EN 55024; EN 50091-2 consisting of IEC 61000-4-2 thru IEC
61000-4-6 ; IEC 61000-4-11
Surge Suppression
Conforms to IEEE 587B and ANSI C62.41
Unit Dimensions (LxWxH)
21.8x 17.2x 1.69 in (554 x 438 x 43 mm)
Shipping Dimensions
30.71x 22.8 x6.1 in (780 x 580 x 155 mm)
Unit Weight
39.06 lb (19.72 kg)
Shipping Weight
54.45 lb (24.7 kg)
10% / +6% of the selected nominal voltage. The regulation is accomplished by
e
e to regulate
Transition set point voltages are subject to a hardware tolerances of +/-3% of the set point value.
R5000 3U UPS
BTU Break Down
BTU On Line
478 BT/hr
BTU On Battery
1041 BTU/hr
Battery Type
12V 27W
Electrical Input
Voltage Range
160-253V at 200/208V nominal; 176-253V at 220, 230, and
240V nominal
Frequency
50/60 Hz
Online Efficiency
94%
REPO
Remote Emergency Power-Off disables AC power to load
Online Regulation
-10% to +6% of nominal voltage
Electrical Output
On battery Regulation
±5% of nominal voltage
Voltage Wave Form
Sine wave
Connections
See Model Matrix; divided into 2 Load Segments
Output Protection
Re-settable circuit protectors
Type
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Battery
Extended Batteries
Up to four ERMs supported
Backup Time
See Backup Times Chart
-1; IEC 60950-1; EN60950-1;EN 62040-1; EN 61000-3-
* The R1500 G4 UPS regulates the output voltage at bucking or boosting the input voltage. The voltage regulation operation is governed by the unit's input voltage spec of +/-20%. The
unit will regulate at -10% / +6% while within the limits set by the input spec. The unit will go to battery operation upon exceeding th
limits set by the input spec. The buck and boost voltage regulation operation, or AVR (Automatic Voltage Regulation), is
accomplished by adjusting output transformer tap selections via electromechanical relays. The transformer tap selection is
controlled via digital transition voltage set point values programmed in the unit's firmware. These programmed values are without
tolerance.
The unit will monitor the input voltage and accept a range of +/-3% of the selected nominal voltage as the target voltag
at -10% / +6%. For example, a unit configured to 120V nominal voltage will regulate at -10% / +6% for any voltage measured
between 116.4V and 123.6V. The digital transition voltage set point values will adjust accordingly to regulate to -10% / +6% of the
measured input voltage.
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
Page 14
Recharge Time
<3 hours to 80% usable capacity; <48 hours for complete recharge
Battery String Voltage
216V
Battery Type
12V 27W
Battery Quantity
18
Communications
LED Indicators
LED and switch membrane integrated into the front panel with fourbutton control (three buttons for UPS power control and one button
under the front bezel for configuration).
Operating Temperature
50° to 104° F (10° to 40° C )
Storage Temperature
32° to 77° F (0° to 25° C )
Transit Temperature
-13° to 131° F (-25° to 55° C)
Unit Dimensions (HxWxD)
5 5 in (12.7 cm) x 17.2 in (43.7 cm) x 29.3 in (74.4 cm)
Shipping Dimensions
14.4 in ( 36.58 cm) x 23.6 in ( 60 cm) x 38.78 in ( 98.5 cm)
Unit Weight
126 lbs (57kg)
Shipping Weight
192 lbs ( 87 kg)
R7000 4U UPS
BTU Break Down
BTU On Line
581 BT/hr
BTU On Battery
1501 BTU/hr
Battery Type
12V 45W
Electrical Input
Voltage Range
160-253V at 200/208V nominal
Frequency
50/60 Hz
Online Efficiency
95%
REPO
Remote Emergency Power-Off disables AC power to load
Online Regulation
-10% to +6% of nominal voltage
Electrical Output
On battery Regulation
±5% of nominal voltage
Voltage Wave Form
Sine wave
Connections
See Model Matrix; divided into 2 Load Segments
Output Protection
Re-settable circuit protectors
Type
Maintenance-free, sealed, valve-regulated lead acid (VRLA)
Battery
Extended Batteries
Up to four ERMs supported
Backup Time
See Backup Times Chart
Recharge Time
<3 hours to 80% usable capacity; <48 hours for complete recharge
Battery String Voltage
216V
Battery Type
12V 45W
Battery Quantity
18
Maximum wattage based on
voltage input
200-240V: 7200VA/7200W
Communications
Serial Ports
Standard DB-9 and USB ports (ships with communication cables)
Option Cards
HPE UPS Network Module
LED Indicators
LED and switch membrane integrated into the front panel with four-
for UPS power control and one button
under the front bezel for configuration).
