Honeywell W6215, W7215, W7460 Data Sheet

Economizer Logic Modules

APPLICATION

W6215, W7215, W7460
FOR VENTILATION CONTROL
PRODUCT DATA

FEATURES

• Operates from the space thermostat and an ISI to provide a totally integrated control system.
• Solid state control package provides accuracy, reliability and stability.
• Housed in high-impact, glass-fiber reinforced plastic case.
• Mounts on sheet metal duct or remotely in a mechanical room. Mounting screws included.
• The W6215 and W7215 are used with Honeywell Series 62 and Series 72 actuators (respectively). The W7460 is used with Honeywell M7415 Damper Actuators.
• Combines minimum and maximum damper position potentiometers and compressor staging relay functions with solid state enthalpy or dry bulb changeover control this control can be tempered by ISI, and fan cycling.
• Outdoor Sensor input incorporated into logic of W7215B and W7460B models.
• Shutdown and Air Change can be used with all models.
• Purge cycling can be used with the W6215A, W7215A and W7460A models.
• Terminals included for connecting optional S963B1128 Remote Potentiometers for remote minimum and maximum damper position control.
• LED and relay terminals indicate when free cooling is available.
• LED indicates when module is in ISI mode.
® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Operation .......................................................................... 5
Settings and Adjustments ................................................. 6
Checkout and Troubleshooting ......................................... 26
63- 2544- 3
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES

SPECIFICATIONS

Models:
See Table 1.
Dimensions: See Fig. 1.
Electrical Ratings:
Input Voltage: 24 Vac +20%, -15%; 50/60 Hz (Class 2). Nominal Power Consumption (at 24 Vac, 60 Hz):
W6215A: 12.5 VA. W7215A, W7460A: 10 VA. W7215B, W7460B: 10.5 VA.
Relay Contact Rating at 30 Vac (maximum power from class 2
input only): 1.5A run, 3.5A inrush.
Ambient Ratings:
Temperature:
Operating Ambient: -25°F to +125°F (-32°C to +52°C). Shipping: -25°F to +125°F (-32°C to +52°C).
Humidity (Noncondensing): 5 to 95 percent rh.
Inputs:
Enthalpy (C7400): 2-wire (18,20,22 AWG) connection. Dry Bulb Temperature (C7650): 2-wire (18,20,22 AWG)
connection. Discharge Air (C7046): 2-wire (18,20,22 AWG) connection. Mixed Air (C7150): 2-wire (18,20,22 AWG) connection. Indoor Sensor: 2-10 Vdc control signal. Outdoor Sensor (W7215B and W7460B only): 2-10 Vdc
control signal.
Outputs:
W7215: 2-10 Vdc. W6215: Series 62 (Open/Close/Hold). 24 Vac out (W7215, W6215 only): 25 VA maximum.
Accessories:
32004783-001 Weather Shield Economizers. 4074EJM Bag Assembly. Consists of: Checkout jumper,
620 ohm, 1.2K ohm, 5.6K ohm, and 6.8K ohm checkout
resistors, and 536 ohm, 665 ohm, and 3480 ohm resistors
for use with Honeywell Series 90 Actuators. C7046A Discharge Air Temperature Sensor. C7150B Mixed Air Temperature Sensor. C7400 Solid State Enthalpy Sensor. C7650 Dry Bulb Temperature Sensor. S963B1128 Remote Potentiometer to provide remote control
of damper minimum or maximum position. ST6008 Energy Management Timer for occupied/unoccupied
control.
Approvals:
Underwriters Laboratories Inc. listed: Meets UL873
plenum requirements.
3/4 (19)
1
(25)
24VAC
TR Hot
BC
A
Maximum
Position
Open
Free Cool
Mininum Position
Closed
6
2
ISI
Set Pt
ISI
50%
0%
Exhaust
Set Pt
Exhaust
100%
TR1 Com
+
D
So
+
Sr
5
1
2
3
4
T
T1
P
Q
AQ
+
AQ1
10
SD
SD1
AC
AC1
PC
PC1
8-5/8
P1
(219)
Q1
1
(25)
1-9/16
(40)
+
24VAC
Hot
24VAC
Com
2-10V
OUT
Free Cool
Unit
Control Exhaust
Fan
Indoor
Fan
W7215A
5-3/4 (146)
Fig. 1. W6215,W7215,W7460 dimensions
in in. (mm). [W7215A shown]
M11788A
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2544—3 2
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
0
Table 1. W6215, W7215, and W7460 Economizer Models.
For Use
Model
W6215A Honeywell Series 62 C7150B or C7046A Sensor No Adjustable Yes
W7215A Honeywell Series 72 C7150B or C7046A Sensor No Adjustable Yes
W7215B Honeywell Series 72 C7150B or C7046A Sensor Yes Fixed No
W7460A Honeywell M7415 C7150B or C7046A Sensor No Adjustable Yes
W7460B Honeywell M7415 C7150B or C7046A Sensor Yes Fixed No
NOTE: All models include minimum and maximum position potentiometers, setpoint for enthalpy or dry-bulb, and ISI setpoint.
with Actuator
Discharge Air
Temperature Input
Outdoor Sensor
Input (OSI) Setpoint
Exhaust
Fan Setpoint Purge

