Honeywell W7761A User Manual

Table of Contents
Excel 10 W7761A Remote Input/Output
Device
CONTENTS
Introduction ...........................................................................................................................
Description of Devices ....................................................................................... 4
Control Application............................................................................................. 5
Control Provided................................................................................................. 5
Products Covered............................................................................................... 6
Organization of Manual...................................................................................... 6
Applicable Literature .......................................................................................... 6
Product Names .................................................................................................. 6
Agency Listings.................................................................................................. 7
Abbreviations and Definitions............................................................................. 7
Construction....................................................................................................... 9
Controllers..................................................................................................... 9
Performance Specifications...................................................................... 12
Wall Modules................................................................................................. 15
Configurations.................................................................................................... 16
Mixed-Output-Type Control........................................................................... 17
Occupancy Sensor........................................................................................ 17
Window Open/Closed Digital Input................................................................ 17
Wall Module Options ..................................................................................... 17
Dirty Filter Monitor......................................................................................... 17
Indoor Air Quality (IAQ) Override................................................................... 17
Application Steps ...........................................................................................................................
Overview ............................................................................................................ 18
Step 1. Plan The System.................................................................................... 18
Step 2. Determine Other Bus Devices Required................................................ 19
Step 3. Lay Out Communications and Power Wiring......................................... 19
E-Bus Layout................................................................................................. 19
Power Wiring................................................................................................. 21
Power Budget Calculation Example:......................................................... 21
Line Loss: ................................................................................................. 22
Step 4. Prepare Wiring Diagrams ...................................................................... 24
General Considerations................................................................................. 24
W7761A Devices........................................................................................... 24
E-Bus Termination Module............................................................................ 30
Step 5. Order Equipment.................................................................................... 33
Step 6. Configure Devices.................................................................................. 36
Step 7. Troubleshooting..................................................................................... 36
Troubleshooting Excel 10 Controllers and Wall Modules.............................. 36
Temperature Sensor and Setpoint Potentiometer Resistance Ranges......... 36
Alarms ........................................................................................................... 36
Broadcasting the Service Message............................................................... 37
W7761A Controller Status LEDs................................................................... 37
T7780 DDWM Bypass Pushbutton................................................................ 38

List of Figures ........................................................................................................................... 2
U.S. Registered Trademark Copyright 1998 Honeywell Inc. All Rights Reserved LonWorks LonMark and LonMark l ogo are Regi stered Trademarks of Echelon Corporat i on.
Fig. 1. Typical system overview......................................................................... 4
Fig. 2. Typical W7761A control application........................................................ 5
Fig. 3. Excel 10 W7761A Remote I/O Device. ................................................... 10
Fig. 4. W7761A construction.............................................................................. 11
74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Fig. 5. DIN rail adapters..................................................................................... 12
Fig. 6. T7770A,B,C,D construction (T7770A,C shown)..................................... 15
Fig. 7. T7780 construction................................................................................. 16
Fig. 8. Connecting the portable operator terminal to the E-Bus. ....................... 18
Fig. 9. Bus wiring layout for doubly terminated daisy-chain E-Bus segment..... 20
Fig. 10. Bus wiring layout for two singly terminated E-Bus segments............... 21
Fig. 11. NEMA class 2 transformer voltage output limits................................... 22
Fig. 12. Power wiring details for one Excel 10 per transformer......................... 22
Fig. 13. Power wiring details for two or more Excel 10s per transformer.......... 23
Fig. 14. Transformer power wiring details for one Excel 10 used in UL 1995
equipment (U.S. only)........................................................................................ 23
Fig. 15. Attaching two or more wires at terminal blocks.................................... 25
Fig. 16. Typical T7770A and C7770A wiring diagram....................................... 26
Fig. 17. Typical Humidity and Enthalpy (4 to 20 mA) sensor wiring diagram.... 27
Fig. 18. Typical Window and Occupancy sensor wiring diagram...................... 28
Fig. 19. Typical PWM Valve Actuator and miscellaneous fan control to W7761A.29
Fig. 20. Typical Pneumatic transducer to (Series 60 - Floating) W7761A......... 30
Fig. 21. Typical E-Bus termination module wiring diagrams.............................. 31
Fig. 22. E-Bus termination wiring options.......................................................... 32
Fig. 23. Temperature sensor resistance plots................................................... 36
Fig. 24. Location of the Service Pin Button. ...................................................... 37
Fig. 25. LED location on W7761A. .................................................................... 38
Fig. 26. Bypass pushbutton location on T7780 DDWM..................................... 39
List of Tables ...........................................................................................................................
Table 1. Agency Listings. .................................................................................. 7
Table 2. List Of Available Points........................................................................ 12
Table 3. Application Steps................................................................................. 18
Table 4. E-Bus Configuration Rules And Device Node Numbers...................... 19
Table 5. VA Ratings For Transformer Sizing..................................................... 22
Table 6. Field Wiring Reference Table.............................................................. 24
Table 7. W7761A I/O Description...................................................................... 25
Table 8. Excel 10 W7761A Device Ordering Information.................................. 33
Table 9. Excel 10 Alarms................................................................................... 37
Table 10. LED States. ....................................................................................... 38
Appendices ...........................................................................................................................
Appendix A. Using E-Vision for Commissioning W7761A Controllers............... 39
SENSOR CALIBRATION.............................................................................. 39
CUSTOM MAPPING ..................................................................................... 39
ADDING ANALOG INPUTS - ENTHALPY (4 to 20 mA)........................... 39
ADDING OTHER VOLTAGE/CURRENT SENSORS............................... 40
Table A-1. Default PID Parameters.......................................................... 41
ADDING DIGITAL INPUTS...................................................................... 41
Table A-2. Supported Digital Input Types................................................ 41
ADDING DIGITAL OUTPUTS.................................................................. 41
Table A-2. Supported Digital Output Types ............................................. 42
Appendix B. Sequences of Operation. .............................................................. 42
Common Operations..................................................................................... 42
Room Temperature Sensor (RmTemp) ................................................... 42
Window Sensor (StatusWndw)................................................................ 43
Dirty Filter Monitor.................................................................................... 43
Series 60 Modulating Control................................................................... 43
Pulse Width Modulating (PWM) Control.................................................. 43
Indoor Air Quality (IAQ) Override............................................................. 43
Appendix C. Complete List of Excel 10 W7761A Remote I/O Device User
Addresses.......................................................................................................... 44
Table C0. Engineering Units For Analog Points........................................... 44
Table C1.Input/Output Points. ...................................................................... 46
Table C2. Control Parameters...................................................................... 56
Table C3. Status Points................................................................................ 58
Table C4. Configurations Parameters. ......................................................... 64
Table C5. Direct Access And Special Points................................................ 70
Appendix D. Q7750A Excel 10 Zone Manager Point Estimating Guide. ........... 71
Approximate Memory Size Estimating Procedure........................................ 71
Fig. D-1 Point capacity estimate for Zone Manager................................. 71
Appendix E. Sensor Data for Calibration........................................................... 72
Resistance Sensors...................................................................................... 72
Voltage/Current Sensors. ............................................................................. 74

2 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
INTRODUCTION
Description of Devices
The W7761A, Excel 10 Remote Input/Output device, provides auxiliary inputs and outputs for use with an Excel 10 Zone
®
Manager and Excel 10 controllers over the Echelon
®
tool. The W7761A device uses Echelon
LonWorks® communication technology and a new free topology twisted pair transceiver (FTT) for greater network installation flexibility. The Excel 10 RIO device can be combined with the Excel 10 Zone Manager (FTT), other Excel Controllers, and the Excel Building Supervisor, to provide a complete and low cost control solution for small to large commercial buildings.
The Q7750A Excel 10 Zone Manager is a communications interface that allows devices on the E-Bus network to communicate with devices on the standard EXCEL 5000® System C-Bus. Fig. 1 shows an overview of a typical system layout. The Q7750A also provides some control and monitoring functions.
Q7752A FTT E-BUS SERIAL ADAPTER
PERSONAL COMPUTER TOOLS E-VISION CARE
FTT E-BUS COMMUNICATIONS NETWORK
LonWorks®E-Bus. These I/O points are configured with the E-Vision
C-BUS COMMUNICATION NETWORK
EXCEL 10 Q7750A FTT ZONE MANAGER
C-BUS TO E-BUS INTERFACE DEVICE
FTT E-BUS COMMUNICATIONS NETWORK
EXCEL BUILDING SUPERVISOR
EXCEL 500
Q7740A 2-WAY REPEATER
Q7751A FTT E-BUS ROUTER
EXCEL 10 T7770E WALL MODULE
65 60
55
auto 0 1
31 30 29 28 27 26 25
DI-4GND
DI-3
DI-2GND DI-1
70
75
80
85
E
LED
BYPASS
SNSR
GND
1234567 891011121314
EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
EXCEL 10 W7750B CVAHU CONTROLLER
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
1234567 89101112131415J3
24
23 22 21 20 19 18 17
24
24
1
16
VAC
2
3
4
VAC
5
COM
6
OUT
7
OUT
8
OUT
OUT
OUT
OUT
OUT
OUT
GND
SET PT
AI-1
GND
A1-2
AI-3
GND
AI-4
OHM
22VDC
OHM
E-BUS
V/mA
E-BUS
V/mA
OUT
JACK
15
J3
EXCEL 10 T7770 WALL MODULE
EXCEL 10 W7752 FTT FAN COIL UNIT CONTROLLER
EXCEL 10 W7751F PANEL PLENUM MOUNT VERSION VARIABLE AIR VOLUME CONTROLLER
FTT E-BUS
COMMUNICATIONS
NETWORK
31 30 29 28 27 26 25
DI-4GND
DI-3
DI-2GND DI-1
E
LED
BYPASS
SNSR
GND
SET PT
GND
1234567 891011121314
24
24
24
VAC
VAC
COM
AI-1
GND
OHM
23 22 21 20 19 18 17
1
2
3
4
5
OUT
OUT
OUT
OUT
OUT
A1-2
AI-3
GND
AI-4
22VDC
OHM
V/mA
V/mA
OUT
EXCEL 10 T7780 DIGITAL DISPLAY WALL MODULE
EXCEL 10
16
6
7
8
OUT
OUT
OUT
E-BUS
E-BUS JACK
15
J3
REMOTE INPUT/ OUTPUT DEVICE
M12884
Fig. 1. Typical system overview.
3 74-2699
Control Application
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
The W7761A, Excel 10 Remote Input/Output device, provides auxiliary inputs and outputs for use with an Excel 10 Zone
®
Manager and Excel 10 controllers over the Echelon
LonWorks®E-Bus. The W7761A Remote Input/Output Device can be connected to outdoor air temperature and humidity sensors that can be used by other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. This would allow the controllers to use their physical inputs for monitoring other elements such as return humidity, IAQ, etc. to achieve better control. The W7761A can be used to average many space temperature sensors that are located in a zone that is controlled by the W7750 Constant Volume AHU Controller. The W7761A device has 8 Digital Outputs which may be Discrete, Modulating or Floating. For example, this allows the control of lighting zones, miscellaneous exhaust or ventilation fans, miscellaneous pumps, and can enable freeze protection. See Fig. 2.
OA
HUMIDITY
TEMPERATURE
EXCEL 10 T7770 WALL MODULE
OA
MISC. FANS
WINDOW CONTACT
EXCEL 10 W7761A REMOTE INPUT/OUTPUT
PUMPS
LIGHTING CONTROL
OCCUPANCY SENSOR
M12885
Fig. 2. Typical W7761A control application.
Control Provided
The W7761A was not intended to control staged or modulating heating/cooling coils, mixed air economizer dampers, or system fan/heat pump units. The W7761A contains inputs and outputs, but no control software. All control that would be associated with the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for VAV control, temperature control, or any control function that would require less than a 30 second update rate.
Products Covered
This System Engineering Guide describes how to apply the W7761A Excel 10 Remote Input/Output Device and related accessories to typical applications. The specific devices covered include:
W7761A Remote I/O device.
T7770 A through D Wall Modules.
Q7750A Excel 10 Zone Manager.
Q7751A Router (FTT to FTT only).
Q7752A Serial Interface Adapter.
Q7740A,B Repeaters (2-way and 4-way).
209541B FTT Termination Module.
Organization of Manual
This manual is divided into three basic parts: the Introduction, the Application Steps, and the Appendices that provide supporting information. The Introduction and Application Steps 1 through 5 provide the information needed to make accurate material ordering decisions. Application Step 6 and the Appendices include configuration engineering that can be started using Excel E-Vision PC Software after the devices and accessories are ordered. Application Step 7 is troubleshooting. The organization of the manual assumes a project is being engineered from start to finish. If an operator is adding to, or is changing an existing system, the Table of Contents can provide the relevant information.
Applicable Literature
The following list of documents contains information related to the Excel 10 W7761 Remote I/O Device and the EXCEL 5000® System in general. Form No. Title
4 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
74-2698 Excel 10 W7761A Device Specification Data 74-2956 Excel 10 W7750A,B Controller Specification Data 74-2697 T7770A through G Wall Module Specification Data 74-2955 T7780 Digital Display Wall Module Specification Data 74-2950 Excel 10 Q7750A, Zone Manager Specification Data 74-2952 Excel 10 Q7751A Router Specification Data 74-2954 Excel 10 Q7752A Serial Interface Specification Data 74-2858 Excel 10 Q7740A,B FTT Repeaters Specification Data
95-7539 Excel 10 W7761A Device Installation Instructions 95-7521 Excel 10 W7750A,B Controller Installation Instructions 95-7538 T7770 Wall Module Installation Instructions 95-7558 T7780 Digital Display Wall Module Installation Instructions 95-7509 Excel 10 Q7750A Zone Manager Installation Instructions 95-7510 Excel 10 Q7751A Router Installation Instructions 95-7511 Excel 10 Q7752A Serial Interface Installation Instructions 95-7516 Excel 10 SLTA Connector Cable Installation Instructions 95-7555 Excel 10 Q7740A,B FTT Repeaters Installation Instructions 95-7554 Excel 10 209541B FTT Termination Module Installation Instructions
74-2588 Excel E-Vision User’s Guide 74-5587 CARE User’s Manual 74-5577 CARE Icon Guide 74-2039 XBS User’s Manual 74-5018 XBS Application Guide
Product Names
The W7761A Remote I/O Device is available in one model:
W7761A
The T7770 Wall Module is available in five models:
T7770A1xxx
20Kohm NTC to a linearized version of a 20 Kohm NTC used with the W7751A,C,E,G).
T7770A2xxx
T7770B
network connection for use with all Excel 5000 controllers (except W7751A,C,E,G).
T7770C
button and LED, and E-Bus network connection for use with all Excel 5000 controllers (except W7751A,C,E,G).
T7770D
LED, and E-Bus network connection for use with all Excel 5000 controllers (except W7751A,C,E,G).
Only one PT3000 sensor is supported with the W7761A device. The T7780 Digital Display Wall Module (DDWM) is available in one model:
T7780
mode/speed selection for all Excel 10 controllers (except W7751 A,C,E,G).
Other products:
Q7750A
Q7751A
Q7752A
Q7740A,B
209541B
• ML6161
• M6410A ML684A
MMC325-010
MMC325-020
ML6464A
ML6474
ML6185A
ML7984B
• EL7680A1008
• EL7628A1007
• EL7611A1003
• EL7612A1001
Refer to Table 8 in Application Step 5. Order Equipment for a complete listing of all available part numbers. NOTE: The Q7750A Zone Manager is referred to as (E-Link) in internal software and CARE.
Remote Input/Output Device.
Wall Module with temperature sensor only ­ Wall Module with temperature sensor and E-Bus network connection.
Wall Module with temperature sensor—(current feature that can be used with the RIO Device), setpoint, and E-Bus Wall Module with temperature sensor—(current feature that can be used with the RIO Device), setpoint, Bypass Wall Module with temperature sensor—(current feature that can be used with the RIO Device), Bypass button and
NOTE: The T7770B,C Models are available with a relative scale plate adjustable in E-Vision °F (± 5°C).
DDWM displays and provides space temperature, setpoint, Occ/Unocc override, Application Mode, and Fan
Excel 10 Zone Manager. Bus Router. Serial Adapter.
FTT Repeaters.
FTT Termination Module. Series 60 Damper Actuator. Series 60 Valve Actuator (use with V5812 or V5813 Valves).
Series 60 Versadrive Valve Actuator (use with V5011 and V5013 Valves).
Transducer, Series 60 to pneumatic 0 to 10 psi. Transducer, Series 60 to pneumatic 0 to 20 psi.
Direct Coupled Damper Actuator, 66 lb-in. torque, Series 60.
Direct Coupled Damper Actuator, 132 lb-in. torque, Series 60.
Direct Coupled Damper Actuator, Spring Return, Series 60. Direct Coupled Valve Actuator, PWM (use with V5011 or V5013F,G Valves).
Wall Module Infrared Occupancy Sensor. Ceiling Mounted Infrared Occupancy Sensor. Ultrasonic Occupancy Sensor. Ultrasonic Occupancy Sensor.
not applicable to the RIO device
(jumper switches the sensor from
5 74-2699
Agency Listings
g
Table 1 provides information on agency listings for Excel 10 products.
Table 1. Agency Listings.
Device Agency Comments
W7761A Input/Output Device
T7770A through D Wall Modules
T7780 DDWM
Q7750A Excel 10 Zone Manager
Q7751A,B Router, Q7752A Serial Adapter Q7740A,B FTT Repeaters
UL Tested and listed under UL916 (file number E87741). cUL Listed (E87741). CE General Immunity per European Consortium Standards EN50081-1 (CISPR
22, Class B) and EN 50082-1:1992 (based on Residential, Commercial, and Light Industrial). EN 61000-4-2: IEC 1000-4-2 (IEC 801-2) Electromagnetic Discharge. EN 50140, EN 50204: IEC 1000-4-3 (IEC 801-3) Radiated Electroma EN 61000-4-4: IEC 1000-4-4 (IEC 801-4) Electrical Fast Transient (Burst).
Radiated Emissions and Conducted Emissions: EN 55022: 1987 Class B. CISPR-22: 1985.
FCC Complies with requirements in FCC Part 15 rules for a Class B Computing
Device. Operation in a residential area can cause interference to radio or TV reception and require the operator to take steps necessary to correct the
interference. UL (Not applicable.) CSA (Not applicable.) FCC (Not applicable.)
CE Emissions; EN50081-1, En55022 (CISPR Class B), Immunity 50082-1
UL &cUL Tested and listed under UL916, S8L9 Energy Management Equipment.
FCC Complies with requirements in FCC Part 15 rules for a Class B Computing
Device. UL Tested and listed under UL916, file number S4804 (QVAX, PAZY). CSA Listing pending. FCC Complies with requirements in FCC Part 15 rules for a Class A Computing
Device. Operation in a residential area can cause interference to radio or TV
reception and require the operator to take steps necessary to correct the
interference. UL UL1784.
CSA Listed. FCC Complies with requirements in FCC Part 15 rules for a Class B Computing
Device.
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
netic Field.
Abbreviations and Definitions
AHU
- Air Handling Unit; the central fan system that includes the blower, heating equipment, cooling equipment, ventilation air equipment, and other related equipment.
CO
- Carbon Monoxide. Occasionally used as a measure of indoor air quality.
CO2
- Carbon Dioxide. Often used as a measure of indoor air quality.
CARE
- Computer Aided Regulation Engineering; the PC based tool used to configure C-Bus and E-Bus devices.
C-Bus
-Honeywell proprietary Control Bus for communications between EXCEL 5000® System controllers and components.
CPU
- Central Processing Unit; an EXCEL 5000® System controller module.
cUL
- Underwriters Laboratories Canada.
CVAHU
-Constant Volume AHU; refers to a type of air handler with a single-speed fan that provides a constant amount of supply air to the space it serves.
6 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
DDF
- Delta Degrees Fahrenheit.
D/X
- Direct Expansion; refers to a type of mechanical cooling where refrigerant is (expanded) to its cold state, within a heat-exchanging coil that is mounted in the air stream supplied to the conditioned space.
E-Bus
- Honeywell implementation of Echelon® LonWorks® network for communication among Excel 10 Controllers.
E-Bus Segment
Echelon® Economizer
E-Link
EEPROM
EPROM
Excel 10 Zone Manager
Firmware
router.
conditions, fresh air can be used to supplement the mechanical cooling equipment. Because this action saves energy, the dampers are often referred to as
EMI
- Electromagnetic Interference; electrical noise that can cause problems with communications signals.
- Refers to the Q7750A Zone Manager. This name is used in internal software and in CARE software.
EMS
- Energy Management System; refers to the controllers and algorithms responsible for calculating optimum operational parameters for maximum energy savings in the building.
and factory calibration information.
- Erasable Programmable Read Only Memory; the firmware that contains the control algorithms for the Excel 10 Controller.
also has the functionality of an Excel 100 Controller, but has no physical I/O points. NOTE: The Q7750A Zone Manager can be referred to as E-Link in the internal software, CARE.
FCU
- Fan Coil Unit.
- An E-Bus section containing no more than 60 Excel 10s. Two segments can be joined together using a
- The company that developed the LON® bus and the Neuron® chips used to communicate on the E-Bus.
- Refers to the mixed-air dampers that regulate the quantity of outdoor air that enters the building. In cool outdoor
economizer dampers
- Electrically Erasable Programmable Read Only Memory; the variable storage area for saving user setpoint values
- A controller that is used to interface between the C-Bus and the E-Bus. The Excel 10 Zone Manager
- Software stored in a nonvolatile memory medium such as an EPROM.
.
Floating Control
Level IV
NEMA
Node
pulse the actuator open, and another digital output to pulse it closed.
FTT
- Free Topology Transceiver.
IAQ
- Indoor Air Quality. Refers to the quality of the air in the conditioned space, as it relates to occupant health and comfort.
I/O
- Input/Output; the physical sensors and actuators connected to a controller.
I x R
- I times R or current times resistance; refers to Ohm’s Law: V = I x R.
K
- Degrees Kelvin.
