Honeywell VR8215S, VR8215T, VR8215Q, VR8215N Installation Instructions Manual

VR8215S,T Single Stage VR8215Q,N Two Stage Direct Ignition Gas Controls
INSTALLATION INSTRUCTIONS

APPLICATION

The VR8215S,T Single Stage and VR8215Q,N Two Stage Direct Ignition Gas Controls are used in gas­fired appliances with up to 150 ft wc pressure drop on natural gas. They have been optimized for direct ignition applications and include a on/off switch and a pressure regulator.
Size
Inlet x
Model
VR8215 1/2 x 1/2 150 4.25
a
Capacity based on 1000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressure drop).
b
Minimum regulation for LP gas is 30,000 Btu/h (0.85 m3/hr).
Table 2. Gas Capacity Conversion Factor.
Manufactured 0.60 0.516
Mixed 0.70 0.765
Propane 1.53 1.62
Table 3. Model Number Suffix Letter Designation.
Regulation
Single Stage
Two Stage
Options:
3/16 in. (4.8 mm) and 1/4 in. (6.4 mm) male quick-
connect ground terminals.
Barbed vent fittings for seated combustion:
Single stage: 1/8 in. (3.2 mm) and 1/4 in. (6.4 mm) Two stage: 1/4 in. (6.4 mm)
Outlet
(in. NPT)
Gas Specific Gravity
Model Number
Suffix Letter
3
/hr capacity at 1 in.
Table 1. Valve Capacity.
AGA Certified Capacity
for Natural Gas
3
/hr m3/hr ft3/hr m3/hr ft3/hr m3/hr
ft
Multiply Listed
Capacity By
Pressure
Regulator Type
SStandard
TSlow Opening
QStandard
NSlow Opening

SPECIFICATIONS

Body Pattern: Straight through; see Table 1 for inlet
and outlet size.
• Valve capacities are shown in Table 1.
• Table 2 provides gas capacity conversion factors.
• For suffix letter designation, see Table 3.
a
AGA Certified
Minimum Regulation
for Natural Gas
b
15
Electrical Ratings:
Voltage and Frequency: 24 Vac, 50/60 Hz. Current Draw:
Field Wiring:
Single Stage: Two 1/4 in. spade quick-connect terminals. Two Stage: Molex and spade quick-connect terminals
Capacity: See Table 1.
Conversion:
Use conversion factors in Table 2 to convert
Regulation Range: See Table 6.
Natural-LP Gas Conversion Kits: See Table 4.
Approvals:
CSA Design Certificate #112395.
Australian Gas Association Certificate #7960.
Outlet: Class 2, Grade 20 pressure regulator
Auto shutoff valve function: Class 3
0.42 200 5.66
Single Stage: 0.5 A. Two Stage: 0.9 A.
(two 1/4 in. and one 3/16 in.).
capacities for other gases.
(-40 °F to +175 °F; -40 °C to +79 °C)
(single stage only) (-20 °C to +79 °C only)
AGA Certified
Maximum Regulation
for Natural Gas
69-2253-07
VR8215S,T SINGLE STAGE VR8215Q,N TWO STAGE DIRECT IGNITION GAS CONTROLS
WARNING
WARNING
Table 4. Natural-LP Gas Conversion Kits.
Model Number Suffix Letter Kit to Convert Natural Gas to LP Kit to Convert LP to Natural Gas
S, T 396221 396222
Q, N 32328605 32328973

PLANNING THE INSTALLATION

Fire or Explosion Hazard. Can cause property damage, severe injury, or death.
Follow these warnings exactly:
1. Plan the installation as outlined below.
2. Plan for frequent maintenance as described in the Maintenance section.
Heavy demands are made on the controls when direct ignition systems are used on central heating equipment in barns, greenhouses, and commercial properties and on heating appliances such as commercial cookers, agricultural equipment, industrial heating equipment and pool heaters.
Special steps may be required to prevent nuisance shutdowns and control failure due to frequent cycling, severe environmental conditions related to moisture, corrosive chemicals, dust or excessive heat. These applications require Honeywell Engineering review; contact your Honeywell Sales Representative for assistance.
Review the following conditions that can apply to your specific installation and follow the precautions suggested.

