Honeywell W7754P1000, W7754Q1008, W7754K1001, W7754R4431, W7754T4431 Installation Instructions Manual

...
Page 1
W7754K,P,Q,R,S,T,V FAN COIL UNIT
HONEYWELL EXCEL 5000 OPEN SYSTEM
GENERAL INFORMATION
LonWorks SERVICE BUTTON
LonWorks
SERVICE LED
LEFT DIP SWITCH (USED = WALL MODULE CONNECTED) RIGHT DIP SWITCH (USED = TERMINAL 11 ENABLED)
TERMINAL ASSIGNMENT LABEL
BEFORE INSTALLATION
IMPORTANT
Excel 10
CONTROLLERS
It is recommended that the unit be kept at room temperature for at least 24 hours before applying power; this is to allow the evaporation of any condensation resulting from low shipping / storage temperatures.
US requirement, only: This device must be installed in a UL-listed enclosure offering adequate space to maintain the segregation of line voltage field wiring and Class 2 field wiring.
RELAYS TRIACS
ANALOG OUTPUT & ANALOG INPUTS
REMOVABLE LonWorks TERMINAL PLUG
BINARY OUTPUT FOR LOW-VOLTAGE PWM
CONTROL OF SOLID-STATE RELAY (W7754K, only)
FUSE
REMOVABLE POWER SUPPLY TERMINAL PLUG
Fig. 1. Excel 10 W7754 FCU Controller (w/o opt. cover)
triac voltage
OS no.
W7754K1001
W7754P1000
W7754Q1008
W7754R4431
W7754S2230
W7754T4431
W7754V1230
power supply
(removable plug)
25, 26
230 VAC 230 VAC
230 VAC 230 VAC
24 VAC 24 VAC
230 VAC 230 VAC
230 VAC 230 VAC
230 VAC 24 VAC
230 VAC 230 VAC
19-22
binary input, for
reading input from,
e.g., window contact,
occupancy sensor, etc.
binary input, for
reading input from
window contact
DI1
X X X X X -- -- -- -- X X -- X X X X
X X XXX X XXXX -- -- X XXX
X X XXX X XXXX -- -- X XXX
X X XXX X XXXX -- X X XXX
X X X X X -- -- X -- X -- -- X X X X
X X XXX X XXXX -- X X XXX
X X -- -- -- X -- X -- X -- X X X X X
DI2
Table 1. Overview of models
CAUTION
To avoid electrical shock or equipment damage, you must switch OFF the power supply before attaching / removing connections to/from any terminals.
n.-o. relays, for 3-speed
fan control
Fan I
Fan II
Fan III
n.-o. relay, for reheat
coil control
Reheat
OUT1 close
triac outputs, for
opening / closing valve
OUT1 open
OUT2 close
output, for low-voltage
OUT2 open
PWM control of solid-
state relay
analog output, for
variable-speed fan
control
binary input, for con-
nection to wall module
LED
analog inputs, for con-
nection to wall module
solid state
AO1
LED
FanSwitch
Sensor
Setpoint
® U.S. Registered Trademark Copyright © 2016 Honeywell Inc. EN1B-0304GE51 R0916M All Rights Reserved
Page 2
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
MOUNTING
All models have the same dimensions (W x L x H = 110 x 180 x 60 mm) (see Fig. 2) conforming to IP20. With optional terminal protection cover, width is 130 mm.
59.5
cover (optional)
terminal protection
90
110
130
Fig. 2. Excel 10 W7754 dimensions (in mm)
The unit is suitable for mounting on a standard rail (DIN EN 50022-35 x 7,5), on walls, as well as for installation in wiring cabinets or fuse boxes.
DIN Rail Mounting/Dismounting
SCREWING NOSE
(oval hole)
SCREWING NOSE
(oval hole)
EYELETS FOR
CABLE BINDERS
STIRRUP; PULL DOWN
EYELETS FOR
CABLE BINDERS
TO DISMOUNT UNIT
Fig. 3. Housing base (view from below)
The unit can be mounted onto the DIN rail simply by snapping it into place. It is dismounted by gently pulling the stirrup located in the base of the housing (see Fig. 3). When mounted on a DIN rail, the unit must be secured in place with a stopper to prevent sliding.
