W6215, W7215, and W7460 Economizer Logic Modules are
used with an indoor sensor input (ISI), and solid state C7400
Enthalpy Sensors or C7650 Dry Bulb Temperature Sensors.
All models proportion outdoor and return air dampers for
control of free cooling in commercial HVAC equipment. The
W7215B and W7460B are used with an outdoor sensor input
(OSI) along with the ISI.
W6215, W7215, W7460
FOR VENTILATION CONTROL
PRODUCT DATA
FEATURES
• Operates from the space thermostat and an ISI to
provide a totally integrated control system.
• Solid state control package provides accuracy,
reliability and stability.
• Housed in high-impact, glass-fiber reinforced
plastic case.
• Mounts on sheet metal duct or remotely in a
mechanical room. Mounting screws included.
• The W6215 and W7215 are used with Honeywell
Series 62 and Series 72 actuators (respectively).
The W7460 is used with Honeywell M7415 Damper
Actuators.
• Combines minimum and maximum damper position
potentiometers and compressor staging relay
functions with solid state enthalpy or dry bulb
changeover control this control can be tempered
by ISI, and fan cycling.
• Outdoor Sensor input incorporated into logic of
W7215B and W7460B models.
• Shutdown and Air Change can be used with all
models.
• Purge cycling can be used with the W6215A, W7215A
and W7460A models.
• Terminals included for connecting optional S963B1128
Remote Potentiometers for remote minimum and
maximum damper position control.
• LED and relay terminals indicate when free cooling
is available.
620 ohm, 1.2K ohm, 5.6K ohm, and 6.8K ohm checkout
resistors, and 536 ohm, 665 ohm, and 3480 ohm resistors
for use with Honeywell Series 90 Actuators.
C7046A Discharge Air Temperature Sensor.
C7150B Mixed Air Temperature Sensor.
C7400 Solid State Enthalpy Sensor.
C7650 Dry Bulb Temperature Sensor.
S963B1128 Remote Potentiometer to provide remote control
of damper minimum or maximum position.
ST6008 Energy Management Timer for occupied/unoccupied
control.
Approvals:
Underwriters Laboratories Inc. listed: Meets UL873
plenum requirements.
3/4 (19)
1
(25)
24VAC
TR Hot
BC
A
Maximum
Position
Open
Free Cool
Mininum
Position
Closed
6
2
ISI
Set Pt
ISI
50%
0%
Exhaust
Set Pt
Exhaust
100%
TR1
Com
+
D
So
+
Sr
5
1
2
3
4
T
T1
P
Q
AQ
+
AQ1
10
SD
SD1
AC
AC1
PC
PC1
8-5/8
P1
(219)
Q1
–
1
(25)
1-9/16
(40)
+
–
24VAC
Hot
24VAC
Com
2-10V
OUT
Free
Cool
Unit
Control
Exhaust
Fan
Indoor
Fan
W7215A
5-3/4 (146)
Fig. 1. W6215,W7215,W7460 dimensions
in in. (mm). [W7215A shown]
M11788A
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2544—32
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
0
Table 1. W6215, W7215, and W7460 Economizer Models.
For Use
Model
W6215AHoneywell Series 62C7150B or C7046A Sensor NoAdjustableYes
W7215AHoneywell Series 72C7150B or C7046A Sensor NoAdjustableYes
W7215BHoneywell Series 72C7150B or C7046A Sensor YesFixedNo
W7460AHoneywell M7415C7150B or C7046A Sensor NoAdjustableYes
W7460BHoneywell M7415C7150B or C7046A Sensor YesFixedNo
NOTE: All models include minimum and maximum position potentiometers, setpoint for enthalpy or dry-bulb, and ISI setpoint.
with Actuator
Discharge Air
Temperature Input
Outdoor Sensor
Input (OSI) Setpoint
Exhaust
Fan SetpointPurge
INSTALLATION
When Installing this Product...
1.
Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
2.
Check the ratings given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
Location and Mounting
All wiring must agree with applicable codes,
ordinances and regulations.
OUTDOOR AIR SENSING
1.