Environmental and Safety
Operating Temperature
50° to 104° F (10° to 40° C )
Storage Temperature
32° to 77° F (0° to 25° C )
Environmental and Safety
button control (three buttons
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Rack/Tower UPS specifications
Page 15
Transit Temperature
-13° to 131° F (-25° to 55° C)
Operating Humidity
20% to 80% (non-condensing)
Storage Humidity
5% to 95%
Operating Altitude
Up to 6,562 ft (2000 m) above sea level
Transit Altitude
49,212 ft (15,000 m) above sea level
Audible Noise
<46db in normal operation(at 1m from surface of unit)
6.75 in (17.1 cm) x 17.2 in (43.7 cm) x 28.9 in (73.4 cm)
Shipping Dimensions
(H x L x W)
16.10 in (40.9cm) x 23.6 in. (59.9cm) x 38.8 (98.6cm)
Unit Weight
165 lbs/75 kg
Shipping Weight
210 lbs/100 kg
QuickSpecs
HPE Line Interactive Single Phase UPS
Related Options
Page 16
UPS Network Module
The HPE UPS Network Module enables you to monitor and manage power environments through
comprehensive control of
UPS configuration or provide additional power protection with support for dual red
configuration for no
management control and flexible monitoring.
The management module can be configured to send alert traps to
othe
enables you to monitor and manage UPSs through the network. To facilitate day
tasks, the embedded management software provides detailed system logs.
The
to the network. Configuration & Management of the UPS from anywhere and at anytime via a standard
web browser.
NOTE:
see: http://www.hp.com/go/hpunm.
Extended Runtime
Module (ERM)
Extended Runtime Modules increase the available runtime for the larger rack mounted UPS units to
allow customers to ensure all of their
failure.
2U R/T UPS ERM
Shipping Kit
HPE 2U Rack/Tower UPS Shipping Kit
L4Q11A
NOTE: The optional 2U shipping kit consists of heavy duty rails, front and back
CTO brackets and required mounting hardware for attaching the UPS or ERM to
the rack. This kit is an option that is required if the UPS and or ERM are going to
be mounted into a rac
required per unit, whether UPS or ERM.
Extended Runtime
Modules (ERM)
HPE R/T2200 G4 Extended Runtime Module
HPE
HPE
NOTE:
J2R09A
J2R10A
AF455A
HPE R5KVA and R7KVA 3U Extended Runtime Module
AF464A
NOTE: #0D1 will appear after the part number on the sales order if HPE factory
integration is indicated.
UPS Management
HPE UPS Network Module Mini-slot Kit
AF465A
HPE UPSs. The HPE UPS Management Module can support either a single
undant UPS
-single-point-of-failure. The additional serial ports will provide greater power
HPE Systems Insight Manager and
r SNMP management programs or used as a standalone management system. This flexibility
-to-day maintenance
HPE UPS Network Module provides remote management of a UPS by connecting the UPS directly
For more information on the UPS Network Module please
applications can be gracefully shutdown in the event of a power
When you need it, use outstanding HPE support services for your whole data center environment. With
HPE
service level and coverage period as your
warranty, with the first year including parts and labor. Also, standard on all
exclusive 30
from
under the warranty. This warranty is offered worldwide.
NOTE: $250,000 Computer/Load Protection Guarantee is also provided (applicable in North America
only).
The
standard on all
advantage of a
the battery before it actually fails. This
warranty is offered worldwide. Specifically, the Battery Pre-Failure Warning ensures that when customers
receive notification from
replaced
NOTE: $250,000 Computer/Load Protection Guarantee is also provided in North America, in addition
to the
Warranty Upgrade Options
• Duration - Select duration of coverage for a minimum period of 1 year or multiple years
Service and Support
HPE Technology Services
HPE
infrastructure problems. We help keep your business running, boost availability and avoid downtime.
