Honeywell W7220 Data Sheet

63-2700-10
JADE™ Economizer Module
(MODEL W7220)

System Components

The JADE™ Economizer System includes an Economizer Module, 20k mixed air sensor, damper actuator, an optional CO
sensor, and either a 20k outdoor air temperature sensor
2
or Sylk Bus sensors for measuring Outdoor Air and return air enthalpy, temperature, and humidity.
Economizer Module
This is the core of the JADE™ Economizer System and includes the user interface for the system. The W7220 Economizer Module provides the basic inputs and outputs to provide simple economizer control. When used with the optional Sylk Bus sensors, the Economizer Module provides more advanced economizer functionality.
Sylk Bus Sensors (optional)

PRODUCT DESCRIPTION

The JADE™ Economizer System is an expandable economizer control system, which includes a W7220 Economizer Module (controller) with an LCD and keypad. The W7220 can be configured with optional sensors.
The W7220 Economizer Module can be used as a stand­alone economizer module wired directly to a commercial set back space thermostat and sensors to provide Outdoor Air dry-bulb economizer control.
The W7220 Economizer Module can be connected to optional Sylk Bus sensors for single or differential enthalpy control. The W7220 Economizer Module provides power and communications on the Sylk Bus for the Sylk Bus sensors.
The W7220 Economizer Module automatically detects sensors by polling to determine which sensors are present. If a sensor loses communications after it has been detected, the W7220 Economizer indicates a device fail error on its LCD.
The Sylk Bus Sensor is a combination temperature and humidity sensor which is powered by and communicates on the Sylk Bus. Up to three sensors may be configured with the JADE™ Economizer Module. See page 2 for details.
CO2 Sensor (optional)
A CO2 sensor can be added for Demand Control Ventilation (DCV). Either an analog (2-10 Vdc) or a wall-mount Sylk bus TR40 CO2 sensor can be used with the Jade economizer.
PC MOD Tool (optional)
The PC MOD tool is connected to a personal computer and communicates with the Jade economizer controller via the Sylk bus. The W7220 PCMOD tool software is free and can be downloaded from the url in the Accessories section.
Some features on the Jade controller can only be enabled or disabled using the W7220 PC MOD tool. See the PC MOD tool options section in Table 5.
Product Description .......................................................... 1
Specifications ................................................................... 2
Before Installation ............................................................ 3
Installation and Setup ...................................................... 3
Mounting .......................................................................... 3
Wiring ............................................................................... 4
Wiring Application Examples ........................................... 9
Interface Overview ........................................................... 18
Setup and Configuration .................................................. 18
Checkout .......................................................................... 30
Troubleshooting ................................................................ 31
PRODUCT DATA
Contents
E4436E4436
JADE™ ECONOMIZER MODULE

SPECIFICATIONS

W7220A Economizer Module

The module is designed for use with any Honeywell 2 to 10 Vdc or Honeywell Sylkbus communicating actuator. The module includes terminals for a CO and an Outdoor Dry Bulb sensor. Enthalpy and other options are available with Sylk Bus sensors.
User Interface: Provides status for normal operation, setup
parameters, checkout tests, and alarms and error conditions with a 2-line 16 character LCD display and a four button keypad.

