Appendix A. Using E-Vision to Commission a Fan Coil Unit .................................................................................................38
Appendix B. Configuring for Master/Slave Operation.............................................................................................................39
Appendix C. Complete List of Excel 10 FCU Controller User Addresses .............................................................................41
Appendix D. Q7750A Excel 10 Zone Manager Point Estimating Guide.................................................................................82
Temperature Sensor Calibration .............................................................................38
On the following pages changes have been made compared to the previous release of this document:
Page:Change:
EN0B-0377GE51 R07032
EXCEL 10 FAN COIL UNIT CONTROLLER - SYSTEM ENGINEERING
INTRODUCTION
Description of Devices
The W7752D,E,F,G,J and W7754K,L,M,N,P Fan Coil Unit
(FCU) Controllers all belong to the Excel 10 family product
line. FCU systems control the space temperature in a given
room by regulating the heating and/or cooling equipment
which control the temperature of the air delivered to that
space and the fan which controls air flow. Reheat coils are
often included at the fan coil unit. Excel 10 FCU controllers
are capable of stand-alone operation; however, optimum
functional benefits are achieved when the network
communication capabilities are used.
Excel 500
The zone controlled by the Excel 10 FCU controllers will
typically use an Excel 10 wall module with a temperature
sensor for space temperature measurement, analog setpoint
input, bypass push-button, and occupancy/unoccupancy
override. See page 4 for form numbers of Excel 10 wall
module literature for further information.
The Excel 500 can assume all of the Excel 10 FCU
controllers' scheduling functions. The number of Excel 10
FCU controllers on the L
ONWORKS network is determined by
the rules of LonWorks network design (see Table 10). Frontends can be either EBNI, SymmetriE, or SynOpsys,
depending upon the size and complexity of the connected
system.
PCLTA10
PCC10
Excel 10 W7754
FCU Controller
LonWorks network
ONUNUSED
UNUSED
W7754Kxxxx
0345
WALL MOD.
USED
+ -
RS1A
23D25
LON
Honeywell
DI2
USED
230 Vac, 50/60 Hz
D-71101 Schönaich
max. 5 VA unloaded
Made in Ger man y
GND9LED10FAN11DI2
triac
2 A10A
0.5 A
8
12
321
4 5 6
23247
1314
15 181716
1920
2122
2526
2A/M
IIIII I
DI1
SET
SENS
534
21
T7460 / T7560
LN
com
com
close
open
close
open
GND
230 V
fan
L
OUT1OUT2
230 V
N
230 Vac
Excel 10 W7752
FCU Controller
Excel 10
wall module
Fig. 1. Typical EXCEL 5000® System overview
Excel 10
wall module
3EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER - SYSTEM ENGINEERING
Products Covered
This System Engineering Guide describes how to apply the
Excel 10 FCU controller and the accessories to typical FCU
applications. The specific devices covered include:
• W7752D,E,F,G, and J FCU Controllers.
• W7754K,L,M,N, and P FCU Controllers.
• T7460 Wall Modules.
• T7560 Wall Modules.
• for further products, see Appendices.
Organization of Manual
The Introduction and Application Steps 1 through 5 provide
the information needed to make accurate ordering decisions.
Application Step 6 and the Appendices include configuration
engineering that can be started using E-Vision software after
the devices and accessories are ordered. Application Step 7
is troubleshooting. Information provided in support of the use
of third-party L
ONWORKS communication packages to con-
figure FCU Controllers is found in the Appendices.
The organization of the manual assumes a project is being
engineered from start to finish. If you are adding to or
changing an existing system, the Table of Contents can
guide you to the relevant information.
Applicable Literature
The following is a list of documents containing information
related to the Excel 10 FCU Controller and the EXCEL 5000
System in general.
Form No.Title
EN0B-0376GE51Excel 10 W7752D,E,F,G,J FCU
Controller Specification Data
EN1B-0250GE51Excel 10 W7752D,E,F,G,J FCU
Controller Installation Instructions
EN1B-0251GE51Excel 10 W7754K,L,M,N,P FCU
Controller Installation Instructions
74-3083Excel 10 T7460 Wall Modules
Specification Data
95-7610Excel 10 T7460 Wall Modules
Installation Instructions
74-3097Excel 10 T7560 Wall Modules
Specification Data
95-7620Excel 10 T7560 Wall Modules
Installation Instructions
74-2950Excel 10 Q7750A, Excel 10 Zone
Manager Specification Data
95-7509Excel 10 Q7750A Zone Manager
Installation Instructions.
95-7554Excel 10 FTT/LPT 209541B
Termination Module Installation
Instructions
95-7510Excel 10 Q7751A Router Installation
Instructions (US only)
95-7511Excel 10 Q7752A Serial Interface
Installation Instructions (US only)
74-2588Excel E-Vision User Guide
74-5587Excel CARE User Guide
74-2039XBS User’s Manual
74-5018XBS Application Guide
Product Names
The W7752 Controller is available in five models:
•W7752D FCU Controller with 230 Vac power input and
with reheat relay.
•W7752E FCU Controller with 230 Vac power input without
reheat relay.
•W7752F FCU Controller with 115 Vac power input with
reheat relay.
•W7752G FCU Controller with 115 Vac power input without
reheat relay.
•W7752J FCU Controller with 100 Vac power input without
reheat relay.
The W7754 Controller is available in five models:
•W7754K FCU Controller with 230 Vac power supply, one
triac output, and one digital output for the low-voltage
Pulse-Width Modulated (PWM) control of a solid-state
relay employed in high-current electric reheat
applications
•W7754L FCU Controller with 24 Vac power supply and
two triac outputs
• W7754M FCU Controller with 230 Vac power supply
• W7754N FCU Controller with 230 Vac power supply and
two triac outputs
•W7754P FCU Controller with 230 Vac power supply, four
triac outputs, and an extra, fourth relay
The 2000-series FCU controllers can use any of the following
Excel 10 wall modules:
• T7460A with temperature sensor.
• T7460B with temperature sensor and setpoint adjustment.
• T7460C with temperature sensor, setpoint adjustment,
and bypass button and LED.
•T7460D with temperature sensor, setpoint adjustment and
5-position fan switch.
•T7460E with temperature sensor, setpoint adjustment,
bypass button and LED, and 3-position fan switch.
•T7460F with temperature sensor, setpoint adjustment,
bypass button and LED, and 5-position fan switch.
•T7560A with temperature sensor, unit enable button,
setpoint adjustment, bypass button, LCD display and
configurable fan override with up to five settings.
•C7608A Return Air Sensor (Europe, only).
Refer to the Table 15 (see section "Step 5. Order
Equipment") for complete listing of all available part numbers.
Control Application
FCU systems in commercial buildings control room
temperature through the control of heat and/or cold water
valves and fan speed. Electric reheat coils may also be used
in the system. The FCU Controller is located in the fan coil
unit and is typically connected to an Excel 10 wall module
which incorporates a temperature sensor, setpoint and fan
EN0B-0377GE51 R07034
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
speed controls, and a bypass or override button. Fig. 2
shows a typical FCU control application.
Excel 10 W7754
FCU Controller
ONUNUSED
UNUSED
W7754Kxxxx
DI2
USED
GND9LED10FAN11DI2
8
321 4 5 623247
DI1
Honeywell
0345
230 Vac, 50/60 Hz
D-71101 Schönaich
max. 5 VA unloaded
Made in Germany
triac
2 A10A
0.5 A
12
131415 181716
192021 22
2526
2A/M
III II I
LN
com
com
close
open
close
open
SET
GND
230 V
fan
SENS
L
5342 1
OUT1OUT2
230 V
N
T7460 / T7560
230 Vac
WALL MOD.
USED
+ -
RS1A
23D25
LON
wall
contact
Excel 10
wall module
LonWorks network
Fig. 2. Typical Excel 10 FCU control application
Control Provided
The Excel 10 FCU controllers provide room temperature control for two- and four-pipe fan coil units with optional electric
heating coil. The basic control sequence is shown in Fig. 3.
As space temperature falls below the heating setpoint, the
heating output is increased. As space temperature increases
above the cooling setpoint, the cooling output is modulated to
100%. Switching levels for staged heating/cooling and fan
speeds are configurable. The fan may still be configured to
run continuously during the zero energy band in the occupied
mode. Additional configurable fan control features include fan
min. ON and OFF times, run-up times, and overrun times.
The Excel 10 FCU controllers use a PID control algorithm
with which each of the three parameters can be configured.
There are additional configurable boost parameters
(HeatBoost and CoolBoost) which specify a range outside of
which the heating or cooling outputs are turned on fully for
faster response (for thermal actuators this specifies the control hysteresis). The controllers are delivered with factory
defaults for each of the parameters.
5EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Fig. 3. Control sequence diagram
Setpoints
Setpoint Knob
The Excel 10 FCU controllers may be connected to an Excel
10 wall module equipped with a setpoint knob. When
configured (UseWallModSpt), the value from the setpoint
knob is used to calculate the "occupied" setpoint for the
heating and the cooling modes. There are two options
(SptKnob) which determine how the setpoint used by the
control algorithm is calculated: "relative" (or "offset") and
"absolute middle". When configured for "relative", the Excel
10 wall module setpoint knob represents a number from
-9...+9 DDF(-5...+5 K) which is added to the configured
"occupied" and "standby" setpoints for the heating and the
cooling modes (SptCoolOcc and SptHeatOcc). When
SptKnob is set to "absolute middle", the setpoint knob
becomes the mid-point of the Zero Energy Band (ZEB)
extending between the "occupied" or "standby" setpoints for
the heating and the cooling modes. The range of the ZEB is
found by taking the difference between the "occupied" or
"standby" setpoints configured for the heating and the cooling
modes; in the case of "absolute middle", the current
"occupied" and "standby" setpoints are therefore found as
follows:
"occupied" setpoint:
SrcRmTempSptEff (in cooling mode) =
SrcRmTempSptHw + (SptCoolOcc - SptHeatOcc) / 2
SrcRmTempSptEff (in heating mode) =
SrcRmTempSptHw - (SptCoolOcc - SptHeatOcc) / 2
"standby" setpoints:
SrcRmTempSptEff (in cooling mode) =
SrcRmTempSptHw + (SptCoolStby - SptHeatStby) / 2
SrcRmTempSptEff (in heating mode) =
SrcRmTempSptHw - (SptCoolStby - SptHeatStby) / 2
SptKnobLowLim and SptKnobHiLim. In the case of absolute
"occupied" and "standby" setpoints, the setpoint knob still
represents the mid-point of the ZEB, even when set to either
of these limits. The actual setpoints are given by the
equations shown above. When the setpoint knob is configured to be "relative", the lowest actual "occupied" setpoint
allowed is equal to SptHeatOcc - SptKnobLowLim, and the
highest allowed is equal to SptCoolOcc + SptKnobHiLim. The
lowest and highest "standby" setpoints are found in an
analogous way.
Setpoint from Network
When not configured for UseWallModSpt, DestRmTempSpt
must be bound to another node that provides a setpoint.
When bound and when a valid update is received,
DestRmTempSpt is used with the appropriate ZEB:
The "unoccupied" setpoint does not depend on
DestRmTempSpt at all.
Setpoint Offset
Third-party nodes may be bound to DestSptOffset in order to
shift the setpoint in the range of -18...+18 DDF (-10...+10 K).
When in the "unoccupied" mode, the remote setpoint knob is
ignored, and the configured setpoints for those modes are
used instead.
Setpoint Limits
Setpoints are limited to the range of 50...95°F (10...35°C).
The value of the setpoint knob (SrcRmTempSptHw) is limited
to the range provided by the configuration parameters
EN0B-0377GE51 R07036
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Table 1. Example setpoint values based upon default configuration – "absolute middle" setpoint knob (°C)
occupancy
mode
"occupied"23212212220
"standby"25196212418
"unoccupied"281612X2816
NOTES:
1. Sample value shown. Limited by default configuration settings to the range of 12...30°C.
2. Limited to the range of 10...35°C.
3. = setpoint knob + (ZEB/2)
4. = setpoint knob – (ZEB/2)
Table 2. Example setpoint values based upon default configuration - Relative setpoint knob (°C)
occupancy
mode
"occupied"23212-22119
"standby"25196-22317
"unoccupied"281612X2816
NOTES:
1. Sample value shown. Limited by default configuration settings to the range of -5...+5°C.
2. Limited to the range of 10...35°C.
3. = configured cooling setpoint + setpoint knob
4. = configured heating setpoint + setpoint knob
Bypass
Bypass Mode
During periods scheduled as being unoccupied, the Excel 10
wall module's bypass push-button may be used to force the
FCU controller into the "occupied" mode. The FCU controller
can also be forced into the "occupied" mode by means of a
ONWORKS network command (DestManOcc set to
L
OC_BYPASS). The controller will then remain in "bypass"
mode until:
1. The bypass timer has timed out, or
2. The user again presses the Excel 10 wall module's
bypass push-button, thus cancelling the "bypass"
mode, or
3. The occupancy schedule (DestSchedOcc network
input) switches the mode to "occupied".
4. The network input DestManOcc is set to OC_NUL.
The Excel 10 wall module indicates the current bypass mode
status (see Excel 10 wall module literature for further
information).
Bypass Timer
When the "bypass" mode has been activated, the bypass
timer is set to BypTime (default of 180 minutes), at the end of
which the mode will revert to its original state (see Excel 10
wall module literature for further information).
Continuous Unoccupied Mode
The "continuous unoccupied" mode is entered when an Excel
10 wall module is configured to allow it and if :
• (in the case of the T7460) the bypass button is pressed for
four to seven seconds (until the LED blinks),
• (in the case of the T7560) the bypass button is pressed for
more than five seconds (until the flashing moon appears).
configured
cooling setpoint
configured
cooling setpoint
configured
heating setpoint
configured
heating setpoint
ZEB
ZEB
setpoint
knob
setpoint
1
knob
effective cooling
1
effective cooling
setpoint
setpoint
2,3
2,3
effective heating
setpoint
effective heating
setpoint
The FCU controller can also be forced into the "continuous
unoccupied" mode by means of a L
ONWORKS network
command (DestManOcc set to OC_UNOCCUPIED). The
FCU controller will then remain in this mode indefinitely, or
until the bypass button is pressed to exit the mode or a
network command is sent to clear the mode.
Bypass Push-Button
The FCU Controller may be connected to an Excel 10 wall
module equipped with a bypass push-button. There are three
ways to configure the bypass push-button (see Table 17 for
further information):
NONE
BYPASS_UNOCCUPIED
BYPASS_ONLY
Override Priority
The FCU Controller can be configured to arbitrate overrides
coming from the bypass push-button and the L
ONWORKS
network. There are two possible states which have the
following meanings:
LAST_WINS specifies that the last command received
from either the wall module or DestManOcc determines
the effective override state.
NETWORK_WINS specifies that when DestManOcc is not
OC_NUL, then the effective occupancy mode is
determined by DestManOcc regardless of the wall
module override state.
LED/LCD
LED Override
The wall module’s LED indicates that the FCU controller is
being overridden by either the bypass button or the
ONWORKS network.
L
• LED ON "override bypass"
2,4
2,4
7EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
• One flash per second "override unoccupied"
• Two flashes per second "override standby" or
"occupied"
• LED OFF no override
• Four flashes per second The controller is responding
ONWORKS network management wink command.
to a L
LED Occupancy
The wall module’s LED indicates the effective occupancy
mode.
• LED ON effective "occupied" or effective "bypass"
• One flash per second effective "standby"
• LED OFF effective "unoccupied"
• Four flashes per second The controller is responding
ONWORKS network management wink command.
to a L
LCD Display
This mode is used only for T7560 Wall Modules. The
occupancy mode is represented by the following symbols:
effective "occupied" or effective "bypass"
effective "standby"
effective "unoccupied"
Controller is OFF
and Controller is OFF, frost protection is enabled.
Flashing symbols indicate the "override" mode:
override "occupied" or override "bypass"
override "standby"
override "unoccupied"
The controller is responding to a LONWORKS network
management wink command.