Protect your business beyond warranty with
When you buy
HPE
designed to meet your IT and business need.
Insight Remote Support
Delivers secure remote monitoring and support for Hewlett Packard Enterprise servers and storage,
24x7 at no additional cost. Available as part of HPE Warranty, Care Pack and Service Contract offers.
Parts and materials
Hewlett Packard Enterprise will provide HPE-supported replacement parts and materials necessary to
maintain the covered hardware product in operating condition, including parts and materials for
available and recommended engineering improvements. Supplies and consumable
provided as part of this service; standard warranty terms and conditions apply. Parts and components
that have exceeded their maximum supported lifetime and/or the maximum usage limitations as set
forth in the manufacturer's operating man
repaired or replaced as part of this service.
Coverage
For ProLiant servers and storage systems, this service covers HPE-branded hardware options qualified
for the server, purchased at the
monitors up to 22" and tower UPS products; these items will be covered at the same service level and for
the same coverage period as the server unless the maximum supported lifetime an
usage limitation has been exceeded. Coverage of the UPS battery is not included; standard warranty
terms and conditions apply.
The defective media retention service feature option applies only to Disk or eligible SSD/Flash Drives
replaced
due to malfunction. It does not apply to any exchange of Disk or SSD/Flash Drives that
have not failed. SSD/Flash Drives that are specified by
exceeded maximum supported lifetime and/or the maximum usage limit as set forth in the
Care Pack Services, have the security of knowing that your HPE UPS will be covered at the same
HPE server. HPE UPSs are backed by a 3-year limited
HPE UPS units is our
-day Battery Pre-Failure Warranty, which ensures that when customers receive notification
HPE Power Manager Software that the battery may fail, the battery is replaced free of charge
HPE UPS is covered by a three year warranty, with the first year including parts and labor. Also,
HPE UPS units, is our exclusive Battery Pre-Failure Warning, which extends the
HPE three-year, limited warranty by applying it to
HPE Power Management Software that the battery may fail, the battery is
free of charge under the warranty.
HPE three year, limited warranty.
:
• Response - Upgrade on-site response from next business day to same day 4-hours
• Coverage - Extend hours of coverage from 5 days x 9 hours to 7 days x 24 hours
Technology Services offers you consultants and support experts to solve your most complex
HPE Care Pack Services
HPE Options, it's also a good time to think about what level of service you may need.
Care Pack services provide total care and support expertise with committed response choices
ual or the technical product data sheet will not be provided,
same time or afterward, internal to the enclosure, as well as external
by HPE
HPE as consumable parts and/or that have
parts will not be
d/or the maximum
QuickSpecs
HPE Line Interactive Single Phase UPS
Warranty and Care Pack
Page 18
manufacturer's operating manual or the technical data sheet are not eligible for the defective media
retention service feature option.
For more information
To learn more on services for HPE ESSN Options, please contact your Hewlett Packard Enterprise sales
representative or
visit: http://www.hp.com/services/proliant
http://www.hp.com/services/bladesystem
Recommended HPE Care Pack Services for optimal satisfaction with your HPE product
Recommended Services
3-Year HPE 24x7 4 hour Response, Hardware Support Onsite Service
Provides you with rapid remote support and if required
representative who will arrive on site any time and day of the year to begin hardware maintenance
service within 4 hours of the service request being logged.
HPE ProLiant Server Hardware Installation
Provides for the basic hardware installation of
devices and networking options to assist you in bringing your new hardware into operation in a timely
and professional manner
3-Year HPE 6 hour Hardware Support Onsite Call-to-Repair Service
Provides an IT manager with a team of support specialists who will quickly begin troubleshooting the
system to help return the hardware to operating condition within 6 hours of the initial service request to
the HPE Global Solution Center
HPE Proactive Select Service
Provides a flexible way to purchase
Proactive Select Service Credits when you purchase your hardware and then use the credits over the
next 12 months.
