box. In this condition any ‘A’ Alarm or ‘T’ Trip indication will also be displayed by the X8I.
The X8I will display an IO Box fault code that describes the IO Box system number and the input (digital or analog) identification. All inputs on all system IO Box(s) will have a unique alarm code in the format:
B’nn’ . ’XX’
‘nn’ = IO Box number (01 or 2)
‘XX’ = Input identification Code
The alarm code will also differ dependent on the alarm type for a particular input (Alarm ‘A’ or Trip ‘T’).
Digital; Input Identification Codes:
Input No. A T
1 01 17
2 02 18
3 03 19
4 04 20
5 05 21
6 06 22
7 07 23
8 08 24
Analog; Input Identification Codes:
Input No. A T
1 49 57
2 50 58
3 51 59
4 52 60
Network Communications Error:
B’nn’. - - -
(IO Box identification followed by dashes)
This message indicates an IR485 network communication disruption or loss. The management system is no longer receiving data from the IO Box.
19
20
24mm
238mm
24mm
188mm
8mm Ø
236mm
286mm
SECTION 8  PARTS LIST
20mm
5mm
IEC
X
P
M
-
T
A
C2
4
XPM-PSU24
XPM-Ai4
6
4
3
2
1
5
Item Part No. Description
- 42659409 IO Box Kit
- 23242209 IO Box Unit
- 80444086 Manual, User CD
1 42659482 Controller, IO
2 42659284 XPM-PSU24
3 42659326 XPM-Ai4
4 39265913 Unit, XPM-TAC24
5 39265905 PCB, Terminal
6 38036703
Qty Part No. Description
10 39265962 IEC Fuse T1.0A
10 39265970 IEC Fuse T1.6A
10 39265988 IEC Fuse T3.15A
Gland, Set - Pg13.5
SECTION 9  TECHNICAL DATA
Dimensions 291mm x 241mm x 152mm
11.45” x 9.45” x 6.0”
Weight 6.5kg (14Ib)
Mounting wall, 4 x screw fixings
Enclosure IP54, NEMA 12
Supply 230Vac +/- 10%
115Vac +/- 10%
Power 50VA
Temperature 0°C to 46°C (32°F to 115°F)
Humidity 95% RH non-condensing
INSTALLATION AND MOUNTING DIMENSIONS
SECTION 10  WIRING DIAGRAM
21
22
XPMTAC24
230V
115V
24Vac/1 isolated
24Vac/2 earthed
EE
L
N
N L E
BLUE
BROWN
RED
GREEN
VIOLET
WHITE
ORANGE
BLACK
FH1
FH2FH3
FH4
FH5
1
VOLTAGE SELECT
2 3 4
X04
2 1 2
X03
X02
X01
T3.15A
T1.6A
T1.6A
T1.0A
T1.0A
1 2 3 4
115V +-10%
230V +-10%
1 2 3 4
IEC
5x20mm
Customer
Contact
Phone
Installation/Site
Ser No.
Software
Commission Date
Commission Engineer
Customer Ref:
Internal Ref:
S01 Ad Box Number (Network Address) S01 PD Reference Pressure Detect Enable
isp/ rabnoitarbilaC tesffO PRoP10S
isp/ rabnoitarbilaC egnaR PRrP10S S01 P> RP Pressure Display Units S01 ID Default User Menu Item S01 RP Pulse Counter Reset Enable
1 2 3
4
5
6 7 8 9
10
11
12
bar psi kPa
0 1:on
0 1:on
d01 ST Normal State d01 Fn Function d01 DT Delay Time sec d01 RF Reset Function
“-“ A T
NO NC
0 1:on
S
d02 ST Normal State d02 Fn Function d02 DT Delay Time sec d02 RF Reset Function
“-“ A T
NO NC
0 1:on
S P
d03 ST Normal State d03 Fn Function d03 DT Delay Time sec d03 RF Reset Function
“-“ A T
NO NC
0 1:on
S P
d04 ST Normal State d04 Fn Function d04 DT Delay Time sec d04 RF Reset Function
“-“ A T
NO NC
0 1:on
S P
d05 ST Normal State d05 Fn Function d05 DT Delay Time sec d05 RF Reset Function
“-“ A T
NO NC
0 1:on
S P
d06 ST Normal State d06 Fn Function d06 DT Delay Time sec d06 RF Reset Function
“-“ A T
NO NC
0 1:on
S P
d07 ST Normal State d07 Fn Function d07 DT Delay Time sec d07 RF Reset Function
“-“ A T
NO NC
0 1:on
S P
d08 ST Normal State d08 Fn Function d08 DT Delay Time sec d08 RF Reset Function
“-“ A T
NO NC
0 1:on
S
I/O Commissioning Form
23
A01 AT Input Type
A01 Ut Display Units A01 Vo Value Offset Calibration A01 Vr Value Range Calibration A01 DF Display Function A01 FH Fault High Level Set Point A01 FL Fault Low Level Set Point A01 Fn Fault Function A01 FI Fault Inhibit Function Enable
cesemiT yaleDtD10A
A01 RT Reset Function
“-“
1
0 1:on
0 1:on
“-“ A T S
2 3 4 5 6 F7 F8 F9 F10
