These intermittent pilot gas controls are used in gas-fired
appliances with capacities up to 300 ft
pressure drop (8.5 m
They include a manual valve, two automatic operators,
and a pressure regulator. See Table 1 for temperature
ranges and regulator types.
Table 1. Temperature ranges and regulator types
Model number
VR8304H0 F to 175 F
VR8304K-40 F to 175 F
VR8304M-40 F to 175 F
VR8304P-40 F to 175° F
3
/h at 0.25 kPa) on natural gas.
Ambient
temperature range Regulator type
(-18 C to +79 C)
(-40 C to +79 C)
(-40 C to +79 C)
(-40 C to +79 C)
3
/hr at 1 in. WC
Slow-opening
Slow opening
Standard-opening
Step-opening
SPECIFICATIONS
Body pattern: Straight-through body pattern.
Inlet x outlet sizes available: 1/2 x 1/2 in., 1/2 x 3/4 in.,
and 3/4 x 3/4 in. (factory-installed inlet flange).
Adapters Adapters available for 3/8, 1/2 and 3/4 in.
straight and angle connections. Refer to Table 2.
Electrical Ratings: voltage and frequency: 24 Vac,
50/60 Hz.
Current Draw: 0.7A.
Capacity: See Table 3.
Approvals:
• American Gas Association Design Certificate:
UP-70-69A
• Canadian Gas Association Design Certificate:
UP-70-69A.
• Australian Gas Association Certificate: Applied for.
• Delta C: Applied for.
Inlet/outlet pipe size Flange typePart number
3/8 inch NPTStraight393690-11
1/2 inch NPTElbow393690-13
3/4 inch NPTStraight393690-4
NOTE: Flange kits include one flange with attached O-
(inlet x
outlet)
1/2 x 1/2
1/2 X 3/4
3/4 X 3/4
a
Capacity based on 1000 Btu/ft3, 0.64 specific gravity
natural gas at 1 in. WC pressure drop (37.3 MJ/m
0.64 specific gravity natural gas at 0.25 kPa pressure
drop.
Use conversion factors in Table 4 to convert capacities
for other gases.
Manufactured0.600.516
Mixed0.700.765
Propane1.531.62
Table 2. Flange part numbers
Elbow393690-15
ring and fan mounting screw.
Table 3. Capacity
Capacity at 1 in.
Size
WC pressure
a
drop
3
/hr
240 ft
3
/hr)
(6.8 m
3
/hr
270 ft
3
/hr)
(7.6 m
3
/hr
300 ft
3
/hr)
(8.5 m
Table 4. Gas capacity conversion factors
GasSpecific gravity
Minimum
regulated
capacity
3
30 ft
/hr
3
(0.8 m
3
30 ft
/hr
3
(0.8 m
3
30 ft
/hr
3
(0.8 m
Maximum
regulated
capacity
3
340 ft
/hr)
(9.6 m
3
370 ft
/hr)
(10.5 m
3
415 ft
/hr)
(11.8 m
Multiply listed
capacity by
/hr
3
/hr
/hr
/hr)
3
3
3
/hr)
/r)
,
69-0625—03
VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROL
WARNING
CAUTION
WARNING
INSTALLATION
When installing this product ...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to ensure the product is suitable for
your application.
3. Ensure installer is a trained, experienced service
technician.
4. After installation is complete, use these instructions
to check out product operation.
Fire or explosion hazard. Can cause property
damage, severe injury, or death.
Follow these warnings exactly:
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off gas supply at the appliance service
valve before starting installation, and perform
the gas leak test after completion of installation.
3. Do not bend pilot tubing at gas control or pilot
burner after compression fitting has been
tightened, or gas leakage at the connection
may result.
4. Always install sediment trap in gas supply line
to prevent contamination of gas control.
5. Do not force the gas control knob. Use only
your hand to turn the gas control knob. Never
use tools. If the gas control knob will not
operate by hand, the gas control should be
replaced by a qualified service technician.
Force or attempted repair may result in fire or
explosion.
Never apply a jumper across or short the valve
coil terminals. This may burn out the heat
anticipator in the thermostat or damage the
electronic intermittent pilot (IP) module.
IMPORTANT
These gas controls are shipped with protective
seals over inlet and outlet tappings. Do not
remove the seals until you are ready to connect
piping.
Follow the appliance manufacturer’s instructions if available; otherwise, use the instructions
provided below.
Converting Between Natural and
LP Gas
Fire or explosion hazard. Can cause property
damage, severe injury, or death.
Do not attempt to use a gas control set for
natural gas on LP gas or a gas control set for
LP gas on natural gas.
To convert a gas control from natural gas to LP gas or
from LP gas to natural gas, contact your Honeywell
representative.
Standard- or slow-opening gas controls are converted
from one gas to another with a conversion kit (order
separately). Order Part Number 393691 to convert from
natural to LP gas. Order Part Number 394588 to convert
from LP to natural gas. Step-opening gas controls cannot
be converted.
Install Adapters to Gas Control
Install adapters to the gas control as follows:
Flanges
1. Choose the appropriate flange for your application.
2. Remove the seal over the gas control inlet or outlet.
3. Ensure the O-ring is fitted in the groove of the
flange. If the O-ring is not attached or is missing, do
not use the flange.