SCREWING NOSE
FROM RAIL
SCREWING NOSE
(round hole)
(oval hole)
Wall Mounting/Dismounting
The unit can be mounted on walls in any desired orientation. The unit is mounted by inserting 3.5-mm dowel screws through the corresponding screwing noses.
154 mm
round hole
(diameter: 4 mm)
oval hole (4x7 mm)
Fig. 4. Drilling template (view from above)
After mounting the unit onto the wall, provide for cable access by snipping out the terminal protection cover's cut-out tabs and snap it (by hand) into place on the housing. To remove the cover, place a screwdriver in the leverage slot and pry it loose.
Terminal Assignment
The unit features two rows of terminal blocks located on one side for the connection of cables to the relays, inputs, and outputs as well as for connecting the removable power supply terminal plug and removable L
NOTE: All high-voltage terminal blocks are orange-colored.
Depending on the given hardware model, the units have different power supplies and are equipped with different numbers of triac outputs, relay outputs, etc. See Table 2 on page 3.
Every unit is therefore equipped with a terminal assignment label on the top of the housing (see Fig. 1 on page 1). Unused terminals are indicated by dotted lines.
NOTE: According to VDE guidelines, it is not allowed to mix
low-voltage and high-voltage signals on the relays.
See also Table 4 on page 6.
ONWORKS terminal plug.
100 mm
EN1B-0304GE51 R0916M
2
Page 3
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
Table 2. W7754 Controller: Overview of terminals and functions (by model)
24
VAC
model
230
VAC
230
VAC
230
VAC
230
VAC
term.
#
function
(1)
K
P Q R S T V
1+2 Removable plug; receiving/sending data on the LONWORK S network X X X X X X X
BINARY INPUT (DI1), configurable (via the LNS plug-in) to read input from, e.g., a hardwired
3
window contact, occupancy sensor, etc.; suitable for dry contacts, only; max. voltage at open contact = 5 Vdc
ANALOG INPUT (AI3), permanently configured to read input from a hardwired wall module's
4
temperature setpoint adjustment knob; enabled / disabled using the left DIP switch
ANALOG INPUT (AI2), permanently configured to read input from a hardwired wall module's room temperature sensor (use NTC20k sensor, only; accuracy [w/o sensor] = 0.5 °C at 25 °C);
5
enabled / disabled using the left DIP switch
X X X X X X X
X X X X X X X
X X X X X X X
6 GND serving terminals 4, 5, 9, 10, and 11 (I/Os for wall module) X X X X X X X
7 GND serving terminal 12 (AO1) -- -- -- X -- X X
8 GND serving terminal 3 (DI1) X X X X X X X
BINARY OUTPUT (LED), permanently configured to write output to switch the LED of a hard-
9
wired wall module ON/OFF; enabled / disabled using the left DIP switch; max. voltage = 5 Vdc; max. current = 5 mA
ANALOG INPUT (AI1), permanently configured to read input on whether a hardwired wall module's 3-speed fan control knob has been set to AUTO, OFF, LOW, MEDIUM, or HIGH and
10
whether its "occupancy override" button has been pressed; enabled / disabled using the left DIP switch
BINARY INPUT (DI2), permanently configured to read input on condition (open/closed) of
11
window contact; enabled / disabled using the right DIP switch; suitable for dry contacts, only; max. voltage at open contact = 5 Vdc
ANALOG OUTPUT (AO1), used (depending upon configuration via the LNS plug-in) to control a
12
variable speed fan or to control a proportional valve
A normally-open relay (Rel4), permanently configured to write output to switch a hardwired
13+14
electrical reheat coil ON/OFF; switching voltage = 24...230 Vac; switching current = 0.05...10 A
(2)
or to control a 6-way ball valve