Electrical

Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5 VA
without sensors or actuators
Relay Digital Output Rating at 30 Vac (maximum power from Class 2 input only): 1.5A run;
3.5A inrush @ 0.45PF (200,000 cycles) or
7.5A inrush @ 0.45PF (100,000 cycles)
External Sensors Power Output: 21 Vdc +/- 5% @ 48mA
IMPORTANT
All inputs and outputs must be Class 2 wiring.
Inputs
sensor, Mixed Air sensor,
2
Dry Bulb Temperature (optional) and Mixed Air (required), C7250A:
2-wire (18 to 22 AWG); Temperature range -40 to 150 °F (-40 to 65 °C). Temperature accuracy -0°F/+2°F
Temperature and Humidity, C7400S1000 (optional):
Sylk Bus; 2-wire (18 to 22 AWG) Temperature: range -40 to 150 °F (-40 to 65 °C) Temperature accuracy -0°F/+2°F Humidity: range 0 to 100% RH with 5% accuracy.
NOTE: Up to three (3) SYLK Bus sensors may be
connected to the JADE™ Economizer module. For outdoor air (OA), return air (RA) and discharge (supply) air (DA).
DCV (CO
2-10 Vdc control signal; minimum impedance >50k ohm.
4 Binary inputs:
1-wire 24 Vac + common GND (see page 6 for wiring details). 24 Vac power supply: 20 to 30 Vac 50/60Hz; 100 VA Class 2 transformer.
) Sensor (C7232 or C7632):
2
Outputs
Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O: All Relay Outputs (at 30 Vac):
Running: 1.5A maximum Inrush: 7.5A maximum
SENSORS:
NOTE: A Mixed Air (MA) analog sensor is required on all
W7220 units; either an Outdoor Air (OA) sensor for dry bulb change over or an OA Sylkbus sensor for outdoor enthalpy change over is required in addition to the MA sensor. An additional Return Air (RA) Sylkbus sensor can be added to the system for differential enthalpy or dry bulb changeover. For differential dry bulb changeover a 20k ohm sensor is required in the OA and a Sylkbus sensor in the RA. Dip switch on RA Sylkbus sensor must be set in the RA position.

Environmental

Operating Temperature: -40 to 150 °F (-40 to 65 °C).
Exception of display operation down to -4 °F with full recovery at -4 °F from exposure to -40 °F
Storage Temperature: -40 to 150 °F (-40 to 65 °C)
Shipping Temperature: -40 to 150 °F (-40 to 65 °C)
Relative Humidity: 5% to 95% RH non-condensing
Dimensions (See Fig. 1 on page 3):
Height: 4.98 inches (126.4 mm) Width: 6.3 inches (160 mm) Depth: 1.34 inches (34 mm)
Weight: 0.58 lb. (0.265 kg)
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
63-2700—10 2
JADE™ ECONOMIZER MODULE
4-63/64
(126)
6-19/64 (160)
MOUNTING HOLE (X2)
M32273A
3-5/32 (80)
Approvals: UL listed (XAPX) for USA and Canada;
California Energy Commission (CEC) FDD ID number HJW10.
Fig. 1. Dimensions in inches (mm) showing mounting
holes.

Accessories

— 50048926-001 2-pin edge connector for sensors (20
pieces per bag)
— 50048926-002 6-pin edge connector for field wiring (20
pieces per bag) — C7250A 20k sensor for MA or OA (dry bulb changeover) — C7400S Sylkbus sensor for enthalpy control in OA and/
or RA and RA for differential dry bulb changeover — W7220 PCMOD interface tool for JADE controller and
Personal Computer. For the software, go to
www.customer.honeywell.com/economizertools — 50053060-001 Duct mounting kit for sensors — C7632 or C7232 CO
Sylk bus CO
sensor
2
analog sensors OR one TR40
2

INSTALLATION AND SETUP

The following installation procedures should be performed in the order listed:
1. Mounting — see page 3.
2. Wiring — see page 4.
3. Interface and Programming overview – see page 18.
4. Setup and Configuration — see page 18
5. Checkout — see page 30.
Troubleshooting and Alarms—see page 31.

MOUNTING

This section describes the mounting procedures for the JADE™ Economizer module and the sensors.

Economizer Module Location and Mounting

IMPORTANT
Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the module’s circuit board, or in areas where escaping gas or other explosive vapors are present.
IMPORTANT
The module must be mounted in a position that allows clearance for wiring, servicing, and removal.
Mount the Economizer module on any convenient interior location using the two mounting holes provided on the enclosure using #6 or #8 screws (screws are not provided and must be obtained separately). Use the dimensions in Fig. 1 on page 3 as a guide.

BEFORE INSTALLATION

Review the “Specifications” on page 2 before installing the The JADE™ Economizer System.