Mount sensor in any orientation that exposes it to freely
circulating air and protects it from rain, snow, and direct
sunlight.
2. Connect it to the S
RETURN AIR SENSING
1.
Ensure differential enthalpy control has a second
sensor in the return air duct.
2. Connect this sensor to the S
W6215, W7215, or W7460.
and + terminals of the device.
O
and + terminals of the
R
W6210 A 1003
W6215, W7215, W7460 Economizer Logic Module
W6215, W7215, and W7460 Logic Modules mount directly on
a sheet metal duct or panel. When planning the installation,
allow enough clearance for maintenance and service. Mount
device in a location protected from rain, snow, and direct
sunlight. Secure device to sheet metal using the three supplied
mounting screws, see Fig. 2.
NOTE: See Fig. 3 for representative locations of connected
system devices.
C7400 Enthalpy Sensor and
C7650 Dry Bulb Temperature Sensor
W6215,W7215,W7460 Logic Modules accept signals from
either the C7400 Enthalpy Sensor or the C7650 Dry Bulb
Temperature Sensor. The wiring is the same for either sensor.
IMPORTANT
When using differential sensing, both sensors must
be of the same type (enthalpy or dry bulb).
M1179
Fig. 2. Mounting W6215, W7215, W7460 on sheet metal.
Indoor Sensor Input
The ISI can be any sensor that provides a 2-10 Vdc output.
The ISI modulates the outdoor damper to provide ventilation
based on occupancy. The designer determines contaminants
to monitor, selects appropriate sensor, determines the sensor
threshold, and adjusts the ISI potentiometer accordingly. The
ISI LED lights when the ISI signal is above setpoint. Mount the
sensor according to the manufacturer specifications. If not
available, use the following guidelines:
1. Mount sensor in an area with unobstructed air circulation.
2. Connect it to the AQ
W7215, or W7460 (see Wiring section for details).
3. Adjust the ISI potentiometer setpoint to correspond to
ISI voltage output at the threshold.
IMPORTANT
Ensure proper polarity of sensor connections.
Incorrect polarity negates the sensor signal.
363-2544—3
and AQ1 terminals of the W6215,
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
Outdoor Sensor Input (W7215B and W7460B only)
The OSI sensor can be any sensor that provides a 2-10 Vdc
output. Mount the sensor according to the manufacturer
specifications. If not available, use the following guidelines:
1. Mount sensor in an area with unobstructed air circulation
that is protected from rain, snow, and direct sunlight.
DISCHARGE
AIR SENSOR
INDOOR
FAN
DIRECT
EXPANSION
COIL
W6215,
W7215,
OR
W7460
C7046A
DISCHARGE
AIR
2
C7150B
MIXED AIR
SENSOR
C7400
ENTHALPY
SENSOR
IMPORTANT
Ensure proper polarity of sensor connections.
Incorrect polarity negates the sensor signal.
2. Connect it to the OA
or W7460B (see Wiring section for details).
and OA1 terminals of the W7215B,
3. Adjust the OSI potentiometer setpoint to correspond to
OSI sensor voltage output at the threshold.
SPACE
2
SERIES
62 OR 72
ACTUATOR
1
THERMOSTAT
1
C7400
OUTDOOR
AIR
SENSOR
INDOOR
AIR
SENSOR
ENTHALPY
SENSOR
OUTDOOR
AIR
FOR DIFFERENTIAL ENTHALPY, THE TWO C7400
1
ENTHALPY SENSORS ARE CONNECTED TO THE
W6215/W7215/W7460 ECONOMIZER CONTROL—ONE
IS MOUNTED IN RETURN AIR, AND THE OTHER IS
MOUNTED IN OUTDOOR AIR. DIFFERENTIAL
ENTHALPY CONTROL PROVIDES GREATER
ENERGY SAVINGS THAN SINGLE ENTHALPY.
2
USE EITHER MIXED AIR SENSOR OR DISCHARGE
AIR SENSOR, NOT BOTH.
Fig. 3. Representative locations of connected Economizer system devices.
Wiring
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
Disconnect power supply before installation.
IMPORTANT
1. All wiring must comply with applicable local codes,
ordinances and regulations.