4. With the O-ring facing the gas control, align the
screw holes on the gas control with the holes in the
flange. Insert and tighten the screws provided with
the flange. See Fig. 1. Tighten the screws to 25 in.
pounds of torque to provide a gas-tight seal.
9/64 INCH HEX
SCREWS (4)
GAS CONTROL OUTLET
FLANGE
1 DO NOT OVERTIGHTEN SCREWS.
TIGHTEN TO 25 INCH POUNDS.
Fig. 1. Install flange to gas control.
1
M3087
Bushings
1. Remove the seal over the gas control inlet or outlet.
2. Apply moderate amount of good quality pipe com-
pound to the bushing, leaving two end threads bare.
On LP installation, use a compound resistant to LP
gas. Do not use Teflon tape.
3. Insert the bushing into the gas control and thread
the pipe carefully into the bushing until tight.
Using Adapters to Solve Swing
Radius Problems
In some field service applications, it is difficult or
impossible to thread the gas control onto the gas supply
pipe because of space limitations. This problem can be
resolved in many instances by using an adapter. The
adapter is installed on the end of the supply pipe in place
of the gas control, following the same precautions and
instructions that are used for installing the gas control.
After the adapter is installed, the gas control is attached to
the adapter as outlined above. Note that using an adapter
increases the overall length of the gas control.
69-0625—032
Choose Gas Control Location
GAS
CONTROL
GAS
CONTROL
HORIZONTAL
DROP
PIPED
GAS
SUPPLY
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
3 IN.
(76 MM)
MINIMUM
RISER
GAS
CONTROL
TUBING
GAS
SUPPLY
HORIZONTAL
DROP
3 IN.
(76 MM)
MINIMUM
RISER
M3077A
2
1
2
2
1
2
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
OUTLET
PRESSURE
TAP
INLET
OUTLET
WIRING
TERMINALS (3)
INLET
PRESSURE
TAP
PRESSURE REGULATOR
ADJUSTMENT
(UNDER CAP SCREW)
PILOT OUTLET
PILOT ADJUSTMENT
(UNDER CAP SCREW)
GAS CONTROL
KNOB
RED
RESET BUTTON
M1639C
Do not locate the gas control where it may be affected by
steam cleaning, high humidity, dripping water, corrosive
chemicals, dust or grease accumulation, or excessive heat.
To ensure proper operation, follow these guidelines.
• Locate the gas control in a well ventilated area.
• Mount the gas control high enough above the
cabinet bottom to avoid exposure to flooding or
splashing water.
• Ensure the ambient temperature does not
exceed the ambient temperature ratings for each
component.
• Cover the gas control if the appliance is cleaned
with water, steam, or chemicals or to avoid dust
and grease accumulation.
• Avoid locating the gas control where exposure to
corrosive chemical fumes or dripping water is
likely.
Locate the gas control in the appliance vestibule on the
gas manifold. In replacement applications, locate the gas
control in the same location as the old gas control.
Install Piping to the Gas Control
All piping must comply with local codes and ordinances or
with the National Fuel Gas Code (ANSIZ223.1 NFPA No.
54), whichever applies. Tubing installation must comply
with approved standards and practices.
1. Use new, properly reamed pipe free of chips. If tubing is used, ensure the ends are square, deburred
and clean. All tubing bends must be smooth and
without deformation.
2. Run a pipe or tubing to the gas control. If tubing is
used, obtain a tube-to-pipe coupling to connect the
tubing to the gas control.
3. Install a sediment trap in the supply line to the gas
control. See Fig. 2.
Install the Gas Control
1. Mount the gas control 0–90 degrees in any direction
from the upright position of the gas control knob,
including vertically.
Mount the gas control so that gas flow is in the direc-
2.
tion of the arrow on the bottom of the gas control.
3. Thread the pipe the amount shown in Table 5 for
insertion into the gas control or adapter. DO NOT
THREAD THE PIPE TOO FAR. Valve distortion or
malfunction may result if the pipe is inserted too
deeply into the gas control.
4. Apply a moderate amount of good quality pipe compound (DO NOT use Teflon tape) to the pipe only,
leaving two end threads bare. On LP installations,
use a compound resistant to LP gas. Refer to Fig. 3.
5. Remove the seals over the gas control inlet and
outlet if necessary.
Connect the pipe to the gas control inlet and outlet.
6.
Use a wrench on the square ends of the gas control. If
an adapter is used, place the wrench on the adapter
rather than the gas control. Refer to Figs. 4 and 5.
Table 5. NPT pipe thread length (inches)
Pipe size
3189/163/8
1/23/41/2
3/413/163/4
Thread pipe this
amount
Maximum depth pipe
can be inserted into the
control
VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROL
Fig. 2. Install a sediment trap.
TWO IMPERFECT
THREADS
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR
INSERTION INTO GAS CONTROL
GAS CONTROL
PIPE
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).
M3075B
Fig. 3. Use a moderate amount of pipe compound.
Fig. 4. Top view of gas control.
Connect Pilot Gas Tubing
1. Cut tubing to desired length and bend as necessary
for routing to the pilot burner. Do not make sharp
bends or deform the tubing. Do not bend tubing at
gas control or pilot burner after compression fitting
has been tightened, as this may result in gas leakage at the connection.
Square off and remove burrs from the ends of tubing.
2.
369-0625—03
Loading...
+ 5 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.