Honeywell W7340, W7345 User Manual

W7340, W7345
W7340
W7345
Communicating Economizer Logic Modules
FOR VENTILATION CONTROL
PRODUCT DATA

FEATURES

• Solid state control package provides accuracy, reliability and stability.
• Housed in high-impact, glass-fiber reinforced plastic case.
• Terminals included for connecting optional S963B1136 Remote Potentiometer for remote minimum damper position control.
• Communicates using a modified Modbus protocol.
• Case matches the lines of the M7215 Damper Motor.
• LED indicates the status of the device input.

W7340 Only

APPLICATION

The W7340 Communicating Economizer Logic Module is a full featured economizer that incorporates Demand Control Ventilation (DCV) to provide free cooling and ventilation for occupants in a space while saving energy.
The W7345 Communicating Economizer Logic Module is a dry bulb only economizer that does not incorporate Demand Control Ventilation.
The W7340 is used with both solid state temperature and humidity or enthalpy sensors. The W7345 is used with solid state temperature sensors only.
• Operates from the Modbus input, environmental sensors, and a DCV sensor to provide a totally integrated control system.
• Combines minimum damper position potentiometer with solid state temperature (10K NTC) and humidity or enthalpy changeover control to provide economizer free cooling function; this control can be overridden by input via Modbus or DCV sensor.

W7345 Only

• Operates from the Modbus input and mixed/discharge air sensor to provide a temperature control system.
• Combines the Modbus indoor and/or outdoor temperature input with the mixed air input to provide economizer dry bulb free cooling function.
Contents
Application.........................................................................1
Features ............................................................................1
Specifications ....................................................................2
Installation .........................................................................3
Wiring ................................................................................6
Operation...........................................................................7
Settings and Adjustment ...................................................7
Troubleshooting.................................................................11
63-2569—04
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

SPECIFICATIONS

Models:
W7340: Communicating Economizer Logic Module with
minimum position potentiometer, setpoints for enthalpy or dry-bulb, and DCV.
W7345: Communicating Economizer Logic Module with
minimum position potentiometer and setpoint for dry-bulb temperature only.
IMPORTANT
W7340A, W7340B and W7345A:
1. Do not have the ability to set DCV minimum position for damper position for demand control ventilation. Damper may drive 100% open on call from CO sensor.
2. Do not have the E (enthalpy or dry bulb) curve setting.
3. W7340C has the ability to set DCV minimum position and has the E curve setting.
Dimensions: See Fig. 1.
Temperature Ratings:
Operating Ambient: -40 to +149 °F (-40 to +65 °C). Shipping: -25 to +125 °F (-32 to +52 °C).
Humidity Ratings:
Noncondensing: 5 to 95% RH. Condensing: 100% RH.
Inputs and Outputs: See Table 1.
Electrical Ratings:
Input Voltage: 24 Vac ±25%; 50/60 Hz (Class 2). Nominal Power Consumption (at 24 Vac, 60 Hz): 5 VA. Relay Contact Rating at 30 Vac (maximum power from class 2
input only): 1.5 A run, 7.5 A inrush.
Patents:
U.S. Patent 6,1,764. Other Patents Pending.
2
Approvals:
cUL listed. Underwriters Laboratories Inc. listed:
Meets UL873 plenum requirements.
Meets UL94-5VA plenum flammability requirements. FCC Part 15 Class B. CE. This product complies with Title 24 Part 6 CEC standard for
Residential and Non-Residential Buildings - 2005, when
installed according to instructions.
4-1/16
(103)
1-15/16
(49)
1-3/4 (44)
4-7/16 (112)
1-3/8
(35)
5/8
(16)
M22813
Fig. 1. Dimensions of W7340 and W7345 in inches (mm).
Accessories:
32005191-001 Sensor, 10K ohm with 2-1/4 in. (57 mm) probe. C7150B1046 Mixed Air Sensor, 10K ohm with mounting
bracket. C7232 Carbon Dioxide Sensor for DCV. C7632 Carbon Dioxide Sensor for DCV. C7400A Solid State Enthalpy Sensor for use with W7340A
and W7340B. C7400C Solid State Enthalpy Sensor for use with W7340C. C7600C Relative Humidity Sensor. S963B1136 Remote Potentiometer to provide remote control
of damper minimum position. ST6008 Energy Management Timer for occupied/unoccupied
control. ST7009 Electronic Programmable Timer for occupied/
unoccupied control.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2569—04 2
®
Catalog or price sheets for complete ordering number.
1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
CAUTION
CAUTION
Table 1. Logic Module Inputs and Outputs.
W7340 W7345
Inputs
Enthalpy
Modbus yes yes
Return Sensor optional
Mixed/Discharge Air
Outdoor Sensor
Indoor DCV Sensor 0-10 Vdc control signal
Remote Minimum Position Potentiometer
Motor Feedback 2-10 Vdc
Outputs
Modbus yes yes
Exhaust One set of 24 Vac
Motor Output Signal 2-10 Vdc
a
2-wire (18, 20, 22 AWG) connection.
4-20 mA
10K ohm
10K ohm
optional optional
contacts (spst)
a
a
a
10K ohm