HPE Care Pack Services
HPE Install Universal Power Supply 3KVA to Below 6KVA Service
U4693E
HPE Install Universal Power Supply Less Than 3KVA Service
U4690E
Hewlett Packard Enterprise Authorized Channel Partner. Or
HPE best-in-class consultancy and technical services. You can buy
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Model Matrix
Page 19
HPE T750 G4 UPS Model
Part Number
Operating Voltage
Settings
Power Out (VA/Watts)
Input Connection
Output Connection
J2P85A
(North America/Japan
110V to 120V
100V- Japan
750VA/525W
750VA/500W
Attached NEMA 5-15
16AWG
6 – NEMA 5-15
100V- Japan
750VA/500W
J2P88A
International model
220V/230V/240V
750VA/525W
C14 Inlet ( For
specific power cord
6 – IEC C13 receptacles
HPE T1000 G4 UPS Model
Part Number
Operating Voltage
Settings
Power Out (VA/Watts)
Input Connection
Output Connection
J2P86A NA/JP
100V (Japan) to 110V
1000VA/680W
Attached Nema 5-15
16AWG
8 – Nema 5-15
J2P89A INTL
220V/230V/240V
1000VA/700W
C14 Inlet ( For
specific power cord
8 – IEC C13 receptacles
HPE T1500 G4 UPS Model
Part Number
Operating Voltage
Settings
Power Out (VA/Watts)
Input Connection
Output Connection
J2P87A NA/JP
100V Japan
120V
1200VA/980W
1440VA/1080W
Attached Nema 5-15
14AWG
8 – Nema 5-15
J2P90A INTL
220V/230V/240V
1500VA/1050W
C14 Inlet ( For
specific power cord
8 – IEC C13 receptacles
HPE R1500 G4 UPS Models
Part Number
Operating Voltage
Settings
Power Out
(VA/Watts)
Input Connection
Output Connection
Low-Voltage Models
J2Q99A NA
120V to 125V
1440/1100
NEMA 5-15P
5- Nema 5-15R
100V
1200/900
receptacles
J2R05A JP/TWN
100V
1200/900
NEMA 5-15P
5- Nema 5-15R
120V to 125V
1440/1100
Nema 5-15P With
Taiwan approval
5-Nema 5-15R
High Voltage Model
J2R03A INTL
220V/230V/240V
1550/1100
C14 inlet (for
specific power cord
6- IEC 320-C13
200V to 208V
1395/990
NOTE: Voltage is user selectable via LCD Front Display Panel
HPE R/T2200 G4 UPS
Part Number
Operating Voltage
Settings
Power Out
(VA/Watts)
Input Connection
Output Connection
J2R00A NA/JP
120V to 125V
1920/1920
Nema 5-20P 20A 3m
8 –Nema 5-20
100V
1500/1400
HPE R/T3000 G4 UPS Models
Part Number
Operating Voltage
Settings
Power Out
(VA/Watts)
Input Connection
Output Connection
)
120V
1000VA/700W
Plug type power cord,
detachable country
Plug type power cord,
receptacles
receptacles
detachable country
110V
1325VA/994W
Plug type power cord,
receptacles
detachable country
detachable country
cord
receptacles
Receptacles
QuickSpecs
HPE Line Interactive Single Phase UPS
HPE Model Matrix
Page 20
J2R01A LV NA/JP
120V1 to 125V
2880/2700
L5-30P, 2.4m cord
LS1-LS42: 6x NEMA 5-20
receptacle
100V
1500/1400
J2R02A HV NA/JP
208V1 to 240V
3000/2700
L6-20P, 2.4m cord
LS1-LS32:8xIEC C13
outlet)
200V
2490/2241
J2R04A HV INTL
208V to 240V (230V
1
)
3000/
2700
Detachable IEC C-20
cord
LS1-LS32: 8x IEC C13
200V
2490/2241
1
Factory default setting.