(6)
X X X X X X X
X X X X X X X
X X X X X X X
-- -- -- X -- X X
-- X X X -- X X
15 A common terminal for terminals 16, 17, and 18 X X X X X X --
A normally-open relay (Rel3), permanently configured to write output to a hardwired three-speed
(3)
16
fan, setting it to HIGH
A normally-open relay (Rel2), permanently configured to write output to a hardwired three-speed
(3)
17
fan, setting it to MEDIUM
A normally-open relay (Rel1), permanently configured to write output to a hardwired three-speed
(3)
18
fan, setting it to LOW
(4)(7)
19
Triac output (Triac1), perm. configured to write output to OUT1 & close hardwired valve --
(4)(7)
20
Triac output (Triac2), perm. configured to write output to OUT1 & open hardwired valve --
(4)(7)
21
Triac output (Triac3), perm. configured to write output to OUT2 & close hardwired valve -- X X X -- X --
(4)(7)
22
Triac output (Triac4), perm. configured to write output to OUT2 & open hardwired valve X X X X X X X
24 VAC common terminal for terminals 19 & 20; internally connected to terminal 24;
(3)(7)
23
W7754T4431, only: internally connected also to terminal 27
24 VAC common terminal for terminals 19 & 20; internally connected to terminal 23;
(3)(7)
24
W7754T4431, only: internally connected also to terminal 27
The "N" (25) & "L" (26) power supply terminals (removable plug); W7754Q: 24 VAC (20%),
25+26
50/60 Hz; W7754K,P,R,S,T,V: 230 VAC (-15%/+10%), 50/60 Hz
(7)
27
24 VAC / 200 mA auxiliary voltage; internally connected to terminals 23 & 24 -- -- -- -- -- X --
(7)
28
A common terminal for terminal 27; internally connected to terminals 6, 7, & 8 -- -- -- -- -- X --
(1)
The W7754K features an extra socket (2-pin connector located to the left of the terminal blocks) containing an output suitable for attachment to a solid-state relay (use only Carlo Gavazzi RS1A23D25-P64; max. voltage = 12 VDC; max. current = 12 mA at 10 VDC) for low-voltage PWM control in high-current electrical reheat applications. To enable it, term. 19 and 20 must be configured (via LNS plug-in) for “Heat” -> “PWM”.
(2)
For AO1 (terminal 12) to be used to control a proportional valve, OUT1 (term. 19 and 20) must be configured (via LNS plug-in) for “PWM”, and the fan must not be configured for “variable speed fan”.
(3)
If all three relays (term. 16, 17, and 18) are switched OFF, the 3-speed fan will likewise be switched OFF. Switching voltage = 24...230 VAC; switching current =
0.05...3 A (max. 3 A for all three relays together).
(4)
Switching voltage = 230 VAC (W7754K,P,R,S,V) or 24 VAC (W7754Q,T), max. switching current = 0.5 A; max. peak (10 sec) current = 1 A
(5)
For output for low-voltage PWM control of a solid-state relay (W7754K, only) to be used, these terminals must be configured (via LNS plug-in) for “Heat” -> “PWM”.
(6)
In order for AO1 (terminal 12) to be used to control a 6-way ball valve from Belimo, OUT1 must be configured for "Not USED," OUT2 (term. 21 and 22) must be configured (via LNS plug-in) for "Changeover Mode" type "Floating Mid," and the fan must not use the analog output (no fan or 1…3-speed fan).
(7)
Total current draw of terminals 19 through 24 and 27 through 28 must not exceed 450 mA.
X X X X X X --
X X X X X X --
X X X X X X --
(5)
X X X -- X --
(5)
X X X X X X
X X X X X X X
X X X X X X X
230
230
VAC
VAC
3
EN1B-0304GE51 R0916M
Page 4
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
V
V
V
V
Power Supply
General Information
CAUTION
To prevent a risk of injury due to electrical shock and/or damage to device due to short-circuiting, low­voltage and high-voltage lines must be kept physically separate from one another.