Energy-Saving Features
The "Standby" Mode
The digital input for reading input from an occupancy sensor
(usually a motion detector) provides the FCU controller with a
means to enter an energy-saving standby mode whenever
there are no people in the room. The "standby" mode occurs
when the scheduled occupancy mode is "occupied" but the
occupancy sensor indicates that the room is nevertheless
currently unoccupied. If no occupancy sensor is directly connected to the FCU controller, an occupancy sensor from
another node may be bound to the network input
DestOccSensor. The FCU controller can also be forced into
the "standby" mode by means of a L
command (DestManOcc set to OC_STANDBY). When in the
"standby" mode, the FCU Controller uses the "standby"
setpoints configured for the heating and the cooling modes
(SptHeatStby or SptCoolStby).
ONWORKS network
used by binding it to DestWindow. Frost protection remains
active. Normal temperature control resumes when the
window closes.
Demand Limit Control
When a high-electrical-demand signal is received from an
energy management system via the L
ONWORKS network
(DestDlcShed), the FCU controller uses DlcStptBump to shift
the current setpoint (down for heating and up for cooling) by
the configured value to save energy.
Fig. 4. Optimum start (heating)
Optimum Start Gradients
There are two parameters, RecRampCool and
RecRampHeat, that can be configured to cause the cooling
and heating setpoints respectively to ramp up to their
occupied settings from their unoccupied or standby settings
prior to scheduled occupancy. The FCU controller
uses the configured rates to determine the optimum
time to start increasing the heating or cooling
demand. See the following figures. The configuration
parameters are in K/hour.
Fig. 5. Optimum start (cooling)
Window Sensor
The digital input for reading input from a window contact
provides the FCU controller with a means to disable its temperature control activities if someone has opened a window
or door in the room. If no window sensor is directly connected
to the FCU controller, the sensor from another node may be
EN0B-0377GE51 R07038
Occupancy Status
The occupancy status is determined based upon Table 3.
Manual override may come from the network input
DestManOcc or from the bypass push-button.
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
"occupied"room occupiednot assignedOC_OCCUPIED
"occupied"room not occupiednot assignedOC_STANDBY
XX"occupied"OC_OCCUPIED
XX"unoccupied"OC_UNOCCUPIED
XX"standby"OC_STANDBY
"occupied"X"standby"OC_OCCUPIED
"standby"Xnot assignedOC_STANDBY
"standby"X"standby"OC_OCCUPIED
"unoccupied"Xnot assignedOC_UNOCCUPIED
"unoccupied"X"standby"OC_BYPASS
X=Don't care
Safety Features
Frost Protection
If the room temperature falls below 46.4°F (8°C), the FCU
controller enables the heating circuit to ensure frost protection and an alarm is issued. When the temperature rises
above 48.2°F (9°C) again, the heating circuit is turned OFF
again.
Smoke Control
The FCU controller will respond to L
emergency commands by switching OFF heating/cooling
outputs and switching OFF the fan (depressurize) or
switching ON the fan at its highest speed (pressurize). An
alarm is issued for any emergency commands
ONWORKS network
Fan Failure Protection
When configured with an airflow detector, the FCU controller
protects equipment by switching OFF heating / cooling
outputs and issuing an alarm when the fan fails.
Fan Interlocks
The FCU controller can be configured such that heating
and/or cooling outputs are never ON unless the fan is
running. A fan run-up time can be configured to turn ON the
fan prior to the heating/cooling outputs being switched ON,
and a fan overrun time can be configured to keep the fan
running for a period of time after the heating/cooling outputs
are switched OFF.
9EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Operating Modes
The possible modes of operation are listed in Table 4.
Table 4. Modes of Operation for Excel 10 FCU Controller
modedescriptionevents causing a controller to switch to this mode
operational modes (user address: SrcFcuModeS)
START-UP AND
WAIT
FLOATING
OUTPUTS SYNCH
COOLINGThe FCU controller is controlling in
HEATINGThe FCU controller is controlling in
MANUAL MODEThe control algorithms stay active
FACTORY TESTControl algorithm is disabled; a
DISABLEDControl algorithms are terminated,
PRESSURIZEHeating/cooling outputs are switched
DEPRESSURIZEHeating, cooling and fan outputs are
Control algorithms are disabled.
Outputs stay in their initial positions.
Physical inputs are periodically read
and digital filtering of analog inputs is
turned OFF to speed up settling time.
Input NVs are received and output
NVs are sent periodically.
The FCU controller drives the floating
control valves to their initial positions
and then transitions to one of the
control modes.
the cooling mode.
the heating mode.
and outputs are controlled automatically until set individually to test
positions using the network input
nviTest.
special factory test program runs.
outputs are turned OFF (turn-OFF
sequences and interlocks are active).
Frost protection is disabled.
OFF, and the fan is switched ON at
its highest speed.
switched OFF.
This is the first mode after an application restart.
When the effective occupancy changes to "unoccupied" or
"standby", after start-up, after 24 hours since the last positioning,
or after each positioning to 0%, the FCU controller transitions to
this mode.
Input NV (DestHvacMode) has a value of HVAC_COOL or
HVAC_AUTO and the space temperature is above the cooling
setpoint.
Input NV (DestHvacMode) has the value of HVAC_HEAT or
HVAC_AUTO and the space temperature is below the heating
setpoint.
Input NV (DestManMode) has value of MODE_MANUAL.
This mode is for factory testing, only.
Input NV (DestManMode) has a value of MODE_DISABLED.
Input NV (DestEmerg) containing smoke control signal from C-
Bus has the value of EMERG_PRESSURIZE.
Input NV (DestEmerg) containing smoke control signal from C-
Bus has the value of EMERG_DEPRESSURIZE.
EN0B-0377GE51 R070310
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Agency Listings
Table 5 provides information on agency listings for Excel 10 FCU Controller products.
Table 5. Agency listings
deviceagencycomments
W7752D to J
FCU Controller
W7752D to J
FCU Controller
W7752D to G
FCU Controller
W7752D to G
FCU Controller
CEGeneral Immunity per European Consortium standards EN50081-1 (CISPR 22
Class B) and EN 50082-1:1992 (based on Residential, Commercial, and Light
Industrial).
EN 61000-4-2IEC 1000-4-2 (IEC 801-2) Electromagnetic Discharge.
EN 50140, EN 50204 IEC 1000-4-3 (IEC 801-3) Radiated Electromagnetic Field.
EN 61000-4-4IEC 1000-4-4 (IEC 801-4) Electrical Fast Transient (Burst).
Radiated Emissions and Conducted Emissions.
EN 55022:1987 Class B.
CISPR-22: 1985.
FCCComplies with requirements in FCC Part 15 rules for a Class B Computing
Device.
ULTested and listed under UL 916 (file number E87744).
Ambient Temperature Rating: 32...122 °F (0...50 °C).
cULTested and listed under UL 916 (file number E87744).
Ambient Temperature Rating: 32...122 °F (0...50 °C).
Construction
Excel 10 W7752 FCU Controllers
The Excel 10 W7752 FCU Controller is available in five basic
models, each with two different possibilities for L
transceivers. All of these controllers are mains-powered, and
two models are equipped with an additional high-power relay
for applications with electric reheat. Table 6 shows the
differences between models.
Table 6. Excel 10 W7752 FCU Controller models
OS numberPower inputReheat relay
W7752D2007230 VacX
W7752E2004230 Vac
W7752F2002115 VacX
W7752G2000115 Vac
W7752J2003100 Vac
All wiring connections to the controllers are made at screw
terminal blocks accessible beneath a plastic safety cover.
Mounting dimensions are shown in Fig. 6.
ONWORKS
Excel 10 W7754 FCU Controllers
The Excel 10 W7754 FCU Controller is available in five basic
models, each with two different possibilities for L
transceivers. Table 7 shows the differences between models.
Table 7. Excel 10 W7754 FCU Controller models
OS numberPower inputReheat relay
W7754K1001230 VacX
W7754L100924 Vac
W7754M1007230 Vac
W7754N1004230 Vac
W7754P1000230 Vac
ONWORKS
CAUTION
If FCU Controllers are mounted vertically and thermal
actuators are used, the transformer must not be
located below the electronics due to heating effects.
WARNING
Electrical Shock Hazard.
Mains power at terminal block can cause personal
injury or death. FCU Controllers must be mounted
inside their fan coil unit boxes to prevent access by
unauthorized personnel.
To reduce the risk of fire or electric shock, install in a
controlled environment relatively free of contaminants.
11EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Fig. 6. W7752 construction in inches (mm)
WALL MOD.
+ -
RS1A
59.5180
ONUNUSED
UNUSED
DI2
USED
USED
GND9LED10FAN11DI2
8
3214 5 623247
DI1
SET
5342 1
T7460 / T7560
SENS
23D25
LON
12
GND
0345
230 V
W7754Kxxxx
230 Vac, 50/60 Hz
max. 5 VA unloaded
1314 15181716
L
N
2 A10A
III II I
Honeywell
D-71101 Schönaich
Made in Germany
triac
0.5 A
1920 2122
close
fan
OUT1 OUT2
230 Vac
2526
2A/M
LN
com
com
open
open
close
230 V
Fig. 7. "7754 dimensions (in mm)
130
110
90
terminal protection
cover (optional)
EN0B-0377GE51 R070312
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Controller Performance Specifications
Power:
W7752D and W7752E; W7754K,M,N,P
230 Vac +10%, -15%, 50/60 Hz.
W7752F and W7752G
115 Vac +10%, -15%, 50/60 Hz.
W7752J
100 Vac ±6%, 50/60 Hz.
W7754L
24 Vac ±20%, 50/60 Hz.
Operating Temperature:
32...122°F (0...50°C).
Shipping/Storage Temperature:
-40...+158°F (-40...+70°C).
Relative Humidity:
5% to 95% non-condensing
Inputs:
Temperature Sensor:
20k ohm NTC
Setpoint Potentiometer:
10k ohm
Digital Input:
Closed ≤ 400 ohms
Open ≥ 10 K ohms
Outputs:
Triac voltage range:
24 Vac ± 20%.
Triac max. current ratings:
250 mA continuous
650 mA surge for 30 sec.
IMPORTANT:
When any device is energized by a Triac, the device
must be able to sink a minimum of 15 mA. If nonHoneywell motors, actuators, or transducers are to be
used with Excel 10 FCU Controllers, compatibility must
be verified.
The W7752 Controllers use the LonTalk protocol. They
support the L
ONMARK Functional Profile # 8020 “Fan Coil Unit
Controller”, version 2.0. Fig. 8 shows the implementation
used.
nviSensorOcc
SNVT_Occupancy
Manufacturer
Defined
nvoSensorOcc
SNVT_occupancy
Section
nviEmerg
SNVT_hvac_emerg
nviReheatRelay
SNVT_switch
nvoDigitInState
SNVT_switch
Hardware
Input
NOT SUPPORTED.
Fig. 8. LONMARK FCU object profile
13EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Configurations
General
The following sections provide an overview of the Excel 10
FCU Controller options related to inputs and outputs. See
section "Step 6. Configure Controllers" (page 28) for a
complete list of configuration options and defaults.
Table 8. Hardware options summary
optionpossible configurations
fan typeno fan
fan interlockenabled
FCU system typetwo-pipe
output 1 actuator typefloating
output 2 actuator typefloating
valve directiondirect
reheatnone
digital inputnot used
wall module optionlocal
temperature sensor
type
NOTE:
1
The floating-mid option is only for changeover applications
and uses only one of the two outputs.
one-speed
two-speed
three-speed
disabled
four-pipe
floating mid (one for heat/cool)
one-stage
two-stage
three-stage
PWM
thermal
floating mid (one for heat/cool)
one-stage
two-stage
three-stage
PWM
thermal
reverse
reheat (W7752D and F only)
free use (W7752D and F only)
W7754?
window closed
occupied sensor
air flow detector
cool changeover
window open
unoccupied sensor
no air flow
heat changeover
movement
no movement
shared
none
NTC non-linearized
1
1
Fan Type
Each fan coil unit controlled by an FCU controller can have a
fan with up to three different speeds or no fan at all. Multispeed fans are switched at the same switching levels as
multi-staged heating control points (see Fig. 9). For example,
a three-speed fan will switch ON its first speed at the same
control level as the first stage of heating or cooling up until
the second stage of heating or cooling where the second fan
speed will switch ON. A two-stage fan will switch with the first
two stages of a 3-stage heating or cooling system. Likewise,
a single-speed fan will turn ON at the first stage of any multistaged system. Conversely, a multi-speed fan may follow
multiple switching levels even for single-staged, floating,
PWM, or thermal actuator-based systems.
Hysteresis
The hysteresis for fan speed extends to the next lower
switching level (or a control level of 0) as is shown in Fig. 9.
For example, the second fan speed will remain ON until the
control level falls below the switching point for the first fan
speed. Min. ON and OFF times can be configured and will
apply to all fan switching points.
Interlock
A fan interlock can be configured which prevents heating or
cooling outputs from being turned ON in the event of a fan
failure (where an air flow detector is installed to detect fan
failure). When fan interlock is configured, run-up and overrun
times can be configured to delay switching ON the heating or
cooling equipment after switching ON the fan and delay
switching OFF the fan after the heating or cooling equipment
is switched OFF.
The fan can be configured to run continuously during the
zero energy band during occupied periods.
EN0B-0377GE51 R070314
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Fig. 9. Three-speed fan switching and hysteresis, cooling mode (defaults for switching levels shown)
Type of Heating and Cooling Equipment
The FCU controller can operate with either two-pipe or fourpipe systems. A two-pipe system requires a changeover input
to the controller (hardware or network input).
The FCU controller can operate with a variety of actuators for
heating and cooling equipment. Floating actuators can be
used which will require specifying the valve run time during
configuration of the controller. Valve action can be configured
as either direct or reverse. When in a two-pipe system with a
changeover input, a floating actuator can be used which has
the middle position (50%) as the zero energy position. The
cool range is then 0 to 50% and the heat range 50 to 100%.
The output must be configured as floating-mid.
Multi-stage systems can be controlled with up to three
different stages of heating/cooling control. Switching levels
are specified in % of control level (see Fig. 10) as is a
hysteresis setting which applies to all switching levels.
Heating and cooling switching levels and hysteresis are
specified separately. Min. OFF times can be configured, and
for one-, two- and three-stage systems, a min. ON time can
also be configured.
PWM electronic valves and thermal actuators can also be
connected and can be configured as either direct or reverse
action. The cycle time must be specified during configuration.
In the case of PWM valves, the zero and full positions must
also be configured.
Fig. 10. Three-stage heating/cooling switching (defaults for switching levels and hysteresis shown)
15EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Reheat Output
W7752D and F Controllers have an additional high-current of
10 A max. (UL916: 6 A max.) output relay to control an electric reheater (refer to Fig. 2 for sample application). The
reheat output has its own switching level and hysteresis
settings (see Fig. 11). The reheat relay may also be used as
an auxiliary output for other purposes, in which case the
W7752 must be configured to specify that the output is under
the control of the L
control algorithm.
Fig. 11. Reheat switching and hysteresis (defaults
ONWORKS network, and not of the FCU
shown)
Digital Input
There is a single digital input in the W7752 Controller which
may be configured to accommodate an occupancy sensor, a
window open/closed contact, an air flow detector (for fan
failure detection), or a changeover input. It is possible to
configure this input for either normally-open or normallyclosed contacts for any of the switches.
The control algorithm in the Excel 10 FCU controller uses the
occupancy sensor, if configured, to determine the effective
occupancy mode (see Table 3). If the Time Of Day (TOD)
schedule indicates an occupied state, and the eccupancy
sensor contact is closed, the effective occupancy mode will
be "occupied". However, if the TOD schedule indicates an
occupied state and the occupancy sensor contact is open,
then the effective occupancy mode will be "standby". The
control algorithm will then control according to the "standby"
setpoints configured for the heating and the cooling modes.