When Installing This Product

1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi­tion.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
NOTE: Jade will be in the "set up" mode for the first 60
minutes after powered. If a sensor for OA air or Sylkbus device (sensor, actuator) is disconnected during the set up mode, the Jade will not alarm that failure. The MA sensor is a system "critical" sensor, if the MA sensor is removed during the set up mode, the Jade will alarm. After 60 minutes the Jade controller will change to operation mode and all components removed or failed will alarm in the operation mode.
The Economizer module may be mounted in any orientation. However, mounting in the orientation shown in Fig. 1 on page 3 permits proper viewing of the LCD display and use of the keypad.

Sensor Location and Mounting

The JADE™ Economizer W7220 uses digital and communicating sensors for control. The C7250 temperature sensors (MA for all applications and is mounted in the mixed air section of a rooftop unit either directly to the sheet metal using self tapping sheet metal screws or in the air stream using the duct mounting kit. Duct mount kit is part number 50053060-001.
Optional OA, RA the W7220 on the two-wire communication bus and can either be wired using a two pin header or using a side connector. Each Sylkbus sensor includes a two pin side connector with the packaging. The SKU number of the Sylkbus sensor is C7400S. All OA, RA and DA sensors are the same SKU
a
MA = Mixed Air
b
OA = Outdoor Air
c
RA = Return Air
d
DA = Discharge Air
3 63-2700—10
a
and OAb) are 20k NTC. A MA sensor is required
c
and DAd Sylkbus sensors communicate with
JADE™ ECONOMIZER MODULE
WARNING
CAUTION
ROD - 1 PIECE
FLANGE - 1 PIECE
GASKET - 1 PIECE
M32281A
WIRE HO LDER
EXTENDED RELIEF
(FOR CORRECT MOUNTING)
M32282A
LENGTH ADJUSTS
6-12 INCHES
number. The sensor is set for the appropriate type of sensing using the three position DIP switch located on the sensor. OA position is OFF, OFF, OFF; RA is ON, OFF, OFF and DA is OFF, ON, OFF. During installation the sensors are set for the usage desired. See “Sylk Bus Sensor Wiring” on page 7 for DIP switch details.
NOTE: The protective film on the dip switch is only nec-
essary during the factory assembly process. Sim­ply push through the film to set the dip switches; this will not harm the device.
Once installed, a sensor can be changed to a different application by simply changing the DIP switch setting.
Sensor Mounting
The sensors can be mounted directly on to the sheet metal of unit or can be mounted in the air stream using the duct mounting kit (order separately).
The kit contains a rod to hold the sensor in the duct, a flange to secure the sensor rod to the duct wall and fill the hole and a gasket to prevent air from leaking through the duct wall. There are five (5) kits in each bag assembly. See Fig. 2.
The rod has slots for threading the wire to prevent loose or hanging wire in the duct and can be adjusted for 6 to 12 inch length. The flange has extended relief for ease of mounting. See Fig. 3.
Fig. 3. Duct Mounting Adjustments.
Fig. 2. Duct Mounting Kit (Part No. 50053060-001).

