Y8150 Fresh Air Ventilation System,
W8150 Fresh Air Ventilation Control
PRODUCT DATA
FEATURES
• Designed to help meet local ventilation codes and
standards, including ASHRAE 62.2-2010 standard,
“Ventilation and Acceptable Indoor Air Quality in
Low-Rise Residential Buildings.”
• Microcontroller optimizes the air delivery schedule to
make efficient use of normal HVAC run times.
• Easy-to-use input dials allow customized ventilation
for each installation.
• Test mode that includes immediate feedback to
installer to confirm that air delivery requirements of
selected ventilation standard are being met.
• Economical supply-only ventilation; works with forced
air system.
• Can be used with other equipment, such as an HRV/
ERV, for balanced ventilation.
APPLICATION
The Y8150 Fresh Air Ventilation System, W8150 Fresh Air
Ventilation Control provide fresh air to a home. The control
operates a fresh air intake damper and, when necessary,
activates the main HVAC blower to efficiently meet ASHRAE
ventilation rates.
IMPORTANT
Please read these instructions and keep them in your
records.
68-0282-07
Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL
SPECIFICATIONS
Y8150 includes:
W8150A Fresh Air Ventilation Control.
EARD6 Fresh Air Damper.
AT120B Transformer.
Mounting hardware for control.
Homeowner information label.
W8150 includes:
W8150 Fresh Air Ventilation Control.
Mounting hardware for control.
Homeowner information label.
Control (W8150A):
Power Supply: 20-30 Vac, 60 Hz.
Power Consumption: 3.5 VA at 24 Vac.
Thermostat Fan Load: 10 mA resistive at 24 Vac.
Thermostat Heat Load: 10 mA resistive at 24 Vac.
Remote Terminals: 10 mA resistive at 24 Vac.
Relay Contacts:
Fan: 1.5A full load, 7.5A locked rotor at 24 Vac.
Damper: 0.6A inductive, 3.1A locked rotor at 24 Vac.
Auxiliary: 0.5A inductive, 2.5A locked rotor at 24 Vac.
Damper (EARD6): 24 Va c , 1 2 VA , 6 0 H z .
Operation: Power-open, spring-closed.
Diameter: 6 in.
W8150A Ventilation Control dimensions in in. (mm).
3-3/8
(86)
4-3/16 (106)
1-1/2
(38)
3-1/2 (89)
5-3/4
(146)
1-1/4
(32)
M19988A
Transformer (AT120):
Input: 120 Vac.
Output: 27 Vac open circuit, 24 Vac full load at 20 VA.
Mounting: Foot mounted.
Temperature: -20 °F to 160 °F (-29 °C to 71 °C).
Humidity: 5 to 90% RH, noncondensing.
Input Setting Ranges:
Bedrooms: 2-5.
Area: 1000-4600 sq ft.
Vent Airflow: 40-160 cfm.
Composite Setting Resolution: +/- 12% of ASHRAE
62.2-2010, recommended ventilation for single-system setup.
AT120B Approvals: UL Component Recognized: Class 2,
File No. 14881.
Location: Device can be installed in unconditioned space.
Multiple devices can be installed when operating multiple
HVAC systems.
Dimensions: See device dimension diagrams.
6
(152)
8 (203)
M19989
EARD6 Fresh Air Damper dimensions in in. (mm).
3/16
(5)
1-3/4
(44)
15/16
1
(24)
(25)
1-5/8
(41)
3/16
2-13/16 (71)
(5)
1-7/8 (48)
68-0282—072
1/16 (2)
M22022
AT120B Transformer dimensions in in. (mm).
Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL
1
F
G
2
R
C
C
C
3
C
H
4
W
5
G
T
6
7
8
9
10
11
12
BEDROOMSAREA (SQFT)VENT AIRFLOW (CFM)
ON
13
XFMR
R
C
REMOTE AUX DAMPER
M19990
20
19
18
17
16
15
14
W8150 QUICK GUIDE
No.NameDescriptionFunction
1GFEquipment fanAllows W8150 to pass thermostat calls and, when necessary, turn on
2R
C24 Vac cooling system
power
3C
C24 Vac cooling system
common
H24 Vac heating system
4C
common
5WHeatingAllows W8150 to monitor when heating is energized.
