Honeywell W7751H3007 INSTALLATION INSTRUCTIONS

Page 1
Excel 10
W7751H3007 VAV ACTUATORS
HONEYWELL EXCEL 5000 OPEN SYSTEM
The W7751H Smart VAV Actuator consists of a factory­combined variable air volume (VAV) box controller and a direct-coupled damper actuator with de-clutch mechanism. The actuator/controller assembly is field-mounted to the VAV box damper shaft similar to the mounting of a standard actuator, and the controller wiring is terminated to the screw terminals accessible inside the detachable wiring box. See Fig. 2.
The W7751H's built-in actuator with de-clutch mechanism allows the installer to manually open or close its built-in VAV box damper without power or software tool.
The W7751H contains a Free Topology Transceiver (FTT) LonMark® compliant controller containing a Microbridge flow­through pressure sensor and communicates via the 78 kbaud L
ONWORKS
The W7751H actuator mounts directly onto the VAV box damper shaft and has up to 6 Nm torque, 95 degree stroke, and 110 sec. timing at 50 Hz and 90 sec at 60 Hz.
If desired, the SSW2 Auxiliary Switch Kit (see "SSW2 Auxiliary Switch Kit for N05xx, N10xx Non-Spring Return Direct-Coupled Damper Actuators – Installation Instructions", Product Literature No.: MU1B-0284GE51) can be attached to the W7751H. See also section "Optional Accessories" on page 9.
NOTE: Any hardware driven by the triac outputs must have
® Network.
a min. current draw, when energized, of 25 mA at 24 Vac and a max. current draw of 770 mA.
INSTALLATION INSTRUCTIONS
Fig. 1. Excel 10 Smart VAV Actuator
1
2
MAIN FEATURES
Legend for Fig. 2:
1) Universal shaft adapter
2) Mechanical end limits (manually adjustable in increments of 5.5°)
3) Air flow pick-up connector (-LO)
4) Air flow pick-up connector (-HI)
5) L
ONWORKS
6) Declutch button
7) L
ONWORKS
8) Detachable wiring box
9) Anti-rotation bracket
® U.S. Registered Trademark EN1B-0279GE51 R0707B
Copyright © 2007 Honeywell Inc. • All rights reserved
service LED
service pin
3
4
6
5
7
9
Fig. 2. W7751H main features
8
Page 2
EXCEL 10 W7751H SMART VAV ACTUATOR
INSTALLATION
The W7751H provides IP40 in all mounting orientations.
IP40 IP40
360° 360°
2
1
1
1
0
1
9
8
7
6
5
4
3
2
1
Fig. 4. Opening wiring box (1)
Fig. 3. Permissible orientations providing IP40
Mount the W7751H on the damper shaft and allow clearance for wiring, servicing, and module removal. Avoid mounting the W7751H in areas where acid fumes or other corrosive vapors can attack the actuator's metal parts, or in areas where escaping gas or other explosive vapors are present. See Fig. 23 for mounting dimensions.
The W7751H is field-mounted to the VAV box damper shaft. The W7751H actuator opens or closes a damper by driving the damper shaft in either the counterclockwise (CCW) or clockwise (CW) direction. If the W7751H is to be mounted directly onto a damper shaft, use the mounting bracket and screw included in the delivery.
The wiring of the W7751H controller is terminated to a screw terminal block accessible inside the detachable wiring box. See section "Wiring".
The W7751H actuator is shipped in the fully counterclockwise (CCW) position (95 degrees). Mount the W7751H so that the actuator is parallel with the VAV box damper housing.
CAUTION
Equipment damage hazard. Mounting actuator unevenly with damper housing can damage actuator.
Mount the actuator flush with the damper housing or add a spacer between the anti-rotation bracket and the VAV damper box housing (see Fig. 6).
4
3
2
1
2
1
1
1
0
1
9
8
7
6
5
Fig. 5. Opening wiring box (2)
VAV b ox
damper shaft
VAV b ox
damper housing
spacer or washer
Fig. 6. Mounting W7751H with washer/spacer
Before mounting the W7751H onto the VAV box damper shaft, do the following:
1. Ensure that the diameter of the damper shaft is within the allowed limits (round: 8…16 mm, square: 6…13 mm).
EN1B-0279GE51 R0707B
2
Page 3
2. Ensure that the damper shaft has a length of at least 40 mm.
3. Determine the direction (CW or CCW) in which the damper shaft rotates to open the damper (see Fig. 7).
4. Determine the angle of the damper opening (can be adjusted in increments of 5.5°).
TYPE A DAMPER
COOLING
AIR FLOW
CW TO OPEN, CCW TO CLOSE
TYPE B DAMPER
COOLING
AIR FLOW
CCW TO OPEN, CW TO CLOSE
Fig. 7. Determining direction of rotation
The W7751H actuator is shipped in the fully counterclockwise (CCW) position (95 degrees). The installation procedure varies depending on the damper direction.
