Honeywell W7215B Catalog Page

Economizer Logic Modules
70-6910 405
Commercial
Components
PC Interface Module
Digital economizer controller for programming and remote fault
detection and diagnostics
Dimensions, Approximate: 4.98 in. high x 6.3 in. wide x 1.34 in. deep
(126.4 mm high x 160 mm wide x 34mm deep)
Voltag e: 12-30 VAC
(powered by Jade controller)
Frequency: 60 Hz/50Hz
Operating Temperature Range: -40 F to -150 F (-40 C to +65 C)
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Approvals
Federal Communications Commission: Compliant
Underwriters Laboratories, Inc: Flammability Rating UL94V-5V
Other Agencies: Complies with California Title 24
W7215B Enhanced Economizer Logic Modules
Use with C7400A, or C7660 and C7150B or C7046 Sensors; Demand
Control Ventilation (DCV) sensor C7232 C02 sensor (2-10 Vdc); and
Honeywell Series 72 actuators to proportion outdoor and return air
dampers for economizer and ventilation control in commercial HVAC
equipment. (See below)
Input from DCV C02 sensor provides optimum ventilation
based on occupancy
Includes air change and shutdown
Demand control ventilation economizer provides comfort,
energy savings, reliability, air quality compliance and
flex bility in heating, cooling and ventilating applications
Combines enthalpy or dry bu b changeover control, minimum and maximum
damper position potentiometer and DCV setpoint functions
Optional differential enthalpy control (enthalpy setpoint D with two C7400A
sensors) provides greater economizer savings and maximum comfort over
single enthalpy control
Enthalpy setpoint (A-D) on economizer module controls the combination of
air temperature and humidity that is suitable for free cooling
LEDs indicates when economizer is in free cooling and DCV modes
Provides for input from an outdoor air quality sensor
Dimensions, Approximate: 8 11/16 in. high x 5 13/16 in. wide x 1 11/16 in.
deep (221 mm high x 147 mm wide x 43 mm deep)
Contact Ratings: 1.5 A Run @ 30 Vac; 3.5 A Inrush @ 30 Vac
Voltag e: 24 Vac
Frequency: 50 Hz; 60 Hz
Operating Temperature Range: -25 F to +125 F (-32 C to +52 C)
Operating Humidity Range (% RH): 5 to 95% RH, non-condensing
Used With: Honeywell Series 72 actuators
Approvals
CE: CE Report: GV02-003
C-Tick: Approved
Underwriters Laboratories, Inc: UL Listed File: E4436, Guide: XAPX,
Meets UL873 plenum requirements
Other Agencies: Complies with California Title 24
Accessories:
4074EJM-1.2K ohm checkout resistor, 620 ohm resistor, and jumper
S963B1128-Manual Potentiometer (135 ohm)
Product Number Input Output Color Description
W7220-PCMOD/U Sylk bus communication
to JADE (W7220A1000)
USB connection to a
personal computer
Gray W7220-PCMOD interface module used with
JADE (W7220A1000) and Personal Computer
Product Number Input Output Use with Sensor Comments
W7215B1004/U Discharge Air Temperature
sensor: C7150 or C7046;
Air Quality Sensor
2-10 Vdc to
actuator
C7232; C7400A;
C7150; C7046;
C7660
Can accept remote minimum position damper position potentiometer
and/or analog input from two carbon dioxide sensors for indoor and
outdoor air.Economizer Logic Module operates Series 72 actuators
Loading...