HPE Adaptive Rack Cooling System
Installation Guide
Abstract
This document is for the person who installs racks and rack products. This procedure should
only be performed by trained personnel. Hewlett Packard Enterprise assumes you are
qualified in performing installations and trained in recognizing hazards in rack products.
Part Number: P07978-001
Published: December 2018
Edition: 1
Copyright 2018 Hewlett Packard Enterprise Development LP
Notices
The information contained herein is subject to change without notice. The only warranties for Hewlett
Packard Enterprise products and services are set forth in the express warranty statements accompanying
such products and services. Nothing herein should be construed as constituting an additional warranty.
Hewlett Packard Enterprise shall not be liable for technical or editorial errors or omissions contained
herein.
Confidential computer software. Valid license from Hewlett Packard Enterprise required for possession,
use, or copying. Consistent with FAR 12.211 and 12.212, Commercial Computer Software, Computer
Software Documentation, and Technical Data for Commercial Items are licensed to the U.S. Government
under vendor's standard commercial license.
Links to third-party websites take you outside the Hewlett Packard Enterprise website. Hewlett Packard
Enterprise has no control over and is not responsible for information outside the Hewlett Packard
Enterprise website.
Acknowledgments
Microsoft® and Windows® are either registered trademarks or trademarks of Microsoft Corporation in the
United States and/or other countries.
Google ® and the Google Logo® are registered trademarks of Google Inc.
Contents
About this guide......................................................................................4
CAUTION: Water quality that is out of spec may cause decreased cooling capacity or disruption in
service. The facility water supplied to the HPE Adaptive Rack Cooling System must meet the
guidelines stated in this manual. The HPE Adaptive Rack Cooling System warranty does not cover
damage caused by facility water that does not meet specifications.
To provide optimum performance with minimum maintenance, your site must meet environmental
requirements. The HPE Adaptive Rack Cooling System is intended to be installed in an indoor location
that is temperature controlled and relatively free of conductive contaminants.
To route water lines to your HPE Adaptive Rack Cooling System, use one of the following methods:
•Through an opening in the raised floor
•Through the top of the HPE Adaptive Rack Cooling System
Safety information
The HPE Adaptive Rack Cooling System is rated at a maximum facility pressure of 8 bar (116 PSI).
If valves are installed on the external pipe work that could potentially trap fluid inside the HPE Adaptive
Rack Cooling System, special precautions must be taken. To prevent severe plumbing failure due to
extreme pressure, use an expansion tank with a preinstalled safety valve in the plumbing circuit
connected to the unit.
WARNING: This equipment must be installed in a restricted access area. The equipment is not to
be accessible to persons (including children) with reduced physical, sensory, or mental capabilities,
or a lack of experience and knowledge, unless they have been given supervision or instruction. Only
authorized technicians trained by Hewlett Packard Enterprise should attempt to repair this
equipment. All troubleshooting and repair procedures are detailed to allow only subassembly- or
module-level repair. Because of the complexity of the individual boards and subassemblies, no one
should attempt to make repairs at the component level or to modify any printed wiring board.
Improper repairs can create a safety hazard.
4 About this guide
Installation
Accessory and option kit contents
If any of the following items are missing or damaged, contact your Hewlett Packard Enterprise authorized
reseller. Listed materials are subject to change.
Accessory Kits
HPE ARCS Accessory Kit
The HPE ARCS Accessory Kit comes with the HPE Adaptive Rack Cooling System. Use the parts
included in this kit to properly install the HPE Adaptive Rack Cooling System.
ItemDescriptionQuantity
1Baying brackets6 small
26-32 x 5/8 Phillips head screws16
3M5.5 x 10 Torx screws with serrated
head
4Air pressure tubing kit with brackets (not
shown)*
5Leveling pads2
6M6 x 1 x 10 Flathead Torx trilobe screws 16
7M5.5 x 13 Torx screws6
12
1
Table Continued
Installation5
ItemDescriptionQuantity
8HPE G2 Rack Baying Kit (Contains
brackets and screws used to bay the
racks together on either a 600mm or 24inch pitch.)