NOTE: Be aware that, until the W7751H is powered and the
damper is driven open, starting the fan system with all the VAV box dampers closed can cause duct over-pressurization and damage.
If Damper Rotates CW to Open
If the damper rotates clockwise (CW) to open, mount the W7751H as follows:
1. Manually open the damper.
2. Push down the declutch button of the W7751H, and while
holding it down, manually rotate its shaft adapter fully to the clockwise position.
3. Mount the W7751H to the VAV damper box and shaft.
4. Set the mechanical end limits of the W7751H (see Fig. 8).
When the W7751H closes, the damper will thus rotate CCW until the mechanical end limits are reached.
If Damper Rotates CCW to Open
If the damper rotates counterclockwise (CCW) to open, mount the W7751H as follows:
1. Manually open the damper.
2. Push the declutch button of the W7751H, and while
holding it down, manually rotate its shaft adapter fully to the counterclockwise position.
3. Mount the W7751H to the VAV damper box and shaft.
4. Set the mechanical end limits of the W7751H (see Fig. 8).
When the W7751H closes, the damper will thus rotate CW until the mechanical end limits are reached.
EXCEL 10 W7751H SMART VAV ACTUATOR
Fig. 8. Setting the mechanical end limits
Reconfiguring to Match Rotation Direction
Using the LNS plug-in, the W7751H can be reconfigured to match the direction the damper shaft rotates to open the damper. Reconfigure the damper's direction of rotation to "open" or "closed," according to your needs.
To change the damper direction from CW to CCW using the LNS plug-in, proceed as follows.
1. Open the configuration part of the plug-in and select the "Wiring" tab (see Fig. 9).
Fig. 9. Wiring tab (default configuration)
2. Then deselect the output configuration (see Fig. 10).
3
EN1B-0279GE51 R0707B
Page 4
EXCEL 10 W7751H SMART VAV ACTUATOR
fan startup. Use the de-clutch button to open the W7751H's box damper only after the W7751H has been powered down (this is to prevent over­pressurization in the ductwork on fan startup). To use the de-clutch button, press and hold down the button (this disengages the motor). Turn the damper shaft until the damper is open and then release the button. When power is restored to the W7751H, it synchronizes the damper actuator so that the damper is in the correct position on startup.
Air Flow Pick-up
Connect the air flow pick-up to the two connectors on the W7751H. See Fig. 12.
AIRFLOW DELTA-P PICK-UP
AIRFLOW
DIRECTION
Fig. 10. Deselecting the output configuration
3. Now, configure the outputs so that the W7751H operates
counterclockwise (CCW) (see Fig. 11).
Fig. 11. Configuring the W7751H to open CCW
The damper direction has now been reconfigured.
IMPORTANT
It is recommended that the dampers be left in an "open" position after W7751H installation to avoid the possibility of over-pressurizing the ductwork on
-LOW
+HIGH
Fig. 12. Air flow pick-up connections
NOTES:
Use 6-mm outside diameter with 1-mm wall thickness plenum-rated 1219 FR (94V-2) pneumatic tubing.
Always use a fresh cut on the end of the tubing that connects to the air flow pick-ups and the connectors on the W7751H.
Connect the high pressure or upstream tube to the plastic restrictor labeled (+ HI) or P1 and the low-pressure or down­stream tube to the restrictor labeled (- LO) or P2. See labeling in Fig. 12.
NOTE: If controllers are mounted in unusually dusty or dirty
environments, a 5-micron disposable air filter is re­commended for the high-pressure line (marked as +) connected to the air flow pick-up.
When twin tubing is used from the pick-up, split the pick-up tubing a short length to accommodate the connections.
NOTES:
The tubing from the air flow pick-up to the W7751H should not exceed 0.914 m in length. Lengths much longer than this can degrade the flow sensing accuracy.
