Honeywell Uv100a1018, Uv100a1026, Uv100a1059, Uv100a1000 Product Data

UV100A Ultraviolet Systems
UV100A1000 AND UV100A1018 AIR TREATMENT SYSTEMS UV100A1059 AND UV100A2008 SURFACE TREATMENT SYSTEMS
PRODUCT DATA

FEATURES

• SnapLamp™ features replacement lamp handle with detachable replacement bulb, UC18W or UC36W, to make replacement more economical.
• UV-C light kills airborne bacteria or surface mold.
• Continuously emits ultraviolet energy.
• UV lamp does not produce ozone.
• Sealed unit design prevents accidental installer and homeowner contact with the voltage and with the ultraviolet rays.

APPLICATION

When installed in forced air heating and cooling systems, the UV100A Ultraviolet System kills airborne or surface micro-organism contaminants.
• Safe design prevents lamps from lighting unless the base is correctly mounted on the HVAC duct.
• Lamp light indicator to safely view the lamp operation.
• Power cord that plugs into electrical outlet.
• Quick and easy bulb replacement.
• Easy lamp maintenance.
• Optional AIRWATCH™ Indicator can be installed to remind customers when to change bulb.
• To capture and minimize micro-organism pass-through in residential heating, ventilation and air conditioning (HVAC) systems, combine the Ultraviolet System with a high-efficiency air filtration system that includes an electronic air cleaner.
Contents
Application/Features ......................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Checkout .......................................................................... 9
Troubleshooting and Service ............................................ 9
Maintenance ..................................................................... 9
Parts List .......................................................................... 12
68-0248-4
UV100A ULTRAVIOLET SYSTEMS

SPECIFICATIONS

IMPORTANT
The specifications in this publication do not include normal manufacturing tolerances; therefore, an individual unit may not exactly match the listed specifications. This product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed.
TRADELINE® Models available:
The UV100A Ultraviolet System is available in four models: a single-lamp air treatment system; a dual-lamp air treatment system; a 120V surface treatment system; and a 240V surface treatment system.
• UV100A Air Treatment System (single-lamp) is mounted in the return air duct of an HVAC system. It has moderate­efficiency performance against airborne bacteria in return air applications.
• UV100A AIr Treatment System (dual-lamp) is mounted in the return air duct of an HVAC system. It has high­efficiency performance against airborne bacteria in return air applications.
• UV100A Surface Treatment System (120V or 240V) is mounted downstream from air conditioner cooling coils of HVAC system. The unit reduces mold growth and spores on duct surfaces, coils and drip pans. (Optionally, UV100A Surface Treatment System can be mounted in return air duct of HVAC system. It has moderate efficiency per­forming against airborne bacteria in return air applications.)
Efficiencies:
• UV100A Surface Treatment System (120V and 240V): Kills up to 99.9% of mold on system cooling coils or kills up to 75% of airborne bacteria passing by the system (depending on installation). — Test performed in a test duct showed reduction in
colony-forming aspergillus niger mold spores when surface was irradiated at a distance of 18 in. for three hours in still air, using new lamps.
— Test showed single-pass kill-rate of serratia bacteria in
a clean metal 12 in. x 25 in. duct at an airflow of 2000 cfm using new lamps.
• UV100A Air Treatment System (dual-lamp): Kills up to 87% of airborne bacteria passing by the system. — Test showed single-pass kill-rate of serratia
marcescens bacteria in a clean metal 12 in. x 25 in. duct at an airflow rate of 2000 cfm using new lamps.
• UV100A Air Treatment System (single lamp): Kills up to 70% of airborne bacteria passing by the system. — Test showed single-pass kill-rate of serratia
marcescens bacteria in a clean metal 12 in. x 25 in. duct at an airflow rate of 2000 cfm using new lamps.
Electrical Ratings:
Power Rating: 120 Vac, 60 Hz or 240V, 60 Hz. Consumption:
Input
Vol tag e
Model
UV100A1000 Air Treatment System (single lamp)
UV100A1018 Air Treatment System (dual lamp)
UV100A1059 Surface Treatment System (120V)
UV100A2008 Surface Treatment System (240V)
Temperature Ratings:
Air Treatment System (dual lamp):
Ambient Temperature Range: 30°F to 104°F (-2°C to
40°C).
Lamp Temperature Range: 30°F to 104°F (-2°C to 40°C)
and 170°F (77°C) in moving air.
Air Treatment System (single lamp) and Surface Treatment
System: Ambient Temperature Range: 30°F to 120°F (-2°C to 49°C)
and 170°F (77°C) in moving air.
Lamp Temperature Range: 30°F to 120°F (-2°C to 49°C)
and 170°F (77°C) in moving air.
Relative Humidity:
Up to 95% rh, non-condensing.
Dimensions: See Fig. 3.
Approvals:
Underwriters Laboratories: File no. E223009 The health aspects associated with the use of this product and its ability to aid in disinfection of environmental air have not been investigated by UL.
(Vac)
Power
(A)
120 0.4 18
120 0.7 36
120 0.85 36
240 0.35 36
Bulb
Wattage
(W)
(each bulb)
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
68-0248—4 2

INSTALLATION

UV100A ULTRAVIOLET SYSTEMS

When Installing this Product…

1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the rating given in the instructions and on the
product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
WARNING
UV Light Hazard. Harmful to bare skin and eyes. Can cause temporary or permanent loss of vision.
Never look at the bulbs while illuminated. View illumination only through light indicator located on lamp handle. To prevent exposure to ultraviolet light, disconnect power to Ultraviolet System before servicing any part of the heating and air conditioning system. Do not mount device in location that allows ultraviolet light to be seen after installation. Do not attempt to bypass duct mount switch. Do not attempt to open housing; unit is sealed to prevent ultraviolet light exposure.
Depending on installation location, the UV System can operate as an Air Treatment System or as a Surface Treatment System.

