The JADE™ Economizer System includes an Economizer
Module, 20k mixed air sensor, damper actuator, an optional
CO
sensor, and either a 20k outdoor air temperature sensor
2
or Sylk Bus sensors for measuring Outdoor Air and return air
enthalpy, temperature, and humidity.
Economizer Module
This is the core of the JADE™ Economizer System and
includes the user interface for the system. The W7220
Economizer Module provides the basic inputs and outputs to
provide simple economizer control. When used with the
optional Sylk Bus sensors, the Economizer Module provides
more advanced economizer functionality.
Sylk Bus Sensors (optional)
PRODUCT DESCRIPTION
The JADE™ Economizer System is an expandable
economizer control system, which includes a W7220
Economizer Module (controller) with an LCD and keypad. The
W7220 can be configured with optional sensors.
The W7220 Economizer Module can be used as a standalone economizer module wired directly to a commercial set
back space thermostat and sensors to provide Outdoor Air
dry-bulb economizer control.
The W7220 Economizer Module can be connected to optional
Sylk Bus sensors for single or differential enthalpy control. The
W7220 Economizer Module provides power and
communications on the Sylk Bus for the Sylk Bus sensors.
The W7220 Economizer Module automatically detects
sensors by polling to determine which sensors are present. If
a sensor loses communications after it has been detected, the
W7220 Economizer indicates a device fail error on its LCD.
The Sylk Bus Sensor is a combination temperature and
humidity sensor which is powered by and communicates on
the Sylk Bus. Up to three sensors may be configured with the
JADE™ Economizer Module. See page 2 for details.
CO2 Sensor (optional)
A CO2 sensor can be added for Demand Control Ventilation
(DCV). Either an analog (2-10 Vdc) or a wall-mount Sylk bus
TR40 CO2 sensor can be used with the Jade economizer.
PC MOD Tool (optional)
The PC MOD tool is connected to a personal computer and
communicates with the Jade economizer controller via the
Sylk bus. The W7220 PCMOD tool software is free and can be
downloaded from the url in the Accessories section.
Some features on the Jade controller can only be enabled or
disabled using the W7220 PC MOD tool. See the PC MOD
tool options section in Table 5.
The module is designed for use with any Honeywell 2 to 10
Vdc or Honeywell Sylkbus communicating actuator. The
module includes terminals for a CO
and an Outdoor Dry Bulb sensor. Enthalpy and other options
are available with Sylk Bus sensors.
User Interface: Provides status for normal operation, setup
parameters, checkout tests, and alarms and error
conditions with a 2-line 16 character LCD display and a
four button keypad.
Electrical
Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer:100 VA maximum system input
Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5 VA
without sensors or actuators
Relay Digital Output Rating at 30 Vac (maximum power
from Class 2 input only): 1.5A run;
3.5A inrush @ 0.45PF (200,000 cycles) or
7.5A inrush @ 0.45PF (100,000 cycles)
External Sensors Power Output: 21 Vdc +/- 5% @ 48mA
IMPORTANT
All inputs and outputs must be Class 2 wiring.
Inputs
sensor, Mixed Air sensor,
2
Dry Bulb Temperature (optional) and Mixed Air
(required), C7250A:
2-wire (18 to 22 AWG);
Temperature range -40 to 150 °F (-40 to 65 °C).
Temperature accuracy -0°F/+2°F
Temperature and Humidity, C7400S1000 (optional):
Sylk Bus; 2-wire (18 to 22 AWG)
Temperature: range -40 to 150 °F (-40 to 65 °C)
Temperature accuracy -0°F/+2°F
Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) SYLK Bus sensors may be
connected to the JADE™ Economizer module.
For outdoor air (OA), return air (RA) and
discharge (supply) air (DA).
DCV (CO
2-10 Vdc control signal; minimum impedance >50k ohm.
