Honeywell W7220 Installation Guide

Page 1
JADE™ Economizer Module
(MODEL W7220)
INSTALLATION INSTRUCTIONS
for differential enthalpy changeover. JADE can be used with a CO2 indoor air sensor for Demand Control Ventilation and with a VFD for two speed fan operation.
This document describes wiring, power up, basic troubleshooting, and common installation issues for the JADE™ Economizer Module (Model W7220). For further information on mounting and operation, refer to Honeywell document 63-2700.

BEFORE INSTALLATION

Review the following before installing the The W7220:

Electrical

Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
Relay Digital Output Rating: 30 Vac
IMPORTANT
All inputs and outputs must be Class 2 wiring.

Inputs

A Mixed air (MA) analog sensor is required on all W7220 units; either an OA (Outdoor Air) sensor for dry bulb change over or an OA Sylkbus sensor for outdoor enthalpy change over is required in addition to the MA sensor. An additional Return Air (RA) Sylkbus sensor can be added to the system
DCV (CO
) Sensor (C7232): 2-10 Vdc control signal;
2
minimum impedance >50k ohm.

Outputs

Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac) All Relay Outputs (at 30 Vac):
Running: 1.5A maximum Inrush: 7.5A maximum

When Installing This Product

1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi­tion.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service techni­cian.
4. After installation is complete, check out product opera­tion as provided in these instructions.
5. For additional detailed information on this product go to customer.honeywell.com and download the product data sheet (lit no 63-2700) or scan QR code located on the label above MAT terminals with your smart phone.

Accessories

50048926-001 2-pin edge connector for sensors
(20 pieces per bag)
50048926-002 6-pin edge connector for field wiring
(20 pieces per bag) C7250 20k sensor for MA or OA (dry bulb changeover) C7400S Sylkbus sensor for enthalpy control in OA and/or RA
and RA for differential dry bulb changeover W7220 PCMOD interface tool for JADE controller and Per-
sonal Computer. Go to www.customer.honeywell.com/
economizertools for the software 50053060-001 Duct mounting kit for sensors C7632 or C7232 CO
sensors
2
62-0331-13
Page 2
JADE™ ECONOMIZER MODULE
WARNING
CAUTION

INSTALLATION AND SETUP

The Economizer module may be mounted in any orientation. However, mounting in the orientation shown above permits proper viewing of the LCD display and use of the keypad.
NOTE: JADE will be in the “set up” mode for the first 60
minutes after powered. If a sensor for OA air or Sylkbus device (sensor, actuator) is discon­nected during the set up mode, the JADE will not alarm that failure. The MA sensor is a system “critical” sensor; if the MA sensor is removed during the set up mode, the JADE will alarm. After 60 minutes the JADE controller will change to operation mode and all components removed or failed will alarm in the operation mode.

WIRING

All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Module wiring in the field is terminated to the four screw terminal blocks located on the left and right sides.
Module wiring at the OEM factory is terminated via the header pin terminals located on the left and right sides. The header terminal pins and the terminal blocks have common terminations for the appropriate input or output. The part number for the OEM female mating connector is 0039973997.
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.

Actuator Wiring Options:

