UV100A1000 AND UV100A1018 AIR TREATMENT SYSTEMS
UV100A1059 AND UV100A2008 SURFACE TREATMENT SYSTEMS
PRODUCT DATA
FEATURES
• SnapLamp™ features replacement lamp handle with
detachable replacement bulb, UC18W or UC36W, to
make replacement more economical.
• UV-C light kills airborne bacteria or surface mold.
• Continuously emits ultraviolet energy.
• UV lamp does not produce ozone.
• Sealed unit design prevents accidental installer and
homeowner contact with the voltage and with the
ultraviolet rays.
APPLICATION
When installed in forced air heating and cooling systems,
the UV100A Ultraviolet System kills airborne or surface
micro-organism contaminants.
• Safe design prevents lamps from lighting unless the
base is correctly mounted on the HVAC duct.
• Lamp light indicator to safely view the lamp operation.
• Power cord that plugs into electrical outlet.
• Quick and easy bulb replacement.
• Easy lamp maintenance.
• Optional AIRWATCH™ Indicator can be installed to
remind customers when to change bulb.
• To capture and minimize micro-organism pass-through
in residential heating, ventilation and air conditioning
(HVAC) systems, combine the Ultraviolet System with
a high-efficiency air filtration system that includes an
electronic air cleaner.
Parts List .......................................................................... 12
68-0248-4
UV100A ULTRAVIOLET SYSTEMS
SPECIFICATIONS
IMPORTANT
The specifications in this publication do not include
normal manufacturing tolerances; therefore, an
individual unit may not exactly match the listed
specifications. This product is tested and calibrated
under closely controlled conditions and some minor
differences in performance can be expected if those
conditions are changed.
TRADELINE® Models available:
The UV100A Ultraviolet System is available in four models: a
single-lamp air treatment system; a dual-lamp air treatment
system; a 120V surface treatment system; and a 240V
surface treatment system.
• UV100A Air Treatment System (single-lamp) is mounted in
the return air duct of an HVAC system. It has moderateefficiency performance against airborne bacteria in return
air applications.
• UV100A AIr Treatment System (dual-lamp) is mounted in
the return air duct of an HVAC system. It has highefficiency performance against airborne bacteria in return
air applications.
• UV100A Surface Treatment System (120V or 240V) is
mounted downstream from air conditioner cooling coils of
HVAC system. The unit reduces mold growth and spores
on duct surfaces, coils and drip pans. (Optionally, UV100A
Surface Treatment System can be mounted in return air
duct of HVAC system. It has moderate efficiency performing against airborne bacteria in return air applications.)
Efficiencies:
• UV100A Surface Treatment System (120V and 240V): Kills
up to 99.9% of mold on system cooling coils or kills up to
75% of airborne bacteria passing by the system
(depending on installation).
— Test performed in a test duct showed reduction in
colony-forming aspergillus niger mold spores when
surface was irradiated at a distance of 18 in. for three
hours in still air, using new lamps.
— Test showed single-pass kill-rate of serratia bacteria in
a clean metal 12 in. x 25 in. duct at an airflow of
2000 cfm using new lamps.
• UV100A Air Treatment System (dual-lamp): Kills up to 87%
of airborne bacteria passing by the system.
— Test showed single-pass kill-rate of serratia
marcescens bacteria in a clean metal 12 in. x 25 in.
duct at an airflow rate of 2000 cfm using new lamps.
• UV100A Air Treatment System (single lamp): Kills up to
70% of airborne bacteria passing by the system.
— Test showed single-pass kill-rate of serratia
marcescens bacteria in a clean metal 12 in. x 25 in.
duct at an airflow rate of 2000 cfm using new lamps.
Electrical Ratings:
Power Rating: 120 Vac, 60 Hz or 240V, 60 Hz.
Consumption:
Input
Vol tag e
Model
UV100A1000 Air Treatment
System (single lamp)
UV100A1018 Air Treatment
System (dual lamp)
UV100A1059 Surface
Treatment System (120V)
UV100A2008 Surface
Treatment System (240V)
Temperature Ratings:
Air Treatment System (dual lamp):
Ambient Temperature Range: 30°F to 104°F (-2°C to
40°C).
Lamp Temperature Range: 30°F to 104°F (-2°C to 40°C)
and 170°F (77°C) in moving air.
Air Treatment System (single lamp) and Surface Treatment
System:
Ambient Temperature Range: 30°F to 120°F (-2°C to 49°C)
and 170°F (77°C) in moving air.
Lamp Temperature Range: 30°F to 120°F (-2°C to 49°C)
and 170°F (77°C) in moving air.
Relative Humidity:
Up to 95% rh, non-condensing.
Dimensions: See Fig. 3.
Approvals:
Underwriters Laboratories: File no. E223009
The health aspects associated with the use of this product and
its ability to aid in disinfection of environmental air have not
been investigated by UL.
(Vac)
Power
(A)
1200.418
1200.736
1200.85 36
2400.35 36
Bulb
Wattage
(W)
(each bulb)
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0248—42
INSTALLATION
UV100A ULTRAVIOLET SYSTEMS
When Installing this Product…
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous
condition.