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.

Location and Mounting

Communicating Economizer Logic Modules

When planning the installation, allow enough clearance for maintenance and service. Mount the device in a location protected from rain, snow, and direct sunlight. The logic module mounts on the side of an M7215 Damper Motor or directly on a sheet metal duct or panel.
a
NOTE: Refer to Figures 4 and 5 for representative locations
of connected system devices.
Equipment Damage Hazard. Mounting screws longer than 5/8 in. can damage internal motor components.
When mounting the module to an M7215 use only the included #6 5/8 in. thread-forming screw.
MOUNTING DIRECTLY TO THE MOTOR
1. Mount the motor.
2. Secure the W7340 or W7345 to the motor using the
supplied mounting screw (See Fig. 2).
MOUNTING SEPARATE FROM THE MOTOR
Secure the device to the sheet metal using appropriate fasteners (not supplied)(See Fig. 3).
5/8 INCH SCREW INCLUDED WITH LOGIC MODULE.
ECONOMIZER LOGIC MODULE
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
M7215 DAMPER MOTOR
Fig. 2. Mounting Economizer Logic Module on Damper
Motor.
3 63-2569—04
M17550B
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
M17638
IMPORTANT
W7340B: The W7340B DCV economizer logic modules incorporate a minimum position setting that defaults to 20%, but can be overridden using the Modbus communication link.
The W7340B DCV maximum position sets the damper position to a position that the damper goes to if the CO the minimum position set point is higher than the DCV maximum position, on sensor failure, the damper goes to the higher of the two DCV maximum and minimum position setting. There is no limit on the damper position on a call from the CO sensor (DCV); the damper can go 100% open.
W7340C: The W7340C DCV economizer logic module has the ability to set DCV minimum damper position and minimum position. The DCV minimum position is set to ventilate the building contaminants and the minimum position is set to ventilate for the building contaminants and the building occupants. The installer sets the damper DCV minimum position and the minimum position based on the design occupancy and CFM of outdoor air requirements for the space. The damper will modulate open between the DCV minimum damper position and the minimum position based on input from a CO2 sensor. The damper will not drive 100% open on a
Fig. 3. Mounting to a Duct or Panel.
call for ventilation, but can drive 100% open on a call for cooling. If the CO minimum position ventilating for building contaminants and

Enthalpy Sensor (W7340 only)

To measure enthalpy, the logic module accepts signals from either:
the building occupants. If the DCV minimum position has not been set using the following procedure, the default setting will be 50% of the minimum position setting.
— C7600C Humidity and 10K NTC temperature sensors. — or a C7400 Enthalpy Sensor.
IMPORTANT
• When using C7400 Enthalpy Sensors, connect the enthalpy sensors to the humidity sensor terminals; leave the temperature sensor terminals empty.
• Use C7400A sensor with W7340A or W7340B.
• Use C7400C sensor with W7340C.
OUTDOOR AIR SENSING
1. Mount each sensor in any orientation that exposes it to freely circulating air and protects it from rain, snow, and direct sunlight.
2. Connect it to the logic module.