2. Refer to Fig. 6 through 25 for typical wiring diagrams.
3. Refer to Table 2 for a list of the wiring diagrams and
corresponding Figure numbers in this document.
4. All device inputs and outputs must be 24 Vac Class 2.
NOTE: All connections with label designation ending in 1
(examples: TR1, T1, P1, Q1, AQ1) are ac/dc
common connections.
EXHAUST
FAN
RETURN AIR
EXHAUST AIR
M11816
Optional Applications
Remote Minimum Position Control
Remote control of outdoor air dampers is desirable when
requiring temporary additional ventilation. One potentiometer
controls the damper minimum position, another potentiometer
controls the damper maximum position. The addition of
S963B1128 Remote Potentiometers allows occupants to open
or close the dampers beyond minimum position for modified
ventilation. Connect the potentiometers as shown in Fig. 4.
IMPORTANT
Free Cool Timing
The Free Cool contacts close while the logic module operates
free cooling. Connecting a timer to these contacts allows
tracking of the free cooling usage time.
The minimum position signal takes priority to the
maximum position signal. With the maximum set
below the minimum, the logic module signals the
actuator to maintain the minimum position.
W6215Honeywell Series 62 Single or Differential21Honeywell Series 62 Direct Coupled Actuators.
W7215AHoneywell Series 7222Honeywell Series 72 Direct Coupled Actuators.
23Honeywell Series 72 Modutrol Motors.
Honeywell M741524M7415 Motors.
OPERATION
The purpose of the economizer is to use outdoor air for
cooling, whenever possible, to reduce compressor operation.
When wired as shown in Fig. 6 through 25, the logic module
responds to the cooling thermostat signal. This system
uses C7400 Solid State Enthalpy Changeover Sensor(s) or
C7650 Dry Bulb Temperature Sensor(s). The C7400 responds
to both dry bulb temperature and humidity, allowing use of
outdoor air at higher temperatures for free cooling when
humidity is low. The C7650 responds only to dry bulb
temperature; use only in dry, arid climates.
The logic module functions as a true first stage of cooling
providing maximum fuel economy during the cooling cycle.
It automatically locks out free cooling during heating; holding
the outdoor air damper at the minimum position setting.
The logic module can operate as either a basic free cooling
controller, or it can incorporate additional functions. Tables 3
and 5 detail the input/output (I/O) logic of the module. Certain
functions—Purge, Shutdown, and Air Change—override
others, see Table 3. When these functions are all off, the logic
module energizes the Unit Control and Indoor Fan contacts,
operating according to Table 5.
Purge (W6215A, W7215A, and W7460A only)
When terminals PG and PG1 connect through relay contacts
or a jumper:
1. Outdoor damper drives fully closed.
2.
Exhaust fan turns on.
S963B1128 REMOTE
OPEN
MINIMUM
POSITION
ADJUSTMENT
CW
MAXIMUM
POSITION
ADJUSTMENT
CW
W6215/W7215/W7460 ECONOMIZER
P1
P
Q1
Q
Fig. 4. S963B1128 Remote Potentiometer used with
W6215, W7215, W7460 for remote damper control.
POTENTIOMETER
R
CCW
OPEN
135 OHM
S963B1128 REMOTE
POTENTIOMETER
CCW
OPEN
135 OHM
CW
CLOSE
R
CW
CLOSE
M11796A
WB
WB
563-2544—3
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
Table 3. W6215, W7215, W7460 Economizer Purge,
Shutdown, and Air Change I/O Logic.
INPUTSOUTPUTS
Purge
Shut-
a
down
Air
ChangeDamper
Unit
Control
Indoor
FanExhaust
On--Fully Closed OffOffOn
OffOn-Off
OffOnFully OpenOnOn
a
Purge present only on W6215A, W7215A, and W7460A.
Shutdown
One contact closure shuts down all systems. When terminals
SD and SD1 connect through relay contacts or a jumper:
1.
Outdoor damper drives fully closed.
2.
Exhaust fan turns off.
