Honeywell W7220 Installation Guide

JADE™ Economizer Module
(MODEL W7220)
INSTALLATION INSTRUCTIONS
for differential enthalpy changeover. JADE can be used with a CO2 indoor air sensor for Demand Control Ventilation and with a VFD for two speed fan operation.
This document describes wiring, power up, basic troubleshooting, and common installation issues for the JADE™ Economizer Module (Model W7220). For further information on mounting and operation, refer to Honeywell document 63-2700.

BEFORE INSTALLATION

Review the following before installing the The W7220:

Electrical

Rated Voltage: 20 to 30 Vac RMS; 50/60 Hz
Transformer: 100 VA maximum system input
Relay Digital Output Rating: 30 Vac
IMPORTANT
All inputs and outputs must be Class 2 wiring.

Inputs

A Mixed air (MA) analog sensor is required on all W7220 units; either an OA (Outdoor Air) sensor for dry bulb change over or an OA Sylkbus sensor for outdoor enthalpy change over is required in addition to the MA sensor. An additional Return Air (RA) Sylkbus sensor can be added to the system
DCV (CO
) Sensor (C7232): 2-10 Vdc control signal;
2
minimum impedance >50k ohm.

Outputs

Actuator signal: 2-10 Vdc; minimum actuator impedance is
2k ohm; Sylkbus two-wire output for Honeywell Sylkbus communicating actuators.
Exhaust fan, Y1, Y2 and AUX1 O: Contact closure (24 Vac) All Relay Outputs (at 30 Vac):
Running: 1.5A maximum Inrush: 7.5A maximum

When Installing This Product

1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condi­tion.
2. Check ratings given in instructions and on the product to ensure the product is suitable for your application.
3. Installer must be a trained, experienced service techni­cian.
4. After installation is complete, check out product opera­tion as provided in these instructions.
5. For additional detailed information on this product go to customer.honeywell.com and download the product data sheet (lit no 63-2700) or scan QR code located on the label above MAT terminals with your smart phone.

Accessories

50048926-001 2-pin edge connector for sensors
(20 pieces per bag)
50048926-002 6-pin edge connector for field wiring
(20 pieces per bag) C7250 20k sensor for MA or OA (dry bulb changeover) C7400S Sylkbus sensor for enthalpy control in OA and/or RA
and RA for differential dry bulb changeover W7220 PCMOD interface tool for JADE controller and Per-
sonal Computer. Go to www.customer.honeywell.com/
economizertools for the software 50053060-001 Duct mounting kit for sensors C7632 or C7232 CO
sensors
2
62-0331-13
JADE™ ECONOMIZER MODULE
WARNING
CAUTION

INSTALLATION AND SETUP

The Economizer module may be mounted in any orientation. However, mounting in the orientation shown above permits proper viewing of the LCD display and use of the keypad.
NOTE: JADE will be in the “set up” mode for the first 60
minutes after powered. If a sensor for OA air or Sylkbus device (sensor, actuator) is discon­nected during the set up mode, the JADE will not alarm that failure. The MA sensor is a system “critical” sensor; if the MA sensor is removed during the set up mode, the JADE will alarm. After 60 minutes the JADE controller will change to operation mode and all components removed or failed will alarm in the operation mode.

WIRING

All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Module wiring in the field is terminated to the four screw terminal blocks located on the left and right sides.
Module wiring at the OEM factory is terminated via the header pin terminals located on the left and right sides. The header terminal pins and the terminal blocks have common terminations for the appropriate input or output. The part number for the OEM female mating connector is 0039973997.
Electrical Shock Hazard. Can cause severe injury, death or property damage.
Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.

