Honeywell W7752D2007, W7752E2004, W7752F2002, W7752G2000 Installation Instructions Manual

Page 1
® U.S. Registered Trademark Copyright © 2011 Honeywell Inc. All Rights Reserved EN1B-0250GE51 R0111B
Excel 10
W7752D,E,F,G FAN COIL UNIT CONTROLLERS
HONEYWELL EXCEL 5000 OPEN SYSTEM
The Excel 10 Fan Coil Unit (FCU) Controller is available in the following four models:
W7752D2007 (230 Vac, with electric reheat relay), W7752E2004 (230 Vac, without electric reheat relay), W7752F2002 (115 Vac, with electric reheat relay), W7752G2000 (115 Vac, without electric reheat relay).
All have identical housings and mounting procedures.
IMPORTANT
It is recommended that devices be kept at room temperature for at least 24 hours before applying power to allow any condensation resulting from low shipping/storage temperatures to evaporate.
This device must be installed in a UL-listed enclosure offering adequate space to maintain the segregation of line voltage field wiring and Class 2 field wiring (US requirement only).
INSTALLATION
Mount the Fan Coil Unit controllers in locations that allow clearance for wiring. The controllers can be mounted on a panel with screws or by snapping onto standard EN 50 022 DIN rail, 1-3/8 by 9/32 in. (35 mm by 7.5 mm). See Fig. 1 for
mounting dimensions. See Fig. 2 for DIN rail mounting. The type and length of screw required for screw mounting depends upon the panel material used to mount the con­troller.
The controller can be mounted either vertically or horizontally. However, if thermal actuators are connected to the controller outputs, it is recommended that the controller be mounted so that the transformer is not located beneath the electronics.
WARNING
ELECTRICAL SHOCK HAZARD.
Source power at terminal block can cause personal injury or death. W7752 FCU Controllers must be mounted inside their respective fan coil unit boxes to prevent access by unauthorized personnel.
To reduce the risk of fire or electric shock, install in a controlled environment relatively free of contaminants.
Wiring
All wiring must comply with applicable electrical codes and ordinances. Refer to job or manufacturers’ drawings for details.
Fig. 1. Excel 10 Fan Coil Unit Controller outside and mounting dimensions in in. (mm)
BEFORE INSTALLATION
Page 2
W7752D,E,F,G FAN COIL UNIT CONTROLLERS INSTALLATION INSTRUCTIONS
EN1B-0250GE51 R0111B
2
Fig. 2. DIN rail mounting
Power
Input power provided must be 230 Vac (+10%, -15%), 50 or 60 Hz for W7752D and E; 115 Vac (+10%, -15%), 50 or 60 Hz for W7752F and G.
CAUTION
Turn OFF power prior to connecting to or removing connections from any terminals to avoid electrical shock or equipment damage.
Use the heaviest gauge wire available, up to 14 AWG (2.5 mm
2)
with a minimum of 18 AWG (1.0 mm2) for all power wiring. Strain relief/support must be provided for power wiring within 2-3/8 in. (60 mm) of controller connection.
IMPORTANT
To comply with CE requirements, with devices having a voltage range of 50 to 1000 Vac or 75 and 1500 Vdc which are not provided with a supply cord and a plug or with other means for disconnection from the supply having a contact separation of at
least 3 mm in all poles, the means for disconnection must be incorporated in the fixed wiring.
LonWorks Communications
The unit is equipped with a free-topology transceiver for communication on L
ONWORKS® networks. The LONWORKS
network is insensitive to polarity, eliminating the possibility of installation errors due to miswiring.
Different network configurations (daisy-chain, loop, and star configurations, or any combination thereof) are possible (see also Excel 50/500 L
ONWORKS Mechanisms Interface
Description, EN0B-0270GE51).
IMPORTANT
Do not bundle wires carrying field device signals or L
ONWORKS communications together with high-
voltage power supply or relay cables. Specifically, maintain a min. separation of 3 inches (76 mm) between such cables. Local wiring codes may take precedence over this recommendation.
IMPORTANT
Try to avoid installing in areas of high electro­magnetic noise (EMI).
The unit must be wired to the L
ONWORKS network using level
IV 22 AWG (Belden part number 9D220150) or plenum-rated level IV 22 AWG (Belden part number 9H2201504) non­shielded, twisted-pair, solid-conductor wire. When possible, use Honeywell AK3781, AK3782, AK3791, or AK3792 cable (US part numbers). See Excel 50/5000 L
ONWORKS
Mechanisms (EN0B-0270GE51) for details, including max. lengths. Use wire with a min. size of 20 AWG (0.5 mm
2
) and a
max. size of 14 AWG (2.5 mm
2
).