3. Indoor fan turns off.
Air Change
When terminals AC and AC1 connect through relay contacts
or a jumper:
1. Outdoor damper drives fully open.
2. Exhaust fan turns on.
3. Indoor fan turns on.
NOTE: With Purge, Shutdown, and Air Change de-
energized, Exhaust will be de-energized unless the
signal exceeds the exhaust fan setpoint; other logic
module functions remain unaltered.
SETTINGS AND ADJUSTMENTS
Potentiometers with screwdriver adjustment slots, located on
the device face, provide adjustments for several parameters
(see Fig. 5 for locations on device):
— ISI setpoint.
— OSI setpoint (W7215B and W7460B only).
— Minimum damper position.
— Maximum damper position.
— Enthalpy changeover.
— Exhaust setpoint (W6215A, W7215A and W7460A only).
Indoor Sensor Input Setpoint
The logic module modulates the outdoor damper to provide
ventilation based on the 2-10 Vdc ISI. With no cooling signal,
the ISI overrides the outdoor air damper when ventilation
requires outdoor air.
Outdoor Sensor Input Setpoint
(W7215B and W7460B only)
The OSI logic operates from a 2-10 Vdc sensor signal. The
operation of these logic modules is slightly different from the
other models, see Table 4.
Table 4. W7215B and W7460B OSI Operation.
OSIISIActuatorOSI LEDAlarm
Below set Below set
Above set
Modulates
Modulates
Modulates
Above set Below set Fully closed OnOff
Above set
a
Modulation based on signal from mixed air sensor.
b
With ISI signal greater than mixed air sensor signal:
Modulates
Modulation, based on ISI signal, between minimum and
maximum positions.
c
With ISI signal less than mixed air sensor signal:
Modulation, based on mixed air sensor signal, between:
M7215B: Minimum and full open positions
M7460B: Minimum and maximum positions.
d
Modulation based on mixed air sensor signal;
connect to energize warning light, audio alarm, or air cleaner.
High (Free Cooling LED Off)LowOnOnMinimum position OnOn
Low (Free Cooling LED On)HighOnOn
OnOffOffOff
Above set
(ISI LED On)
High (Free Cooling LED Off)LowOnOn
OnOffOnOff
Low (Free Cooling LED On)HighOnOn
Modulating
Modulating
d
e
OnOn
OnOff
OnOffOffOff
a
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
b
If both stages of cooling are off, the system is off and the damper is at:• Minimum position if ISI is below setpoint.
c
W6215, W7460: Modulation, based on the mixed air sensor signal, between minimum and maximum positions.
W7215: Modulation, based on the mixed air sensor signal, between minimum and full-open positions.
d
Modulation, based on the ISI, between minimum and maximum positions.
e
Modulation, based on the greater of ISI and mixed air sensor signals, between minimum and either maximum position (ISI) or
• Modulating if ISI is above setpoint.
fully open (mixed air signal).
NOTE: Each sensor has it’s own setpoint for threshold and LED indication.
63-2544—36
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
T
24VAC
24VAC
Hot
24VAC
Com
+
2-10V
OUT
–
Free
Cool
Unit
Control
Exhaust
Fan
Indoor
Fan
LED LIGHTS WHEN EXHAUST IS ON
W7215A
TR Hot
BC
A
Mininum
Position
Open
Free Cool
Maximum
Position
Closed
2
ISI
Set Pt
ISI
50%
0%
Exhaust
Set Pt
Exhaust
TR1
Com
+
D
So
+
Sr
5
1
2
3
4
T
T1
P
P1
Q
Q1
AQ
6
+
AQ1
–
Q
10
SD
SD1
AC
AC1
Q
PG
PG1
Q
100%
Fig. 5. Potentiometer and LED locations.
ENTHALPY
CHANGEOVER
SETPOINT
MINIMUM
DAMPER
POSITION
SETTING
LED LIGHTS
WHEN
OUTDOOR
AIR IS
SUITABLE
FOR FREE
COOLING
MAXIMUM
DAMPER
POSITION
SETTING
INDOOR AIR
SENSOR
SETPOINT
LED LIGHTS
WHEN INDOOR
SENSOR INPU
IS ABOVE
SETPOINT
EXHAUST
FAN
SETPOINT
M11787A
NOTE: Make minimum position adjustments with at least a
10°F [6°C] temperature difference between outdoor
and return air.