- Refers to a classification of digital communication wire. Formerly known as UL Level IV, but Category IV cable. If there is any question about wire compatibility, use Honeywell-approved cables (see Step 5 Order Equipment section).
NEC
- National Electrical Code; the body of standards for safe field-wiring practices.
- National Electrical Manufacturers Association; the standards developed by an organization of companies for safe field wiring practices.
- A Communications Connection on a network; an Excel 10 Controller is one node on the E-Bus network.
NV
- Network Variable; an Excel 10 parameter that can be viewed or modified over the E-Bus network.
PC
- An IBM compatible Personal Computer with 386 or higher processor and capable of running Microsoft® Windows™ Version 3.1.
- Refers to Series 60 Modulating Control of a valve or damper. Floating Control utilizes one digital output to
not
equivalent to
Pot
- Potentiometer. A variable resistance electronic component located on the T7770B,C Wall Module; used to allow user­adjusted setpoints to be input into the Excel 10 Controller.
7 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
PWM
- Pulse Width Modulated output; allows analog modulating control of equipment using a digital output on the controller.
RTD
- Resistance Temperature Detector; refers to a type of temperature sensor whose resistance output changes according to the temperature change of the sensing element.
RIO
- Remote Input/Output Device. Provides auxiliary inputs and outputs for use with an Excel 10 Zone Manager and Excel 10 controllers.
Subnet
W7750 W7751 W7752 W7753 W7761 Wall Module
- An E-Bus segment that is separated by a router from its Q7750A Zone Manager.
TOD
- Time-Of-Day; the scheduling of Occupied and Unoccupied times of operation.
TPT
- Twisted Pair Transceiver.
UV
- Unit Ventilator Controller.
VA
- Volt Amperes; a measure of electrical power output or consumption as applies to an ac device.
Vac
- Voltage alternating current; ac voltage rather than dc voltage.
VAV
- Variable Air Volume; Refers to either a type of air distribution system, or to the W7751 Excel 10 VAV Box Controller that controls a single zone in a variable air volume delivery system.
VOC
- Volatile Organic Compound; refers to a class of common pollutants sometimes found in buildings. Sources include out-gassing of construction materials, production-line by-products, and general cleaning solvents. A VOC is occasionally used as a measure of indoor air quality.
-The model number of the Excel 10 CVAHU Controllers (also see CVAHU).
-The model number of the Excel 10 VAV Box Controllers (also see VAV).
-The model number of the Excel 10 FCU Controllers (also see FCU).
-The model number of the Excel 10 UV Controllers (also see UV).
-The model number of the Excel 10 RIO Device (also see RIO).
- The Excel 10 Space Temperature Sensor and other optional controller inputs are contained in the T7770 or
T7780 Wall Modules. See Application Step 5. Order Equipment for details on the various models of Wall Modules.
XBS
- Excel Building Supervisor; a PC based tool for monitoring and changing parameters in C-Bus devices.
Construction
Controllers
The Excel 10 W7761A RIO Device is available in one model. It contains 4 resistive inputs that can be configured for either 20Kohm NTC or PT3000 sensors, 2 voltage or current inputs, 4 digital inputs and 8 Digital Outputs (Triacs) which may be Discrete (maintained or momentary), Modulating (PWM) or Floating.
The W7761A consists of a single circuit board that is mounted in a sheet metal subbase and protected by a factory snap-on cover. The device mounts with two screws (see Fig. 3 or 4). Using DIN rail adapters (see Fig. 5) they can also be snapped onto standard EN 50 022 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) DIN rail. DIN rail is available through local suppliers. If using DIN rail also purchase from Augat Inc. part number 2TK2D DIN rail (adapter) two each for every device (see Fig. 5). Wires are attached to the screw terminal blocks on both sides of the device. Connection for operator access to the E-Bus is provided by plugging the SLTA connector cable into the communications jack.
A channel in the cover allows the device status LED to be visible when the cover is in place. There are no field-serviceable parts on the circuit board and, therefore,
The W7761A can be mounted in any orientation. Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation. See Fig. 3 and 4.
it is intended that the cover never be removed
.
8 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
W7761A
3
1
3
0
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
D
I-
4
G
N
D
D
I
-3 D
I-
2
G
N
D
D
I-1V
AC 24
V
AC 24 COM
O
U
T
1
O
U
T
0
1
9
1
8
1
7
1
6
2
O
U
T
3
O
U
T
4
O
U
T
5
O
U
T
6
O
U
T
7
O
UT
8
EGND
1
NOT
USED
2
NOT
USED
3
AI-1
OHM
GND
AI-2
AI-3
OHM
4
5
6
OHM
GND
AI-4
AI-5
OHM
7
8
9
1
V/mA
GND
AI-6
22
V
D
C
V/mA
0
1
1
1
2
E
B
US
O
U
T
1
3
1
4
E
B
U
S
JA
C
K
1
5
J
3
M1 0118
Fig. 3. Excel 10 W7761A Remote I/O Device.
9 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
2-1/8
(54)
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
VAC 24
VAC 24
OUT1 OUT2 OUT 3 OUT 4 OUT5 OUT 6 OUT7 OUT8
COM
AI-3
AI-4
AI-5
OHM
GND
OHM
V/mA
GND
AI-6
V/mA
22V DC
EBUS
OUT
EBUS JACK
EGND
GNDGND
DI-1
DI-2DI-3DI-4
NOT
NOT
AI-1
AI-2
USED
GND
USED
OHM
OHM
1 2 3 4 5 6 7 8 9101112131415J3
5-3/16 (132)
6 (152)
3-1/16
(77)
5-5/8 (143)
Fig. 4. W7761A construction in in. (mm).
10 74-2699
M6856
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
2
3
1
M6857
Fig. 5. DIN rail adapters.
The input/output points are summarized in Table 2.
Table 2. List Of Available Points.
W7761A
Digital Outputs 8 Triac Outputs Digital Inputs 4 Analog Inputs 6
DC Power 20 Vdc available to
Floating (Series 60) Control
PWM Control Heating or Cooling
Performance Specifications Power:
24 Vac with a minimum of 20 Vac and a maximum of 30 Vac at either 50 or 60 Hz. The W7761A power consumption is 6 VA maximum at 50 or 60 Hz. The W7761A is a NEC Class 2 rated device. This listing imposes limits on the amount of power the product can consume or directly control to a total of 100 VA (U.S. only).
(4 Resistive and 2 Voltage/Current Inputs)
power optional sensors (50 mA max.)
Heating or Cooling
The individual Triac outputs incorporate an internal common connection with the input power transformer. The Triacs provide a switched path from the hot side (R) of the transformer through the load to the common of the transformer. The W7761A Device
must
design Each individual Triac is rated 500mA at 30 Vac maximum. Under all operating conditions, the maximum load/source power
budget for the W7761A Device is 100 VA.
use the same power transformer for any loads connected to that device; see Fig. 19.
11 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
CPU:
Motorola or Toshiba 3150 Neuron processor, containing three eight-bit CPU’s. Each Neuron has a unique 48-bit network identification number.
Memory Capacity:
64K ROM/PROM (6K reserved for network operations, 58K usable for control algorithm code). 512 bytes EEPROM. 2K RAM.
Specified Space Temperature Sensing Range:
45 to 99°F (7 to 37°C) with an allowable control setpoint range from 50 to 90°F (10 to 32°C) when initiated from the network and 55 to 85°F (13 to 29°C) when configured and connected to T7770 Wall Modules or T7780 DDWM.
Communications:
The W7761A Device uses a transformer-coupled communications port with differential Manchester-encoded data at 78 kilobits per second (kbs). The transformer-coupled communications interface offers a much higher degree of common-mode noise rejection while ensuring dc isolation.
2
Approved cable types for E-Bus communications wiring is Level IV 22 AWG (0.34 mm unshielded, twisted pair, solid conductor wire. For non-plenum areas, use Level IV 22 AWG (0.34 mm AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). (See Tables 6 and 8 for part numbers.) Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved cables.
The Free Topology Transceiver (FTT) supports polarity insensitive free topology wiring. This frees the system installer from the need to wire using a bus topology. Star, bus, mixed, and loop wiring are all supported by this architecture. The maximum E-Bus length when using a combination of star, loop, and bus wiring (singly terminated) is 1640 ft (500m) with the maximum node-to­node length of 1312 ft (400m). In the event that the total wire length is exceeded, then a Q7740A 2-Way Repeater or a Q7740B 4-Way Repeater can be used to allow the number of devices to be spread out as well as increasing the length of wire over which they communicate. The maximum number of repeaters per segment is one (on either side of the router). A Q7751A E­Bus Router can also be used to effectively double the maximum E-Bus length. The advantage of using the router is that it will segregate traffic to a segment while when using the repeater, all traffic is repeated on each segment. When utilizing a doubly terminated E-Bus structure, use a continuous daisy-chain with no stubs or taps from the main backbone, The maximum E-Bus length is 4593 ft (1400m) with the maximum node-to-node length of 3773 ft (1150m).
) plenum or non-plenum rated
2
) such as U.S. part
2
) such as
FTT networks are very flexible and convenient to install and maintain, but it is imperative to carefully plan the network layout and create and maintain accurate documentation. Unknown or inaccurate wire run lengths, node-to-node distances, node counts, total wire length, and misplaced or missing terminators can cause poor network performance. Refer to E-Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules.
LonMark Functional Profile
W7761A Device supports the LonMark Preliminary Functional Profile for a Remote Input/Output Device.
Environmental: Operating Temperature:
-40° to 150°F (-40° to 65.5°C).
Shipping Temperature:
-40° to 150°F (-40° to 65.5°C).
Relative Humidity:
5% to 95% noncondensing.
Vibration:
Rated V2 level compliant.
Inputs/Outputs:
The W7761A Unit supports the following hardware features:
• Four 20KNTC (1000 through 150,000 ohm) or PT3000 (250 through 12,000 ohm) resistive analog inputs.
• Two 0.2 to 10 VDC or 2 to 20 mA (user selectable) analog inputs.
• Four dry contact digital inputs.
• Eight 24 Vac Triac digital outputs (500 mA MAX).
• One 22 Vdc power supply for auxiliary devices with a maximum current of 50 mA.
Analog Inputs:
Space Temperature:
Type: RTD.
12 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Supported Sensors: T7770A,B,C,D sensor—(current feature that can be used with the RIO Device) and T7780 DDWM.
Discharge Air Temperature:
Type: RTD. Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050, C7031K1017.
Outdoor Air Temperature:
Type: RTD. Supported Sensors: C7170A1002.
Return Air Temperature:
Type: RTD. Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050, C7031K1017.
Mixed Air Temperature:
Type: RTD. Supported Sensors: C7100A1015*, C7770A1006, C7031B1033, C7031C1031, C7031D1062, C7031J1050, C7031K1017.
*The PT3000 sensor is not recommended for floating control (real time - discharge or return configured as space sensor). The PT3000 sensor is intended for monitoring or differential (staged) control.
Outdoor Air Humidity:
Type: Voltage/Current. Supported Sensors: C7600B1000 and C7600B1018 (2 to 10V), C7600C1008 (4 to 20mA).
Return Air Humidity:
Type: Voltage/Current. Supported Sensors: C7600B1000 and C7600B1018 (2 to 10V), C7600C1008 (4 to 20mA).
Outdoor Air Enthalpy:
Type: Current. Supported Sensors: C7400A1004 (4 to 20mA).
Return Air Enthalpy:
Type: Current. Supported Sensors: C7400A1004 (4 to 20mA).
Air Filter Differential Pressure:
Type: Voltage. Supported Sensors: Third party 2 to 10V, 0 to 5 inw ( 0 to 1.25 kPa) differential pressure sensors.
Space CO
Sensor:
2
Type: Voltage. Supported Sensors: Third party 0 to 10V, 0 to 2000 ppm CO
Outdoor Air CO
Sensor:
2
sensors.
2
Type: Voltage. Supported Sensors: Third party 0 to 10V, 0 to 2000 ppm CO
sensors.
2
Outdoor Air CO Sensor:
Type: Current. Supported Sensors: Third party 4 to 20mA, 0 to 300 ppm CO sensor.
Monitor Sensor for network use:
Type: Voltage. Supported Sensors: Third party 2 to 10V, 2 to 10 volts displayed.
Digital Inputs:
Dry-contact inputs are sensed using a 9 milliamp at 4.8 volts detection circuit. It is very important that the device used contains high quality, noncorroding contacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as gold or silver) or pimpled or sealed contacts to assure consistent, long-term operation.
Triac Outputs:
Triac Outputs on the RIO: — Power ratings: 20 Vac to 30 Vac at 25 mA MIN to 500 mA MAX current for any voltage.
13 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
CAUTION
When any device is energized by a Triac, the device must be able to sink a minimum of 25 mA. NOTE: Triacs sink current to the 24 Vac common (COM terminal on the W7761A); see Fig. 19 for wiring example.
IMPORTANT:
If non-Honeywell motors, actuators, or transducers are to be used with Excel 10 Controllers, Triac compatibility must be verified (see previous NOTE).
Wall Modules
The T7770A,B,C,D Wall Module sensor—(current feature that can be used with the Excel 10 W7761A RIO Device). See Fig. 6.
KNOCKOUTS FOR EUROPEAN APPLICATIONS
5-1/16 (128)
60
55
65
70
KNOCKOUTS FOR EUROPEAN APPLICATIONS
75
80
85
5-1/16 (128)
3-5/32 (80)
2-3/8 (60)
2-3/8 (60)
T7770A1006
29/32 (23)
STANDARD UTILITY CONDUIT BOX (2 X 4) MOUNTING HOLES
3-5/32 (80)
2-3/8 (60)
9 8 7 6 5 4 3 2 1
W7752
DIP Switch S4 Settings:
XL600-XL20
W7753
LED RETURN
1,3,5=on; 2,4=off 2,4=on; 1,3,5=off 1,2,3,4=on; 5=0ff
BYPASS
LED
LED
LED
2-3/8 (60)
E-BUS
SENSOR
GND
SENSOR
AL COM
E-BUS
SETPT
BYPASS/FAN BYPASS/FAN
SETPT
T7770C
FAN
SETPT
SENSOR
GND
1-1/4 (32)
STANDARD UTILITY CONDUIT BOX (2 X 4) MOUNTING HOLES
M15119
Fig. 6. T7770A,B,C,D (T7770A,C shown) construction in in. (mm), sensor—(current feature that can be used with RIO
Device).
14 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
The T7780 DDWM for the Excel 10 Controllers (see Product Names section) is shown in Fig. 7.
3-5/32 (80)
KNOCKOUTS FOR EUROPEAN APPLICATIONS
1 (25)
5-1/16 (128)
2-3/8 (60)
2-3/8 (60)
STANDARD UTILITY CONDUIT BOX (2 X4) MOUNTING HOLES
M11391
Fig. 7. T7780 construction, subbase dimensions in in. (mm).
Configurations
Each W7761A device can control or monitor a variety of different types of mechanical equipment. The W7761A was not intended to control staged or modulating heating/cooling coils, mixed air economizer dampers, or system fan/heat pump units. The W7761A contains inputs and outputs, but no control software. All control that would be associated with the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for VAV control, temperature control, or any control function that would require less than a 30 second update rate. It would be suitable to control miscellaneous exhaust or ventilation fans, lighting zones that are spread out through a building which need to be linked to a start/stop time program through the Zone Manager or to enable freeze protection. The W7761A device can be connected to outdoor air temperature and humidity sensors that can be used by other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. The W7761A can be used to monitor Occupancy, Window, Dirty filter, Indoor air quality, and Smoke control sensors. This allows the controllers to use their physical inputs for monitoring other elements such as return humidity, IAQ, etc. to achieve better control. The W7761A can be used to
15 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
average many space temperature sensors that are located in a zone that is controlled by the W7750 Constant Volume AHU Controller.
Mixed-Output-Type Control
The W7761A Device can control mixed-output-types of applications such as PWM and staged control occurring simultaneously with Series 60 Floating Control.
Occupancy Sensor
Excel 10 W7761A device can be connected to an occupancy sensor through a digital input. This is a device, such as a passive infrared motion detector, that contains a dry contact (see following NOTE) closure to indicate whether or not people are present in the space. The Excel 10 W7761A Device expects a contact closure to indicate the space is Occupied. See Fig. 18 in Application Step 4, Prepare Wiring Diagrams, for details on wiring connections. This occupancy sensor can then be bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. This would allow the other Excel 10 controllers to use their physical inputs for monitoring other elements such as return humidity, IAQ, etc. to achieve better control.
NOTE: The Excel 10 Controllers (W7750 CVAHU and W7761A RIO) have limited power available (only 9 mA at 4.8 volts) for
The recommended devices for use with the Excel 10 W7750 Controller and W7761A Device are the EL7628A1007 Ceiling Mounted Infrared or the EL7680A1008 Wall Mounted Wide View Infrared Occupancy Sensors. If ultrasonic sensors are required, the EL7611A1003 and the EL7612A1001 Occupancy Sensors are recommended. An EL76XX Power Supply/Control Unit is required for use with these occupancy sensors. The EL7630A1003 can power up to four sensors, and is multi-tapped for several line voltages. The EL7621A1002 can power three sensors and it connects to 120 Vac line voltage. The EL7621A1010 can also power three sensors but it connects to 277 Vac line voltage.
checking the digital inputs for contact closures. It is very important that the device used contains high quality, noncorroding contacts with resistivity that does not degrade; that is, increase over time. Use noble metal (such as gold or silver), pimpled or sealed contacts to assure consistent, long-term operation.
Window Open/Closed Digital Input
Excel 10 W7761A device can be connected to a window sensor to indicate whether a window in the space was opened. The Excel 10 W7761A device can be connected to a dry contact (see the NOTE for the Occupancy Sensor and Fig. 18 in Application Step 4. Prepare Wiring Diagrams, for details) or a set of contacts wired in series (for monitoring multiple windows) to verify that the window(s) are closed. This window(s) sensor can then be bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. The algorithm in the other Excel 10 controllers expects a contact closure to indicate the window is closed. If an open window is detected, the algorithm in the other Excel 10 controllers changes the mode of operation to FREEZE_PROTECT, which shuts down the control functions, and watches for low space temperature conditions. The freeze protection setpoint is 46.4°F (8°C), and the frost alarm occurs at 42.8°F (6°C).
Wall Module Options
As previously discussed, there are five basic varieties of the T7770. There is one variety of the PT3000 sensor and the T7780 DDWM (see the Product Names and the Construction sections). The T7770A,B,C,D 20Kohm NTC sensor—(current feature that can be used with the RIO Device) and one PT3000 sensor can be configured on any of the four resistive inputs. The T7780 is an E-Bus node and would not be directly connected to the RIO Device.
Dirty Filter Monitor
The air filter in the air handler can be monitored by the W7761A RIO device and an alarm issued by the Zone Manager when the filter media needs replacement. The two methods of monitoring the filter are:
1. Connecting a differential pressure switch to a digital input on the W7761A.
2. Wiring a 2-to-10V differential pressure sensor to a voltage input on the W7761A. If the analog input sensor is used, its measured value 0 to 5 inw (0 to 1.25 kPa) is compared to a user-selectable setpoint. The comparison is done in the Zone Manager —valid range: 0 to 5 inw (0 to 1.25 kPa), and the Dirty Filter alarm is issued when the pressure drop across the filter exceeds the setpoint.
Indoor Air Quality (IAQ)
The Excel 10 W7761A device can monitor IAQ using one of two different methods of detecting poor air quality. The first is with an IAQ switch device connected to a digital input on the W7761A, where a contact closure indicates poor air quality, and an alarm can be issued by the Zone Manager. The device can detect poor air quality using any desired measure such as CO VOC, CO, etc. The second method, is through an analog input that connects to a CO
from this sensor (0 to 2000 ppm) is compared to a user-selectable setpoint (the comparison is done in the Zone
of CO
2
Manager —valid range: 0 to 2000 ppm), and an IAQ alarm can be issued when the CO sensor that is connected to the W7750 RIO, can be bound to other W7750 CVAHU Excel 10 controllers on the E-Bus.
16 74-2699
sensor (0 to 10V). The measured value
2
level exceeds the setpoint. The IAQ
2
,
2
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
APPLICATION STEPS
Overview
The seven application steps shown in Table 3 are planning considerations for engineering an Excel 10 W7761 Remote Input/Output Device. These steps are guidelines intended to aid understanding of the product I/O options, bus arrangement choices and the Excel 10 W7761A Devices role in the overall EXCEL 5000® System architecture.
Step No. Description
1 Plan The System 2 Determine Other Bus Devices Required 3 Lay Out Communication and Power Wiring 4 Prepare Wiring Diagrams 5 Order Equipment 6 Configure Devices 7 Troubleshooting
Step 1. Plan The System
Plan the use of the W7761A Devices according to the job requirements. Determine the location, functionality and sensor or actuator usage. Verify the sales estimate of the number of W7761A Devices and the number and type of output actuators and other required accessories. When planning the system layout, consider potential expansion possibilities to allow for future growth. Planning is very important to be prepared for adding HVAC systems and controllers in future projects. T7770A,B,C,D Wall Modules (sensor—current feature that can be used with the RIO Device)can be installed as either hardwired I/O-only devices or additional wiring can be run to them (for the E-Bus network ) to allow a CARE/E-Vision operator terminal to have access to the E-Bus. The application engineer needs to determine how many wall modules or other input sensors are required. This information is required during installation to ensure that the proper number and type of wires are pulled to the wall modules, and the building operators are informed about where they can plug in to the E-Bus network with a portable operator terminal (see Fig. 8 through 10).
Table 3 . Application Steps.
(;&(/  :$
,1387287387 '(9,&(
127(%22. 3&
6+,(/'(' ,17(5)$&(
56 6(5,$/ 3257
&$%/(
4$ 6/7$
&$%/( 3$57 12 
(%86 3257
0-'
Fig. 8. Connecting the portable operator terminal to the E-Bus.