Wall Modules
A variety of Excel 10 wall modules can be used with W7752 FCU Controllers. See T7460 Wall Modules Installation Instructions (95-7610) and T7560 Digital Wall Module Installation Instructions (EN1B-0146GE51) for details.
W7752 FAN COIL UNIT CONTROLLER
W7752 FAN COIL UNIT CONTROLLER
TERMINATIO
N
MODULE
991010111112
12
Fig. 3. Termination module connection (daisy-chain network configuration)
Page 3
W7752D,E,F,G FAN COIL UNIT CONTROLLERS INSTALLATION INSTRUCTIONS
3 EN1B-0250GE51 R0111B
Wiring Details
Connections to the FCU controllers are made at two terminal blocks protected by a plastic cover. W7752D and F models have two additional terminals on terminal block 2 for electric reheat connections. Fig. 4 shows removal of the terminal block cover.
Use a minimum wire size of 20 AWG (0.5 mm
2
) for all input/output connections. Use a minimum of 16 AWG (1.5 mm
2
) for electric reheat output connections. The maximum length of all input/output cables and wall module interface cables is 65 ft (20 m). The maximum length for fan power switching cables is 3 1/2 ft (1 m).
Fig. 6 illustrates the terminal assignments of the controllers. Table 1 lists Triac output assignments for various actuator types. Refer to job drawings for specific wiring diagrams.
IMPORTANT
Screw-type terminal blocks are designed to accept no more than one 14 AWG (2.5 mm
2
) conductor.
Multiple wires that are 14 AWG (2.5 mm
2
) can be connected using a wire nut. Include a pigtail with this wire group and attach the pigtail to the individual terminal block.
Fig. 4. Terminal cover removal
Wire to the terminal blocks as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Insert the wire in the required terminal location and tighten the screw to complete the termination.
3. If two or more wires are being inserted into one terminal location, twist the wires together before inserting them.
IMPORTANT
When two or more wires are to be attached to the same terminal, be sure to twist them together. Deviations from this rule can result in improper electrical contact. See Fig. 5. Local wiring codes may take precedence over this recommendation.
Page 4
W7752D,E,F,G FAN COIL UNIT CONTROLLERS INSTALLATION INSTRUCTIONS
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Strasse 17 71101 Schönaich / Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://ecc.emea.honeywell.com Subject to change without notice. Printed in Germany
EN0B-0250GE51 R0111B
D
G
N
D
D
I
G
I
T
A
L
I
N
P
U
T
LED SETPOINT FAN / BYPASS TEMP SENSOR AGND
LonWorks BUS IN
LonWorks BUS IN
LonWorks BUS OUT
LonWorks BUS OUT
OUT 1 COM OUT 1 OPEN OUT 1 CLOSE OUT 2 COM OUT 2 OPEN OUT 2 CLOSE
RELAY COM RELAY 1 RELAY 2 RELAY 3 SUPPLY VOLT SUPPLY VOLT PWR RELAY IN (D,F MODELS, ONLY) PWR RELAY OUT (D,F MODELS, ONLY)
W7752 FAN COIL UNIT CONTROLLER
WALL MODULE
CONNECTIONS
LONW
ORKS
NETWORK IN
L
ONWORKS
NETWORK OUT
OCCUPANCY SENSOR
CHANGEOVER CONTACT
AIRFLOW CONTACT
WINDOW CONTACT
MOTION SENSOR
OPEN
OPEN
CLOSE
CLOSE
COM
COM
HI
MED
LO
HEAT
COOL
REHEAT
RETURN
POWER MAINS
L N
FAN
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18
19 20 21 22 23 24 25 26
4A
0.5A
16A
Fig. 6. Input/output details
Table 1. Output assignments for various actuator types
output type Out 1 terminal Out 2 terminal
13 14 15 16 17 18
floating 24 Vac open close 24 Vac open close
1-stage 24 Vac ON/OFF 24 Vac ON/OFF
2-stage 24 Vac stage 1 stage 2 24 Vac stage 1 stage 2
3-stage 24 Vac stage 1 stage 2 24 Vac stage 1 stage 2
stage 3 stage 3
PWM 24 Vac PWM 24 Vac PWM
thermal 24 Vac ON/OFF 24 Vac ON/OFF