NOTE: All wiring must comply with applicable electrical
NOTE: To comply with CE requirements, devices having a
Use a min. of 18 AWG (1.0 mm (2.5 mm
Power is supplied via a removable terminal plug (attached to terminals 25, 26) allowing individual units to be disconnected from the power supply without disturbing the operation of other devices powered by the same source. See Fig. 5.
NOTE: To prevent a risk of short-circuiting and damage to
codes and ordinances. Refer to job or manu­facturers’ drawings for details. Local wiring guide­lines (e.g., IEC 364-6-61 or VDE 0100) may take precedence over recommendations provided in these installation instructions.
voltage of 50...1000 Vac or 75...1500 Vdc but lacking a supply cord, plug, or other means for disconnecting from the power supply must have the means of disconnection incorporated in the fixed wiring. This means of disconnection must have a contact separation of at least 3 mm at all poles.
2
2
) for all power wiring.
Excel 10
W7754K,P,R,S,T,V
230
230
Vac
Vac
25 26
230
230
Vac
Vac
25 26
230
230
Vac
Vac
25 26
NL
230 Vac (-15% / +10%),
50 / 60 Hz
) and a max. of 14 AWG
Excel 10 W7754Q
24
24
ac
ac
252526
24
24
ac
ac
26
24 Vac
(+/-20%)
NL
230 Vac (-15% / +10%),
50 / 60 Hz
Fig. 5. Connection to power supply
your unit, do not reverse the polarity of the power connection cables, and avoid ground loops (i.e. avoid connecting one field device to several controllers).
Electrical Data
W7754K,P,R,S,V: 230 Vac +10%, -15%, 50/60 Hz;
W7754T: 230 Vac +10%, -15%, 50/60 Hz;
W7754Q: 24 Vac 20%, 50/60 Hz
max. 6 VA power consumption (unloaded)
max. 12 VA power consumption (unloaded)
max. 6 VA power consumption (unloaded)
Wall Modules
The T7460 and T7560 Wall Modules can be used in con­junction with the W7754 to perform room temperature sensing, set-point adjustment, fan speed manual override, and occupancy override. When hardwired to the controller (via terminals 4, 5, 6, 9, and 10), the wall module's LED/LCD can be configured to provide information about
any override of the controller by, e.g., manual operation of
the wall module or the receipt by the controller of a net­work command (see section "Configuration of LED to Display Info on Overrides" below);
the controller's effective occupancy mode (see sections
"Configuration of LED to Display Info on Occupancy Mode" and "Configuration of LCD to Display Info on Occupancy Mode” below).
NOTE: The left DIP switch located on the top of the con-
NOTE: The intended use of the wall module's buttons must
T7460C
T7460D
T7460E
T7460F
T7560A
T7560B
Example:
The T7560A has a left button configurable as a fan speed button, a middle button configurable as a unit ON/OFF button, and a right button for override. See T7460 Wall Modules Installation Instructions (95-7610) and T7560 Digital Wall Module Installation Instructions (EN1B-0146GE51) for details.
troller (see Fig. 1 on page 1) is used to indicate that a wall module can be hardwired to the controller. Setting the left DIP switch to USED means that a wall module can be hardwired; setting it to UNUSED means that no wall module can be hardwired. Use only an appropriate tool (e.g., ball-point pen) to set the DIP switch.
be configured using Honeywell's LNS plug-in.
Table 3. Supported wall module functions
T7560 button
--
override unit ON/OFF fan speed
-- --
-- -- --
--
--
-- --
left -- --
middle --
right
left -- --
middle --
right
-- --
--
--
--
EN1B-0304GE51 R0916M
4
Page 5
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
Configuration of the Wall Module's LED / LCD
When either a T7460 or a T7560 Wall Module has been hardwired to the W7754, the module's LED can be configured (using Honeywell's LNS plug-in) to provide information about, e.g., overrides or effective occupancy modes. The LCD of a T7560 Wall Module can likewise be configured to display such information.
