For more information .......................................................................................................................... 16
Call to action .................................................................................................................................... 16
ITE racks
Introduction
If you’re deploying the latest generation of information technology (IT) equipment or adding more
servers to a crowded data center, conventional data center cooling methods and systems will likely be
inadequate. The most effective cooling solution for any computing facility depends on the specific
characteristics of the facility, equipment layout, and server density.
This technology brief first explains limitations of traditional cooling practices. Then it describes a
range of systems you can choose from to modify or supplement your existing cooling system to get the
cooling capacity your data center requires.
Limits of traditional cooling practices
Enterprise data centers have most often used an open-area approach to cool racks of servers and
storage systems. With this approach, one or more computer room air handlers (CRAHs) are placed
on the periphery of the data center room. IT equipment (ITE) racks are arranged in a cold-aisle/hotaisle layout (Figure 1). Cool air is forced through a raised floor plenum and up through vented floor
tiles in the cold aisle toward the front of the ITE racks. The cool air is drawn through the ITE racks, and
warm air is vented out the rear of the racks and upward toward the ceiling. Air circulation works on
the basic strategy of providing cool air at the floor level and collecting warm air near the ceiling.
Figure 1: Traditional open-area data center cooling
Basic room requirement:
Raised floor
CRAH
The open-area strategy is generally adequate for racks using up to 10 kilowatts of power and lets
data centers scale relatively easily. However, some of the warm air mixes with the cool air, reducing
cooling system efficiency. Some equipment generates excessive heat, creating hot spots that need
supplemental cooling or specific air channeling. The typical remedy has been to set the cooling
system to run colder to compensate for the hot spot.
2
(20 servers @ 423.9 W per server)
8.47 kW
20 servers
10 servers
4.23 kW
16.1 kW
8.0 kW
42 servers
21 servers
Server blade systems and 1U servers let you assemble high-density infrastructures; however, these
systems create much more heat per square foot of floor space and more hot spots. In instances like
this, the open-area approach cannot keep up with the demand for cool air.
Figure 2 compares two examples of server loading for a 42U rack. In Figure 2A, our rack contains
20 HP ProLiant DL380 G5 servers, each consuming approximately 424 watts for a total rack
consumption of 8.47 kW. In Figure 2B, our rack contains 42 dual-processor DL160 G6 servers
consuming 383 watts per server for a total rack consumption of over 16 kW of power.
Figure 2: Examples of power consumption in 42U IT equipment racks with different server loads
A: ProLiant DL380 G5 2U servers
Power
consumption
B: ProLiant DL160 G6 1U servers
(42 servers @ 383 W per server)
Power
consumption
Higher power consumption produces more heat. Virtually all power consumed by rack-mounted
equipment is converted to sensible heat, which increases the temperature in the environment. The
sensible heat load is typically expressed in British Thermal Units per hour (BTU/hr) or watts, where
1 W equals 3.413 BTU/hr. The rack’s heat load in BTU/hr can be calculated as follows:
Heat Load = Power [W] × 3.413 BTU/hr per watt
For example, the heat load for a ProLiant DL160 G6 server in a 2P configuration consuming
383 watts is calculated as follows:
383 W × 3.413 BTU/hr/W =1307 BTU/hr
This means that the heat load of our fully-loaded 42U rack of DL160 G6 servers is 54,901 BTU/hr. In
the United States, cooling capacity is often expressed in "tons" of refrigeration, which is derived by
dividing the sensible heat load by 12,000 BTU/hr per ton. Therefore, the cooling requirement for our
rack of DL160 G6 servers is computed as follows:
54,901 BTU/hr ÷ 12,000 BTU/hr per ton = 4.58 tons
3
Cold/hot
24
32
Closed-loop
Supplemented
25
50
The increasing heat loads created by the latest server systems require more aggressive cooling
strategies than the traditional open-area approach. Such strategies include the following:
• Free cooling
• Air containment
• Closed-loop cooling
Figure 3 identifies cooling strategies and implementations based on kilowatts per rack and on the
server density per rack.
Figure 3: Cooling strategies based on server density/power per rack
data center
cooling
Traditional
open-area
cooling
aisle
containment
cooling
Chassis/component
level cooling,
future cooling
technologies
Density (nodes per rack)
8
16
40
Power (kW per rack)
Free cooling strategies
Free cooling strategies use ambient outside temperature to remove heat from inside a data center.
You can implement free cooling as either a primary or secondary system. Free cooling systems take
advantage of regional climate conditions for more efficient operation, but they do include mechanical
and electrical equipment. Free cooling is generally applied using one of two methods: air-side
economization or water-side economization.
4
ITE racks
Air-side economization
Air-side economization uses a system of supply and return fans, filters, and dampers that maintain
positive air pressure with respect to the IT equipment exhaust, and positive data center air pressure
with respect to the outside. Air-side economization may also include supplemental cooling coils that
you can switch in and out of circuit as needed for changes in climate. You can implement air-side
economization as either a direct or indirect system. In direct air-side economization, outside air is
filtered, stabilized for relative humidity, and then delivered to the ITE racks (Figure 4). The ITE rack
layout and exhaust venting is similar to a hot-aisle containment strategy.
Figure 4: Air-side economization (direct method)
Exhaust
Input
Filters/fans
Filter/fan
Exhaust
air to
outside
Air from
outside
Room requirements:
Air circulation system built into facility
Air-side economization using the direct method is more applicable in cool regions where outside air
requires little or no refrigeration.
With indirect air-side economization, outside air cools data center air through an air-to-air heat
exchanger. This method uses two air circulation circuits: one for outside air and one for inside air.
Outside air is collected, cooled, and then used to cool re-circulated indoor air in a heat exchanger
that is common to both air circulation circuits. The two air circuits share the heat exchanger, but
indoor and outside air flows are segregated. Even though it requires two fan systems, indirect air-side
economization can be more energy efficient and may be the preferred method for warmer climates.
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.