Configuring the digital input for movement or no movement
(dependent upon normally-open or normally-closed contacts)
adds a delay of 15 minutes to the occupancy sensor such
that the space is considered occupied until 15 minutes has
elapsed since the last movement is detected.
If the digital input is configured to read input from a window
open/closed contact, heating, cooling, and fan control will be
disabled while the window is detected open. Frost protection
will be enabled. A set of contacts may be wired in series for
multiple windows. If the window open/closed contact is not
configured, a one-to-one association (binding) of the window
sensor from another controller on the L
can be made. A locally-wired contact can also be used in
combination with the network input, the result being a logical
OR of the inputs.
If the digital input is configured to read input from an air flow
detector (fan status), heating and cooling control will be
disabled for a fan failure (fan ON and no air flow detected).
The input may also be configured for changeover for a twopipe system.
NOTE: The Excel 10 FCU Controller has limited power
available (only 1.5 mA/4.8 V) for checking the digital
input for contact closures. Ensure that contacts
used remain within the specified resistance
tolerance range (closed ≤ 400 ohms) even when
aged.
ONWORKS network
EN0B-0377GE51 R070316
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Excel 10 Wall Module Options
A typical FCU installation will include an Excel 10 wall
module containing a 20k ohm NTC room temperature sensor
and additional features depending on the wall module type
(see Excel 10 wall module literature for further information).
The FCU controller can use a return air sensor rather than
the sensor in the wall module if it is wired to the wall module
sensor input. Setpoint adjustments can be configured as
relative or absolute, and upper and lower limits can be set. A
configuration option for the fan speed switch allows it to be
disabled if not required. The bypass button can be configured
to override the control mode to "occupied" for a configurable
bypass time and to override the control mode to
"unoccupied" for an indefinite time, or it may be configured to
only override to "occupied". The button may also be used to
cancel the override.
Common Temperature Control (Master/Slave Controllers)
When one or more FCU controllers serve a common area
and a single temperature sensor is to be used, a
master/slave arrangement can be configured. One Excel 10
FCU Controller is configured for the local wall module with
the desired options. The other Excel 10 FCU Controller(s) will
be configured without wall modules and with certain network
variables bound with the master controller. Refer to
Application Step 6 of this document for more details.
IMPORTANT
The slave units must have the same HVAC equipment
connected to it as the master units.
The slave units will not use any internal temperature
setpoints or control algorithms. The master controller
determines heating/cooling output based upon setpoints
and occupancy and L
ONWORKS network command
mode status and communicates this to the slave via the
ONWORKS network.
L
17EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Abbreviations and Definitions
CAREComputer Aided Regulation Engineering;
C-BusHoneywell proprietary Control Bus for
CPUCentral Processing Unit; an EXCEL 5000
Echelon
EMSEnergy Management System; refers to the
EEPROMElectrically Erasable Programmable Read
EPROMErasable Programmable Read Only
E-VisionPC-based tool used for configuration and
Excel 10 Zone Manager - A controller that is used to
FirmwareSoftware stored in a nonvolatile memory
the PC based tool used to configure C-Bus-
Bus devices.
communications between EXCEL 5000
System controllers and components.
System controller module.
®
The company that developed the
ONWORKS
L
®
network and the Neuron
chips used to communicate on it.
EMIElectromagnetic Interference; electrical
noise that can cause problems with
communications signals.
controllers and algorithms responsible for
calculating optimum operational
parameters for max. energy savings in the
building.
Only Memory; the variable storage area for
saving user setpoint values and factory
calibration information.
Memory; the firmware that contains the
control algorithms for the Excel 10 FCU
Controller.
commissioning of Excel 10 devices.
interface between the C-Bus and the
ONWORKS network. The Excel 10 Zone
L
Manager also has the functionality of an
Excel 100 Controller, but has no physical
I/O points. (Note: The Q7750A Zone
Manager may be referred to as E-Link.)
medium such as an EPROM.
I/OInput/Output; the physical sensors and
actuators connected to a controller.
I x RI times R or current times resistance; refers
to Ohms Law: V = I x R.
KKelvin.
LiveCAREThe PC based tool used to monitor and
®
ONWORKSEchelon® LONWORKS® network for
L
®
change parameters in C-Bus devices.
communication among Excel 10 FCU
controllers.
NECNational Electrical Code; the body of
®
standards for safe field-wiring practices.
NEMANational Electrical Manufacturers
Association; the standards developed by an
organization of companies for safe field
wiring practices.
NVNetwork Variable; an Excel 10 FCU
controller parameter that can be viewed or
modified over the L
ONWORKS network.
OEMOriginal Equipment Manufacturer; the
company that builds the fan coil units.
PCPersonal Computer.
PotPotentiometer. A variable resistance
electronic component located on Excel 10
wall modules. Used to allow user-adjusted
Setpoints to be inputted into the Excel 10
FCU Controller.
segmentA L
ONWORKS section containing no more
than 60 Excel 10s. Two segments can be
joined together using a router.
SubnetAn L
ONWORKSsegment that is separated
by a router from its Q7750A Zone Manager.
TODTime-Of-Day; the scheduling of Occupied
and Unoccupied times of operation.
VAVolt Amperes; a measure of electrical
power output or consumption as applicable
to an ac device.
VacVoltage alternating current; ac voltage as
opposed to dc voltage.
XBSExcel Building Supervisor; a PC based tool
for monitoring and changing parameters in
C-Bus devices.
EN0B-0377GE51 R070318
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
APPLICATION STEPS
Overview
Steps one through seven, see Table 9, address considerations for engineering an Excel 10 FCU System. These
steps are guidelines intended to aid understanding of the product I/O options, bus arrangement choices, configuration
options and the Excel 10 FCU Controllers’ role in the overall
EXCEL 5000
Step No.Description
Step 1. Plan the System
Plan the use of the FCU controllers according to the job
requirements. Determine the location, functionality and
sensor or actuator usage. Verify the sales estimate of the
number of FCU controllers and wall modules required for
each model type. Also check the number and type of output
actuators and other accessories required.
When planning the system layout, consider potential expansion possibilities to allow for future growth. Planning is
very important to be prepared for adding HVAC systems and
controllers in future projects.
®
System architecture.
Table 9. Application steps
1Plan the System
2Determine Other Bus Devices Required
3Lay out Communication and Power Wiring
4Prepare Wiring Diagrams
5Order Equipment
6Configure Controllers
7Troubleshooting
notebook PC
using E-Vision
shielded
interface
cable
Excel 10
FCU
RS-232
serial
port
SLTA
controller
LonWorks
port
The L
ONWORKS communication loop between controllers
must be laid out according to the guidelines applicable for
that topology. FCU Controllers use FTT technology which
allows daisy chain, star, loop or combinations of these bus
configurations. See section "Step 3. Lay Out
Communications and Power Wiring" (page 20) for more
information on bus wiring layout, and see Fig. 13, Fig. 14,
and Fig. 15 in section "Step 4. Prepare Wiring Diagrams"
(page 22) for wiring details.
It is important to understand the interrelationships between
FCU controllers on the L
ONWORKSnetwork early in the job
engineering process to ensure their implementation when
configuring the controllers. (See section "Step 6. Configure
Controllers" [page 28] for information on the various Excel 10
FCU Controller parameters and on Excel 10 FCU Controller
point mapping.)
Step 2. Determine Other Bus Devices
Required
A max. of 62 nodes can communicate on a single LONWORKS
segment. If more nodes are required, a router is necessary.
Using a router allows up to 125 nodes, divided between two
ONWORKS segments. The router accounts for two of these
L
nodes (one node on each side of the router); a Q7750A Excel
10 Zone Manager can take one node and two slots are
available for operator terminal nodes, leaving 120 nodes
available for Excel 10 FCU Controllers. All 120 controllers are
able to communicate through the router. A Q7750A Excel 10
Zone Manager is required to connect the L
to the standard EXCEL 5000 System C-Bus. Each Excel 10
Zone Manager can support no more than 120 W7752s. This
is a limit set in the Excel 10 Zone Manager database and is
an absolute maximum.
ONWORKS segment is set up with two unused nodes to
Each L
allow for an E-Vision operator terminal to be connected to the
ONWORKS network. Multiple E-Vision terminals can be
L
connected to the bus at the same time. Table 10 summarizes
ONWORKSsegment configuration rules.
the L
ONWORKSnetwork
Fig. 12. Connecting the portable operator terminal to the
ONWORKS network
L
19EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Table 10. LonWorks configuration rules and device node numbers
One L
ONWORKS Segment Examplemax. number of nodes equals 62
one Q7750A Excel 10 Zone Manager 1 node
port for operator terminal access (E-Vision) 1 node
max. number of Excel 10 Controllers 60 nodes (wall modules are not LONWORKSnodes)
Total 62 nodes
Two LONWORKS Segments Examplemax. number of nodes equals 125
one Q7750A Excel 10 Zone Manager 1 node
one Q7751A Router 2 nodes (1 in each Bus Segment)
ports for operator terminal access (two E-Vision terminals) 2 nodes (1 in each Bus Segment)
max. number of Excel 10 Controllers in segment number one 60 nodes (wall modules are not LONWORKSnodes)
max. number of Excel 10 Controllers in segment number two 60 nodes (wall modules are not LONWORKSnodes)
Total 125 nodes
The max. length of an FTTLONWORKSsegment is 4600 ft
(1400 m) for a daisy chain configuration or 1650 ft (500 m)
total wire length and (400 m) node-to-node for any other type
of configuration.
NOTE: In the case of FTTL
ONWORKSsegments, the
distance from each transceiver to all other transceivers and to the termination must not exceed the
max. node-to-node distance. If multiple paths exist,
the longest one should be used for the calculation.
If longer runs are required, add a Q7751A Router to partition
the system into two segments. It is not legal to use more than
one router per Excel 10 Zone Manager.
In addition, all L
a Bus Termination Module. For an FTTL
ONWORKS segments require the installation of
ONWORKS segment,
one or two Termination Modules may be required depending
upon the bus configuration. See section "Step 3. Lay Out
Communications and Power Wiring" (page 20) and the
ONWORKS Termination Module subsection in section "Step
L
4. Prepare Wiring Diagrams" (page 22) for more details.
Step 3. Lay Out Communications and Power
Wiring
LONWORKS Layout
The communications bus, LONWORKS, is a 78-kilobit serial
link that uses transformer isolation and differential
Manchester encoding. Wire the L
AWG or plenum rated level IV 22 AWG non-shielded, twisted
pair, solid conductor wire as the recommended wire size (see
Table 11 for part numbers). An FTTL
in daisy chain, star, loop or any combination thereof as long
as the max. wire length requirements given in Step 2 are met.
NOTE: Due to the transformer isolation, the bus wiring does
not have a polarity; that is, it is not important which
of the two L
ONWORKSterminals are connected to
each wire of the twisted pair.
LONWORKS networks can be configured in a variety of ways,
but the rules listed in Table 10 always apply. Fig. 13 and Fig.
14 depict two typical daisy chain L
one as a single bus segment that has 60 nodes or less, and
one showing two segments. Fig. 15 shows examples of free
topology bus layouts using 2000-series devices. The bus
configuration is set up using the Network Manager tool from
within E-Vision (see the E-Vision User Guide).
ONWORKS using level IV 22
ONWORKScan be wired
ONWORKSnetwork layouts;
Note: C7750A Zone Manager has internal termination module (with jumpers installed as shown).
Fig. 13. LONWORKS wiring layout for one daisy-chain network segment
EN0B-0377GE51 R070320
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Fig. 14. LONWORKS wiring layout for two daisy-chain network segments
Fig. 15. Free topology LONWORKS layout examples
NOTE: See section "L
ONWORKS Termination" on page 25
for additional details.
IMPORTANT
Notes on Communications Wiring:
• All field wiring must conform to local codes and
ordinances.
• Do not use different wire types or gauges on the
ONWORKS segment. The step change in
same L
line impedance characteristics would cause
unpredictable reflections on the L
ONWORKS net-
work. When using different types is unavoidable,
use a Q7751A Router at the junction.
21EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
• Do not use shielded cable for LONWORKS wiring
runs. The higher capacitance of the shielded
cable will cause degradation of communications
throughput. In noisy (high EMI) environments,
avoid wire runs parallel to noisy power cables, or
lines containing lighting dimmer switches, and
keep at least 3 in. (76 mm) of separation
between noisy lines and the L
• Make sure that neither of the L
grounded.
Power Wiring
IMPORTANT
Notes on Power Wiring:
• All field wiring must conform to local codes and
ordinances.
• Use the heaviest gauge wire available, up to
14 AWG (2.0 mm
(1.0 mm
connections.
• To minimize EMI noise, do not run Triac and/or
relay output wires in the same conduit as the
input wires or the L
loop.
ONWORKS cable.
ONWORKS wires is
2
2
) for all power and earth ground
) with a minimum of 18 AWG
ONWORKS communications
• To comply with CE requirements, in the case of
devices having a voltage range of 50 to 1000
Vac or 75 and 1500 Vdc which are not provided
with a supply cord and a plug or with other
means for disconnection from the supply having
a contact separation of at least 3 mm in all poles,
the means for disconnection must be
incorporated in the fixed wiring.
Step 4. Prepare Wiring Diagrams
General Considerations
The purpose of this step is to assist the application engineer
in developing job drawings to meet job specifications. Wiring
details for the W7752 FCU Controller are shown in Fig. 17.
Table 12 gives additional details for output connections.
NOTE: For field wiring, when two or more wires are to be
attached to the same connector block terminal, be
sure to twist them together. Deviation from this rule
can result in improper electrical contact. See Fig.
16.
Table 11 lists wiring types, sizes, and length restrictions for
Excel 10 FCU Controller products.
Table 11. Field wiring reference table (US part numbers shown)
wire
function
LONWORKS
(plenum)
LONWORKS
(nonplenum)*
input
wiring,
sensors,
contacts
output
wiring,
actuators,
relays
power
wiring
recommended
min. wire size
AWG (mm
2
)
22 AWG
22 AWG
14 to 20 AWG
(2.0 to 0.5 mm
14 AWG (2.5 mm
(18 AWG (1.0
2
) acceptable
mm
for short runs)
14 AWG
(2.5 mm
2
)
construction
twisted pair solid
conductor, non-shielded.
twisted pair solid
conductor, non-shielded.
multi-conductor (usually
five-wire cable bundle); for
2
runs >100 ft (30 m),
)
twisted pair or shielded
cable is recommended.
2
)
any pair non-shielded (use
heavier wire for longer
runs).
any pair non-shielded (use
heavier wire for longer
runs).
specification
or
requirement
Level IV 140°F
(60°C) rating
Level IV 140°F
(60°C) rating
140°F (60°C)
rating
NEC Class 2
140°F (60°C)
rating
NEC Class 2
140°F (60°C)
rating
NOTE: PVC wire must not be used where prohibited by local fire regulations.
vendor wire typemax. length ft (m)
Honeywell (US)
AK3791 (one twisted pair)
AK3792 (two twisted pairs)
See Step 2
(Europe: Belden
9H2201504)
Honeywell (US)
AK3781 (one twisted pair)
AK3782 (two twisted pairs)
See Step 2
(Europe: Belden
9D220150)
Standard thermostat wire82.5 ft (25 m)
Honeywell (US)
AK3702 (18 AWG)
AK3712 (16 AWG)
200 ft (60 m)
AK3754 (14 AWG)
or equivalent
Honeywell (US)
AK3754 (14 AWG)
(twisted pair)
AK3909 (14 AWG) single
conductor or equivalent
Limited by line loss
effects on power
consumption.
(See Line Loss
subsection.)
EN0B-0377GE51 R070322
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Terminal Block Assignment and Wiring Example forthe W7752 Controller
Fig. 17 illustrates terminal block assignments and wiring for
an example Excel 10 W7752 FCU Controller installation. All
connections are made at terminal blocks. Table 12 lists
wiring information for wiring all of the possible actuator types.