EN1B-0279GE51 R0707B
4
Page 5
To avoid damaging the air flow connectors, use caution when removing tubing from them. Always pull straight away from the connector; never remove by pulling at an angle.
Wiring
All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams.
NOTES:
24 Vac power connections. Verify that multiple controllers powered by the same transformer are wired with the transformer secondary connected to the same input terminal numbers on each W7751. See Fig. 13. Controller configurations are not necessarily limited to three devices, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer. For power wiring recommendations, refer to Excel 10 W7751B,D,F,H,J Variable Air Volume Controller – Application Guide (Product Literature No.: 74-2949).
In the case of multiple W7751H units operating from a single transformer, the same side of the transformer secondary must be connected to the same input terminal in each W7751H and the ground terminals (terminal 3 of the W7751H) must be connected to a verified earth ground for each controller in the group. See Fig. 14. Controller configurations are not necessarily limited to three devices, but the total power draw including accessories cannot exceed 100 VA when powered by the same transformer. For power wiring recommendations, refer to Excel 10 W7751B,D,F,H,J Variable Air Volume Controller – Application Guide (Product Literature No.: 74-
2949).
All loads on a W7751H must be powered by the same transformer that powers the W7751H.
Keep the earth ground connection (terminal 3) wire run as short as possible. See Fig. 14.
Do not connect the analog ground (terminal 5) to the earth ground. See Fig. 15.
W7751H W7751H W7751H W7751H
21 21 21 21
24 VAC
50/60 Hz
COM
Fig. 13. Wiring multiple W7751 units (with transformer
secondary connected to same input terminal numbers)
X
EXCEL 10 W7751H SMART VAV ACTUATOR
W7751H
231
24 VAC
50/60 Hz
COM
Fig. 14. Earth grounding
Power
The 24 Vac power from an energy-limited Class II Power Source must be provided to each W7751H. To conform to Class II restrictions, transformers must not be larger than 100 VA.
IMPORTANT
Power must be OFF prior to connecting to or disconnecting from output terminals 9 and 10.
Use the heaviest gauge wire available, up to 2.0 mm2 with a minimum of 1.0 mm
2
, for all power and earth ground wiring. For non-plenum, open areas, run cables exposed (or in conduit, if required).
2832
W7751D,F
24V 24VCOM COM
234
24 VAC
50/60 Hz
W7751B
W7751H
9110
IF THE W7751H IS USED IN UL 1995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 150 V, GROUND ONE SIDE OF TRANS­FORMER SECONDARY.
231
Fig. 15. Power wiring for multiple controllers
NOTES:
Unswitched 24 Vac power wiring can be run in the same conduit as the L
ONWORKS
® network cable.
Maintain a 76-mm separation between triac outputs and L
ONWORKS
® network wiring throughout the installation.
Communications
See Chapter "LonWorks System Engineering" of Excel 50/500 LonWorks Mechanisms – Interface Description (Product Literature No.: EN0B-0270GE51) for a complete description of L cable types for L is Level IV 0.34 mm twisted pair, solid conductor wire. For non-plenum areas, US part AK3781 (one pair) or US part AK3782 (two pair) can be uses. In plenum areas, US part AK3791 (one pair) or US part AK3792 (two pair) can be used. Communications wiring can be run in a conduit, if needed, with non-switched 24 Vac or sensor wiring. Only one router is allowed with each Excel 10
ONWORKS
ONWORKS
® network topology rules. Approved
® network communications wiring
2
plenum or non-plenum rated unshielded,
5
EN1B-0279GE51 R0707B
Page 6
EXCEL 10 W7751H SMART VAV ACTUATOR
V
Zone Manager, and each network segment can have a maximum of one repeater.
Pull the cable to each device on the L
ONWORKS
® network and connect to communication terminals 11 and 12 of the W7751H.
Notes on Communications Wiring:
All field wiring must conform to local codes and
ordinances (or as specified on the installation drawings).
Approved cable types for LONW
munications wiring is Level IV 0.34 mm
ORKS
® network com-
2
plenum or non­plenum rated unshielded, twisted pair, solid conductor wire. For non-plenum areas, US part AK3781 (one pair) or US part AK3782 (two pair) can be used. In plenum areas, US part AK3791 (one pair) or US part AK3792 (two pair) can be used.
Unswitched 24 Vac power wiring can be run in the same conduit as the L
ONWORKS
® network cable.