4 Binary inputs:
1-wire 24 Vac + common GND (see page 6 for wiring
details). 24 Vac power supply: 20 to 30 Vac 50/60Hz;
100 VA Class 2 transformer.
) Sensor (C7232 or C7632):
2
Outputs
Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus
communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O:
All Relay Outputs (at 30 Vac):
Running: 1.5A maximum
Inrush: 7.5A maximum
SENSORS:
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor
for dry bulb change over or an OA Sylkbus
sensor for outdoor enthalpy change over is
required in addition to the MA sensor. An
additional Return Air (RA) Sylkbus sensor can be
added to the system for differential enthalpy or
dry bulb changeover. For differential dry bulb
changeover a 20k ohm sensor is required in the
OA and a Sylkbus sensor in the RA. Dip switch
on RA Sylkbus sensor must be set in the RA
position.
Environmental
Operating Temperature: -40 to 150 °F (-40 to 65 °C).
Exception of display operation down to -4 °F with full
recovery at -4 °F from exposure to -40 °F
Storage Temperature: -40 to 150 °F (-40 to 65 °C)
Shipping Temperature: -40 to 150 °F (-40 to 65 °C)
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
63-2700—102
JADE™ ECONOMIZER MODULE
4-63/64
(126)
6-19/64 (160)
MOUNTING HOLE (X2)
M32273A
3-5/32 (80)
Approvals: UL listed (XAPX) for USA and Canada;
California Energy Commission (CEC) FDD ID number
HJW10.
Fig. 1. Dimensions in inches (mm) showing mounting
holes.
Accessories
— 50048926-001 2-pin edge connector for sensors (20
pieces per bag)
— 50048926-002 6-pin edge connector for field wiring (20
pieces per bag)
— C7250A 20k sensor for MA or OA (dry bulb changeover)
— C7400S Sylkbus sensor for enthalpy control in OA and/
or RA and RA for differential dry bulb changeover
— W7220 PCMOD interface tool for JADE controller and
Personal Computer. For the software, go to
www.customer.honeywell.com/economizertools
— 50053060-001 Duct mounting kit for sensors
— C7632 or C7232 CO
Sylk bus CO
sensor
2
analog sensors OR one TR40
2
INSTALLATION AND SETUP
The following installation procedures should be performed in
the order listed:
1. Mounting — see page 3.
2. Wiring — see page 4.
3. Interface and Programming overview – see page 18.
4. Setup and Configuration — see page 18
5. Checkout — see page 30.
Troubleshooting and Alarms—see page 31.
MOUNTING
This section describes the mounting procedures for the
JADE™ Economizer module and the sensors.
Economizer Module Location and
Mounting
IMPORTANT
Avoid mounting in areas where acid fumes or other
deteriorating vapors can attack the metal parts of the
module’s circuit board, or in areas where escaping
gas or other explosive vapors are present.
IMPORTANT
The module must be mounted in a position that allows
clearance for wiring, servicing, and removal.
Mount the Economizer module on any convenient interior
location using the two mounting holes provided on the
enclosure using #6 or #8 screws (screws are not provided and
must be obtained separately). Use the dimensions in Fig. 1 on
page 3 as a guide.
BEFORE INSTALLATION
Review the “Specifications” on page 2 before installing the The
JADE™ Economizer System.
When Installing This Product
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check ratings given in instructions and on the product to
ensure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
NOTE: Jade will be in the "set up" mode for the first 60
minutes after powered. If a sensor for OA air or
Sylkbus device (sensor, actuator) is disconnected
during the set up mode, the Jade will not alarm
that failure. The MA sensor is a system "critical"
sensor, if the MA sensor is removed during the
set up mode, the Jade will alarm. After 60 minutes
the Jade controller will change to operation mode
and all components removed or failed will alarm
in the operation mode.
The Economizer module may be mounted in any orientation.
However, mounting in the orientation shown in Fig. 1 on page 3
permits proper viewing of the LCD display and use of the
keypad.