1. The JADE economizer controller can only have one (1)
communicating actuator connected to it.
2. Up to four (4) non-communicating and (2) 2-position actuators (1 each on EXH1 and AUX1 O)
3. One (1) communicating and up to four (4) non-commu­nicating and (2) 2-position actuators (1 each on EXH1 and AUX1 O)
When using a 2-position actuator on the AUX1 O the AUX1 O must be programmed for Exh2 and the % open is the % open of the outdoor damper when the 2-pos actuator opens. Connect 24 V to Exh1 and/or AUX1 O and ground to the JADE “C” terminal.
Note the W7220 economizer will not work with an old “black motor” M7415; replace the M7415 with a M7215 or MS3103 DCA.
Table 1. Economizer Module - Left hand terminal blocks.
Label Type Description
Top Left Terminal Block
MAT MAT
OAT OAT
S-BUS S-BUS
IAQ 2-10 2-10 Vdc Air Quality Sensor Input
IAQ COM COM Air Quality Sensor Common
IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source
ACT 2-10 2-10 Vdc Damper Actuator Output (2-10 Vdc)
ACT COM COM Damper Actuator Output Common
ACT 24V 24 Vac Damper Actuator 24 Vac Source
20k NTC and COM
20k NTC and COM
SYLK Bus Sylk Bus sensor
Bottom Left Terminal Block
Mixed Air Temperature Sensor (polarity insensitive connection)
Outdoor Air Temperature Sensor (polarity insensitive connection)
(polarity insensitive connection)
(e.g. CO
sensor)
2
Equipment Damage Hazard. Electrostatic discharge can short equipment circuitry.
Ensure that you are properly grounded before handling the unit.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 18 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
• For the 24 Vac connections: single wire – from 14 to 18 AWG solid or stranded
For S-BUS wiring, the sensors may be mounted up to 200 ft. (61 m) from the JADE controller. When the length of wire is over 100 feet use twisted pair shielded wire.
NOTE: All wiring is polarity insensitive.
Refer to Fig. 1 through Fig. 7 for common wiring configurations. Refer to Fig. 8 for use with the Smart VFD. Figure 8 shows how to make a single-speed blower operate with two speeds with JADE. When the thermostat calls for first stage cooling or independent fan, the VFD will operate the fan at low speed. When the thermostat calls for first stage heat or second stage cooling, it will operate the fan at high speed. To achieve this, wire relays as shown, and configure the VFD to the minimum frequency M3.3.1 for low speed fan, and for high speed fan configure Preset frequency 1, M3.3.12.
62-0331—13 2
Table 2. Economizer Module - Right hand terminal blocks.
Label Type Description
Top Right Terminal Block
n/a The first terminal is not used
AUX2 I 24 Vac IN Shut Down (SD) or Heat (W)
Conventional only or Heat Pump Changeover (O/B) in Heat Pump mode.
OCC 24 Vac IN Occupied / Unoccupied Input
E-GND EGND Earth Ground - System Required
EXH1 24 Vac OUT Exhaust Fan 1 Output
AUX1 O 24 Vac OUT Programmable:
Exhaust fan 2 output or ERV or System Alarm output.
Bottom Right Terminal Block
Y2-I 24 Vac IN Y2 in - Cooling Stage 2 Input from
space thermostat
Y2-O 24 Vac OUT Y2 out - Cooling Stage 2 Output to
stage 2 mechanical cooling
Page 3
Table 2. Economizer Module - Right hand terminal blocks.
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC
24 VAC
1K1
1K1
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MA MA
OAT OAT
C R
M28980D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V
AUX1-0
AUX2-I
OA TEMP SENSOR
20K NTC
M7215
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.
1
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
3
3
1
MA TEMP
SENSOR 20K NTC
+
-
TR1
TR
IN
IN
2
R(+)
C(-)
Label Type Description
Y1-I 24 Vac IN Y1 in - Cooling Stage 1 Input from
space thermostat
Y1-O 24 Vac OUT Y1 out - Cooling Stage 1 Output to
stage 1 mechanical cooling
C COM 24 Vac Common
R 24 Vac 24 Vac Power (Hot)
JADE™ ECONOMIZER MODULE
Fig. 1. Stand-alone dry bulb Economizer configuration with black motor M7215.
3 62-0331—13
Page 4
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC
24 VAC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MAT MAT
OAT OAT
C R
M32564D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V
3
OAT TEMP
SENSOR 20K NTC
MS7503 OR MS7505
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
1
1
MA TEMP
SENSOR
20K NTC
R(+)
C(-)
AUX1-0
AUX2-I
2
3
2
3
1K1
1K1
Fig. 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7503 Direct Coupled Actuator.
62-0331—13 4
Page 5
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC
24 VAC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MAT MAT
OAT OAT
C R
R(+)
C(-)
M32650D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V
3
1
2
OAT TEMP
SENSOR 20K NTC
MS3103J OR MS3105J
1
1
MA TEMP
SENSOR 20K NTC
S-BUS
4
5
S-BUS
AUX1-0
AUX2-I
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
2
3
3
1K1
1K1
Fig. 3. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators.
5 62-0331—13
Page 6
JADE™ ECONOMIZER MODULE
S-BUS
S-BUS
OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
RETURN AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
MAT MAT
C R
R(+)
C(-)
M32565D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
1
4
1
2
CO2
SENSOR
2-10 VDC
(OPTIONAL)
IAQ (2-10V) IAQ COM IAQ 24V
ACT (2-10V) ACT COM ACT 24V
+
-
TR1
TR
IN
IN
M7215
MA TEMP
SENSOR 20K NTC
AUX1-0
AUX2-I
3
2
4
3
1K1
1K1
24 VAC
Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.