The FTT communication loop, (E-Bus) between controllers is a free topology wiring scheme that supports star, loop, and/or bus wiring. Refer to the E-Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules. See Application Step 3. Lay Out Communications and Power Wiring, for more information on bus wiring layout, and see Fig. 16 through 19 in Application Step 4. Prepare Wiring Diagrams, for wiring details. The application engineer must review the Direct Digital Control (DDC) job requirements. This includes the Sequences of Operation for the Excel 10 controllers, and for the system as a whole. Usually there are variables that must be passed between the W7750 (CVAHU), Q7750A Zone Manager, W7761 (RIO), and other Excel 10 controller(s), or central plant controller(s) that are required for optimum system-wide operation. Typical examples are the TOD Occ/Unocc signal, the outdoor air temperature, demand limit control signal, and smoke control mode signal.
17 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
It is important to understand these interrelationships early in the job engineering process to ensure implementing when configuring the controllers. (See Application Step 6. Configure Devices, for information on the various Excel 10 parameters and on Excel 10 point mapping.)
Step 2. Determine Other Bus Devices Required
A maximum of 62 nodes can communicate on a single E-Bus segment. Each W7761A (RIO), W7750 (CVAHU), W7751 (VAV) Controller or T7780 Wall Module constitutes one node. If more nodes are required, a Q7751A Router is necessary. Using a router allows up to 125 nodes, divided between two E-Bus segments. The router accounts for two of these nodes (one node on each side of the router); a Q7750A Excel 10 Zone Manager takes one node and two nodes are available for operator terminal nodes, leaving 120 nodes available for Excel 10 Controllers and T7780 Wall Modules. All 120 controllers and T7780 Wall Modules are able to talk to each other through the router. A Q7750A Excel 10 Zone Manager is required to connect the E-Bus to the standard EXCEL 5000® System C-Bus. Each Excel 10 Zone Manager can support no more than 120 Excel 10 Controllers and T7780 Wall Modules. This limit is set in the Excel 10 Zone Manager database as an absolute maximum. Each E-Bus segment is set up with two unused nodes to allow for a CARE/E-Vision or Hand Held Tool (HHT) to be connected to the E-Bus. Multiple CARE/E-Vision or HHT terminals can be connected to the bus at the same time. Table 4 summarizes the E-Bus segment configuration rules.
Table 4 . E-Bus Configuration Rules And Device Node Numbers.
One E-Bus Segment Example Maximum Number of Nodes Equals 62
One Q7750A Excel 10 Zone Manager 1 node
Port for operator terminal access (CARE/E-Vision or HHT) 1 node
Maximum number of Excel 10s and T7780s 60 nodes (Only T7780 Wall Modules are E-Bus nodes)
Total 62 nodes
Two E-Bus Segments Example Maximum Number of Nodes Equals 125
One Q7750A Excel 10 Zone Manager 1 node
One Q7751A Router 2 nodes (1 in each Bus Segment)
Ports for operator terminal access (two CARE/E-Vision or HHT
terminals)
Maximum number of Excel 10s and T7780s in segment number
Maximum number of Excel 10s and T7780s in segment number
Refer to the E-Bus Wiring Guidelines form, 74-2865 for complete description of network topology rules and the maximum wire length limitations. If longer runs are required, a Q7740A 2-way or Q7740B 4-way repeater can be added to extend the length of the E-Bus. A Q7751A Router can be added to partition the system into two segments and effectively double the length of the E-Bus. Only one router is allowed with each Excel 10 Zone Manager and each network segment can have a maximum of 1 repeater. In addition, all E-Bus segments require the installation of a Bus Termination Module for a singly terminated E-Bus or two Bus Termination Modules for a doubly terminated E-Bus. For more details on E-Bus termination, refer to the E-Bus Wiring Guidelines form, 74-2865, or see Application Step 3. Lay Out Communications and Power Wiring, and the E-Bus Termination Module subsection in Application Step 4.
2 nodes (1 in each Bus Segment)
60 nodes (Only T7780 Wall Modules are E-Bus nodes)
one
60 nodes (Only T7780 Wall Modules are E-Bus nodes)
two
Total 125 nodes
Step 3. Lay Out Communications and Power Wiring
E-Bus Layout
The communications bus, E-Bus, is a 78-kilobit serial link that uses transformer isolation and differential Manchester encoding. Approved cable types for E-Bus communications wiring is Level IV 22 AWG (0.34 mm unshielded, twisted pair, solid conductor wire. For nonplenum areas, use Level IV 22 AWG (0.34 mm AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). See Tables 9 and 10 for part numbers. Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved cables. The FTT communications bus, E-Bus, supports a polarity insensitive, free topology wiring scheme that supports star, loop, and/or bus wiring. E-Bus networks can be configured in a variety of ways, so refer to the E-Bus Wiring Guidelines form, 74-2865 for a complete description of network topology rules and Table 4. Fig. 9 and 10 depict two typical E-Bus network topologies; one as a singly terminated bus segment that has 60 nodes or less, and one showing a doubly terminated segment. The bus configuration is set up using the Network Manager tool from within CARE (see the CARE User’s Manual form, 74-5587 or Excel E-Vision User’s Guide form, 74-2588).
2
) plenum or non-plenum rated
2
), such as U.S. part
2
) such as
18 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
NOTE: For wiring details see the E-Bus Termination Module subsection in Step 4. For wall module wiring, US part AK3782
(non-plenum) or US part AK3792 (plenum) can be used. These cables contain two twisted pairs (one for the run down to the wall module, and one for the run back up to the controller) for ease of installation.
(;&(/ 
89
7
% 7(50,1$7,21 02'8/(6 $7 (1'6 2) (%86 '$,6<&+$,1
(;&(/  9$9
(;&(/  4$ )77 =21( 0$1$*(5
72 &%86 6(( ),* 
(%86
(;&(/  9$9
(%86
(;&(/ 
89
(;&(/  9$9
(;&(/  9$9
(;&(/  9$9
6+$5(' 7
83 72  727$/ 12'(6
(%86
(;&(/ 
5,2
(;&(/ 
5,2
(;&(/ 
5,2
7V
:,7+ 12 (%86
$&&(66
7
(%86
,2 &211(&7,216
Fig. 9. Bus wiring layout for doubly terminated daisy-chain E-Bus segment.
7
7
7
-$&. )25 23(5$725 7(50,1$/
0-'
19 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
(%86 6(*0(17 180%(5
(;&(/  9$9
7
(%86 6(*0(17 180%(5
(;&(/  9$9
(;&(/  4$ )77 =21( 0$1$*(5
(;&(/ 
89
72 &%86 6(( ),* 
(%86 $&&(66
(;&(/ 
5,2
(;&(/ 
5,2
% 7(50,1$7,21 02'8/(
(;&(/  9$9
(%86 6(*0(17 180%(5
7
(%86 $&&(66
(;&(/ 
89
% 7(50,1$7,21 02'8/(
4$ )77 (%86 5287(5
(;&(/ 
89
0-'
Fig. 10. Bus wiring layout for two singly terminated E-Bus segments.
NOTE: See the E-Bus Termination Module section for wiring details.
IMPORTANT
Notes on communications wiring:
All field wiring must conform to local codes and ordinances.
Approved cable types for E-Bus communications wiring is Level IV 22 AWG (0.34 mm2) plenum or non-plenum
rated unshielded, twisted pair, solid conductor wire. For nonplenum areas, use Level IV 22 AWG (0.34 mm as U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair). In plenum areas, use plenum-rated Level IV, 22 AWG (0.34 mm
2
) such as U.S. part AK3791 (one pair) or U.S. part AK3792 (two pair). See Tables 9 and 10 for part
2
), such
numbers. Contact Echelon Corp. Technical Support for the recommended vendors of Echelon approved cables. Unswitched 24 Vac power wiring can be run in the same conduit as the E-Bus cable.
Do not use different wire types or gauges on the same E-Bus segment. The step change in line impedance
characteristics causes unpredictable reflections on the bus. When using different types is unavoidable, use a Q7751A Router at the junction. In noisy (high EMI) environments, avoid wire runs parallel to noisy power cables, or lines containing lighting
dimmer switches, and keep at least 3 in. (76 mm) of separation between noisy lines and the E-Bus cable. Make sure that neither of the E-Bus wires is grounded.
Power Wiring
A power budget must be calculated for each Excel 10 W7761 Device to determine the required transformer size for proper operation. A power budget is simply the summing of the maximum power draw ratings (in VA) of all the devices to be controlled by an Excel 10 W7761 Device. This includes the device itself, the equipment actuators (ML6161, or other motors) and various contactors and transducers, as appropriate, for the Excel 10 configuration.
Power Budget Calculation Example
The following is an example power budget calculation for a typical W7761A Excel 10 Device. Device VA Information Obtained from the Excel 10 W7761 6.0 VA W7761 Device Specification Data
20 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
ML6161 2.2 VA TRADELINE® Damper Actuator Catalog
R8242A 21.0 VA TRADELINE® Contactor for fan Catalog in-rush rating
M6410A Steam 0.7 VA TRADELINE® Heating Coil Valve Catalog, 0.32A at 24 Vac
The Excel 10 System example requires 29.9 VA of peak power; therefore, a 40 VA AT72D Transformer is able to provide ample power for this device and its accessories. Alternatively, a 75 VA AT88A Transformer could be used to power two Excel 10 Systems of this type, or a 100 VA AT92A Transformer could be used to power three of these controllers and meet NEC Class 2 restrictions (no greater than 100 VA). See Fig. 12 through 14 for illustrations of power wiring details. See Table 5 for VA ratings of various devices.
W7761A Excel 10 W7761 Device 6.0 ML6161A/B Damper Actuator, 35 lb-in. 2.2 R8242A Contactor 21.0 R6410A Valve Actuator 0.7 MMC325 Pneumatic Transducer 5.0 ML684 Versadrive Valve Actuator 12.0 ML6464 Damper Actuator, 66 lb-in. 3.0 ML6474 Damper Actuator, 132 lb-in. 3.0 ML6185 Damper Actuator SR 50 lb-in. 12.0
TOTAL: 29.9 VA
Table 5 . VA Ratings For Transformer Sizing.
Device Description VA
For contactors and similar devices, the in-rush power ratings should be used as the worst case values when performing power budget calculations. Also, the application engineer must consider the possible combinations of simultaneously energized outputs and calculate the VA ratings accordingly. The worst case, that uses the largest possible VA load, should be determined when sizing the transformer.
Line Loss
Excel 10 Controllers must receive a minimum supply voltage of 20 Vac. If long power or output wire runs are required, a voltage drop due to Ohms Law (I x R) line loss must be considered. This line loss can result in a significant increase in total power required and thereby affect transformer sizing. The following example is an I x R line-loss calculation for a 200 ft (61m) run from the transformer to a W7761 Device drawing 37 VA using 18 AW G (1.0 mm
2
) wire. The formula is: Loss = [length of round-trip wire run (ft)] x [resistance in wire (ohms per ft)] x [current in wire (amperes)] From specification data: 18 AWG twisted pair wire has 6.52 ohms per 1000 feet. Loss = [(200 ft) x (2 - round-trip) x (6.52/1000 ohms per ft)] x [(37 VA)/(24V)] = 4.02 volts This means that four volts are going to be lost between the transformer and the device; therefore, to assure the device receives at least 20 volts, the transformer must output more than 24 volts. Because all transformer output voltage levels depend on the size of the connected load, a larger transformer outputs a higher voltage than a smaller one for a given load. Fig. 11 shows this voltage load dependence. In the preceding I x R loss example, even though the device load is only 37 VA, a standard 40 VA transformer is not sufficient due to the line loss. From Fig. 11, a 40 VA transformer is just under 100 percent loaded (for the 37 VA device) and, therefore, has a secondary voltage of 22.9 volts. (Use the lower edge of the shaded zone in Fig. 11 that represents the worst case conditions.) When the I x R loss of four volts is subtracted, only 18.9 volts reaches the device, which is not enough voltage for proper operation. In this situation, the engineer basically has three alternatives:
1. Use a larger transformer; for example, if an 80 VA model is used, see Fig. 11, an output of 24.4 volts minus the four volt line loss supplies 20.4V to the device. Although acceptable, the four-volt line-loss in this example is higher than recommended. See the following
IMPORTANT
2. Use heavier gauge wire for the power run. 14 AWG (2.0 mm using the preceding formula, gives a line-loss of only 1.58 volts (compared with 4.02 volts). This would allow a 40 VA transformer to be used. 14 AWG (2.0 mm
.
2
) wire is the recommended wire size for 24 Vac wiring.
2
) wire has a resistance of 2.57 ohms per 1000 ft which,
3. Locate the transformer closer to the device, thereby reducing the length of the wire run, and the line loss.
The issue of line-loss is also important in the case of the output wiring connected to the Triac digital outputs. The same formula and method are used. The rule to remember is to keep all power and output wire runs as short as practical. When necessary, use heavier gauge wire, a bigger transformer, or install the transformer closer to the device.
IMPORTANT
21 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
No installation should be designed where the line loss is greater than two volts to allow for nominal operation if the primary voltage drops to 102 Vac (120 Vac minus 15 percent).
To meet the National Electrical Manufacturers Association (NEMA) standards, a transformer must stay within the NEMA limits. The chart in Fig. 11 shows the required limits at various loads. With 100 percent load, the transformer secondary must supply between 23 and 25 volts to meet the NEMA standard. When a purchased transformer meets the NEMA standard DC20-1986, the transformer voltage-regulating ability can be considered reliable. Compliance with the NEMA standard is voluntary. The following Honeywell transformers meet this NEMA standard:
Transformer Type VA Rating
AT20A 20 AT40A 40 AT72D 40 AT87A 50
AK3310 Assembly 100
27 26 25 24 23
22
21 20 19
18
SECONDARY VOLTAGE
17 16 15
14
0 50 100 150
% OF LOAD
Fig. 11. NEMA class 2 transformer voltage output limits.
200
M993
Attach earth ground to W7761 Device terminal 1. See Fig. 12, 13 and 14, 16 through 20.
TRIAC` COMMON
TRANSFORMER
CONNECT POWER TO ` TERMINALS 24 AND 25
W7761A
1
EARTH` GROUND
TRIAC LINES` TO ACTUATORS` ANDCONTACTORS
20222425
M10089
Fig. 12. Power wiring details for one Excel 10 per transformer.
22 74-2699
TRANSFORMER
LINEVOLTAGE
`
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
120/240 VAC
IMPORTANT
If the W7761A Device is used on Heating and Cooling Equipment (UL 1995 US only) devices and the transformer primary power is more than 150 volts, connect the transformer secondary to earth ground, see Fig. 14.
24VAC
W7761A W7761A W7761A
2425
1
EARTH` GROUND
1
EARTH` GROUND
2425
1
EARTH` GROUND
Fig. 13. Power wiring details for two or more Excel 10s per transformer.
GREATER` THAN 150 VAC
24 VAC
TRANSFORMER
W7761A
2425
M10090
Fig. 14. Transformer power wiring details for one Excel 10 used in UL 1995 equipment (U.S. only).
IMPORTANT
Notes on power wiring:
EARTH` GROUND
1` IF THE W7761 CONTROLLER IS USED IN UL 1995 EQUIPMENT AND `
THEPRIMARYPOWERISMORETHAN150VOLTS,GROUNDONE` SIDE OF TRANSFORMER SECONDARY.
1
1
EARTH` GROUND
M10088
All field wiring must conform to local codes and ordinances. To maintain NEC Class 2 and UL ratings, the installation must use transformers of 100 VA or less capacity. For multiple controllers operating from a single transformer, the same side of the transformer secondary must be connected to the same input terminal in each device and the ground terminals (1 on the W7761A) must be connected to a verified earth ground for each device in the group. See Fig. 13. (Device configurations are not necessarily limited to three devices per transformer.) For the W7761A Device (which has Triac outputs), all output devices must be powered from the same transformer as the one powering the Excel 10 W7761A Device. Use the heaviest gauge wire available, up to 14 AWG (2.0 mm2) with a minimum of 18 AWG (1.0 mm2) for all power and earth ground connections. To minimize EMI noise, do not run Triac output wires in the same conduit as the input wires or the E-Bus communications loop. Unswitched 24 Vac power wiring can be run in the same conduit as the E-Bus cable.
23 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Make earth ground connections with the shortest possible wire run using 14 AWG (2.0 mm2) wire. A good earth
ground is essential for W7761A operation. Ideally, connect the earth ground to the ground bus at a motor control center or circuit breaker panel. However, if the nearest ideal earth ground is inaccessible, consider an alternate source for earth ground. Metal water pipe is generally a good ground, but do not use sprinkler pipe if prohibited by local codes. Attention must be given when duct work, conduit, or rebar are to be considered as ground sources. It is the responsibility of the installer to assure that these structures are tied back to a known earth ground.
Step 4. Prepare Wiring Diagrams
General Considerations
The purpose of this step is to assist the application engineer in developing job drawings to meet job specifications. Wiring details are included for the W7761A device the T7770A,B,C,D wall module (sensor—current feature that can be used with the RIO Device) and the T7780 DDWM. The drawings detail I/O, power, and communication bus wiring connections.
NOTE: For field wiring, when two or more wires are to be attached to the same connector block terminal, be sure to twist
them together. Deviation from this rule can result in improper electrical contact. See Fig. 15.
2
The connector block terminals on the W7761A and on the T7770 accept 14 through 22 AWG (2.0 to 0.34 mm
) wire. Table 6
lists wiring types, sizes, and length restrictions for Excel 10 products.
Table 6 . Field Wiring Reference Table.
Wire
Function
E-Bus (Plenum)
Recommended
Minimum Wire
Size AWG (mm
22 AWG (0.34 mm
2
)
2
) Construction
Twisted pair solid conductor, nonshielded or Echelon approved shielded cable.
Specification
or
Requirement Vendor Wire Type
Level IV 140°F
(60°C) rating
Honeywell AK3791 (one twisted pair) AK3792 (two twisted pairs)
Maximum Length
ft (m)
Refer to E-Bus Wiring Guidelines for maximum length
E-Bus (Non­Plenum)
22 AWG (0.34 mm
2
)
Twisted pair solid conductor, nonshielded or Echelon approved shielded cable.
Level IV 140°F
(60°C) rating
Honeywell AK3781 (one twisted pair) AK3782 (two twisted pairs)
Refer to E-Bus Wiring Guidelines for maximum length
I
nput Wiring Sensors Contacts
Output Wiring Actuators Relays
Power Wiring
18 to 22 AWG (1.0 to 0.34 mm
14 AWG (2.0
2
)
mm (18 AWG (1.0
2
) acceptable
mm for short runs)
14 AWG (2.0 mm
2
)
Multiconductor (usually five-
2
)
wire cable bundle). For runs >200 ft (61m) in noisy EMI areas, use shielded cable.
Any pair nonshielded (use heavier wire for longer runs).
Any pair nonshielded (use heavier wire for longer runs).
140°F (60°C) rating
NEC Class 2 140°F (60°C) rating
NEC Class 2 140°F (60°C) rating
Standard thermostat wire 1000 ft (305m)
for 18 AWG 200 ft (61m) for 22 AWG
Honeywell AK3702 (18 AWG) AK3712 (16 AWG) AK3754 (14 AWG) or equivalent
Honeywell AK3754 (14 AWG) twisted pair AK3909 (14 AWG) single conductor or equivalent
Limited by line-loss effects on power consumption. (See Line Loss subsection.)
Limited by line-loss effects on power consumption. (See Line Loss subsection.)
W7761A Devices
Fig. 16 through 20 illustrate W7761A Device wiring for various configurations. Connections to the wall module terminals (4 through 6) and the communications terminals (14 and 15) are made at terminal blocks. Connection for access to the E-Bus is provided by plugging the connector into the communications jack. NOTE: If an Excel 10 W7761A Device or Zone Manager is not connected to a good earth ground, the device internal transient
protection circuitry is compromised and the function of protecting the device from noise and power line spikes cannot be fulfilled. This can result in a damaged circuit board and require replacing the device.
24 74-2699
3/8`
`
(10)
STRIP 3/8 IN. (10 MM) FROM WIRES `
1. 2. TWIST WIRES TOGETHER ` TO BE ATTACHED AT ONE TERMINAL.
WITH PLIERS (A MINIMUM ` OF THREE TURNS).
Fig. 15. Attaching two or more wires at terminal blocks.
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
TWO 14 AWG` (2.0 MM2) WIRES
3. C UT TWIST ED END OF WIRE S TO 3/ 16 IN. (5 MM) ` BEFORE INSERTI NG IN TO TERM IN AL A ND TIGHTENING` SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M10086
See Table 7 for a description of the W7761A terminals.
Table 7 . W7761A I/O Description.
Terminal
Terminal
Number Description
OUT 8 16 Digital Output 8 OUT 7 17 Digital Output 7 OUT 6 18 Digital Output 6 OUT 5 19 Digital Output 5 OUT 4 20 Digital Output 4 OUT 3 21 Digital Output 3 OUT 2 22 Digital Output 2 OUT 1 23 Digital Output 1 +24Vac (H) 25 Power for the device COM (N) 24 Return for power to device E-Bus 15 Echelon® comm unications screw terminals E-Bus 14 Echelon® comm unications screw terminals DI -4 31 Digital Input 4 DGND 30 Digital Ground DI -3 29 Digital Input 3 DI -2 28 Digital Input 2 DGND 27 Digital Ground DI -1 26 Digital Input 1 22 VDC out 13 22 Vdc power supply for auxiliary devices with a maximum current of 50 mA. AI-6 12 Analog Input 6 voltage or current AGND 11 Analog ground AI-5 10 Analog Input 5 voltage or current AI-4 9 Analog Input 4 resistance AGND 8 Analog ground AI -3 7 Analog Input 3 resistance AI-2 6 Analog Input 2 resistance
25 74-2699
GROUND 5 Analog ground AI-1 4 Analog Input 1 resistance
3 Not Used 2 Not Used
EGND 1 Earth Ground
See Fig. 20 to wire a pneumatic transducer to a W7761A.