WIRING

All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Module wiring in the field is terminated to the four screw terminal blocks located on the left and right sides.
Module wiring at the OEM factory is terminated via the header pin terminals located on the left and right sides. The header terminal pins and the terminal blocks have common terminations for the appropriate input or output. See OEM wiring diagram in Fig. 20.
The remainder of this section describes the wiring for the JADE™ Economizer module, W7220A.
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.
Equipment Damage Hazard. Electrostatic discharge can short equipment circuitry.
Ensure that you are properly grounded before handling the unit.
63-2700—10 4
JADE™ ECONOMIZER MODULE
DISCHARGE AIR SENSOR
C7400S
DIRECT EXPANSION COIL
C7400S
ENTHALPY SENSOR
C7400S
ENTHALPY SENSOR
RETURN AIR
OUTDOOR AIR
C7250A
MIXED AIR SENSOR
TWO STAGE COOL PROGRAMMABLE THERMOSTAT
FOR DIFFERENTIAL ENTHALPY, THE TWO C7400S ENTHALPY SENSORS ARE CONNECTED TO THE W7720A ECONOMIZER CONTROL ONE IS MOUNTED IN RETURN AIR, AND THE OTHER IS MOUNTED IN OUTDOOR AIR. DIFFERENTIAL ENTHALPY CONTROL PROVIDES GREATER ENERGY SAVINGS THAN SINGLE ENTHALPY.
M35163
1
1
1
MS3103J MS3105J MS7505 ACTUATOR
W7720A
Fig. 4. Location of Outdoor Air, Return Air, Mixed Air, and Discharge Air Sensors in an economizer system.
5 63-2700—10
JADE™ ECONOMIZER MODULE
1/2 (13)
1. STRIP 1/2 IN. (13 MM) FROM WIRES TO BE ATTACHED AT ONE TERMINAL.
2. TWIST WIRES TOGETHER WITH PLIERS (A MINIMUM OF THREE TURNS).
3. CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION.
M24382A
JADE CONTROLLER
LEFT TERMINAL BLOCK LABEL
RIGHT TERMINAL BLOCK LABEL
M32283C
AUX2-I
AUX1-O
AUX2-I
OCC
E-GND
EXH1
AUX1-O
Y2-I
Y2-O
Y1-I
Y1-O
C
R

Economizer Module Wiring Method

Wire the sensors and outputs, then wire the power connection.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 18 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
• For the 24 Vac connections: single wire – from 14 to 18 AWG solid or stranded
• For S-BUS wiring, the sensors may be mounted up to 200 ft. (61 m) from the JADE controller. When the length of wire is over 100 feet use twisted pair shielded wire.
• All sensor wiring to the Sylk bus and analog sensors is polarity insensitive.
Prepare wiring for the terminal blocks, as follows:
1. Remove the plastic tabs from the side of the controller where the connectors will slide onto the PWA.
2. Strip 1/2 in. (13 mm) insulation from the conductor.
3. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the
required terminal location and tighten the screw.
4. If two or more wires are being inserted into one terminal location, twist the wires together a minimum of three turns before inserting them to ensure proper electrical contact. See Fig. 5 on page 6.
5. Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening the screw.
6. Pull on each wire in all terminals to check for good mechanical connection.