2
3
LS5 = Load Segment 5
HPE R5000 and R7000 UPS Models
Part Number
Operating Voltage
Settings
Power Out
(VA/Watts)
Input Connection
Output Connection
AF462A 200/208*
7200VA/7200W
Hubble CS8265C, 3m
LS1: 15A CB - 3 x C19 +
AF460A
200/208*, 220,
5000/4500
L6-30P, 3m cord
LS1: 15A CB - 2 x C19 +
1 x L6-30R
HPE R/T2200 G4 UPS
Part Number
Operating Voltage
Settings
Power Out
(VA/Watts)
Input Connection
Output Connection
J2R00A NA/JP
120V to 125V
1920/1920
Nema 5-20P 20A 3m
8 –Nema 5-20
100V
1500/1400
HPE R/T3000 G4 UPS Models
Part Number
Operating Voltage
Settings
Power Out
(VA/Watts)
Input Connection
Output Connection
J2R01A LV NA/JP
120V1 to 125V
2880/2700
L5-30P, 2.4m cord
LS1-LS42: 6x NEMA 5-20
receptacle
100V
1500/1400
J2R02A HV NA/JP
208V1 to 240V
3000/2700
L6-20P, 2.4m cord
LS1-LS32:8xIEC C13
outlet)
200V
2490/2241
J2R04A HV INTL
208V to 240V (230V
1
)
3000/
2700
Detachable IEC C-20
cord
LS1-LS32: 8x IEC C13
200V
2490/2241
1
Factory default setting.
2
3
LS5 = Load Segment 5
outlets,
3
LS5
: 1X NEMA L5-30
LS1 thru LS4 = Load Segment 1 thru 4 (or less depending on unit)
230, 240
inlet plug for attaching
country specific power
cord
LS53: 1x IEC C-19 (16A
LS53: 1x IEC C-19 (16A
outlet)
1 x L6-30R
LS2: 15A CB - 3 x C19 +
1 x L6-30R
2 x C13
LS2: 15A CB - 2 x C19 +
2 x C13
Plus one pigtailed
receptacle (LS1)
LS1 thru LS4 = Load Segment 1 thru 4 (or less depending on unit)
cord
Receptacles
LS5
inlet plug for attaching
country specific power
LS53: 1x IEC C-19 (16A
LS53: 1x IEC C-19 (16A
outlets,
3
: 1X NEMA L5-30
outlet)
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Page 21
Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Tower UPS Models
Load
Load
Estimated battery runtime at 100%
T750 UPS
10%
53W
68
20%
105W
37
30%
158W
21
50%
263W
15
70%
368W
9
80%
420W
7
90%
473W
7
100%
525W
6
T1000 UPS
10%
70W
65
20%
140W
32
30%
210W
21
40%
280W
16
50%
350W
12
60%
420W
10
70%
490W
9
80%
560W
8
90%
630W
7
100%
700W
6
T1500 UPS
10%
108W
80
20%
216W
36
30%
324W
23
40%
432W
16
50%
540W
13
60%
648W
10
70%
756W
9
90%
972W
7
100%
1080W
6
Rack UPS Models
R1500 G4 UPS
(Percent)
40% 210W 16
60% 315W 10
(Watts)
battery charge
(Minutes)
80% 864W 7
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Page 22
Load
(Percent)
Load
(Watts)
Minutes of Back up time
10%
109W
97
20%
219W
39
30%
328W
23
40%
438W
16
50%
547W
12
60%
656W
10
70%
766W
8
80%
875W
7
90%
985W
6
100%
1094W
5
Estimated Runtime with Extended Runtime Module (ERM)
R/T2200 G4 UPS
Load
(Percent)
With internal batteries
(Minutes)
With One ERMs
(Minutes)
With Two ERMs
(Minutes)
With Three ERMs
(Minutes)
With Four ERMs
(Minutes)
191W (10%)
80
287
491
725
898
382W (20%)
30
123
218
311
406
573W (30%)
17
75
135
189
255
764W (40%)
12
53
97
133
184
956W (50%)
9
40
74
101
142
1147W (60%)
7
32
60
81
115
1338W (70%)
5
27
50
67
97
1529W (80%)
4
23
43
57
83
1720W (90%)
4
20
37
49
73
1911W (100%)
3
17
33
44
64
R/T3000 G4 UPS High Voltage
Load
(Percent)
With internal batteries
(Minutes)
With One ERMs
(Minutes)
With Two ERMs
(Minutes)
With Three ERMs
(Minutes)
With Four ERMs
(Minutes)
270W (10%)
83
259
457
655
854
540W (20%)
31
122
219
317
414
810W (30%)
18
78
143
207
271
1080W (40%)
12
57
105
153
201
1350W (50%)
9
45
83
121
159
1620W (60%)
7
37
68
100
132
1890W (70%)
5
31
58
85
112