+
24 VAC
-
31 30 29 28 27 26 25 24 23 22 21 20
GND
DI-3
DI-2
GND
DI-4
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
C7770A AIR TEMPERATURE SENSOR
19 18 17 16
OUT 1
OUT 3
DI-1
24 VAC
24 VAC COM
OUT 2
OUT 4
OUT 5
OUT 6
OUT 7
OUT 8
W7761A
TRIAC EQUIVALENT CIRCUIT
REMOTE I/O DEVICE
AI-6 V/mA
22 VDC OUT
13
2
E-BUS
GND
E GND
NOT USED
NOT USED
12345678
1
AI-1 OHM
7 69 8 54321
SENSOR
GND
E-BUS
AI-3 OHM
AI-2 OHM
2
E-BUS
GND
GND
AI-5 V/mA
AI-4 OHM
9 101112 14 J315
JACK FOR E-BUS NETWORK ACCESS
T7770A WALL MODULE
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM WITH A MINIMUM OF 18 AWG (1.O MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
2
), FOR EARTH GROUND WIRE.
E-BUS
E-BUS
M15276
2
JACK
)
Fig. 16. Typical T7770A and C7770A wiring diagram. (For note 2, refer to Fig. 15.)
26 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
+
24 VAC
-
30 29 28 27 26 2 5 24 23 22 21 20
31
DI-4
W7 761 A
DI-2
DI-3
GROUND
DI-1
COM
OUT 1
24 VAC
GROUND
24 VAC
TRIAC EQUIV AL ENT CIRCUIT
OUT 2
OUT 3
OUT4
19 18 17 1 6
OUT5
RE M O T E I/O DE VIC E
AI- 1 O H M
C7600C
GRO U N D
+ S
NOT
USED
EARTH
GROUND
1234 5678
1
Humidity
(4 to 20mA)
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.
1
USE THE HEAVIEST GAUGE WIRE AVAILABLE,UP TO 14 AWG (2.OMM2) WITH A M IN IM U M OF 18 A WG (1.O MM2), FOR EARTH GROU N D WIRE.
TO ASSURE PROPERELECTRICAL CONTACT, WIRES MUST BE TWISTED
2
TOGETHER BEFO RE INSERTION INTO THE TERMINAL B LOCK.
AI-3 OHM
AI-2 OHM
GROUN D
9101112 1415
C7400A
Enthalpy
(4 to 20mA)
GROUND
AI-6 V/mA
AI-5 V/mA
AI-4 OHM
+ S
22 VDC OUT
13
E-BUS
2
OUT 7
OUT 6
OUT8
E-BUS
JACK
J3
E-B
Fig. 17. Typical Humidity and Enthalpy (4 to 20mA) sensor wiring diagram. (For note 2, refer to Fig. 15.)
27 74-2699
WINDOW CONTACT (CONTACT CLOSED = WINDOW CLOSED)
OCCUPANCY SENSOR (CONTACT CLOSED = OCCUPIED)
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
+
24 VAC
-
31 30 29 28 27 26 25 24 23 22 21 20
OUT 1
OUT 2
24 VAC COM
TRIAC EQUIVALENT CIRCUIT
DI-4
DI-3
GND
W7761A
DI-2
GND
24 VAC
DI-1
OUT 3
OUT 4
19 18 17 16
OUT 6
OUT 5
REMOTE I/O DEVICE
AI-6 V/mA
22 VDC OUT
13
2
E-BUS
GND
E GND
NOT USED
NOT USED
12345678
1
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM WITH A MINIMUM OF 18 AWG (1.O MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
AI-1 OHM
AI-3 OHM
AI-2 OHM
GND
9 101112 14 J315
GND
AI-5 V/mA
AI-4 OHM
2
), FOR EARTH GROUND WIRE.
OUT 7
OUT 8
E-BUS
JACK
E-BUS
M15277
2
)
Fig. 18. Typical Window and Occupancy sensor wiring diagram. (For note 2, refer to Fig. 15.)
28 74-2699
PWM
VALVE ACTUATOR
ML7984B
24 (H)
24 (N)
PWM
(H 24 VAC)
PWM OUTPUT
T6 T5 C B W R
FROM CNTRL
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
LINE POWER
+
24 VAC
-
31 30 29 28 27 26 25 24 23 22 21 20
24 VAC
DI-4
DI-3
GND
W7761A
DI-2
GND
DI-1
24 VAC COM
TRIAC EQUIVALENT CIRCUIT
CONTACTOR (24 VAC)
OUT 1
OUT 3
OUT 2
19 18 17 16
OUT 5
OUT 4
REMOTE I/O DEVICE
AI-6 V/mA
22 VDC OUT
13
2
E-BUS
GND
E GND
NOT USED
NOT USED
12345678
1
1
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM WITH A MINIMUM OF 18 AWG (1.O MM
2
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK.
AI-1 OHM
AI-3 OHM
AI-2 OHM
GND
9 101112 14 J315
GND
AI-5 V/mA
AI-4 OHM
2
), FOR EARTH GROUND WIRE.
OUT 6
FAN
OUT 7
E-BUS
E-BUS
OUT 8
JACK
2
M15279
)
Fig. 19. Typical PWM Valve Actuator and miscellaneous fan control to W7761A. (For note 2, refer to Fig. 15.)
29 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
MMC325 PNEUMATIC TRANSDUCER
24 (H)
24 (N)
24 (H)
24 (N)
INCREASE
DECREASE
1
24 VAC
2
3
+
-
31 30 29 28 27 26 25 24 23 22 21 20
OUT 1
OUT 3
OUT 2
24 VAC COM
TRIAC EQUIVALENT CIRCUIT
GND
DI-3
DI-2
DI-4
W7761A REMOTE I/O DEVICE
GND
24 VAC
DI-1
M
M
4
B
PNEUMATIC
VALVE
19 18 17 16
OUT 6
OUT 5
OUT 4
OUT 7
OUT 8
AI-6 V/mA
22 VDC OUT
13
E-BUS
E-BUS
JACK
2
M15278
)
GND
E GND
NOT USED
NOT USED
12345678
5
REVERSE WIRES (INCREASE/DECREASE) TO REVERSE ACTION
1
(DIRECT/REVERSE).
2
MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN: REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION.
3
OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER.
4
USE 1/4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE MUST BE 6 FT. (1.8M) OR LONGER.
EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM.
5
USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 14 AWG (2.O MM WITH A MINIMUM OF 18 AWG (1.O MM
AI-1 OHM
AI-3 OHM
AI-2 OHM
GND
9 101112 14 J315
GND
AI-5 V/mA
AI-4 OHM
2
), FOR EARTH GROUND WIRE.
Fig. 20. Typical Pneumatic transducer (Series 60 - Floating) to W7761A.
E-Bus Termination Module
One E-Bus Termination Module, part number 209541B is required for a single terminated E-Bus or two E-Bus Termination Module, part number 209541B for a double terminated E-Bus (see Fig. 21). Refer to the E-Bus Wiring Guidelines form, 74­2865 for termination module placement rules.
30 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
W7753A
W7753A
1415 1415
BROWN
ORANGE
PART NO. 209541B TERMINATION MODULE
PART NO. 209541B TERMINATION MODULE
W7753A
BROWN
1415
ORANGE
M12690
Fig. 21. Typical E-Bus termination module wiring diagrams (place a wire nut on each remaining wire that is not
connected to a controller or device).
See Fig. 22 for E-Bus termination wiring options.
31 74-2699
D
$
86( )25 '28%/< 7(50,1$7(' '$,6<&+$,1 6(*0(17
,17(51$/
7(50,1$7,21
1(7:25.
,17(51$/
7(50,1$7,21
1(7:25.
7(50,1$/ %/2&. )25 4$ =21( 0$1$*(5
),(/' ,167$//('
-803(5
(%86 (%86
),(/' ,167$//(' -803(5
6,1*/< 7(50,1$7(' 6(*0(17
$ (QDEOLQJ ,QWHUQDO 7HUPLQDWLRQ 1HWZRUN XVLQJ
MXPSHUV LQ WKH 4$ =RQH 0DQDJHU
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
:$
3$57 12 % 7(50,1$7,21 02'8/(
% ,QVWDOOLQJ (%XV 7HUPLQDWLRQ 0RGXOH :$
(%86
(%86
3$57 12 % 7(50,1$7,21 02'8/(
,16(57 ,172 7(50,1$/6 $1' :,7+ 7+( (%86 :,5( 7(50,1$7,21 02'8/( ,6 3+<6,&$//< /2&$7(' %(+,1' 7+( 7 ,16,'( 7+(;2500%2;
& (%XV 7HUPLQDWLRQ 0RGXOH LQVWDOOHG
DW[RUPPER[PRXQWHG 7
3$57 12 % 7(50,1$7,21 02'8/(
(%86
( ,QVWDOOLQJ (%XV 7HUPLQDWLRQ 0RGXOH
DW :+ WHUPLQDOV  DQG 
6(*0(176
2,,,
$%
2,,,
&
/$%(/ 21 4% :$< 5(3($7(5
127( 4% :$< 5(3($7(5 6+2:1 4$ :$< 5(3(
2,,,
6:,7&+(6 21 6,'( 81'(5 4$% &,5&
%2$5' 86( 60$// )/$7 2%-(&7 72 029( 7+( 6:,7&+(6 $6 1(('(' )520 326,7,21 2 12 7(50,1$7,21 326,7,21 , 6,1*/< 7(50,1$7(' 326,7,21 ,, '28%/< 7(50,1$7('
2,,,
'
+$6 7:2 6:,7&+(6
' (%XV 7HUPLQDWLRQ QHWZRUN VZLWFKHV LQ WKH 4$% 5HSHDWHUV
5- 3/8*
4$ (%86 5287(5
1(7
3$57 12 % 7(50,1$7,21 02'8/(
(%86
:,5( 1876
) 7ZLVW ZLUHV DQG DWWDFK ZLUH QXWV WR 5- $GDSWHU
FDEOHV (%XV VHJPHQW ZLUHV DQG 7HUPLQDWLRQ 0RGXOH
WR FRQQHFW WR D 4$% 5RXWHU
0 -'
Fig. 22. E-Bus termination wiring options.
32 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Step 5. Order Equipment
After compiling a bill of materials through completion of the previous application steps, refer to Table 8 for ordering information. Contact Honeywell for information about Controllers and Wall Modules with no logo.
Table 8. Excel 10 W7761A Device Ordering Information.
Part Number Product Description Comments
Excel 10 W7761A
W7761A2002 Remote Input/Output Device
Excel 10 W7750 Controllers:
W7750A1007 Constant Volume AHU Controller (W7750A) — W7750B1005 Constant Volume AHU Controller (W7750B)
T7770 Wall Modules:
T7770A1006 Sensor with Honeywell Logo (Not used with RIO) Used with Excel 5000 and Excel 10 Controllers T7770A1014 Sensor with No Logo (Not used with RIO) Used with Excel 5000 and Excel 10 Controllers T7770A2004 Sensor with Network Jack and Honeywell Logo Used with Excel 5000 and Excel 10 Controllers T7770A2012 Sensor with Network Jack and No Logo Used with Excel 5000 and Excel 10 Controllers T7770B1004 Sensor with Setpoint and Network Jack, Honeywell
Logo
T7770B1046 Sensor with Setpoint and Network Jack, Honeywell
Logo
T7770B1012 Sensor with Setpoint and Network Jack, No Logo Degrees F Absolute. Sensor—(current feature
T7770B1020 Sensor with Setpoint and Network Jack, Honeywell
Logo
T7770B1053 Sensor with Setpoint and Network Jack, No Logo Relative Setpoint. Sensor—(current feature
T7770B1038 Sensor with Setpoint and Network Jack, No Logo Degrees C Absolute. Sensor—(current feature
T7770C1002 Sensor with Setpoint, Bypass/LED and Network
Jack, Honeywell Logo
T7770C1044 Sensor with Setpoint, Bypass/LED and Network
Jack, Honeywell Logo
T7770C1010 Sensor with Setpoint, Bypass/LED and Network
Jack, No Logo
T7770C1028 Sensor with Setpoint, Bypass/LED and Network
Jack, Honeywell Logo
T7770C1051 Sensor with Setpoint, Bypass/LED and Network
Jack, No Logo
T7770C1036 Sensor with Setpoint, Bypass/LED and Network
Jack, No Logo
T7770D1000 Sensor with Bypass/LED and Network Jack,
Honeywell Logo
T7770D1018 Sensor with Bypass/LED and Network Jack, No
Logo
T7780A1004 Sensor, Digital Display Wall Module with Network
Jack, Honeywell Logo
T7780A1012 Sensor, Digital Display Wall Module with Network
Jack, No Logo
Sensors:
C7770A1006 Air Temperature Sensor. 20 Kohm NTC
nonlinearized
Degrees F Absolute. Sensor—(current feature that can be used with the RIO Device).
Relative Setpoint. Sensor—(current feature that can be used with the RIO Device).
that can be used with the RIO Device). Degrees C Absolute. Sensor—(current feature
that can be used with the RIO Device).
that can be used with the RIO Device).
that can be used with the RIO Device). Degrees F Absolute. Sensor—(current feature
that can be used with the RIO Device). Relative Setpoint. Sensor—(current feature
that can be used with the RIO Device). Degrees F Absolute. Sensor—(current feature
that can be used with the RIO Device). Degrees C Absolute. Sensor—(current feature
that can be used with the RIO Device). Relative Setpoint. Sensor—(current feature
that can be used with the RIO Device). Degrees C Absolute. Sensor—(current feature
that can be used with the RIO Device). Degrees F Absolute. Sensor—(current feature
that can be used with the RIO Device). Degrees C Absolute. Sensor—(current feature
that can be used with the RIO Device). Degrees F Absolute (default)
Degrees F Absolute (default)
Duct-mounted sensor that functions as a primary and/or secondary sensor.
(continued)
33 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
g
Table 8. Excel 10 W7761A Device Ordering Information (Continued).
Part Number Product Description Comments
Sensors (Continued):
C7031J1050 Averaging Discharge/Return Air Temperature
C7031B1033 Discharge Air or Hot Water Temperature Sensor.
C7031C1031 Duct Discharge/Return Air Sensor. 20 Kohm 18 in. (457mm) insertion length. C7031D1062 Hot or chilled Water Temperature Sensor. 20 Kohm
C7031K1017 Hot or chilled Water Temperature Sensor. 20 Kohm
C7100A1015 Averaging Discharge/Return Air Temperature
C7170A1002 Outdoor Air Temperature Sensor. PT3000
Q7750A1003 Excel 10 Zone Manager Free Topology Tranceiver (FTT) Q7751A2002 Router (FTT) Q7752A2001 Serial Interface (FTT) Q7740A1008 Excel 10 2-Way Repeater Used to extend the length of the E-Bus.
Q7740B1006 Excel 10 4-Way Repeater Used to extend the length of the E-Bus.
XD 505A Standard C-Bus Communications Submodule — XD 508 C-Bus Communications Submodule (1 megabit baud
209541B Termination Module One or two required per E-Bus segment 205979 Operator Terminal Cable for E-Bus Serial interface to wall module or controller
EL7680A1008 Wall Mounted Wide View Infrared Occupancy
EL7628A1007 Ceiling Mounted Infrared Occupancy Sensor — EL7611A1003,
EL7612A1001 EL7630A1003,
EL7621A1002, EL7621A1010
C7400A1004 Solid State Enthalpy Sensor (4 to 20 mA) For outdoor and return air enthalpy C7600B1000 Solid State Humidity Sensor (2 to 10 V) For outdoor and return air humidity C7600C1008 Solid State Humidity Sensor (4 to 20 mA) For outdoor and return air humidity C7600C1018 Solid State Humidity Sensor (2 to 10 V) For outdoor and return air humidity MMC325-010,
MMC325-020
MMCA530 DIN rail adapter for MMC325 Transducers — MMCA540 Metal enclosure for MMC325 Transducers — ML7984B3000 Valve Actuator Pulse Width Modulation (PWM) Use with V5011 or V5013 F and G Valves ML6161B1000 Damper Actuator Series 60 — M6410A Valve Actuator Series 60 Use with V5812/V5813 Valves ML684A1025 Versadrive Valve Actuator with linkage, Series 60 Use with V5011 and V5013 Valves ML6464A1009 Direct Coupled Actuator, 66 lb-in., Series 60
Sensor. 20 Kohm NTC
20 Kohm NTC
NTC
NTC
Sensor. PT3000
Echelon® Based Components and Parts:
rate)
Accessories:
Sensor
Ultrasonic Occupancy Sensors
Power Supply/Control Units for Occupancy sensors
Pneumatic Retrofit Transducers. Select pressure ran or (020) 0 to 20 psi (137.93 kPa).
e: (010) 0 to 10 psi (68.97 kPa)
Duct element cord length 12 ft. (3.7m)
Use 112622AA Immersion Well
Strap-on
13 in. (330mm) insertion length.
Contains built in termination modules.
Contains built in termination modules.
Use to control Pneumatic reheat valves
(continued)
34 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table 8. Excel 10 W7761A Device Ordering Information (Continued).
Part Number Product Description
Accessories (Continued):
ML6474A1008 Direct Coupled Actuator, 132 lb-in. torque, Series 60 — ML6185A1000 Direct Coupled Actuator, 50 lb-in. spring return Series 60 EL7680A1008 Wall Mounted Wide View Infrared Occupancy Sensor — EL7628A1007 Ceiling Mounted Infrared Occupancy Sensor — EL7611A1003,
Ultrasonic Occupancy Sensors
EL7612A1001 EL7630A1003,
Power Supply/Control Units for Occupancy sensors EL7621A1002, EL7621A1010
C7400A1004 Solid State Enthalpy Sensor (4 to 20 mA) For outdoor and return air enthalpy C7600B1000 Solid State Humidity Sensor (2 to 10 V) For outdoor and return air humidity C7600C1008 Solid State Humidity Sensor (4 to 20 mA) For outdoor and return air humidity C7600C1018 Solid State Humidity Sensor (2 to 10 V) For outdoor and return air humidity MMC325-010,
MMC325-020
Pneumatic Retrofit Transducers.
Select pressure range: (010) 0 to 10 psi (68.97 kPa)
Use to control Pneumatic reheat valves
or (020) 0 to 20 psi (137.93 kPa). MMCA530 DIN rail adapter for MMC325 Transducers — MMCA540 Metal enclosure for MMC325 Transducers — ML7984B3000 Valve Actuator Pulse Width Modulation (PWM) Use with V5011 or V5013 F and G Valves ML6161B1000 Damper Actuator Series 60 — M6410A Valve Actuator Series 60 Use with V5812/V5813 Valves ML684A1025 Versadrive Valve Actuator with linkage, Series 60 Use with V5011 and V5013 Valves ML6464A1009 Direct Coupled Actuator, 66 lb-in., Series 60 — ML6474A1008 Direct Coupled Actuator, 132 lb-in. torque, Series 60 — ML6185A1000 Direct Coupled Actuator, 50 lb-in. spring return Series 60 V5812A Two-way terminal unit water valve; 0.19, 0.29, 0.47,
0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm) or
2.9 and 4.9 Cv 3/4 in. npt (19 mm)
Use with M6410 Valve Actuator. Close-off rating for 0.19 to 1.9 Cv is 65 psi; for 2.9 and 4.9, Cv is 45 psi. (Coefficient of volume or capacity index C minute divided by the square root of the pressure drop across the valve.)
V5813A Three-way mixing terminal unit hot water valve; 0.19,
0.29, 0.47, 0.74, 1.2, and 1.9 Cv 1/2 in. npt (13 mm)
or 2.9 and 4.9 Cv 3/4 in. npt (19 mm)
Use with M6410 Valve Actuator. Close-off rating 0.19 to 0.74 Cv is 55 psi; 1.2, and
1.9 Cv is 22 psi; 2.9 and 4.9 Cv is 26 psi. R8242A Contactor, 24 Vac coil, DPDT — AT72D, AT88A, AK3310, etc. Transformers — EN 50 022 DIN rail 35 mm by 7.5 mm (1-3/8 in. by 5/16 in.) Obtain locally: A controller requires 5 in.
Augat Inc. part number 2TK2D DIN rail (adapter) Purchase from Augat Inc. two DIN rail
adapters for each controller
Serial Interface Cable, male DB-9 to female DB-9 or
female DB-25.
Obtain locally from any computer hardware vendor.
Cabling
Honeywell AK3791 (one twisted pair) AK3792 (two twisted pairs)
Honeywell AK3781 (one twisted pair) AK3782 (two twisted pairs)
E-Bus (plenum): 22 AWG (0.34 mm solid conductor, nonshielded or Echelon approved cable.
E-Bus (nonplenum): 22 AWG (0.34 mm solid conductor, nonshielded or Echelon approved cable.
2
) twisted pair
2
) twisted pair
Level IV 140°F (60°C) rating
Level IV 140°F (60°C) rating
Honeywell AK3725 Inputs: 18 AWG (1.0 mm2) five wire cable bundle Standard thermostat wire
Comments
= gallons per
(continued)
35 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table 8. Excel 10 W7761A Device Ordering Information (Continued).
Part Number Product Description Comments
Cabling (Continued):
Honeywell AK3752
Outputs/Power: 14 to 18 AWG (2.0 to 1.0 mm2) NEC Class 2 140°F (60°C) rating
(typical or equivalent) Honeywell AK3702
18 AWG (1.0 mm2) twisted pair Non-plenum
(typical or equivalent) Honeywell AK3712
16 AWG (1.3 mm2) twisted pair Non-plenum
(typical or equivalent) Honeywell AK3754
14 AWG (2.0 mm2) two conductor Non-plenum
(typical or equivalent)
Step 6. Configure Devices
Excel E-Vision PC Software is used to configure W7761A Devices to match their intended application. The E-Vision User Guide form, 74-2588 provides details for operating the PC software.
Step 7. Troubleshooting
Troubleshooting Excel 10 Controllers and Wall Modules
In addition to the following information, refer to the Installation Instructions and Checkout and Test manual for each product. See the Applicable Literature section for form numbers.