Configuration of LED to Display Info on Overrides
The wall module's LED can be configured to indicate if an override has been activated by either the wall module's over­ride button being pushed or because the controller has re­ceived a network command. Specifically:
If the wall module's LED is OFF, then no override (from
the wall module or the L effect.
If the wall module's LED is ON continuously, the override
button or a network command has placed the controller into the "occupied" or "override" mode (but if the override button is again pushed or if a cancellation network command is received or if the override time expires, the controller will return to its scheduled occupancy mode).
If the wall module's LED flashes once per second, the
override button or a network command has placed the controller into the "unoccupied" mode (however, if the override button is again pushed or if a cancellation net­work command is received, the controller will return to its scheduled occupancy mode).
If the wall module's LED flashes twice per second, a
network command has placed the controller into either the "standby" or the "occupied" mode.
If the wall module's LED flashes four times per second, the
controller is responding to a network management "wink" command.
Configuration of LED to Display Info on Occupancy Mode
The wall module's LED can also be configured to indicate the effective occupancy mode of the W7754. Specifically:
If the wall module's LED is OFF, the controller is in the
"unoccupied" mode.
If the wall module's LED is ON, the controller is in the
"occupied" mode.
If the wall module's LED flashes once per second, the
controller is in the "standby" mode.
If the wall module's LED flashes four times per second, the
controller is responding to a network management "wink" command.
Configuration of LCD to Display Info on Occupancy Mode
The T7560 Wall Module's LCD can be configured to display various symbols to indicate the effective occupancy mode of the W7754. Specifically:
If
is displayed continuously, the controller is in the "occupied" or "override" mode; if it flashes, the given mode has been overridden.
If
is displayed continuously, the controller is in the "standby" mode; if it flashes, the "standby" mode has been overridden.
ONWORKS network) is currently in
If
is displayed continuously, the controller is in the "unoccupied" mode; if it flashes, the "unoccupied" mode has been overridden.
NOTE: If all three of these symbols are flashing simul-
taneously, the controller is responding to a network management "wink" command.
means that the controller is OFF.
and mean that the controller is OFF, but that "frost protection" has been enabled.
LonWorks Communications
General Information
The unit is equipped with a free-topology transceiver for communication on L network is insensitive to polarity, eliminating the possibility of installation errors due to miswiring.
Different network configurations (daisy-chain, loop, and star configurations, or any combination thereof) are possible (see also Excel 50/500 L Description, EN0B-0270GE51).
Connecting to the LONWORKS Network
IMPORTANT
Do not bundle wires carrying field device signals or L
ONWORKS communications together with high-
voltage power supply or relay cables. Specifically, maintain a min. separation of 3 inches (76 mm) between such cables. Local wiring codes may take precedence over this recommendation.
IMPORTANT
Try to avoid installing in areas of high electro­magnetic noise (EMI).
The unit must be wired to the L IV 22 AWG (Belden part number 9D220150) or plenum-rated level IV 22 AWG (Belden part number 9H2201504) non­shielded, twisted-pair, solid-conductor wire. When possible, use Honeywell AK3781, AK3782, AK3791, or AK3792 cable (US part numbers). See Excel 50/5000 L Mechanisms, EN0B-0270GE51, for details, including max. lengths. Use wire with a min. size of 20 AWG (0.5 mm max. size of 14 AWG (2.5 mm
W7754K,P,Q,R,S,T,V
1 2 1 2
Fig. 6. Connection to LonWorks network and termination
module (here: daisy-chain network configuration)
The unit is connected to the L removable terminal plug (attached to terminals 1 and 2) permitting individual units to be connected / disconnected without disturbing the operation of other devices.
ONWORKS® networks. The LONWORKS
ONWORKS Mechanisms Interface
ONWORKS network using level
ONWORKS
2
).
D-71101 Schönaich Made in Germany
W7754K,P,Q,R,S,T,V
ONWORKS network via a
D-71101 Schönaich Made in Germany
2
) and a
termination
module
5
EN1B-0304GE51 R0916M
Page 6
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
Depending upon the chosen network configuration, one or two terminations (see section "L
8) may be required.