INSTALLATION

When Installing this Product...

1.
Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2.
Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
IMPORTANT

Location and Mounting

All wiring must agree with applicable codes, ordinances and regulations.
OUTDOOR AIR SENSING
1.
Mount sensor in any orientation that exposes it to freely circulating air and protects it from rain, snow, and direct sunlight.
2. Connect it to the S
RETURN AIR SENSING
1.
Ensure differential enthalpy control has a second sensor in the return air duct.
2. Connect this sensor to the S W6215, W7215, or W7460.
and + terminals of the device.
O
and + terminals of the
R
W6210 A 1003
W6215, W7215, W7460 Economizer Logic Module
W6215, W7215, and W7460 Logic Modules mount directly on a sheet metal duct or panel. When planning the installation, allow enough clearance for maintenance and service. Mount device in a location protected from rain, snow, and direct sunlight. Secure device to sheet metal using the three supplied mounting screws, see Fig. 2.
NOTE: See Fig. 3 for representative locations of connected
system devices.
C7400 Enthalpy Sensor and C7650 Dry Bulb Temperature Sensor
W6215,W7215,W7460 Logic Modules accept signals from either the C7400 Enthalpy Sensor or the C7650 Dry Bulb Temperature Sensor. The wiring is the same for either sensor.
IMPORTANT
When using differential sensing, both sensors must be of the same type (enthalpy or dry bulb).
M1179
Fig. 2. Mounting W6215, W7215, W7460 on sheet metal.
Indoor Sensor Input
The ISI can be any sensor that provides a 2-10 Vdc output. The ISI modulates the outdoor damper to provide ventilation based on occupancy. The designer determines contaminants to monitor, selects appropriate sensor, determines the sensor threshold, and adjusts the ISI potentiometer accordingly. The ISI LED lights when the ISI signal is above setpoint. Mount the sensor according to the manufacturer specifications. If not available, use the following guidelines:
1. Mount sensor in an area with unobstructed air circulation.
2. Connect it to the AQ
W7215, or W7460 (see Wiring section for details).
3. Adjust the ISI potentiometer setpoint to correspond to ISI voltage output at the threshold.
IMPORTANT
Ensure proper polarity of sensor connections. Incorrect polarity negates the sensor signal.
3 63-2544—3
and AQ1 terminals of the W6215,
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
Outdoor Sensor Input (W7215B and W7460B only)
The OSI sensor can be any sensor that provides a 2-10 Vdc output. Mount the sensor according to the manufacturer specifications. If not available, use the following guidelines:
1. Mount sensor in an area with unobstructed air circulation that is protected from rain, snow, and direct sunlight.
DISCHARGE AIR SENSOR
INDOOR FAN
DIRECT EXPANSION COIL
W6215, W7215, OR W7460
C7046A
DISCHARGE AIR
2
C7150B
MIXED AIR SENSOR
C7400
ENTHALPY SENSOR
IMPORTANT
Ensure proper polarity of sensor connections. Incorrect polarity negates the sensor signal.
2. Connect it to the OA or W7460B (see Wiring section for details).
and OA1 terminals of the W7215B,
3. Adjust the OSI potentiometer setpoint to correspond to OSI sensor voltage output at the threshold.
SPACE
2
SERIES 62 OR 72 ACTUATOR
1
THERMOSTAT
1
C7400
OUTDOOR AIR SENSOR
INDOOR AIR SENSOR
ENTHALPY SENSOR
OUTDOOR AIR
FOR DIFFERENTIAL ENTHALPY, THE TWO C7400
1
ENTHALPY SENSORS ARE CONNECTED TO THE W6215/W7215/W7460 ECONOMIZER CONTROL—ONE IS MOUNTED IN RETURN AIR, AND THE OTHER IS MOUNTED IN OUTDOOR AIR. DIFFERENTIAL ENTHALPY CONTROL PROVIDES GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY.
2
USE EITHER MIXED AIR SENSOR OR DISCHARGE AIR SENSOR, NOT BOTH.
Fig. 3. Representative locations of connected Economizer system devices.