Do not bundle output wires with sensor, digital input or LONW
ORKS
® network wires.
Ensure that neither L
ONWORKS
® bus wire is grounded.
In noisy (high EMI) environments, avoid wire runs parallel to noisy power cables, motor control centers, or lines con­taining lighting dimmer switches, and keep at least 76 mm of separation between noisy lines and the L
ONWORKS
®
network cable.
Do not use different wire types or gauges on the same L
ONWORKS
® bus segment: Step changes in line im­pedance characteristics cause unpredictable reflections on the L
For L
ONWORKS
ONWORKS
® bus.
termination, use an XAL-Term or a
209541B termination module.
Verify Termination Module Placement
The installation wiring diagrams should indicate the locations for placement of termination module(s). See Chapter "LonWorks System Engineering" of Excel 50/500 LonWorks Mechanisms – Interface Description (Product Literature No.: EN0B-0270GE51). Correct placement of the termination module(s) is required for proper L
ONWORKS
® network
communications.
Wiring Details
Wire to the terminal blocks as follows:
1. Strip 5 mm insulation from the conductor
2. Insert the wire into the required terminal location and
tighten the screw to complete the termination.
NOTE: Earth ground wire length should be held to a
minimum. Use the heaviest gauge wire available, up to 14 AWG (2.0 mm2), with a minimum of 18 AWG (1.0 mm
NOTE: With the exception of 2.0 mm2, if inserting two or
more wires into one terminal location, use end sleeves. Deviation from this rule can result in improper electrical connection.
2
).
Fig. 16 through Fig. 21 provide detailed wiring diagrams for the W7751H. See the installation diagrams for specific wiring.
NOTE: Ensure that the wall module's Configuration DIP
Switch is set as shown in Fig. 19. Switches 1 through 3 set the timing of the valve actuator to match the W7751H outputs (minimum of 0.1 s, with a max. time of 25.6 s). Switch 4 determines the action of the actuator (OFF = Direct Acting, ON = Reverse Acting).
TRIAC
NOT EARTH
GROUND
EQUIVALENT
CIRCUIT
W7751H
LED
GND
BYPASS
SENSOR
SET PT
24VAC
COM
21
MODULE
EARTH
3
4
WALL
765
8
OUT1
9 10
OUT2
1112
LON
24VAC COMM IN
5
1 234
COM
SENSOR
6 7
OPEN SIGNAL
LED
BYP/FAN
LED/RTN
BYP/RTN
SET PT
CLOSED SIGNAL
T7460E
STEM
UP
ALVE ACTUATOR
COM
STEM
DOWN
Fig. 16. W7751H modulating reheat valve wiring diagram
TRIAC
NOT EARTH
GROUND
EQUIVALENT
CIRCUIT
W7751H
LED
GND
BYPASS
SENSOR
SET PT
24VAC
COM
21
EARTH
MODULE
3
4
WALL
765
8
OUT1
9 10
OUT2
1112
LON
24VAC COMM IN
1 234
COM
SENSOR
SET PT
T7460E
STAGE 1
5
6 7
LED
BYP/FAN
LED/RTN
BYP/RTN
LINE POWER
STAGE 2
Fig. 17. W7751H two-stage reheat wiring diagram
EN1B-0279GE51 R0707B
6
Page 7
EXCEL 10 W7751H SMART VAV ACTUATOR
*
TRIAC
NOT EARTH
GROUND
EQUIVALENT
CIRCUIT
W7751H
LED
GND
BYPASS
SENSOR
SET PT
WALL
COM
24VAC
EARTH
MODULE
5
3
21
24VAC COMM IN
1 2 3 456
BYP/FAN
SET PT
LED
BYP/RTN
COM
SENSOR
76
4
8
*
7
TEMPERATURE SENSOR
LED/RTN
OUT1
OUT2
9 10
1112
MODULATING OR STAGED REHEAT
LF20 DUCT
LON
WIRED FOR
T7460E
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION.
Fig. 18. W7751H discharge air sensing
CHECKOUT
Step 1. Wiring Connections
Inspect all wiring connections at the W7751H and the T7460 terminals, and verify compliance with installation diagrams. If any wiring changes are required, first be sure to remove power from the controller before starting work. Pay particular attention to:
Controller wiring: Be sure that each W7751H is wired (terminal 3 on the W7751H) to a verified earth ground using a wire run as short as possible with the heaviest
gauge wire available, up to 2.0 mm
1.0 mm2 for each controller in the group. See Fig. 15.