62-0331—13 6
Page 7
JADE™ ECONOMIZER MODULE
OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
RETURN AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
C R
R(+)
C(-)
M32566D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
1
1
2
MS7503 OR MS7505
3
S-BUS S-BUS
MAT MAT
CO2 SENSOR 2-10 VDC
(OPTIONAL)
IAQ (2-10V) IAQ COM IAQ 24V
ACT (2-10V) ACT COM ACT 24V
MA TEMP
SENSOR 20K NTC
AUX1-0
AUX2-I
2
3
4
3
4
1K1
1K1
24 VAC
Fig. 5. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7505 or MS7503 Direct
Coupled Actuator.
7 62-0331—13
Page 8
JADE™ ECONOMIZER MODULE
C7400S OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
C7400S RETURN AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
C R
C(-)
M32653D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEM/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
1
1
THE S-BUS COMPONENTS MAY BE DAISY CHAINED TO ANOTHER S-BUS COMPONENT.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
S-BUS S-BUS
MAT MAT
CO2 SENSOR 2-10 VDC
(OPTIONAL)
IAQ (2-10V) IAQ COM IAQ 24V ACT (2-10V)
ACT COM ACT 24V
MA TEMP
SENSOR 20K NTC
AUX1-0
AUX2-I
3
1
2
MS3103J OR MS3105J
S-BUS
4
5
S-BUS
2
R(+)
24 VAC
3
3
4
1K1
1K1
4
Fig. 6. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating
actuators.
62-0331—13 8
Page 9
JADE™ ECONOMIZER MODULE
M35158
TO THERMOSTAT
STATUS
LEDS
SENSORS
CONV
POWER
HEAT
COOL
FAN
U1
U2
U3
A
EIM
JADE W7220A1000
ON JADE CONTROLLER:
1. Y2-O CONNECT TO STAGE 2 MECHANICAL COOLING
2. Y1-O CONNECT TO STAGE 1 MECHANICAL COOLING
3. MAT IS MIXED AIR SENSOR C7250A1001
4. OAT IS TEMPERATURE CHAGEOVER C7250A1001 SENSOR OR S-BUS OA ENTHALPY SENSOR C7400S1000
5. AUX1 OUT PROGRAM TO SYS IN SYSTEM SETUP MENU
OCC E-GND
AUX1 OUT
AUX2-I
Y1O
Y2O Y1I
Y2I
C
TRANSFORMER
24
VAC
120 VAC
C
R
R
1 2 3 4 5
KIT WITH PRESTIGE AND EIM YTHX9421R5051
EIM THM5421R1013
RELAY R822N1011
MS3103J1030 COMMUNICATING DCA
1
3
PRESTIGE THX9421R5013
C R
1
THE TRANSFORMER NEEDS TO BE 100VA.
1
Fig. 7. Economizer with Honeywell MS3103 or MS3105 communicating actuator and thermostat EIM.
9 62-0331—13
Page 10
JADE™ ECONOMIZER MODULE
C7400S OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
C7400S RETURN AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
C R
C(-)
M35172
S-BUS S-BUS
MAT MAT
CO2 SENSOR 2-10 VDC
(OPTIONAL)
IAQ (2-10V) IAQ COM IAQ 24V ACT (2-10V)
ACT COM ACT 24V
MA TEMP
SENSOR
20K NTC
AUX1-0
AUX2-I
3
1
2
MS3103J OR MS3105J
S-BUS
4
5
S-BUS
R(+)
24 VAC
8
1K1
1K1
1
2
3
4
I/O BOARD ON SMARTVFD HVAC DRIVE HVFDSD
G
C
Y2
Y1
W1
Y1
W1
Y2
G
Y2
W1
C
C
C
C
6
14
C
RELAY 1, DPDT RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 4 FOR HIGH SPEED FAN WITH W1 CALL.
RELAY 2, DPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 4 FOR HIGH SPEED FAN WITH Y2 CALL.
RELAY 3, SPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 1 FOR LOW SPEED FAN WITH Y1 CALL.
RELAY 4, SPST RELAY, NO CONTACTS ENERGIZE DIGITAL INPUT 1 FOR LOW SPEED FAN WITH G CALL.
LOW SPEED FAN IS CONFIGURED BY SETTING “MINIMUM FREQUENCY” WITH PARAMETER M1.8 OF THE STARTUP WIZARD OF THE SMARTVFD HVAC.
HIGH SPEED FAN IS CONFIGURED BY SETTING “PRESET FREQUENCY 1” WITH PARAMETER M3.3.12 OF THE SMARTVFD HVAC.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
3
4
2
1
5
6
5
6
1 +10 Vref REFERENCE OUTPUT
2AI1+
ANALOG INPUT,
VOLTAGE OR CURRENT*
VOLTAGE
3
AI1- ANALOG INPUT COMMON
(CURRENT)
4AI2+
ANALOG INPUT,
VOLTAGE OR CURRENT
CURRENT
5
AI2 ANALOG INPUT COMMON
(CURRENT)
6 24Vou 24V AUX. VOLTAGE
7 GND I/O GROUND
8
DI1 DIGITAL INPUT 1
START FWD
9 DI2 DIGITAL INPUT 2START REV
10
DI3
DIGITAL INPUT 3
FAULT
11 CM
COMMON A FOR DIN1-DIN6**
12 24Vout 24V AUX. VOLTAGE
13 GND I/O GROUND
14 DI4
DIGITAL INPUT PRESET
FREQ SELECT 1
15 DI5
DIGITAL INPUT PRESET
FREQ
SELECT 2
16 DI6 DIGITAL INPUT 6
FAULT RESET
17
C
COMMON A FOR DIN1-DIN6**
18
AO1 ANALOG SIGNAL (+OUTPUT)
OP FREQ
19
AO-/GND ANALOG OUTPUT COMMON
30
+24 Vin
24V AUXILIARY INPUT VOLTAGE
A
RS485
DIFFERENTIAL RECEIVER/
TRANSMITTER
B
RS485
DIFFERENTIAL RECEIVER/
TRANSMITTER
BASIC I/O BOARD
TERMINAL SIGNAL DEFAULT
8
7
8
7
Fig. 8. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating
actuators, thermostat and VFD for Two-speed fan operation .
62-0331—13 10
Page 11
Fig. 9. 2-position actuator.
1
2
ACTUATOR
EXH1 OR AUX1 O
NOTE: ON/OFF ACTUATORS CAN BE USED ON THE EXH1 OR AUX1 O TERMINAL WITH GROUND TO THE C TERMINAL. WHEN PROGRAMMING THE EXH1 OR AUX1 O, THE % IS THE PERCENT OPEN POSITION OF THE OUTDOOR AIR DAMPER WHEN THE EXH1 OR AUX1 O TERMINAL IS ENERGIZED AND THE 2-POS DAMPER GOES OPEN. IF USING THE AUX1 O TERMINAL PROGRAM AUX1 O FOR EXH2.
C
M33409
V
JADE™ ECONOMIZER MODULE
ECONOMIZING
AVAILABLE
NOT AVAILABLE
TEMPERATURE
ENTHALPY
A
R
RA TEMP
)
H
R
%
(
M
U
H
ABSOLUTE HUMIDITY
DUAL ENTHALPY
SINGLE ENTHALPY
P2 (T,RH)
ES4 ES3 ES2 ES1 HL
ES5
HIGH LIMIT
P1 (T,RH)
Fig. 10. Single Enthalpy curves and boundaries.
Table 3. Single Enthalpy and Dual Enthalpy High Limit Curves.
Enthalpy
Curve
Tem p.
Dry-Bulb (°F)
Temp.
Dewpoint (°F)
Enthalpy
(btu/lb/da)
Temp. °F Humidity %RH Temp. °F Humidity %RH
Point P1 Point P2
ES1 80.0 60.0 28.0 80.0 36.8 66.3 80.1
ES2 75.0 57.0 26.0 75.0 39.6 63.3 80.0
ES3 70.0 54.0 24.0 70.0 42.3 59.7 81.4
ES4 65.0 51.0 22.0 65.0 44.8 55.7 84.2
ES5 60.0 48.0 20.0 60.0 46.9 51.3 88.5
HL 86.0 66.0 32.4 86.0 38.9 72.4 80.3
M32286
11 62-0331—13
Page 12
JADE™ ECONOMIZER MODULE