Actuator Wiring Options:

1. The JADE economizer controller can only have one (1)
communicating actuator connected to it.
2. Up to four (4) non-communicating and (2) 2-position actuators (1 each on EXH1 and AUX1 O)
3. One (1) communicating and up to four (4) non-commu­nicating and (2) 2-position actuators (1 each on EXH1 and AUX1 O)
When using a 2-position actuator on the AUX1 O the AUX1 O must be programmed for Exh2 and the % open is the % open of the outdoor damper when the 2-pos actuator opens. Connect 24 V to Exh1 and/or AUX1 O and ground to the JADE “C” terminal.
Note the W7220 economizer will not work with an old “black motor” M7415; replace the M7415 with a M7215 or MS3103 DCA.
Table 1. Economizer Module - Left hand terminal blocks.
Label Type Description
Top Left Terminal Block
MAT MAT
OAT OAT
S-BUS S-BUS
IAQ 2-10 2-10 Vdc Air Quality Sensor Input
IAQ COM COM Air Quality Sensor Common
IAQ 24V 24 Vac Air Quality Sensor 24 Vac Source
ACT 2-10 2-10 Vdc Damper Actuator Output (2-10 Vdc)
ACT COM COM Damper Actuator Output Common
ACT 24V 24 Vac Damper Actuator 24 Vac Source
20k NTC and COM
20k NTC and COM
SYLK Bus Sylk Bus sensor
Bottom Left Terminal Block
Mixed Air Temperature Sensor (polarity insensitive connection)
Outdoor Air Temperature Sensor (polarity insensitive connection)
(polarity insensitive connection)
(e.g. CO
sensor)
2
Equipment Damage Hazard. Electrostatic discharge can short equipment circuitry.
Ensure that you are properly grounded before handling the unit.
Each terminal can accommodate the following gauges of wire:
• Single wire – from 18 AWG to 22 AWG solid or stranded
• Multiple wires – up to two 22 AWG stranded
• For the 24 Vac connections: single wire – from 14 to 18 AWG solid or stranded
For S-BUS wiring, the sensors may be mounted up to 200 ft. (61 m) from the JADE controller. When the length of wire is over 100 feet use twisted pair shielded wire.
NOTE: All wiring is polarity insensitive.
Refer to Fig. 1 through Fig. 7 for common wiring configurations. Refer to Fig. 8 for use with the Smart VFD. Figure 8 shows how to make a single-speed blower operate with two speeds with JADE. When the thermostat calls for first stage cooling or independent fan, the VFD will operate the fan at low speed. When the thermostat calls for first stage heat or second stage cooling, it will operate the fan at high speed. To achieve this, wire relays as shown, and configure the VFD to the minimum frequency M3.3.1 for low speed fan, and for high speed fan configure Preset frequency 1, M3.3.12.
62-0331—13 2
Table 2. Economizer Module - Right hand terminal blocks.
Label Type Description
Top Right Terminal Block
n/a The first terminal is not used
AUX2 I 24 Vac IN Shut Down (SD) or Heat (W)
Conventional only or Heat Pump Changeover (O/B) in Heat Pump mode.
OCC 24 Vac IN Occupied / Unoccupied Input
E-GND EGND Earth Ground - System Required
EXH1 24 Vac OUT Exhaust Fan 1 Output
AUX1 O 24 Vac OUT Programmable:
Exhaust fan 2 output or ERV or System Alarm output.
Bottom Right Terminal Block
Y2-I 24 Vac IN Y2 in - Cooling Stage 2 Input from
space thermostat
Y2-O 24 Vac OUT Y2 out - Cooling Stage 2 Output to
stage 2 mechanical cooling
Table 2. Economizer Module - Right hand terminal blocks.
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC
24 VAC
1K1
1K1
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MA MA
OAT OAT
C R
M28980D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V
AUX1-0
AUX2-I
OA TEMP SENSOR
20K NTC
M7215
NOTE THAT THE C7250 20K NTC SENSOR CAN BE MOUNTED IN THE OAT ONLY IN THIS CONFIGURATION.