REHEAT
+
1. STRIP 1/2 IN. (13 MM) FROM WIRES
TO BE ATTACHED AT ONE
TERMAINAL
Fig. 16. Attaching two or more wires at terminal blocks
OCCUPANCY SENSOR
CHANGEOVER CONTACT
AIRFLOW CONTACT
WINDOW CONTACT
MOTION SENSOR
WALL MODULE
CONNECTIONS
HEAT
COM
-
COOL
FAN
LO
MED
HI
RETURN
OPEN
CLOSE
POWER MAINS
2. TWIST WIRES TOGETHER WITH
PLIERS (A MINIMUM OF THREE
TURNS).
LONW
ORKS
NETWORK IN
L
ONWORKS
L
N
COM
+
OPEN
CLOSE
NETWORK OUT
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE
INSERTING INTO T ERMINAL AND TIGHTENI NG SCREW. THEN
PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD
MECHANICAL CONNECTION.
W7752 FAN COIL UNIT CONTROLLER
D
G
N
D
1
T
A
D
G
I
I
L
N
I
P
U
T
4A
0.5A
16A
2
3
LED
SETPOINT
4
FAN / BYPASS
5
TEMP SENSOR
6
AGND
7
8
E-BUS IN
9
E-BUS IN
10
E-BUS OUT
11
12
E-BUS OUT
OUT 1 COM
13
OUT 1 OPEN
14
OUT 1 CLOSE
15
16
OUT 2 COM
OUT 2 OPEN
17
OUT 2 CLOSE
18
19
RELAY COM
20
RELAY 1
21
RELAY 2
22
RELAY 3
23
SUPPLY VOLT
24
SUPPLY VOLT
PWR RELAY IN (D,F MODELS ONLY)
25
26
PWR RELAY OUT (D,F MODELS ONLY)
Fig. 17. W7752 FCU Controller wiring example
23EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Table 12. Output assignments for various actuator types
Terminal Block Assignment and Wiring for the W7754 Controller
Table 13 lists the terminals and their functions of the Excel 10 W7754 FCU Controller. In addition to connections made at
terminal blocks, there is an extra socket located to the left of the terminal blocks containing a digital output for the low-voltage
PWM control of a solid-state relay employed in high-current electric reheat applications. Table 13 lists wiring information for
wiring all of the possible actuator types.
Table 13. W7754 Controller, terminals and functions
term. #function
1receiving/sending data on the LONWORKS network
2receiving/sending data on the LONWORKS network
3a digital input, configurable (using the LNS plug-in) to read input e.g. from a window contact, an occupancy sensor,
4an analog input, permanently configured to read input from a wall module's temperature setpoint adjustment knob
5an analog input, permanently configured to read input from a room temperature sensor.
6GND
7not present
8GND
9a digital output, permanently configured to write output switching the wall module's LED "on" or "OFF"
10an analog input, permanently configured to read input on whether the wall module's 3-speed fan control knob has
11
12not present
13+14relay 4, permanently configured to switch a hardwired electrical reheat coil ON or OFF
15common terminal for terminals 16, 17, and 18
16
17
18
19a triac output, permanently configured to write output to OUT1, closing it
20a triac output, permanently configured to write output to OUT1, opening it
21a triac output, permanently configured to write output to OUT2, closing it
22a triac output, permanently configured to write output to OUT2, opening it
23a common terminal for terminals 19 and 20
24a common terminal for terminals 21 and 22
25the "N" terminal of the power supply
26the "L" terminal of the power supply
(1)
This digital input can be enabled / disabled using the right DIP switch located on the top of the controller.
(2)
If all three relays (terminals 16, 17, and 18) are switched OFF, then the three-speed fan is switched OFF.
etc.
been set to AUTO, OFF, LOW, MEDIUM, or HIGH and whether the wall module's "occupancy override" button has
been pressed.
(1)
a digital input, permanently configured to read input on whether a window contact is "open" or "closed".
(2)
relay 3, permanently configured to write output to a three-speed fan, setting it to HIGH
(2)
relay 2, permanently configured to write output to a three-speed fan, setting it to MEDIUM
(2)
relay 1, permanently configured to write output to a three-speed fan, setting it to LOW
The triac outputs or relay outputs of the Excel 10 W7754 FCU Controller can be configured (using Honeywell's LNS plug-in) for
different functions.
You can configure the four triac outputs for connection to either a floating drive or to a thermal actuator. Once the outputs have
been configured, the corresponding devices can be directly connected to them.
EN0B-0377GE51 R070324
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Table 14. Output assignments of Excel 10 W7754 FCU Controller for various actuator types
3 ONONONON
PWM----PWM--PW M
thermal----ON/OFF--ON/OFF
OUT1OUT2
LONWORKS Termination
One or two LONWORKS terminations are required, depending
on the given LonWorks bus layout.
Double termination is required only when the network is a
daisy-chain configuration and the total wire length is greater
than 1640 ft (500 m). The max. lengths described in Step 2
must be adhered to for either a daisy chain or free topology
ONWORKS layout. See Fig. 19 for connection details for a
L
doubly terminated bus. See Fig. 20 for connection details for
a singly terminated bus.
on DIN rails and in fuse boxes), order no.:XAL-Term
removable screw-type
3-pole terminal block
ONWORKS termination modules are available:
l
l
we
y
e
n
o
H
m
r
e
T
-
L
A
X
4
3
L
L
O
O
N
N
shieldshield
plug-in
jumper
34
15
06
LON
Term in at io n
FTT/LPT Bus
FTT/LPT Free
Park Position
NOTE: The Q7750A Zone Manager has an internal ter-
mination circuit, although jumpers are required at
the terminal block to connect it. See form number
95-7509 for details.
Fig. 19. Termination Module connections for a doubly-
terminated FTT network
Fig. 20. Termination Module connections for a singly-
terminated FTT network
Fig. 18. LONWORKS connection and termination module
25EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Step 5. Order Equipment
After compiling a bill of materials through completion of the previous application steps, refer to Table 15 for ordering
information. Contact Honeywell for information about controllers and Excel 10 wall modules with no logo.
Table 15. Excel 10 FCU Controller ordering information
Serial Interface Cable, male DB-9 to female
DB-9 or female DB-25.
Honeywell (US)
AK3791 (one twisted pair)
AK3792 (two twisted pairs)
Belden (Europe)
ONWORKS(plenum): 22 AW G twisted pair
L
solid conductor, non-shielded.
9H2201504
Honeywell (US)
AK3781 (one twisted pair)
AK3782 (two twisted pairs)
Belden (Europe)
ONWORKS(non-plenum): 22 AW G twisted
L
pair solid conductor, non-shielded.
9D220150
Honeywell (US) AK3725
Honeywell (US) AK3752
(typical or equivalent)
Honeywell (US) AK3702
(typical or equivalent)
Honeywell (US) AK3712
(typical or equivalent)
Inputs: 18 AWG (1.0 mm
bundle.
Outputs/Power: 14 to 18 AWG (2.5 to
2
1.0 mm
18 AWG (1.0 mm
16 AWG (1.5 mm
ONWORKS version with
ONWORKSversion without
ONWORKSversion with
ONWORKSversion without
ONWORKSversion without
Excel 10 Wall Modules
Excel 10 Sensors
Cabling
2
) five wire cable
).
2
) twisted pair.Non-plenum
2
) twisted pair.Non-plenum
See Excel 10 wall module literature for details.
—
—
Obtain locally from any computer hardware
vendor.
Level IV 140°F (60°C) rating
Level IV 140°F (60°C) rating
Standard thermostat wire
NEC Class 2 140°F (60°C) rating
EN0B-0377GE51 R070326
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Part NumberProduct DescriptionComments
Honeywell (US) AK3754
(typical or equivalent)
14 AWG (2.5 mm
2
) two conductor.Non-plenum
27EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Step 6. Configure Controllers
General
The process of configuring Excel 10 FCU Controllers is the
same for all models. In all cases, the process involves giving
the Excel 10 FCU Controller information using the E-Vision
PC tool. Details on the use of E-Vision are found in the EVision User Guide. The E-Vision User Guide provides
detailed steps for defining the Excel 10 Zone Manager (if
required); creating or starting an existing E-Vision project;
creating or selecting an existing network; building or modifying the network; defining and copying controllers; mapping
points between controllers, the Zone Manager, and thirdparty devices; connecting to controllers for commissioning,
monitoring and uploading; and various other functions. This
section will provide details on the configuration options found
in E-Vision for W7752 and W7754 FCU Controllers. If
another L
see Appendix C for reference information.
Using E-Vision
The configuration process is primarily performed in a series
of screens seen as file tabs under the menu option
Application Selection and is easily followed using the tables
ONWORKS communication tool is used for set-up,
included in this section. There are 9 file tabs:
1. Output
2. Input
3. Equipment Control
4. Fan
5. Switching Levels
6. Zone Options
7. Miscellaneous
8. PID
9. W iring (information only, no configuring).
The specific parameters to be configured in each of these
four categories are tabulated in the following subsections.
For a complete list of all Excel 10 FCU Controller User
Addresses, see Appendix C.
The configuration of the setpoints as either absolute or
relative is performed in E-Vision in the Project Defaults
screen.
NOTE: To set the following configuration parameters, use
the E-Vision PC tool. These sections describe the
various parameters and the allowable settings. For
details on using E-Vision, refer to the E-Vision User
Guide.
EN0B-0377GE51 R070328
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Output
The available options for output configurations with the default values shown are listed in Table 16. See section
"Configurations" (page 14) above for more information about parameters.
FCU controller control algorithm (reheat)
network control (free use)
relay not used
not used
cooling
1
heating
heat/cool changeover
floating
floating-mid
2
1-stage
2-stage
3-stage
PWM
thermal
not used
cooling
1
heating
heat/cool changeover
floating
floating-mid
2
1-stage
2-stage
3-stage
PWM
thermal
W7752D,F
four-pipe
3-speed fan
W7752D,F: reheat
W7752E,G,J: relay not
used
W7754
heating
floating
cooling
floating
29EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Input
The available options for input configurations with the default values shown are listed in Table 17. See Control Provided and
Configurations sections above for more information on parameters.
1. The temperature sensor option no sensor requires that either the FCU Controller be configured as a slave unit receiving
heating and cooling control levels from the master unit via the network, or that it receive temperature information over the
network from another device.
2. The digital input option to be selected is the condition in which the input will be high (switch contact closed).
no sensor
sensor
none - bypass button is disabled.
bypass unoccupied - bypass button overrides current mode to occupied
for configurable bypass time for button press of 1.1 to 4 seconds
(single press with T7560) or permanently overrides to unoccupied for
button press of 4.1 to 7 seconds (more than 5 seconds with T7560).
bypass - bypass button only overrides current mode to occupied and to
cancel the override again.
LED override - shows override from bypass button or from network.
LED occupancy - shows effective occupancy mode.
LCD display - only used with T7560 Wall Modules; occupancy mode is
represented by different symbols.
no switch
3-position switch
4-position switch
5-position switch
no knob
relative
absolute middle
limit for setpoint knob in either degrees F (absolute setpoint, 53.6 to
86°F) or DDF (relative setpoint, -9 to 9 DDF)
(limit for setpoint knob in either degrees C (absolute setpoint, 12 to
30°C) or K (relative setpoint, -5 to 5 K))
limit for setpoint knob in either degrees F (absolute setpoint, 53.6 to
86°F) or DDF (relative setpoint, -9 to 9 DDF)
(limit for setpoint knob in either degrees C (absolute setpoint, 12 to
30°C) or K (relative setpoint, -5 to 5 K))
not used
window closed
occupied sensor
cool changeover
window open
unoccupied sensor
heat changeover
movement
no movement
sensor
bypass unoccupied
LED override
5-position switch
relative
-9 DDF (53.6°F for
absolute setpoint)
(-5 K (12°C for
absolute setpoint))
9 DDF (86°F for
absolute setpoint)
(5 K (30°C for
absolute setpoint))
not used
EN0B-0377GE51 R070330
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Equipment Control
The available options for equipment control configurations with the default values shown are listed in the following table. See
Control Provided and Configurations sections above for more information on parameters.
Table 18. FCU Controller equipment control configuration options
functionconfiguration optionsdefault
output 1 fan interlockenabled / disableddisabled
output 2 fan interlockenabled / disableddisabled
output 1 valve direction
output 2 valve direction
output 1 min. stage OFF time0 to 600 seconds90 s
output 2 min. stage OFF time0 to 600 seconds90 s
output 1 valve run time/PWM
period/min. stage ON time
output 2 valve run time/PWM
period/min. stage ON time
reheat switching level0 to 100%100%
reheat hysteresis0 to 100%5%
PWM zero position
PWM full position
Notes:
1. Valve action settings apply to floating, PWM, or thermal types.
2. Settings apply to both actuators if both are PWM.
1
1
direct / reversedirect
direct / reversedirect
floating - valve run time (20 to 600 seconds)
PWM - cycle time (20 to 600 seconds)
150 s
1, 2, and 3-stage – min. ON time (0 to 1200 seconds)
floating - valve run time (20 to 600 seconds)
PWM - cycle time (20 to 600 seconds)
150 s
1, 2, and 3-stage – min. ON time (0 to 1200 seconds)
2
2
0 to 100%0%
0 to 100%100%
Fan
Available options for fan control are listed in the following table. See Control Provided and Configurations sections above for
more information about parameters.
Table 19. FCU controller fan configuration options
functionconfiguration optionsfefault
fan occupancy mode
fan min. ON time
fan min. OFF time
fan run-up time
fan overrun time
1
1
1
1
Notes:
1. Fan run time options apply to all fan speeds.
continuous during occupied mode;
automatic, based on control algorithm
0 to 1200 seconds0
0 to 1200 seconds0
(with fan interlock only) 0 to 600 seconds0
(with fan interlock only) 0 to 600 seconds0
automatic
31EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Switching Levels
See Configurations section above for more information about parameters.
1. Stage switching levels and hysteresis are used for fan control as well as multi-stage heating/cooling outputs
control.
Zone Options
The Zone configuration options are listed in the following table. See Control Provided and Configurations sections above for
more information on parameters.
Table 21. FCU Controller zone configuration options
functionconfiguration optionsdefault
cooling occupied setpoint50 to 95°F (10 to 35°C)73.4°F (23°C)
heating occupied setpoint50 to 95°F (10 to 35°C)69.8°F (21°C)
cooling standby setpoint50 to 95°F (10 to 35°C)77°F (25°C)
heating standby setpoint50 to 95°F (10 to 35°C)66.2°F (19°C)
cooling unoccupied setpoint50 to 95°F (10 to 35°C)82.4°F (28°C)
heating unoccupied setpoint50 to 95°F (10 to 35°C)60.8°F (16°C)
Notes:
1. Ensure that unoccupied heating<occupied heating<occupied cooling<unoccupied cooling and
standby heating<standby cooling.
Miscellaneous
The options available in the Miscellaneous tab in E-Vision are listed in the following table. See Configurations section above for
more information about parameters.
last wins - the last command from either the wall module or from the
Override priority
Demand limit control bump0 to 18 DDF (0 to 10 K)3.6 DDF (2 K)
Cool rec ramp
(cooling optimum start gradient)
Heat rec ramp
(heating optimum start gradient)
network has priority.
network wins - a network command always has priority until canceled.
-36 DDF/hour to 0 (-20 K/hour to 0)0
0 to 36 DDF/hour (0 to 20 K/hour)0
last wins
EN0B-0377GE51 R070332
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
PID
The options for configuring PID parameters with defaults are shown in the following table. See Control Provided section above
for more information about parameters.
cooling reset time10 to 3200 seconds (0 = disable)250 s
heating reset time10 to 3200 seconds (0 = disable)250 s
cooling derivative time1 to 3200 seconds (0 = disable)0
heating derivative time1 to 3200 seconds (0 = disable)0
cooling boost temperature0.9 to 18 DDF (0.5 to 10 K) (0 = disable)1.8 DDF (1 K)
heating boost temperature0.9 to 18 DDF (0.5 to 10 K) (0 = disable)1.8 DDF (1 K)
Notes:
1. Prior to version 1.0.3, the minimum proportional gain was 7.2 DDF (4 K) for all control algorithms.
1
1
P control: 2.25 to 180 DDF (1.25 to 100 K) (0 = disable)
PI control: 3.6 to 180 DDF (2 to 100 K) (0 = disable)
P control: 2.25 to 180 DDF (1.25 to 100 K) (0 = disable)
PI control: 3.6 to 180 DDF (2 to 100 K) (0 = disable)
36 DDF (20 K)
36 DDF (20 K)
Commissioning
Commissioning is the process of writing the LONWORKS
addresses, the binding information and the configuration to
the Excel 10 Controller. E-Vision is the tool used to perform
these activities, as described in Appendix B.