Power Up

After the module is mounted and wired, apply power.

Power Up Delay

Upon power up (or after a power outage or brownout), the W7220 controller module begins a 5 minute power up delay before enabling mechanical cooling.
Initial Menu Display
On initial start up, Honeywell displays on the first line and Economizer W7220 on the second line. After a brief pause,
the software version appears on the first line and the second line will be blank. After another brief moment the screen will display W7220 on the first line and STATUS on the second line. Refer to table 3 for menu structure.

Power Loss (Outage or Brownout)

All setpoints and advanced settings are restoreda after any power loss or interruption.
NOTE: If power goes below 18 Vac, the W7220 controller
module assumes a power loss and the 5 minute power up delay will become functional when power returns above 18 Vac.
Using the Keypad with Menus
To use the keypad when working with menus:
• Press the
• Press the
• Press the button (Enter) to display the first item in the currently displayed menu.
• Press the button (Menu up) to exit a menu’s item and return to the list of menus.
Using the Keypad with Settings and Parameters
To use the keypad when working with Setpoints, System and Advanced Settings, Checkout tests, and Alarms:
• Navigate to the desired menu.
• Press the button (Enter) to display the first item in the currently displayed menu.
•Use the parameter.
• Press the button (Enter) to display the value of the currently displayed item.
• Press the parameter value.
a
All settings are stored in non-volatile flash memory.
button to move to the previous menu. button to move to the next menu.
and buttons to scroll to the desired
button to increase (change) the displayed
a
• Press the button to decrease (change) the displayed
parameter value.
• Press the button to accept the displayed value and store it in non-volatile RAM.
• CHANGE STORED displays.
• Press the button (Enter) to return to the current menu parameter.
• Press the button (MenuUp/Exit) to return to the previous menu.
a
When values are displayed, pressing and holding the
a
or button causes the display to automatically
increment.

Menu Structure

Table 4 illustrates the complete hierarchy of menus and parameters for the JADE™ Economizer system.
The Menus in display order are:
•STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
•ALARMS
IMPORTANT
Table 4 illustrates the complete hierarchy. Your menu parameters will be different depending on your configuration.
For example if you do not have a DCV (CO then none of the DCV parameters appear and only MIN POS will display. If you have a CO2 sensor, the DCV MIN and DCV MAX will appear AND if you have 2 speed fan DCV MIN (high and low speed) and DCV MAX (high and low speed will appear).
) sensor,
2