Temperature Sensor and Setpoint Potentiometer Resistance Ranges
The T7770 Wall Module or the C7770A Air Temperature Sensor has the following specified calibration points, which are plotted in Fig. 23:
Temperature (°F) Resistance Value (ohms)
99 11,520 85 16,301 70 24,039 55 36,280 45 48,000
80K
70K
60K
50K
40K
30K
RESISTANCE (OHMS)
20K
10K
30
Fig. 23. Temperature sensor resistance plots.
40 50 60 70
0
10
TEMPERATURE (DEGREES)
20K OHM AT
o
F (25oC)
77
80
20
90
30
100
110
40
M5874A
o
F
o
C
Alarms
When an Excel 10 has an alarm condition, it reports it to the central node on the E-Bus (typically, the Excel 10 Zone Manager). See Table 9. Information contained in an alarm message is:
Subnet Number: E-Bus subnet that contains the Excel 10 node that has the alarm condition. Subnet 1 is on the Zone Manager side of the router; Subnet 2 is on the other side.
Node Number: Excel 10 node that has the alarm condition (see Network Status).
Alarm Type: Specific alarm being issued. An Excel 10 can provide the alarm types listed in Table 9.
36 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
r
c
s
t
Table 9. Excel 10 Alarms.
Name of alarm or error bit
RETURN_TO_NORMAL 128U Return to no alarm after being in an alarm condition. This code is added
ALARM_NOTIFY_DISABLED 255U The alarm reporting has been turned off by the DestManMode. No more
NO_ALARM 0 No alarms presently detected. INPUT_NV_FAILURE 1 One or more NV inputs have failed in receiving an update within their spe
NODE_DISABLED 2 The control algorithm has stopped because the RIO device is in
SENSOR_FAILURE 3 One or more sensors have failed.
NOTE: The node can be reset by switching the node to MANUAL and then to the normal operating mode.
Alarm type
number Meaning of alarm code or error bit
numerically to another alarm code to indicate that the alarm condition has returned to normal.
alarms are reported via nvoAlarm until DestManMode turns on alarm repo or upon application restart.
FAILURE_DETECT_TIME.
DISABLED_MODE, MANUAL, or FACTORY_TEST mode. No more alarm reported when the device is in the DISABLED_MODE. Alarms continue to reported if the device is in the MANUAL or FACTORY_TEST mode. The control is shut down and disabled until power is cycled or the node is rese See note 1 below.
Also, the Excel 10 variables,
AlarmLogX
where X is 1 through 5, that store the last five alarms to occur in the device, are
available. These points can be viewed through XBS or E-Vision.
Broadcasting the Service Message
The Service Message allows a device on the E-Bus to be positively identified. The Service Message contains the device ID number and, therefore, can be used to confirm the physical location of a particular Excel 10 in a building. There are two methods of broadcasting the Service Message from an Excel 10 W7761A Device. One uses a hardware service pin button on the side of the device (see Fig. 24). The other involves using the PC Configuration tool, as follows.
The commissioning tool is used to perform the ID Assignment task (see the E-Vision User’s Guide form, 74-2588).
SERVICE PIN BUTTON
M10094
Fig. 24. Location of the Service Pin Button.
W7761A Device Status LED
The LED on the front and center of a W7761A Device provides a visual indication of the status of the device. See Fig. 25. When the W7761A receives power, the LED should appear in one of the following allowable states (see Table 10):
37 74-2699
Table 10. LED States.
Alarm Condition
Hardware or
Software Failure
Service LED Blink Rate
(Cycles per second)
None None 1 Any alarm condition None 2 Don't Care Failed steady ON or OFF
1. Off—no power to the processor.
2. Continuously On—processor is in initialized state.
3. Slow Blink—controlling, normal state.
4. Fast Blink—when the Excel 10 has an alarm condition.
3
1
3
0
2
9
2
D
8
1
4
G
2
R
O
7
U
N
D
2
D
1
3
6
2
D
5
1
2
G
R
O
U
N
D
D
1
1
2
4
V
A
C
2
C
4
O
M
2
3
2
O
U
1
T
W7750
2
2
1
2
O
U
2
T
O
U
T
3
O
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
0
1
9
1
8
1
U
7
4
T
1
O
U
5
T
6
O
U
T
6
O
U
7
T
O
U
T
8
E
A
R
T
H
`
E
L
D
B
Y
P
G
A
S
S
R
O
S
U
N
D
E
N
S
O
R
G
R
O
U
N
D
S
E
T
P
T
A
1
1
R
G
R
O
U
N
D
A
1
2
R
A
1
3
`
G
R
O
U
N
D
A
1
4
V
m
/
A
V
/
m
A
2
2
V
D
C
`
E
B
U
S
O
U
T
1
1
1
2
1
3
1
4
1
5
J
3
STA TUS` LED
1
2
3
4
5
6
7
8
9
1
0
M10095
Fig. 25. LED location on W7761A.
T7780 DDWM Bypass Pushbutton
See Fig. 26 for the T7780 DDWM bypass pushbutton location (occupied or unoccupied). The T7780 DDWM has two methods for generating its neuron ID, shorting two pads or winking.
1.
Pressing the bypass pushbutton whenever a Carat (∇) on the bottom of the LCD display is flashing (Menu Selection Mode).
2.
Pressing the bypass pushbutton when the T7780A DDWM is in wink mode (LCD display shows sends a Service Message out on the E-Bus).
When the space covered by the T7780 DDWM is in Occupied mode, the sun symbol is shown on the left side of the LCD display. When the space is in Standby mode, the half-sun symbol is shown. When the space is in Unoccupied mode, the moon symbol is shown.
WINK
when E-Vision
38 74-2699
APPENDICES
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
T7780A
BYPASS PUSHBUTTON
M11616
Fig. 26. Bypass pushbutton location on T7780 DDWM.
Appendix A. Using E-Vision to Commission a W7761 Device.
CARE/E-Vision must be used to configure the W7761 device. The inputs and outputs will be configured through the application selection menu (see E-Vision user guide form, 74-2588). The RIO does not contain control loops for directly controlling the digital outputs, therefore the Zone Manager or some other device has to be bound to the outputs to perform the control function. Refer to the CARE User’s Manual form, 74-5587 to add Control Strategy, Switching Logic, or Time Programs for control of the RIO digital outputs. Refer to the E-Vision user guide (form, 74-2588 for the RIO commissioning procedure and updating/downloading of the Zone Manager files.
NOTE: The RIO device does not synchronize the floating digital outputs. This function (position is synchronized whenever an
SENSOR CALIBRATION
The resistive temperature sensors and
not supported on the W7761A.
sensed value using E-Vision menus (see E-Vision user guide form, 74-2588). When calibrating voltage/current sensors on the W7761A, the offset amount entered by the user is in volts, regardless of the inputs actual engineering units. See Appendix E for information on how to derive the proper voltage value to enter as an offset during calibration.
CUSTOM MAPPING
The RIO default CARE plant contains all available points that are supported on the RIO device. If the RIO plant was customized by deleting unused points, then the Custom mapping feature will have to be used to add points back into the plant so that they can be used or monitored by other devices. The following procedures will describe the Custom mapping process for adding analog/digital inputs and digital outputs.
endpoint is reached (full open or full close).and when the elapsed time since the last synchronization is 24 hours) must be done by the controlling device (such as the Zone Manager).
Perform the sensor calibration by adding an offset value (either positive or negative) to the
voltage/current
inputs can all be calibrated. The wall module setpoint potentiometer
is
ADDING ANALOG INPUTS - ENTHALPY (4 to 20 mA)
To add an enthalpy (outdoor or return air) sensor to an RIO plant, the user must add a software point (pseudo analog) that can be mapped to the actual hardware input through the Custom Mapping function of E-Vision. The following procedure will instruct the user on adding the pseudo analog and using the Custom Mapping function. This allows the enthalpy input to be used with other Excel 10 controllers (referenced) on the E-Bus, used in Zone Manager control strategy or switching logic, or be used with Excel 5000 controllers on the C-Bus.
1.
With CARE running, open an existing RIO plant. The user can go into either switching logic or control strategy to add the pseudo analog point. If the user does not have an existing control loop through control strategy, use switching logic to add the pseudo point, otherwise a control loop will have to be created along with unnecessary RACL to add the point.
39 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
This procedure will use switching logic to add the pseudo analog point. With the RIO plant having the focus, go into switching logic. Select the dialog box will be displayed. Type in a New point name for the enthalpy sensor (such as button. The new point that was just created will be added to the screen as the header point for switching logic table and also added to the switching logic by selecting the Click the
2.
Go into the just created and click the mA (mA matches the engineering unit of the RIO input) engineering units are displayed. Select the mA engineering unit that is shown with one decimal place (number 66) and click the
Address
3.
Translate the Zone Manager and Export the Zone Manager files to E-Vision by selecting the
Vision
displayed. Select the project and the Zone manager within that project that is being exported and click the Exit CARE and Start E-Vision. Select the E-Vision project to open and the CARE Export Filename created above. Once the project is open, select the RIO device that the enthalpy sensor is connected to and go into the screen (offline) by selecting the
Cancel
list box and select
menu items. Type in the name of the Zone Manager Export file when the
Point List
button to continue.
Data Point Editor (Controller/Edit/Data Point Editor
Application Selection
selection.
4.
Select the analog point. If this function has already been performed before, the user will be prompted with the message CARE Export File has already been imported, do you want to import again?. Select import is finished, E-Vision displays the message CARE Export File has been imported. Select
5.
Select the
Points
CARE. Under (both names should be the same). Next, select the be displayed. Select the address in the RIO device that contains the actual sensor value for the OaEnthalpy (C7400A1004, 4 to 20 mA device). Select the
Controller
Network
dialog box. Under
menu item and then
Unmapped Excel 10
Map
button to add the OaEnthalpy point to the list of
Custom Mapping CARE Points
6.
To use the OaEnthalpy custom mapped point with other Excel 10 controllers on the E-Bus, select the
Refer Excel 10 Points
and
Points
: until you reach
example if the user had selected a CVAHU controller from the
Excel 10 Points
between the RIO and CVAHU controllers. If
Least
one of the output network variables is in an existing connection and E-Vision will not allow this association to be
added. In order to add this association, the user has to remove any other associations with the
Close
the change in an existing association will require commissioning.
7.
Select the to the Zone Manager files. When the to be commissioned, then close the E-Vision project and exit out of E-Vision.
8.
Start CARE and open the Zone Manager that was just updated through the start XI584 by selecting the
Transfer Import
and click OK on the
Import
dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set
by the XI581 Emulation function (
Download
select When the lighted and select the part in controller (CPU address or Controller name). When the download is complete, exit out of the box. From the XI584 main menu, select the
For User Address
the point and select the device. This point can now be used in the Zone Manager control strategy or switching logic. This point can be used in other Excel 5000 (C-Bus) controllers by assigning a global analog point in the destination controller with the user address name of 5000 controllers.
list as the destination point and then click on the
button to exit out of the
Controller
menu items and select
. The
Select Controller/Subsystem
and click the
OaEnthalpy
Software Points
. Select the
File
OK
button. Select the drop down list for the
File/Exit
menu item and then
Cancel
button to exit the
menu item and
to exit out of the Data Point Editor.
Exit
. CARE will display the
Pseudo Analog
Create/Select Software Point <Va
. The
OaEnthaply
Create/Select Software Point <Va
Delete Unused Software Points
) and under
OK
button to save the selection. Cancel the
Point
select the pseudo analog point that was
Engineering Unit
and scroll through the list until the
Project
Export Zone Manager
) and click on the
> dialog box. Exit
list box.
User
Export to E-
and
dialog box is
Export
Application Selection
dialog box, add Oa_Enthalpy to either analog input 5 or 6 and select the OK button to save the
Controller
menu item and then
, then the
Import
Map C-Bus Points
Unmapped CARE
, select the name of the RIO device that the actual enthalpy sensor was added to
OaEnthalpy
dialog box. Click on the
. Select the RIO device name as the
CurrentAI
and select it. Select an Excel 10 controller from the
, select the name of the RIO device that the enthalpy sensor was added to in
point under
DestOaEnth
Refer Excel 10 Points
menu item and the
Update Zone Manager Files
Update Zone Manager Files
Controller, Tools
and
CARE Import
Select Target Controller
Applications, XI581 Emulation
Download
OK
dialog box will be displayed. Check the
dialog box is displayed, make sure that the correct CPU address or name is high
button. Click the
Download
Data, Access by User Address
Search
Attributes
. Refer to the CARE User’s Manual form, 74-5587 for information on creating global points in Excel
button. When the
button. XI584 will now display the value of the enthalpy sensor connected to the RIO
Application Selection
from CARE to import the Zone Manager files with the new pseudo
. Select
Custom
CARE Points
button and the
and
Mapped Points
Close
button to exit the
Source Excel 10
menu items. From the
Yes
to continue with the Import. When the
RIO1
as the Controller Type from the
Custom Mapping CARE Points
CurrentAI
Excel 10
under
. Click on the
Map C-Bus Points
and then scroll down the list of
Destination Excel 10
Destination Excel 10
Add
is already being used in an association, then the message
dialog box. Any controllers involved in the new association or
button to add the point association (Binding)
. E-Vision will add the custom mapping information
function is done, commission any controllers that need
list, the user would select from the
Update Zone Manager Files
XI584
. Select the project and the Zone Manager that was just updated and select
menu items. Once XI584 is started, select the
dialog box. When the CARE Import is complete, close the
menu). Select the
button and click
OaEnthalpy
All
Yes
to the message
menu items. Type
point displays in the
Utilities, File Transfer
selection and click the
Inputs
tab of the
OK
to continue.
Map C-Bus
. CurrentAI is the user
Close
dialog box.
dialog box will
button to exit the
Network
list. For
DestOaEnth
point. Select
function and
Utilities
menu items and
Controller
Replace
updated application
Download
OaEnthalpy
User Addresses
in the
list, click on
menu item
Excel 10
and
CARE
button.
dialog
Search
>
OK
button.
At
File
ADDING OTHER VOLTAGE/CURRENT SENSORS
See Table A-1 for the supported Voltage/Current analog input sensors that can be connected to the RIO Device. The user must add a software point (pseudo analog - in RIO CARE Plant) that can be mapped to the actual hardware input (RIO Plant) through the Custom Mapping function of E-Vision. The procedure described previously for adding an enthalpy ( 4 to 20 mA) sensor should be followed and instructs the user on adding the pseudo analog point in the RIO CARE Plant and using the
40 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the E-Bus, that are used in the Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.
Table A-1. Supported Voltage And Current Input Sensors.
E-Vision Enumerated Name in the Input
RA_Hum_C7600C Humidity1 or Humidity2 OA_Hum_C7600C Humidity1 or Humidity2 Filter_Diff_Pres Pressure1 or Pressure2 RA_Hum_C7600B Humidity1 or Humidity2 OA_Hum_C7600B Humidity1 or Humidity2 RA_Enthalpy CurrentAI OA_Enthalpy CurrentAI Space_CO2 CO2Level Voltage_Monitor VoltageAI
ADDING DIGITAL INPUTS
See Table A-2 for the supported Digital input types that can be connected to the RIO Device. The user must add a software point (pseudo digital nstate - in RIO CARE Plant) that can be mapped to the actual hardware input (RIO Plant) through the Custom Mapping function of E-Vision. The procedure described previously for adding an enthalpy ( 4 to 20 mA) sensor should be followed. The user will add a Plant and then use the Custom Mapping function. From there it can be used with other Excel 10 controllers (referenced) on the E-Bus, that are used in Zone Manager control strategy or switching logic, or are used with Excel 5000 controllers on the C-Bus.
E-Vision Enumerated Name in the Input
Digital Input 1: Active_Short / Active_Open
Digital Input 2: Active_Short / Active_Open
Digital Input 3: Active_Short / Active_Open
Digital Input 4: Active_Short / Active_Open
Application Selection Tab
Pseudo Digital nstate point
Table A-2. Supported Digital Input Types.
Application Selection Tab
(<Vd>) in step one instead of the Pseudo Analog to the RIO CARE
RIO Network Variable that contains the
Hardware Input Value
RIO Network Variable that contains the
Hardware Input Value
SrcDigIn1Sts
SrcDigIn2Sts
SrcDigIn3Sts
SrcDigIn4Sts
ADDING DIGITAL OUTPUTS
See Table A-3 for the supported digital output types that can be connected to the RIO Device. The user must add a software point (pseudo analog) that can be mapped to the actual hardware output through the Custom Mapping function of E-Vision. The following procedure will instruct the user on adding the pseudo analog and using the Custom Mapping function so that the Digital Output can be used in the Zone Manager control strategy or switching logic, or be used with Excel 5000 controllers on the C-Bus.
1.
With CARE running, open an existing RIO plant. The user can go into either switching logic or control strategy to add the pseudo analog point. If the user does not have an existing control loop through control strategy, use switching logic to add the pseudo point, otherwise a control loop will have to be created along with unnecessary RACL to add the point. This procedure will use switching logic to add the pseudo analog point. With the RIO plant having the focus, go into switching logic. Select the dialog box will be displayed. Type in a New point name for the Digital Output (such as button. The new point that was just created will be added to the screen as the header point for switching logic table and also added to the switching logic by selecting the Click the
2.
Go into the just created and the
Cancel
engineering units
OK
button to save the selection.
the
Editor
3.
. Translate the Zone Manager and Export the Zone Manager files to E-Vision by selecting the Vision menu items. Type in the name of the Zone Manager Export file when the
Point
button to continue.
Data Point Editor (Controller/Edit/Data Point Editor
are displayed. Select the Pct engineering unit that is shown with one decimal place (number 55) and
Software Points
list. Select the
File
OK
button. Select the drop down list for the
menu item and then
Cancel
menu item and
Cancel
button to exit the
User Address
the
Exit
. CARE will display the
41 74-2699
Pseudo Analog
Create/Select Software Point <Va
. The
MiscExhFan
Create/Select Software Point <Va
Delete Unused Software Points
) and under
Engineering Unit
list box and select
Point
select the pseudo analog point that was
and scroll through the list until the
File/Exit
to exit out of the
Export Zone Manager
) and click on the
> dialog box. Exit
Project
and
dialog box is
list box.
Data Point
Export
to E-
>
OK
Pct
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
displayed. Select the project and the Zone manager within that project that is being exported and the CARE and Start E-Vision. Select the E-Vision project to open and the CARE Export Filename created previously. Once the project is open, select the RIO device that the Digital Output is connected to and go into the screen (offline) by selecting the
Selection OK
4.
Select the analog point. If this function has already been performed before, the user will be prompted with the message
Export File
import is finished, E-Vision displays the message
5.
Select the
Points
CARE. Under names should be the same). Next, select the displayed. Select the add the
Points
6.
Re-commission the RIO device that had the custom mapping done.
7.
Select the to the Zone Manager files. When the Update Zone Manager Files function is done, close the E-Vision project and exit out of E-Vision.
8.
Start start XI584 by selecting the
Transfer Import Import
by the XI581 Emulation function ( select When the highlighted and select the part in controller (CPU address or Controller name). When the download is complete, exit out of the box. From the
For User Address
on the point and select the device. To command the
greater
point can now be used in the Zone Manager control strategy or switching logic and Time Programs. This point can be used in other Excel 5000 controllers (C-Bus) by assigning a global analog point in the destination controller with the user address name of MiscExhFan. Refer to the CARE User’s Manual form, 74-5587 for information on creating global points in Excel 5000 controllers.
dialog box, select the first Unused_DigOutput and scroll up until
button to save the selection.
Controller
has already been imported, do you want to import again?. Select
Network
dialog box. Under
menu item and then
menu item and then
Unmapped Excel 10
MiscExhFan
MiscExhFan
dialog box. Click on the
Controller
CARE
and open the Zone Manager that was just updated through the
menu items and select and click OK on the dialog box. If this is the initial loading of the Zone Manager, then it will have to be reset and the CPU address set
Download
point to the list of
menu item and the
Download
. The
Select Controller/Subsystem
XI584
main menu, select the
and click on the
. To command the
Controller, Application Selection
Import
from CARE to import the Zone Manager files with the new pseudo
CARE Export File
Map C-Bus Points
Unmapped CARE
, select the name of the RIO device that the actual Digital Output was added to (both
point under
Close
, select the name of the RIO device that the Digital Output was added to in
Custom
button and the
CARE Points
Mapped Points
button to exit the
. Click on the
Map C-Bus Points
Update Zone Manager Files
Controller, Tools
CARE Import
Select Target Controller
XI584
and
. Select the project and the Zone Manager that was just updated and select
menu items. Once XI584 is started, select the
dialog box. When the CARE Import is complete, close the
Applications, XI581 Emulation
dialog box will be displayed. Check the
OK
button. Click the
dialog box is displayed, make sure that the correct CPU address or name is
Download
Data, Access by User Address
Search
Attributes
MiscExhFan
MiscExhFan
button. When the
button. XI584 will now display the value of the Digital Output connected to the RIO
to the On mode, put the point in the
Off
to the
mode, put the point in the
menu items. From the
has been imported. Select OK to continue.
. Select
RIO1
Custom Mapping CARE Points
DigOut1Cmd
and
Close
. E-Vision will add the custom mapping information
menu). Select the
button and
Yes
MiscExhFan
Discrete1
as the Controller Type from the
button to exit the
dialog box.
is displayed and select it. Select the
Yes
to continue with the Import. When the
Excel 10
under
. Select the
Custom Mapping CARE
Update Zone Manager Files
Utilities, File Transfer
All
selection and click the
Outputs
to the message
menu items. Type
point displays in the
Manual
mode and enter a value of
Manual
Replace
mode and enter a value of
Export
button. Exit
Application Selection
tab of the
Application
CARE
Map C-Bus
dialog box will be
Map
button to
function and
Utilities, File
CARE
menu items and
Controller
updated application
Download
MiscExhFan
User Addresses
button.
dialog
in the
list, click
1.0 or
0.0
Search
. This
Table A-3. Supported Digital Output Types.