DCV Min and Min Position Damper Set Up

Set up instructions for W7340C DCV damper positions:
1. Remove RAT sensor from RAT terminals.
2. Connect CO2 sensor to DCV terminals.
3. Apply power to economizer logic module.
4. Wait 10 to 15 seconds for the CO2 sensor to initialize.
5. Remove CO
6. DCV LED will blink 2 times. If LED does not blink, cut
7. Set DCV minimum position using MIN POS/DCV MIN
8. Remove RAT short.
9. DCV minimum position is saved to memory and DCV
RETURN AIR SENSING
1. For differential enthalpy or temperature control mount a second sensor in the return air duct.
2. Connect it to the logic module.
10. Turn off power to economizer logic module.
11. Connect RAT sensor.
12. Turn power on to economizer logic module.
13. Set minimum position using MIN POS/DCV MIN

Demand Control Ventilation (DCV) Sensor Input (W7340 only)

The DCV sensor can be any sensor that provides a 0-10 Vdc output over a range of 0 to 2000 ppm of CO modulates the outdoor damper to provide ventilation based on occupancy. Mount the sensor according to the manufacturer specifications. If not available, mount the sensor in an area with unobstructed air circulation.
. The DCV signal
2
IMPORTANT
• Ensure proper polarity of sensor connections. Incorrect polarity negates the sensor signal.
sensor fails. If
2
sensor fails the damper will drive to the
2
Short RAT terminals.
sensor from DCV terminals.
2
power to economizer logic and repeat steps 1-5.
potentiometer.
LED blinks 5 times.
potentiometer.
Steps 3-8 must be completed within 3 minutes after power up otherwise the configuration process will be terminated, no changes will be saved and you will need to repeat steps 1-13.
2
63-2569—04 4
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
10K NTC DISCHARGE AIR SENSOR
DISCHARGE AIR
1
FOR DIFFERENTIAL ENTHALPY, THE TWO C7400 ENTHALPY SENSORS ARE CONNECTED TO THE ECONOMIZER MODULE—ONE IS MOUNTED IN THE RETURN AIR DUCT, AND THE OTHER IS MOUNTED IN THE OUTDOOR AIR DUCT. DIFFERENTIAL ENTHALPY CONTROL PROVIDES GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY CONTROL.
USE EITHER MIXED AIR SENSOR OR DISCHARGE AIR SENSOR, NOT BOTH.
2
3
A C7600 HUMIDITY SENSOR, USED IN CONJUNCTION WITH A 10K NTC TEMPERATURE SENSOR CAN BE USED INSTEAD OF A C7400 ENTHALPY SENSOR. FOR DRY BULB CONTROL, USE ONLY A 10K NTC TEMPERATURE SENSOR.
2
INDOOR FAN
MODBUS
DIRECT EXPANSION COIL
M7215 MOTOR
WITH W7340
ECONOMIZER
LOGIC MODULE
Fig. 4. Representative Locations of Connected W7340 Economizer System Devices.
10K NTC
C7400
ENTHALPY SENSOR
RETURN AIR
MIXED AIR SENSOR
2
1
3
C7232
C7400
ENTHALPY SENSOR
EXHAUST FAN
INDOOR AIR CO2 SENSOR
1
3
EXHAUST AIR
OUTDOOR AIR
M22814
10K NTC DISCHARGE AIR SENSOR
DISCHARGE AIR
1
USE EITHER MIXED AIR SENSOR OR DISCHARGE AIR SENSOR, NOT BOTH.
1
INDOOR FAN
MODBUS
DIRECT EXPANSION COIL
M7215 MOTOR
WITH W7345
ECONOMIZER
LOGIC MODULE
Fig. 5. Representative Locations of Connected W7345 Economizer System Devices.
MIXED AIR
10K
SENSOR
NTC
1
1
OUTDOOR AIR
EXHAUST FAN
EXHAUST AIR
RETURN AIR
M22822
5 63-2569—04
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
CAUTION
P1
TR1
TR1
24 VAC
TR
TR
P
EXF
M23875
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
OPTIONAL REMOTE MINIMUM POSITION POTENTIOMETER.
WHEN USING C7400 ENTHALPY SENSORS, CONNECT THE ENTHALPY SENSOR TO THE HUMIDITY SENSOR TERMINALS. LEAVE THE TEMPERATURE SENSOR TERMINALS EMPTY.
1
2
3
3
3
3 3
2
R
B W
CCW OPEN
MOD BUS
CW CLOSE
S963B
M7215
W7340
2-10 Vdc FEEDBACK OUTPUT
2-10 Vdc CONTROL SIGNAL INPUT
2-10 Vdc FEEDBACK INPUT
MIN POS/ DCV MIN
DCV SETPOINT
2-10 Vdc CONTROL SIGNAL OUTPUT
POWER EXHAUST CONTACTOR
MIXED AIR TEMP SENSOR 10K NTC
OUTDOOR AIR TEMP SENSOR 10K NTC
RETURN AIR TEMP SENSOR 10K NTC
C7600C OUTDOOR AIR HUMIDITY
C7600C RETURN AIR HUMIDITY
DCV SENSOR (0-10 Vdc)
MAT
OAH
OAT
RAT
RAH
DCV
AE
B
C
+–+–
+– +– +–
+
MOD BUS –
MOD BUS +
1
24 VAC
L1
L2
+
D

