Honeywell VP527A Installation Instructions Manual

BEFORE INSTALLATION

VP527A Pneumatic
Water Valve
INSTALLATION INSTRUCTIONS
Allow sufficient room for servicing or removing the valve. See Fig. 1 for space requirements. This valve can be installed in any position. The direction of the flow should be in the same direction as the arrow cast on the valve body.

INSTALLATION

1. Mount the valve. See Fig. 1 and 2.
2. Connect the control air tubing.
NOTE: No calibration or adjustments are necessary.
AIR CONNECTION FOR 1/4 IN. (6 MM) O.D. PLASTIC TUBING
1 2 ALLOW 1-1/2 IN. (38 MM) MINIMUM CLEARANCE TO SERVICE VALVE,
2-1/2 IN. (63 MM) CLEARANCE TO CONNECT TUBING STRAIGHT TO CONNECTOR. IF CLEARANCE IS LESS THAN 2-1/2 IN. (63 MM), USE AN ELBOW CONNECTOR.
ALLOW 1-3/8 IN. (35 MM) MINIMUM CLEARANCE TO REMOVE VALVE.
2-1/4 (57) DIA.
1-1/2
(38)
1-3/8
(35)
3-1/8 (79)
1/2 IN. (12MM) X 45° SAE FLARED TUBE CONNECTION - 2 (NOT FURNISHED)
1-5/8
(41)
22
3-13/16
M18348
Fig. 1. VP527A dimensions in in. (mm).
1
(97)
® U.S. Registered Trademark Copyright © 2002 Honeywell • All Rights Reserved
95-5555EF
VP527A PNEUMATIC WATER VALVE
Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper fibers.
USE 1/2 IN. (6 MM) O.D. COPPER TUBING
IN
Fig. 2. VP527A connectors and copper tubing dimensions in. (mm).

TYPICAL OPERATION

An increase in control air pressure moves the valve stem toward the closed position, modulating flow through the valve.
CONTROL AIR
VP527A
SYSTEM SUPPLY
N.O.
1/2 IN. O.D. X 45° SAE FLARED TUBE CONNECTORS (2) (NOT FURNISHED)
M18349
OUT
Fig. 3. VP527A typical operation.
Automation and Control Solutions
Honeywell Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario
95-5555EF J.H. Rev. 1-02
M1V 4Z9
M18350
customer.honeywell.com
Loading...
+ 2 hidden pages