SETUP AND CONFIGURATION

Before being placed into service, the JADE™ Economizer module must be setup and configured for the installed system.
IMPORTANT
During setup, the Economizer module is live at all times.
The setup process uses a hierarchical menu structure that is easy to use. You press the forward and backward through the menus and press the button to select and confirm setup item changes.
and arrow buttons to move
62-0331—13 12
Page 13
JADE™ ECONOMIZER MODULE
Table 4. Menu Structurea.
Parameter
Range and Increment
b
Notes
Menu Parameter
Parameter
Default
Val ue
STATUS ECON AVAIL NO YES/NO YES = economizing available; the system can use Outdoor Air for
free cooling when required.
ECONOMIZING NO YES/NO
YES = Outdoor Air being used for 1
st
stage cooling.
OCCUPIED NO YES/NO YES = OCC signal received from space thermostat or unitary
controller. YES = 24 Vac on terminal OCC No = 0 Vac on terminal OCC.
HEAT PUMP
n/a
c
COOL HEAT
Displays COOL or HEAT when system is set to heat pump (non­conventional)
COOL Y1-IN OFF ON/OFF Y1-I signal from space thermostat or unitary controller for
cooling stage 1. ON = 24 Vac on term Y1-I OFF = 0 Vac on term Y1-I
COOL Y1-OUT OFF ON/OFF Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT
terminal).
COOL Y2-IN OFF ON/OFF Y2-I signal from space thermostat or unitary controller for
second stage cooling. ON = 24 Vac on term Y2-I OFF = 0 Vac on term Y2-I
COOL Y2-OUT OFF ON/OFF Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT
terminal).
MA TEMP _ _._ ºF -40 to 150 ºF Displays value of measured mixed air from MAT sensor.
Displays --.- if not connected, short, or out- of-range.
DA TEMP _ _._ ºF -40 to 150 ºF Displays when Discharge Air Sylk Bus sensor is connected and
displays measured discharge air temperature. Displays --.-°F if sensor sends invalid value, if not connected, short or out-of-range.
OA TEMP _ _._ ºF -40 to 140 ºF Displays measured value of outdoor air temperature.
Displays --°F if sensor sends invalid value, if not connected, short or out-of-range.
OA HUM _ _ % 0 to 100% Displays measured value of outdoor humidity from OA Sylkbus
sensor. Displays --% if not connected, short, or out- of-range.
RA TEMP _ _._ ºF 0 to 140 ºF Displays measured value of return air temperature from RA
Sylkbus sensor. Displays --°F if sensor sends invalid value, if not connected, short or out-of-range.
RA HUM _ _ % 0 to 100% Displays measured value of return air humidity from RA Sylkbus
sensor. Displays --% if sensor sends invalid value, if not connected, short or out-of-range.
IN CO2 _ _ _ ppm 0 to 2000 ppm Displays value of measured CO2 from CO2 sensor. Invalid if not
connected, short or out-of-range. May be adjusted in Advanced menu by Zero offset and Span.
DCV STATUS n/a ON/OFF Displays ON if above setpoint and OFF if below setpoint, and
ONLY if a CO2 sensor is connected.
DAMPER OUT 2.0V 2.0 to 10.0 V
Displays output voltage or position to the damper actuator.
e
ACT POS n/a 0 to 100% Displays actual position of actuator.
ACT COUNT n/a 1 to 65,535 Displays number of times actuator has cycled. 1 Cycle equals
the sum of 180° of movement in any direction.
ACTUATOR n/a OK/Alarm (on
Displays Error if voltage or torque is below actuator range
Alarm menu)
EXH1 OUT OFF ON/OFF Output of EXH1 terminal. Displays ON when damper position
reaches programmed percentage setpoint. ON = 24 Vac Output; OFF = No Output.
13 62-0331—13
Page 14
JADE™ ECONOMIZER MODULE
Table 4. Menu Structure
Parameter
Range and
Increment
Menu Parameter
STATUS
EXH2 OUT OFF ON/OFF Output of AUX1 O terminal, if programmed for EXH2. Displays
Parameter
Default
Val ue
CONTINUED
ERV OFF ON/OFF Output of AUX1 O terminal, if programmed for ERV. ON = 24 Vac
MECH COOL ON
0 0, 1, or 2 Displays number of mechanical cooling stages that are active.
or HEAT STAGES ON
FAN SPEED n/a LOW or HIGH Displays speed of fan if JADE is programmed for 2-speed fan.
W (HEAT IN) n/a ON/OFF Displays status of heat if JADE is programmed for 2-speed fan.
SETPOINTS MAT SET 53ºF 38 to 70 ºF;
increment by 1
LOW T LOCK 32ºF -45 to 80 ºF;
increment by 1
DRYBLB SET 63ºF 48 to 80 ºF;
increment by 1
ENTH CURVE ES3 ES1, ES2, ES3,
ES4, or ES5
DCV SET 1100ppm 500 to 2000
ppm increment by 100
MIN POS 2.8 V 2 to 10 Vdc Displays ONLY if a CO2 sensor is NOT connected.
VENTMAX 2.8 V 2 to 10 Vdc Displays only if a CO2 sensor is connected.
100 to 9990 cfm increment by 10
2 to 10 Vdc With 2-speed fan units VENTMAX L (low speed fan) and
VENTMIN 2.25 V 2 to 10 Vdc Displays only if CO2 sensor is connected.
100 to 9990 cfm increment by 10
2 to 10 Vdc With 2-speed fan units VENTMIN L (low speed fan) and
a
. (Continued)
b
Notes
ON when damper position reaches programmed percentage setpoint ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O = EXH2
Output, OFF = No Output; displays only if AUX1 O = ERV
Displays the stage of heat pump heating that is active.
The economizer will modulate the OA damper to maintain the mixed air temperature at the setpoint.
Setpoint determines outdoor temperature when the mechanical cooling cannot be turned on. Commonly referred to as the Compressor lockout. At or below the setpoint the Y1-O and Y2-O will not be energized on the controller.
Dry bulb setpoint will only appear if using dry bulb change over.
Setpoint determines where the economizer will assume outdoor air temperature is good for free cooling; e.g.; at 63 ºF setpoint unit will economizer at 62 ºF and below and not economize at 64 ºF and above. There is a a 2 ºF deadband.
ES curve will only appear if using enthalpy changeover.
Enthalpy boundary “curves” for economizing using single enthalpy. See page 11 for description of enthalpy curves.
Displays ONLY if a CO2 sensor is connected. Setpoint for Demand Control Ventilation of space. Above the setpoint, the OA dampers will modulate open to bring in additional OA to maintain a space ppm level below the setpoint.
With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) settings are required. Default for MIN POS L is 3.2V and MIN POS H is 2.8V.
Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sensor.
If OA, MA RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM and displays from 100 to 9990 cfm.
VENTMAX H (high speed fan) settings are required. Default for VENTMAX L is 3.2V and VENTMAX H is 2.8V.
Used for Va (ventilation min cfm) setpoint. This is the ventilation requirement for less than maximum occupancy of the space.
If OA, MA RA and CO2 sensors are connected and DCV CAL ENABLE is set to AUTO mode, the OA dampers are controlled by CFM and displays from 100 to 9990 cfm.
VENTMIN H (high speed fan) settings are required. Default for VENTMIN L is 2.5V and VENTMIN H is 2.25V.
62-0331—13 14
Page 15
JADE™ ECONOMIZER MODULE
Menu Parameter
SETPOINTS
CONTINUED
ERV OAT SP
EXH1 SET 50% 0 to 100%;
EXH2 SET 75% 0 to 100%;
SYSTEM
INSTALL 01/01/11 Display order = MM/DD/YY
SETUP
UNITS DEG ºF ºF or ºC Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT CONV CONV
AUX2 IN n/a Shutdown (SD)
Table 4. Menu Structure
Parameter
Default
Val ue
d
32ºF 0 to 50 ºF;
Parameter
Range and Increment
a
. (Continued)
b
Only when AUX1 O = ERV
Notes
increment by 1
Setpoint for OA damper position when exhaust fan 1 is powered
increment by 1
by the economizer. With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) settings are required. Default for Exh1 L is 65% and Exh1 H is 50%
Setpoint for OA damper position when exhaust fan 2 is powered
increment by 1
by the economizer. Only used when AUX1 O is set to EHX2. With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) settings are required. Default for Exh2 L is 80% and Exh2 H is 75%
Setting order = DD, MM, then YY.
CONV = conventional.
HP
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump input from thermostat or controller (O or B terminal).
In CONV mode:
Heat (W1) HP(O)
SD = Enables configuration of shutdown (default); W = Informs controller that system is in heating mode.
HP(B)
NOTE: If using 2-speed fan mode, you must pro-
gram CONV mode for W. Shutdown is not available in the two-speed fan mode.
FAN SPEED 1 speed 1 speed/
2 speed
FAN CFM 5000cfm 100 to 50000
cfm; increment by 100
AUX1 OUT NONE NONE
ERV EXH2 SYS
OCC INPUT INPUT or
ALWAYS
In HP O/B mode: HP(O) = energize heat pump on Cool (default); HP(B) = energize heat pump on Heat.
Sets economizer controller for operation of 1 speed or 2 speed supply fan. The controller does not control the fan but positions the OA and RA dampers to the heating or cooling mode settings.
NOTE: 2-speed fan option also needs Heat (W1) pro-