WIRING

Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
IMPORTANT
1. All wiring must comply with applicable local codes, ordinances and regulations.
2. Refer to Figures 6 and 7 for typical wiring diagrams.
3. All inputs and outputs to the device must be 24 Vac Class 2.
4. Ensure proper polarity of sensor connections. Incorrect polarity negates the sensor signal.
NOTE: All connections with label designation ending in 1
(examples: TR1, P1) are ac/dc common connections.
Fig. 6. W7340 Typical Wiring.
63-2569—04 6
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
P1
TR1
TR1
24 VAC
TR
TR
P
MOD BUS –
MOD BUS +
M23876
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
OPTIONAL REMOTE MINIMUM POSITION POTENTIOMETER.
1
1
2
2
R
B W
24 VAC
L1
L2
+
CCW OPEN
MOD BUS
CW CLOSE
S963B
M7215

W7345

MINIMUM POSITION
MIXED AIR TEMP SENSOR 10K NTC
MAT
+
AE
BCD
Fig. 7. W7345 Typical Wiring.

OPERATION

The purpose of the economizer logic modules are to use outdoor air for cooling, whenever possible, to reduce compressor operation.
IMPORTANT
• Use C7400A sensor with W7340A or W7340B.
• Use C7400C with W7340C.
The W7340, when wired as shown in Fig. 6, responds to a signal from the Modbus. This system uses C7400 Solid State Enthalpy Changeover Sensor(s). The C7400 Enthalpy Sensors respond to both dry bulb temperature and humidity, allowing use of outdoor air at higher temperatures for free cooling when humidity is low.
The logic module functions as a first stage of cooling and provides maximum fuel economy during the cooling cycle. The logic module automatically locks out free cooling during heating. It holds the outdoor air damper at the minimum position setting.
The W7340 operates as a basic free cooling controller. Table 2 details the input/output (I/O) logic of the W7340. The logic module energizes the Unit Control and Indoor Fan contacts, and operates according to Table 2.

SETTINGS AND ADJUSTMENT

W7345
Potentiometers with screwdriver adjustment slots, located on the face of the device, provide adjustments for Minimum Damper Position parameters (See Fig. 8 for locations on device).
MINIMUM DAMPER POSITION
MAT
OAT
RAT
P P1
OPEN
C
B
A
TR1 24V COM
MIN POS/ DVC MIN
D
E
MBUS-
MBUS+
TR 24V AC
-
Fig. 8. Location of W7345 Potentiometers and LED.
DRY BULB CHANGEOVER SETPOINT
STATUS LED
M23877
7 63-2569—04
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

W7340

Potentiometers with screwdriver adjustment slots, located on the face of the device, provide adjustments for several parameters (See Fig. 9 for locations on device): — DCV minimum and minimum damper position. — Enthalpy changeover. — DCV setpoint.
MIN POS/DCV MIN DAMPER
ExF
MAT
+
OAH
_
OAT
RAT
+
RAH
_
DCV
PP1
OPEN
C
B
A
TR1 24V COM
2-10 VDC DAMPER
POSITION
2-10 VDC DAMPER POSITION
OVERRIDE
MIN POS/ DCV MIN
D
E
DCV SETPOINT
1500500
MBUS-
MBUS+
TR 24V AC
+
-
+
-
POSITION
ENTHALPY CHANGEOVER SETPOINT
STATUS LED
DEMAND CONTROL VENTILATION SETPOINT
M23878
Fig. 9. Location of W7340 potentiometers and LED.
IMPORTANT
Before powering the device read the following Enthalpy changeover setpoint guidelines:
1. Using the Enthalpy changeover setpoint, the setpoint can be adjusted until three minutes after powering the device. until three minutes after powering the device.
2. Through the Modbus, the Enthalpy changeover setpoint can be modified at any time.
3. If the Enthalpy changeover potentiometer is changed after the three minute power-up time, no change to the Enthalpy changeover setpoint will occur unless power is removed from the device then reapplied.
NOTES:
The DCV setpoint can be changed at anytime by
adjusting the pot.
For Enthalpy changeover setpoint see comments
above.
MIN POS can be changed anytime by adjusting
the pot.
DCV Min can be changed by procedure on page 4.