Job Commissioning
The CARE database that is generated for the Excel 10 FCU
Controllers and associated Zone Managers contains
information concerning interrelationships and network
identifications. For this reason, it is mandatory to commission
(assign ID and download) all Excel 10 FCU Controllers and
the Zone Managers from a single database.
®
CAUTION
If more than one copy of the same database is used
in multiple PCs to assign IDs and download to Excel
10 FCU Controllers, there is currently no means to
recombine the multiple copies into a single database
for any project. If multiple copies are used, it is
necessary to designate one database as the master
and recommission the controllers that do not indicate
being commissioned. If E-Vision displays an assigned
ID only the application needs to be downloaded to the
controller. If no ID has been assigned, assign ID(s)
and download the application to the controller(s). In
both of these cases, parameter changes (Setpoints,
Temperature Sensor Calibration, etc.) made with the
other PC database are lost and have to be reentered.
ID Number
Each Excel 10 FCU Controller is shipped with an internal
Identification Number from the factory called the Neuron ID
The ID number can either be manually entered or it can be
received from the network. Pressing the bypass push-button
on the Excel 10 wall module for an FCU controller when it is
in Service Mode causes it to broadcast a service message
®
containing its Neuron ID number. This ID number is on a
removable sticker on the side of the W7752 housing or on
the adhesive sticker on the top of the W7754 housing and
can be typed in manually. E-Vision is used to perform both
methods (see E-Vision User Guide).
Configuring the Zone Manager
The Q7750A Excel 10 Zone Manager sends a one-time
ONWORKS message containing its 48-bit Neuron ID after any
L
power-up WARMSTART or when the Excel 10 Zone Manager
is reset by pressing the reset button.
IMPORTANT
Pressing the reset button on the Excel 10 Zone
Manager causes all application files in the Q7750A,
including the C-Bus setup, to be lost.
ONWORKS message is sent only once and only on the
The L
ONWORKSnetwork, not on the B-Port. The message will be
L
the same as the one generated after pressing the service
button, which is available on Excel 10 FCU Controllers via
the Excel 10 wall module's bypass push-button. E-Vision
uses this message to assign the node address.
The Assign ID procedure is the same as for an Excel 10 FCU
Controller except, instead of pressing the bypass button, the
reset button must be pressed or the power must be cycled
(down then up) on the Q7750A Excel 10 Zone Manager.
Excel 10 FCU Controller Point Mapping
In typical Excel 10 FCU Systems, there are often variables
containing values or information that must be shared with
devices on the C-Bus. E-Vision is used to perform these
operations through the Point Mapping function. Mapped
points are available to the C-Bus. Table 24 lists FCU
controller source variables for mapping, and Table 25 lists
.
variables from other sources which may be mapped to FCU
controller input variables. See Appendix D for a complete list
of all Excel 10 FCU Controller User Addresses.
33EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Table 24. Mapping of FCU Controller source points with receivers elsewhere on LONWORKS network or C-Bus
source (Excel 10
FCU controller)
variable name
SrcOccEff
SrcOccOvrdHwS
SrcFcuModeS
SrcAlarmNode
SrcReheatS
SrcTermLoad
SrcRmTempSptEffS
NOTE: E-Vision handles the mapping process for C-Bus accessible Excel 10 points. If custom mapping arrangements are
required, see Appendix C for a complete listing of the Excel 10 FCU Controller User Addresses.
OC_OCCUPIED
This signal contains the effective occupancy status
of the Excel 10 FCU Controller.
OC_BYPASS
OC_STANDBY
XBS for monitoring.
OC_UNOCCUPIED
This signal contains the state of the remote override
button.
Indicates the current control mode of the Excel 10
FCU Controller.
Indicates latest alarm detected by the node (if any)
and return to normal.
If the unit has electric reheat, this indicates the
current commanded status.
OC_UNOCCUPIED
OC_BYPASS
OC_NUL (not assigned)
10 possible values. See
Table 4 or Appendix C.
40 possible values. See
Table 26 or Appendix C.
ST_OFF
ST_OFF
ST_NUL (no reheat)
XBS for monitoring
and tenant logging.
XBS for monitoring.
XBS for monitoring.
XBS for monitoring.
This indicates the current calculated terminal cooling
load as a percentage of what the unit is designed to
handle. Positive value indicates a cooling load.
-160 to 160 percentXBS for monitoring.
Negative value indicates a heating load.
This indicates the current temperature control point
calculated from the various setpoints and operating
modes.
50 to 95°F
(10 to 35°C)
XBS for monitoring.
Table 25. Mapping of source points elsewhere on L
typical source
(non-Excel 10
Controller)
descriptionallowable values
variable name
OccSignal
Signal containing TOD Schedule mode command from
the Excel 10 Zone Manager or a C-Bus controller.
Signal from a main equipment controller to command
FcuMode
the Excel 10 FCU Controller into a particular mode of
operation.
Signal to tell Excel 10 FCU Controller to enter
"emergency pressurize", or "emergency depressurize"
CmdEmerg
modes of operation. This signal would come from a
controller that is monitoring/coordinating the building
fire protection system.
Signal containing the Shed mode command (based on
electrical demand) from the Excel 10 Zone Manager, or
DmndShed
a C-Bus controller. When signal is TRUE, the value in
DlcStptBump is added to or subtracted from the
temperature setpoint.
Amount (in degrees) to add to the temperature setpoint
SetPtOffset
reading for energy savings. Typically sent from another
controller doing EMS calculations.
ONWORKS or C-Bus to Excel 10 FCU Controller receiver points
typical destination
(Excel 10 FCU
Controller) name
OC_OCCUPIED
OC_UNOCCUPIED
OC_STANDBY
DestSchedOcc
OC_NUL
HVAC_AUTO
HVAC_HEAT
HVAC_COOL
DestHvacMode
HVAC_OFF
HVAC_NUL
EMERG_NORMAL
EMERG_PRESSURIZE
DestEmerg
EMERG_DEPRESSURIZE
NORMAL
SETPOINT_SHIFT
-18 to +18 DDF
(-10 to +10 K)
DestDlcShed
DestSptOffset
EN0B-0377GE51 R070334
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Step 7. Troubleshooting
Troubleshooting Excel 10 FCU Controllers and Wall
Modules
In addition to the following information, refer to the various
Checkout and Test manuals for these products. See
Applicable Literature section for form numbers.
Alarms
When an Excel 10 FCU Controller has an alarm condition, it
reports it to the central node on the L
(typically, the Excel 10 Zone Manager) via the variable
nvoAlarm. See Table 26. The information contained in
nvoAlarm is:
• Subnet Number: The L
the Excel 10 FCU Controller node that has the alarm
condition. If the system has a Zone Manager and a
router, Subnet 1 is on the Zone Manager side of the
router; Subnet 2 is on the opposite side.
• Node Number: The Excel 10 FCU Controller node that
has the alarm condition.
• Alarm Type: The specific alarm being issued and return
to normal. An Excel 10 FCU Controller can provide the
alarm types listed in Table 26.
All current alarms are contained in a variable called
nvoAlarmStatus which is composed of three bytes
ONWORKSsubnet that contains
ONWORKSnetwork
(nvoAlarmStatus.alarm_bit[n] with n = 0 through 2) with a bit
corresponding to each of the alarms listed in Table 26. The
coding is ordered in that the least significant bit of
nvoAlarmStatus.alarm_bit[0] corresponding to alarm type 1,
the most significant bit corresponding to alarm type 8, the
least significant bit of nvoAlarmStatus.alarm_bit[1]
corresponding to alarm type 9, and so on. Even alarms that
are suppressed in nvoAlarm (see below) are contained in
nvoAlarmStatus.
Also, the Excel 10 FCU Controller variables,
nvoAlarmLog.type[n], where n is 0 through 4, that store the
last five alarms to occur in the controller, are available. These
points can be viewed through XBS or E-Vision.
Certain alarm conditions are suppressed conditionally as
follows:
If an input NV with failure detect is bound to the same node
as nvoAlarm, then nvoAlarm and nvoAlarmLog do not report
the related FCU Controller variable receive failure error and
its associated return to normal. Suppression occurs only
when the nvoAlarm is bound to only one node using
LonWorks subnet/node addressing and only after the input
variable has actually received an NV from the node since the
latest application restart (or power-up condition).
35EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Table 26. Excel 10 FCU Controller alarms
name of alarm or alarm bit
no alarm/return to normal:
RETURN_TO_NORMAL128
ALARM_NOTIFY_DISABLED255
ALM_NO_ALARM0No errors since last application restart; initial condition
FCU Alarms:
ALM_NODE_OFF1
ALM_FROST2
ALM_INVALID_SETPNT3One of the setpoints is not in the valid range
Return to no error after being in an error condition. This code is added
numerically to another alarm code to indicate that the error condition
has returned to normal.
The alarm reporting has been turned OFF by the nviManualMode
=SUPPRESS_ALARMS. No more alarms are reported until
nviManualMode turns ON alarm reporting or upon application restart.
The control algorithm has stopped due to controller disabled, or in test
mode, or other conditions
The space temperature is below the frost alarm limit. The alarm
condition remains until the temperature exceeds the alarm limit plus
hysteresis.
Fan is commanded to be ON, but the air flow detector input does not
detect the fan running.
nviSpaceTemp is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviApplicMode is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviSetPtOffset is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviTodEvent is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviDlcShed is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviTempReset is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviOdTemp is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviSensorOcc is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviWindow is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviManHeat is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
nviManCool is bound and has failed in receiving an update within its
specified FAILURE_DETECT_TIME
The software is not compatible with the hardware configuration specified
by the hardware configuration resistor value. Compatibility is checked
only once after application restart.
EN0B-0377GE51 R070336
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
Broadcasting the Service Message
The Service Message allows a device on the LONWORKS
network to be positively identified. The Service Message
contains the controller Neuron ID number and, therefore, can
be used to confirm the physical location of a particular Excel
10 FCU Controller in a building.
When an Assign Neuron ID command is issued from EVision, the node goes into the SERVICE_MESSAGE mode
for one minute. In the SERVICE_MESSAGE mode, pressing
the occupancy override button on the remote Excel 10 wall
module causes the Service Message to be broadcast on the
ONWORKS network. All other functions are normal in the
L
SERVICE_MESSAGE mode. If an FCU Controller does not
have a bypass button connected, it can still broadcast the
Service Message on the network by temporarily shorting the
controller Fan Speed/Bypass input terminal to the AGND
terminal on the controller (terminals 5 and 7) with the
controller in SERVICE_MESSAGE mode.
E-Vision is used to perform the ID Assignment task during
commissioning (see E-Vision User Guide, Step 12.
Commission Controllers).
Manual Mode
The FCU Controller can be put into a manual mode which
allows manual setting of outputs for system checkout. The
variable nviManualMode must be set to Mode_Manual using
the E-Vision PC tool. Triac outputs can be set to any combination of ON/OFF or can be set to a test position based
upon the configured valve runtime/cycle time. The fan relays
and reheat relay (W7752D and F, only; W7754?) can also be
commanded ON/OFF in any combination. The override LED
can be commanded ON/OFF in this mode also. See the EVision User Guide section for Manual Mode for detailed
procedures.
37EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
APPENDIX A. USING E-VISION TO COMMISSION A FAN COIL UNIT
Temperature Sensor Calibration
The temperature sensor in the Excel 10 wall modules can be
calibrated to correct for sensor inaccuracies, wire resistance,
etc. This allows the Excel 10 FCU Controller to sense the
space temperature with a high degree of accuracy.
Procedure
Select the controller being worked on with E-Vision (see the
E-Vision User Guide for details on using E-Vision
the actual Measured Value. When a value is typed in
and Calibrate is clicked, the offset value is automatically calculated, displayed, and written to the Excel
10 FCU Controller.
From within E-Vision, with the desired project loaded and the
SLTA (Q7752A) connected to the L
perform the following procedure:
1. Select a controller symbol from a network diagram.
2. Click on Calibrate from the Controller menu. Once E-Vision logs on to the controller, the Room
Temperature Calibration dialog box appears.
3. The box displays the Current Value of the sensor and
the current Offset; it also contains a field for entering
ONWORKS network,
Fig. 21. Calibration dialog box
4. Click on Close after completing adjustments.
EN0B-0377GE51 R070338
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
APPENDIX B. CONFIGURING FOR MASTER/SLAVE OPERATION
More than one FCU Controller may be used to control the
temperature of a room. In this situation one controller must
be identified as the master unit which will perform the temperature control algorithm. The other FCU controllers in the
room are designated as slave units, and their control
algorithms are disabled. The slave units receive heating,
cooling, and fan output information from the master controller
via NVs sent across the L
max. of one wall module active in the room, and it must be
wired directly to the master controller. If a slave controller has
a wall module connected to it, the wall module will be
ignored.
Configuration of the master controller is the same as for any
controller operating alone in a room. Configuration of the
slave controllers must follow the rules described in this
section. The following sections correspond to the screens in
E-Vision used for configuring FCU controllers. An additional
section discusses binding of NVs to support master/slave
configurations.
ONWORKS network. There can be a
Output Configuration Options
Slave devices must have their outputs configured identically
with the master controller. The same system type and
actuator types must be used. Valve run times, cycle times,
and PWM zero and full position configuration options must
be the same as well. If the master controller has a reheat
output, the slave units must have one; and both must be
configured the same. Fan control in the slave units is via
network command from the master unit.
IMPORTANT
The fan min. ON time must be configured to zero in the
slave controllers so that the fans in both master and
slave units switch ON at the same time.
Input Configuration Options
Slave controllers may have wall modules connected to them,
but they must be deactivated while the controllers are
operating as slave units. They must be configured for notemperature sensor and no fan speed switch. The digital
input may be used on the slave units for window open/closed
or air flow (fan fail) detection and must be configured as
such. In the case of window sensing, the window status NV
must be mapped to the master controller as the slave
controller does not execute the control algorithm.
Equipment Control Options
Valve action and fan interlock settings must be the same as
for the master controller. Output staging hysteresis, min.
stage OFF times, and reheat switching and hysteresis should
be the same as in the master controller.
If a fan is used in the slave units, all fan control settings must
be the same as in the master controller.
All heating and cooling stage switching levels should be
identical to those of the master controller.
Zone Control Options
All zone temperature control options including PID settings
and miscellaneous settings are used only by the master
controller and are ignored in the slave units.
Network Variable Binding
In a master/slave configuration, the control algorithm is
executed in the master controller only. Heating and cooling
output as calculated by the control algorithm is then sent via
the network to the slave controllers. The master controller
output variables nvoHeatOutput (user address - SrcHeatPos)
and nvoCoolOutput (user address - SrcCoolPos) must be
bound using E-Vision (see E-Vision User Guide) to the slave
input variables nviManHeat (user address - DestManHeat)
and nviManCool (user address - DestManCool), respectively.
For a master/slave system using heat/cool changeover, the
master controller output variable nvoApplicMode (user
address SrcHvacMode) must be bound to the slave controllers’ input variable nviApplicMode (user address DestHvacMode) unless a changeover contact is connected to
the slave devices. The binding of these two NVs is also
required in applications where heat/cool energy is not always
available.
The T7780 wall module must be connected to the master
controller. The master controller output variable
nvoFanSpeed (user address - SrcFanSpeed) must be bound
to the slave controllers’ input variable nviFanSpeedCmd
(user address - DestFanSpeed).