Sensor Location and Mounting
The JADE™ Economizer W7220 uses digital and
communicating sensors for control. The C7250 temperature
sensors (MA
for all applications and is mounted in the mixed air section of a
rooftop unit either directly to the sheet metal using self tapping
sheet metal screws or in the air stream using the duct
mounting kit. Duct mount kit is part number 50053060-001.
Optional OA, RA
the W7220 on the two-wire communication bus and can either
be wired using a two pin header or using a side connector.
Each Sylkbus sensor includes a two pin side connector with
the packaging. The SKU number of the Sylkbus sensor is
C7400S. All OA, RA and DA sensors are the same SKU
a
MA = Mixed Air
b
OA = Outdoor Air
c
RA = Return Air
d
DA = Discharge Air
363-2700—10
a
and OAb) are 20k NTC. A MA sensor is required
c
and DAd Sylkbus sensors communicate with
JADE™ ECONOMIZER MODULE
WARNING
CAUTION
ROD - 1 PIECE
FLANGE - 1 PIECE
GASKET - 1 PIECE
M32281A
WIRE HO LDER
EXTENDED RELIEF
(FOR CORRECT MOUNTING)
M32282A
LENGTH ADJUSTS
6-12 INCHES
number. The sensor is set for the appropriate type of sensing
using the three position DIP switch located on the sensor. OA
position is OFF, OFF, OFF; RA is ON, OFF, OFF and DA is
OFF, ON, OFF. During installation the sensors are set for the
usage desired. See “Sylk Bus Sensor Wiring” on page 7 for
DIP switch details.
NOTE: The protective film on the dip switch is only nec-
essary during the factory assembly process. Simply push through the film to set the dip switches;
this will not harm the device.
Once installed, a sensor can be changed to a different
application by simply changing the DIP switch setting.
Sensor Mounting
The sensors can be mounted directly on to the sheet metal of
unit or can be mounted in the air stream using the duct
mounting kit (order separately).
The kit contains a rod to hold the sensor in the duct, a flange to
secure the sensor rod to the duct wall and fill the hole and a
gasket to prevent air from leaking through the duct wall. There
are five (5) kits in each bag assembly. See Fig. 2.
The rod has slots for threading the wire to prevent loose or
hanging wire in the duct and can be adjusted for 6 to 12 inch
length. The flange has extended relief for ease of mounting.
See Fig. 3.
All wiring must comply with applicable electrical codes and
ordinances, or as specified on installation wiring diagrams.
Module wiring in the field is terminated to the four screw
terminal blocks located on the left and right sides.
Module wiring at the OEM factory is terminated via the header
pin terminals located on the left and right sides. The header
terminal pins and the terminal blocks have common
terminations for the appropriate input or output. See OEM
wiring diagram in Fig. 20.
The remainder of this section describes the wiring for the
JADE™ Economizer module, W7220A.
Electrical Shock Hazard.
Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or
making wiring connections, to prevent electrical shock
or equipment damage.
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Ensure that you are properly grounded before handling
the unit.
63-2700—104
JADE™ ECONOMIZER MODULE
DISCHARGE
AIR SENSOR
C7400S
DIRECT
EXPANSION
COIL
C7400S
ENTHALPY
SENSOR
C7400S
ENTHALPY
SENSOR
RETURN AIR
OUTDOOR
AIR
C7250A
MIXED AIR
SENSOR
TWO STAGE COOL
PROGRAMMABLE
THERMOSTAT
FOR DIFFERENTIAL ENTHALPY, THE TWO C7400S ENTHALPY
SENSORS ARE CONNECTED TO THE W7720A ECONOMIZER
CONTROL ONE IS MOUNTED IN RETURN AIR, AND THE
OTHER IS MOUNTED IN OUTDOOR AIR. DIFFERENTIAL
ENTHALPY CONTROL PROVIDES GREATER ENERGY
SAVINGS THAN SINGLE ENTHALPY.
M35163
1
1
1
MS3103J
MS3105J
MS7505
ACTUATOR
W7720A
Fig. 4. Location of Outdoor Air, Return Air, Mixed Air, and Discharge Air Sensors in an economizer system.