grammed in AUX 2 In.
This is the capacity of the fan. The value is found on the label from the RTU manufacturer. The cfm of the fan is only used with DCV CAL ENABLE AUO
NONE = not configured (output is not used)
ERV= Energy Recovery Ventilator
d
EXH2 = second damper position 24 Vac out for second
exhaust fan.
SYS = use output as an alarm signal
When using a setback thermostat with occupancy out (24 Vac), the 24 Vac is input “INPUT” to the OCC terminal. If no occupancy output from the thermostat then change program to “ALWAYS” OR add a jumper from terminal R to OCC terminal.
15 62-0331—13
Page 16
JADE™ ECONOMIZER MODULE
Menu Parameter
ADVANCED
MA LO SET 45 ºF 35 to 65 ºF;
SETUP
FREEZE POS CLO CLO
CO2 ZERO 0ppm 0 to 500 ppm;
CO2 SPAN 2000ppm 1000 to 3000
STG3 DLY 2.0h 0 min, 5 min, 15
SD DMPR POS CLO CLO
DA LO ALM 45 ºF NONE
DA HI ALM 80 ºF NONE
DCVCAL ENA MAN MAN (manual)
MAT T CAL 0.0 F° +/-2.5F° Allows for the operator to adjust for an out of calibration
OAS T CAL 0.0F° +/-2.5F° Allows for the operator to adjust for an out of calibration
OAS H CAL 0% RH +/-10% RH Allows for the operator to adjust for an out of calibration
RA T CAL 0.0F° +/-2.5F° Allows for the operator to adjust for an out of calibration
RA H CAL 0% RH +/-10% RH Allows for the operator to adjust for an out of calibration
DA T CAL 0.0 F° +/-2.5F° Allows for the operator to adjust for an out of calibration
2SP FAN DELAY 5 Minutes 0 to 20 minutes
Table 4. Menu Structure
Parameter
Default
Val ue
Parameter
Range and
Increment
increment by 1º
MIN
increment by 10
ppm; increment by 50
min, then 15 min intervals. Up to 4h or OFF
OPN
35ºF to 65ºF in 5ºF increments
70 ºF to 180 ºF in 5º F increments
AUTO
in 1 minute increments.
a
. (Continued)
b
Notes
Temp to activate Freeze Protection (close damper or modulate to MIN POS if Mixed air temperature falls below set value)
Damper position when freeze protection is active (closed or MIN POS).
CO2 ppm level to match CO2 sensor start level.
CO2 ppm span to match CO2 sensor; e.g.; 500-1500 sensor output would be 500 CO2 zero and 1000 CO2 span.
Delay after stage 2 (Y2 IN) for cool has been active. Turns on 2nd stage of mechanical cooling when economizer is 1st stage call and mechanical cooling is 2nd stage call. Allows three stages of cooling, 1 economizer and 2 mechanical. OFF = no Stage 3 cooling.
Indicates shutdown signal when JADE is programmed for SHUTDOWN. When controller receives 24 Vac input on the AUX2 IN terminal in conventional mode, the OA damper will open if programmed for OPN and the OA damper will close if programmed for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut off.
Used for alarm for when the DA air temperature is too low. Set lower range of alarm, below this temperature the alarm will show on the display. Must have a DA temperature sensor (C7400S programmed for DA) in the discharge air.
Used for alarm for when the DA air temperature is too high. Set high range of alarm, above this temperature the alarm will show on the display. Must have a DA temperature sensor (C7400S programmed for DA) in the discharge air.
Turns on the DCV automatic control of the dampers. Resets ventilation based on the RA, OA and MA sensor conditions. Requires all sensors (RA, OA, MA and CO2). This operation is not operable with a 2-speed fan unit.
temperature sensor
temperature sensor
humidity sensor
temperature sensor
humidity sensor
temperature sensor
When in economizing mode this is the delay for the high speed fan to try to satisfy the call for second stage cooling before the first stage mechanical cooling is enabled.
62-0331—13 16
Page 17
JADE™ ECONOMIZER MODULE
Table 4. Menu Structurea. (Continued)
Parameter
Range and Increment
b
system. See Table 5.
Notes
Menu Parameter
f
CHECKOUT
DAMPER MINIMUM POSITION
Parameter
Default
Val ue
n/a n/a The checkout for the damper minimum positions is based on the
DAMPER OPEN n/a n/a Positions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make sure you pause in this mode to allow for exhaust contacts to energize due to the delay in the system.
DAMPER CLOSE n/a n/a Positions damper to the fully closed position.
CONNECT Y1-O n/a n/a Closes the Y1-O relay (Y1-O).
See CAUTION on page 23
CONNECT Y2-O n/a n/a Closes the Y2-O relay (Y2-O).
See CAUTION on page 23
CONNECT AUX1-O n/a n/a Energizes the AUX1-O output.
CONNECT EXH1 n/a n/a Closes the power exhaust fan 1 relay (EXH1)
ALARMS(#) Alarms display only when they are active. The menu title
“ALARMS (#)” includes the number of active alarms in parenthesis (). When using SYLK bus sensors, "SYLK" will appear on the screen, and when using 20k OA temperature sensors, "SENS T" will appear on the screen.
MA T SENS ERR n/a n/a Mixed air sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues
CO2 SENS ERR n/a n/a CO2 sensor has failed, gone out of range or become
disconnected - check wiring then replace sensor if the alarm continues
OA SYLK T ERR n/a n/a Outdoor air enthalpy sensor has failed or become disconnected -
OA SYLK H ERR n/a n/a
check wiring then replace sensor if the alarm continues
RA SYLK T ERR n/a n/a Return air enthalpy sensor has failed or become disconnected -
RA SYLK H ERR n/a n/a
check wiring then replace sensor if the alarm continues
DA SYLK T ERR n/a n/a Discharge air sensor has failed or become disconnected - check
wiring then replace sensor if the alarm continues
OA SENS T ERR n/a n/a Outdoor air temperature sensor has failed or become
disconnected - check wiring then replace sensor if the alarm continues
ACT ERROR n/a n/a Actuator has failed or become disconnected - check for stall,
over voltage, under voltage and actuator count. Replace actuator if damper is moveable and supply voltage is between 21.6 V and
26.4 V. Check actuator count on STATUS menu.
FREEZE ALARM n/a n/a Check if outdoor temperature is below the LOW Temp Lockout
on setpoint menu. Check if Mixed air temperature on STATUS menu is below the Lo Setpoint on Advanced setup menu. When conditions are back in normal range then the alarm will go away.
SHUTDOWN ACTIVE n/a n/a AUX2 IN is programmed for SHUTDOWN and 24 V has been
applied to AUX2 IN terminal
DMP CAL RUNNING n/a n/a If DCV Auto enable has been programmed, when the JADE is
completing a calibration on the dampers, this alarm will display. Wait until the calibration is completed and the alarm will go away. Must have OA, MA and RA sensors for DCV calibration; set up is in the Advanced setup menu
DA SENS ALM n/a n/a Discharge air temperature is out of the range set in the
ADVANCED SETUP Menu. Check the temperature of the discharge air.
17 62-0331—13
Page 18
JADE™ ECONOMIZER MODULE
a
. (Continued)
b
Notes
sensors, etc.), the AUX1-O terminal has 24 Vac out.
Menu Parameter
ALARMS(#)
SYS ALARM n/a n/a When AUX1-O is set to SYS and there is any alarm (e.g., failed
CONTINUED
Table 4. Menu Structure
Parameter
Default
Val ue
Parameter
Range and
Increment
ACT UNDER V n/a n/a Voltage received by Actuator is below expected range
ACT OVER V n/a n/a Voltage received by Actuator is above expected range
ACT STALLED n/a n/a Actuator stopped before achieving commanded position
FEATURES ADJUSTABLE ONLY BY USE OF THE W7220 PC MOD TOOL
ACT STALL ALARM SUPPRESSION
a
Table 4 illustrates the complete hierarchy. Your menu parameters may be different depending on your configuration.
For example if you do not have a DCV (CO
b
When values are displayed, pressing and holding the or button causes the display to automatically increment.
c
n/a = not applicable
d
ERV Operation: When in Cooling mode AND the conditions are NOT OK for economizing - the ERV terminal will be energized. In
Disabled Enabled or
Disabled
) sensor, then none of the DCV parameters appear.
2
If enabled this feature allows the operator to suppress the stall alarm in a specific range of the actuator stroke.
the Heating mode the ERV terminal will be energized when the OA is below the ERV OAT setpoint in the setpoint menu.
e
When used with Honeywell communicating actuator the damper out is reported in XX.X% open versus XX.X Vdc.
f
After 10 minutes without a command or mode change, the controller will change to normal operation.
Table 5. Damper minimum position settings and readings on checkout menu.
Demand Control Ventilation
Fan Speed
(CO2 Sensor) Setpoints Checkout
1 NO MIN POS VMAX-HS
1NO N/A N/A
2 NO MIN POS H VMAX-HS
2 NO MIN POS L VMAX-LS
1 YES VENT MIN VMIN-HS
1 YES VENT MAX VMAX-HS
2 YES VENT MIN H VMIN-HS
2 YES VENT MAX H VMAX-LS
2 YES VENT MINL N/A
2 YES VENT MAX L N/A
62-0331—13 18
Page 19
JADE™ ECONOMIZER MODULE