Worm drive hose and tube clamps2
Panduit boots2
Gasket, 15 x 151
Masterkleer PVC clear tubing, 6 ft.2
Safety, compliance, & warranty
information
*The HPE ARCS Air Pressure Tubing Kit contains the following components:
•Aluminum pipe, 1/8" diameter X 18" long, threaded on both ends
•Aluminum end cap, 1/8" diameter
•Barbed, threaded NPTF hose end, 1/8" diameter
•Pipe clamp, galvanized, 3/8"ID X 9/16" long (for HPE Adaptive Rack Cooling System)
2
1
•Pipe clamp, galvanized, 3/8"ID X 11/16" long (for HPE ARCS 42U/48U 600x1600mm Racks)
•Screw, 5.5x1.81x10 Pan Torx T25
•Flat washer, M6
•Plastic barbed tube fittings for air & water, 1/8"
•Polyurethane Tubing for Water, 5/32"ID, 1/4" OD
HPE ARCS Power Cord Kit
The HPE ARCS Power Cord Kit contains:
•IEC 60309 32/30A 220/415V 6h/IP44 power cord (Quantity 2)
•NEMA L22-20P 277/480V 4P/5W power cord (Quantity 2)
HPE ARCS Air Rack Accessory Kit
The HPE ARCS Air Rack Accessory Kit comes with the HPE ARCS 42U/48U 600x1600mm Racks. Use
the parts included in this kit to properly install the racks.
ItemDescriptionQuantity
Gasket, 15x15Foam for sealing the rack1
HPE G2 Rack
Grounding Kit
6Installation
Cables, screws, and washers used to
ground the rack through the rack frame
1
Table Continued
ItemDescriptionQuantity
HPE G2 Rack
Baying Kit
Rack Hardware KitScrews, cage nuts, and other hardware
Cable tiesUsed to attach cables to the rack1
Transportation
bracket kit
Option Kits
HPE ARCS Water Hook-Up Kit
Hewlett Packard Enterprise recommends using the HPE Adaptive Rack Cooling SystemWater Hook-Up
Kit to connect the HPE Adaptive Rack Cooling System to a facility water supply. Each kit includes two
hose assemblies with 2-inch sanitary flange connections that are required for connecting the facility
supply and return lines to the main inlet and outlet connections of an HPE Adaptive Rack Cooling
System. One Water Hook-Up Kit is required for each HPE Adaptive Rack Cooling System.
NOTE: To properly connect the Water Hook-Up Kit, the facility plumbing connection must be a 2-inch
flange fitting.
Brackets and screws used to bay the
racks together on either a 600mm or 24inch pitch
used to install servers to the EIA rail
Install these brackets when rack is fully
loaded and will be shipped
1
1
1
NOTE: The illustration is not drawn to scale. The actual length of the hoses is approximately 1.83 m (6 ft).
HPE ARCS 42U Air Rack Installation Kit
Installation7
ItemDescription
1
2
3
4
5
6
7
HPE ARCS 48U Air Rack Installation Kit
Large side panel blank for the rear extension (4)
Small side panel blank for the rear extension (4)
Rack side panel blank (24)
Side panel blank for the front extension, Panel B (10)
Side panel blank for the front extension, Panel D (2)
Side panel sealing tape
Screws, 6-32, 3/8" long (160)
8Installation
ItemDescription
1
2
3
4
5
6
7
8
9
HPE ARCS Auto Door Release Kit
Rack side panel blank, 48U (8)
Rack side panel blank (8)
Side panel blank for the front extension, Panel C (4)
Side panel blank for the front extension, Panel A (4)
Screw, 6-32, 3/8" long (80)
Grounding screw (1)
Screw, 5.5 X1.81X10 Pan Torx T25 (3)
Facade, 6U (1)
Left and right extension brackets
Installation9
ItemDescription
1
2
3
4
5
6
7
HPE ARCS Auto Controller Kit
Striker assembly with Southco R4-90-121-10 (1)
Front door latch assembly with bracket (1)
Rear door latch assembly (2)
Auto door cable harness assembly (1)
Screws, rear lock mount (8)
Screws, 1/4-20 button head (2)
Screws, M5.5X10 Torx pan head tap (3)
10Installation
ItemDescription
1
2
3
4
5
6
7
8
Required tools
The following tools are required for installation:
•Flat blade screwdriver
•#2 Phillips screwdriver
Power supply, 24 Volt (1) with mounting hardware
CMC III I/O ARCS Rack Module (1) with mounting hardware
Screws, M5.5X10 Torx pan head tap (2)
Custom mounting bracket (1)
Zip ties (50)
C13/14 power cord, 12 ft (1)
CanBus cable, 5 meters (1)
HPE Adaptive Rack Cooling System IO Module cable (1)
•Adjustable wrench
•Torx screwdriver set
Installation11
•Bubble level
•(Optional) 5mm square head key for hex drain
Installing the HPE Adaptive Rack Cooling System
Procedure
1.Read the unpacking instructions on the HPE Adaptive Rack Cooling System packaging material.