Wiring

CAUTION
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
IMPORTANT
1. All wiring must comply with applicable local codes, ordinances and regulations.
2. Refer to Fig. 6 through 25 for typical wiring diagrams.
3. Refer to Table 2 for a list of the wiring diagrams and corresponding Figure numbers in this document.
4. All device inputs and outputs must be 24 Vac Class 2.
NOTE: All connections with label designation ending in 1
(examples: TR1, T1, P1, Q1, AQ1) are ac/dc common connections.
EXHAUST FAN
RETURN AIR
EXHAUST AIR
M11816

Optional Applications

Remote Minimum Position Control
Remote control of outdoor air dampers is desirable when requiring temporary additional ventilation. One potentiometer controls the damper minimum position, another potentiometer controls the damper maximum position. The addition of S963B1128 Remote Potentiometers allows occupants to open or close the dampers beyond minimum position for modified ventilation. Connect the potentiometers as shown in Fig. 4.
IMPORTANT
Free Cool Timing
The Free Cool contacts close while the logic module operates free cooling. Connecting a timer to these contacts allows tracking of the free cooling usage time.
The minimum position signal takes priority to the maximum position signal. With the maximum set below the minimum, the logic module signals the actuator to maintain the minimum position.
63-2544—3 4
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
Table 2. Applicable Wiring Diagrams.
Logic Module Actuator Enthalpy Changeover Figure Comments
W6215A Honeywell Series 62 Single 8 Single-stage cooling system.
Single or Differential 9 Two-stage cooling system.
W7215A Honeywell Series 72 Single 10 Single-stage cooling system.
Single or Differential 11 Two-stage cooling system.
12 T775 controller.
Honeywell Series 90 n/a 6 Add Q7230 Interface Module.
W7215B Honeywell Series 72 Single 13 Single-stage cooling system.
Single or Differential 14 Two-stage cooling system.
15 T775 controller.
W7460A Honeywell M7415 Single 16 Single-stage cooling system.
Single or Differential 17 Two-stage cooling system.
W7460B Honeywell M7415 Single 18 Single-stage cooling system.
Single or Differential 19 Two-stage cooling system.
ALL n/a n/a 20 W7100 controller.
25 W973 Logic Panel.
4 S963 remote damper control.
Parallel Wiring
W6215 Honeywell Series 62 Single or Differential 21 Honeywell Series 62 Direct Coupled Actuators.
W7215A Honeywell Series 72 22 Honeywell Series 72 Direct Coupled Actuators.
23 Honeywell Series 72 Modutrol Motors.
Honeywell M7415 24 M7415 Motors.