Verify that triac wiring to external devices uses the proper load power/24 Vac Hot terminal (terminal 1 on the W7751H).
NOTE: All wiring must comply with applicable electrical
codes and ordinances. See the installation diagrams for specific wiring.
Step 2. Startup
Broadcasting the Service Message
The Service Message allows a device on the LONW network to be positively identified. The Service Message con­tains the device's ID number and, therefore, can be used to confirm the physical location of a particular W7751H in a building. There are two methods for broadcasting the Service Message from the W7751H:
1. Operating the service pin on the W7751H: Insert a thin rod (e.g. paper clip) into the service pin hole (see Fig. 2) and push briefly; the Service Message will then be broadcast on the network.
2
with a minimum of
ORKS
®
2. Using the wall module bypass button: By pressing the wall module's bypass/override button for more than four seconds, the W7751H will send the Service Message (this functionality is supported in firmware version 1.2.15 and higher). When employing this method, the occupancy override state of the W7751H changes depending upon how long the bypass/override button is pressed. For example, if the button is pressed for six seconds, the W7751H will send the Service Message and also enter into the "continuous unoccupied" mode. To clear the "continuous unoccupied" mode, the button must be pressed briefly.
TRIAC
EQUIVALENT
CIRCUIT
LED
BYPASS
LON
OUT1
OUT2
765
9 10
8
1112
24VAC
COM
21
NOT EARTH
EARTH
3
4
GROUND
GND
SENSOR
SET PT
WALL
MODULE
24VAC COMM IN
PERIPHERAL HEAT
VALV E AC TUATOR
ML7984B
PWM VALVE ACTUATOR
COM
24 VAC
PWM 24VAC
FROM CNTRL
PWM OUTPUT
T6T5C B W R
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED
*
TOGETHER BEFORE INSERTION.
REHEAT
VALVE ACTUATOR
ML7984B
PWM VALVE ACTUATOR
COM
24 VAC
PWM 24VAC
FROM CNTRL
PWM OUTPUT
T6T5C B W R
****
CONFIGURATION DIP SWITCHES
LOCATED ADJACENT TO INPUT TERMINAL BLOCK ON ML7948B
ON
OFF
Fig. 19. W7751H to PWM Valve Actuator
NOTE: Ensure that all transformer wiring is as shown.
Reversing terminations will result in equipment malfunction.
W7751H
4321
7
EN1B-0279GE51 R0707B
Page 8
EXCEL 10 W7751H SMART VAV ACTUATOR
*
TRIAC
NOT EARTH
GROUND
EQUIVALENT
CIRCUIT
W7751H
LED
GND
BYPASS
SENSOR
SET PT
24VAC
COM
21
EARTH
MODULE
3
4
WALL
5
76
8
OUT1
9 10
OUT2
1112
LON
24VAC COMM IN
REHEAT
VALV E AC TUATO R
ML7984B
PWM VALVE ACTUATOR
COM
24 VAC
PWM 24VAC
FROM CNTRL
PWM OUTPUT
T6T5C B W R
CONTACTOR
(24 VAC)
SERIES OR
PAR ALLE L FAN
*
TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION.
Fig. 20. W7751H to PWM Valve Actuator and series or
parallel fan
Alarms
CARE is used to perform the ID Assignment task. Once ID Assignment has been performed and commissioning has been completed, check the L determine if there are any alarms. Possible alarm causes can be determined by viewing the nvoAlarm e.g. in CARE.
LONW
ORKS
Service LED
The LONW
ORKS
Service LED on the front of the W7751H (see Fig. 2) provides a visual indication of the status of the device. When the W7751H receives power, the LED appears in one of the following allowable states:
1. OFF = no power to the processor.
2. Continuous ON = processor is in initialized state.
3. Slow blink = controlling, normal state.
4. Fast blink = the W7751H has an alarm condition.
When the W7751H has an alarm condition, it reports it to the central node on the L
ONWORKS
10 Zone Manager). Also, the W7751H variables, AlarmLogX, where X is 1 through 5, that store the last five alarms to occur in the controller, are available. These points can be viewed using XBS or the corresponding LNS plug-in. For a description of Excel 10 Alarms, refer to Table 12 of Excel 10 W7751B,D,F,H,J Variable Air Volume Controller – Application Guide (Product Literature No.: 74-2949)
NOTE: The node can be reset by switching the node to
MANUAL and then to the normal operating mode.