Frequent Cycling

This control is designed for use on appliances that typically cycle three to four times an hour only during the heating season. In year-around applications with greater cycling rates, the control can wear out more quickly. Perform a monthly checkout.
chemicals are suspended in air, as in some industrial or agricultural applications, protect the control with an enclosure.

Dust or Grease Accumulation

Heavy accumulations of dust or grease can cause the control to malfunction. Where dust or grease can be a problem, provide covers for the control to limit contamination.

Heat

Excessively high temperatures can damage the control. Make sure the maximum ambient temperature at the control does not exceed the rating of the control. If the appliance operates at very high temperatures, use insulation, shielding, and air circulation, as necessary, to protect the control. Proper insulation or shielding should be provided by the appliance manufacturer; verify proper air circulation is maintained when the appliance is installed.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to
follow them could damage the product or cause a hazardous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suit­able for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.

Water or Steam Cleaning

If a control gets wet, replace it. If the appliance is likely to be cleaned with water or steam, protect (cover) the control and wiring from water or steam flow. Mount the control high enough above the bottom of the cabinet so it does not get wet during normal cleaning procedures.

High Humidity or Dripping Water

Dripping water can cause the control to fail. Never install an appliance where water can drip on the control. In addition, high ambient humidity can cause the control to corrode and fail. If the appliance is in a humid atmosphere, make sure air circulation around the control is adequate to prevent condensation. Also, regularly check out the system.

Corrosive Chemicals

Corrosive chemicals can attack the control, eventually causing a failure. If chemicals are used for routine cleaning, avoid contact with the control. Where
69-2253—07 2
Fire or Explosion Hazard. Can cause property damage, severe injury or death.
Follow these warnings exactly:
1. Disconnect power supply before wiring to prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas, turn off gas supply at the appliance service valve before star ting installation, and perform Gas Leak Test after installation is complete.
3. Always install a sediment trap in gas supply line to prevent contamination of gas control.
4. Do not force the on-off switch. Use only your fingers to operate the on-off switch. Never use any tools. If the electronic on-off switch does not operate by hand, the gas control should be replaced by a qualified service technician. Force or attempted repair may result in fire or explosion.
5. Gas will leak if installed backwards.
VR8215S,T SINGLE STAGE VR8215Q,N TWO STAGE DIRECT IGNITION GAS CONTROLS
CAUTION
Equipment Damage Hazard. Can burn out thermostat or transformer.
Applying a jumper across (or shorting) the valve coil terminals, even temporarily, can burn out the thermostat or transformer.
Follow the appliance manufacturers instructions if available; otherwise use these instructions as a guide.
IMPORTANT
These gas controls are shipped with protective seals over the inlet and outlet tappings. Do not remove the seals until ready to install adapters or connect the piping.

Install Bushings To Control

If bushings are being installed on the control, mount them as follows:
Bushings
1. Remove the seal over the control inlet or outlet.
2. Apply a moderate amount of good quality pipe
compound to the bushing, leaving two end threads bare. On an LP installation, use compound that is resistant to LP gas. See Fig. 1.
NOTE: Do not use Teflon tape.
3. Insert the bushing in the control and carefully thread the pipe into the bushing until tight.
Complete the instructions below for installing the piping, installing the control, and connecting the wiring. Make sure the leak test you perform on the control after completing the installation includes leak testing the bushings.

Location

The gas controls are mounted in the appliance vestibule on the gas manifold. If this is a replacement application, mount the gas control in the same location as the old control.
Locate the combination gas control where it cannot be affected by steam cleaning, high humidity, or dripping water, corrosive chemicals, dust or grease accumulation or excessive heat.
To assure proper operation, follow these guidelines:
• Locate gas control in a well-ventilated area.
• Mount gas control high enough above cabinet bottom to avoid exposure to flooding or splashing water.
• Assure the ambient temperature does not exceed the ambient temperature ratings for each component.
• Cover gas control if appliance is cleaned with water, steam, or chemicals or to avoid dust and grease accumulation.
• Avoid locating gas control where exposure to corrosive chemical fumes or dripping water are likely.

Install Piping to Control

All piping must comply with local codes and ordinances or with the National Fuel Gas Code (ANSI Z223.1, NFPA No. 54), whichever applies. Tubing installation must comply with approved standards and practices.
1. Use new, properly reamed pipe that is free from chips. If tubing is used, make sure the ends are square, deburred and clean. All tubing bends must be smooth and without deformation.
2. Run pipe or tubing to the control. If tubing is used, obtain a tube-to-pipe coupling to connect the tubing to the control.
3. Install a sediment trap in the supply line to the control. See Fig. 2.