Economizer Module Wiring Details

The wiring connection terminals for each module/sensor are:
• “JADE™ Economizer Module Wiring” on this page.
• “Sylk Bus Sensor Wiring” on page 7.
JADE™ Economizer Module Wiring
Use Fig. 6 and Tables 1 and 2 to locate the wiring terminals for the Economizer module.
NOTE: The four terminal blocks are removable. You can
slide out each terminal block, wire it, and then slide it back into place.
Fig. 5. Attaching two or more wires at terminal blocks.
Fig. 6. W7220 Economizer module terminal connection
labels.
Table 1. Economizer Module - Left hand terminal blocks.
Label Type Description
Top Left Terminal Block
MAT MAT
20k NTC and
Mixed Air Temperature Sensor (polarity insensitive connection)
COM
OAT OAT
20k NTC and
Outdoor Air Temperature Sensor (polarity insensitive connection)
COM
S-BUS S-BUS
SYLK Bus Sylk Bus sensor
(polarity insensitive connection)
Bottom Left Terminal Block
IAQ 2-10 2-10 Vdc Air Quality Sensor Input
(e.g. CO
sensor)
2
IAQ COM COM Air Quality Sensor Common
IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source
ACT 2-10 2-10 Vdc Damper Actuator Output (2-10 Vdc)
ACT COM COM Damper Actuator Output Common
ACT 24V 24 Vac Damper Actuator 24 Vac Source
n/a The bottom pin is not used.
63-2700—10 6
JADE™ ECONOMIZER MODULE
DIP SWITCH LABEL
M32271B
SYLK BUS TERMINALS (1 AND 2)
DIP SWITCHES (3)
SYLK BUS 2 PIN SIDE CONNECTOR
Table 2. Economizer Module - Right hand terminal blocks.
Label Type Description
Top Right Terminal Block
n/a The first pin is not used
AUX2 I 24 Vac IN Shut Down (SD) or Heat (W)
Conventional only or Heat Pump Changeover (O/B) in Heat Pump mode.
OCC 24 Vac IN Occupied / Unoccupied Input
E-GND EGND Earth Ground - System Required
EXH1 24 Vac OUT Exhaust Fan 1 Output
AUX1 O 24 Vac OUT Programmable:
Exhaust fan 2 output or ERV or System Alarm output.
Bottom Right Terminal Block
Y2-I 24 Vac IN Y2 in - Cooling Stage 2 Input from
space thermostat
Y2-O 24 Vac OUT Y2 out - Cooling Stage 2 Output to
stage 2 mechanical cooling
Y1-I 24 Vac IN Y1 in - Cooling Stage 1 Input from
space thermostat
Y1-O 24 Vac OUT Y1 out - Cooling Stage 1 Output to
stage 1 mechanical cooling
C COM 24 Vac Common
R 24 Vac 24 Vac Power (Hot)
Sylk Bus Sensor Wiring
The labels on the sensors and controller are color coded for ease of installation. Orange labeled sensors can only be wired to orange terminals on the controller. Brown labeled sensors can only be wired to S-bus (brown) terminals. Use Fig. 7 and Table 3 to locate the wiring terminals for each Sylk Bus sensor.
Use Fig. 7 and Table 4 to set the DIP switches for the desired use of the sensor.
Table 3. SYLK Bus Sensor Wiring Terminations.
Terminal
Type DescriptionNbr Label
1 S-BUS SYLK
Bus
2 S-BUS SYLK
Bus
Sylk Bus Communications (Sensor Bus) polarity insensitive
Sylk Bus Communications (Sensor Bus) polarity insensitive
Table 4. SYLK Bus Sensor DIP Switch Settings.
DIP Switch Positions for Switches 1, 2, & 3
Use
a
DA
b
RA
c
OA
a
DA = Discharge Air
b
RA = Return Air
c
OA = Outdoor Air
123
OFF ON OFF
ON OFF OFF
OFF OFF OFF
NOTE: When using the Sylkbus sensors there will be a
slight delay while the Jade controller and the sensor communicate. Analog sensors do not communicate on the Sylkbus and output a 20k ohm signal to the Jade controller so the response time is instantaneous.
NOTE: When using the C7400S (Sylk bus enthalpy)
sensor there is an operation that will allow test of the operation of the W7220 economizer when the outdoor air conditions (temperature and humidity) are too high for economizing.
1. Remove the C7250A dry bulb sensor from the OAT
terminals IF you are using temperature only economizing change over.
2. If you are using enthalpy change over and have a C7400S sensor with a date code prior to 1301, remove the sensor and replace it with one with a date code after
1301.
3. Connect a C7400S Sylk bus sensor to the S-Bus terminals (brown colored) on the W7220A Jade using 18 AWG to 22 AWG solid or stranded wires.
4. Check the STATUS screen for actual outdoor air (OA) temperature and OA humidity readings.
5. Change the 3-position DIP switch on the C7400S sensor from 1 OFF, 2 OFF, 3 OFF to 1 ON, 2 ON, 3 ON position and immediately back to 1 OFF, 2 OFF 3 OFF position.
6. The output of the C7400S sensor to the W7220A will be 40 ºF and 40 %RH which will allow the economizer to go into free cooling mode (economizing available).
7. Make sure you have 24 Vac on terminal Y1 In to simulate a call for cooling.
8. After 15 minutes the C7400S sensor will change back to the actual OA temperature and humidity.
NOTE: If you removed a dry bulb sensor, remove the
C7400S from the S-bus terminals and replace the OAT sensor onto the OAT terminals.
Fig. 7. Sylk Bus sensor DIP switches.
7 63-2700—10
JADE™ ECONOMIZER MODULE
Actuator Wiring Options:
1. The JADE economizer controller can only have one (1)
communicating actuator connected to it.
2. Up to four (4) non-communicating and two (2) 2-position actuators (1 each on EXH1 and AUX1 O)
3. One (1) communicating and up to four (4) non-communi­cating and two (2) 2-position actuators (1 each on EXH1 and AUX1 O). When using a 2-position actuator on the AUX1 O, the AUX1 O must be programmed for Exh2 and the % open is the % open of the outdoor damper when the 2-pos actuator opens. Connect 24 V to Exh1 and/or AUX1 O and ground to the Jade "C" terminal.