563-2700—10
JADE™ ECONOMIZER MODULE
1/2 (13)
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
2. TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING SCREW.
THEN PULL ON EACH WIRE IN ALL
TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M24382A
JADE CONTROLLER
LEFT TERMINAL
BLOCK LABEL
RIGHT TERMINAL
BLOCK LABEL
M32283C
AUX2-I
AUX1-O
AUX2-I
OCC
E-GND
EXH1
AUX1-O
Y2-I
Y2-O
Y1-I
Y1-O
C
R
Economizer Module Wiring Method
Wire the sensors and outputs, then wire the power connection.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 18 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
• For the 24 Vac connections: single wire – from 14 to 18
AWG solid or stranded
• For S-BUS wiring, the sensors may be mounted up to 200
ft. (61 m) from the JADE controller. When the length of wire
is over 100 feet use twisted pair shielded wire.
• All sensor wiring to the Sylk bus and analog sensors is
polarity insensitive.
Prepare wiring for the terminal blocks, as follows:
1. Remove the plastic tabs from the side of the controller
where the connectors will slide onto the PWA.
2. Strip 1/2 in. (13 mm) insulation from the conductor.
3. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the
required terminal location and tighten the screw.
4. If two or more wires are being inserted into one terminal
location, twist the wires together a minimum of three
turns before inserting them to ensure proper electrical
contact. See Fig. 5 on page 6.
5. Cut the twisted end of the wires to 3/16 in. (5 mm) before
inserting them into the terminal and tightening the screw.
6. Pull on each wire in all terminals to check for good
mechanical connection.
Economizer Module Wiring Details
The wiring connection terminals for each module/sensor are:
• “JADE™ Economizer Module Wiring” on this page.
• “Sylk Bus Sensor Wiring” on page 7.
JADE™ Economizer Module Wiring
Use Fig. 6 and Tables 1 and 2 to locate the wiring terminals for
the Economizer module.
NOTE: The four terminal blocks are removable. You can
slide out each terminal block, wire it, and then
slide it back into place.
Fig. 5. Attaching two or more wires at terminal blocks.
Table 1. Economizer Module - Left hand terminal blocks.
LabelTypeDescription
Top Left Terminal Block
MAT
MAT
20k NTC
and
Mixed Air Temperature Sensor
(polarity insensitive connection)
COM
OAT
OAT
20k NTC
and
Outdoor Air Temperature Sensor
(polarity insensitive connection)
COM
S-BUS
S-BUS
SYLK Bus Sylk Bus sensor
(polarity insensitive connection)
Bottom Left Terminal Block
IAQ 2-102-10 VdcAir Quality Sensor Input
(e.g. CO
sensor)
2
IAQ COM COMAir Quality Sensor Common
IAQ 24V24 VacAir Quality Sensor 24 Vac Source
ACT 2-102-10 VdcDamper Actuator Output (2-10 Vdc)
ACT COM COMDamper Actuator Output Common
ACT 24V24 VacDamper Actuator 24 Vac Source
n/aThe bottom pin is not used.
63-2700—106
JADE™ ECONOMIZER MODULE
DIP
SWITCH
LABEL
M32271B
SYLK BUS
TERMINALS
(1 AND 2)
DIP
SWITCHES
(3)
SYLK BUS
2 PIN SIDE
CONNECTOR
Table 2. Economizer Module - Right hand terminal blocks.
LabelTypeDescription
Top Right Terminal Block
n/aThe first pin is not used
AUX2 I24 Vac INShut Down (SD) or Heat (W)
Conventional only
or
Heat Pump Changeover (O/B) in
Heat Pump mode.
OCC24 Vac INOccupied / Unoccupied Input
E-GNDEGNDEarth Ground - System Required
EXH124 Vac OUT Exhaust Fan 1 Output
AUX1 O24 Vac OUT Programmable:
Exhaust fan 2 output
or
ERV
or
System Alarm output.
