VRN Pressure Independent Control
Valves and Actuators
PRODUCT DATA
required. In new construction, VRN2 valves perform better
than reverse return piping designs without the extra
materials these systems need.
Pressure-independent control requires less flow, enabling
use of smaller piping, pumps, and chillers.
FEATURES
• Sizes from 1/2 to 3 in. with internal (female) NPT
connections.
• Controls hot or chilled water with up to 50% glycol.
• Regulated flow rates available from 1 to 95 gpm.
• Differential pressure regulator for constant pressure
drop across valve seat.
APPLICATION
The VRN2 two-way pressure independent control valves
maintain constant flow of hot or chilled water with glycol
solutions up to 50% in closed-loop heating, ventilating,
and air conditioning (HVAC Division 23) systems
regardless of head pressure fluctuations above the
minimum specified pressure drop. These valve assemblies
can be used with Honeywell non-spring return or spring
return direct coupled actuators (DCA).
The built-in differential pressure regulator makes fluid
flow through the valve independent of changes in supply
pressure, eliminating “hunting” by the control system,
even at low coil flow. The pressure regulator virtually
eliminates cavitation in the valve, and decouples the
control valve from the effects of piping components such
as reducers and elbows.
Pressure independent control valves are sized to match
design coil flow regardless of coil size. VRN2 valves
eliminate the need to balance the system for proper flow,
and allow chillers to be operated at design temperature
differential for maximum efficiency at every load
condition. When used in a system with variable speed
pump drives, 3-way valves and coil bypass lines are not
• Positive pressure, rolling diaphragm regulator design
for flow control accuracy of ±5%.
• Equal percentage flow characteristic using patented
flow control ball insert.
• Multiple maximum flow rates available per valve size.
• Patented ball seals for low operating torque.
• Nickel-chrome plated brass or stainless steel trim.
• Choice of factory-installed actuation using
Honeywell MVN or MN/MS series direct coupled
actuators: Floating, Modulating (2-10 V), Non-Spring
Return and Spring Return.
• Spring return actuators field-configurable for
normally open or normally closed fail-safe position.
• Removable, manual operating handle to control
valve during installation or in an event of power
failure.
• Upstream Test Port for venting or pressure gauge
attachment.
• Three actuator orientations on the valve for cramped
spaces.
• Integral snubber eliminates effect of system
pressure fluctuations and entrapped air while
improving flow performance.
35 lb-in. (4 Nm) up to 3 in. (≤DN80).
27 lb-in. (3 Nm) up to 1-1/4 in. (≤DN32).
Fail Safe: MSXX05*
Non-Fail Safe: MVN & MNXX05*
* These actuators are available as factory-installed
assemblies.
See Table 1 for all available options.
Approvals Standards
Actuators: See literature for the given actuator.
™
bearings.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further
information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone
directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China,
Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
38-00032—012
Table 1. VRN Model Selection.
Model Selection: Pressure Independent Control Valve
VRN PRESSURE INDEPENDENT CONTROL VALVES AND ACTUATORS
Valve
Fitting
Size
Body/Flow Type
Max flow rate
Trim
Profile
ActuatorFail PositionAccessories
VR - Pressure Independent Control ValveMVN613A0000*Leave blank = Fail in placeC1 - 1 meter cable
N- Female NPT threadedMVN643A0000*3R - NEMA
2- 2 wayMVN713A0000*
Enclosure
MN6105A1011
MN6105A1201
MN7505A2001
A - 1/2 (DN15)
B - 3/4 (DN20)
C - 1 (DN25)
D - 1-1/4 (DN32)
E - 1-1/2 (DN40)
F - 2 (DN50)
G - 2-1/2 (DN65)
H - 3 (DN80)
MN7505A2209
MS7505A2030
MS7505A2130
MS8105A1030
MS8105A1130
MS4105A1030
FSO = Fail Safe Open
FSC = Fail Safe Closed
MS4105A1130
xxx.xx - Max flow rate designator
See Table 4.
P - Plated Brass
S - Stainless Steel
A - Standard Base
X - MN/MS DCA
Actuator Bracket
VR N 2A 001.00 PA+MVN613A0000++C1
Example part number: VRN2A001.00PA+MVN613A0000+C1
* Only compatible with valves 1-1/4” or smaller.
Table 2. Actuator Control Description.
ActuatorControl
MVN613A0000
MVN643A0000
MVN713A0000
Floating, Two-position (SPDT or SPST) (90 sec. timing), 24 V, Fail in Place
Floating, Two-position (SPDT) Fast Acting (30 sec. timing), 24 V, Fail in Place
Modulating, 24 V, Fail in Place
MN6105A1011Floating, Two-position (SPDT), 24 V, Fail in Place
MN6105A1201 Floating, Two-Position (SPDT), 24 V, Fail in Place with end switches
MN7505A2001Modulating, 24 V, Fail in Place
MN7505A2209 Modulating, 24 V, Fail in Place with end switches