Honeywell VS820 User Manual

APPLICATION
These gas controls combine a Lite-Rite manual gas cock, safety shutoff Pilotstat assembly, millivoltage automatic valve operator, and optional gas pressure regulator. They require the use of a 750 mv Powerpile generator (thermopile). The generator, heated by the pilot burner flame, pro­vides the electrical energy to operate the combina­tion gas control.
A millivoltage thermostat with suitable ac­cessory controls completes the automatic control system for the heating appliance.
Models equipped with the standard pressure regulator are identified by the suffix letter “A“ WS820A.j Models without pressure regulator carry the suffix letter “6” (VS820B). Suffix letter “C” (VS82OC) identifies models having step opening type regulators.
Pressure regulators and operator are standardiz­ed and interchangeable on all models in the two capacity ranges - 225 and 335 cubic feet per hour.
MANUAL GAS COCK
INLET STRAIGHT
\
STANDARD OUTLET
I,
THROUGH
-4&.-W
A FLATS (VERTICAL) FOR l-7/8 INCH WRENCH
,a,,.
Fig. 2 - Piping pattern and dimensions (in inches) of
VS820.
SIZE PIPE TAPPINGS
225,000
II2
I
I
II2
PRESSURE REGULATOR ADJUSTMENT
LITE-RITE GAS COCK MANUAL KNOB \ \
PlLOTSTAi POWER UNIT
NOTE: 24 VOLT VALVE OPERATOR ILLUSTRATED
120 VOLT MODELS FEATURE TWO 36 INCH (914 mm) LEADS
WITH A TERMINAL COVER FOR CONDUIT CONNECTION.
(BENEATH COVER SCREW)
*PILOT GAS OUTLET.
PRESSURE TAPPING
\
PILOT FLOW ADJ. SCREW (BENEATH COVER SCREW)
DIRECTLY BENEATH
Fig. 1 - Top view A model. Pressure regulator for “C”
model illustrated at right. (Blank cover plate (Part No. 392782) is available to convert an “A” model to a “B” model without pressure regulator.)
335,000
314
I
314
I
PREPARE AND INSTALL PIPE
1. Use new, properly reamed pipe free from chips.
2. Do not thread pipe too far. Valve distortion or malfunction may result from excess pipe within control.
LENGTH OF STANDARD PIPE THREADS (inches)
4
3. Apply moderate amount of good quality dope to pipe only, leaving two end threads bare. If LP gas in-
stallation, use compound resistant to action of li­quified petroleum gases.
PROPER PIPING PRACTICE
2 IMPERFECT CONTROL USE MODERATE
5-83
*TRADEMARK
PRINTED IN U.S.A.
THREAD PIPE RIGHT LENGTH
LEAVE 2 END THREADS BARE
Form Number 9!%10 0248-l
Residential Division
4. Install drip leg in gas supply pipe. (Fig. 31
DROP
DROP
I I
PIPED
t
PIPED
GAS
SUPPLY
3. Connect other end of tubing to pilot burner ac­cording to the pilot burner manufacturer’s instructions.
WIRING
CAUTION
Never connect these millivoltage controls to
line voltage or to a transformer.
Since the entire system is powered by the millivoltage generated by the Powerpile generator, it is important to clean and scrape all wires before connecting. Solder and tape all necessary splices using rosin flux to prevent corrosion. Tighten terminal screws. Total con-
trol circuit wiring must not exceed 30 feet of
2-wire 18 gauge cable, or 50 feet of 2-wire 16 gauge cable.
A ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
Fig. 3 - SEDIMENT TRAP (DRIP LEG) INSTALLATION.
INSTALL CONTROL
1. These controls can be mounted O-90 degrees, in any direction, from the upright position of the gas cock knob.
2. Install the control so that gas supply is con­nected to the end provided with projecting boss for wrench application. See Fig. 1.
CONNECT PILOT GAS TUBING
1. Square off and remove burrs from end of tubing. Bend tubing to desired form for routing to pilot burner.
GAS CONTROL BODY
TIGHTEN NUT ONE TURN BEYOND FINGER TIGHT
TO PILOT BURNER
FERRULE BREAKS OFF AND CLINCHES TUBING AS NUT IS TIGHTENED
t
2. Slip compression fitting over tubing and slide
out of way. Push tubing into pilot gas tapping on outlet end of control (Fig. 1) until it bottoms. While holding tubing all the way in, slide fitting into place and engage threads - turn until finger tight. Then use wrench and tighten one turn beyond finger tight.
