APPLICATION
W8600F Air Cleaner Monitor
INSTALLATION INSTRUCTIONS
The W8600F AirCleaner Monitor isan option available
for use with theF50F and F52F Honeywell Electronic Air
Cleaners (EAC). The series two F50F and F52F require
a solid state power supply that is compatible with the
W8600F driver board. Any series one F50E, F or F52F
can be upgraded to use the W8600F when the power
supply is replaced and the driver board (included in
W8600F kit) is installed.
The W8600F function indicator panel has four liquid
crystal display (LCD) arrowheads that point to ON,
BATTERY,SERVICE or FAULT. See Fig. 1. The
arrowheads darken to indicate the existing EAC
condition. See Table 1.
INSTALLATION
When Installing this Product..
1. Read these instructions carefully. Failure to follow
the instructions could damage the product or cause
a hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application
3. Installer must be a trained, experienced service
technician.
4. After completing the installation, use these instructions to check out the product operation.
Location
The styling of the W8600F is designed to blend with the
latest T8600 family of Honeywell Chronotherm¨ IV
Deluxe Programmable Thermostats. A special mounting
template is included for mounting next to the T8600. The
W8600F can also be mounted at any other convenient
location in the living area or equipment room. See Fig. 2.
NOTE: The W8600Fshares no common electricalcon-
nections with the thermostat.
ON
BATTERY
SERVICE
FAULT
Air Cleaner Monitor
FUNCTION
INDICATOR
PANEL
RESET BUTTO
M11965
Fig. 1. W8600F Air Cleaner Monitor features.
Table 1. Description of W8600F Function Indicator
Panel.
Indicators Condition
ON EAC ispowered and systemblower is
BATTERY Battery thatmaintains W8600F
SERVICE EAC prefilter and cells need to be
FAULT •Shortingof collectorplates.
running.
memory is low and needs to be
replaced.
a
.
washed
•Continuous ionizer or collector plate
arcing.
•Power supply failure.
•Excessive current.
•Major reduction in high voltage.
•EAC prefilter and cells are past
SERVICE level of dirt and need to be
washed immediately.
Call a service technician.
a
The reset button is located on the bottom of W8600F.
After the prefilters and cells are cleaned and reinstalled,
press this button to turn off the SERVICE indicator and
reset the wash frequency timer.
® U.S. Registered Trademark
Copyright © 2002 Honeywell International Inc. • • All Rights Reserved
69-1200-2
W8600F AIR CLEANER MONITOR
EAC
F52-ATTIC
On
Battery
Service
Fault
Air Cleaner Monitor
EAC
RETURN AIR DUCT
W8600F
W8600F
EAC
CLOSET
Fig. 2. W8600F mounting locations.
W8600F
W8600F
EAC
CEMENT BLOCK WALL
W8600
EAC
GARAGE/DRYWALL
M11966
Mounting
The following mounting instructions assume that the
W8600F is mounted next to a T8600 Thermostat. If
installing the monitor at another location, modify the
procedure to fit the installation.
1. Hold the mounting template (included in the
W8600F kit) next to the T8600 as shown in Fig. 3.
2. Mark the holes for the screw anchors and the
3-conductor thermostat cable.
3. Remove the template and drill the holes.
4. Remove the W8600F from the base.
5. Position the W8600F base over the holes and
install the anchors and screws (included in the bag
assembly). Tighten the screws until the base is
mounted firmly on the wall.
69-1200—2 2
THERMOSTAT
WALLPLATE
Fig. 3. Positioningmounting template.
MOUNTING
TEMPLATE
WIRING HOLE
M11971