6GTThermostat (or other
control) fan terminal
7SwitchOn (optimal ventilation)
Override
Off (Remote Only)
8LightGreenIndicates device is powered and operating normally. Used in Test Mode to
9LightRedIndicates the device is not operating normally. Used in Test Mode to signal
10DIP1Ventilation limitChoose between 60% (default) and 100% maximum fan run time allowed
11DIP2Ventilation standardChoose between ASHRAE 62.2 (default) and 62-1999 ventilation
12BEDROOMS Number of bedroomsUsed to calculate amount of ventilation necessary.
13AREA
(SQ FT)
14VENT
AIRFLOW
Square footage of
conditioned space
Air delivery rate through
fresh air duct.
(CFM)
15TestTest buttonW8150 checks dial and switch settings, activates ventilation for up to three
system fan for ventilation. This should be the only connection to G on the
HVAC equipment.
Provides power to GF terminal to operate system fan, when necessary.
Allows W8150 to monitor when system fan is energized.
Allows W8150 to monitor thermostat heat calls when W is energized.
Allows W8150 to monitor when GT is energized. All external equipment that
controls the system fan should be wired to this terminal.
On (optimal ventilation) – W8150 ventilates, based on control settings.
Override – W8150 runs ventilation continuously.
Off (Remote Only) – W8150 supplies ventilation only when there is a
remote call.
signal if dial settings meet chosen standard.
if dial settings do not meet chosen standard.
by W8150 for ventilation.
standards.
Used to calculate amount of ventilation necessary.
Used to calculate amount of ventilation necessary.
minutes and provides feedback to validate if chosen standard can be met.
368-0282—07
Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL
6
5
uto
(Remote Only)
No.NameDescriptionFunction
16REMOTERemote switch (two
terminals)
24 Vac powered contacts allow a remote switch closure to call for
ventilation.
17AUXAuxiliary (two terminals)24 Vac dry contacts allow W8150 to control an auxiliary device, such as
exhaust fan or HRV/ERV, with a call for ventilation.
18DAMPERDamper (two terminals)24 Vac powered contacts control fresh air damper.
19XFMR C24 Vac ventilation control
Supplies power to W8150 and damper from transformer provided.
common
20XFMR R24 Vac ventilation control
Supplies power to W8150 and damper from transformer provided.
power
INSTALLATION
A fresh air duct and damper must be installed between the
outdoors and the return side of the HVAC equipment. The
W8150 control will be mounted near the HVAC system and
wired between the thermostat and the fan control.
You will need…
• W8150 Fresh Air Ventilation Control.
• damper.
• transformer.
• insulated ductwork.
• outdoor weather hood.
• starting collar.
• access to 120 Vac power.
• airflow measuring tool.
TIPS:
• To meet ASHRAE 62.2-2010, system must have at least a
MERV 6 filter installed.
• In cold climates, balanced ventilation is recommended. An
exhaust fan or heat recovery ventilator can be used.
• Humid climates may require additional dehumidification
equipment.
Choosing a location…
When choosing locations for equipment, duct connections,
and fresh air intake, be sure to consult local code
requirements.
Device
NumberComponent Location
1Fresh air intake Install away from known sources
of pollutants such as auto
exhaust, dryer vent exhaust or
chimney smoke.
2Fresh air ductInstall between weather hood and
upstream of equipment filter and
downstream of any duct-mounted
sensor.
3DamperInstall damper in fresh air duct,
where convenient. Optionally,
install heat recovery ventilator.
4ControlLocate the control for convenient
access and for easy wire routing.
5TransformerLocate where convenient for line
voltage connection.
6 FilterLocate filter downstream of fresh
air intake.
TYPICAL ATTIC
INSTALLATION
2
1
1
68-0282—074
2
TYPICAL BASEMENT
INSTALLATION
3
3
6
1
V
nili
n nrl
A
6
2
TYPICAL HRV/ERV
3
HRV/ERV
INSTALLATION
M19993
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.