Install Control

1. Can be mounted in any direction.
2. Mount so the gas flow is in the direction of the
arrow on the bottom of the control.
NOTE: Gas valve will leak if installed backwards.
3. Thread the pipe the amount shown in Table 5 for insertion into control or adapters. Do not thread pipe too far. Valve distortion or malfunction can result if the pipe is inserted too deeply.
4. Apply a moderate amount of good quality pipe compound (do not use Teflon tape) only to the pipe, leaving two end threads bare. On LP installations, use a compound resistant to LP gas. See Fig. 1.
5. Remove the seals over the control inlet and out­let if necessary.
6. Connect the pipe to the control inlet and outlet. Use a wrench on the hex end of the control. See Fig. 3.
Table 5. NPT Pipe Thread Length.
Pipe
Thread Pipe
Size
this Amount
b
9/16 (14) 3/8 (9)
3/8
Maximum Depth Pipe can be
inserted into Control
1/2 3/4 (19) 1/2 (13)
a
All dimensions are in inches (mm).
b
OK when bushings are used.
TWO IMPERFECT THREADS
THREAD PIPE THE AMOUNT SHOWN IN TABLE FOR INSERTION INTO GAS CONTROL
GAS CONTROL
PIPE
APPLY A MODERATE AMOUNT OF PIPE COMPOUND TO PIPE ONLY (LEAVE TWO END THREADS BARE).
Fig. 1. Use moderate amount of pipe compound.
a
M3075B
3 69-2253—07
VR8215S,T SINGLE STAGE VR8215Q,N TWO STAGE DIRECT IGNITION GAS CONTROLS
WARNING
GAS CONTROL
GAS CONTROL
HORIZONTAL
DROP
PIPED GAS SUPPLY
PIPED GAS SUPPLY
3 IN.
(76 MM)
MINIMUM
3 IN.
(76 MM)
MINIMUM
RISER
GAS CONTROL
TUBING GAS SUPPLY
HORIZONTAL
DROP
3 IN.
(76 MM)
MINIMUM
RISER
M3077
2
1
2
2
1
2
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
M27669
24V
24V (GND)
S87B CONTROL MODULE
ALARM
VALV E
VALV E
GND
TEMPERATURE CONTROLLER
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
ALTERNATE LIMIT CONTROLLER LOCATION.
MAXIMUM IGNITER-SENSOR CABLE LENGTH: 3 ft. (0.9 m) OR LESS.
3A REPLACEABLE FUSE.
ALARM TERMINAL PROVIDED ON SOME MODELS.
M27697
L1
(HOT)
L2
1
2
1
2
3
DUAL VALVE COMBINATION GAS CONTROL
Q347 IGNITER-SENSOR
BURNER
4
4
5
IGNITER-SENSOR AND BURNER GROUND
3
5
ALARM, IF USED
IMPORTANT
All wiring must comply with applicable electri­cal codes and ordinances.
Electrical Shock Hazard or Equipment Damage Hazard. Can cause serious injury, death or equipment damage.
Disconnect power supply before making wiring connections to prevent electrical shock or equipment damage.
1. Check the power supply rating on the gas control and make sure it matches the available supply. Install a transformer and other controls as required.
2. Connect the control circuit to the gas control terminals. See Fig. 4 and 5.
3. Two stage gas valve wiring: MV - Main valve or low fire. C - Common terminal of ignition coils. HI - Second stage or high fire.
4. For single stage controls (VR8215S,T):
adjust thermostat heat anticipator to 0.50A rating stamped on valve label.
For two stage controls (VR8215Q,N): adjust thermostat heat anticipator to 0.90A
Fig. 2. Sediment trap installation.
rating stamped on valve label.

Wiring

Follow the wiring instructions furnished by the appliance manufacturer, if available, or use the general instructions provided below. When these instructions differ from the appliance manufacturer, follow the appliance manufacturer instructions.
69-2253—07 4
Fig. 3. Proper use of wrench on gas control.
Fig. 4. Typical wiring connections for 24 volt
control in S87 Direct Ignition System.
Loading...
+ 8 hidden pages