Bottom Right Terminal Block
Y2-I24 Vac INY2 in - Cooling Stage 2 Input from
space thermostat
Y2-O24 Vac OUT Y2 out - Cooling Stage 2 Output to
stage 2 mechanical cooling
Y1-I24 Vac INY1 in - Cooling Stage 1 Input from
space thermostat
Y1-O24 Vac OUT Y1 out - Cooling Stage 1 Output to
stage 1 mechanical cooling
CCOM24 Vac Common
R24 Vac24 Vac Power (Hot)
Sylk Bus Sensor Wiring
The labels on the sensors and controller are color coded for
ease of installation. Orange labeled sensors can only be wired
to orange terminals on the controller. Brown labeled sensors
can only be wired to S-bus (brown) terminals. Use Fig. 7 and
Table 3 to locate the wiring terminals for each Sylk Bus sensor.
Use Fig. 7 and Table 4 to set the DIP switches for the desired
use of the sensor.
Table 3. SYLK Bus Sensor Wiring Terminations.
Terminal
TypeDescriptionNbrLabel
1S-BUS SYLK
Bus
2S-BUS SYLK
Bus
Sylk Bus Communications
(Sensor Bus) polarity insensitive
Sylk Bus Communications
(Sensor Bus) polarity insensitive
Table 4. SYLK Bus Sensor DIP Switch Settings.
DIP Switch Positions for Switches 1, 2, & 3
Use
a
DA
b
RA
c
OA
a
DA = Discharge Air
b
RA = Return Air
c
OA = Outdoor Air
123
OFFONOFF
ONOFFOFF
OFFOFFOFF
NOTE: When using the Sylkbus sensors there will be a
slight delay while the Jade controller and the
sensor communicate. Analog sensors do not
communicate on the Sylkbus and output a 20k
ohm signal to the Jade controller so the response
time is instantaneous.
NOTE: When using the C7400S (Sylk bus enthalpy)
sensor there is an operation that will allow test of
the operation of the W7220 economizer when the
outdoor air conditions (temperature and humidity)
are too high for economizing.
1. Remove the C7250A dry bulb sensor from the OAT
terminals IF you are using temperature only economizing
change over.
2. If you are using enthalpy change over and have a
C7400S sensor with a date code prior to 1301, remove
the sensor and replace it with one with a date code after
1301.
3. Connect a C7400S Sylk bus sensor to the S-Bus
terminals (brown colored) on the W7220A Jade using
18 AWG to 22 AWG solid or stranded wires.
4. Check the STATUS screen for actual outdoor air (OA)
temperature and OA humidity readings.
5. Change the 3-position DIP switch on the C7400S sensor
from 1 OFF, 2 OFF, 3 OFF to 1 ON, 2 ON, 3 ON position
and immediately back to 1 OFF, 2 OFF 3 OFF position.
6. The output of the C7400S sensor to the W7220A will be
40 ºF and 40 %RH which will allow the economizer to go
into free cooling mode (economizing available).
7. Make sure you have 24 Vac on terminal Y1 In to simulate
a call for cooling.
8. After 15 minutes the C7400S sensor will change back to
the actual OA temperature and humidity.
NOTE: If you removed a dry bulb sensor, remove the
C7400S from the S-bus terminals and replace the
OAT sensor onto the OAT terminals.
Fig. 7. Sylk Bus sensor DIP switches.
763-2700—10
JADE™ ECONOMIZER MODULE
Actuator Wiring Options:
1. The JADE economizer controller can only have one (1)
communicating actuator connected to it.
2. Up to four (4) non-communicating and two (2) 2-position
actuators (1 each on EXH1 and AUX1 O)
3. One (1) communicating and up to four (4) non-communicating and two (2) 2-position actuators (1 each on EXH1
and AUX1 O). When using a 2-position actuator on the
AUX1 O, the AUX1 O must be programmed for Exh2 and
the % open is the % open of the outdoor damper when
the 2-pos actuator opens. Connect 24 V to Exh1 and/or
AUX1 O and ground to the Jade "C" terminal.