Air Treatment System

Installed in the return air duct of the system, the Ultraviolet Air Treatment System kills a high percentage of airborne germs circulating through the forced air heating and cooling system. Individual results depend on careful installation and maintenance and on the actual amount of time the system fan operates. See Fig. 1.
!
W
A
R
N
IN
G
Nocifs pour la pe
/ A
V
E
R
Ve
T
IS
u
S
illez lire et
E
l’in
M
E
stal
N
au
T
lation et la
nue et l
bien com
es
m
pr
a
endre
int
enance.
CAUTION
Personal Injury Hazard. Power supply can cause electrical shock.
Disconnect power supply before beginning installation. Do not open base unit or lamp handle; there are no user-serviceable components inside.

Selecting Mounting Location

CAUTION
Equipment Damage Hazard. Ultraviolet light can cause color shift or structural degradation of plastic HVAC materials.
Select mounting location that prevents exposure to plastic components with unknown resistance to ultraviolet light. Three-feet minimum is recommended between ultraviolet lamp and plastic-fabricated devices (such as humidifiers and non-fiberglass media filters).
T
N
E
M
E
S
IS
T
R
E
V
/A
G
IN
N
et les
R
A
nue
re
W
d
!
eau
pren
our la p
enance.
et bien com
aint
Nocifs p
m
la
Veuillez lire
tallation et
l’ins
M22857
Fig. 1. Typical Air Treatment System installations.
3 68-0248—4
UV100A ULTRAVIOLET SYSTEMS

Surface Treatment System

When installed next to the cooling coil, the Ultraviolet Surface Treatment System prevents a high percentage of the growth of micro-organisms such as mold that may grow on duct surfaces, coils and drain pans. Individual results depend on careful installation and maintenance. See. Fig. 2.
ENT
s e l
et e
re
u
n
u
end
a
WARNING/AVERTISSEM
e
!
p
e.
a l r
u
o
enanc
int
s p
if
c
ma
o
ire et bien compr
N
la
z l
n et
Veuille
latio
stal
l’in
T
N
E
M
E
S
TIS
R
VE
/A
G
es
IN
N
R
A
nue et l
re
W
d
!
n
au
e
r p m
.
o
e
c
c
n
en
a
i
pour la pe
b t
ifs
ten
e
in
e
a
Noc
lir
m
z
t la
ille
u
e
e
n
V
io t
lla
sta
l’in
M22859
Fig. 2. Typical Surface Treatment installations.
IMPORTANT
If mounting options are limited, protect plastic or rubber materials listed in CAUTION with ultraviolet­resistant material such as aluminum foil duct tape.
NOTE: When the installer is uncertain about whether the drip
pan in the installation can tolerate UV exposure, consult the UV exposure white paper, form no. 50-8788, at hbctechlit.honeywell.com Web site.
1. The UV System can be mounted in any orientation.
2. Choose a location that is readily accessible for regular
inspection and cleaning.
3. Allow clearance in front of the device for removing the
bulb assemblies. See Fig. 3 for bulb assembly lengths.
4. Mount the UV System to non-lined metal ductwork. Do
not mount in a location that permits ultraviolet exposure to plastic flexible duct liner.
CAUTION
Sharp Edges Hazard. Can cause personal injury.
Be careful when inserting ultraviolet device into the sheet metal cutout. Wear protective gloves when working near sheet metal.
Duct Mounting
Use the following instructions to mount the UV System on the air duct of an HVAC system:
1. Disconnect power to the HVAC system before installing
the UV System.
2. Determine the location for installation (see Fig. 1 and 2):
a. The UV Air Treatment System requires an easily-
accessible, flat mounting surface on the metal return air duct of the HVAC system. The UV Surface Treatment System requires an easily-accessible, flat mounting surface on the metal supply air duct of the HVAC system. The UV Surface Treatment System must be located so the lamp surrounds the evaporator coil and drip pan with ultraviolet light.
b. The duct mounting location must be a minimum of
8 in. wide. See Fig. 3.
c. The depth of the duct must accommodate the full
length of the ultraviolet bulb for your model as shown in Fig. 3.
d. The unit should be located as far away as possible
from any rubber or plastic components, such as isolators, in the duct.
e. The space adjacent to the mounting location must be
large enough to allow for ultraviolet bulb installation and removal.
f. A 120V or 240V electrical outlet must be within range
of the unit to plug in the power cord.
68-0248—4 4