ONWORKS
service LED to
® network (typically, the Excel
TRIAC
NOT EARTH
GROUND
EQUIVALENT
CIRCUIT
W7751H
LED
GND
BYPASS
SENSOR
SET PT
24VAC
COM
21
EARTH
MODULE
3
4
WALL
765
8
OUT1
9 10
OUT2
1112
LON
24VAC COMM IN
OPTIONAL 24 VAC WIRING TO NEXT CONTROLLER
*
MMC325 PNEUMATIC
TRANSDUCER
COM
COM
24 VAC
24 VAC
INCREASE
DECREASE
*
M
M
B
USE 1/4 IN. (6 MM) MIN. TUBING. BRANCH LINE MUST BE 6 FT. (1.8 M) OR LONGER.
PNEUMATIC
VALV E
Fig. 21. W7751H to pneumatic transducer
NOTE: Reverse wires (INCREASE/DECREASE) to reverse
action (DIRECT/REVERSE).
T7460 Wall Module Override LED
The remote override LED, located on either the T7460 Wall Module, will display the "manual override" mode of the W7751H. Possible modes are:
1. LED = OFF. No override active.
2. LED = Continuously ON. Bypass mode (timed occupied
override).
3. LED = One flash per second. Continuous unoccupied override.
4. LED = Two flashes per second. Remote only, continuous occupied override.
Step 3. I/O Tests
The W7751H controller must be configured using the LNS plug-in. Once this is done, the W7751H can be commanded to the "manual" mode, and each output and input can be exercised/viewed to verify proper wiring connections and equipment operation.
W7751H Actuator Checkout
To check out the W7751H actuator, determine the direction the damper shaft moves to open the damper (CW or CCW). See Fig. 7.
Connect the W7751H with the laptop PC. To do this, the W7751H must be wired, powered, and connected to the portable PC via the LonTalk adapter. The LonTalk® Adapter connects to the W7751H either directly via the L network or via the T7460-LONJACK (accessory available with the T7460 and T7560 Wall Modules). Using the L
ONWORKS
ONWORKS
®
EN1B-0279GE51 R0707B
8
Page 9
EXCEL 10 W7751H SMART VAV ACTUATOR
tool, you should then drive the W7751H actuator fully open and then closed. Observe the actuator's operation; if the damper is closed, it should begin to open. If the damper is open, it should begin to close.
If no movement is observed, check to see if 24 Vac is present at the W7751H. With proper wiring, with 24 Vac present, and with proper commands from the LNS plug-in, the actuator should operate properly.
Step 4. Verify Sequences of Operation
For the detailed descriptions of the sequences of operation, see Excel 10 W7751B,D,F,H,J Variable Air Volume Controller – Application Guide (Product Literature No.: 74-2949).
Optional Accessories
Spare Parts Kit
Order no.: A7211.2071. Contains:
1 anti-rotation bracket + screws
2 universal terminal blocks
2 strain-relief clamps
2 grommets*
2 adjustable end stops
*In order to guarantee IP54, only original Honeywell grommets may be used.
Table 1. Internal end switches of SSW2
terminal type of switch
S1
S2 / S3
S5 / S6
common lead for switches A and B
change-over switch A (S1/S2 opens and S1/S3 closes when shaft adapter moves CW past 5°; reverts to original state when shaft adapter moves CCW past 5°).
change-over switch B (S1/S5 opens and S1/S6 closes when shaft adapter moves CW past 85°; reverts to original state when shaft adapter moves CCW past 85°).
SSW2 Auxiliary Switch Kit
Fig. 22. Internal end switches of SSW2 (max. 230 V, 5 A)
NOTE: Both internal end switches must be connected to the
same power source.
9
EN1B-0279GE51 R0707B
Page 10
41
85
142
105
76
Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37, Switzerland by its Authorized Representative:
Automation and Control Solutions
Honeywell GmbH Böblinger Straße 17 71101 Schönaich Germany Phone: (49) 7031 63701 Fax: (49) 7031 637493 http://europe.hbc.honeywell.com
Subject to change without notice. Printed in Germany
EN1B-0279GE51 R0707B
103
Fig. 23. Dimensions (in mm)
Loading...