1. Calculate the appropriate mixed air temperature, see
Equation 1.
2. Disconnect mixed air sensor from terminals T and T1.
3. Ensure that either the factory-installed jumper is in
place across terminals P and P1 or, of remote damper
position is required, that it is wired according to Fig. 4
and turned fully clockwise.
4.
Connect 24 Vac across terminals TR and TR1.
5. Carefully adjust the potentiometer on the face of the
device with a small screwdriver until the mixed air
temperature reaches the calculated value.
NOTE: Ensure that the sensed air is well mixed.
Equation 1. Formula to aid in minimum position
adjustment.
TOOA×()TRRA×()+TM=
Where:
TO = Outdoor air temperature
OA = Percent of outdoor air
= Return air temperature
T
R
RA = Percent of return air
= Resulting mixed air temperature
T
M
IMPORTANT
This procedure requires use of a quality thermometer
capable of reading to 0.5°F [0.25°C].
Adjusting Minimum and Maximum Positions
The minimum position potentiometer maintains the minimum
outdoor air flow into the building during occupied period. The
maximum position potentiometer allows the installer to limit
the amount of outdoor air flow into the building, when the ISI
overrides the mixed air sensor. Setting the maximum position
of the damper prevents the introduction of large amounts of
hot or cold air into the space.
IMPORTANT
NOTES:
Minimum Position Adjustment
For detailed assistance in minimum position selection
reference the Economizer Application Guide (form 63-8594)
Ventilation section. The following provides basic guidelines for
minimum position selection and adjustment:
IMPORTANT
With the maximum position set below the minimum
position, the minimum position overrides the
maximum position (negating most functions of the
logic module, as the damper cannot move).
—When the mixed air sensor takes control, it
overrides the maximum position potentiometer.
—If mixed air temperature drops to 40°F, the mixed
air sensor overrides the ISI and closes the damper
to minimum position to protect from freezing the
hot or chilled water coils. Control returns to normal
once the mixed air temperature rises to 43°F.
Adjust the minimum position potentiometer to allow
the minimum amount of outdoor air, as required by
local codes, to enter the building.
NOTE: The following sample calculation uses only
Fahrenheit temperature.
EXAMPLE: Assume local codes require 10% outdoor air
during occupied conditions, outdoor air is 60°F
and return air is 75°F. Under these conditions,
what is the temperature of the mixed air?
0.160°F×()0.9 75°F×()+6.0°F 67.5°F+73.5°F==
Mixed air will be 73.5°F when OA is 60°F and RA is 75°F with
10 percent outdoor air entering the building.
Maximum Position Adjustment
1. Disconnect mixed air sensor from terminals T and T1
and short terminals T and T1.
2. Make sure either the factory-installed jumper is in place
across terminals Q and Q1 or, if remote damper position
is required, that it is wired according to Fig. 4 and turned
fully clockwise.
3. Connect 24 Vac across terminals TR and TR1.
4. Adjust the potentiometer on the face of the device with a
screwdriver for desired maximum position.
Enthalpy Changeover
Outdoor Enthalpy Changeover Setpoint
The outdoor enthalpy changeover setpoint returns the outdoor
air damper to minimum position when enthalpy rises above its
setpoint. Enthalpy setpoint scale markings, located in the
device, are A, B, C, and D. See Fig. 7 for the corresponding
control point. The factory-installed 620-ohm jumper must be in
place across terminals S
and +.
R
763-2544—3
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
85
100
105
110
)
0
)
Differential Enthalpy Changeover Setting
Differential enthalpy control uses two C7400 Enthalpy
Sensors connected to one logic module. The logic module
compares outdoor air to return air instead of to a setpoint as it
does for single enthalpy. Turn the setpoint potentiometer fully
clockwise to the D setting. The logic module selects the lower
enthalpy air (return or outdoor) for cooling; for example, when
outdoor air has lower enthalpy than return air, the outdoor air
damper opens to bring in outdoor air for free cooling.
