Honeywell W7340, W7345 User Manual

W7340, W7345
W7340
W7345
Communicating Economizer Logic Modules
FOR VENTILATION CONTROL
PRODUCT DATA

FEATURES

• Solid state control package provides accuracy, reliability and stability.
• Housed in high-impact, glass-fiber reinforced plastic case.
• Terminals included for connecting optional S963B1136 Remote Potentiometer for remote minimum damper position control.
• Communicates using a modified Modbus protocol.
• Case matches the lines of the M7215 Damper Motor.
• LED indicates the status of the device input.

W7340 Only

APPLICATION

The W7340 Communicating Economizer Logic Module is a full featured economizer that incorporates Demand Control Ventilation (DCV) to provide free cooling and ventilation for occupants in a space while saving energy.
The W7345 Communicating Economizer Logic Module is a dry bulb only economizer that does not incorporate Demand Control Ventilation.
The W7340 is used with both solid state temperature and humidity or enthalpy sensors. The W7345 is used with solid state temperature sensors only.
• Operates from the Modbus input, environmental sensors, and a DCV sensor to provide a totally integrated control system.
• Combines minimum damper position potentiometer with solid state temperature (10K NTC) and humidity or enthalpy changeover control to provide economizer free cooling function; this control can be overridden by input via Modbus or DCV sensor.

W7345 Only

• Operates from the Modbus input and mixed/discharge air sensor to provide a temperature control system.
• Combines the Modbus indoor and/or outdoor temperature input with the mixed air input to provide economizer dry bulb free cooling function.
Contents
Application.........................................................................1
Features ............................................................................1
Specifications ....................................................................2
Installation .........................................................................3
Wiring ................................................................................6
Operation...........................................................................7
Settings and Adjustment ...................................................7
Troubleshooting.................................................................11
63-2569—04
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES

SPECIFICATIONS

Models:
W7340: Communicating Economizer Logic Module with
minimum position potentiometer, setpoints for enthalpy or dry-bulb, and DCV.
W7345: Communicating Economizer Logic Module with
minimum position potentiometer and setpoint for dry-bulb temperature only.
IMPORTANT
W7340A, W7340B and W7345A:
1. Do not have the ability to set DCV minimum position for damper position for demand control ventilation. Damper may drive 100% open on call from CO sensor.
2. Do not have the E (enthalpy or dry bulb) curve setting.
3. W7340C has the ability to set DCV minimum position and has the E curve setting.
Dimensions: See Fig. 1.
Temperature Ratings:
Operating Ambient: -40 to +149 °F (-40 to +65 °C). Shipping: -25 to +125 °F (-32 to +52 °C).
Humidity Ratings:
Noncondensing: 5 to 95% RH. Condensing: 100% RH.
Inputs and Outputs: See Table 1.
Electrical Ratings:
Input Voltage: 24 Vac ±25%; 50/60 Hz (Class 2). Nominal Power Consumption (at 24 Vac, 60 Hz): 5 VA. Relay Contact Rating at 30 Vac (maximum power from class 2
input only): 1.5 A run, 7.5 A inrush.
Patents:
U.S. Patent 6,1,764. Other Patents Pending.
2
Approvals:
cUL listed. Underwriters Laboratories Inc. listed:
Meets UL873 plenum requirements.
Meets UL94-5VA plenum flammability requirements. FCC Part 15 Class B. CE. This product complies with Title 24 Part 6 CEC standard for
Residential and Non-Residential Buildings - 2005, when
installed according to instructions.
4-1/16
(103)
1-15/16
(49)
1-3/4 (44)
4-7/16 (112)
1-3/8
(35)
5/8
(16)
M22813
Fig. 1. Dimensions of W7340 and W7345 in inches (mm).
Accessories:
32005191-001 Sensor, 10K ohm with 2-1/4 in. (57 mm) probe. C7150B1046 Mixed Air Sensor, 10K ohm with mounting
bracket. C7232 Carbon Dioxide Sensor for DCV. C7632 Carbon Dioxide Sensor for DCV. C7400A Solid State Enthalpy Sensor for use with W7340A
and W7340B. C7400C Solid State Enthalpy Sensor for use with W7340C. C7600C Relative Humidity Sensor. S963B1136 Remote Potentiometer to provide remote control
of damper minimum position. ST6008 Energy Management Timer for occupied/unoccupied
control. ST7009 Electronic Programmable Timer for occupied/
unoccupied control.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2569—04 2
®
Catalog or price sheets for complete ordering number.
1885 Douglas Drive North Minneapolis, Minnesota 55422-4386
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
CAUTION
CAUTION
Table 1. Logic Module Inputs and Outputs.
W7340 W7345
Inputs
Enthalpy
Modbus yes yes
Return Sensor optional
Mixed/Discharge Air
Outdoor Sensor
Indoor DCV Sensor 0-10 Vdc control signal
Remote Minimum Position Potentiometer
Motor Feedback 2-10 Vdc
Outputs
Modbus yes yes
Exhaust One set of 24 Vac
Motor Output Signal 2-10 Vdc
a
2-wire (18, 20, 22 AWG) connection.
4-20 mA
10K ohm
10K ohm
optional optional
contacts (spst)
a
a
a
10K ohm

INSTALLATION

When Installing this Product...