CO2 Sensor Wiring

When using the C7232 Honeywell CO2 sensors the black and brown common wires are internally connected and only one is connected to "IAQ COM" on the Jade. Use the power from the Jade to power the CO2 sensor OR make sure the ground for the power supplies are common. See wiring diagram below for the C7232 and C7632 wiring diagrams.
NOTE: When using the C7632 (or any 0-10 Vdc CO
sor) with the Jade you will need to set the CO2ZERO to 400 ppm and the CO2SPAN to 1600 ppm in the ADVANCED SETUP menu.
NOTE: When using the TR40 CO
on the TR40-CO2 to 6. Only one TR40 CO
sensor set the address
2
can be used with the Jade economizer controller. Address 6 is for a CO communicating actuator.
sensor, address 11 is for a
2
sen-
2
sensor
2
C7232
ANALOG
24V
OUT
+
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
L1 (HOT)
L2
1
1 POWER SUPPLY. PROVIDE
DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 8. Wiring for C7232
C7632
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 9. Wiring for C7632
L1 (HOT)
L2
1
0-10 VDC
M34095
M17543B
63-2700—10 8
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC
24 VAC
1K1
1K1
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2 SENSOR 2-10 VDC
(OPTIONAL)
MA MA
OAT OAT
C R
M28980D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V
AUX1-0
AUX2-I
OA TEMP
SENSOR
20K NTC
M7215
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.
1
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
3
3
1
MA TEMP
SENSOR 20K NTC
+
-
TR1
TR
IN
IN
2
R(+)
C(-)
1
2
ACTUATOR
EXH1 OR AUX1 O
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1 O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL PROGRAM AUX1 O FOR EXH2.
C
M33409
V

WIRING APPLICATION EXAMPLES

This section shows the wiring configurations for the JADE™ Economizer system.

Stand-alone Economizer

The most basic configuration is the stand-alone Economizer (see Fig. 10 and Fig. 15).
A stand-alone Economizer is directly wired to sensors, actuators, thermostat, and mechanical cooling controls in the roof top unit. It does not require Sylk Bus communications.
Fig. 10. Stand-alone dry bulb Economizer configuration with black motor M7215.
Fig. 11. 2-position actuator.
9 63-2700—10
JADE™ ECONOMIZER MODULE
M35158
TO THERMOSTAT
STATUS
LEDS
SENSORS
CONV
POWER
HEAT
COOL
FAN
U1
U2
U3
A
EIM
JADE W7220A1000
ON JADE CONTROLLER:
1. Y2-O CONNECT TO STAGE 2 MECHANICAL COOLING
2. Y1-O CONNECT TO STAGE 1 MECHANICAL COOLING
3. MAT IS MIXED AIR SENSOR C7250A1001
4. OAT IS TEMPERATURE CHAGEOVER C7250A1001 SENSOR OR S-BUS OA ENTHALPY SENSOR C7400S1000
5. AUX1 OUT PROGRAM TO SYS IN SYSTEM SETUP MENU
OCC E-GND
AUX1 OUT
AUX2-I
Y1O
Y2O Y1I
Y2I
C
TRANSFORMER
24
VAC
120 VAC
C
R
R
1 2 3 4 5
KIT WITH PRESTIGE AND EIM YTHX9421R5051
EIM THM5421R1013
RELAY R822N1011
MS3103J1030 COMMUNICATING DCA
1
3
PRESTIGE THX9421R5013
C R
1
THE TRANSFORMER NEEDS TO BE 100VA.
1
Fig. 12. Prestige and EIM with communicating actuator.
63-2700—10 10
Loading...
+ 22 hidden pages