E-Vision Enumerated Name in the Output
Application Selection Tab
Float1_Open through Float8_Open (Series 60 ­requires two outputs assigned. Float1_Open must be assigned before Float1_Close)
Float1_Close through Float8_Close (Series 60
- requires two outputs assigned. Float1_Open must be assigned before Float1_Close)
Discrete1 through Discrete8 (Maintained On/Off outputs)
Modulate1 through Modulate8 (PWM outputs) DigOut1Cmd through DigOut8Cmd
RIO Network Variable that contains the
Hardware Output Value
DigOut1Cmd through DigOut8Cmd
DigOut1Cmd through DigOut8Cmd
DigOut1Cmd through DigOut8Cmd
Appendix B. Sequences of Operation.
Common Operations
The Excel 10 W7761A Device contains inputs and outputs, but no control software. All control that would be associated with the inputs and outputs in the W7761A would be accomplished though the Excel Zone Manager and would not be suitable for VAV control, temperature control, or any control function that would require less than a 30 second update rate. The analog and digital sensors could be shared or bound to other Excel 10 controllers on the E-Bus or Excel 5000 controllers on the C-Bus through the Excel 10 Zone Manager. This would allow the other Excel 10 controllers to use their physical inputs for monitoring other elements such as return humidity, IAQ, etc. to achieve better control.
Room Temperature Sensor (RmTemp)
42 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
The T7770A,B,C,D wall module is the room space temperature sensor—(current feature that can be used with the RIO Device). When it is configured, it provides the temperature input that can be shared with the W7750 or W7751 controllers. If there are multiple space sensors in a area controlled by one W7750 CVAHU, then the space temperatures can be wired into the W7761A controller and mapped to the Zone Manager. The Zone Manager can average all of the space temperatures and then have that value can be bound to the W7750 controlling that area.
Window Sensor (StatusWndw)
The digital input for a window contact can be wired into the W7761A device and then bound to a W7750 CVAHU to disable its temperature control algorithm if someone has opened a window or door in the room or area that the W7750 is serving. When a window is detected to be Open (digital input contacts Open equals window open), the normal temperature control is disabled, and the W7750 Controller enters the Freeze Protect mode. Freeze Protect mode sets the space setpoint to 50 °F (10°C) and brings on the fan and heat if the space temperature falls below this setpoint. Normal temperature control resumes on window closure.
Dirty Filter Monitor
The air filter in the air handler can be monitored by a digital input in the W7761A and an alarm issued by the Zone Manager when the filter media needs replacement. The two methods of monitoring the filter are:
1. A differential pressure switch whose contacts are connected to a digital input on the W7761A and;
2. A 2 to 10V differential pressure sensor wired to a voltage input on the W7761A. If the analog input sensor is used, its measured value 0 to 5 inw (0 to 1.25 kPa) is compared to a user-selectable setpoint in the Zone Manager, the comparison is done in the Zone Manager - valid range: 0 to 5 inw (0 to 1.25 kPa), and the Dirty Filter alarm is issued by the Zone Manager when the pressure drop across the filter exceeds the setpoint.
Series 60 Modulating Control
Series 60 Control is also commonly referred to as Floating Control. The Excel 10 W7761A Device can drive Series 60 type actuators to control a modulating damper or valve actuator. The W7761A device contains no control software, so these outputs would have to be bound to either the Zone Manager or other Excel 10 controllers. When floating control is used, the full-stroke motor drive time of the actuator must be entered into the configuration parameter DO1FlSpeed (for output 1), DO2FlSpeed (for output 2). When Floating control is configured, two digital outputs are required, so the user has to change the configuration parameter for the appropriate digital outputs.
Pulse Width Modulating (PWM) Control
The Excel 10 W7761A device can drive a PWM-type actuator to control a modulating actuator. The W7761A device contains no control software, so these outputs would have to be bound to either the Zone Manager or other Excel 10 controllers. PWM control positions the actuator based on the length, in seconds, of the pulse from the digital output. The controller outputs a pulse whose length consists of two parts, a minimum and a maximum. The minimum pulse time represents the analog value of zero percent (also indicates a signal presence) and the maximum pulse length that represents an analog value of 100 percent. If the analog value is greater than zero percent, an additional time is added to the minimum pulse time. The length of time added is directly proportional to the magnitude of the analog value. If PWM control is used, the configuration parameters for the PWM operation must be specified. These parameters are DO1PWMPeriod and PWMZeroScale, and PWMFullScale.
Example: To find the pulse width of a valve actuator (for example stroke mid position - 50 percent) with the PWMZeroScale =
0.1 seconds, PWMFullScale = 25.5 seconds, and the PWMPeriod = 25.6 seconds. There are 256 increments available, so the number of increments required for 50 percent would be (0.5 X 256) or 128. The time for each increment for this industry standard pulse time is 0.1 seconds. The pulse width is the minimum time (0.1 second) + the number of increments (128 times the seconds added 0.1) = 12.9 seconds. The W7750B Controller would command the valve output on for 12.9 seconds every
25.6 seconds to maintain the valve position at 50 percent.
Indoor Air Quality (IAQ) Override
The Excel 10 W7761A Device can monitor an IAQ sensor and that input can be bound to a W7750 CVAHU Controller that supports an IAQ override feature, that upon detection of poor air quality in the space, allows the economizer dampers to be opened above the standard minimum position setting to a value set in EconIAQPos (parameter located in W7750). Two different methods of detecting poor air quality are supported, The first is by using an IAQ switch device connected to a digital input on the W7761A Device, where a contact closure indicates poor air quality. This digital input would then be bound to the W7750 Controller that is serving the area being monitored and would initiate the IAQ override mode. The second is through an analog input that connects to a CO mapped into the Zone Manager where it is compared to a setpoint (parameter located in the Zone Manager). When the CO
Sensor (0 to 10V). The measured value of CO2 from this sensor (0 to 2000 ppm) is
2
2
level is higher than the setpoint, the Zone Manager can initiate an IAQ alarm. A pseudo digital point in the Zone Manager can be bound to the W7750 CVAHU Controller which can initiate the IAQ override mode.
43 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Appendix C. Complete List of Excel 10 W7761A Remote I/O Device User Addresses.
C1. Input/Output Points. C2. Control Parameters. C3. Status Points. C4. Configuration Parameters. C5. Direct Access And Special Points.
Table C0 lists the applicable Engineering Units for the analog points found in the W7761A.
Measured Item Description Abbreviation Description Abbreviation Temperature Relative
Temperature Relative Humidity Air Flow CO2 Concentration Enthalpy
Differential Pressure
Tables C1 through C5 list all network variables associated with the W7761A Controller and the default User Address names. Table C1 lists the Network Variable Inputs and Outputs, which are stored in RAM memory. Table C2 lists the Control Parameters, which are the values stored in the controllers EEPROM memory.
Degrees Fahrenheit F Degrees Celsius C Delta Degrees Fahrenheit DDF Degrees Kelvin K
Percent % Percent % Cubic Feet per Minute CFM Meters cubed per hour m3h Parts Per Million PPM Parts Per Million PPM British Thermal Units per Pound
of Air Inches of Water Column inw kiloPascal kPa
Table C0. Engineering Units For Analog Points.
English Units (Inch-Pound) Standard International Units (SI)
btu/lb kiloJoules/kilogram kJ/kg
NOTE: Table C2. User Addresses For W7761A Control Parameters. (Control Parameters are stored in EEPROM - limited to
Tables provides point attributes as follows:
Engineering Units— This field indicates the point valid range and displayed Engineering Unit. For digital points, the valid states
Default— The value or state of the point on controller start-up. Shareable— The point can be set up for data sharing in Command Multiple Points, Read Multiple Points, or Refer Excel
Mappable— The point can be converted into a C-Bus point used by C-Bus devices. A mappable point has a one-to-one Direct
Access— The point is accessible through the Subsystem Points mechanism in XBS. E-Vision Monitor— These points are viewable within the E-Vision Controller Monitoring on-line screen. PAR refers to control
Hardware Config— These are points that involve controller I/O configuration. Any change to HW Config. points causes the
Manual— These points are used to set the controller outputs when in manual mode. The W7761A is placed in manual Fixable— These input points can be set to a constant value in the E-Vision Controller Monitor screen.
NOTES:
writes
10,000 are changed more than 10,000 times, irreversible hardware failure results).
. Do NOT use as outputs from Control Strategies, Time Programs, or Switching Tables. If these points
and the corresponding enumerated values are shown.
10 Points as either a data source or a destination. relationship with a C-Bus User Address.
parameters that are set in the Application Selection dialog boxes in E-Vision.
W7761A to perform an application reset; therefore, these points can only be modified off-line. mode through a menu selection in the E-Vision Controller Monitor screen.
1. Mapped points can be viewed and changed, XI584 and on an XBS central and E-Vision.
2. All Excel 10 points, mappable, calibration, configuration and internal data sharing points, can be viewed and changed,
3. E-Vision - These points are displayed to the user and polled during the E-Vision monitor function. Monitor (M) indicates the point appears in the Software list box. Schematic (S) indicates the point is to be displayed on the schematic air handler diagram directly. Calibrate (C) - These points are calibratible and the calibration dialog (either the temperature or air flow dialog) is displayed. These points are displayed in a listbox by selection of the menu item Controller, Calibration. When the user double clicks on these points the calibration dialog is displayed. Parameter (P) - This information is displayed to the user in the Application Selection screens. These fields are read/write when offline and read only when online.
4. Manual - These points can be placed in the manual mode. When the user double clicks on these points the manual dialog is displayed, this contains radio buttons; one for Auto and one for Manual.
as allowed
, via Direct Access (DA) mode in the XBS subsystem menu or via XI584.
if applicable
44 74-2699
, on C-Bus devices such as an XI581, XI582 and
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Left).
Digital
State
Engineering Units:
English (Metric) or
User Address NvName Field Nam e States plus Range State Default
AI1RType ncirioIoSelect Resist iveIn0 DA_Temp_PT3000
OA_Temp_PT3000 RA_Temp_PT3000 Custom_PT3000 DA_Temp_20KNTC RA_Temp_20KNTC Space_Temp_T7770 Custom_20KNTC Unused_Res_AI
AI2RType ncirioIoSelect Resist i veI n1 See AI1RType Eng. Units/S tates
column for selections
AI3RType ncirioIoSelect Resist i veI n2 See AI1RType Eng. Units/S tates
column for selections
AI4RType ncirioIoSelect Resist i veI n3 See AI1RType Eng. Units/S tates
column for selections
AI5VType ncirioIoSelect VoltageIn0 RA_Hum_C7600C
OA_Hum_C7600C Filter_Diff_Pres RA_Hum_C7600B OA_Hum_C7600B RA_Enthalpy OA_Enthalpy Space_CO2 Voltage_Monitor Unused_Volt_AI
AI6VType ncirioIoSelect VoltageIn1 S ee AI5VType Eng. Units/S tates
column for selections
or
Value
of
0 1 2 3 4 5 6 7 255
0 1 2 3 4 5 6 7 8 255
Unused_Res_AI
Unused_Res_AI
Unused_Res_AI
Unused_Res_AI
Unused_Volt_AI
Unused_Volt_AI
(continued)
45 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Right).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X AI1RType specifies which logic al sensor is assigned to which physi cal analog input
X X AI2RType: Refer to the descripti on for AI1RType.
X X AI3RType: Refer to the descripti on for AI1RType.
X X AI4RType: Refer to the descripti on for AI1RType.
sensor channel according to t he enumerated list shown in the Eng. Uni ts/States column.
X X AI5VType specifies which logical voltage or current sensor is assigned to which
X X AI6VType: Refer to the description for AI5VType.
physical analog input sensor channel according to the enumerat ed l i st that is shown in the Eng. Units/St ates column.
(continued)
46 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Left Continued).
Digital
State
Engineering Units:
English (Metric) or
User Address NvName Field Name States plus Range State Default
DestOut1Cmd nviRemoteCmd(0) percent
-163 to 163
DestOut2Cmd nviRemoteCmd(1) percent -163 to 163 0 DestOut3Cmd nviRemoteCmd(2) percent -163 to 163 0 DestOut4Cmd nviRemoteCmd(3) percent -163 to 163 0 DestOut5Cmd nviRemoteCmd(4) percent -163 to 163 0 DestOut6Cmd nviRemoteCmd(5) percent -163 to 163 0 DestOut7Cmd nviRemoteCmd(6) percent -163 to 163 0 DestOut8Cmd nviRemoteCmd(7) percent -163 to 163 0 DI1Sel1Type ncirioIoSelect Di gitalIn0S1 Active_Short
Active_Open Unused_DigInput
DI2Sel1Type ncirioIoSelect Di gi t al In1S1 See DI 1S el 1Type Eng.
Units/States c ol umn for selections.
or
Value
of
0 1 255
0
Unused_DigInput
Unused_DigInput
(continued)
47 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X X M DestOut1Cmd: Dest Out 1Cmd through DestOut8Cmd corresponds to DO1 through
X X X M DestOut2Cmd: Refer to the description for DestOut1Cmd. X X X M DestOut3Cmd: Refer to the description for DestOut1Cmd. X X X M DestOut4Cmd: Refer to the description for DestOut1Cmd. X X X M DestOut5Cmd: Refer to the description for DestOut1Cmd. X X X M DestOut6Cmd: Refer to the description for DestOut1Cmd. X X X M DestOut7Cmd: Refer to the description for DestOut1Cmd. X X X M DestOut8Cmd: Refer to the description for DestOut1Cmd.
X X DI1Sel1Type specifies the s ensor type and function connected to DigitalIn0S1
X X DI2Sel1Type: Refer to the descript i on for DI1Sel1Type.
DO8. Refer to the Eng. Units /States column for DO1Type for the enumerated values that can be assigned t o any output channels. Note that a selection of FLOA T means that the two DO channels are us ed for output. RIO assum es that the tool makes the proper assignment of enumerated values to DO1 through DO8 and also takes the respons ibility to avoid assignment of multiple or overlapping c ommands on the sam e output channels. An example of the relationship between nviRemoteCmd and ncirioIoSelect is discribed below: RIO is receiving a command to DestOut4Cmd. Thi s can be mapped as one of the three output types (Discret e, Modulate, Float_Open, or Float_Close) by DO3Type. If the user selects an enumerated value of Discret e2 for DO3Type, this value would be stored in (DO2). Then the DestOut4Cm d will command DO2.
through DigitalIn3S1. The valid enumerated list of logic al di gi tal states for DigitalIn0S1 is lis ted in the Eng. Units/S t ates column.
(continued)
48 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Left Continued).
Digital
State
Engineering Units:
English (Metric) or
User Address NvName Field Name States plus Range State Default
DI3Sel1Type ncirioIoSelect Digit al I n2S1 See DI1Sel1Type Eng. Uni ts/States
column for selections.
DI4Sel1Type ncirioIoSelect Digit al I n3S1 See DI1Sel1Type Eng. Uni ts/States
column for selections.
DI1Sel2Type ncirioIoSelect DigitalIn0S2 Momentary
Maintained Unused_DigInput
DI2Sel2Type ncirioIoSelect Digit al I n1S2 See DI1Sel2Type Eng. Uni ts/States
column for selections.
DI3Sel2Type ncirioIoSelect Digit al I n2S2 See DI1Sel2Type Eng. Uni ts/States
column for selections.
DI4Sel2Type ncirioIoSelect Digit al I n3S2 See DI1Sel2Type Eng. Uni ts/States
column for selections.
DO1Type ncirioIoSelect DigitalOut0 Discrete1
Discrete2 Discrete3 Discrete4 Discrete5 Discrete6 Discrete7 Discrete8 Modulate1 Modulate2 Modulate3 Modulate4 Modulate5 Modulate6 Modulate7 Modulate8 Float1_Open Float2_Open Float3_Open Float4_Open Float5_Open Float6_Open Float7_Open Float8_Open Float1_Close Float2_Close Float3_Close Float4_Close Float5_Close Float6_Close Float7_Close Float8_Close Unused_DigOutput
or
Value
of
0 1 255
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 255
Unused_DigInput
Unused_DigInput
Maintained
Maintained
Maintained
Maintained
Unused_DigOutput
49 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X DI3Sel1Type: Refer to the descript i on for DI1Sel1Type.
X X DI4Sel1Type: Refer to the descript i on for DI1Sel1Type.
X X DI1Sel2Type specifies the s ensor type and function connected to DigitalIn0S2
X X DI2Sel2Type: Refer to the descript i on for DI1Sel2Type.
X X DI3Sel2Type: Refer to the descript i on for DI1Sel2Type.
X X DI4Sel2Type: Refer to the descript i on for DI1Sel2Type.
X X DO1Type specifies which logical digi t al output function is ass i gned to the digital
through DigitalIn3S2. The valid enumerated list of logic al di gi tal states for DI1Sel2Type is listed in the Eng. Units/Stat es column.
physical output according to the enumerated list t hat is shown in the Eng. Units/States c ol umn.
50 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Left Continued).
Digital
State
Engineering Units:
English (Metric) or
User Address NvName Field Nam e States plus Range State Default
DO2Type ncirioIoSelec t DigitalOut1 Refer to the Eng. Uni t s/States
column for DO1Type for selec tions available.
DO3Type ncirioIoSelec t DigitalOut2 Refer to the Eng. Uni t s/States
column for DO1Type for selec tions available.
DO4Type ncirioIoSelec t DigitalOut3 Refer to the Eng. Uni t s/States
column for DO1Type for selec tions available.
DO5Type ncirioIoSelec t DigitalOut4 Refer to the Eng. Uni t s/States
column for DO1Type for selec tions available.
DO6Type ncirioIoSelec t DigitalOut5 Refer to the Eng. Uni t s/States
column for DO1Type for selec tions available.
DO7Type ncirioIoSelec t DigitalOut6 Refer to the Eng. Uni t s/States
column for DO1Type for selec tions available.
DO8Type ncirioIoSelec t DigitalOut7 Refer to the Eng. Uni t s/States
column for DO1Type for selec tions available.
FiftySixtyHz nciIoSelect FiftySixtyHz Sixty
Fifty
or
Value
of
0 1
Unused_DigOutput
Unused_DigOutput
Unused_DigOutput
Unused_DigOutput
Unused_DigOutput
Unused_DigOutput
Unused_DigOutput
Sixty
SrcCO2Level nvoRemoteCO2 PPM
SrcCurrentAI nvoRemoteCurrent milliamps
SrcDigIn1Sts nvoRemoteDigIn(0) DI1Value 0 t o 255 0
nvoRemoteDigIn(0) DI1St ate ST_OFF
0 to 65535
-20.0 to 200.0
ST_LOW ST_MED ST_HIGH ST_ON ST_NUL
0 1 2 3 4 255
0
0
ST_NUL
(continued)
51 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X DO2Type:
Refer to the description f or DO1Type.
X X DO3Type:
X X DO4Type:
X X DO5Type:
X X DO6Type:
X X DO7Type:
X X DO8Type:
X X FiftySixtyHz specifies the power supply frequency. Correctly select i ng Fi ftySixtyHz
X X X M SrcCO2Level is an output network variable c orresponding to the voltage or current
X X X M SrcCurrentAI is an output net work variabl e corresponding to the voltage or current
X X X M DI1State: There are four digital i nput channels (DI1 through DI4). If any of the four
Refer to the description f or DO1Type.
Refer to the description f or DO1Type.
Refer to the description f or DO1Type.
Refer to the description f or DO1Type.
Refer to the description f or DO1Type.
Refer to the description f or DO1Type.
decreases the noise pick ed up by anal og sensor wiring from the power supply. When FiftySi xtyHz is 1, the power supply frequency is Fifty Hz and when FiftySixtyHz is 0, the power suppl y f requency is Sixty Hz.
input channel (AI5 or AI6) if the selection for a CO2 sensor was made via ncirioIoSelect.
input channel (AI5 or AI6) if the selection for a current s ensor was made via ncirioIoSelect.
SrcDigIn1Sts: There are f our di gi t al i nput channels (DI1 through DI4). If any of the four channels are configured, the corres ponding out put network variable will be updated with the value whose data type is SNVT_s witch.
channels are configured, the corresponding out put network variable will be updated with the value whose data type is SNVT_switch. Refer to the enumerated li st that is shown in the Eng. Units/St ates column.
(continued)
52 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Left Continued).
Digital
State
Engineering Units:
English (Metric) or
User Address NvName Field Name States plus Range State Default
SrcDigIn2Sts nvoRemoteDigIn(1) DI2Value 0 to 255 0
nvoRemoteDigIn(1) DI2St ate Refer to the DI1State enumerated li st
shown in the Eng. Units/St ates column.
SrcDigIn3Sts nvoRemoteDigIn(2) DI3Value 0 to 255 0
nvoRemoteDigIn(2) DI3St ate Refer to the DI1State enumerated li st
shown in the Eng. Units/St ates column.
SrcDigIn4Sts nvoRemoteDigIn(3) DI4Value 0 to 255 0
nvoRemoteDigIn(3) DI4St ate Refer to the DI1State enumerated li st
shown in the Eng. Units/St ates column.
SrcHumidAI5 nvoRemoteHum(0) percent
-163 to 163
or
Value
of
ST_NUL
ST_NUL
ST_NUL
0
SrcHumidAI6 nvoRemoteHum(1) percent
-163 to 163
SrcPressAI5 nvoRemotePres(0) inw -131.5 to 131.5
kPa (-32.768 to 32.767)
SrcPressAI6 nvoRemotePres(1) inw -131.5 to 131.5
kPa (-32.768 to 32.767)
SrcTempAI1 nvoRemoteTemp(0) degrees F -40 to 240
degrees C (-40 to 116)
SrcTempAI2 nvoRemoteTemp(1) degrees F -40 to 240
degrees C (-40 to 116)
SrcTempAI3 nvoRemoteTemp(2) degrees F -40 to 240
degrees C (-40 to 116)
SrcTempAI4 nvoRemoteTemp(3) degrees F -40 to 240
degrees C (-40 to 116)
SrcVoltageAI nvoRemoteVolt Volt s
0.0 to 10.5
0
0
0
0
0
0
0
0
)
53 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C1. Input/Output Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
SrcDigIn2Sts: Refer to the description for SrcDigIn1Sts.