Demand Control Ventilation (DCV) Setpoint

The logic module modulates the outdoor damper to provide ventilation based on the 2-10 Vdc DCV sensor. With no cooling signal, DCV overrides the DCV minimum damper position when ventilation requires outdoor air.
Table 2. W7340 Economizer I/O Logic.
INPUTS OUTPUTS
Enthalpy
DCV
Below
High Low On On On On Minimum
set
a
Y1bY2
On Off On Off
Low High On On On Off
Compressor
b
DamperOutdoor Return Stage 1 Stage 2
position
Modulating
On Off Off Off
Above
High Low On On On On
set
On Off On Off
Low High On On On Off
Modulating
Modulating
On Off Off Off
a
For single enthalpy control, the module compares outdoor enthalpy to the ABCDE setpoint.
b
If both stages of cooling are off, the system is off and the damper is:
• At DCV minimum position if DCV is below setpoint.
• Modulating if DCV is above setpoint.
c
Modulation based on mixed air sensor signal, modulating between DCV minimum position and 100% open.
d
Modulation based on DCV signal, limited by minimum position.
e
Modulation based on the greater of the DCV and mixed air sensor signals.

Adjusting Minimum Damper Position

The minimum position potentiometer maintains the minimum outdoor air flow into the building during occupied period.
NOTE: If the mixed air temperature drops to 45° F (7° C), the
mixed air sensor overrides the DCV sensor and closes the damper to DCV minimum position to protect the hot or chilled water coils from freezing. When the mixed air temperature rises to 48° F (9° C), control reverts to normal operation.
For detailed assistance in minimum position selection, reference the Economizer Application Guide (form 63-8594) Ventilation section. The following provides basic guidelines for minimum position selection and adjustment:
IMPORTANT
1. Adjust the minimum position potentiometer to allow the amount of outdoor air, as required by local codes, to enter the building for building contaminants and the maximum building occupants.
2. This procedure requires use of a quality thermometer capable of reading to 0.5° F (0.-17.5° C).
c
d
e
63-2569—04 8
NOTE: Make minimum position adjustments with at least a
10° F (-12° C) temperature difference between outdoor and return air.
See section on DCV setpoint set up on page 4.
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
T
O
OA×()TRRA×()+ T
M
=
TOT
R
()OA TR+× T
M
=
0.1x 6° F()0.9x 75° F()+ 6.0° F 67.5° F+ 73.5° F==
60° F 75° F()0.1 75° F+× 1.5 75° F+ 73.5° F==

Limit On Minimum Damper Position

On the W7340A and B models, the logic module as shipped from the factory, limits the minimum position setpoint to 50%. The logic module will not allow a minimum position greater than 50% open (from fully closed).
NOTE: This setpoint limit can only be changed using a
Modbus command.
Equation 1. Formula to aid in minimum position adjustment.
or
Where: T
= Outdoor air temperature
O
OA = Percent of outdoor air
= Return air temperature
T
R
RA = Percent of return air T
= Resulting mixed air temperature
M
NOTE: The following sample calculation uses only
Fahrenheit temperature.
EXAMPLE: Assume local codes require 10% outdoor air
during occupied conditions, outdoor air is 60° F and return air is 75° F. Under these conditions, what is the temperature of the mixed air?

Differential Enthalpy Changeover Setting

Differential enthalpy control uses: — W7340A and B use two C7400A Enthalpy Sensors
connected to one logic module, or
— Two 10K NTC temperature sensors and two C7600C
Humidity Sensors connected to one logic module.
— W7340C uses C7400C Enthalpy Sensor(s) or — Two 10K NTC temperature sensors and two C7600C
Humidity Sensors connected to one logic module.
With outdoor and return air sensors, the logic module compares outdoor air to return air instead of to a setpoint as it does for single enthalpy. The logic module selects the lower enthalpy air (return or outdoor) for cooling; for example, when outdoor air has lower enthalpy than return air, the outdoor air damper opens to bring in outdoor air for free cooling.
NOTE: When using the W7340 for differential enthalpy, keep
the setpoint potentiometer set at D.