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.

Location and Mounting

Communicating Economizer Logic Modules

When planning the installation, allow enough clearance for maintenance and service. Mount the device in a location protected from rain, snow, and direct sunlight. The logic module mounts on the side of an M7215 Damper Motor or directly on a sheet metal duct or panel.
a
NOTE: Refer to Figures 4 and 5 for representative locations
of connected system devices.
Equipment Damage Hazard. Mounting screws longer than 5/8 in. can damage internal motor components.
When mounting the module to an M7215 use only the included #6 5/8 in. thread-forming screw.
MOUNTING DIRECTLY TO THE MOTOR
1. Mount the motor.
2. Secure the W7340 or W7345 to the motor using the
supplied mounting screw (See Fig. 2).
MOUNTING SEPARATE FROM THE MOTOR
Secure the device to the sheet metal using appropriate fasteners (not supplied)(See Fig. 3).
5/8 INCH SCREW INCLUDED WITH LOGIC MODULE.
ECONOMIZER LOGIC MODULE
IMPORTANT
All wiring must agree with applicable codes, ordinances and regulations.
Electrical Shock or Equipment Damage Hazard. Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
M7215 DAMPER MOTOR
Fig. 2. Mounting Economizer Logic Module on Damper
Motor.
3 63-2569—04
M17550B
W7340, W7345 COMMUNICATING ECONOMIZER LOGIC MODULES
M17638
IMPORTANT
W7340B: The W7340B DCV economizer logic modules incorporate a minimum position setting that defaults to 20%, but can be overridden using the Modbus communication link.
The W7340B DCV maximum position sets the damper position to a position that the damper goes to if the CO the minimum position set point is higher than the DCV maximum position, on sensor failure, the damper goes to the higher of the two DCV maximum and minimum position setting. There is no limit on the damper position on a call from the CO sensor (DCV); the damper can go 100% open.
W7340C: The W7340C DCV economizer logic module has the ability to set DCV minimum damper position and minimum position. The DCV minimum position is set to ventilate the building contaminants and the minimum position is set to ventilate for the building contaminants and the building occupants. The installer sets the damper DCV minimum position and the minimum position based on the design occupancy and CFM of outdoor air requirements for the space. The damper will modulate open between the DCV minimum damper position and the minimum position based on input from a CO2 sensor. The damper will not drive 100% open on a
Fig. 3. Mounting to a Duct or Panel.
call for ventilation, but can drive 100% open on a call for cooling. If the CO minimum position ventilating for building contaminants and

Enthalpy Sensor (W7340 only)

To measure enthalpy, the logic module accepts signals from either:
the building occupants. If the DCV minimum position has not been set using the following procedure, the default setting will be 50% of the minimum position setting.
— C7600C Humidity and 10K NTC temperature sensors. — or a C7400 Enthalpy Sensor.
IMPORTANT
• When using C7400 Enthalpy Sensors, connect the enthalpy sensors to the humidity sensor terminals; leave the temperature sensor terminals empty.
• Use C7400A sensor with W7340A or W7340B.
• Use C7400C sensor with W7340C.
OUTDOOR AIR SENSING
1. Mount each sensor in any orientation that exposes it to freely circulating air and protects it from rain, snow, and direct sunlight.
2. Connect it to the logic module.

DCV Min and Min Position Damper Set Up

Set up instructions for W7340C DCV damper positions:
1. Remove RAT sensor from RAT terminals.
2. Connect CO2 sensor to DCV terminals.
3. Apply power to economizer logic module.
4. Wait 10 to 15 seconds for the CO2 sensor to initialize.
5. Remove CO
6. DCV LED will blink 2 times. If LED does not blink, cut
7. Set DCV minimum position using MIN POS/DCV MIN
8. Remove RAT short.
9. DCV minimum position is saved to memory and DCV
RETURN AIR SENSING
1. For differential enthalpy or temperature control mount a second sensor in the return air duct.
2. Connect it to the logic module.
10. Turn off power to economizer logic module.
11. Connect RAT sensor.
12. Turn power on to economizer logic module.
13. Set minimum position using MIN POS/DCV MIN

Demand Control Ventilation (DCV) Sensor Input (W7340 only)

The DCV sensor can be any sensor that provides a 0-10 Vdc output over a range of 0 to 2000 ppm of CO modulates the outdoor damper to provide ventilation based on occupancy. Mount the sensor according to the manufacturer specifications. If not available, mount the sensor in an area with unobstructed air circulation.
. The DCV signal
2
IMPORTANT
• Ensure proper polarity of sensor connections. Incorrect polarity negates the sensor signal.
sensor fails. If
2
sensor fails the damper will drive to the
2
Short RAT terminals.
sensor from DCV terminals.
2
power to economizer logic and repeat steps 1-5.
potentiometer.
LED blinks 5 times.
potentiometer.
Steps 3-8 must be completed within 3 minutes after power up otherwise the configuration process will be terminated, no changes will be saved and you will need to repeat steps 1-13.
2
63-2569—04 4
Loading...
+ 8 hidden pages