OPERATION

The purpose of the economizer is to use outdoor air for cooling, whenever possible, to reduce compressor operation.
When wired as shown in Fig. 6 through 25, the logic module responds to the cooling thermostat signal. This system uses C7400 Solid State Enthalpy Changeover Sensor(s) or C7650 Dry Bulb Temperature Sensor(s). The C7400 responds to both dry bulb temperature and humidity, allowing use of outdoor air at higher temperatures for free cooling when humidity is low. The C7650 responds only to dry bulb temperature; use only in dry, arid climates.
The logic module functions as a true first stage of cooling providing maximum fuel economy during the cooling cycle. It automatically locks out free cooling during heating; holding the outdoor air damper at the minimum position setting.
The logic module can operate as either a basic free cooling controller, or it can incorporate additional functions. Tables 3 and 5 detail the input/output (I/O) logic of the module. Certain functions—Purge, Shutdown, and Air Change—override others, see Table 3. When these functions are all off, the logic module energizes the Unit Control and Indoor Fan contacts, operating according to Table 5.

Purge (W6215A, W7215A, and W7460A only)

When terminals PG and PG1 connect through relay contacts or a jumper:
1. Outdoor damper drives fully closed.
2.
Exhaust fan turns on.
S963B1128 REMOTE
OPEN
MINIMUM POSITION ADJUSTMENT
CW
MAXIMUM POSITION ADJUSTMENT
CW
W6215/W7215/W7460 ECONOMIZER
P1
P
Q1
Q
Fig. 4. S963B1128 Remote Potentiometer used with
W6215, W7215, W7460 for remote damper control.
POTENTIOMETER
R
CCW OPEN
135 OHM
S963B1128 REMOTE POTENTIOMETER
CCW OPEN
135 OHM
CW CLOSE
R
CW CLOSE
M11796A
WB
WB
5 63-2544—3
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
Table 3. W6215, W7215, W7460 Economizer Purge,
Shutdown, and Air Change I/O Logic.
INPUTS OUTPUTS
Purge
Shut-
a
down
Air
Change Damper
Unit
Control
Indoor
Fan Exhaust
On - - Fully Closed Off Off On
Off On - Off
Off On Fully Open On On
a
Purge present only on W6215A, W7215A, and W7460A.

Shutdown

One contact closure shuts down all systems. When terminals SD and SD1 connect through relay contacts or a jumper:
1.
Outdoor damper drives fully closed.
2.
Exhaust fan turns off.
3. Indoor fan turns off.

Air Change

When terminals AC and AC1 connect through relay contacts or a jumper:
1. Outdoor damper drives fully open.
2. Exhaust fan turns on.
3. Indoor fan turns on.
NOTE: With Purge, Shutdown, and Air Change de-
energized, Exhaust will be de-energized unless the signal exceeds the exhaust fan setpoint; other logic module functions remain unaltered.

SETTINGS AND ADJUSTMENTS

Potentiometers with screwdriver adjustment slots, located on the device face, provide adjustments for several parameters (see Fig. 5 for locations on device): — ISI setpoint. — OSI setpoint (W7215B and W7460B only).
— Minimum damper position. — Maximum damper position. — Enthalpy changeover. — Exhaust setpoint (W6215A, W7215A and W7460A only).

Indoor Sensor Input Setpoint

The logic module modulates the outdoor damper to provide ventilation based on the 2-10 Vdc ISI. With no cooling signal, the ISI overrides the outdoor air damper when ventilation requires outdoor air.

