
BEFORE INSTALLATION
VP527A Pneumatic
Water Valve
INSTALLATION INSTRUCTIONS
Allow sufficient room for servicing or removing the valve. See
Fig. 1 for space requirements. This valve can be installed in
any position. The direction of the flow should be in the same
direction as the arrow cast on the valve body.
INSTALLATION
1. Mount the valve. See Fig. 1 and 2.
2. Connect the control air tubing.
NOTE: No calibration or adjustments are necessary.
AIR CONNECTION
FOR 1/4 IN. (6 MM)
O.D. PLASTIC TUBING
1 2 ALLOW 1-1/2 IN. (38 MM) MINIMUM CLEARANCE TO SERVICE VALVE,
2-1/2 IN. (63 MM) CLEARANCE TO CONNECT TUBING STRAIGHT TO
CONNECTOR. IF CLEARANCE IS LESS THAN 2-1/2 IN. (63 MM),
USE AN ELBOW CONNECTOR.
ALLOW 1-3/8 IN. (35 MM) MINIMUM CLEARANCE TO REMOVE VALVE.
2-1/4 (57) DIA.
1-1/2
(38)
1-3/8
(35)
3-1/8 (79)
1/2 IN. (12MM) X 45° SAE FLARED TUBE
CONNECTION - 2 (NOT FURNISHED)
1-5/8
(41)
22
3-13/16
M18348
Fig. 1. VP527A dimensions in in. (mm).
1
(97)
® U.S. Registered Trademark
Copyright © 2002 Honeywell • All Rights Reserved
95-5555EF

VP527A PNEUMATIC WATER VALVE
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
USE 1/2 IN. (6 MM) O.D.
COPPER TUBING
IN
Fig. 2. VP527A connectors and copper tubing dimensions in. (mm).
TYPICAL OPERATION
An increase in control air pressure moves the valve stem
toward the closed position, modulating flow through the valve.
CONTROL AIR
VP527A
SYSTEM
SUPPLY
N.O.
1/2 IN. O.D. X 45° SAE
FLARED TUBE
CONNECTORS (2)
(NOT FURNISHED)
M18349
OUT
Fig. 3. VP527A typical operation.
Automation and Control Solutions
Honeywell Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North 35 Dynamic Drive
Golden Valley, MN 55422 Scarborough, Ontario
95-5555EF J.H. Rev. 1-02
M1V 4Z9
M18350
customer.honeywell.com