VR8104, VR8204, AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
Corrosive Chemicals
Corrosive chemicals can attack the control, eventually
causing a failure. If chemicals are used for routine
cleaning, avoid contact with the control. Where chemicals
are suspended in air, as in some industrial or agricultural
applications, protect the control with an enclosure.
Dust or Grease Accumulation
Heavy accumulations of dust or grease can cause the
control to malfunction. Where dust or grease can be a
problem, provide covers for the control to limit
contamination.
Heat
Excessively high temperatures can damage the control.
Make sure the maximum ambient temperature at the
control does not exceed the rating of the control. If the
appliance operates at very high temperatures, use
insulation, shielding, and air circulation, as necessary, to
protect the control. Proper insulation or shielding should
be provided by the appliance manufacturer; verify proper
air circulation is maintained when the appliance is
installed.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury
or death.
Follow these warnings exactly:
1. Disconnect power supply before wiring to
prevent electrical shock or equipment damage.
2. To avoid dangerous accumulation of fuel gas,
turn off the gas supply at the appliance service
valve before starting installation, and perform
Gas Leak Test after installation is complete.
3. Do not bend pilot tubing at gas control or pilot
burner after compression fitting is tightened, or
gas leakage at the connection can result.
4. Always install a sediment trap in the gas supply
line to prevent contamination of the gas control.
5. Do not force the gas control knob. Use only
your hand to turn the gas control knob. Never
use any tools. If the gas control knob will not
operate by hand, the gas control should be
replaced by a qualified service technician.
Force or attempted repair may result in fire or
explosion.
CAUTION
Equipment Damage.
Can burn out valve coil terminals.
Never apply a jumper across (or short) the valve
coil terminals, even temporarily.
Follow the appliance manufacturers instructions if
available; otherwise, use these instructions as a guide.
IMPORTANT
These gas controls are shipped with protective
seals over the inlet and outlet tappings. Do not
remove the seals until ready to install adapters
or connect the piping.
Converting Gas Control from Natural Gas
to LP Gas (or LP Gas to Natural Gas)
WARNING
Fire Or Explosion Hazard.
Can cause property damage, severe injury
or death.
1. Do not attempt to convert step-opening models
(suffix letter P).
2. Always change the main and pilot burner
orifices when converting from natural to LP gas
or from LP to natural gas. Carefully follow
appliance manufacturer specifications and
instructions to assure proper appliance
conversion.
3. Gas controls are factory-set for natural (and
manufactured) or LP gas. Do not attempt to use
a gas control set for natural (manufactured) gas
on LP gas, or a gas control set for LP gas on
natural (manufactured) gas.
Controls with standard, slow-opening, and two-stage
regulators (model numbers with suffix H, K, M, or Q) can
be converted from one gas to the other with a conversion
kit (ordered separately). See Table 4 for the correct
conversion kit.
Convertible Pressure Regulators
Controls with suffix letter R are convertible pressure
regulator models. They can be converted from natural gas
to LP gas or from LP gas to natural gas without a
conversion kit.
Before converting the control from one gas to another,
check the control label and the appliance manufacturer’s
rating plate to determine if the pressure regulator setting
(factory set) will meet the appliance manifold
requirements after conversion.
NOTE: Convertible pressure regulator models (suffix
letter R) do not have field-adjustable regulators.
If the factory pressure regulator setting meets the
appliance manifold requirement, convert the control as
follows:
1. Remove the pressure regulator cap, Fig. 1.
2. Invert the cap so that the letters appear that
represent the gas type appropriate for the
appliance. NAT for natural manufactured gas, LP
for liquid petroleum gas.
3. Replace the cap and tighten firmly.
69-1225—5 4
VR8104, VR8204, AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
T
N
A
A
N
T
PRESSURE
REGULATOR
CAP
T
N
A
A
N
T
Fig. 1. Top view of convertible
pressure regulator cap.
P
OR
L
OTHER SIDE
OF CAP
M11678
L
P
Install Adapters To Control
If adapters are being installed on the control, mount them
as follows:
Flanges
1. Choose the appropriate flange for your application.
2. Remove the seal over the gas control inlet or outlet.
3. Make sure that the O-ring is fitted in the groove of
the flange. If the O-ring is not attached or is missing,
do not use the flange.
4. With the O-ring facing the control, align the screw
holes on the gas control with the holes in the flange.
Insert and tighten the screws provided with the
flange. See Fig. 2. Tighten the screws to 25
inch-pounds of torque to provide a gas-tight seal.
Bushings
1. Remove the seal over the control inlet or outlet.
2. Apply a moderate amount of good quality pipe
compound to the bushing, leaving two end threads
bare. On an LP installation, use compound that is
resistant to LP gas. Do not use Teflon tape.
3. Insert the bushing in the control and carefully thread
the pipe into the bushing until tight.