In POWERPILE
-W
y A
L-
-k****r-----
A MUST BE APPROVED SAFETY-CIRCUIT WIRING. A COMBINATION scREw, 114 INCH 0uicK CONNECT
TERMINAL (3). POWERPILE OPERATOR COIL (INTERNAL WIRING). PILOTSTAT POWER UNIT COIL (INTERNAL WIRING).
Fig. 4 -Typical Powerpile system wiring diagram.
1. Install Powerpile thermostat, limit control (if re­quired), and Powerpile generator according to manufacturer’s installation instructions.
2. After Powerpile generator is installed, route generator lead to Powerpile operator and connect to Powerpile terminals labeled PP. Make certain jumper lead from Powerpile operator to safety shutoff Pilotstat power unit is connected and tightened l/4
turn beyond finger tight.
3. Route wires from control circuit and connect to
the two Powerpile operator terminals labeled TH.
START-UP AND ADJUSTMENTS GAS COCK SETTINGS (Refer to Fig. I)
The Lite-Rite gas cock knob has three settings: OFF, prevents any gas from passing through valve
2
to either main or pilot burner.
PILOT, which permits gas to flow to pilot burner only (when gas cock knob is held depressed or when generator is heated sufficiently to hold valve open).
ON, which permits gas to flow to both main and pilot burners when the system is calling for heat.
PILOT LIGHTING PROCEDURE
1. Slightly depress Lite-Rite knob if at PILOT position and turn clockwise m to OFF. Wait 5 minutes for all unburned gas to vent. REMEMBER that LP gas does not vent upward naturally.
2. Turn the Lite-Rite knob to PILOT, depress it completely, and light the pilot burner. The knob must
be held down about one minute before the pilot burner will stay lit after releasing the knob.
3. Turn the knob to ON, and set the thermostat above room temperature to turn on main burner.
TEST FOR GAS LEAKS
WARNING - DO NOT OMIT THIS TEST With main burner in operation, paint pipe joints, pilot gas tubing connections, and valve gasket lines with rich soap and water solution. Bubbles indicate gas leakage. To stop leak, tighten joints and screws or replace the gasket.
ADJUST PILOT FLAME
The pilot flame should envelop 3/8 to l/2 inch of the tip of the thermocouple. Remove pilot adjustment cover screw (refer to Fig. 1). Turn inner adjustment screw clockwise mto decrease or counterclockwise n to increase pilot flame. Be sure to replace cover after adjustment to prevent possible gas leakage.
PROPER
3/S TO 112 INCH
CHECK GAS INPUT TO APPLIANCE
IMPORTANT Do not exceed input rating stamped on nameplate of appliance, or manufacturer’s recommended burner orifice pressure for size orifice(s) used. Make certain primary air supply to main burner is properly adjusted for complete combustion. Follow instructions of appliance manufacturer if provided.
‘A” MODEL PROCEDURE (with pressure regulator)
1. Check input to main burner by clocking gas meter or by using a pressure gauge (manometer) connected to downstream tapping (Fig. 1). The standard natural gas model is factory set at 3.5 inches WC outlet pressure, and the standard LP gas model is set at 11 inches. If adjustment is required, proceed with step 2.
2. Remove cover screw (see Fig. 1). Using screwdriver, turn adjusting screw clockwise m to increase or counterclockwise n to decrease gas pressure to burner. (Note: Adjustment fitting is plastic and may require slightly greater turning force
than metal thread.) Replace cover screw.
“B” MODEL PROCEDURE (no pressure regulator)
1. With main burner off, connect pressure gauge (manometer) to downstream pressure tapping (Fig. 1).
2. With main burner operating, check burner
manifold pressure.
3. If pressure is not as specified by the appliance
manufacturer, readjust regulator on LP gas storage
tank.
STEP-OPENING PRESSURE REGULATOR 1°C” MODELS)
1. With main burner operating, check input by clocking gas meter, or check burner manifold pressure using pressure gauge (manometer)
connected to downstream pressure tapping (Fig. 1).