Exhaust Setpoint (W7340 only)

The exhaust setpoint determines when the exhaust fan will run based on the damper position.
The logic module, as shipped from the factory, uses an exhaust setpoint of 25%. When the damper position is greater than 25% open (from fully closed), relay contact for the exhaust fan is closed. When the damper position is below 22% open, the relay is de-energized.
or
Mixed air will be 73.5° F when OA is 60° F and RA is 75° F with 10 percent outdoor air entering the building.
NOTE: The W7340C model min position and DCV min must
be set in the field by the installer. See Section DCV Min and Min Position Damper Set up.

Enthalpy Changeover (W7340 only)

Outdoor Enthalpy Changeover Setpoint (Single Enthalpy Changeover)

The outdoor enthalpy changeover setpoint returns the outdoor air damper to minimum position when enthalpy rises above its setpoint. Enthalpy setpoint scale markings, located on the device, are A, B, C, D and E. See Fig. 10 for the corresponding control point.

Control Configuration (W7340 only)

The W7340 can be configured for humidity or enthalpy sensors. Configuration can be performed manually or over the Modbus.
IMPORTANT
If only a temperature sensor is connected to the W7340, the device will operate using dry bulb changeover control.
To configure the W7340 manually:
1. Within the first three minutes after powering the device, short the external minimum damper position terminals (P-P1).
NOTE: The LED will go solid within five seconds of
shorting these terminals.
2. Maintaining the short for another five seconds causes the LED to flash quick pulses (between off periods) indicating the sensor configuration type: a. Two quick pulses: Humidity. b. Three quick pulses: Enthalpy.
3. To toggle the sensor configuration type: a. Remove the short until the LED goes solid again. b. Reapply the short for another five seconds.
NOTE: Once the short is removed for over 10 seconds,
the device saves the most recent configuration.
9 63-2569—04
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
CONTROL
CURVE
A B C D E
CONTROL POINT
APPROX. °F (°C)
AT 50% RH
73 (23) 70 (21) 67 (19) 63 (17) 55 (13)
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46
90
100
80
70
60
50
40
30
20
10
ENTHALPY—BTU PER POUND DRY AIR
85
(29)90(32)95(35)
100 (38)
105
(41)
110
(43)
35 (2)
35 (2)
40 (4)
40 (4)
105 (41)
110
(43)
45 (7)
45 (7)
50
(10)
50
(10)
55
(13)
55
(13)
60
(16)
60
(16)
65
(18)
65
(18)
70
(21)
70
(21)
75
(24)
75
(24)
80
(27)
80
(27)
85
(29)90(32)95(35)
100 (38)
APPROXIMATE DRY BULB TEMPERATURE— °F (°C)
A
A
B
B
C
C
D
D
M23879
RELATIVE HUMIDITY (%)
1
1
HIGH LIMIT CURVE FOR W7210D, W7212, W7213, W7214, W7340B.
E
E
Fig. 10. W7340 Performance Characteristics for Enthalpy Changeover Settings.
Table 3. W7345 Performance Characteristics
for Temperature Changeover Settings.
Temperature
Changeover Setting
A7323
Approximate Control Point
°F °C
B7021
C6719
D6317
E5513
63-2569—04 10
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

TROUBLESHOOTING

The status LED is visible through a hole in the device cover. A priority-based LED flash sequence indicates a detected fault.
0.25 seconds elapses between each pulse, a higher pulse count indicates higher priority. A two-second on period precedes each repeated sequence.
The diagnostic bit position corresponds to the Modbus diagnostic register. The diagnostic bit resets when the respective fault is present. To read all active faults, read the diagnostic register via Modbus function code 8 (no flash priority needed).
NOTES:
All pulse counts (Table 4) are based on the
number of times the light pulses off.
In the event of a Communications Failure, the LED
pulses on for 0.25 seconds every 2 seconds.
Table 4. W7340 Economizer Checkout.
Pulse
Description
Booting (0-3 min. after power-up) NA 12
Mixed air temperature sensor fault 87
Outdoor air temperature sensor fault 76
Outdoor air humidity sensor fault 65
Return air temperature sensor fault 43
Return air humidity sensor fault 32
Indoor air quality sensor fault 21
Actuator fault 10
Proper operation (outdoor air appropriate for free cooling)
Proper operation (NO free cooling) 2 Hz flash NA
Communications failure 1 (pulses
count
Solid
ON NA
on) NA
Diagnostic
bit
11 63-2569—04
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark © 2007 Honeywell International Inc. 63-2569—04 J.I. Rev. 06-07
Loading...