Outdoor Sensor Input Setpoint (W7215B and W7460B only)

The OSI logic operates from a 2-10 Vdc sensor signal. The operation of these logic modules is slightly different from the other models, see Table 4.
Table 4. W7215B and W7460B OSI Operation.
OSI ISI Actuator OSI LED Alarm
Below set Below set
Above set
Modulates
Modulates
Modulates
Above set Below set Fully closed On Off
Above set
a
Modulation based on signal from mixed air sensor.
b
With ISI signal greater than mixed air sensor signal:
Modulates
Modulation, based on ISI signal, between minimum and maximum positions.
c
With ISI signal less than mixed air sensor signal: Modulation, based on mixed air sensor signal, between: M7215B: Minimum and full open positions M7460B: Minimum and maximum positions.
d
Modulation based on mixed air sensor signal; connect to energize warning light, audio alarm, or air cleaner.
a
Off Off
b
c
d
On On
Alarm
terminals
Table 5. W6215, W7215, W7460 Economizer I/O Logic.
INPUTS OUTPUTS
a
Y1
b
Y2
b
Damper
Compressor
On Off On Off
Modulating
c
On Off
ISI
Below set (ISI LED Off)
Enthalpy
Outdoor Return 1 2
High (Free Cooling LED Off) Low On On Minimum position On On
Low (Free Cooling LED On) High On On
On Off Off Off
Above set (ISI LED On)
High (Free Cooling LED Off) Low On On
On Off On Off
Low (Free Cooling LED On) High On On
Modulating
Modulating
d
e
On On
On Off
On Off Off Off
a
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
b
If both stages of cooling are off, the system is off and the damper is at: • Minimum position if ISI is below setpoint.
c
W6215, W7460: Modulation, based on the mixed air sensor signal, between minimum and maximum positions. W7215: Modulation, based on the mixed air sensor signal, between minimum and full-open positions.
d
Modulation, based on the ISI, between minimum and maximum positions.
e
Modulation, based on the greater of ISI and mixed air sensor signals, between minimum and either maximum position (ISI) or
• Modulating if ISI is above setpoint.
fully open (mixed air signal).
NOTE: Each sensor has it’s own setpoint for threshold and LED indication.
63-2544—3 6
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
T
24VAC
24VAC
Hot
24VAC
Com
+
2-10V
OUT
Free Cool
Unit
Control Exhaust
Fan
Indoor
Fan
LED LIGHTS WHEN EXHAUST IS ON
W7215A
TR Hot
BC
A
Mininum Position
Open
Free Cool Maximum
Position
Closed
2
ISI
Set Pt
ISI
50%
0% Exhaust
Set Pt
Exhaust
TR1 Com
+
D
So
+
Sr
5
1
2
3
4
T
T1
P
P1
Q
Q1
AQ
6
+
AQ1
Q
10
SD
SD1
AC
AC1
Q
PG
PG1
Q
100%
Fig. 5. Potentiometer and LED locations.
ENTHALPY CHANGEOVER SETPOINT
MINIMUM DAMPER POSITION SETTING
LED LIGHTS WHEN OUTDOOR AIR IS SUITABLE FOR FREE COOLING
MAXIMUM DAMPER POSITION SETTING
INDOOR AIR SENSOR SETPOINT
LED LIGHTS WHEN INDOOR SENSOR INPU IS ABOVE SETPOINT
EXHAUST FAN SETPOINT
M11787A
NOTE: Make minimum position adjustments with at least a
10°F [6°C] temperature difference between outdoor and return air.
1. Calculate the appropriate mixed air temperature, see Equation 1.
2. Disconnect mixed air sensor from terminals T and T1.
3. Ensure that either the factory-installed jumper is in
place across terminals P and P1 or, of remote damper position is required, that it is wired according to Fig. 4 and turned fully clockwise.
4.
Connect 24 Vac across terminals TR and TR1.
5. Carefully adjust the potentiometer on the face of the device with a small screwdriver until the mixed air temperature reaches the calculated value.
NOTE: Ensure that the sensed air is well mixed.
Equation 1. Formula to aid in minimum position
adjustment.
TOOA×()TRRA×()+ TM=
Where: TO = Outdoor air temperature OA = Percent of outdoor air
= Return air temperature
T
R
RA = Percent of return air
= Resulting mixed air temperature
T
M
IMPORTANT
This procedure requires use of a quality thermometer capable of reading to 0.5°F [0.25°C].