SEQUENCE OF OPERATION

Table 6. Dry Bulb Operation No DCV (CO2 sensor) - 1 Speed Fan.
DCV
None No Off Off High 0-v/Off 0-v/Off MIN POS Closed
None Yes Off Off High 0-v/Off 0-v/Off MIN POS Closed
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have not been satisfied.
DCV
Below CO2 set
Above CO2 set
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if the call for Y1-I and Y2-I have not been satisfied.
OA Good to
economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied
On Off High 24-v/On 0-v/Off MIN POS Closed
On On High 24-v/On 24-v/On MIN POS Closed
On Off High 0-v/Off 0-v/Off MIN POS to Full-
Closed to Full-Open
Open
On On High 24-v/On
0-v/Off
a
MIN POS to Full­Open
Closed to Full-Open
Table 7. Dry Bulb Operation With DCV (CO2 sensor) - 1 Speed Fan.
OA Good to
economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied
No Off Off High 0-v/Off 0-v/Off VENTMIN Closed
On Off High 24-v/On 0-v/Off VENTMIN Closed
On On High 24-v/On 24-v/On VENTMIN Closed
Yes Off Off High 0-v/Off 0-v/Off VENTMIN Closed
On Off High 0-v/Off 0-v/Off VENTMIN to Full-
Closed to Full-Open
Open
On On High 24-v/On
No Off Off High 0-v/Off 0-v/Off VENTMIN to
0-v/Off
a
VENTMIN to Full­Open
Closed to Full-Open
Closed
VENTMAX
On Off High 24-v/On 0-v/Off VENTMIN to
Closed
VENTMAX
On On High 24-v/On 24-v/On VENTMIN to
Closed
VENTMAX
Yes Off Off High 0-v/Off 0-v/Off VENTMIN to
Closed
VENTMAX
On Off High 0-v/Off 0-v/Off VENTMIN to Full-
Closed to Full-Open
Open
a
On On High 24-v/On
0-v/Off
VENTMIN to Full­Open
Closed to Full-Open
19 62-0331—13
Page 20
JADE™ ECONOMIZER MODULE
Table 8. Enthalpy Operation No DCV (CO2 sensor) - 1 Speed Fan.
OA Good to
DCV
economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied
None No Off Off High 0-v/Off 0-v/Off MIN POS Closed
On Off High 24-v/On 0-v/Off MIN POS Closed
On On High 24-v/On 24-v/On MIN POS Closed
None Yes Off Off High 0-v/Off 0-v/Off MIN POS Closed
On Off High 0-v/Off 0-v/Off MIN POS to Full-
Closed to Full-Open
Open
On On High 24-v/On
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
MIN POS to Full­Open
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
Table 9. Enthalpy Operation With DCV (CO2 sensor) - 1 Speed Fan.
OA Good to
DCV
economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied
Below set No Off Off High 0-v/Off 0-v/Off VENTMIN Closed
On Off High 24-v/On 0-v/Off VENTMIN Closed
On On High 24-v/On 24-v/On VENTMIN Closed
Yes Off Off High 0-v/Off 0-v/Off VENTMIN Closed
On Off High 0-v/Off 0-v/Off VENTMIN to Full-
Closed to Full-Open
Open
On On High 24-v/On
Above set No Off Off High 0-v/Off 0-v/Off VENTMIN to
0-v/Off
a
VENTMIN to Full­Open
Closed to Full-Open
Closed
VENTMAX
On Off High 24-v/On 0-v/Off VENTMIN to
Closed
VENTMAX
On On High 24-v/On 24-v/On VENTMIN to
Closed
VENTMAX
Yes Off Off High 0-v/Off 0-v/Off VENTMIN to
Closed
VENTMAX
On Off High 0-v/Off 0-v/Off VENTMIN to Full-
Closed to Full-Open
Open
a
On On High DELAY (b)
24-v/On
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
VENTMIN to Full­Open
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
62-0331—13 20
Page 21
JADE™ ECONOMIZER MODULE
Table 10. Dry Bulb Operation No DCV (CO2 sensor) - 2 Speed Fan.
OA Good to
DCV
economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied
None No Off Off Low 0-v/Off 0-v/Off MIN POS L Closed
On Off Low 24-v/On 0-v/Off MIN POS L Closed
On On High 24-v/On 24-v/On MIN POS H Closed
None Yes Off Off Low 0-v/Off 0-v/Off MIN POS L Closed
On Off Low 0-v/Off 0-v/Off MIN POS L to Full-
Closed to Full-Open
Open
On On High
DELAY
b
24-v/On
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
MIN POS H to Full­Open
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Table 11. Dry Bulb Operation With DCV (CO2 sensor) - 2 Speed Fan.
OA Good to
DCV
economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied
Below set No Off Off Low 0-v/Off 0-v/Off VENTMIN L Closed
On Off Low 24-v/On 0-v/Off VENTMIN L Closed
On On High 24-v/On 24-v/On VENTMIN H Closed
Yes Off Off Low 0-v/Off 0-v/Off VENTMIN L Closed
On Off Low 0-v/Off 0-v/Off VENTMIN L to Full-
Closed to Full-Open
Open
On On High 24-v/On
Above set No Off Off Low 0-v/Off 0-v/Off VENTMIN L to
0-v/Off
a
VENTMIN H to Full­Open
Closed to Full-Open
Closed
VENTMAX L
On Off Low 24-v/On 0-v/Off VENTMIN L to
Closed
VENTMAX L
On On High 24-v/On 24-v/On VENTMIN H to
Closed
VENTMAX H
Yes Off Off Low 0-v/Off 0-v/Off VENTMIN L to
Closed
VENTMAX L
On Off Low 0-v/Off 0-v/Off VENTMIN L to Full-
Closed to Full-Open
Open
On On High
DELAY
b
24-v/On
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
VENTMIN H to Full­Open
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
21 62-0331—13
Page 22
JADE™ ECONOMIZER MODULE
Table 12. Enthalpy Operation No DCV (CO2 sensor) - 2 Speed Fan.
OA Good to
DCV
NO CO2
economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied
No Off Off Low 0-v/Off 0-v/Off MIN POS L Closed
SENSOR
On Off Low 24-v/On 0-v/Off MIN POS L Closed
On On High 24-v/On 24-v/On MIN POS H Closed
Yes Off Off Low 0-v/Off 0-v/Off MIN POS L Closed
On Off Low 0-v/Off 0-v/Off MIN POS L to Full-
Closed to Full-Open
Open
On On High
DELAY
b
24-v/On
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
MIN POS H to Full­Open
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
Table 13. Enthalpy Operation With DCV (CO2 sensor) - 2 Speed Fan.
OA Good to
DCV
economize? Y1-I Y2-I FAN SPD Y1-O Y2-O Occupied Unoccupied
Below set No Off Off Low 0-v/Off 0-v/Off VENTMIN L Closed
On Off Low 24-v/On 0-v/Off VENTMIN L Closed
On On High 24-v/On 24-v/On VENTMIN H Closed
Yes Off Off Low 0-v/Off 0-v/Off VENTMIN L Closed
On Off Low 0-v/Off 0-v/Off VENTMIN L to Full-
Closed to Full-Open
Open
On On High 24-v/On
Above set No Off Off Low 0-v/Off 0-v/Off VENTMIN L to
0-v/Off
a
VENTMIN H to Full­Open
Closed to Full-Open
Closed
VENTMAX L
On Off Low 24-v/On 0-v/Off VENTMIN L to
Closed
VENTMAX L
On On High 24-v/On 24-v/On VENTMIN H to
Closed
VENTMAX H
Yes Off Off Low 0-v/Off 0-v/Off VENTMIN L to
Closed
VENTMAX L
On Off Low 0-v/Off 0-v/Off VENTMIN L to Full-
Closed to Full-Open
Open
On On High
DELAY
b
24-v/On
a
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if
0-v/Off
a
VENTMIN H to Full­Open
Closed to Full-Open
the call for Y1-I and Y2-I have not been satisfied.
b
With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
62-0331—13 22
Page 23
JADE™ ECONOMIZER MODULE
CAUTION