ONWORKS Termination" on page
Inputs/Outputs
Wiring the Inputs/Outputs
Use a min. size of 20 AWG (0.5 mm2) and a max. of 14 AWG (2.5 mm all input/output cables is 400 m.
Two wires with a total thickness of 14 AWG can be twisted together and connected using a wire nut (include a pigtail with this wire group and attach the pigtail to the individual terminal block). Deviations from this rule can result in improper electrical contact. Local wiring codes may take precedence over this recommendation.
Binary Inputs
The unit's binary inputs are suitable for connection with dry contacts, only.
Relay Outputs
The relay outputs can be configured (via the LNS plug-in) for a variety of different functions. Once the relay outputs have been configured, the corresponding devices can then be con­nected to them directly.
Hardware Limits
Min. current of 50 mA required to ensure reliable contact.
The normally-open contacts are designed for a max.
NOTE: If inductive components are to be connected to the
Triac Outputs
The triac outputs can be configured (via the LNS plug-in) for a variety of different functions, e.g., for connection to either a floating drive or to a thermal actuator (see Table 4 to Table 6). Once the triac outputs have been configured, the cor­responding devices can then be connected to them directly.
NOTE: VC6983 generates high-voltage pulses in the end
2
) for all input/output connections. The max. length of
continuous current of 3 A (for relays 1, 2, and 3 together) and 10 A (relay 4), respectively.
relays and if these relays switch more often than once every two minutes, these components must be prevented from causing harmful interference to radio or television reception (conformance with EN 45014).
position and therefore cannot be used in conjunction with the W7754.
Hardware Limits for W7754K,P,R,S,T,V (230 Vac Power Supply)
Low signal: 0 V; high signal: 230 Vac Max. allowable continuous current for each individual triac
output: 500 mA
Max. allowable peak current (for 10 seconds) for each
individual triac output: 1 A
Max. allowable continuous current for all of the triac
outputs together: 1 A.
cos  > 0.8
Hardware Limits for W7754Q1008 (24 Vac Power Supply)
Low signal: 0 V; high signal: 24 Vac Max. allowable continuous current for each individual triac
output: 500 mA
Max. allowable peak current (for 10 seconds) for each
individual triac output: 1 A
Max. allowable continuous current for all of the triac
outputs together: 1 A.
cos  > 0.8
Table 4. W7754K Output assignments
output
type
1-stage
PWM -- enabled for heating PWM
thermal -- enabled for heating ON / OFF
output
type
floating -- close open close open --
1-stage
2-stage
3-stage
PWM -- -- PWM -- PWM
thermal -- --
stage
0 -- OFF
1 -- ON
Table 5. W7754P,Q,R,T, Output assignments
stage
0 -- OFF -- OFF --
1 -- ON -- ON --
0 OFF OFF OFF OFF --
1 OFF ON OFF ON --
2 ON ON ON ON --
0 OFF OFF OFF OFF --
1 OFF ON OFF ON --
2 ON OFF ON OFF --
3 ON ON ON ON --
solid state OUT2
plug terminal 22
OUT1 OUT2
19 20 21 22 12
ON / OFF
--
AO (W7754R,T,
figured for “PWM”
parallel to OUT1
ON / OFF
only)
If OUT1 is con-
and fan is not
configured for
“variable-speed
fan”, AO runs in
--
EN1B-0304GE51 R0916M
6
Page 7
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
Table 6. W7754S,V Output assignments
output
type
1-stage
stage
0 -- OFF -- OFF --
1 -- ON -- ON --
OUT1 OUT2
19 20 21 22 12
PWM -- -- PWM -- PWM
thermal -- --
ON / OFF
ON /
-­OFF
AO (W7754V,
only)
If OUT1 is con-
figured for “PWM”
and fan is not
configured for “variable-speed fan”, AO runs in
parallel to OUT1
--
Analog Inputs
The unit is equipped with two analog inputs (for connection to a room sensor and to a wall module with temperature setpoint adjustment, respectively).