Adjusting Minimum and Maximum Positions

The minimum position potentiometer maintains the minimum outdoor air flow into the building during occupied period. The maximum position potentiometer allows the installer to limit the amount of outdoor air flow into the building, when the ISI overrides the mixed air sensor. Setting the maximum position of the damper prevents the introduction of large amounts of hot or cold air into the space.
IMPORTANT
NOTES:
Minimum Position Adjustment
For detailed assistance in minimum position selection reference the Economizer Application Guide (form 63-8594) Ventilation section. The following provides basic guidelines for minimum position selection and adjustment:
IMPORTANT
With the maximum position set below the minimum position, the minimum position overrides the maximum position (negating most functions of the logic module, as the damper cannot move).
When the mixed air sensor takes control, it
overrides the maximum position potentiometer.
If mixed air temperature drops to 40°F, the mixed
air sensor overrides the ISI and closes the damper to minimum position to protect from freezing the hot or chilled water coils. Control returns to normal once the mixed air temperature rises to 43°F.
Adjust the minimum position potentiometer to allow the minimum amount of outdoor air, as required by local codes, to enter the building.
NOTE: The following sample calculation uses only
Fahrenheit temperature.
EXAMPLE: Assume local codes require 10% outdoor air
during occupied conditions, outdoor air is 60°F and return air is 75°F. Under these conditions, what is the temperature of the mixed air?
0.1 60°F×()0.9 75°F×()+ 6.0°F 67.5°F+ 73.5°F==
Mixed air will be 73.5°F when OA is 60°F and RA is 75°F with 10 percent outdoor air entering the building.
Maximum Position Adjustment
1. Disconnect mixed air sensor from terminals T and T1 and short terminals T and T1.
2. Make sure either the factory-installed jumper is in place across terminals Q and Q1 or, if remote damper position is required, that it is wired according to Fig. 4 and turned fully clockwise.
3. Connect 24 Vac across terminals TR and TR1.
4. Adjust the potentiometer on the face of the device with a
screwdriver for desired maximum position.

Enthalpy Changeover

Outdoor Enthalpy Changeover Setpoint
The outdoor enthalpy changeover setpoint returns the outdoor air damper to minimum position when enthalpy rises above its setpoint. Enthalpy setpoint scale markings, located in the device, are A, B, C, and D. See Fig. 7 for the corresponding control point. The factory-installed 620-ohm jumper must be in place across terminals S
and +.
R
7 63-2544—3
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
85
100
105
110
)
0
)
Differential Enthalpy Changeover Setting
Differential enthalpy control uses two C7400 Enthalpy Sensors connected to one logic module. The logic module compares outdoor air to return air instead of to a setpoint as it does for single enthalpy. Turn the setpoint potentiometer fully clockwise to the D setting. The logic module selects the lower enthalpy air (return or outdoor) for cooling; for example, when outdoor air has lower enthalpy than return air, the outdoor air damper opens to bring in outdoor air for free cooling.

Exhaust Setpoint

Except for Purge, Shutdown, and Air Change, the exhaust setpoint determines when the exhaust fan runs based on the damper position. When the ISI call for exhaust comes, the module provides a 45 ±15 second delay before exhaust fan activation. This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload.

Adjustable Exhaust Setpoint (W6215A, W7215A, and W7460A only)

The W6215A, W7215A, and W7460A Logic Modules have an adjustable setpoint. This potentiometer allows the installer to set the exhaust setpoint at an actual damper position percentage open from fully closed.