CO2 Sensor Wiring
When using the C7232 Honeywell CO2 sensors the black and
brown common wires are internally connected and only one is
connected to "IAQ COM" on the Jade. Use the power from the
Jade to power the CO2 sensor OR make sure the ground for
the power supplies are common. See wiring diagram below for
the C7232 and C7632 wiring diagrams.
NOTE: When using the C7632 (or any 0-10 Vdc CO
sor) with the Jade you will need to set the
CO2ZERO to 400 ppm and the CO2SPAN to
1600 ppm in the ADVANCED SETUP menu.
NOTE: When using the TR40 CO
on the TR40-CO2 to 6. Only one TR40 CO
sensor set the address
2
can be used with the Jade economizer controller.
Address 6 is for a CO
communicating actuator.
sensor, address 11 is for a
2
sen-
2
sensor
2
C7232
ANALOG
24V
OUT
+
–
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
L1
(HOT)
L2
1
1 POWER SUPPLY. PROVIDE
DISCONNECT MEANS AND
OVERLOAD PROTECTION
AS REQUIRED.
Fig. 8. Wiring for C7232
C7632
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 9. Wiring for C7632
L1
(HOT)
L2
1
0-10 VDC
M34095
M17543B
63-2700—108
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O
Y1I
Y2I
OCC
24 VAC
1K1
1K1
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MA
MA
OAT
OAT
C R
M28980D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V)
ACT COM
ACT 24V
AUX1-0
AUX2-I
OA TEMP
SENSOR
20K NTC
M7215
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.
1
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O
OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
3
3
1
MA TEMP
SENSOR
20K NTC
+
-
TR1
TR
IN
IN
2
R(+)
C(-)
1
2
ACTUATOR
EXH1 OR AUX1 O
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1
O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN
PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT
OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE
EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS
DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL
PROGRAM AUX1 O FOR EXH2.
C
M33409
V
WIRING APPLICATION EXAMPLES
This section shows the wiring configurations for the JADE™ Economizer system.
Stand-alone Economizer
The most basic configuration is the stand-alone Economizer (see Fig. 10 and Fig. 15).
A stand-alone Economizer is directly wired to sensors, actuators, thermostat, and mechanical cooling controls in the roof top unit.
It does not require Sylk Bus communications.
Fig. 10. Stand-alone dry bulb Economizer configuration with black motor M7215.
Fig. 11. 2-position actuator.
963-2700—10
JADE™ ECONOMIZER MODULE
M35158
TO THERMOSTAT
STATUS
LEDS
SENSORS
CONV
POWER
HEAT
COOL
FAN
U1
U2
U3
A
EIM
JADE W7220A1000
ON JADE CONTROLLER:
1. Y2-O CONNECT TO STAGE 2 MECHANICAL COOLING
2. Y1-O CONNECT TO STAGE 1 MECHANICAL COOLING
3. MAT IS MIXED AIR SENSOR C7250A1001
4. OAT IS TEMPERATURE CHAGEOVER C7250A1001
SENSOR OR S-BUS OA ENTHALPY SENSOR C7400S1000
5. AUX1 OUT PROGRAM TO SYS IN SYSTEM SETUP MENU
OCC
E-GND
AUX1 OUT
AUX2-I
Y1O
Y2O
Y1I
Y2I
C
TRANSFORMER
24
VAC
120
VAC
C
R
R
1
2
3
4
5
KIT WITH PRESTIGE AND EIM
YTHX9421R5051
EIM
THM5421R1013
RELAY
R822N1011
MS3103J1030
COMMUNICATING DCA
1
3
PRESTIGE
THX9421R5013
C
R
1
THE TRANSFORMER NEEDS
TO BE 100VA.
1
Fig. 12. Prestige and EIM with communicating actuator.
63-2700—1010
Loading...
+ 22 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.