1
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
3
3
1
MA TEMP
SENSOR 20K NTC
+
-
TR1
TR
IN
IN
2
R(+)
C(-)
Label Type Description
Y1-I 24 Vac IN Y1 in - Cooling Stage 1 Input from
space thermostat
Y1-O 24 Vac OUT Y1 out - Cooling Stage 1 Output to
stage 1 mechanical cooling
C COM 24 Vac Common
R 24 Vac 24 Vac Power (Hot)
JADE™ ECONOMIZER MODULE
Fig. 1. Stand-alone dry bulb Economizer configuration with black motor M7215.
3 62-0331—13
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC
24 VAC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MAT MAT
OAT OAT
C R
M32564D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V
3
OAT TEMP
SENSOR 20K NTC
MS7503 OR MS7505
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
1
1
MA TEMP
SENSOR
20K NTC
R(+)
C(-)
AUX1-0
AUX2-I
2
3
2
3
1K1
1K1
Fig. 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7503 Direct Coupled Actuator.
62-0331—13 4
JADE™ ECONOMIZER MODULE
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC
24 VAC
E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
CO2
SENSOR
2-10 VDC
(OPTIONAL)
MAT MAT
OAT OAT
C R
R(+)
C(-)
M32650D
IAQ (2-10V)
IAQ COM
IAQ 24V
ACT (2-10V) ACT COM ACT 24V
3
1
2
OAT TEMP
SENSOR 20K NTC
MS3103J OR MS3105J
1
1
MA TEMP
SENSOR 20K NTC
S-BUS
4
5
S-BUS
AUX1-0
AUX2-I
NOTE THAT THE 20K NTC SENSOR CAN BE MOUNTED IN THE OAT TERMINALS ONLY IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
2
3
3
1K1
1K1
Fig. 3. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators.
5 62-0331—13
JADE™ ECONOMIZER MODULE
S-BUS
S-BUS
OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
RETURN AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
MAT MAT
C R
R(+)
C(-)
M32565D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
1
4
1
2
CO2
SENSOR
2-10 VDC
(OPTIONAL)
IAQ (2-10V) IAQ COM IAQ 24V
ACT (2-10V) ACT COM ACT 24V
+
-
TR1
TR
IN
IN
M7215
MA TEMP
SENSOR 20K NTC
AUX1-0
AUX2-I
3
2
4
3
1K1
1K1
24 VAC
Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.
62-0331—13 6
JADE™ ECONOMIZER MODULE
OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
RETURN AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
C R
R(+)
C(-)
M32566D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS CONFIGURATION.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
1
1
2
MS7503 OR MS7505
3
S-BUS S-BUS
MAT MAT
CO2 SENSOR 2-10 VDC
(OPTIONAL)
IAQ (2-10V) IAQ COM IAQ 24V
ACT (2-10V) ACT COM ACT 24V
MA TEMP
SENSOR 20K NTC
AUX1-0
AUX2-I
2
3
4
3
4
1K1
1K1
24 VAC
Fig. 5. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7505 or MS7503 Direct
Coupled Actuator.
7 62-0331—13
JADE™ ECONOMIZER MODULE
C7400S OUTSIDE AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
C7400S RETURN AIR TEMP/HUMIDITY (ENTHALPY) SYLKBUS SENSOR
ROOF TOP UNIT
Y1O
Y2O Y1I
Y2I
OCC E-GND
Y1
G
W2
W1
Y2
O/B
OCC
W7220 ECONOMIZER CONTROLLER MODULE
THERMOSTAT
C R
C(-)
M32653D
IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEM/HUMIDITY (ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.
1
1
THE S-BUS COMPONENTS MAY BE DAISY CHAINED TO ANOTHER S-BUS COMPONENT.
WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.
WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION RELAY BETWEEN O AND C.
2
S-BUS S-BUS
MAT MAT
CO2 SENSOR 2-10 VDC
(OPTIONAL)
IAQ (2-10V) IAQ COM IAQ 24V ACT (2-10V)
ACT COM ACT 24V
MA TEMP
SENSOR 20K NTC
AUX1-0
AUX2-I
3
1
2
MS3103J OR MS3105J
S-BUS
4
5
S-BUS
2
R(+)
24 VAC
3
3
4
1K1
1K1
4
Fig. 6. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating
actuators.
62-0331—13 8