Fixed Exhaust Setpoint (W7215B and W7460B)

The W7215B and W7460B Logic Modules have a fixed exhaust setpoint. The logic module uses an exhaust setpoint of 60 percent. When the damper reaches 60 percent open (from fully closed), the logic module calls for exhaust.
W7215A
HONEYWELL SERIES 90 ACTUATOR
(ML9175, ML9185, M9175, M9185)
1
M11903A
W
R
1
B
USE 1/2 WATT, 1% RESISTORS OF SPECIFIED OHM RATINGS (INCLUDED IN 4074EJM RESISTOR KIT). FOR MOD IV MOTORS, THE Q7230 MODULE CAN REPLACE THE RESISTORS.
665 Ohms
3480 Ohms
536 Ohms
Fig. 6. W7215A used with Honeywell Series 90 Actuator.
24 VAC HOT 24 VAC COM
+
2-10V OUT
TR
TR1
CONTROL
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
CURVE
A
B C D
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17)
ENTHALPY—BTU PER POUND DRY AIR
60
(16)
55
(13)
B
50
C
(10)
45
D
(7) 40 (4)
35 (2)
75
(24)
70
(21)
100
90
65
(18)
80
70
A
80
(27)
60
50
(29)90(32)95(35)
RELATIVE HUMIDITY (%)
40
30
(38)
20
(41)
(43
10
35
40
45
50
(2)
(4)
(7)
(10)
55
(13)
APPROXIMATE DRY BULB TEMPERATURE—°F (°C)
Fig. 7. W6215, W7210, and W7460/C7400 performance characteristics for enthalpy changeover settings.
63-2544—3 8
60
(16)
65
(18)
70
(21)
A
B
C
D
105
75
80
(24)
85
(27)
(29)90(32)95(35)
100 (38)
(41)
(43
M11806
11
HONEYWELL
SERIES 62
ACTUATOR
(ML6275,
ML6285,
M6275,
M6285)
24 VAC HOT 24 VAC COM
CLOSE
OPEN
W6215A
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
TR1
TR
C7400 OUTDOOR
+
S
O
+
S
R
620 OHM RESISTOR
5
6
9
+
AIR ENTHALPY
S
SENSOR
500 OHM
W2
1S
OPEN
WIPER
CLOSED
5
Y1
Y2
4
1S1
MINIMUM POSITION ADJUSTMENT
MAXIMUM
FREE
POSITION
COOL
ADJUSTMENT
UNIT CONTROL
EXHAUST FAN
INDOOR FAN
T6031 AMBIENT
W
LOCKOUT CONTROL
R
50 F SETPOINT
1K
2K
1
3
T
P
Q
AQ
SD
AC
PG
2
4
T1
P1
Q1
AQ1
SD1
AC1
PG1
C7150B MIXED AIR OR C7046A DISCHARGE AIR SENSOR
2-10 VDC INDOOR AIR SENSOR
+
SHUT DOWN
AIR CHANGE
PURGE
Y1
W2
9
8
UNOCCUPIED
ST6008 TIMER
OCCUPIED
C
COOL 1
HEAT 2
2
HEAT 1
FAN DELAY RELAY
FAN
M11803A
3
L2 L1
(HOT)
1
W1
G
RH
RC
7
X
T7300 OR T874 THERMOSTAT
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
3
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED
4
BY A 24 VAC INPUT.
5
THE COMMON FOR THE W6215A IS DIFFERENT THAN THE COMMON (WIPER) FOR THE SERIES 62 ACTUATORS. BE SURE TO CONNECT EACH TO A DIFFERENT CIRCUIT.
W1
FDR
G
FDR
R
HVAC EQUIPMENT TERMINAL STRIP
6
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
7
FOR T7300 ONLY.
8
FOR T7300, USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER.
9
FOR TWO-STAGE THERMOSTATS ONLY.
Fig. 8. W6215A used in single-stage cooling system with single enthalpy changeover and Honeywell Series 62 Actuator.
9 63-2544—3
Loading...
+ 19 hidden pages