IMPORTANT
The OFF position of the fan speed switch ON the wall
module turns OFF heating and cooling control functions
as well as the fan, so the NV binding described above
for fan speed must still be performed as described.
For applications with reheat, the master controller output
variable nvoReheat (user address - SrcReheatPos) must be
bound to the slaves’ input variable nviReheatRelay (user
address - DestReheat).
39EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
APPENDIX C. COMPLETE LIST OF EXCEL 10 FCU CONTROLLER USER
ADDRESSES
Table C1. Analog points engineering units
English Units (Inch-Pound)Standard International Units (SI)
The following tables list all NVs associated with the FCU Controllers and the default User Address names. Point attributes
given are defined as follows:
—
Abbreviations
(used in CARE
and E-Vision)
—
Abbreviations
(used in CARE
and E-Vision)
SH—Sharable (bindable) points can be set up for data sharing in Command Multiple Points, Read Multiple Points,
MA—Mappable can be converted into a C-Bus point use by C-Bus devices. A mappable point has a one-to-one
DA—Direct Access points are accessible through the Subsystem Points mechanism in XBS.
M—These points are viewable within the E-Vision Controller Monitoring on-line screen.
HBT—These points are either sent out on the network (outputs) or received from the network (inputs) at a certain
NOTES:
1. Mapped points can be viewed and changed, on C-Bus devices such as an XI581, XI582 and XI584 and on an XBS
central and LiveCARE.
2. All Excel 10 points, mappable and calibration, configuration and internal data sharing points, can be viewed and
changed, as allowed, via Direct Access (DA) mode in the XBS subsystem menu or via XI584.
or Refer Excel 10 Points as either a data source or a destination.
relationship with a C-Bus User Address.
fixed interval (heartbeat).
41EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
user addressNvNamefield name
ApplTypenciApplVerapplication_typeUBYTE, 0 to 2550
ApplVernciApplVerversion_noUBYTE, 0 to 2550
ApplTime0nciApplVertime[0]UBYTE, 0 to 2550
ApplTime1nciApplVertime[1]UBYTE, 0 to 2550
ApplTime2nciApplVertime[2]UBYTE, 0 to 2550
ApplTime3nciApplVertime[3]UBYTE, 0 to 2550
nciDeviceNamech[0-17]UBYTE, 0 to 2550
nciLocationSNVT_str_asc0x00
nciMaxSendTimeSNVT_temp_p
nciRcvHrtBtSNVT_time_sec
engineering units:
English (metric) or states
plus range
0 to 6553 seconds
0 to 6553 seconds
0 = Disabled
digital
state
or
value
default
0 s from factory, 60 s
default from E-Vision
0 s from factory, 300 s
default from E-Vision
nciSndHrtBtSNVT_time_sec
EN0B-0377GE51 R070342
0 to 6553 seconds
0 = Disabled
0 s from factory, 300 s
default from E-Vision
(continued)
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XApplicationType identifies the current application number of the Excel 10.
XVersionNo identifies the version number of the Excel 10 application.
XThe time stamp of the last change to the Excel 10 application configuration. Time meets the ANSI
XSee above.
XSee above.
XSee above.
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
C time stamp requirement specifying the number of seconds elapsed since midnight (0:00:00),
January 1, 1970. It is represented in the Intel Format and is four bytes in length.
nciDeviceName contains the name of each device. This is an ASCII string with the a size of 18
characters. A name with all NULLs means that the device has not been configured.
This configuration property can be used to provide more descriptive physical location information
than can be provided by the Neuron chip's 6 byte location string.
This is the configuration property used to control the max. time that expires before the node object
automatically transmits nvoStatus. This provides a heartbeat output that can be used by the
destination objects to ensure that the node is still healthy. The heartbeat output may be disabled
by setting nciMaxSendTime = 0.
This is the configuration property used to control the max. time that elapses after the last update to
• nviApplicMode
• nviDlcShed
• nviManCool
• nviManHeat
• nviSensorOcc
• nviSetPtOffset
• nviSpaceTemp
• nviTodEvent
• nviWindow
before these NV inputs adopt their default values. Setting nciRcvHrtBt = 0 means that the
assigned NV input does not wait for an periodic update, and that it will never revert to any default
when not receiving an update. If nviSpaceTemp and nviApplicMode are not received at regular
intervals that are less than the heartbeat time, the controller will assume that there is a
communication failure and revert to the "occupied" mode.
This is the configuration property used to control the max. time that expires before the object
automatically transmits the current value of
• nvoActiveSetPt
• nvoAlarm
• nvoApplicMode
• nvoCoolOutput
• nvoFanSpeed
• nvoFcuStatus
• nvoHeatOutpu
• nvoReheatt
• nvoSensorOcc
• nvoSpaceTemp
• nvoTerminalLoad
• nvoUnitStatus
• nvoWindow
This provides a heartbeat output that can be used by the destination objects to ensure that the
node is still healthy. The heartbeat output may be disabled by setting nciSndHrtBt = 0.
(continued)
43EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XFan_auto_mode is the configuration setting to determine the fan operation during the occupied
XFan_run_up_time is the time the fan runs before the outputs are switched ON. It is typically used
XFan_overrun_time is the time the fan still runs after the control algorithm has turned OFF the
XThis is the switching level to turn ON stage 1 of the cooling equipment (if configured as
XThis is the switching level to turn ON stage 2 of the cooling equipment (if configured as
XThis is the switching level to turn ON stage 2 of the cooling equipment (if configured as
XThis is the switching level to turn ON stage 1 of the heating equipment (if configured as
XThis is the switching level to turn ON stage 2 of the heating equipment (if configured as
XThis is the switching level to turn ON stage 3 of the heating equipment (if configured as
XThis value only applies to cool outputs configured as multistage outputs and specifies the
XThis value only applies to heat outputs configured as multistage outputs and specifies the
XReheat_switch_level specifies the switch-over control output level for the reheat output.
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
mode. CONTINUOUS will cause the fan to run even in the zero energy band.
for electric heat outputs with fan interlock (see nciFcuConfig.fan_interlock_0 and _1). The interlock
must be set.
cooling/heating outputs. It's typically used for electric heat with fan interlock (see
nciFcuConfig.fan_interlock_0 and _1). The interlock must be set. In case of smoke purge, the
overrun time will be ignored.
multistage).
multistage).
multistage).
multistage).
multistage).
multistage).
hysteresis between switching the cool stages ON and OFF.
hysteresis between switching the heat stages ON and OFF.
XReheat_hysteresis specifies the hysteresis between switching the reheat output ON and OFF.
XFan_min_on_time is the min. time the fan has to run when commanded ON by the control
XFan_min_off_time is the min. time the fan has to remain OFF when commanded OFF by the
XThis is used to shift the temperature setpoint during demand limit control load shedding. When
XThis is the cooling gradient used by the optimum start function to calculate the optimum time for
XThis is the heating gradient used to determine the optimum time to start increasing the current
algorithm. In case of smoke purge, this time will be ignored. The min_on_time starts as soon as
the fan is switched ON.
control algorithm. In case of smoke purge, this time will be ignored. The min_on_time starts as
soon as the fan is switched OFF.
nviDlcShed is different from zero, the current occupancy setpoint will be decreased by this value
for heating and increased for cooling.
starting to decrease the effective setpoint smoothly from the unoccupied or standby cooling
setpoint to the occupied cooling setpoint.
effective setpoint smoothly to the occupied setpoint at the beginning of scheduled occupancy.
(continued)
45EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
This specifies whether a direct wired room temperature sensor is connected to the node or a room
temperature value from the network is used.
This variable specifies the type of fan speed switch ON the wall module.
This variable specifies the digital input function and type of switch. The option to be selected is the
one which is the condition for a closed switch contact (e.g., normally-closed window switch contact
= DI_WINDOW_CLOSED, normally-open window switch contact = DI_WINDOW _OPEN).
DI_MOVEMENT and DI_NO_MOVEMENT are supported starting with FCU2 version 1.0.3. These
configuration settings cause the controller to retain the occupied state for 15 minutes after the last
movement is detected.
This specifies the type of fan connected to the controller.
This specifies the operating mode of the output 1.
This specifies the operating mode of the output 2. This setting is ignored for nciNumValve =
TWO_PIPE.
This specifies the output type to drive the connected actuator for the output 1:
FLOATING/FLOATING_MID - This setting considers valve_reverse[] and cycle_time[].
Synchronization is performed at every restart and at least once per day.
ONE_STAGE - Triac 2 is not used.
TWO_STAGE/THREE_STAGE - Triac 1 and 2 used (triac 1 and 2 both ON for stage 3). When
configured as multistage, cycle_time and min_stage_off_time are considered.
PWM/THERMAL - Triac 2 is not used. Triac 1 operates as a pulse-width modulated output, and
the cycle time must be specified in cycle_time[]. For PW M outputs, PwmZeroPosn and
PwmFullPosn must also be specified.
This specifies the output type to drive the connected actuator for the output 2 (see above).
(continued)
47EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
user addressNvNamefield name
nciFcuConfigvalve_reverse_0Bit
nciFcuConfigvalve_reverse_1Bit
nciFcuConfigfan_interlock_0Bit
nciFcuConfigfan_interlock_1Bit
nciFcuConfigcycle_time[0]SNVT_time_sec
nciFcuConfigcycle_time[1]SNVT_time_sec
engineering units:
English (metric) or states
plus range
DIRECT
REVERSE
DIRECT
REVERSE
NO
YES
NO
YES
0 to 1200s for stage output
0 to 600s for floating output
20 to 600s for PWM output
0 to 1200s for stage output
0 to 600s for floating output
20 to 600s for PWM output
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XThis is only used for ONE_STAGE, TWO_STAGE, and THREE_STAGE output 1 and specifies
XThis is only used for ONE_STAGE, TWO_STAGE, and THREE_STAGE output 2 and specifies
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
This setting applies to outputs only that have been configured as FLOATING, PWM, or THERMAL
and specifies the direct/reverse operation of output 1.
This setting applies to outputs only that have been configured as FLOATING, PWM, or THERMAL
and specifies the direct/reverse operation of output 2.
This variable configures interlock between fan and output 1 to provide equipment protection for
electric heat or compressor. fan_interlock_0=1 enables interlock which guarantees that output 1
will be driven only when the fan is running.
This variable configures interlock between fan and output 2 to provide equipment protection for
electric heat or compressor. fan_interlock_1=1 enables interlock which guarantees that output 2
will be driven only when the fan is running.
This specifies for the output 1 configured as
• FLOATING: the runtime of the valve (time to run from fully closed to fully open)
• PWM: the cycle time
• ONE_STAGE, TWO_STAGE, and THREE_STAGE: min. ON time before switching to the next
stage.
This specifies for the output 2 configured as
• FLOATING: the runtime of the valve (time to run from fully closed to fully open)
• PWM: the cycle time
• ONE_STAGE, TWO_STAGE, and THREE_STAGE: min. ON time before switching to the next
stage.
the min. OFF time before switching to the next stage.
the min. OFF time before switching to the next stage
This variable specifies the usage of the reheat relay. FREE_USE specifies that the relay is
controlled via the network using the DestReheat user address.
This specifies the zero position for PWM actuators. This setting applies to PWM actuators only
and is used for both actuators if both are configured as PW M actuators.
This specifies the fully open position for PWM actuators. This setting applies to PWM actuators
only and is used for both actuators if both are configured as PW M actuators.
(continued)
49EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
user addressNvNamefield name
GainCoolPropnciFcuGainssi_pid_Xp[0]SNVT_temp_p
GainHeatPropnciFcuGainssi_pid_Xp[1]SNVT_temp_p
GainCoolIntnciFcuGainssi_pid_Tn[0]SNVT_time_sec
GainHeatIntnciFcuGainssi_pid_Tn[1]SNVT_time_sec
GainCoolDernciFcuGainssi_pid_Tv[0]SNVT_time_sec
GainHeatDernciFcuGainssi_pid_Tv[1]SNVT_time_sec
CoolBoostnciFcuGainssi_boost[0]SNVT_temp_p
HeatBoostnciFcuGainssi_boost[1]SNVT_temp_p
nciNumValveSNVT_count
SptCoolOccnciSetPntsoccupied_coolSNVT_temp_p
engineering units:
English (metric) or states
plus range
2.25 to 180 DDF
(1.25 to 100 K), 0 = Disable
2.25 to 180 DDF
(1.25 to 100 K), 0 = Disable
10 to 3200 seconds
0 = Disable
10 to 3200 seconds
0 = Disable
10 to 3200 seconds
0 = Disable
10 to 3200 seconds
0 = Disable
0.9 to 18 DDF (0.5 to 10 K)
0 = Disable
0.9 to 18 DDF (0.5 to 10 K)
0 = Disable
TWO_PIPE
FOUR_PIPE
50 to 95°F (10 to 35°C)
digital
state
or
value
1
2
default
36 DDF (20 K)
36 DDF (20 K)
250 s
250 s
0 s
0 s
1.8 DDF (1 K)
1.8 DDF (1 K)
FOUR_PIPE
73.4°F (23°C)
SptCoolStbynciSetPntsstandby_coolSNVT_temp_p
50 to 95°F (10 to 35°C)
EN0B-0377GE51 R070350
77°F (25°C)
(continued)
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XThis is the throttling range for use in the proportional portion of the PID loop gain for the cooling
XThis is the throttling range for use in the proportional portion of the PID loop gain for the heating
XThis is the integral time for use in the integral portion of the PID loop gain for the cooling mode.
XThis is the integral time for use in the integral portion of the PID loop gain for the heating mode.
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
mode. The min. configurable value (not including 0 for disabling) is 3.6 DDF (2 K) for PI or 2.25
DDF (1.25 K) for P control. For versions prior to 1.0.3, the min. value is 7.2 DDF (4 K).
mode. The min. configurable value (not including 0 for disabling) is 3.6 DDF (2 K) for PI or 2.25
DDF (1.25 K) for P control. For versions prior to 1.0.3, the min. value is 7.2 DDF (4 K).
XThis is the derivative time for use in the derivative portion of the PID loop gain for the cooling
XThis is the derivative time for use in the derivative portion of the PID loop gain for the heating
XThis is the temperature range to be added to the cooling setpoint, above which the cooling output
XThis is the temperature range to be subtracted from the heating setpoint, below which the heating
XXThis is the default setpoint for the occupied cooling setpoint which is used in case there is no
XXThis is the configured setpoint which applies to the standby cooling mode. Where the ZEB for
mode.
mode.
is fully open to allow a faster response. For thermal actuators it is the hysteresis for thermal
control algorithm.
output is fully open to allow a faster response. For thermal actuators it is the hysteresis for thermal
control algorithm.
This is the configuration property used to specify a two-pipe system (one valve) or a four-pipe
system (two valves). If set to TWO_PIPE, only the output terminals for output1 are used. If set to
FOUR_PIPE, output1 and output2 are defined by nciFcuConfig.output_mode[].
locally wired setpoint knob or nviSetpoint has not been bound. Where the ZEB for occupied is
used, it is derived from the difference between occupied_cool and occupied_heat.
standby is used, it is derived from the difference between standby_cool and standby_heat.