1:no 2:10V 3:0mA
7
6 8
1:nc
3:4mA
4:0mA 4:4mA
5:KTY 5:RTD
A02 AT Input Type
A02 Ut Display Units A02 Vo Value Offset Calibration A02 Vr Value Range Calibration A02 DF Display Function A02 FH Fault High Level Set Point A02 FL Fault Low Level Set Point A02 Fn Fault Function A02 FI Fault Inhibit Function Enable
cesemiT yaleDtD20A
A02 RT Reset Function
“-“
1
0 1:on
0 1:on
“-“ A T S
2 3 4 5 6 F7 F8 F9 F10
1:no 2:10V 3:0mA
7
6 8
1:nc
3:4mA
4:0mA 4:4mA
5:KTY 5:RTD
A03 AT Input Type
A03 Ut Display Units A03 Vo Value Offset Calibration A03 Vr Value Range Calibration A03 DF Display Function A03 FH Fault High Level Set Point A03 FL Fault Low Level Set Point A03 Fn Fault Function A03 FI Fault Inhibit Function Enable
cesemiT yaleDtD30A
A03 RT Reset Function
“-“
1
0 1:on
0 1:on
“-“ A T S
2 3 4 5 6 F7 F8 F9 F10
1:no 2:10V 3:0mA
7
6 8
1:nc
3:4mA
4:0mA 4:4mA
5:KTY 5:RTD
A04 AT Input Type
A04 Ut Display Units A04 Vo Value Offset Calibration A04 Vr Value Range Calibration A04 DF Display Function A04 FH Fault High Level Set Point A04 FL Fault Low Level Set Point A04 Fn Fault Function A04 FI Fault Inhibit Function Enable
cesemiT yaleDtD40A
A04 RT Reset Function
“-“
1
0 1:on
0 1:on
“-“ A T S
2 3 4 5 6 F7 F8 F9 F10
1:no 2:10V 3:0mA
7
6 8
1:nc
3:4mA
4:0mA 4:4mA
5:KTY 5:RTD
ACM
ACM
ACM
ACM
mpr1# deepS tfahS1r01F
mm1# retemaiD tfahS1d01F
mpr2# deepS tfahS2r01F
mm2# retemaiD tfahS2d01F
mpr3# deepS tfahS3r01F
mm3# retemaiD tfahS3d01F
mpr4# deepS tfahS4r01F
mm4# retemaiD tfahS4d01F
SPM Bearing Monitoring
24
LOOK WHAT INGERSOLL RAND CAN DO FOR YOU!
Efficient Field Service
We maintain a highly trained staff of technicians to service your equipment for preventive maintenance, or to assist you should emergencies ever occur.
Complete Repair Service
Our trained technicians will repair or overhaul your equipment to factory specifications, using only genuine Ingersoll Rand parts.
Special Engineering Service
We can help you identify and solve your problems by evaluating your needs and recommending theproper equipment to give your maximum efficiency.
Spare Parts
By stocking genuine Ingersoll Rand spare parts, we can help you avoid costly delays or substituting inferior parts. Using genuine Ingersoll Rand parts on you Ingersoll Rand equipment will help to keep even older equipment running in good-as-new
Complete Stock of Equipment
We carry a complete line of Ingersoll Rand equipment and accessories designed to meet any compressed air application. We are backed by Ingersoll Rand’s prompt factory shipment to ensure you on-time delivery.
condition.
A SUBSTITUTE IS NOT A REPLACEMENT!
Ensure you get peak performance and longevity out of your Ingersoll Rand product by insisting on genuine Ingersoll Rand replacement parts and maintenance kits. Not only are the replacement parts made to precise dimensions and OEM­specified metallurgy, but each part is backed by the Ingersoll Rand warranty. Your local Customer Center, Distributor, or direct Ingersoll Rand salesperson will work with your to ensure you get the parts you need to do the job right. Equip your machines with only the best Ingersoll Rand genuine parts.
NOTE: THE USE OF REPAIR PARTS OTHER THAN THOSE INCLUDED WITHIN THE INGERSOLL RAND COMPANY APPROVED PARTS LIST MAY CREATE UNSAFE CONDITIONS OR MECHANICAL FAILURES OVER WHICH INGERSOLL RAND COMPANY HAS NO CONTROL. INGERSOLL RAND COMPANY SHALL BEAR NO RESPONSIBILITY FOR EQUIPMENT ON WHICH NON-APPROVED REPAIR PARTS ARE INSTALLED.
The manufacturer reserves the right to make changes or add improvements without notice and without incurring any obligation to make such changes to products previously sold.
Loading...