2160W (80%)
4
27
50
74
97
2430W (90%)
4
24
45
65
86
2700W (100%)
3
21
40
59
77
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Page 23
R/T3000 G4 UPS Low Voltage
Load
(Percent)
With internal batteries
(Minutes)
With One ERMs
(Minutes)
With Two ERMs
(Minutes)
With Three ERMs
(Minutes)
With Four ERMs
(Minutes)
270W (10%)
61
281
475
665
860
540W (20%)
28
127
219
311
405
810W (30%)
17
79
140
200
260
1080W (40%)
12
57
101
146
190
1350W (50%)
10
44
79
114
149
1620W (60%)
8
36
65
93
122
1890W (70%)
7
30
54
79
104
2160W (80%)
6
26
47
68
90
2430W (90%)
5
22
41
60
79
2700W (100%)
4
20
37
53
70
R5000 UPS
Load
(Percent*)
With internal batteries
(Minutes)
With One ERM (Minutes)
With Four ERMs (Minutes)
450W (10%)
87
206
755
900W (20%)
36
99
349
1350W (30%)
22
64
222
1800W (40%)
15
47
162
2250W (50%)
12
37
126
2700W (60%) 9 31
103
3150W (70%) 8 26
87
3600W (80%) 6 23
75
4050W (90%) 6 20
66
4500W (100%) 5 18
58
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
R7000 UPS INTL
Load
(Percent*)
With internal batteries
(Minutes)
With One ERM (Minutes)
With Four ERMs (Minutes)
650W (10%)
185
282
834
1300W (20%)
62
118
357
1950W (30%)
33
70
218
2600W (40%)
21
49
153
3250W (50%)
15
37
117
3900W (60%)
11
29
93
4550W (70%) 9 24
77
5200W (80%) 7 20
66
5850W (90%) 6 18
57
6500W (100%) 5 15
50
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Page 24
R7000 UPS NA/JP
Load
(Percent*)
With internal batteries
(Minutes)
With One ERM (Minutes)
With Four ERMs (Minutes)
720W (10%)
160
237
736
1440W (20%)
53
100
309
2160W (30%)
28
60
186
2880W (40%)
18
42
130
3600W (50%)
12
32
98
4320W (60%) 9 25
78
5040W (70%) 7 21
64
57600W (80%) 6 18
54
6480W (90%) 5 15
47
7200W (100%) 4 13
41
NOTE: Backup times are estimated for typical applications. Actual performance will depend on load and battery conditions.
QuickSpecs
HPE Line Interactive Single Phase UPS
Estimated Backup Times
Page 25
R/T2200 G4 UPS
1920W 100%
R/T3000 G4 Low Voltage UPS
R/T3000 G4 High Voltage UPS
Environment-friendly
End-of-life Management
Hewlett Packard Enterprise offers end-of-life product return, trade-in, and
recycling.html#.V-lPA_krKiM
Rack/Tower UPS Models
Load (Percent*)
Estimates
battery
runtime
(Minutes)
With One
Extended
Runtime
Module
(Minutes)
With Two
Extended
Runtime
Modules
(Minutes)
With Three
Extended
Runtime
Modules
(Minutes)
With Four
Extended
Runtime
Modules
(Minutes)
384W 20%45142256346448
960W 50%155599110144
1536W 80%734605378
526473657
540W 20%40125225349452
1350W 50%125099107140
2160W 80%630606788
2700W 100%424475268
540W 20%45142256321417
1350W 50%155599115152
2160W 80%734607295
2700W 100%526476079
Products and Approach
and Recycling
recycling programs, in many geographic areas, for our products. Products
returned to Hewlett Packard Enterprise will be recycled, recovered or
disposed of in a responsible manner.
The EU WEEE directive (2002/95/EC) requires manufacturers to provide
treatment information for each product type for use by treatment facilities.
This information (product disassembly instructions) is posted on the
Hewlett Packard Enterprise web site. These instructions may be used by
recyclers and other WEEE treatment facilities as well as Hewlett Packard
Enterprise OEM customers who integrate and re-sell Hewlett Packard
Enterprise equipment.