(continued)
51EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
user addressNvNamefield name
SptCoolUnoccnciSetPntsunoccupied_coolSNVT_temp_p
SptHeatOccnciSetPntsoccupied_heatSNVT_temp_p
SptHeatStbynciSetPntsstandby_heatSNVT_temp_p
SptHeatUnoccnciSetPntsunoccupied_heatSNVT_temp_p
BypTimenciWallModui_bypass_timeUWORD
SptKnobLowLimnciWallModsi_low_setptSNVT_temp_p
SptKnobHiLimnciWallModsi_high_setptSNVT_temp_p
nciWallModsi_space_temp_zero_calSNVT_temp_p
UseWallModSptnciWallModuse_wall_mod_st_ptBit
engineering units:
English (metric) or
states plus range
50 to 95°F (10 to 35°C)
50 to 95°F (10 to 35°C)
50 to 95°F (10 to 35°C)
50 to 95°F (10 to 35°C)
0 to 1080 minutes
-9 to 9 DDF (-5 to 5 K) for
relative
53.6 to 86°F (12 to 30°C)
for absolute
-9 to 9 DDF (-5 to 5 K) for
relative
53.6 to 86°F (12 to 30°C)
for absolute
--9 to 9 DDF (-5 to 5 K)
NO
YES
digital
state
or
value
0
1
default
82.4°F (28°C)
69.8°F (21°C)
66.2°F (19°C)
60.8°F (16°C)
180 min
-9 DDF (-5 K)
(53.6°F (12°C) for
absolute setpoint)
9 DDF (5 K)
(86°F (30°C) for absolute
setpoint)
0 DDF (0 K)
YES
SptKnobnciWallModset_pnt_knob2 Bits
OFFSET
ABSOLUTE_MIDDLE
nciWallModoverride_type2 Bits
NO_BUTTON
BYPASS_UNOCCUPIED
BYPASS
nciWallModoverride_priorityBit
LAST_WINS
NETWORK_W INS
nciWallModdisplay_typeBit
LED_OVERRIDE
LED_OCCUPANCY
LCD_DISPLAY
EN0B-0377GE51 R070352
0
OFFSET
2
BYPASS_UNOCCUPIED
0
1
2
LAST_WINS
0
1
LED_OVERRIDE
0
1
2
Table C2. Configuration Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXThis is the configured setpoint which applies to the "unoccupied" cooling mode.
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
XXThis is the default setpoint for the "occupied" heating setpoint which is used in case there is no
XXThis is the configured setpoint which applies to the "standby" heating mode. Where the ZEB for
XXThis is the configured setpoint which applies to the "unoccupied" heating mode.
XThis is the parameter which determines the time the controller remains in the "occupied" mode
XXThis is the low limit for the setpoint knob. It can be relative or absolute depending on the
XXThis is the high limit for the setpoint knob. It can be relative or absolute depending on the
locally wired setpoint knob or nviSetpoint has not been bound. Where the ZEB for "occupied" is
used, it is derived from the difference between occupied_cool and occupied_heat.
standby is used, it is derived from the difference between standby_cool and standby_heat.
before reverting to the original occupancy mode after pressing the wall module's override button or
initiating BYPASS via the network. When the "bypass" mode has been activated, the bypass timer
is set to ui_bypass_time. When the timer expires, nvoFcuStatus.occ_status.hw_override reverts
from OC_BYPASS to OC_NUL to quit the bypass override function.
configuration in nciWallMod.set_pnt_knob.
configuration in nciWallMod.set_pnt_knob.
The space temperature sensor is corrected by adding this calibration setting (an offset value) to
the sensed value.
This specifies whether the setpoint used is from the knob on the wall module connected to the
controller or ifrom the network via nciTempSetPts. If set to NO, all setpoints to be used come from
the network via nciTempSetPts. If set to YES, an additional option set_pnt_knob must be set to
specify type of setpoint adjustment (see below).
This setting specifies the usage of the setpoint knob on the wall module for the occupied setpoint.
OFFSET specifies a relative scale on the wall module where the setpoint is calculated by adding
the setpoint potentiometer value (± 5 K) to the appropriate value of nciTempSetPts.
ABSOLUTE_MIDDLE specifies an absolute scale on the wall module. The setpoint knob directly
determines the center point of occupied cooling and heating setpoints. The respective cooling and
heating setpoint is determined by the setpoint knob position adding or subtracting half of the user
selectable ZEB defined in nciSetPnts.<occ_mode>_cool or nciSetPnts.<occ_mode>_heat . This
applies to <occ_mode> OCCUPIED and STANDBY.
This setting determines the behavior of the override button. BYPASS_UNOCCUPIED allows
overriding the current occupancy mode to OCCUPIED for a configurable bypass time, or causing a
permanent override to UNOCCUPIED. BYPASS allows only the temporary override to OCCUPIED
and canceling it.
This setting configures the priority of the local (wall module push-button) or central (network
interface) override. If NETW ORK_WINS is set and the network sends value NUL, then the
override button is active.
This setting configures the display of occupancy and/or override. LED_OVERRIDE shows the
override from the bypass button or from the network. LED_OCCUPANCY shows the effective
occupancy mode. LCD_DISPLAY is only used for T7560 Wall Modules. The display shows the
occupancy mode with different symbols, and the override mode with flashing symbols.
53EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C3. Input Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
HVAC_AUTO
(if bound but fails to be
received or at application
restart)
0 (if bound but fails to be
received or at application
restart)
EMERG_NORMAL
(at application restart)
100% (at application restart)
nviFanSpeedCmdstateSNVT_switch
OFF
ON
NUL
nviInUseUWORD
0 to 65535
0
NUL (at application restart)
1
255
0 (if bound but fails to be
received), 65535 ( for 60s at
application restart)
(continued)
EN0B-0377GE51 R070354
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C3. Input Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXXXXThis is an input that coordinates the controller operation with the main equipment controller.
Depending on the available supply energy, the main equipment controller commands the FCU
controller to operate in heat mode only, cool mode only or heat and cool mode if appropriate to the
configuration. HVAC_AUTO means that both heating and cooling equipment are available, and the
current mode is determined by the control algorithm depending upon the room temperature and
effective setpoint. HVAC_AUTO is invalid for changeover applications. When the digital input is
configured for heating/cooling changeover input, this input will always have priority over the
network nviApplicMode’s HVAC_HEAT or HVAC_COOL.
XXXXXThis is an input from an energy management system (e.g. Zone Manager). When = 0, the
temperature control algorithm operates in a normal mode. When = 1, the effective setpoint will be
shifted by the amount defined in nciEmergyManag.si_dlc_setpt_bump. For cooling, the effective
setpoint will be increased; for heating, the effective setpoint will be decreased always with regard
to the frost protection limit.
XXXXIt is an emergency input from a device that determines the correct action during a given
emergency (such as a fire).
• EMERG_NORMAL, EMERG_NUL: terminate EMERG_ commands and restores the control
algorithm.
• EMERG_PRESSURIZE, EMERG_PURGE, EMERG_SHUTDOWN: heat/cool outputs OFF, fan
ON at highest speed.
• EMERG_DEPRESSURIZE: heat/cool outputs OFF, fan OFF.
XXXXThis input allows control of the fan speed by another node, such as another FCU Controller acting
as a master in a master/slave relationship or a Zone Manager providing central override capability
for fan speed.
See above.
Comments
XThis is used by the engineering tool or other supervisory node that it is "logged on" to the
controller node. It should be set every minute, or the controller will reset it after 60s to
automatically log OFF the supervisory node.
(continued)
55EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C3. Input Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
MODE_ENABLE and
UNSUPPRESS_ALARMS
(at application restart)
DestReheatnviReheatRelayvalueSNVT_switch
0 to 100%
nviReheatRelaystateSNVT_switch
OFF
ON
NUL
0 (at application restart)
OFF (at application restart)
0
1
255
(continued)
EN0B-0377GE51 R070356
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C3. Input Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXXXXThis can be used for master/slave installations where the cool output is controlled by an external
controller node. In this case, the output signal of the cooling control algorithm (0-100%) of the
master has to be bound to nviManCool and then takes over the task of the local (slave) control
algorithm while the switch levels operate as locally configured. The heating output will be closed.
XXXXXThis can be used for master/slave installations where the heat output is controlled by an external
controller node. In this case, the output signal of the heating control algorithm (0-100%) of the
master has to be bound to nviManHeat and then takes over the task of the local (slave) control
algorithm while the switch levels operate as locally configured. The cooling output will be closed.
XXXXThis is an input from an network connected operator interface or other node that indicates the
state of manual occupancy control (schedule override). It has priority over the time program
(DestSchedOcc). W hen the "bypass" mode is set, the bypass time is active. When the bypass
time has elapsed, the master controller automatically sets nviManOccCmd to OC_NUL.
NviManOccCmd does not provide a failure detect mechanism in case no periodic update is
received.
XXXThis is an input which is used to disable the controller’s control algorithms in order to manually set
its physical outputs. The controller still responds to smoke purge even when disabled or set to
manual or factory test mode. It remains unchanged until another mode has been commanded or
an application restart has been performed.
• MODE_ENABLE: starts the control algorithm at an initial state after MODE_DISABLE or
MODE_MANUAL.
• MODE_DISABLE: all outputs switched OFF, the alarm ALARM_NODE_OFF is issued.
• MODE_MANUAL: all control loops are disabled and the alarm ALARM_NODE_OFF is issued.
The outputs can be controlled manually via the nviTest command
• SUPPRESS_ALARMS: nvoAlarm is not sent and nvoAlarmStatus and nvoAlarmLog are not
updated until UNSUPPRESS_ALARMS is set or an application restart.
• UNSUPPRESS_ALARMS: releases alarm suppression after SUPPRESS_ALARMS.
XXXXThis variable is used to control the reheat relay via the network. This permits use of the relay as an
auxiliary output in applications where reheat is not required as well master/slave applications
where the reheat output is controlled by another controller acting as master.
See above.
Comments
(continued)
57EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C3. Input Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
0 (if bound but fails to
be received or at
application restart)
INVALID
(if bound but fails to be
received or at
application restart)
0
1
2
3
4
5
0
1
2
3
4
5
NORMAL_HC_MODE
(at application restart)
0 (at application restart)
NORMAL_HC_MODE
(at application restart)
0 (at application restart)
(continued)
EN0B-0377GE51 R070358
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C3. Input Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XThis input variable belongs to the Node Object and provides the mechanism to request a particular
mode for a particular object within a node.
See above. Commanding any modes other the ones listed will result in an “invalid_request” when
reading nvoStatus.
Comments
XXThis allows an occupancy sensor of another Excel 10 controller to be used to indicate the sensed
XXXXThis is an input intended for binding third-party nodes to authorize them for setpoint modifications.
XXXXXThis is an input intended for binding third-party nodes to authorize them for setpoint shifting.
XXXXXThis is the space temperature transmitted from another Excel 10 controller or another node that
occupancy state of the space. OC_NUL means no input is available because it is not bound,
bound but not received periodically, or not configured by nciFcuConfig.DI1_config. More than one
occupancy sensor may be bound to nviSensorOcc. If any one sensor detects occupancy, the
controller considers the space occupied.
When this has been bound and a valid update is received, the local configured setpoints will no
longer be directly used to determine the current occupancy setpoint. In the case of the "occupied"
and "standby" modes, this input is used with the appropriate ZEB (derived from the configured setpoints); in the case of the "unoccupied" mode, the setpoint depends only on
nciTempSetPts.unoccupied_cool/_heat. This input is stored in RAM and is lost after power failure.
In this case, the setpoints of nciTempSetPts will be used until a valid nviSetpoint is received.
nviSetPtOffset is stored in RAM and will be initialized to zero after application restart or power
failure. If nviSetPtOffset is bound and fails to be received periodically as configured with
nciRcvHrtBt, it will be reset to zero.
has a temperature sensor wired to it. If bound or has a value other than INVALID, then it is used
as the sensed space temperature instead of the wired wall module's temperature. NviSpaceTemp
may be set to a value other than INVALID using a network management tool when nviSpaceTemp
is not bound to set the temperature to a fixed value.
This is used by factory test, OEM field test, field installation, and field testing to manually
command the physical output 1 when the node has been put into manual mode (nviManualMode =
MODE_MANUAL).
NORMAL_HC_MODE: output 1 remains in its current position
OFF1_OFF2, ON1_OFF2, OFF1_ON2, ON1_ON2: set the individual triacs ON or OFF
TESTPOSITION: sets output based on output1_test_pos.
This is used for the TESTPOSITION of the output1_cmd and is based on the configured
runtime/cycle time.
Same as output1_cmd for output 2.
Same as output1_test_pos for output 2
59EN0B-0377GE51 R0703
(continued)
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C3. Input Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
OC_OCCUPIED
(if bound but fails to be
received or at
application restart)
OC_OCCUPIED
(if bound but fails to be
received or at
application restart)
0 (if bound but fails to be
received or at
application restart)
0 (if bound but fails to be
received or at
application restart)
nviWindowstateSNVT_switch.state
EN0B-0377GE51 R070360
CLOSED
OPEN
NO_WINDOW
0
1
255
NO_WINDOW
(if bound but fails to be
received or at
application restart)
(continued)
Table C3. Input Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
This is used to test the reheat relay.
This is used to test the fan speed relays.
This can be used to test the wall module LED when nviManualMode = MODE_MANUAL.
XXXXThis indicates to the node whether the space is currently scheduled to be occupied, standby or
XXXThis indicates to the node whether the next scheduled occupancy mode will be occupied, standby
XXXThis is the time in minutes until the next change of scheduled occupancy state. This time is
XXXXThis allows a window contact node or another controller to be used as remote window contact.
unoccupied.
or unoccupied. This information is required by the controller to perform the optimum start strategy.
updated by the Zone Manager once every 60 seconds. This data is also used by the optimum start
calculation (see nciEnergyManag).
More than one nvoWindow may be bound to one nviW indow, which allows one node to be used to
handle several distributed window contacts. In this case the control process assumes an open
window if at least one bound window node detects an open window. ‘Window Closed’ would be
assumed if all nvoW indows bound to nviWindow indicate the window being closed for at least the
failure detect time (nciSndHrtBt).
XSee above.
(continued)
61EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXThis is an output showing the active setpoint of the control algorithm. It is based on the occupancy
setpoints, the offset and recovery ramping.
XThe subnet is the LonWorks subnet number (in domain entry 1 of the node’s domain table).
XThe node is the LonWorks node number (in domain entry 1 of the node’s domain table).
This is an output reporting the latest changed error condition detected in the node. The first 5 bits
are used for the alarm type number, and this number is added to RETURN_TO_NORMAL (128)
when the error condition is no longer true. Each error condition/return-to-normal is issued only
once. The type is also recorded in nvoAlarmLog and nvoFcuStatus.alarm_type.
Alarm reporting is suppressed by settin nviManualMode to SUPPRESS_ALARMS, in which case
nvoAlarm.type is set to ALARM_NOTIFY_DISABLED. Alarm reporting is turned ON again by
setting nviManualMode to UNSUPPRESS_ALARMS, after which all existing alarms (or
ALM_NO_ALARM) are reported one at a time.
Comments
(continued)
63EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
user addressNvNamefield name
SrcAlarmLog1nvoAlarmLogalarm_type[0]Same as nvoAlarm.typeSee nvoAlarm.type
SrcAlarmLog2nvoAlarmLogalarm_type[1]Same as nvoAlarm.typeSee nvoAlarm.type
SrcAlarmLog3nvoAlarmLogalarm_type[2]Same as nvoAlarm.typeSee nvoAlarm.type
SrcAlarmLog4nvoAlarmLogalarm_type[3]Same as nvoAlarm.typeSee nvoAlarm.type
SrcAlarmLog5nvoAlarmLogalarm_type[4]Same as nvoAlarm.typeSee nvoAlarm.type
Bit coded Alarm:
ALM_COMFAIL_MANHEAT
ALM_COMFAIL_MANCOOL
ALM_HW_SW_MISMATCH
HVAC_AUTO
HVAC_HEAT
HVAC_COOL
HVAC_OFF
0 to 100%
163.835% = INVALID
digital
state
or
value
1
2
4
8
16
32
64
128
1
2
4
8
16
32
64
128
1
2
4
0
1
3
6
default
HVAC_OFF
(at application restart)
EN0B-0377GE51 R070364
(continued)
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XA central node may poll the nvoAlarmLog output for a short history of alarms. It contains the last
XSee above.
XSee above.
XSee above.
XSee above. NvoAlarmLog.alarm_type[4] is the oldest alarm.
XThis is a polled output containing a list of all the current errors detected by the node. A search for
XSee above.
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
five alarms reported via nvoAlarm. At the time a new nvoAlarm is issued, nvoAlarmLog is updated.
error conditions in the node is made periodically. A central node may poll the nvoAlarmStatus
output for all of the current errors. NvoAlarmStatus contains all the current detected errors even
though they may be suppressed for reporting by nvoAlarm.