Complete the instructions below for installing the piping,
installing the control, connecting the pilot gas tubing and
the wiring. Make sure the leak test you perform on the
control after completing the installation includes leak
testing the adapters and screws. If you use a wrench on
the valve after the flanges are installed, use the wrench
only on the flange, not on the control. See Fig. 5.
VALVE OUTLET
FLANGE
9/64 INCH HEX SCREWS (4)
DO NOT OVERTIGHTEN SCREWS. TIGHTEN TO
1
25 INCH-POUNDS.
Fig. 2. Firmly fasten flange to valve, but
do not overtighten screws.
1
M9046
Location
The combination gas control is mounted in the appliance
vestibule on the gas manifold. If this is a replacement
application, mount the gas control in the same location as
the old control.
Locate the combination gas control where it cannot be
affected by steam cleaning, high humidity, or dripping
water, corrosive chemicals, dust or grease accumulation
or excessive heat. To assure proper operation, follow
these guidelines:
• Locate gas control in a well-ventilated area.
• Mount gas control high enough above cabinet bottom
to avoid exposure to flooding or splashing water.
• Assure the ambient temperature does not exceed the
ambient temperature ratings for each component.
• Cover gas control if appliance is cleaned with water,
steam, or chemicals or to avoid dust and grease
accumulation.
• Avoid locating gas control where exposure to corrosive
chemical fumes or dripping water are likely.
Install Piping to Control
All piping must comply with local codes and ordinances or
with the National Fuel Gas Code (ANSI Z223.1,
NFPA No. 54), whichever applies. Tubing installation must
comply with approved standards and practices.
1. Use new, properly reamed pipe that is free from
chips. If tubing is used, make sure the ends are
square, deburred and clean. All tubing bends must
be smooth and without deformation.
2. Run pipe or tubing to the control. If tubing is used,
obtain a tube-to-pipe coupling to connect the tubing
to the control.
3. Install a sediment trap in the supply line to the
control. See Fig. 3.
5 69-1225—5
VR8104, VR8204, AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
4. Apply a moderate amount of good quality pipe
DROP
3 IN.
PIPED
GAS
SUPPLY
GAS
CONTROL
2
DROP
TUBING
1
GAS
SUPPLY
2
GAS
CONTROL
2
HORIZONTAL
3 IN.
(76 MM)
MINIMUM
HORIZONTAL
RISER
(76 MM)
MINIMUM
ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
1
2
CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING
END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST
FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
RISER
PIPED
GAS
SUPPLY
3 IN.
(76 MM)
MINIMUM
GAS
CONTROL
M3077
Fig. 3. Sediment trap installation.
Install Control
1. Mounted 0 to 90 degrees in any direction, including
vertically, from the upright position of the gas control
knob.
2. Mount so the gas flow is in the direction of the arrow
on the bottom of the control.
3. Thread the pipe the amount shown in Table 7 for
insertion into control or adapters. Do not thread
pipe too far. Valve distortion or malfunction can
result if the pipe is inserted too deeply.
Table 7. NPT Pipe Thread Length (in.).
Pipe
Size
Thread Pipe
this Amount
Maximum Depth Pipe can
be Inserted into Control
compound (do not use Teflon tape) only to the pipe,
leaving two end threads bare. On LP installations,
use a compound resistant to LP gas. See Fig. 4.
5. Remove the seals over the control inlet and outlet if
necessary.
6. Connect the pipe to the control inlet and outlet. Use
a wrench on the square ends of the control. If a
flange is used, place the wrench on the flange
rather than on the gas control. Refer to Fig. 5 and 6.
Connect Pilot Gas Tubing
1. Cut tubing to the desired length and bend as
necessary for routing to the pilot burner. Do not
make sharp bends or deform the tubing. Do not
bend the tubing at the gas control after the
compression nut is tightened, because this can
result in gas leakage at the connection.
2. Square off and remove burrs from the end of the
tubing.
3. Unscrew the brass compression fitting from the pilot
outlet (Fig. 6). Slip the fitting over the tubing and
slide out of the way. See Fig. 7.
NOTE: When replacing a control, cut off the old
compression fitting and replace with the
compression fitting provided on the combination
gas control. Never use the old compression
fitting because it may not provide a gas-tight
seal.
4. Push the tubing into the pilot gas tapping on the
outlet end of the control until it bottoms. While
holding the tubing all the way in, slide the fitting into
place and engage the threads; then turn until finger
tight. Tighten one more turn with a wrench, but do
not overtighten.
5. Connect the other end of the tubing to the pilot
burner according to the pilot burner manufacturer’s
instructions.
TWO IMPERFECT
THREADS
THREAD PIPE THE AMOUNT
SHOWN IN TABLE FOR
INSERTION INTO GAS CONTROL
GAS CONTROL
PIPE
3/8 9/16 3/8
1/2 3/4 1/2
Fig. 4. Use moderate amount of pipe compound.
3/4 13/16 3/4
APPLY A MODERATE AMOUNT OF
PIPE COMPOUND TO PIPE ONLY
(LEAVE TWO END THREADS BARE).
M3075B
69-1225—5 6