WARNING: The HPE Adaptive Rack Cooling System is shipped on a pallet and weighs
approximately 645 kg (1,423 lb) by itself or 732 kg (1,614lb) including packaging. Hewlett
Packard Enterprise recommends hiring professional movers to move the unit, remove the HPE
Adaptive Rack Cooling System from the pallet, and move the HPE Adaptive Rack Cooling
System to the final location.
2.Using four or more people and the ramps that came with the HPE ARCS 42U/48U 600x1600mm
Rack, remove the HPE Adaptive Rack Cooling System from the pallet.
3.Roll the HPE Adaptive Rack Cooling System to the final location.
CAUTION: Before attaching the hoses to the HPE Adaptive Rack Cooling System, verify that
the water supply and return are closed. Water that leaks into the unit can cause significant
damage.
4.Install the hoses, differential pressure tube, and Panduit boots.
5.To level the HPE Adaptive Rack Cooling System:
a. Remove the screws from the fan housing.
b. Unplug the fan communication and power cables.
c. Remove the lower fan from the rack.
CAUTION: Use a minimum of two people to manually move the fan.
d. Adjust the leveling feet using a bubble level.
12Installation
WARNING: To avoid tipping the HPE Adaptive Rack Cooling System over, be sure that the
leveling feet are lowered when the HPE Adaptive Rack Cooling System is equipped, serviced,
and operated.
6.Connect the network cable to the RJ-45 connector (labeled "ETH") on the transfer switch at the top
right on the rear of the HPE Adaptive Rack Cooling System.
7.Plug the other end of the network cable into the facility network connection outlet.
WARNING: Before connecting the power cords to a power source, be sure that the unit is
properly grounded for potential equalization caused by high leakage current.
IMPORTANT: Do not connect the power cords into a power source before connecting to the
HPE Adaptive Rack Cooling System.
8.Plug the primary power cord into the power connector on the left at the power distribution inside the
HPE Adaptive Rack Cooling System.
Installation13
If you are using a secondary power cord, plug it into the power connector on the right.
CAUTION: Do not force installation of power cords. Power cords are keyed and can only be
installed in one direction. Forcing cables into plugs can permanently damage the cable or the
plug.
WARNING: To reduce the risk of electric shock or damage to the equipment:
•Do not disable the power cord grounding plug. The grounding plug is an important safety
feature.
•Plug the power cord into a grounded (earthed) electrical outlet that is easily accessible at all
times.
•To disconnect power to the equipment, unplug the power cord from the power source.
•Do not route the power cord where it can be walked on or pinched by items placed against
it. Pay particular attention to the plug, electrical outlet, and the point where the cord extends
from the rack.
WARNING: To reduce the risk of fire, connect the power cord to a power outlet with overcurrent
protection not exceeding 20A.
14Installation
WARNING: To reduce the risk of electric shock, completely remove power before servicing by
disconnecting both power cords.
NOTE: If no secondary power is connected, the transfer switch will indicate a fail status for the
secondary power supply.
9.Guide the other ends of the power cords through the HPE Adaptive Rack Cooling System, and then
plug them into an appropriate power source.
10. Check for any errors on the display screen. If errors are displayed, see " HPE Adaptive Rack Cooling
System troubleshooting" in the HPE Adaptive Rack Cooling System User Guide.
For information on entering network settings, accessing controls, reviewing the details on the info
page, and resetting to factory defaults, see the HPE Adaptive Rack Cooling System Web InterfaceGuide.
Installation15