X X X M DI2State:
X X X M DI3State:
X X X M DI4State:
X X X M SrcHumidAI5 is an output network variable corresponding to the vol t age or current
X X X M SrcHumidAI6 is an output network variable corresponding to the vol t age or current
X X X M SrcPressAI5 is an output network variable corresponding to the voltage or current
X X X M SrcPressAI6 is an output network variable corresponding to the voltage or current
X X X M SrcTempAI1 is an output network variable corresponding to the anal og i nput
X X X M SrcTempAI2 is an output network variable corresponding to the anal og i nput
X X X M SrcTempAI3 is an output network variable corresponding to the anal og i nput
X X X M SrcTempAI4 is an output network variable corresponding to the anal og i nput
X X X M SrcVoltageAI is an output network variable corresponding to the voltage or current
Refer to the description for DI1State. SrcDigIn3Sts: Ref er t o the description for SrcDigI n1Sts above.
Refer to the description for DI1State. SrcDigIn4Sts: Ref er t o the description for SrcDigI n1Sts above.
Refer to the description for DI1State.
input channel (AI5) if the selection for humidit y sensor was made via ncirioIoSel ect for AI5.
input channel (AI6) if the selection for humidit y sensor was made via ncirioIoSel ect for AI6.
input channel (AI5) if the selection for a pressure sens or was made via ncirioIoSelect for AI5.
input channel (AI6) if the selection for a pressure sens or was made via ncirioIoSelect for AI6.
channel (AI1). This NV will contain AI1 temperature value with the OffsetCal1AI1 applied to it.
channel (AI2). This NV will contain AI2 temperature value with the OffsetCal1AI2 applied to it.
channel (AI3). This NV will contain AI3 temperature value with the OffsetCal1AI3 applied to it.
channel (AI4). This NV will contain AI4 temperature value with the OffsetCal1AI4 applied to it.
input channel (AI5 or AI6) if the selection for a voltage s ens or was made via ncirioIoSelect.
54 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C2. Control Parameters (Left).
Digital
State
Engineering Units:
English (Metric) or
User Address NvName Field Nam e States plus Range State Default
nviInUse InUseNumber 0 to 65534 0xFFFF
or
Value
of
55 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C2. Control Parameters (Right).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
nviInUse is used by a management node to indicate to all other management nodes that it is logged on, to the Excel 10 node and that they should not t ry to interact with any of the Excel 10s net work variabl es. Before the managem ent node reads or writes any network variables, the management node checks nviInUse for a zero value meaning no other managem ent nodes are already logged on and that a management node may log on, to the node. Then the managem ent node writes a number, 1 through 65534, to nviInUse and periodically writes the sam e val ue to indicate that the managem ent node is still logged on. If there are no writes m ade to nviInUse for approximately 60 s econds, then the Excel 10 reset s nviInUse to zero to automatically l og of f the management node. B efore interacting with any network variables, the managem ent node verifies that the nviInUse has not changed. The management node logs off by writing 0 to nviInUse. During power up, an application restart, or return to on-line from off-li ne, the Excel 10 sets nviInUse to 65535 to i ndi cate to the management node that it has returned to on-line.
56 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C3. Status Points (Left).
Digital
State
Engineering Units: English (Metric) or
User Address NvName Field Name States plus Range State Default
AlarmNode nvoAlarm node 0 to 127 0
AlarmSubnet nvoAlarm subnet 1 to 255 0
or
Value
of
AlarmType nvoAlarm type
0 to 255
AlarmTypeLog0 nvoAlarmLog type0 Refer t o the AlarmType
AlarmTypeLog1 nvoAlarmLog type1 Refer t o the AlarmType
AlarmTypeLog2 nvoAlarmLog type2 Refer t o the AlarmType
AlarmTypeLog3 nvoAlarmLog type3 Refer t o the AlarmType
AlarmTypeLog4 nvoAlarmLog type4 Refer t o the AlarmType
Errorbyte1 nvoError error_bit(0)
Byte Offset = 0 Bit Offset = 0 ResSensor1Error(AI1)
NO_ALARM INPUT_NV_FAILURE NODE_DISABLED SENSOR_FAILURE rINPUT_NV_FAILURE rNODE_DISABLED rSENSOR_FAILURE ALARM_NOTIFY_DISABLED
enumerated list shown in the Eng. Units/Stat es column.
enumerated list shown in the Eng. Units/Stat es column.
enumerated list shown in the Eng. Units/Stat es column.
enumerated list shown in the Eng. Units/Stat es column.
enumerated list shown in the Eng. Units/Stat es column.
FALSE TRUE
0 1 2 3 129 130 131 255
0 1
NO_ALARM
NO_ALARM
NO_ALARM
NO_ALARM
NO_ALARM
NO_ALARM
FALSE
(continued)
57 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C3. Status Points (Right).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
AlarmNode: is the LonWorks node number (i n domain entry 1 of the nodes dom ai n table) assigned to the node.
AlarmSubnet: is the LonWorks s ubnet number (in domain entry 1 of t he nodes domain table) to which the node is assigned.
AlarmType: is the al arm type being issued. When an alarm condition i s no longer TRUE, type is set to t he sum of the alarm condi tions numeric value and the RETURN_TO_NORMAL numeric value. The type also is recorded in AlarmTypeLog0 through AlarmTypeLog4. When a new alarm is detected, just the corresponding numeric value f or t he al arm is reported. Refer to tabl e 9 (Excel 10 Alarms) in the System Engineering Guide for all t he error c ondi tions that may be reported.
X M AlarmTypeLog0 (0, 1, 2, 3, 129, 130, 131, 255)
X M AlarmTypeLog1:
X M AlarmTypeLog2:
X M AlarmTypeLog3:
X M AlarmTypeLog4:
X M ResSensor1Error(AI1): The nvoError i s a polled output containing a list of the current
A supervisory node may poll the AlarmTypeLog output for a short alarm history. The last five alarm reports sent via nvoAlarm are reported via AlarmTypeLog. When ALARM_NOTIFY_DISABLED is entered into the log, further alarms or return to normals are not entered into t he l og, until alarm reporting is agai n enabl ed. If nvoAlarm is bound and not being acknowledged, the last alarm report ent ered i nto the AlarmTypeLog is the one that was not acknowledged. See nvoAlarm and for related s ubj ec ts. type ( n ) specifies the alarm that was issued via nvoAlarm. See nvoAlarm for t he alarm types used in AlarmTypeLog. The newest alarm is report ed i n type( 0 ) and the oldest is reported in type( 4 ). When a new entry is made to the log, the oldest entry is lost.
Refer to the description f or A l armTypeLog0.
Refer to the description f or A l armTypeLog0.
Refer to the description f or A l armTypeLog0.
Refer to the description f or A l armTypeLog0.
errors detected by the node. A search for error conditions in the node is made periodically. A diagnosti c tool may poll nvoError for all of the current errors. nvoError uses one bit for each possi ble error condition. nvoError contains all the detected current errors even though they may be suppressed for reporting by nvoAlarm. There is a correspondence between the error conditi ons and alarm types. nvoError includes sensor failure errors and input network variable failure detect errors. Any sensor failure errors result i n a SENSOR_FAILURE alarm. Fai l ure to receive any bound network variable periodically results i n an INPUT_NV_FAILURE alarm. nvoError tells which sensor(s) or network variable(s) have failed. See nvoAlarm, AlarmTypeLog for related subj ects.
(continued)
58 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C3. Status Points (Left Continued).
Digital
State
Engineering Units:
User Address NvName Field Name States plus Range State Default
Errorbyte2 nvoError error_bit(0)
Byte Offset = 0 Bit Offset = 1 ResSensor2Error(AI2)
Errorbyte3 nvoError error_bit(0)
Byte Offset = 0 Bit Offset = 2 ResSensor3Error(AI3)
Errorbyte4 nvoError error_bit(0)
Byte Offset = 0 Bit Offset = 3 ResSensor4Error(AI4)
BugFixVer nroPgmVer BugVer 3
nroPgmVer NodeType RIO1 MajorVer nroPgmVer MajorVer 2 MinorVer nroPgmVer MinorVer 1
nroPgmVer NodeType 6
English (Metric) or
FALSE TRUE
FALSE TRUE
FALSE TRUE
or
Value
of
0 1
0 1
0 1
FALSE
FALSE
FALSE
nvoStatus CommFailure FALSE
TRUE
nvoStatus disabled FALSE
TRUE
nvoStatus ElectricalFault FALSE
TRUE
nvoStatus FailSelfTest FALSE
TRUE
nvoStatus FeedbackFailure FALSE
TRUE
nvoStatus InAlarm FALSE
TRUE
nvoStatus InvalidId FALSE
TRUE
nvoStatus InvalidRequest FALSE
TRUE
0 1
0 1
0 1
0 1
0 1
0 1
0 1
0 1
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
(continued)
59 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C3. Status Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X M ResSensor2Error(AI2): Refer to the description of ResSensor1Error(AI1).
X M ResSensor3Error(AI3): Refer to the description of ResSensor1Error(AI1).
X M ResSensor4Error(AI4): Refer to the description of ResSensor1Error(AI1).
X Software version.
A four byte ASCII st ri ng i ndi cating the type of node (model). X Software version. X Software version.
The NodeType is a numeric identif i er that is stored in EPROM that i dentifies the
Excel 10 node type. Whenever a new soft ware version or upgrade i s issued, this is
reflected in nroPgmV er which typically is read by a network management node to
identify the node type. The contents of nroPgmVer cont ai n compatible model t ype
information and is fi xed at t he t i me when the node software is compil ed.
CommFailure:
This field is not support ed and i s set to 0 (FALSE).
disabled: disabled reports 1 if nvoIO mode is set t o DISABLED_MODE or
FACTORY_TEST mode. Otherwise dis abl ed i s set to 0.
ElectricalFault:
This field is not support ed and i s set to 0 (FALSE).
FailSelfTest:
This field is not support ed and i s set to 0 (FALSE).
FeedbackFailure:
This field is not support ed and i s set to 0 (FALSE).
InAlarm: If t here are currently any active alarms reported by InAlarm, or InAlarm is
set to AlarmNotifyDisabled, then InAlarm is set to True, if not InAlarm is set to False.
InvalidId: If object_id is not a valid object, invalid_id is set to 1 (TRUE) ot herwise i t is
set to 0 (FALSE).
InvalidRequest: If object_request is not a valid request for the object addressed,
InvalidRequest is set to 1 (TRUE) otherwise it is set t o 0 (FALSE).
(continued)
60 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C3. Status Points (Left Continued).
Digital
State
Engineering Units: English (Metric) or
User Address NvName Fi el d Name States plus Range State Default
nvoStatus InOverride FALSE
TRUE
nvoStatus LockedOut FALSE
TRUE
nvoStatus ManualControl FALSE
TRUE
nvoStatus MechanicalFault FALSE
TRUE nvoStatus ObjectId 0 TO 65535 0 nvoStatus OpenCircuit FALSE
TRUE nvoStatus OutOfLlimits FALSE
TRUE nvoStatus OutOfServic e FALSE
TRUE nvoStatus OverRange FALSE
TRUE nvoStatus SelfTestInProgress FALSE
TRUE nvoStatus UnableToMeasure FA LSE
TRUE nvoStatus UnderRange FALSE
TRUE
or
Value
of
0 1
0 1
0 1
0 1
0 1
0 1
0 1
0 1
0 1
0 1
0 1
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
61 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C3. Status Points (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
InOverride: This field is not support ed and i s set to 0 (FALSE).
LockedOut: This field is not support ed and i s set to 0 (FALSE).
ManualControl: This field is not support ed and i s set to 0 (FALSE).
MechanicalFault: This field is not support ed and i s set to 0 (FALSE).
ObjectId: is set to the current value of nviRequest. obj ect_id OpenCircuit:
This field is not support ed and i s set to 0 (FALSE). OutOfLlimits:
This field is not support ed and i s set to 0 (FALSE). OutOfService:
This field is not support ed and i s set to 0 (FALSE). OverRange:
This field is not support ed and i s set to 0 (FALSE). SelfTestInProgress:
This field is not support ed and i s set to 0 (FALSE). UnableToMeasure:
This field is not support ed and i s set to 0 (FALSE). UnderRange:
This field is not support ed and i s set to 0 (FALSE).
62 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C4. Configuration Parameters (Left).
Digital
State
Engineering Units:
English (Metric) or
User Address NvName Field Name States plus Range State Default
nciApplVer ApplicationType 0 t o 255 0 nciDeviceName DeviceName ASCII Blanks
nciApplVer Time1Jan70 seconds 0
nciApplVer VersionNumber 0 to 255 0
AILowLimit nciEUConvrtRes LowerLimi tS7 degrees F -40 to 240
degrees C (-40 to 116)
or
Value
of
0
AIOutputRHigh nciEUConvrtRes Output Res Hi ghS7 degrees F -40 to 240
degrees C (-40 to 116)
AIOutputRLow nciEUConvrtRes OutputResLowS7 degrees F -40 to 240
degrees C (-40 to 116)
AIResHigh nciEUConvrtRes ResHigh Ohms
10 to 150000
AIResLow nciEUConvrtRes ResLow Ohms
10 to 150000
0
0
0
0
(continued)
63 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C4. Configuration Parameters (Right).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
ApplicationType identifi es the current application number of the Excel 10. nciDeviceName is an 18 character field used to identify the node uniquely as one
object at the site or project. The contents of t he nciDeviceName is m ai ntained by a management node. If nciDeviceName is all ASCII blanks, it is considered unconfigured.
The time stamp of the last change to the Excel 10 appl i cation configuration. Time meets the ANSI C time stamp requirement specifying the number of seconds elapsed since midnight (0:00:00), January 1, 1970. It i s represented in the Intel Format.
VersionNumber identifi es the version number of the Excel 10 appl i cation.
X M X AILowLimit: This is the low limit value or the lowest value that will be displayed for
this sensor. This value must be between the AIOutputRLow and AIOutputRHigh and lower than the value specified for AIUpperLimit.
X M X AIOutputRHigh: This is the equivalent temperature degrees F (degrees C) value for
the resistance entered for AIResHigh. Using the resistance example for AIResHigh of 48,000 ohms, you would enter the equival ent temperature of 45.0 degrees F (7. 2 degrees C) for the AIOutputRHigh value.
X M X AIOutputRLow: This is the equi val ent temperature degrees F (degrees C) value for
the resistance entered for AIResLow. Using the resistance example for AIResLow of 11,520 ohms, you would enter the equivalent temperature of 99.0 degrees F (37.2 degrees C) for the AIOutputRLow value.
X M X AIResHigh: This is the highest resistance value of the user specified range for a
custom resistive input as selected through E-Vision in the input Tab of t he Application select i on screen. The user can select between a PT3000 (Custom_PT3000) or a 20 Kohm NTC (Custom_20 Kohm NTC) s ensor. This value is specified in ohms with LS B in 10 Ohms. This m eans that if your high resist ance value for a 20 Kohm NTC sensor was 48,000 ohms, 45.0 degrees F (7.2 degrees C), the value that would be entered for AIResHigh would be 4800 (the resistance value divided by ten).
X M X AIResLow: This is the lowest resistance value of the user s pecified range for a
custom resistive input as selected through E-Vision in the input Tab of t he Application select i on screen. The user can select between a PT3000 (Custom_PT3000) or a 20 Kohm NTC (Custom_20 Kohm NTC) s ensor. This value is specified in ohms with LS B in 10 Ohms. This m eans that if the low resistance value for a 20 Kohm NTC sensor was 11,520 ohms, 99.0 degrees F (37.2 degrees C), t he value that would be entered for AIResLow would be 1152 (the resistance value divided by ten).
(continued)
64 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C4. Configuration Parameters (Left Continued).
Digital
State
Engineering Units:
English (Metric) or
User Address NvName Field Name S tates pl us Range State Default
AIUpperLimit nciEUConvrtRes UpperLimitS7 degrees F -40 to 240
degrees C (-40 to 116)
or
Value
of
0
DeltaC nciDelt a deltacurrent mA
0 to 256
DeltaCO2 nciDelta deltaCO2 PPM 0 to 2000 0 DeltaH nciDelt a deltahum percent 0 to 163 0 DeltaP nciDelta deltapres inw 0 to 32
kPa (0 to 7.97)
DeltaT1 nciDelta deltatemp(0) degrees F 0 to 256
degrees C (0 to 124)
DeltaT2 nciDelta deltatemp(1) degrees F 0 to 256
degrees C (0 to 124)
DeltaT3 nciDelta deltatemp(2) degrees F 0 to 256
degrees C (0 to 124)
DeltaT4 nciDelta deltatemp(3) degrees F 0 to 256
degrees C (0 to 124) DeltaV nciDelta deltaVolt 0 to 10.5 volts 0 DO1FlSpeed nciFloatConfig DO0 seconds
0 to 900
DO2FlSpeed nciFloatConfig DO1 seconds
0 to 900
0
0
0
0
0
0
90
90
DO3FlSpeed nciFloatConfig DO2 seconds
0 to 900
DO4FlSpeed nciFloatConfig DO3 seconds
0 to 900
65 74-2699
90
90
(continued)
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C4. Configuration Parameters (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X M X AIUpperLimit: This is the high limit value or the highest value that will be displayed
X M P X DeltaC: The default value of delta for all RIO sensor types is set to zero. With this
X M P X DeltaCO2: Refer to the description for DeltaC. X M P X DeltaH: Refer to the description for DeltaC. X M P X DeltaP: Refer to the description for DeltaC.
X M P X DeltaT1: Refer t o the description for DeltaC.
for this sensor. This val ue must be between the AIOutputRLow and AIOutputRHigh and higher than the value specified f or AILowLimit.
default value, the RIO will send the sensor values at t he f astest rate of 2 seconds update rate. However, if the user desires to reduce the network traffic or not receive the noisy sensor values, a delta value can be specified. This value will force the RIO to transmit the sensor value when the current value exceeds the last sent value by the delta amount. RIO will also send the s ensor value whenever the time of update exceeds nciRioSendT. RIO will send the sensor value at the rate of nciRioSendT regardless of delta change.
X M P X DeltaT2: Refer t o the description for DeltaC.
X M P X DeltaT3: Refer t o the description for DeltaC.
X M P X DeltaT4: Refer t o the description for DeltaC.
X M P X DeltaV: Refer to the description for DeltaC. X X DO1FlSpeed is how long it takes for the actuator motor to move one cycle of t ravel
X X DO2FlSpeed is how long it takes for the actuator motor to move one cycle of t ravel
X X DO3FlSpeed is how long it takes for the actuator motor to move one cycle of t ravel
X X DO4FlSpeed is how long it takes for the actuator motor to move one cycle of t ravel
from closed to open. Thi s value would be required if DO1Type were configured to either Float_Open or Float_Close.
from closed to open. Thi s value would be required if DO2Type were configured to either Float_Open or Float_Close.
from closed to open. Thi s value would be required if DO3Type were configured to either Float_Open or Float_Close.
from closed to open. Thi s value would be required if DO4Type were configured to either Float_Open or Float_Close.
(continued)
66 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C4. Configuration Parameters (Left Continued).
Digital
State
Engineering Units: English (Metric) or
User Address NvName Field Name States plus Range State Default
DO5FlSpeed nciFloatConfig DO4 s econds
0 to 900
or
Value
of
90
DO6FlSpeed nciFloatConfig DO5 s econds
0 to 900
DO7FlSpeed nciFloatConfig DO6 s econds
0 to 900
DO8FlSpeed nciFloatConfig DO7 s econds
0 to 900
DO1PWMPeriod nciPWMConfig1 DO0.si_period_pwm seconds
0.0 to 3000
DO1PWMZero nciPWMConfi g1 DO0.si_pnct _time seconds 0.0 to 3000 0.1 DO1PWMFull nciPWMConfig1 DO0.si_delta_time seconds 0.0 to 3000 25.5 DO2PWMPeriod nciPWMConfig1 DO1.si_period_pwm seconds 0.0 t o 3000 25.6 DO2PWMZero nciPWMConfi g1 DO1.si_pnct _time seconds 0.0 to 3000 0.1 DO2PWMFull nciPWMConfig1 DO1.si_delta_time seconds 0.0 to 3000 25.5 DO3PWMPeriod nciPWMConfig1 DO2.si_period_pwm seconds 0.0 t o 3000 25.6 DO3PWMZero nciPWMConfi g1 DO2.si_pnct _time seconds 0.0 to 3000 0.1 DO3PWMFull nciPWMConfig1 DO2.si_delta_time seconds 0.0 to 3000 25.5 DO4PWMPeriod nciPWMConfig1 DO3.si_period_pwm seconds 0.0 t o 3000 25.6 DO4PWMZero nciPWMConfi g1 DO3.si_pnct _time seconds 0.0 to 3000 0.1 DO4PWMFull nciPWMConfig1 DO3.si_delta_time seconds 0.0 to 3000 25.5 DO5PWMPeriod nciPWMConfig2 DO4.si_period_pwm seconds 0.0 t o 3000 25.6 DO5PWMZero nciPWMConfi g2 DO4.si_pnct _time seconds 0.0 to 3000 0.1 DO5PWMFull nciPWMConfig2 DO4.si_delta_time seconds 0.0 to 3000 25.5
90
90
90
25.6
(continued)
67 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C4. Configuration Parameters (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X DO5FlSpeed is how long it takes for the actuator motor to move one cycle of t ravel
from closed to open. Thi s value would be required if DO5Type were configured to either Float_Open or Float_Close.
X X DO6FlSpeed is how long it takes for the actuator motor to move one cycle of t ravel
from closed to open. Thi s value would be required if DO6Type were configured to either Float_Open or Float_Close.
X X DO7FlSpeed is how long it takes for the actuator motor to move one cycle of t ravel
from closed to open. Thi s value would be required if DO7Type were configured to either Float_Open or Float_Close.
X X DO8FlSpeed is how long it takes for the actuator motor to move one cycle of t ravel
from closed to open. Thi s value would be required if DO8Type were configured to either Float_Open or Float_Close.