TROUBLESHOOTING

Alarms

The Economizer module provides alarm messages that display on the 2-line LCD.
NOTE: JADE will be in the “set up” mode for the first 60
minutes after powered. If a sensor for OA air or Sylkbus device (sensor, actuator) is discon­nected during the set up mode, the JADE will not alarm that failure. The MA sensor is a system “critical” sensor; if the MA sensor is removed during the set up mode, the JADE will alarm. After 60 minutes the JADE controller will change to operation mode and all components removed or failed will alarm in the operation mode.
You can also navigate to the Alarms menu at any time.
Clearing Alarms
Once the alarm has been identified and the cause has been removed (e.g. replaced faulty sensor), the alarm can be cleared from the display.
To clear an alarm, perform the following:
1. Navigate to the desired alarm.
2. Press the button.
3. ERASE? displays.
4. Press the button.
5. ALARM ERASED displays.
6. Press the button (MenuUp/Exit) to complete the
action and return to the previous menu.
NOTE: If an alarm still exists after you clear it, it re-dis-
plays within 5 seconds.

Checkout Tests

Use the Checkout menu (Table 4) to test the damper operation and any configured outputs. Only items that are configured are shown in the Checkout menu.
NOTE: See “Interface Overview” on page 18 of 63-2700 for
information about menu navigation and use of the keypad.
To perform a Checkout test:
1. Scroll to the desired test in the Checkout menu using
the and buttons.
2. Press the button to select the item.
3. RUN? appears on the display.
4. Press the button to start the test.
5. The unit pauses and then displays IN PROGRESS.
6. When all parameters have been tested, press the
button (Menu up) to end the test (e.g. turn off the relay). The checkout tests can all be performed at the time of installation or any time during the operation of the system as a test that the system is operable.
Equipment damage may result.
Be sure to allow enough time for compressor startup and shutdown between checkout tests so that you do not short-cycle the compressors
23 62-0331—13
Page 24
JADE™ ECONOMIZER MODULE
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
customer.honeywell.com
® U.S. Registered Trademark © 2014 Honeywell International Inc. 62-0331—13 M.S. Rev. 04-14 Printed in United States