2. If adjustment is required, remove cover screw. Using a small screwdriver, turn adjusting screw
clockwise m to increase or counterclockwise
n to decrease gas pressure to burner. Replace
cover screw.
3. Check burner performance at step pressure,
observing burner ignition and flame characteristics.
Burner should ignite properly and without flashback
to orifice, and all ports should remain lit. Cycle burner several times (wait 30 seconds between cycles to allow servo regulator to resume step action.) Repeat after allowing appliance to cool.
NOTE: IF METER CLOCKING METHOD IS USED
Make certain there is no gas flow through the meter other than to the appliance being checked. Other appliances must remain off, and the pilot extinguished (or their consumption deducted from
the meter reading).
CHECKOUT Put the system into operation and observe through complete cycle to be sure all controls function properly. Make certain the Pilotstat unit shuts off gas flow to main burner within 2-l/2 minutes after pilot flame is extinguished.
3
PILOT GOES OUT WHEN LITE-RITE KNOB IS RELEASED
1. Check pilot flame adjustment. See page 3.
2. Check the Powerpile generator connection to Pilotstat power unit (Fig. 1). This is an electrical con­nection and must be clean and secure. Also check the Powerpile generator connections to the valve operator.
3. If power unit still does not hold in, use the W720 Systems Tester to obtain the exact open and closed circuit output voltages of the generator. Compare with the Acceptable Range Charts in W720 manual or Gas Controls Service Handbook. Next check resistance of Pilotstat power unit.
OPERATING INSTRUCTIONS FOR THE HOMEOWNER
‘MPORTANT
Follow the operating instructions provided by the manufacturer of your heating appliance. The infor-
mation below will be of assistance in a typical con­trol application, but the specific controls used and the procedures outlined by the manufacturer of your appliance may differ, requiring special instructions.
LITE-RITE KNOB SETTINGS
Refer to GAS COCK SETTINGS, page 2.
If W720 or other meter is not available, first replace generator. If this does not correct the condition replace power unit (adjacent to gas cock knob - see Fig. 1). Turn off gas supply to appliance (at service cock or meter) and remove power unit with wrench. Install and tighten new power unit. Turn on gas supply and check for gas leakage.
COMPONENT AND PARTS REPLACEMENT
The automatic valve operators and servo regulators
may be added in the field, or replaced in service maintenance. (Model number is stamped on side of component.) Complete instructions are furnished with the component.
REPLACEMENT VALVE OPERATOR: VS824A.
REPLACEMENT SERVO PRESSURE REGULATOR:
V5306 standard and V5307 step opening type. Either models are field addable to “B” models.
VS820 “A” or “C” models can be converted to
“B” models by removing the pressure regulator and
applying a blank plate and gasket, Pt. No. 392782.
REPLACEMENT PARTS:
Pilotstat power unit (750 mv) - 392395. Compression fitting for pilot tubing connection-
386449.
Pilot gas filter - 391158.
TO LIGHT PILOT AND TURN ON MAIN BURNER
Follow PILOT LIGHTING PROCEDURE, page 3.
TO SHUT OFF
1. For TEMPORARY situations: Main burner can be shut off by turning clockwise m from ON to PILOT. Pilot will remain lit - ready for return to nor­mal service without relighting. (This is the recom­mended summer shutdown position.)
2. For COMPLETE SHUTDOWN: Slightly depress
Lite-Rite knob when at PILOT position and turn clockwise m to OFF Both pilot and main burner now are shut off.
AUTOMATIC SAFETY SHUTOFF
The automatic safety shutoff valve blocks gas flow to the main burner and pilot burner if the pilot flame goes out or becomes too small for adequate ignition.
If safety shutoff occurs, check pilot flame after
relighting and adjust if necessary. See ADJUST PILOT FLAME, page 3. If shutoff reoccurs, contact your local dealer or gas utility to correct condition causing shutdown.
ELECTRICAL DATA:
Pilotstat Power Unit - Hold-in 15 ma maximum;
dropout 10.5 to 4.5 ma; resistance 11 ohms.
Valve Operator - Pull-in 65 ma maximum; coil
resistance 2 ohms.
This material is proprietary to Honeywell Limited and shall not be reproduced, copied or used in any manner without prior written consent of Honeywell Limited.
HONEYWELL l 740 Ellesmere Road l Scarborough l Ontario MlP 2V9
Loading...