2. Check the rating given in the instructions and on the
product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
UV Light Hazard.
Harmful to bare skin and eyes.
Can cause temporary or permanent loss of vision.
Never look at the bulbs while illuminated.
View illumination only through light indicator located on
lamp handle.
To prevent exposure to ultraviolet light, disconnect
power to Ultraviolet System before servicing any part of
the heating and air conditioning system.
Do not mount device in location that allows ultraviolet
light to be seen after installation.
Do not attempt to bypass duct mount switch.
Do not attempt to open housing; unit is sealed to
prevent ultraviolet light exposure.
Depending on installation location, the UV System can operate
as an Air Treatment System or as a Surface Treatment
System.
Air Treatment System
Installed in the return air duct of the system, the Ultraviolet Air
Treatment System kills a high percentage of airborne germs
circulating through the forced air heating and cooling system.
Individual results depend on careful installation and
maintenance and on the actual amount of time the system fan
operates. See Fig. 1.
!
W
A
R
N
IN
G
Nocifs pour la pe
/
A
V
E
R
Ve
T
IS
u
S
illez lire et
E
l’in
M
E
stal
N
au
T
lation et la
nue et l
bien com
es
m
pr
a
endre
int
enance.
CAUTION
Personal Injury Hazard.
Power supply can cause electrical shock.
Disconnect power supply before beginning installation.
Do not open base unit or lamp handle; there are no
user-serviceable components inside.
Selecting Mounting Location
CAUTION
Equipment Damage Hazard.
Ultraviolet light can cause color shift or structural
degradation of plastic HVAC materials.
Select mounting location that prevents exposure to
plastic components with unknown resistance to ultraviolet light. Three-feet minimum is recommended
between ultraviolet lamp and plastic-fabricated devices
(such as humidifiers and non-fiberglass media filters).
T
N
E
M
E
S
IS
T
R
E
V
/A
G
IN
N
et les
R
A
nue
re
W
d
!
eau
pren
our la p
enance.
et bien com
aint
Nocifs p
m
la
Veuillez lire
tallation et
l’ins
M22857
Fig. 1. Typical Air Treatment System installations.
368-0248—4
UV100A ULTRAVIOLET SYSTEMS
Surface Treatment System
When installed next to the cooling coil, the Ultraviolet Surface
Treatment System prevents a high percentage of the growth of
micro-organisms such as mold that may grow on duct
surfaces, coils and drain pans. Individual results depend on
careful installation and maintenance. See. Fig. 2.
ENT
s
e
l
et
e
re
u
n
u
end
a
WARNING/AVERTISSEM
e
!
p
e.
a
l
r
u
o
enanc
int
s p
if
c
ma
o
ire et bien compr
N
la
z l
n et
Veuille
latio
stal
l’in
T
N
E
M
E
S
TIS
R
VE
/A
G
es
IN
N
R
A
nue et l
re
W
d
!
n
au
e
r
p
m
.
o
e
c
c
n
en
a
i
pour la pe
b
t
ifs
ten
e
in
e
a
Noc
lir
m
z
t la
ille
u
e
e
n
V
io
t
lla
sta
l’in
M22859
Fig. 2. Typical Surface Treatment installations.
IMPORTANT
If mounting options are limited, protect plastic or
rubber materials listed in CAUTION with ultravioletresistant material such as aluminum foil duct tape.
NOTE: When the installer is uncertain about whether the drip
pan in the installation can tolerate UV exposure,
consult the UV exposure white paper, form no.
50-8788, at hbctechlit.honeywell.com Web site.
1. The UV System can be mounted in any orientation.
2. Choose a location that is readily accessible for regular
inspection and cleaning.
3. Allow clearance in front of the device for removing the
bulb assemblies. See Fig. 3 for bulb assembly lengths.
4. Mount the UV System to non-lined metal ductwork. Do
not mount in a location that permits ultraviolet exposure
to plastic flexible duct liner.
CAUTION
Sharp Edges Hazard.
Can cause personal injury.
Be careful when inserting ultraviolet device into the
sheet metal cutout.
Wear protective gloves when working near sheet metal.
Duct Mounting
Use the following instructions to mount the UV System on the
air duct of an HVAC system:
1. Disconnect power to the HVAC system before installing
the UV System.
2. Determine the location for installation (see Fig. 1 and 2):
a. The UV Air Treatment System requires an easily-
accessible, flat mounting surface on the metal return
air duct of the HVAC system. The UV Surface
Treatment System requires an easily-accessible, flat
mounting surface on the metal supply air duct of the
HVAC system. The UV Surface Treatment System
must be located so the lamp surrounds the
evaporator coil and drip pan with ultraviolet light.
b. The duct mounting location must be a minimum of
8 in. wide. See Fig. 3.
c. The depth of the duct must accommodate the full
length of the ultraviolet bulb for your model as shown
in Fig. 3.
d. The unit should be located as far away as possible
from any rubber or plastic components, such as
isolators, in the duct.
e. The space adjacent to the mounting location must be
large enough to allow for ultraviolet bulb installation
and removal.
f.A 120V or 240V electrical outlet must be within range
of the unit to plug in the power cord.
68-0248—44