Table 7. Analog input usage
analog input wall module
AI1 room sensor 1) AI2 setpoint adjustment
1) If sensor measures a temperature outside range of 0...70 °C, this is interpreted as a sensor break / short circuit.
Analog Output
The W7754R, W7754T, and W7754V feature an analog output which can be used to control
a variable speed fan, or a proportional valve (provided that, via the LNS plug-in,
OUT1 has been configured for “PWM” and the fan has not been configured for “variable speed fan”), or
a 6-way valve (provided that, via the LNS plug-in, OUT1
has been configured for “Not USED,” OUT2 has been configured for the “Changeover Mode” of type “Floating Mid,” and the fan is not using the analog output (no fan or 1…3-speed fan)).
Table 8. Analog output usage
voltage / current
resolution
NOTE: Connecting 24 Vac to the analog output will damage
the hardware.
0…10 V, -1 / +5 mA
8 bit
Table 9. Use of the analog output
function fan output
1 mode
var.-speed fan var.-
0…10 V actu­ator with prop. characteristic
0…10 V actu­ator with “floating mid” characteristic
2…10 V actu­ator with 6-way valve charac­teristic
speed fan
no fan or 1…3­speed fan
no fan or 1…3­speed fan
no fan or 1…3­speed fan
don’t care
heat, cool or change­over
change­over mode
not used - change-
output
1 type
don’t care
PWM don’t
floating mid
OUTPUT 1
10.0 V
5.0 V
0.0 V 100%
0%
Fig. 7. Operational sequence with “floating mid
characteristic” on the analog output (0….10 V)
AO (0...100% = 0...10 V),
no feedback on LonWorks network
no heat, no cool
0% 0%
nvoCoolOutput nvoHeatOutput
nvoFCUStatus.output_position[0]
output
2 mode
don’t care
care
not used -
over mode
100%
100%
output
2 type
don’t care
don’t care
floating mid
7
EN1B-0304GE51 R0916M
Page 8
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
OUTPUT 2
10.0 V
7.3 V
6.0 V
4.7 V
2.0 V
0.0 V 100%
0%
Fig. 8. Operational sequence with Belimo 6-way valve
connected to the analog output (2….10 V)
Replacing the Fuse
NOTE: Before replacing the fuse (see also Fig. 1 on page
1), disconnect the controller from the power source by detaching the removable terminal plug attached to terminals 25 and 26.
AO (0...100% = 0...10 V),
no feedback on LonWorks network
no heat, no cool
0% 0%
nvoCoolOutput nvoHeatOutput
nvoFCUStatus.output_position[0]
100%
100%
Possible Problems and Recommended Actions
Check if the LONWORKS service LED's behavior is changed if you switch the power OFF/ON. Please contact Honeywell if this does not solve the problem.
Accessories
Terminal Protection Cover
Required for wall mounting. Set of eight covers.
order no.: XAL_COV_L
LONWORKS Termination
One or two LONWORKS terminations are required, depending on the given LonWorks bus layout. See section "Connecting to the L
ONWORKS Network" on page 5.
The following L
XAL-Term2 L
Module, which can be mounted on DIN rails and in fuse boxes
1
2
ONWORKS termination module is available:
ONWORKS Connection and Termination
LONWORKS TERMINATION
PLUG-IN JUMPER
5
6
PARK POSITION
(NO TERMINATION)
CAUTION
Depending upon actual wiring, even after you have switched OFF the power supply, the relays may still be under high voltage.
When replacing the controller's fuse, please replace with the same type listed on the terminal assignment label (e.g.: F2.5H250V).
Troubleshooting
All units feature a LONWORKS service LED and corresponding L
ONWORKS service button (see Fig. 1) for commissioning and
troubleshooting.
When the service button is pressed, the service pin message is broadcast.
See Table 10 on page 9 for a description of the meaning of the various different possible behaviors of the L service LED. For more information on standard service LED behavior, refer to Motorola L
ONWORKS Technology Device
Data Manual, page AL-190.