Exhaust Setpoint
Except for Purge, Shutdown, and Air Change, the exhaust
setpoint determines when the exhaust fan runs based on the
damper position. When the ISI call for exhaust comes, the
module provides a 45 ±15 second delay before exhaust fan
activation. This delay allows the damper to reach the
appropriate position to avoid unnecessary fan overload.
Adjustable Exhaust Setpoint
(W6215A, W7215A, and W7460A only)
The W6215A, W7215A, and W7460A Logic Modules have an
adjustable setpoint. This potentiometer allows the installer to
set the exhaust setpoint at an actual damper position
percentage open from fully closed.
Fixed Exhaust Setpoint (W7215B and W7460B)
The W7215B and W7460B Logic Modules have a fixed
exhaust setpoint. The logic module uses an exhaust setpoint
of 60 percent. When the damper reaches 60 percent open
(from fully closed), the logic module calls for exhaust.
W7215A
HONEYWELL
SERIES 90
ACTUATOR
(ML9175,
ML9185,
M9175,
M9185)
1
M11903A
W
R
1
B
USE 1/2 WATT, 1% RESISTORS OF
SPECIFIED OHM RATINGS (INCLUDED
IN 4074EJM RESISTOR KIT). FOR
MOD IV MOTORS, THE Q7230 MODULE
CAN REPLACE THE RESISTORS.
665
Ohms
3480
Ohms
536
Ohms
Fig. 6. W7215A used with Honeywell Series 90 Actuator.
Fig. 7. W6215, W7210, and W7460/C7400 performance characteristics for enthalpy changeover settings.
63-2544—38
60
(16)
65
(18)
70
(21)
A
B
C
D
105
75
80
(24)
85
(27)
(29)90(32)95(35)
100
(38)
(41)
(43
M11806
11
HONEYWELL
SERIES 62
ACTUATOR
(ML6275,
ML6285,
M6275,
M6285)
24 VAC HOT
24 VAC COM
CLOSE
OPEN
W6215A
W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
TR1
TR
C7400
OUTDOOR
+
S
O
+
S
R
620 OHM
RESISTOR
5
6
9
+
AIR
ENTHALPY
S
SENSOR
500 OHM
W2
1S
OPEN
WIPER
CLOSED
5
Y1
Y2
4
1S1
MINIMUM POSITION
ADJUSTMENT
MAXIMUM
FREE
POSITION
COOL
ADJUSTMENT
UNIT
CONTROL
EXHAUST
FAN
INDOOR
FAN
T6031 AMBIENT
W
LOCKOUT
CONTROL
R
50 F SETPOINT
1K
2K
1
3
T
P
Q
AQ
SD
AC
PG
2
4
T1
P1
Q1
AQ1
SD1
AC1
PG1
C7150B MIXED
AIR OR
C7046A
DISCHARGE
AIR SENSOR
2-10 VDC
INDOOR AIR
SENSOR
+
SHUT DOWN
AIR CHANGE
PURGE
Y1
W2
9
8
UNOCCUPIED
ST6008
TIMER
OCCUPIED
C
COOL 1
HEAT 2
2
HEAT 1
FAN
DELAY
RELAY
FAN
M11803A
3
L2
L1
(HOT)
1
W1
G
RH
RC
7
X
T7300 OR T874
THERMOSTAT
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
3
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA
LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED
4
BY A 24 VAC INPUT.
5
THE COMMON FOR THE W6215A IS DIFFERENT THAN THE
COMMON (WIPER) FOR THE SERIES 62 ACTUATORS. BE SURE
TO CONNECT EACH TO A DIFFERENT CIRCUIT.
W1
FDR
G
FDR
R
HVAC EQUIPMENT
TERMINAL STRIP
6
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE
REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING
THERMOSTATS.
7
FOR T7300 ONLY.
8
FOR T7300, USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER.
9
FOR TWO-STAGE THERMOSTATS ONLY.
Fig. 8. W6215A used in single-stage cooling system with single enthalpy changeover and Honeywell Series 62 Actuator.
963-2544—3
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.