X M X DO1PWMPeriod is a intermittent voltage pul se whose width varies in proportion to
the desired actuator posit i on. The PWM signal has t hree parameters that have to be configured in order for the output t o f unction correctly. The period, i s the overall pulse lenegth in seconds. The percent _time (signal presence) is the zero percent position of the actuator output. The actuator requires this si gnal (pul se width) sent once every period, so that it knows that it is still connected to the controller and where the zero position starts. The vari abl e width (del ta_time) portion is inc remented in proportion to the signal percentage. There are 255 increments available (for example 0.1 second). Thus, the pulse width will be the minimum width (percent_time) plus the number of increments (delta_t i me/ 255). The smalles t time that can be us ed with t he RIO controller is 0.1 second. An example stroke at m i d position is: 0.1 sec ond (percent_time) + 128 x 0.1 (255/0.5 - 50 percent position) = 12.9 seconds. The period would equal the percent_time plus the delta_time (for example 0. 1 seconds) + 255 x
0.1 seconds = 25.6 seconds . X M X DO1PWMZero: Refer to the description for DO1PWMPeriod. X M X DO1PWMFull: Refer to the description for DO1PWMPeriod. X M X DO2PWMPeriod: Refer to the description for DO1PWMPeriod. X M X DO2PWMZero: Refer to the description for DO1PWMPeriod. X M X DO2PWMFull: Refer to the description for DO1PWMPeriod. X M X DO3PWMPeriod: Refer to the description for DO1PWMPeriod. X M X DO3PWMZero: Refer to the description for DO1PWMPeriod. X M X DO3PWMFull: Refer to the description for DO1PWMPeriod. X M X DO4PWMPeriod: Refer to the description for DO1PWMPeriod. X M X DO4PWMZero: Refer to the description for DO1PWMPeriod. X M X DO4PWMFull: Refer to the description for DO1PWMPeriod. X M X DO5PWMPeriod: Refer to the description for DO1PWMPeriod. X M X DO5PWMZero: Refer to the description for DO1PWMPeriod. X M X DO5PWMFull: Refer to the description for DO1PWMPeriod.
(continued)
68 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C4. Configuration Parameters (Left Continued).
Digital
State
Engineering Units: English (Metric) or
User Address NvName Field Name States plus Range State Default
DO6PWMPeriod nciPWMConfig2 DO5.si_period_pwm seconds 0.0 t o 3000 25.6 DO6PWMZero nciPWMConfi g2 DO5.si_pnct _time seconds 0.0 to 3000 0.1 DO6PWMFull nciPWMConfig2 DO5.si_delta_time seconds 0.0 to 3000 25.6 DO7PWMPeriod nciPWMConfig2 DO6.si_period_pwm seconds 0.0 t o 3000 25.6 DO7PWMZero nciPWMConfi g2 DO6.si_pnct _time seconds 0.0 to 3000 0.1 DO7PWMFull nciPWMConfig2 DO6.si_delta_time seconds 0.0 to 3000 25.5 DO8PWMPeriod nciPWMConfig2 DO7.si_period_pwm seconds 0.0 t o 3000 25.6 DO8PWMZero nciPWMConfi g2 DO7.si_pnct _time seconds 0.0 to 3000 0.1 DO8PWMFull nciPWMConfig2 DO7.si_delta_time seconds 0.0 to 3000 25.5
Table C4. Configuration Parameters (Right Continued).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X M X DO6PWMPeriod: Refer to the description for DO1PWMPeriod. X M X DO6PWMZero: Refer to the description for DO1PWMPeriod. X M X DO6PWMFull: Refer to the description for DO1PWMPeriod. X M X DO7PWMPeriod: Refer to the description for DO1PWMPeriod. X M X DO7PWMZero: Refer to the description for DO1PWMPeriod. X M X DO7PWMFull: Refer to the description for DO1PWMPeriod. X M X DO8PWMPeriod: Refer to the description for DO1PWMPeriod. X M X DO8PWMZero: Refer to the description for DO1PWMPeriod. X M X DO8PWMFull: Refer to the description for DO1PWMPeriod.
or
Value
of
69 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table C5. Direct Access And Special Points (Left).
Digital
State
Engineering Units: English (Metric) or
User Address NvName Field Name States plus Range State Default
DestManMode nviManualMode MODE_ENABLE
MODE_DISABLE MODE_MANUAL SUPPRESS_ALARMS UNSUPPRESS_ALARMS
or
Value
of
0 1 2 3 4
MODE_ENABLE
Table C5. Direct Access And Special Points (Right).
Share (SH), Map (MA), Direct Access (DA)
E-Vision (EV): Cal ibrate (C), Monitor (M ),
Parameter (P), Schematic (S )
Hardware Configuration (HW),
Manual Point (MN), Test (TS)
SH MA DA EV HW MN TS Comments
X X M P DestManMode: is an input which is used t o manually set the physical outputs.
DestManMode remains unchanged until anot her mode has been commanded or an application restart has been performed. The valid enumerated val ues are: MODE_ENABLE enables the node so t hat the RIO controls the physi cal outputs as the normal mode. MODE_ENABLE is the default s t ate after power is restored or an application restart occurs. If the mode was MANUAL and DestManMode is set to MODE_ENABLE, the node then goes through application restart. MODE_DISABLED sets the node into the DISABLED mode. The alarm NODE_DISABLED is initiated, and the physical outputs are turned off. The physical inputs, network variable inputs, and network variable outputs are s till functioning when the node is in the DISABLED mode. MODE_MANUAL sets the node into the MANUAL mode. The alarm NODE_DISABLED is initiated, and the physical outputs are c ont rolled manually as commanded by DestManMode. The nodes configuration variables and DestManMode are used to set valves, dampers, and/or digital output t o the desired manual positions or s t ate(s). The physical inputs , network variable inputs, and network variable outputs are still functioning when the node is in t he MANUA L mode. SUPPRESS_ALARMS causes AlarmType to be set to ALARM_NOTIFY_DISABLED, and AlarmTypeLog to no longer record alarms. If alarms are suppressed, UNSUPPRESS_ALARMS causes AlarmType and AlarmTypeLog to be returned to reporting alarms. See nvoA l arm for more details. All unspecified values are t he same as MODE_ENABLE.
70 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Appendix D. Q7750A Excel 10 Zone Manager Point Estimating Guide.
Memory size approximation is shown below: (all sizes in bytes)
memory size
When
memory size
When the application complexity, reduce the number of attached Excel 10s or distribute the Excel 10s over more than one Zone Manager.
memory size
When
Approximate Memory Size Estimating Procedure.
is less than 110,000 bytes, the size is OK. is between 110,000 and 128,000 bytes, the application may be too large. The user must expect to reduce
is greater than 128,000, the size is too large. The application size must be reduced as described above.
1. Determine the number of points per controller required at the Central (for example, XBS). NOTE: All remaining points that are not mapped can be accessed through the
Direct Access
feature.
2. Calculate the number of Excel 10 Zone Manager program points that are used in control logic and in the switching table.
3. Estimate the program complexity of the Zone Manager (one of three levels).
a. No time programs, control logic, or switching tables. b. 10K of control logic (one time program, five switching tables, and five control loops).
c. 20K of control logic (multiple time programs, ten switching tables, and ten control loops). Use Fig. D-1 to determine the number of Excel 10s that can be connected to the Zone Manager. NOTE: More than 60 Excel 10s requires a Router.
4. Repeat for each Q7750A Excel 10 Zone Manager in a project.
NO TIME PROGRAM,
(A)
NO CONTROL LOOPS, NO SWITCHING TABLES.
10K CONTROL PROGRAM
(B)
(I.E., 1 TIME PROGRAM, 5 CONTROL LOOPS, 5 SWITCHING TABLES.)
20K CONTROL PROGRAM
(C)
(I.E., MULTIPLE TIME PROGRAMS, 10 CONTROL LOOPS, 10 SWITCHING TABLES.)
NUMBER OF EXCEL 10s
895
740
585
900
800
700
600
NUMBER OF C-BUS POINTS (EXCEL 10 MAPPED POINTS PLUS ZONE MANAGER POINTS)
M8729
NUMBER OF C-BUS POINTS (EXCEL 10 MAPPED POINTS PLUS ZONE MANAGER POINTS)
920
900
800
765
700
610
600
20 60 120
(OR LESS) (ADD ROUTER)
Fig. D-1. Point capacity estimate for Zone Manager.
The exact equation for calculating memory size follows: Memory size = 21,780
+ 4096 (in case of a time program). + CARE Control Program. + 14 x time points x Excel 10 units. + 50 x Excel 10 units. + map complexity x Excel 10 units x mapped points. + 57 x C-Bus points. + 7488 x Excel 10 types.
Where:
Time points = number of switch points in time program per Excel 10.
Excel 10 units = number of attached Excel 10s.
C-Bus points = including mapped points and others; for example, remote points.
Mapped points = number of mapped points per Excel 10,
including One-to-Many and Many-to-One mechanism.
Excel 10 types = number of different Excel 10 types (currently three)
Map complexity =
20 = using One-to-Many and not using
points with read/write. 30 = average. 45 = many points with read/write ability.
71 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Appendix E. Sensor Data for Calibration.
Resistance Sensors.
Sensor Type:
C7100A1015, (and C7170A1002).
Sensor Use:
Discharge air, Outdoor air. Table E-1 lists the points for Sensor Resistance versus Temperature. Fig. E-1 shows the graph of these points.
Table E-1. Sensor Resistance Versus Temperature.
°F (°C) Resistance Ohms
-40 (-40) 2916.08
-30 (-34.5) 2964.68
-20 (-28.9) 3013.28
-10 (-23.3) 3061.88 0 (-17.8) 3110.48
10 (-12.2) 3159.08 20 (-6.7) 3207.68 30 (-1.1) 3256.28 40 (4.4) 3304.88 50 (10) 3353.48 60 (15.6) 3402.08 70 (21.1) 3450.68 80 (26.7) 3499.28
90 (32.2) 3547.88 100 (37.8) 3596.48 110 (43.4) 3645.08 120 (49) 3693.68
SENSOR RESISTANCE VERSUS TEMPERATURE
3750 3700 3650 3600 3550 3500 3450 3400 3350 3300
OHMS
3250 3200 3150 3100 3050 3000 2950 2900
°F
-40
-12.2
-23.3
-34.5
°C
-28.9
-40 15.6
-17.8
-6.7
-1.1
50403020100-10-20-30
60 70 80 90 100 110 120
10
4.4
21.1
26.7
32.2
37.8
43.4
M11959
49
Fig. E-1. Graph of Sensor Resistance versus Temperature.
Sensor Type:
C7031B1033, C7031C1031, C7031D1062, C7031F1018, C7031J1050, C7031K1017.
Sensor Use:
Return Air, Discharge Air Temperature.
72 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table E-2 lists the points for Sensor Resistance versus Temperature. Fig. E-2 shows the graph of these points.
Table E-2. Sensor Resistance Versus Temperature.
°F (°C) Resistance Ohms
30 (-1.1) 1956.79
35 (1.7) 1935.79 40 (4.4) 1914.79 45 (7.2) 1893.79
50 (10) 1872.79 55 (12.8) 1851.79 60 (15.6) 1830.79 65 (18.3) 1809.79 70 (21.1) 1788.79 75 (23.9) 1767.79 80 (26.7) 1746.79 85 (29.4) 1725.79 90 (32.2) 1704.78
95 (35) 1683.78
100 (37.8) 1662.78 105 (40.6) 1641.78 110 (43.3) 1620.78 115 (46.1) 1599.78 120 (48.9) 1578.78
SENSOR RESISTANCE VERSUS TEMPERATURE
2000 1950 1900 1850 1800
OHMS
1750 1700 1650 1600 1550 1500
°F
1.7
°C
4.4
-1.1 26.7
555045403530 60 65 70 75 80 85 90 95 100 105110 115120
12.8
7.2
15.6
10
18.3
21.1
23.9
29.4
32.2
35 40.6 46.1
37.8
43.3
48.9
M11960
Fig. E-2. Graph of Sensor Resistance versus Temperature.
Sensor Type:
T7770A,B,C,D sensor—(current feature that can be used with the RIO Device) and C7770A.
Sensor Use:
Space Temperature and Discharge/Return Air Temperature. Table E-3 lists the points for Sensor Resistance versus Temperature. Fig. E-3 shows the graph of these points.
Table E-3 Sensor Resistance Versus Temperature.
°F (°C) Resistance Ohms
40 (4.4) 9961.09 45 (7.2) 9700.90
50 (10) 9440.72 55 (12.8) 9180.53 60 (15.6) 8920.35
73 74-2699
65 (18.3) 8660.16 70 (21.1) 8399.98 75 (23.9) 8139.79 80 (26.7) 7879.61 85 (29.4) 7619.42 90 (32.2) 7359.24
95 (35) 7099.06
100 (37.8) 6838.87
80K
70K
60K
50K
40K
30K
RESISTANCE (OHMS)
20K
10K
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
20K OHM AT
o
F (25oC)
77
40 50 60 70
30
0
10
80
20
TEMPERATURE (DEGREES)
90
30
100
110
40
M5874A
o
F
o
C
Fig. E-3. Graph of Sensor Resistance versus Temperature.
Voltage/Current Sensors.
Sensor Type:
C7600B1000 (Decorative Wall Mount) and C7600C1018 2 to 10V.
Sensor Use:
Humidity. Table E-4 lists the points for Sensor Voltage versus Humidity. Fig. E-4 shows the graph of these points.
Table E-4. Sensor Voltage Versus Humidity.
Humidity Percentage Sensor Voltage
10 2.67 15 3.08 20 3.48 25 3.88 30 4.28 35 4.68 40 5.08 45 5.48 50 5.88 55 6.28 60 6.69 65 7.09 70 7.49 75 7.89 80 8.29
74 74-2699
85 8.69 90 9.09
Sensor Type:
C7600C1008 (4 to 20 mA).
Sensor Use:
Humidity.
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
SENSOR VOLTAGE VERSUS HUMIDITY PERCENTAGE
10.00
9.50
9.00
8.50
8.00
7.50
7.00
6.50
6.00
VOLTS
5.50
5.00
4.50
4.00
3.50
3.00
2.50 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
PERCENTAGE
Fig. E-4. Graph of Sensor Voltage versus Humidity.
M11610
Table E-5 lists the points for Sensor Current versus Humidity. Fig. E-5 shows the graph of these points.
Table E-5. Sensor Current Versus Humidity.
Humidity Percentage Sensor Current
10 5.6 15 6.4 20 7.2 25 8.0 30 8.8 35 9.6 40 10.4 45 11.2 50 12.0 55 12.8 60 13.6 65 14.4 70 15.2 75 16.0 80 16.8 85 17.6 90 18.4
75 74-2699
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
20 18 16 14 12 10
8
CURRENT IN MILLIAMPS
6 4
0
10
20 10090807060504030
HUMIDITY IN PERCENT RELATIVE HUMIDITY
RH (%) I (mA)
5.6
10
7.2
20
8.8
30
10.4
40
12.0
50
13.6
60
15.2
70
16.8
80
18.4
90
M3131B
Fig. 5. C7600C output current vs. humidity.
Sensor Type:
C7400A1004.
Sensor Use:
Enthalpy. Table E-6 lists the points for Sensor Current versus Enthalpy (volts). Fig. E-6 shows the graph of these points.
Table E-6. Sensor Current Versus Enthalpy (Volts).
Enthalpy (volts) Sensor Current (mA)
41
51.25
61.49
71.74
81.99
92.24 10 2.49 11 2.74 12 2.99 13 3.24 14 3.49 15 3.74 16 3.98 17 4.23 18 4.48 19 4.73 20 4.98
SENSOR CURRENT VERSUS ENTHALPY (VOLTS)
5.00
4.75
4.50
4.25
4.00
3.75
3.50
3.25
3.00
2.75
2.50
2.25
ENTHALPY (VOLTS)
2.00
1.75
1.50
1.25
1.00 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
(MA)
76 74-2699
M11607
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Fig. E-6. Graph of Sensor Current versus Enthalpy (volts).
See Fig. E-7 for a partial psychometric chart for the a C7400A Solid State Enthalpy Sensor.
85
(29)90(32)95(35)
CONTROL
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
CURVE
A B C D
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17)
ENTHALPY—BTU PER POUND DRY AIR
60
(16)
55
(13)
B
50
C
(10)
45
D
(7)
40
(4)
35 (2)
44 46
80
(27)
75
(24)
70
(21)
100
90
65
(18)
A
80
70
60
50
40
100
(38)
RELATIVE HUMIDITY (%)
30
20
105 (41)
110 (43)
10
1
A
B
C
D
35
40
45
50
55
60
65
70
75
80
(2)
(4)
(7)
(10)
(13)
(16)
(18)
(21)
(24)
85
(27)
(29)90(32)95(35)
APPROXIMATE DRY BULB TEMPERATURE—°F (°C)
1
HIGH LIMIT CURVE FOR W6210D,W7210D.
Fig. E-7. Partial psychometric chart for a C7400A Solid State Enthalpy Sensor.
See Fig. E-8 for a C7400A Solid State Enthalpy Sensor output current versus relative humidity.
100
90
80
70
60
50
PERCENT RH
40
30
20 10
(4) (10) (16) (21) (27) (32) (38)
C7400A OUTPUT CURRENT
10 mA
12 mA
14 mA
16 mA
18 mA
20 mA
BA
DC
605040 70 80 90 100
TEMPERATURE °F (°C)
8 mA
6 mA
4 mA
D = 17 MA C = 15.5 MA B = 13.5 MA A = 11 MA
M11605
100 (38)
105
(41)
M11160
110
(43)
Fig. E-8. C7400A Solid State Enthalpy Sensor output current vs. relative humidity.
77 74-2699
Sensor Type:
T7242 or equivalent.
Sensor Use:
concentration.
CO
2
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
Table E-9 lists the points for Sensor Voltage versus CO
Table E-9. Sensor Voltage Versus CO
CO
Concentration PPM Sensor Voltage
2
00.00 100 0.50 200 1.00 300 1.50 400 2.00 500 2.50 600 3.00 700 3.50 800 4.00 900 4.50
1000 5.00 1100 5.50 1200 6.00 1300 6.50 1400 7.00 1500 7.50 1600 8.00 1700 8.50 1800 9.00 1900 9.50 2000 10.00
concentration. Fig. E-9 shows the graph of these points.
2
Concentration.
2
SENSOR VOLTAGE VERSUS CO2 CONCENTRATION
10
9 8 7 6 5
VOLTS
4 3 2 1 0
100 300 500 700 900 1100 1300 1500 1700 1900
200 400 600 800 1000 1200 1400 1600 1800 2000
PPM
M11611
Fig. E-9. Graph of Sensor Voltage versus CO2 concentration.
Sensor Type:
Third party (2 to 20V).
Sensor Use:
Monitor voltage. Table E-10 lists the points for Sensor Voltage versus input Voltage to A/D. Fig. E-10 shows the graph of these points.
Table E-10. Sensor Voltage Versus Input Voltage To A/D.
78 74-2699
Voltage to A/D Sensor Voltage
0.00 0.00
0.50 0.25
1.00 0.50
1.50 0.75
2.00 1.00
2.50 1.25
3.00 1.50
3.50 1.75
4.00 2.00
4.50 2.25
5.00 2.50
5.50 2.75
6.00 3.00
6.50 3.25
7.00 3.50
7.50 3.75
8.00 4.00
8.50 4.25
9.00 4.50
9.50 4.75
10.00 5.00
EXCEL 10 W7761A INPUT/OUTPUT DEVICE
SENSOR VOLTAGE VERSUS INPUT VOLTAGE TO A/D
5.00
4.50
4.00
3.50
3.00
2.50
2.00
A/D VOLTS
1.50
1.00
0.50 0
1000 300 500 700 900200 400
VOLTS
600 800
1000
M11612
Fig. E-10. Graph of Sensor Voltage versus input Voltage to A/D.
Sensor Type:
Third party.
Sensor Use:
Sensor Voltage (Vdc)/Pressure Inw (kPa) 2 to 10V, 0 to 5 inw (0 to 1.25 kPa). Table E-11 lists the points for Sensor Voltage (Vdc) versus Pressure (Inw). Fig. E-11 shows the graph of these points.
Table E-11. Sensor Voltage (Vdc) Versus Pressure (Inw).
Pressure Inw (kPa) Sensor Voltage (Vdc)
0.00 (0.00) 2.00
0.50.(0.13) 2.80
1.00 (0.25) 3.60
1.50 (0.37) 4.40
2.00 (0.5) 5.20
2.50 (0.62) 6.00
79 74-2699
3.00 (0.75) 6.80
3.50 (0.87) 7.60
4.00 (1.00) 8.40
4.50 (1.12) 9.20
5.00 (1.25) 10.00
10.00
9.00
8.00
7.00
6.00
5.00
VOLTS (VDC)
4.00
3.00
2.00 0 0.50 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00
Inw
0 0.13 0.25 0.37 0.5 0.62 0.75 0.87 1.0 1.12 1.25
kPa
Fig. E-11. Graph of Sensor Voltage (Vdc) versus Pressure (Inw).
SENSOR VOLTAGE VERSUS PRESSURE
M11963
+RPH DQG %XLOGLQJ &RQWURO +RPH DQG %XLOGLQJ &RQWURO +RPH DQG %XLOGLQJ &RQWURO 3URGXFWV
+RQH\ZHOO ,QF +RQH\ZHOO /LPLWHG+RQH\ZHOO /LPLWHH +RQH\ZHOO $* +RQH\ZHOO 3OD]D  *RUGRQ %DNHU 5RDG %|EOLQJHU 6WUDH  32 %R[  1RUWK <RUN 2QWDULR ' 6FK|QDLFK 0LQQHDSROLV 01  0+ 1 3KRQH  
)D[  
Printed in U.S.A. on recycled paper containing at least 10%
74-2699 J.D. 6-98
post-consumer paper fibers.
www.honeywell.com
Loading...