ONWORKS
3
4
1
5
2
6
3
4
REMOVABLE SCREW-TYPE
2-POLE TERMINAL BLOCK
Fig. 9. L
ONWORKS connection and termination module
FTT/LPT BUS FTT/LPT FREE
FTT/LPT
BUS TOPOLOGY:
105 OHM
100 μ
105 Ohm
100 μ
1
2
FTT/LPT
FREE TOPOLOGY:
52.3 OHM
100 μ
52.3 Ohm
100 μ
1
2
EN1B-0304GE51 R0916M
8
Page 9
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
Table 10. LONWORKS Service LED Behaviors and Meanings
1 LED remains OFF after power-up.
2
3
4 LED flashes briefly periodically.
5
6a
6b
6c
6d
7
8
LED blinking pattern meaning
Defective device hardware. Suspect power supply problems, clock problems, or defective Neuron Chip.
LED is lit continuously after first power-up.
LED flashes at power-up, goes OFF, then is lit continuously.
LED repeatedly blinks ON for 1 s and OFF for 1 s.
OFF 10 s. Afterwards, service LED turns ON and remains ON, indicating completion of blanking process.
OFF 1 s. The service LED is then lit continuously.
OFF = 1...15 s, depending on application size and system clock. Service LED then repeatedly blinks ON for 1 s and OFF for 1 s.
OFF indefinitely (1...15 s to load internal EEPROM; remains OFF).
LED remains OFF after a short ON duration.
LED flashes ON. Controller has received
Defective hardware.
Controller lacks application.
Controller probably ex­periencing continuous watchdog resets, or external memory or EEPROM is corrupt.
Controller is unconfigured but has an application.
Using EEBLANK on a Neuron 3150 Chip-based custom node.
First power-up with a new PROM on a Neuron 3150 Chip-based customized node. Application-less firmware state exported.
Controller is configured and running normally.
WINK command from net­work. Other physical outputs are unaffected.
Approvals, Certifications, and Standards
Approvals and Certifications
CE-approved Certified as per LonMark® Application Layer Guidelines V
3.0, thus interoperable with all other devices in open
ONWORKS® networks (incl. 3
L
EUBAC-certified as follows:
W7754Q1008:
rd
-party devices)
eu.bac
020706
Cert
Temperature Control Accuracy (CA)
W7754P1000, W7754Q1008 with Motorized Actuator
FCU heating mode: 0.5 K FCU cooling mode: 0.2 K
(min. CA values requested by EUBAC for fan coil unit applications: 1.4 K)
W7754R4431, W7754S2230 with Low-Cost Thermal Actuator
FCU heating mode: 0.8 K FCU cooling mode: 0.9 K
(min. CA values requested by EUBAC for fan coil unit applications: 1.4 K)
W7754R4431, W7754T4431 with Floating-Point Actuator
(PID parameters: Xp = 1.5; Tn = 1100; Dn = 600)
FCU heating mode: 0.2 K FCU cooling mode: 0.1 K
Classification according to EN 60730-1
EN 60730 sub part: EN 60730-2-9
Environmental conditions: For use in home (residential,
commercial, and light-industrial) environments
Construction: independently mounted control
Action: type 1.C
Rated impulse voltage: 2500 V at 230 V; 500 V at 24 V
Pollution degree: Class 2
Protection against shock: Class 0 (without terminal cover)
Class II (with terminal cover)
Software class: Class A
Classification according to EN 60529
(Degree of protection provided by enclosures)
IP20
Ambient Environmental Limits
Operating temperature: 0 … +50 °C at 5…90% r.H.
Storage temperature: -40 … +70 °C at 5…90% r.H.
9
EN1B-0304GE51 R0916M
Page 10
EXCEL 10 W7754K,P,Q,R,S,T,V FCU CONTROLLERS INSTALLATION INSTRUCTIONS
Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany Phone +49 (0) 7031 637 01 Fax +49 (0) 7031 637 740 http://ecc.emea.honeywell.com
EN1B-0304GE51 R0916M Subject to change without notice
Loading...