XSee above.
XXThis is an output used to coordinate the slave devices with the master controller. It reflects the
XXThis is the cooling output which is typically used for monitoring or bound to a cooling actuator node
current heat/cool medium based on supply energy available. This is required for configurations
with heat/cool changeover. HVAC_OFF switches the heat/cool control OFF while still providing
frost protection and reporting status and alarms.
or another controller operating as slave. nvoCoolOutput will be transmitted immediately when its
value has changed significantly (>= 1%), and periodically according to nciSndHrtBt. The output
value represents the output of the control algorithm but is limited to a range of 0% to 100%.
(continued)
65EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXXXThis indicates the binary state of the controller's digital input which can be configured to support a
window contact, an occupancy/movement sensor, an air flow contact, or a heat/cool changeover
contact. It can be bound to another Excel 10 controller or a third-party node.
See above.
Comments
XThis is the output reflecting the effective occupancy mode derived from the time schedule,
XXThis output reports the fan speed for the controller. It can be bound to another Excel 10 controller
XXXXThis output allows the fan speed switch of a master controller to be used for all slave Excel 10
occupancy sensor, override button, and network occupancy override.
with a fan connected or to a third-party fan node.
XSee above.
controllers in the same room.
See above.
XThis is used to indicate which other data field in nvoFcuStatus has changed since the last time
nvoFcuStatus was sent out on the network. If any field has had a significant change, only that field
is updated, and field_no indicates which field. If three or more fields have changed significantly,
then all fields are updated and field_no is set to 0. All fields are also updated every refresh time
(55s).
(continued)
67EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXXThis is the effective occupancy mode resulting from scheduled occupancy mode, occupancy
XXXIt reports the current state of the remote override button.
XXIt reports the current scheduled occupancy received via the network.
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
sensor information, bypass push-button, or manual operator interface.
XXXThis reports the effective state of occupancy sensor(s) connected either to the input terminals or to
XXThis reports the manual occupancy from the network.
XXXIt reports the state of the occupancy sensor wired to the node.
XXThis variable reports the current state of the remote override LED which indicates the effective
XXXThis is the current operating mode of the node determined by many inputs and arbitrated by
other nodes on the network that are bound to this controller..
schedule override resulting from the bypass push-button or a network override.
OC_OCCUPIED: 2 flashes per second
OC_UNOCCUPIED: 1 flash per second
OC_BYPASS: ON
OC_STANDBY: 2 flashes per second
OC_NUL: OFF
control logic.
CTL_PRESSURIZE disables the heat/cool outputs, fan runs at highest speed.
CTL_DE_PRESSURIZE disables the heat/cool outputs, fan is turned OFF.
CTL_MODE_MANUAL allows turning ON and OFF outputs manually through nviTest.
CTL_MODE_FACTORY_TEST is intended only for the factory.
CTL_FLOATING_OUT_SYNCH allows enough time (150% valve run time) for the valve(s) are at
their initial positions (control algorithms are active). The controller then goes into one of the normal
operating modes, such as CTL_COOL. When the effective occupancy changes to unoccupied or
24 hours have elapsed since the last start-up or CTL_FLOATING_OUT_SYNCH mode, the
controller enters this mode again to reset the floating output position tracking.
CTL_START_UP_WAIT is the first mode after an application restart. No control algorithms are
active, and heat/cool outputs stay in their default positions. CTL_FLOATING_OUT_SYNCH
follows.
CTL_DISABLED disables heat/cool control.
(continued)
69EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XThis is the latest alarm detected by the node (if any) and has the same value as nvoAlarm.type.
XXThis indicates the state of the demand limit control.
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
XXXThis indicates the real status of the window detection, either from the digital input or from the
XXXThis indicates the status of the digital input configured as a window contact.
XXXThis indicates the status of the fan when the digital input is configured for an air flow sensor.
XXThis applies to nciFcuConfig.reheat_config = EXTERNAL only and indicates the state of the relay.
XXXWhen the controller is configured for one or more fan stages, this output reports the current fan
XXThis indicates the position of the output 1.
XXThis indicates the position of the output 2.
XXThis output reports the current state of the reheat output, when the controller is configured for one.
network.
stage active.
XXXThis reports the current temperature control point calculated from the various setpoints, operating
XXXThis reports the current space temperature used for the control algorithm.
XXThis shows the current value in minutes of the active bypass timer
modes, and optimum start-up gradients.
(continued)
71EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
user addressNvNamefield name
nvoFcuStatusPfield_noSame as nvoFcuStatus.
SrcOccEffPnvoFcuStatusPeffect_occSame as nvoFcuStatus.
SrcOccOvrdHwPnvoFcuStatusPhw_overrideSame as nvoFcuStatus.
SrcOccSchedPnvoFcuStatusPsched_occSame as nvoFcuStatus.
SrcOccSensorPnvoFcuStatusPeff_sen_occSame as nvoFcuStatus.
SrcOccOvrdNetPnvoFcuStatusPnet_man_occSame as nvoFcuStatus.
SrcOccSensorHwPnvoFcuStatusPhw_sen_occSame as nvoFcuStatus.
SrcOvrdLedPnvoFcuStatusPr_o_ledSame as nvoFcuStatus.
SrcFcuModePnvoFcuStatusPmodeSame as nvoFcuStatus.
nvoFcuStatusPalarm_typeSame as nvoFcuStatus.
SrcDlcShedPnvoFcuStatusPdlc_shedSame as nvoFcuStatus.
SrcWindowPnvoFcuStatusPeff_window_openSame as nvoFcuStatus.
SrcWindowHwPnvoFcuStatusPhw_window_openSame as nvoFcuStatus.
SrcAirFlowPnvoFcuStatusPfan_feedbackSame as nvoFcuStatus
SrcExternalRelPnvoFcuStatusPexternal_activeSame as nvoFcuStatus
SrcFanSpeedPnvoFcuStatusPfan_stages_activeSame as nvoFcuStatus
SrcOutput1PnvoFcuStatusPoutput_position[0]Same as nvoFcuStatus.
SrcOutput2PnvoFcuStatusPoutput_position[1]Same as nvoFcuStatus.
SrcReheatPnvoFcuStatusPreheat_activeSame as nvoFcuStatus
SrcRmTempSptEffPnvoFcuStatusPactive_set_ptSame as nvoFcuStatus.
SrcRmTempEffPnvoFcuStatusPspace_tempSame as nvoFcuStatus.
SrcRestBypassTimePnvoFcuStatusPrest_bypass_timeSame as nvoFcuStatus.
SrcHeatPosnvoHeatOutputSNVT_lev_percent
0 to 100%
163.835% = INVALID
engineering units:
English (metric) or states plus
range
digital
state
or
value
default
EN0B-0377GE51 R070372
(continued)
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
Same as nvoFcuStatus except not sent as heartbeat. This variable is sent only in response to a
poll request, typically from a supervisory device.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
Same as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XSame as nvoFcuStatus.
XXThis is the heating output which is typically used for monitoring or bound to a heat actuator node
or another Excel 10 controller operating as slave. nvoHeatOutput will be transmitted immediately
when its value has changed significantly (>= 1%), and periodically according to nciSndHrtBt. The
output value represents the output of the control algorithm but is limited to a range of 0% to 100%.
Comments
(continued)
73EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXThis output reports the actual state of the reheat output. It can be bound to another Excel 10
controller acting as a slave, or it can be bound to a third-party reheat node.
XSee above.
This indicates the status of the override push-button.
This indicates the state of the digital input.
This contains the analog to digital converter count measured from the analog value of the temp.
sensor, which represents the measured time during the second part of each A/D conversion.
Same as above for the fan speed switch.
Same as above for the setpoint knob.
Comments
This output indicates the position of the fan speed switch on the wall module.
XThis is the set point from the wall module setpoint knob and may be absolute or relative depending
XThis is the measured space temperature.
upon nciWallMod.set_pnt_knob.
This is used to establish hardware-dependent factory default configuration settings for the FCU
controller. Note that D and F versions and E, G and J versions differ only in their supply voltage.
(continued)
75EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXXXThis is an output showing the state of the locally-wired occupancy sensor, if one is configured by
nciFcuConfig.DI1_config. OC_NUL means no input is available because it is not bound or not
configured by nciFcuConfig.DI1_config.
Comments
XXThis is the sensed space temperature at the node taken from the locally-wired sensor. It is
XXThis output belongs to the Node Object and reports the status for any object on a node. This is the
typically bound to nviSpaceTemp of another node which may not have its own space temperature
sensor but controls the same space. It is also used for monitoring purposes, showing the current
space temperature used for the control algorithm. nvoSpaceTemp is transmitted immediately
when its value has changed significantly (> 0.5 delta°C). The reported space temperature includes
the offset correction nciWallMod.si_space_temp_zero_cal. If a space temperature sensor is not
connected or is shorted or if nviSpaceTemp is bound to another node, nvoSpaceTemp is not
reported on the network.
answer to the nviRequest.
XThis indicates whether nviRequest uses a fault object ID.
XThis indicates whether nviRequest uses a fault request.
XThis indicates whether the device is enabled or disabled (nviManualMode = DISABLE).
XThis indicates whether an update nviRcvHrtBt is missing.
XThis indicates whether an alarm occured. See nvoAlarm.
XThis shows the answer to nviRequest > REPORT_MASK
XXXXXThis is an output showing the terminal load, which is a percentage between -160% and +160%
XXXXXThis output variable reports the last operating mode of the control algorithm. It is not set to
XXXXThis reports the actual heating output value. Any change forces nvoUnitStatus to be transmitted
XXXXThis output reports the reheat output value.
based on the control output level. Negative values indicate heating load and positive values
indicate cooling load. 100% is the full terminal capacity. An absolute terminal load value of more
than 100% indicate that the terminal is not able to supply the required heating or cooling energy
which at the zone controller should cause a demand for more supply energy. nvoHeatOutput will
be transmitted immediately when its value has changed significantly (>= 1%).
HVAC_OFF if the heating and cooling output shows 0%. HVAC_OFF is set when the device is
disabled from nviRequest, nviManualMode or nviApplicMode.
immediately.
(continued)
77EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
Table C4. Output Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XXXXThis reports the actual cooling output value. A change of more than 1% forces nvoUnitStatus to be
XXXThis output reports the actual fan speed level.
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
transmitted immediately.
XXXThis reports the actual alarm status of the controller and is set to ALARM_NOTIFY_DISABLE
XXXXThis reports the status of the window sensor. It allows the locally-wired window sensor to be used
XThis identifies the Excel 10 node type by an eight byte constant describing the node type, major
XSecond character.
XThird character.
XFourth character.
XMajor Functional Release Number:
XMinor Functional Release Number:
XBug Fix Number:
XNode type number.
when nviManualMode = SUPPRESS_ALARMS.
by other nodes on the network.
XSee above.
and minor functional release number and bug fix. First character.
1. Add or delete a network variable (NV), nv field.
2. Change the name of a nv or nv field.
3. Range or type (short / long) of data in a nv field is changed.
4. Enumerated value list of a nv field is changed.
NOTE: Algorithm changes or bug fixes may also be included.
1. Network variables are unchanged.
2. Functionality of the control algorithm has been revised and affects compatibility with other
nodes or the equipment being controlled.
3. The network interface or physical input / output subsystem was revised and affects
compatibility with other nodes.
NOTE: Bug fixes may also be included in a minor functional release.
Network variables are unchanged. A change to the algorithm, network interface, or physical
input/output subsystem was made that does not affect compatibility with other nodes or the
equipment controlled by the node.
79EN0B-0377GE51 R0703
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Table C5. Unused Variables for Excel 10 W7752 and W7754 FCU Controllers (left)
user addressNvNamefield name
nciApplVernot_used1UBYTE
nciApplVernot_used2UBYTE
nciCntrlSettingsreserve7 bits
nciFcuConfignot_used4 bits
nciWallModspare_field[0]UBYTE
nciWallModspare_field[1]UBYTE
nvoFcuStatusnot_used3 bits
nvoFcuStatusspare_field[0]WORD
nvoFcuStatusPnot_usedSame as nvoFcuStatus
nvoFcuStatusPspare_field[0]Same as nvoFcuStatus
nvoSensornot_used6 bits
nvoStatusout_of_limitsBit
nvoStatusopen_circuitBit
nvoStatusout_of_serviceBit
nvoStatusmechanical_faultBit
nvoStatusfeedback_failureBit
nvoStatusover_rangeBit
nvoStatusunder_rangeBit
nvoStatuselectrical_faultBit
nvoStatusunable_to_measureBit
nvoStatusfail_self_testBit
nvoStatusself_test_in_progressBit
nvoStatuslocked_outBit
nvoStatusmanual_controlBit
nvoStatusin_overrideBit
nvoStatusreserved1Bit
nvoStatusreserved2Bit
nvoUnitStatusecon_outputSNVT_lev_percent
engineering units:
English (metric) or states
plus range
digital
state
or
value
default
EN0B-0377GE51 R070380
Table C5. Unused Variables for Excel 10 W7752 and W7754 FCU Controllers (right)
Share (SH), Map (MA),
Direct Access (DA)
Monitor (M), Heartbeat (HBT)
SHMADAMHBT
XNot used.
XNot used.
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
XNot supported
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
Comments
Reserved for future use.
Reserved for future use.
Reserved for future use.
Reserved for future use.
Reserved for future use.
Reserved for future use.
Not used.
Not used
Reserved for future use.
81EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING
APPENDIX D. Q7750A EXCEL 10 ZONE MANAGER POINT ESTIMATING GUIDE
Memory size approximation is shown in Fig. 22: (All sizes in
bytes.) When memory size is less than 110 Kbytes, the size
is adequate.
2. Calculate the number of Excel 10 Zone Manager
program points that will be used in the control logic and
in the switching table.
When memory size is between 110 and 128 Kbytes, the
application may be too large. The user must expect to reduce
the application complexity, reduce the number of attached
Excel 10 FCU Controllers or distribute the Excel 10 FCU
Controllers among more than one Zone Manager.
When memory size is greater than 128 Kbytes, the size is too
large. The application size must be reduced as described
above.
Approximate Memory Size Estimating
Procedure
1. Determine the number of points per controller required
at the Central (for example, XBS).
NOTE: All remaining points that are not mapped are
available for accessing through the DirectAccess feature.
3. Estimate the program complexity of the Zone Manager
(one of three levels).
a.No time programs, control logic, or switching
tables.
b.10 Kbyte of control logic (one time program, five
switching tables, and five control loops).
c.20 Kbyte of control logic (multiple time programs,
ten switching tables, and ten control loops).
Use Fig. 22 to determine the number of Excel 10
Controllers that can be connected to the Zone
Manager.
NOTE: Where the number of Excel 10 Controllers
exceeds 60 a router is required.
4. Repeat the calculation for each Q7750A Excel 10 Zone
Manager in the project.
Fig. 22. Point capacity estimate for Zone Manager
The exact equation to use to calculate memory size is:
Memory size = 21,780 byte
+ 4096 byte (in case of a time program)
+ CARE Control Program
+ 14 byte x time points x Excel 10 Controllers
+ 50 byte x Excel 10 Controllers
+ map complexity x Excel 10 Controllers x mapped points
+ 57 byte x C-Bus points
+ 7488 byte x Excel 10 Controller types
Where:
time points = number of switch points in time
program per Excel 10 FCU
Controller
Excel 10 Controllers = number of attached Excel 10
FCU Controllers
EN0B-0377GE51 R070382
C-Bus points = including mapped points and
others; for example, Remote
Points
Mapped points = number of mapped points for
each Excel 10 FCU Controller,
including one-to-many and
many-to-one mechanism
Excel 10 Controller types = number of different Excel 10
Controller types (currently one)
Map complexity =
20 = using one-to-many and not
using points with read/write
ability
30 = average
45 = many points with read/write
ability
EXCEL 10 FCU CONTROLLER SYSTEM ENGINEERING
83EN0B-0377GE51 R0703
EXCEL 10 FAN COIL UNIT CONTROLLER SYSTEM ENGINEERING